62
- ISA-ds77.44.01-2006 Draft Standard Fossil Fuel Power Plant - Steam Temperature Controls Draft 5 December 2006 ISA grants permission to anyone to reproduce and distribute copies of this draft ISA standard, in whole or in part, but only for the following purposes and only as long as the recipient is not charged any fee for the copy (nor may the copy be included as part of a package with other materials or presentations for which a fee is charged): Review of and comment on the draft standard; Provide to others for review and comment; Promotion of the standard; or Informing and educating others about the standard. In addition, all copies must reproduce a copyright notice as follows:

ISA-774401

  • Upload
    jomolt

  • View
    8

  • Download
    1

Embed Size (px)

DESCRIPTION

Steam Temperature Control For Power Plants

Citation preview

IECSTD - Version 3.2

52 XXX ( CEI:1997

-

ISA-ds77.44.01-2006

Draft Standard

Fossil Fuel Power Plant -

Steam Temperature ControlsDraft 5

December 2006ISA grants permission to anyone to reproduce and distribute copies of this draft ISA standard, in whole or in part, but only for the following purposes and only as long as the recipient is not charged any fee for the copy (nor may the copy be included as part of a package with other materials or presentations for which a fee is charged):

Review of and comment on the draft standard;

Provide to others for review and comment;

Promotion of the standard; or

Informing and educating others about the standard.

In addition, all copies must reproduce a copyright notice as follows:

Copyright ( 2001 by ISAThe Instrumentation, Systems, and Automation Society. All rights reserved. Reproduced and distributed with permission of ISA.

ISA reserves all other rights to the draft standard. Any other reproduction or distribution without the prior written consent of ISA is prohibited.

Document NumberDocument Title

ISBN:

Copyright [INSERT DATE] by ISA The Instrumentation, Systems, and Automation Society. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means (electronic mechanical, photocopying, recording, or otherwise), without the prior written permission of the Publisher.

ISA67 Alexander DriveP.O. Box 12277Research Triangle Park, North Carolina 27709

Preface

This preface, as well as all footnotes and annexes, is included for information purposes and is not part of ANSI/ISA-77.44.01-2007.

This document has been prepared as part of the service of ISA(the Instrumentation, Systems, and Automation Society(toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (919) 549-8288; E-mail: [email protected].

The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommended practices, and technical reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing & Materials as IEEE/ASTM SI 10-97, and future revisions, will be the reference guide for definitions, symbols, abbreviations, and conversion factors.

It is the policy of ISA to encourage and welcome the participation of all concerned individuals and interests in the development of ISA standards, recommended practices, and technical reports. Participation in the ISA standards-making process by an individual in no way constitutes endorsement by the employer of that individual, of ISA, or of any of the standards, recommended practices, and technical reports that ISA develops.

CAUTION ISA adheres to the policy of the American National Standards Institute with regard to patents. If ISA is informed of an existing patent that is required for use of the DOCUMENT, it will require the owner of the patent to either grant a royalty-free license for use of the patent by users complying with the DOCUMENT or a license on reasonable terms and conditions that are free from unfair discrimination.

Even if ISA is unaware of any patent covering this DOCUMENT, the user is cautioned that implementation of the DOCUMENT may require use of techniques, processes, or materials covered by patent rights. ISA takes no position on the existence or validity of any patent rights that may be involved in implementing the DOCUMENT. ISA is not responsible for identifying all patents that may require a license before implementation of the DOCUMENT or for investigating the validity or scope of any patents brought to its attention. The user should carefully investigate relevant patents before using the DOCUMENT for the users intended application.

However, ISA asks that anyone reviewing this DOCUMENT who is aware of any patents that may impact implementation of the DOCUMENT notify the ISA Standards and Practices Department of the patent and its owner.

Additionally, the use of this DOCUMENT may involve hazardous materials, operations or equipment. The DOCUMENT cannot anticipate all possible applications or address all possible safety issues associated with use in hazardous conditions. The user of this DOCUMENT must exercise sound professional judgment concerning its use and applicability under the users particular circumstances. The user must also consider the applicability of any governmental regulatory limitations and established safety and health practices before implementing this DOCUMENT.

THE USER OF THIS DOCUMENT SHOULD BE AWARE THAT THIS DOCUMENT MAY BE IMPACTED BY ELECTRONIC SECURITY ISSUES. tHE COMMITTEE HAS NOT YET ADDRESSED THE POTENTIAL ISSUES IN THIS VERSION.

The following people served as members of ISA Subcommittee SP77.44:

NAMECOMPANY

D. Lee, ChairmanABB Automation Inc.

W. Holland, Managing DirectorSouthern Company

L. AltchehIsrael Electric Corporation

D. ChristopherReliant Energy

D. Crow*TXU

D. FitzgeraldFoster Wheeler Energy Corporation

J. GleggCentral & South West

R. HubbyConsultant

G. KumarFichtner Consulting Engineers

J. LeeKorea Electric Power Company

G. McFarlandWestinghouse Process Control Inc.

R. McSpaddenVision Controls Company

R. PapillaSouthern California Edison Company

L. RawlingsPalm Beach Resource Recover Company

D. RoneyRaytheon Engineers & Constructors

M. SkonceyDuquesne Light Company

C. TaftElectric Power Research Institute

J. VavrekSargent & Lundy Inc.

D. Wade*TXU Electric

The following served as members of the ISA SP77 Committee:

NAMECOMPANY

W. Holland, Managing DirectorSouthern Company

E. Adamson*Foxboro Company

L. AltchehIsrael Electric Corporation

S. AlvarezCompania Inspeccion Mexicana

J. BatugPennsylvania Power & Light Company

L. BroekerConsultant

Q. ChouConsultant

D. ChristopherReliant Energy

D. CrowTXU

F. CunninghamSwagelok Company

G. DavisDuke Power Company

D. ForemanBrown & Root Energy Services

W. FrymanIllinois Power Company

K. GabelCenterior Energy

A. GilePotomac Electric Power Company

R. Hicks*Black & Veatch

R. HubbyConsultant

R. JohnsonSargent & Lundy Engineers

J. KennardOntario Hydro

J. Kling*Black & Veatch

G. KumarFichtner Consulting Engineers

D. LeeABB Automation Inc.

W. Matz*Foxboro Company

G. McFarlandWestinghouse Process Control Inc.

R. McSpaddenVision Controls Company

G. MookerjeeU.S. Department of Energy

N. Obleton*Honeywell Inc.

R. PapillaSouthern California Edison Company

G. RamachandranCytec Industries Inc.

L. RawlingsPalm Beach Resource Recover Company

D. RoneyRaytheon Engineers & Constructors

R. RoopHoosier Energy Inc.

A. SchagerVitec Inc.

T. StevensonBaltimore Gas & Electric Company

C. Taft*Electric Power Research Institute

D. TennantInternational Applied Engineering

B. TraylorGE Instrument Control Service

J. Weiss*Electric Power Research Institute

D. Younie*Woodward Global Services

F. ZikasParker Hannifin Corporation

T. Zuvlis*Woodward Global Services

This standard was approved for publication by the ISA Standards and Practices Board on _________________________.

