JR/JR20-IMP DESCRIPTION The JR-IMP and JR20-IMP models are counters that can display two variables; the number of pulses of the actual process, and a total of accumulated pulses during several measures, both multiplied by a programmable factor. Accepts, by a DIP-switch selection, the most commonly used pulse generators, with a programmable factor range from 0,001 to 9,999; and an offset (initial counting value) programmable from 0 to 9999. Reset by keyboard or remote. The counting is always ascending unidirectional. Totalizer up to 999999 (informative only) visualized in to parts. Accepts the 2RE output option (works with the counting value not the total), with various programmable work modes.
JUNIOR-IMP
STRUCTURE
JUNIOR20-IMP
STANDARD
• Panel-mounting 1/8 DIN case, depth 60mm. • Electronics assembly :
• Main board. • Keyboard and display module.
• Fixing clips for panel mounting. • Frontal sealing gasket. • Plug-in terminal block connectors.
OPTIONS • 2 SPDT relays rated 8A @ 250V AC ........ Ref. 2RE
CONECTIONS
CN1 POWER SUPPLY
PIN AC VERSION DC VERSION
1
AC HI
+V DC
2
GND (GROUND)
-
3
AC LO
-V DC
CN2 INPUT SIGNAL
PIN TRANSDUCERS
1 NEGATIVE INPUT
2 POSITIVE INPUT
3 + EXCITATION 24 V
4 + EXCITATION 8 V
DIMENSIONS AND MOUNTING
FIXING CLIPS SEALING
GASKET
PANEL PANEL CUTOUT 92x45mm
5 RESET
3.9 C
OU
NTER
/TOTA
LIZER
FRONT-PANEL COVER
2RE OPTION
CASE
MAIN BOARD
KEYBOARD AND DISPLAY MODULE
JR/JR20-IMP DISASSEMBLY
POWER SUPPLY (JUMPER SELECTION)
PANEL FUNCTIONS
MODE RUN PROG
Label 1 Measurement unit
Led 2 2 Indicates setpoint 2 is active
Indicates programming of the setpoint2
Key 3 Shows programming data. Gives access to PROG mode
Validates programmed data. Advances one program step. Exit program mode.
Key 4 - Shifts to the rigth
Key 5 - Gives access to the setpoint values. Increments the active d ig it value.
Led 1 6 Indicates setpoint 1 is active
Indicates programming of the setpoint1
Display 7 Disp lays the variab le being measured
Shows programming parameters
INPUT SIGNAL • Max. Frequency..............................................4 kHz • Excitation................8V @ 20mA or 22 V ±5 @ 20mA Magnetic pickup • Sensibility ............................ Vin (AC) > 120 mV eff. NAMUR sensor • Rc ............................................. 1KΩ (incorporated) • Ion ........................................................< 1 mA DC • Ioff........................................................> 3 mA DC 5 V TTL o 24 V DC (encoder) • Logic levels .............. "0" < 2.4 V DC, "1" > 2.6 V DC NPN y PNP • Rc ............................................ 1 KΩ (incorporated) • Logic levels ............... "0" <2.4 V DC, "1" > 2.6 V DC Contact closure • Vc ..................................................................... 5V • Rc .......................................... 3.9KΩ (incorporated) • Fc...................................................................20Hz
POWER SUPPLY • AC Voltages ..............115 V/230 V 50/60 Hz (±10%) 24 V/48 V 50/60 Hz (±10%) • DC Voltages ...............................12 V (10.5 to 16 V) 24 V (21 to 32 V) 48 V (42 to 64 V) • Consumption..................................................... 3W
FUSES (DIN 41661) (Recommended) • JR/JR20-IMP (115/230 V AC) .............F 0.1 A/ 250 V • JR/JR20-IMP2 (24/48 V AC) ...............F 0.2 A/ 250 V • JR/JR20-IMP3 (12 V DC) .......................F 1 A/ 250 V • JR/JR20-IMP4 (24 V DC) ....................F 0.5 A/ 250 V • JR/JR20-IMP5 (48 V DC) ....................F 0.5 A/ 250 V
DISPLAY • JR-IMP...................................... 4 red digits 14 mm • JR20-IMP................................... 4 red digits 20 mm • LEDs................................................2 output status • Overflow indication........................................... OvE
ENVIRONMENTAL / MECHANICAL • Operating temperature-10 ºC to +60 ºC (0ºC to 50ºC) s/UL • Storage temperature ....................... -25ºC to +85ºC • Relative humidity .................................<95% to 40ºC • Max. Altitude............................................... 2000 m • Dimensions ...........................1/8 DIN 96x48x60 mm • Weight...........................................................250 g • Case material ....................UL 94 V-0 poly carbonate • Sealed front panel .........................IP65 (indoor use)
ORDERING REFERENCES • 115/230 V AC 50/60 Hz powered...........JR/JR20-IMP • 24/48 V AC 50/60 Hz powered ............JR/JR20-IMP2 • 12 V DC powered ...............................JR/JR20-IMP3 • 24 V DC powered ...............................JR/JR20-IMP4 • 48 V DC powered ...............................JR/JR20-IMP5
Table 1. Jumper settings. Pin 1 2 3 4 5 230 V AC - 115 V AC - 48 V AC - 24 V AC -