NAMECOMPANY

M. ZielinskiFisher-Rosemount Systems, Inc.

D. BishopConsultant

P. BrettHoneywell, Inc.

M. CohenSenior Flexonics, Inc.

M. CopplerAmetek, Inc.

B. DumortierSchneider Electric SA

W. HollandSouthern Company

A. IversonIvy Optiks

R. JonesDow Chemical Company

V. MaggioliFeltronics Corporation

T. McAvinewInstrumentation & Control Engineering LLC

A. McCauley, Jr.Chagrin Valley Controls, Inc.

G. McFarlandHoneywell, Inc.

R. ReimerRockwell Automation

J. RennieFactory Mutual Research Corporation

H. SasajimaAdvanced Architecture and Technologies

R. WebbAltran Corporation

W. WeidmanParsons Energy & Chemicals Group

J. WeissEPRI

J. WhetstoneNational Institute of Standards & Technology

M. WidmeyerEG&G

R. WiegleCANUS Corporation

C. WilliamsEastman Kodak Company

G. WoodGraeme Wood Consulting

This page intentionally left blank.

Table of Contents

101Purpose

102Scope

103Definitions

124Process measurement requirements

124.1Instrument installations for superheat and reheat steam temperature control

134.2Design of thermocouples and temperature sensors

134.3Isolation valves and impulse lines

134.4Process measurements for superheat and reheat steam temperature control

145Attemperation Methods Control and logic requirements for an attemperator control system for control of steam temperatures

155.1Single-stage attemperation

165.2Two-stage attemperation

175.3Multiple-stage attemperation

175.4Attemperator spray and block valve logic

186Control and logic requirements for a reheat steam temperature control by means of heat distribution

186.1Fuel nozzle tilts

196.2Flue gas pass dampers

196.3Flue gas recirculation

206.4Compartmented windbox

206.5Single-stage spray water attemperation

207Superheat control and logic requirements for once through type boilers

217.1Firing rate-feedwater flow ratio control

227.2Attemperator control

228Common design requirements

228.1Automatic tracking

228.2Integral windup prevention

228.3Final control element requirements

228.4System reliability and availability

238.5Minimum alarm requirements

238.6Operator interface

25A.1References

27B.1Purpose

27B.2Introduction

28B.3Requirements

30B.4Principles and methods of steam temperature control

31B.5Saturation protection/water induction

32B.6Two-stage attemperation

32B.7Use of cascade spray valve control

32B.8NOx control

33B.9Redundancy

33B.10Reset windup prevention

34B.11Advanced steam temperature control

This page intentionally left blank.

Forward

A variety of steam temperature control systems have been developed over the years to fit the needs of particular applications. Operating philosophy, plant layout, and type of firing must be considered before the ultimate selection of a system is made. Therefore, this standard is not intended to limit the complexity or scope of the steam temperature control system design that one might wish to implement, but rather to establish a minimum of control needed.

This standard is part of a series resulting from the efforts of the SP77 Committee on Fossil Power Plant Standards, especially subcommittee SP77.40 on Boiler Controls. It should be used in conjunction with the other SP77 series of standards for safe, reliable, and efficient design, construction, operation, and maintenance of the power plant. It is not the intent of this standard to establish any procedures or practices that are contrary to any other standard in this series.1 Purpose

The purpose of this standard is to establish the minimum requirements for the functional design specification of steam temperature control systems for drum type and once-through type fossil fuel power plant boilers.

2 Scope

The scope of this standard addresses the major steam temperature control subsystems in boilers with steaming capacities of 200,000lb/hr (25kg/s) or greater. These subsystems include, but are not limited to, superheat temperature control and reheat temperature control. Specifically excluded from consideration are controls associated with fluidized-bed, stoker-fired furnace combustion units and mud drum desuperheaters.

3 Definitions

The following definitions are provided to clarify their use in this standard and may not be relevant to the use of the words in other texts. For other definitions, please refer to ANSI/ISAS51.11979 (R1993) Process Instrumentation Terminology.

3.1attemperator:

a device used for maintaining and controlling the temperature of superheated steam.

3.2attemperator (direct contact type):

a device in which the steam and the cooling medium (water) are mixed.

3.3boiler:

the entire vessel in which steam or other vapor is generated for use external to the vessel. This includes the furnace, consisting of waterwall tubes; the firebox area, including burners and dampers; the convection area, consisting of any superheater, reheater, economizer sections or any combination thereof, as well as drums and headers.

3.4cascade control system:

a control system in which the output of one controller (the outer loop) is the setpoint for another controller (the inner loop). The outer loop is normally a slow responding process than the inner loop.

3.5control loop:

a combination of field devices and control functions arranged so that a control variable is compared to a setpoint and its output returns to the process in the form of a manipulated variable.

3.6controller:

any manual or automatic device or system of devices used to regulate a process within defined parameters. If automatic, the device or system responds to variations in a process variable.

3.7desuperheater (direct contact type):

a device in which the steam and the cooling medium (water) are mixed.3.8deviation:

the difference between the loop setpoint and the process variable (also called error).

3.9error:

see 3.9 deviation.

3.10feedback:

a concept in which a process measurement in used to determine whether the control variable is at the desired value. A signal produced by a measuring device that is proportional to the magnitude of a controlled variable or position of a control element.

3.11final control element:

component of a control system (such as a control valve) that directly regulates the flow of energy or material to or from the process.

3.12gas pass:

an arrangement in which the convection banks of a boiler are separated by gas-tight baffles into two or more parallel gas paths isolating portions of the superheater and reheater surfaces. The proportion of total gas flow through each gas pass may be varied by regulating dampers.

3.13gas recirculation:

a method by which flue gas from the boiler, economizer, or air heater outlet is reintroduced to the lower furnace to reduce furnace heat absorption while increasing convection pass heat absorption or to reduce NOx emission.

3.14integral control action:

an action in which the controller's output is proportional to the time integral of the error input. It is also called reset action.

3.15integral windup:

the saturation of the integral controller output in the presence of a continuous error, which may cause unacceptable response in returning the process to its setpoint within acceptable limits of time and overshoot.

3.16interlock:

a device or group of devices (hardware or software) arranged to sense a limit or off-limit condition, or improper sequence of events, and to shut down the offending or related piece of equipment, or to prevent proceeding in an improper sequence in order to avoid an undesirable condition.

3.17linearity:

the nearness with which the plot of a signal or other variable plotted against a prescribed linear scale approximates a straight line.

3.18master fuel trip:

An event resulting in the rapid shutoff of all fuel including igniters.

3.19primary air:

combustion air that enters the fuel-burning zone and directly supports initial combustion. On pulverized coal-fired units, the primary air is used to transport the coal from the pulverizers to the burners.

3.20reheater:

a heating surface receiving steam returning to the boiler from the high-pressure turbine exhaust.

3.21secondary air:

combustion air introduced on the edge of the burning zone to supplement the primary air for support of the combustion process.

3.22setpoint:

the desired operating value of the process variable.

3.23superheater:

boiler heating surface that is not part of the boiler enclosure which receives only steam already at or above its saturation temperature. (See Figure 3.26.a and Figure 3.26.b for typical steam and gas flow paths.)3.23.1 Intermediate Superheater - Section or sections of superheating surface located between primary and secondary superheaters.

3.23.2 Platen Superheater - Intermediate superheater surface which is also a radiant superheater.

3.23.3 Primary Superheater - First boiler heating surface to receive steam at or slightly above saturation temperature.

3.23.4 Secondary Superheater - Final stage of boiler superheating surface.

3.23.5 Radiant Superheater - Steam superheating surface where the primary means of heat transfer to the steam is by radiation rather than convection. Typically, an intermediate superheater section.

Figure 3.23.a - Typical Superheater Steam Flow Path

Figure 3.26.b - Typical Superheater Gas Flow Path3.24trip:

the automatic removal from operation of specific equipment or the automatic discontinuance of a process action or condition as the result of an interlock or operator action.

3.25transient correction:

a control action specifically applied to minimize any process error resulting from a temporary process change; e.g., temperature control action applied to counter the effects of over- or under-firing during load changes.

4 Process measurement requirements

4.1 Instrument installations for superheat and reheat steam temperature control

Instruments should be installed as close as is practical to the source of the measurement, with consideration being given to excessive vibration, ambient temperature, and accessibility for periodic maintenance. Temperature measurement should be located at least 20 pipe diameters downstream of any attemperator.

4.2 Design of thermocouples and temperature sensors

Design of thermocouples and temperature sensors shall meet the requirements of ASME Power Test Code PTC19.3 Temperature Measurements.

Design of the attachment of the thermowell to the pipe shall meet the requirements of either ASME Boiler Pressure Vessel Code Section I Power Boilers for Boilers or ASME B31.1 Power Piping Code depending on the code jurisdiction for the pipe.

Thermowell installations shall consider location, mounting, and velocity criteria in making a proper interface with the process.

4.3 Isolation valves and impulse lines

Separate isolation valves and impulse lines shall be provided for head-type instrumentation.

4.4 Process measurements for superheat and reheat steam temperature controlProcess measurements for superheat temperature control are listed below. For location of these measurements see figures C.1a, C.1b, C.1c, and C.1d.

4.4.1 Secondary (final) superheater outlet steam temperature measurementA temperature measurement, taken at the outlet of the secondary (final) superheater, is required for superheat steam temperature control strategies.

4.4.2 Secondary superheater inlet temperature measurementA temperature measurement, taken at the attemperator outlet(s) for single-stage or multiple-stage attemperation and followed by a superheater section, is required as the secondary variable in a cascade loop with feedforward control strategy.

4.4.3 Primary (initial, platen) inlet temperature measurement

A temperature measurement, taken at the primary superheater inlet (or outlet of the first stage attemperator of multiple-stage attemperation), is required as the secondary variable in a cascade loop with feedforward control strategy.

4.4.4 Primary (initial, platen) outlet temperature measurement

A temperature measurement, taken at the outlet of the primary superheater section before the first stage attemperator, is required in a single or multiple-stage attemperator control strategy.

4.4.5 Primary (initial, platen, intermediate) inlet pressure measurementA pressure measurement is required in a multiple-stage attemperator control strategy to prevent saturation following first-stage spray attemperation. Typically, this pressure is measured at the inlet of the primary superheater. A pressure measurement is required in a two-stage attemperator control strategy to prevent saturation following first-stage spray attemperation. Typically, this pressure is measured at the inlet of the intermediate superheater; however, drum pressure may be used if primary superheaters pressure loss is considered.4.4.6 Intermediate inlet temperature measurementA temperature measurement, taken at the intermediate superheater inlet (or outlet of the first stage attemperator of two-stage attemperation), is required as the secondary variable in a three- element control strategy.

4.4.7 Intermediate outlet temperature measurement

A temperature measurement, taken at the outlet of the intermediate superheater section before the second stage attemperator, is required in a two-stage attemperator control strategy.

4.4.8 Reheat steam temperature measurement

A temperature measurement, taken at the outlet of the final reheater, is required for single loop and single loop with feedforward reheat steam temperature control strategies for modulation of the reheat steam temperature control mechanisms provided by the boiler manufacturer.

4.4.9 Attemperator spray water-flow measurement

An attemperator spray water mass flow signal provides an alternative to the use of the attemperator outlet steam temperature as the secondary variable in a cascade loop with feedforward control strategy.

4.4.10 Waterwall (convection pass) outlet temperature measurement

A temperature measurement, taken at the outlet of the furnace walls (convection pass) section and followed by a superheater section, is required in a multiple-stage attemperator control strategy.

5 Attemperation Methods Control and logic requirements for an attemperator control system for control of steam temperatures

The function of the superheat temperature control system is to maintain superheat steam temperature within the boiler manufacturer's specified limits. Generally, the goal is to obtain a specified final superheat steam temperature over the specified boiler-load range. Control strategy must be based on the particular control mechanisms used and the boiler manufacturer's philosophy for controlling steam temperature. Although the strategies in this standard use conventional PID control techniques, it is not the intention to preclude the use of advanced control strategies. Refer to Table B.1 for summary of typical control systems.For the control of superheat steam temperature, this standard addresses single-stage attemperation and two-stage attemperation. For typical boiler superheater attemperation arrangements, see FiguresC.1a and C.1b.

Single loop steam temperature control is the minimum control strategy for reheat steam temperature leaving the boiler and shall be used only for applications where reheat spray is the secondary means of reheat temperature control.

Referring to FigureC.9, reheat steam temperature is measured and compared to a setpoint. The setpoint bias in Figures C.5C.8, which is used to slightly increase the setpoint above the setpoint of the primary controlling mechanism, is summed with the reheat temperature error to develop the final error signal. Proportional and integral control action, along with a automatic/manual station function, completes the control scheme to regulate the valve.

Single loop with feedforward and cascade loop with feedforward steam temperature control strategy should be used in applications where reheat spray is the primary method of reheat temperature control; with variable steam pressures; and with variable spray water pressure supplies.

5.1 Single-stage attemperation

Single-stage attemperation refers to the boiler design that provides a single location for the introduction of spray water for the regulation of steam temperature. This application is typical of boilers with a single reheater section or a single superheat section with the attemperation at the inlet. If a boiler has two superheater sections in series, (i.e., the primary and secondary superheaters) then it is normal to have the spray attemperation located between the two superheater sections. Note that a single attemperation location does not necessarily refer to a single set of spray equipment because there may be more than one parallel path for the steam leaving the drum.5.1.1 Single loop steam temperature controlSingle loop steam temperature control is the minimum control strategy required to regulate the steam temperature leaving the boiler and should be used only in applications with slow load changes (e.g., approximately 0.2%/min as in building heating system or where constant steam temperature is not critical).

Referring to FigureC.2, final steam temperature is measured and compared to a setpoint with the result used to regulate the spray valve(s).

5.1.2 Single loop with feedforward steam temperature control

Single loop with feedforward steam temperature control strategy shall be used only in applications with slow to moderate load changes (e.g., < 1.0 %/min) and with steady spray water pressure supply and fixed steam pressure applications.

Referring to FigureC.3, Single loop with feedforward steam temperature control adds a feedforward signal and a transient correction signal to the single loop control described in 5.1.1. As a minimum, the feedforward signal is derived from a load index (or indices). This feedforward signal should recognize all major influences on steam temperature, including adjustments to heat distribution within the boiler.

5.1.3 Cascade loop with feedforward steam temperature control

Cascade loop with feedforward steam temperature control strategy shall be used in applications with rapidly changing loads (e.g., > 1 %/min), with variable steam pressures or with variable spray water pressure supplies.

The cascade loop with feedforward control strategy is applicable only when attemperation takes place between two superheater sections.

Referring to Figure C.4a and Figure 4b, cascade loop with feedforward steam temperature control adds a cascade control arrangement to the single loop with feedforward control strategy described in 5.1.2 for the control of the spray valve. The single loop with feedforward control strategy acts as the setpoint development for the inner control loop of the cascade control arrangement. The process variable for the inner control loop is a monitor of the spray action. Although steam temperature immediately after the attemperation is the preferred process variable, spray water flow also may be used. As a minimum, the feedforward signal is derived from a load index (or indices). This feedforward signal should recognize all major influences on steam temperature, including adjustments to heat distribution within the boiler.

For variable pressure operation, a suitable feedforward shall be provided to reflect the influence of changes in the thermodynamic properties of steam on the final steam temperature.

5.2 Two-stage attemperationTwo-stage attemperation refers to the boiler design when spray attemperation is applied at two different locations along the same steam path, typically between the primary and intermediate superheaters and also between the intermediate and secondary superheaters. There are two common approaches to controlling a two-stage attemperation systemindependent systems or coupled systems. Consideration should be given to the boiler manufacturer's recommendations when selecting a control strategy.

5.2.1 Independent two-stage controlIn the independent system, the first-stage attemperator is used to control the outlet temperature of the intermediate superheater. The second-stage attemperator is used to control the final outlet temperature. Referring to Figure C.2, the setpoint for the first-stage control loop usually is a fixed value dependent on the metal temperature limits of the intermediate superheater. A single loop control is the minimum system required for the first stage. Referring to Figure C.4, the setpoint for the second-stage control loop is operator set. A cascade control scheme using final outlet temperature as the primary process variable and either the second-stage attemperator outlet temperature or spray water flow as the secondary process variable is the minimum system required for controlling the final outlet temperature.

Feed-forward signals usually are required to obtain satisfactory transient control performance from a steam temperature control loop. In the independent strategy, the feed-forward signals are used only on the final outlet temperature control loop, where they are added to the outlet of the primary controller. The exact arrangement of the feedforward signals must be determined on a case-by-case basis. As a minimum, the feedforward signal is derived from a load index (or indices). This feedforward signal should recognize all major influences on steam temperature, including adjustments to heat distribution within the boiler. Some common feedforward signals include load index, heat distribution signals (fuel nozzle tilt positions), fuel flow, and air flow.

5.2.2 Coupled two-stage control

In the coupled two-stage control strategy, the total spray attemperator demand is distributed between both stages of attemperation. Referring to Figure C.5, cascade loop with feedforward XE "three-element control" control is the minimum system required for the coupled two-stage attemperation to maintain the superheat steam temperature setpoint. The load index (or indices) feedforward signal is summed with a transient signal(s) and a final steam temperature feedback controller signal to develop a total spray attemperator demand. This feedforward signal should recognize all major influences on steam temperature, including adjustments to heat distribution within the boiler.

The individual spray attemperator demand is distributed between both stages of attemperation. The individual spray demands are developed from the spray distribution and coordination control strategy as determined from the boiler manufacturer's recommendations and specifications or as process constraints dictate. Both valves shall participate during transient boiler operation to minimize temperature excursions.

The intermediate (platen) spray demand shall protect the intermediate (platen) superheater from going into saturation at the inlet and from high temperature at the outlet. The control system must coordinate the intermediate (platen) spray demand and the secondary spray demand to minimize correction from the final steam temperature controller.

5.3 Multiple-stage attemperation

Multiple-stage attemperation refers to the boiler design when spray attemperation is applied at two or more different locations, typically between the furnace and primary superheaters and also between the primary and secondary superheaters. This sub clause also applies to parallel multiple-stage attemperation.

5.3.1 Multiple-stage control

The first-stage attemperator is used to control the outlet temperature of the primary superheater. The second-stage attemperator is used to control the final outlet temperature. Referring to Figure C.5, the setpoint for the second-stage control loop is operator set. A cascade control scheme using final outlet temperature as the primary process variable and either the second-stage attemperator outlet temperature or spray water flow, as the secondary process variable is the minimum system required for controlling the final outlet temperature.

Feed-forward signals usually are required to obtain satisfactory transient control performance from a steam temperature control loop. The feed-forward signals are used only on the final outlet temperature control loop, where they are added to the outlet of the primary controller. The exact arrangement of the feedforward signals must be determined on a case-by-case basis. As a minimum, the feedforward signal is derived from a load index(es). This feedforward signal should recognize all major influences on steam temperature, including adjustments to heat distribution within the boiler. Some common feedforward signals include load index, heat distribution signals (fuel nozzle tilt positions), fuel flow, and airflow.

The individual spray attemperator demand is distributed between both stages of attemperation. The individual spray demands are developed from the spray distribution and coordination controls strategy as determined from the boiler manufacturer's recommendations and specifications or as process constraints dictate. Both valves shall participate during transient boiler operation to minimize temperature excursions.

The first spray demand shall protect the primary superheater from going into saturation at the inlet and from high temperature at the outlet. The control system must coordinate the first spray demand and the second spray demand to minimize correction from the final steam temperature controller.

5.4 Attemperator spray and block valve logic

A spray water block valve(s) shall be furnished to provide tight shutoff to prevent water leakage past the spray control valve and to provide backup in the event that the spray control valve fails to close when required. Each spray valve shall have its own dedicated block valve, or several valves may share a common block valve.

Control logic shall be provided for block valve operation to preserve its tight shutoff ability. The following permissive shall be satisfied before spray and block valves are opened:

Reset the turbine trip logic

Load greater than the preset amount

Spray demand greater than the preset amount (e.g., 2 to 3 % to minimize valve wear)

The attemperator spray water block valve logic shall open the block valve to its full open position prior to the initial opening of its associated modulating attemperator spray control valve(s). The block valve logic shall close the block valve after its associated modulating attemperator spray control valve(s) is fully closed. The block valve logic shall be designed to minimize repeated opening and closing of the block valve when operating near minimum spray conditions. Provisions shall be made to override the sequence logic and close both the block and spray valves in the event of a turbine trip (or master fuel trip when the master fuel trip does not initiate a turbine trip) to minimize the possibility of water carryover as the unit is shut down.

The block valve logic design shall be fully compliant with ANSI/ASME TDP-1, "Recommended Practices for the Prevention of Water Damage to Steam Turbines Used in Electric Power Generation".

5.5 Saturation ProtectionTo prevent the steam temperature control system from spraying into saturation, logic shall be provided which calculates the saturation temperature as a function of the steam pressure in the superheater. When the desuperheater outlet temperature approaches the saturation temperature, usually within 5.5-11.1OC (10-20 OF), an interlock shall be activated which prevents the spray valve from injecting any additional water. The upstream controller shall take appropriate action to prevent windup while the saturation interlock is active in the inner controller. For two-stage attemperator arrangements, each loop should have independent saturation protection6 Control and logic requirements for a reheat steam temperature control by means of heat distribution

The function of the reheat steam temperature control system is to maintain reheat steam temperature, leaving the boiler within manufacturer's specified limits. The strategy must be based on the particular mechanism(s) used and the boiler manufacturer's philosophies for controlling reheat steam temperature. The control mechanism(s) that are operated by the reheat steam temperature control equipment may involve the fire-side or the water-side of the boiler, or a combination of both. Although the strategies describe the use of conventional PID control techniques, it is not the intention to preclude the use of advanced control strategies.

This standard addresses the following means or mechanisms employed for the control of reheat steam temperature:

a) Fuel nozzle tilts

b) Flue gas pass dampers

c) Flue gas recirculation

d) Single-stage spray water attemperation

6.1 Fuel nozzle tilts

Fuel nozzle tilts are a means of altering the distribution of heat in a furnace to effect changes in reheater and superheater outlet steam temperatures. Generally, the fuel nozzle tilts are mounted in the furnace corners and can be tilted up or down from horizontal. Lowering the fuel nozzle tilts increases furnace heat absorption, which in turn lowers the flue gas temperature as it enters the reheater and the superheater. Raising the fuel nozzle tilts has the opposite effect. Fuel nozzle tilts usually are operated in parallel, although biasing of individual corners may be included and incorporated in the control strategy employed.

Referring to Figure C.6, single loop with feedforward control (reheat temperature control with feedforward) is the minimum system requirement for the fuel nozzle tilt arrangement to maintain the reheat steam temperature setpoint. The load index feedforward signal is summed with transient correction signals and a reheat temperature controller output to develop a fuel nozzle tilt demand.

Fuel nozzle tilts may also be used to control superheater steam temperature in accordance with the boiler manufacturer's recommendation.

Single-stage spray water attemperation is provided to supplement the normal controls of reheat steam temperature (see 6.4 and 5.1).

6.2 Flue gas pass dampers

Flue gas pass dampers are a means to distribute the flue gas between the superheater and the reheater to control reheat temperature. The pass damper demand shall be indexed to position the two pass dampers in opposite directions. During start-up and at low loads, the reheat pass damper will normally be wide open, and the superheat pass damper will be at a minimum position, and will approach full open while the reheat pass damper closes to its minimum position as load is increased. The relationship of the damper positions is such that the combined flow restriction of both devices remains relatively constant.

Referring to figure C.7, single loop with feedforward control (reheat temperature control with feedforward) is the minimum system requirement for the flue gas pass damper arrangement to maintain the reheat steam temperature setpoint. The load index feedforward signal is summed with transient correction signals and a reheat temperature controller output to develop a flue gas pass damper demand.

Single-stage spray water attemperation is provided to supplement the normal controls of reheat steam temperature (see 6.4 and 5.1).

6.3 Flue gas recirculation

Flue gas recirculation is a means of altering the distribution of heat within a furnace to affect changes in reheater outlet steam temperature. Typically, at low loads, gas recirculation is high to assist in achieving reheat temperature. At high loads, gas recirculation is reduced to its minimum value. Generally, the recirculation of flue gas is introduced into the furnace hoppers for temperature control. For some boiler designs, flue gas recirculation is introduced in the furnace airfoil and a combination of airfoil and hoppers for control of temperature and NO( (see B7).

Referring to figure C.8, single loop with feedforward control (reheat temperature control with feedforward) is the minimum system requirement for the gas recirculation to maintain reheat temperature at the setpoint. The load index feedforward signal is summed with transient correction signals and a reheat temperature controller output to develop a flue gas damper demand. Gas recirculation control damper demand shall be constrained by a current limiting program to keep fan current within acceptable limits. Safety interlocks, such as furnace purge, needs to be considered but, are not addressed by this standard.

An alternate arrangement for the application of gas recirculation is as a supplement to the normal temperature control. When used in conjunction with fuel nozzle tilt control (see 6.1), gas recirculation may be applied to maintain the fuel nozzles in their horizontal position. When used in conjunction with flue gas pass damper control (see 6.2), the gas recirculation is used to maintain the pass dampers in a regulating range at low loads.

Single-stage water attemperation is provided to supplement the normal controls of reheat steam temperature (see 6.4 and 5.1).

6.4 Single-stage spray water attemperation

The use of spray water attemperators is a method of controlling reheater outlet steam temperature. Water is sprayed into the superheated steam to lower its temperature. Temperature control is achieved by varying the water flow.

Since water injection into the reheater will lower the overall unit thermal efficiency, spray-water attemperation normally is employed as a secondary means of reheat steam temperature control in combination with other control mechanisms.

Single-stage spray water attemperation is often combined with one of the other aforementioned means of controlling reheat steam temperature. When combined with fuel nozzle tilts, flue gas pass dampers, flue gas recirculation, and excess air, single-stage spray water attemperation reduces cycle efficiency and is effective only in reducing temperature. In such cases, other means shall be employed in the control strategy to limit the use of spray-water attemperation and to maximize the use of these other means of final reheater outer steam temperature control. One method of accomplishing this control strategy is to introduce a positive offset (e.g., +10o F), into the temperature setpoint for the reheat spray control. The boiler manufacturer's recommendations should be followed in the implementation of combined control strategies.

7 Superheat control and logic requirements for once through type boilers

For once-through type fossil fuel power plant boilers, the transition between water and steam occurs without boiling. Water becomes steam as it flows through the waterwall tubing. With continuous heating, fluid temperatures increase throughout the process. For subcritical boiler, the phase change point between water and steam can move further down the piping within the waterwalls as load (intermediate steam pressure) increases. For supercritical boilers (critical point pressure [3206.2 psia]) there is no change in phase between water and steam.

The ratio of firing rate to feedwater flow determines the final value for the superheat steam leaving the boiler. To improve the transient temperature response, boiler design may include single or multiple stages of spray attemperation.

Since all feedwater entering the waterwalls becomes steam (once-through), the throttle pressure is directly related to feedwater flow. Low pressure requires an increase in feedwater flow; high pressure requires a reduction in feedwater flow. Since all the feedwater entering the boiler must be heated into superheated steam, the firing rate controls (fuel and air) are modulated to provide the required heating. The ratio of feedwater to firing rate determines the final value for the main superheat steam leaving the boiler.

Since superheater spray flow is extracted from feedwater flow, a change of superheat spray flow will not result in a permanent change in final steam temperature leaving the boiler since it does not change the ratio of firing rate to feedwater flow. Eventually, final steam temperature will return to its previous value, as the intermediate steam temperature will rise due to less feedwater flow.

This standard addresses the following means or mechanisms for the control of final steam temperature:

a) Firing rate-feedwater ratio control

b) Attemperation control

7.1 Firing rate-feedwater flow ratio control All once-through boilers include a firing ratefeedwater ratio control strategy as a means to control steam temperatures. For boilers without spray attemperation, the firing ratefeedwater flow ratio regulates the final superheater outlet temperature. For boilers with single or multiple spray attemperation, the firing rate-feedwater flow ratio regulates the specified superheater outlet temperature or attemperator differential temperature in accordance with the boiler manufacturers recommendation.

Referring to figure C.10, single loop with feedforward firing rate-feedwater flow control is the minimum control strategy to regulate the steam temperature. Final steam temperature is measured and compared to a setpoint with the results used to regulate the firing ratefeedwater flow ratio. As a minimum, the temperature setpoint is derived from a load index and modified by an operator bias. In accordance with the boiler manufacturers recommendation, the feedback controller is constrained by a waterwall outlet or primary superheater outlet temperature controller to protect against high temperature in the water walls or primary superheater outlet tubes respectively.

A feedforward signal(s) and transient correction signal(s) is added to the final steam temperature controller. As a minimum, the feedforward signal is derived from a load index(es). This feedforward signal should recognize all major influences on steam temperature, including adjustments to heat distribution within the boiler. As a minimum transient correction, waterwall outlet temperature should be an anticipating signal. This signal compensates for upsets due to sudden changes in slag formation, feedwater temperature, mill starts, etc.

For once-through boilers with single or multiple-stage attemperators, the firing rate-feedwater flow ratio control strategy shall return final steam temperature to setpoint and spray attemperation to its nominal value. As a minimum, the average temperature difference across the attemperator is compared to a setpoint. Any deviation from a differential temperature setpoint is included in the control strategy to return the spray attemperator to its nominal value.

The firing rate-feedwater flow ratio control loop provides a signal both to the feedwater control sub-loop and to the fuel control sub-loop. To raise steam temperature, the firing rate-feedwater flow ratio must either increase firing rate or decrease feedwater flow or both (see B2.2 Steam temperature control by ratio adjustment). To lower steam temperature, the firing rate-feedwater flow ratio must either decrease firing rate or increase feedwater flow or both.

The firing rate-feedwater flow ratio control shall be interlocked to manual until the subloops being modified (i.e., feedwater flow and/or firing rate) are in automatic mode.

7.2 Attemperator control

For once-through boilers, spray attemperator(s) are not used for steady state correction but serve to stabilize steam temperature during transient disturbance. To allow the transient temperature control to operate in both directions (increase/decrease of main steam temperature), the superheat spray valves should be maintained at a normal regulating range. See Clause 5.1 for single stage attemperation control and logic requirements and Clause 5.2 for two-stage attemperation control and logic requirements.8 Common design requirementsThe control system shall meet all operational requirements and properly interface with the process. To accomplish these objectives, the following minimum system design requirements are defined.8.1 Automatic trackingAutomatic tracking shall be provided such that any control mode transfer is accomplished without a sudden process upset.

8.2 Integral windup preventionMeans shall be provided with the superheater outlet steam temperature control strategy to prevent integral windup of steam temperature controller(s) when the boiler load is below that of the superheat steam temperature control range or when the final control element is at a limit (full open or full closed).

8.3 Final control element requirements

All final temperature control elements shall be designed to fail safe on loss of demand signal or control power (i.e., close, or lock in place). The fail-safe position shall be determined by the user, based on the specific application and the recommendations from the boiler/turbine supplier. The final control element should have the capability to be characterized to linearize the process.

8.4 System reliability and availability

As minimum criteria, the design basis of the steam temperature's control system shall include the capability for

a)Maximum unit load/temperature control;

b)Normal operating load range;

c)Anticipated load changes (transients); and

d)Unit design characteristics, including spray water pressure and capacity for attemperation.

8.5 Minimum alarm requirements

As a minimum, alarm requirements shall include the following information:

a)High final superheater outlet steam temperature

b)Low final superheater outlet steam temperature

c)High differential header temperature between parallel paths of the final superheater (if applicable)

d)Low primary superheater inlet steam temperature (multiple-stage attemperation and saturation protection)

e)High primary superheater outlet steam temperature (multiple-stage attemperation and tube metal protection)

f)High final reheater outlet steam temperature

g)Loss of control power

h)Loss of final drive power

i)Control loop trip-to-manual

In addition to the above, the following alarms should be made available to the operator. a) Block valve failed to open

b)Block valve failed to close

8.6 Operator interface

8.6.1 Operation information

The following information used in the steam temperature control system shall be made available to the operator:

a)Final superheater outlet steam temperature (per outlet)

b)Final superheater outlet steam temperature setpoint

c)Primary superheater inlet temperature(s) (multiple-stage attemperation)

d)Primary superheater outlet temperature (multiple-stage attemperation)

e) Secondary superheater inlet steam temperature(s) or attemperator spray flow measurement

f) Inner loop process variable for cascade loop with feedforward steam temperature control (temperature or flow)

g) Intermediate superheater outlet temperature (two-stage attemperation)

h)Final reheater outlet steam temperature (per outlet)

i)Final reheater outlet steam temperature setpoint

j)All alarms (see 8.5)k)Automatic/manual control loop status

In addition to the above, the following information should be made available to the operator:

a)Final control element(s) positionb)Attemperator spray flow measurement (if not used for control)

8.6.2 Operator control functions

The control system shall include capabilities for the automatic/manual mode transfer and manual control of firing rate feedwater flow ratio for once through boiler and each individual final control element except the fuel nozzle tilt final control element which may be operated in parallel. The operator shall not have manual control of the block valves.

The control system shall include capabilities for the operator to adjust the final superheater outlet steam temperature setpoint and the final reheater outlet steam temperature setpoint. Consideration should be given to setpoint limits, which should not be accessible to the operator.

Annex A ReferenceAMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

ASME B31.1

Power Piping for Boilers

PTC19.3

Power Test Code Temperature Measurement

BPVC Section 1-2004

Boiler and Pressure Vessel Code, Power Boiler

ANSI/ASME TDP-1-1998Recommended Practices for the Prevention of Water Damage to Steam Turbines Used for Electric Power Generation

Available from:ASME

Tel: (212) 591-8500

Three Park Avenue

New York, NY 10016-5990

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE/ASTM SI 10-97 Standard of Use of International System of Units (SI): The Modern Metric System

Available from:IEEE

Tel. (800) 678-4333

345 East 47th Street

New York, NY 10017

ASTM

Tel. (610)-832-9585

100 Barr Harbor Dr.

Fax: (610)-832-9555

West Conshohocken, PA 19428-2959

Instrumentation, Systems and Automation (ISA)

ANSI/ISA-S5.1-1984

Instrumentation Symbols and Identification (R1992)

ANSI/ISA-S5.4-1976

Instrument Loop Diagrams (R-1981)

ANSI/ISA-S51.1-1979

Process Instrumentation Terminology

Control of Boilers, 2nd ed.Dukelow, S.G.; ISA Press-1986 (ISBN: 1-55617-330-x)

Available from:ISA

Tel. (919) 549-8411

67 Alexander Drive

P.O. Box 12277

Research Triangle Park, NC 27709

International ElectroTechnical Commission (IEC)

IEC TR62140-3:2002

Fossil-fired power station- Part 3, Steam Temperature Control

Available from:IEC

Tel. +41 22 919 02 11

www.iec.ch

MEASUREMENT, CONTROL AND AUTOMATION ASSOCIATION (MCAA)

Functional Diagramming of Instrument and Control Systems (Previously PMC 22.1-1981)

Process Measurement and Control Terminology (Previously PMC 20.1-1973)

Available from: MCAA

2093 Harper's Mill Rd.

P.O. Box 3698

Williamsburg, VA 23187-3698

www.measure.orgMISCELLANEOUS

Babcock & Wilcox, Steam It's Generation and Use, 41st ed., The Babcock & Wilcox Company, 20 S Van Buren Ave., P.O. Box 351, Barberton, OH. 44203-0351.

Design, Operation, Control and Modeling of Pulverized Coal-fired Boilers; Control of Boilers, 2nd. ed.; Dukelow, S. G.; ISA Press-1986 (ISBN: 1-55617-330-X)

Durrant, O. W.; Boiler-Turbine Modeling and Control Seminar, University of New South Wales, February 14-18, 1977

Standard Handbook of Power Plant Engineering, McGraw-Hill Publishing Co.; 1989 (ISBN: 0-07-01906-9)

Singer, Joseph G., Combustion: Fossil Power Systems, 4th ed., Combustion Engineering Inc., 1000 Prospect Hill Rd. Windsor, CT. 06095, 1991.

Control Valve Sourcebook, Power and Severe Services, 2nd ed., Fisher Controls International, Inc., 1990.

AnnexB Steam Temperature Control

B.1 Purpose

The purpose of this annex is to provide tutorial information on the philosophy underlying this standard and to assist the user of this standard in specifying and applying steam temperature control schemes. This annex is included for information purposes only and is not part of ISA-dS77.44.01.

B.2 Introduction

B.2.1 Subcritical vs. supercritical in once through boiler design

A boiler is either subcritical or supercritical depending on whether it is designed to be operated below or above the critical pressure, respectively (critical pressure is 3206.2 psia). At critical pressure and above, boiling, as it is known within the saturation region, does not take place. The transition from water to steam is abrupt, and the temperature steadily increases rather than flattening completely. At critical pressure, the density differential between water and steam becomes zero, thus making natural circulation impossible.

Operation at subcritical pressures creates certain problems for the boiler designer. Probably the most important problem is the handling of water-steam mixtures. At subcritical pressures, the water-steam mixtures can separate into all water in one tube and all steam in an adjacent tube. Thus, the boiler design must achieve good mixing of the water-steam mixture and limit the amount of heat absorbed by a furnace panel to a value that will not cause damaging thermal stresses in the membrane walls. As examples, variable orifices are installed in each furnace panel to balance the flows and furnace-mixing headers are used at particular locations to limit the heat absorption.

Operation at supercritical pressures eliminates concern over the separation of water-steam mixtures because this phenomenon does not occur. However, furnace-mixing headers redistribute the fluid where adjacent tubes are in different fluid passes. In supercritical operation, it is important to avoid subcritical pressures because of the possibility of steam to water separation where the boiler design does not consider this.

There are many similarities between subcritical and supercritical boilers. The gas side arrangement is practically identical, although some furnace panel surfaces may be located differently. The fluid side is also quite similar, particularly in the furnace circuitry. The boiler responses are quite similar, with supercritical boiler being slightly faster.

B.2.2 Steam temperature control by ratio adjustment

In a once-through boiler, final steam temperature is affected by the ratio of firing rate to feedwater flow. Therefore, changing firing rate, feedwater flow, or both, can affect control of steam temperature. The boiler master demand signal is typically sent in parallel to the firing rate demand and the feedwater demand. The temperature controller output is then configured as a ratio setting and applied to the firing rate, feedwater flow, or both.

The boiler master is tuned for pressure and load response, that is orders of magnitude faster than the temperature loop. Therefore, changes to ratio setting have been applied with success in either or both subsystems. Generally, though, it is simplified to modify the firing rate demand.

Recognizing that megawatts output is proportional, the input firing rate and feedwater flow must equal the flow leaving the boiler to maintain constant storage of fluid; it is logical to send boiler demand to the firing rate and feedwater together. Adjusting firing rate for final steam temperature results in a compromise between controlling temperature and controlling load. Adjusting feedwater flow for final steam temperature results in a compromise between controlling temperature and controlling pressure. Furthermore, firing rate and feedwater flow are conditioned upon the specific boiler design, boiler/process constraints, and process variable responses.

Once-through boiler designs require a minimum feedwater rate to protect the furnace tubes from overheating. This boiler constraint requires that the firing rate be adjusted to control steam temperature until load exceeds the minimum feedwater flow. At which time, feedwater flow can participate in controlling final steam temperature.

When feedwater flow or firing rate changes, a temperature delay exists before final steam temperature changes. The temperature delay time for firing rate is shorter than feedwater flow due to shorter transport delay and provides better transient correction for steam temperature. Boilers with spray attemperation have means to shorten feedwater flow transport delays by introducing spray water before the superheater(s). While spray attemperation may initially control temperature excursions, steady state temperature is achieved when total feedwater flow (boiler inlet water flow and spray attemperation flow) is in correct ratio with firing rate.

The controls will over-fire or under-fire the firing rate to respond to load changes. This transient condition creates an incorrect steady state fuel demand that causes temperature and pressure errors. Using temperature controls to modify firing rate demand and feedwater demand in opposite direction helps the overall system stability because one process effect counter acts the other.

B.3 Requirements

B.3.1 Design specification requirement

To adequately specify a steam temperature control strategy, the following three fundamental questions must be addressed:

a) What are the anticipated process operational requirementse.g., steady-state or cyclic operations, variable or fixed pressure operation, rates-of-change, etc.?

b) What equipment and operating parameters are required to properly interface the control system?

c) What characteristics must the control system possess to maintain the desired performance?

d) What are the boiler-design characteristics in the heat absorption pattern of the economizer, steam generation (water-wall), and the steam superheating (superheater and reheater)?

The extent to which these questions are answered will directly determine how well the control system is fitted to the design and operating requirements. A misapplication, at the least, could result in poor operating performance and, at the worst, could result in extensive boiler damage. The following is intended to supplement good engineering judgment with a consistent means of communicating design requirements to suppliers, designers, and constructors.

B.3.2 Summary of process performance requirements

A significant factor to consider in boiler control system selection is the heat absorption pattern in each steam generation (water wall and economizer) and steam superheater. Different boiler designs are used to properly balance the list absorption between the steam generation and steam super listing as well as the heat distribution requirements between the superheater and reheater sections.

When the superheater and reheater surfaces are designed to provide full load temperature at control load, resulting in excessive steam temperatures at full load, the following control means are provided for achieving the desired balance between steam generation and steam superheating over the load range:

a) Spray attemperation

b) Gas by-pass and damper control

c) Burner manipulation

d) A combination of the above is often needed to control superheat and reheat temperature independently.

When the superheat and reheat surfaces are designed to provide full load temperature only near full load, the following means are provided to increase the balance toward superheating and/or reheating as the load is reduced:

a) Increase excess air at reduced load

b) Burner manipulation

c) Gas recirculation

d) Gas by-pass and damper control (for distribution between superheat and reheat absorption)

e) A combination of the above is often needed to control superheat and reheat temperature independently

A second significant factor in steam temperature control system selection is the intended boiler usage. Since the operating requirements of the boiler define the required control system capabilities, design specifications must address the following unit characteristics:

a) Unit load/steaming capacity

b) Normal operating load range

c) Anticipated load changes (transients)

d) Start-up and shutdown frequency

A complete description of the anticipated load characteristics will allow the engineer/supplier to properly evaluate the system and to propose a control strategy. When the control strategy is preselected, these characteristics still should be defined as part of the design basis.

Table B.1 provides a general comparison of typical control systems for specification development and evaluation. This table is not intended to be all-inclusive; rather, it is a summary of commonly used control strategies. The important conclusion to be drawn from the table is that all control systems are not the same, and, therefore, selection of a specific system requires careful consideration of design parameters.

Table B.1 Summary of typical control systems

ProcessPrerequisitesSingle LoopSingle Loop with FeedforwardCascade Loop with Feedforward

Slow load changes or constant final steam temperature not criticalSlow to moderate load changes or steady spray water pressure supply or fixed final steam temperatureRapidly changing loads, variable spray water supply or variable final steam temperature

Steady-state operabilityGoodGoodGood

Transient operabilityPoorGoodGood

Response to load changeSlowFastFast

Control system typeFeedbackFeedback and FeedforwardFeedback, Feedforward, and Cascade

Process measurement requirementsFinal steam temperatureFinal steam temperature and feedforward signalSecondary Superheater (SSH) inlet temperature or attempt flow, feedforward signal, and final steam temperature

Potential for excessive temperature deviation during load changeProbableDependent on final drive linearity and repeatable through the load rangeMinimal

B.3.3 System description and interface requirements

To achieve the desired performance objectives, the control system interface with the process must be considered carefully. At a minimum, a detailed process description should be provided that includes

a) a specification for all process design parameters such as temperature, pressures, and normal flows;

b) final drive descriptions of sufficient detail that a control strategy can be selected to provide appropriate control action;

c) existing process measurement interfaces, dimension sketches or diagrams. All measurements should be taken where vibrations, pulsations, and other flow disturbances are at a minimum;

d) a description of available electrical power and pneumatic supplies;

e) control interlocks, setpoints, and alarm points; and

f) instrument loop diagrams as defined by ISAS5.41976 (R1981).

B.4 Principles and methods of steam temperature control

B.4.1 Steam temperature feedback control

A typical boiler arrangement is one where the spray attemperation takes place between the primary and secondary superheaters. With this arrangement, a large process time lag exists between the introduction of spray water and the detection and stabilization of exit steam temperature. A final steam temperature is used as the feedback measurement for control.

B.4.2 Load index development

The load index feedforward may be steam flow, air flow, or other measures of boiler load. Air flow offers the advantage of including excess combustion air requirements as a part of the load index signal. The load index feedforward signal is summed with the output signal from the steam temperature controller.

B.4.3 Transient correction signal development

A steam temperature transient correction is a signal that is applied to the normal steam temperature control strategy to counter the impact of a transient process change. An example of a transient process change, and the most typical, would be overfiring or underfiring. Overfiring and underfiring are considered transients because they are not required to maintain a steady-state condition. A steam temperature transient correction recognizes the impact of a transient on the final steam temperature and attempts to minimize this impact.

Probably the best way to describe this action is to consider an example. Assuming that a load increase is occurring, the firing rate will increase to meet the new load setting and will increase even more to assist in achieving the new energy storage level in the unit. This additional firing is referred to as overfiring, and once the unit's energy level is satisfied, it will be removed. Since the overfiring is only temporary, it is considered a transient condition. Assuming that no transient correction is made, the new load setting will require an adjustment to the steam temperature control, which normally is satisfied through feedforward action. The overfiring would cause the steam temperature to increase, and the steam temperature controller would react to counter the temperature excursion by increasing the spray.

When the overfiring is removed, the steam temperature would drop because excess spray exists. The excess spray would then cause the steam temperature controller to reduce the spray flow. The end results are a longer time period to reach steady-state conditions and a greater deviation versus time. A transient correction would recognize when overfiring is occurring and bias the controls to increase the spray to help minimize the temperature excursion and to prevent the temperature controller from integrating a temperature error over time. Ideally, no temperature transient would occur; thus steady state is achieved more quickly, and the temperature deviation versus time will be reduced.

The actual transient correction for overfiring or underfiring is a function of the overall control strategy. One approach is to use the throttle pressure error as the source for the transient correction. Throttle pressure error is scaled and summed with other feedforward signals.

B.5 Saturation protection/water induction protectionSteam temperature control maintains final steam temperature by injecting water into the steam flow upstream of the final superheater section. There are two potential problems with this process. The first can lead to water induction into the steam turbine and the second can cause a loss of control function along with severe downstream temperature transients.

If spray water is allowed to enter the desuperheater while the turbine is not operating, either by a leaking valve or a control malfunction, it may collect in the superheater tubes without being fully vaporized. Later when the turbine is started or the steam flow is increased, the water can be carried into the turbine where it can cause thermal or mechanical damage. The relatively cold water will tend to collect in the bottom of the turbine shell and shrink the hot metal which distorts the shape of the turbine shell causing rubbing and vibration.

The second problem is that during boiler upsets that cause the steam temperature to increase significantly, the steam temperature control system may call for more spray flow than can be completely vaporized by the steam flow. If the water is not completely vaporized, the steam leaving the desuperheater will be saturated. As long as the steam remains saturated, its temperature will not depend on the amount of spray flow but will only depend on the steam pressure. The saturation causes two problems. First, the desuperheater outlet temperature will stop changing. If the temperature is used as the feedback for the inner loop in a cascade control strategy, the inner loop will begin to "windup." This windup will not be prevented by normal anti-windup logic because the controller output will not be at a limit. Since the inner loop is normally tuned with significant integral action, the windup will occur fairly quickly. When the desuperheater outlet temperature eventually emerges from saturation, the controller will have to unwind before it begins to control properly. This condition can be detected very easily by watching for a clipped wave in the desuperheater outlet temperature response.

Secondly, when the desuperheater outlet steam is saturated, the small water droplets in the steam can affect downstream piping and superheater tubing. It also can cause severe thermal transients downstream as the steam emerges from the saturation condition.

B.6 Two-stage attemperation

Two-stage attemperation is provided in a boiler for one or both of the following reasons: first, the quantity of spray flow required is so great that a single attemperator would have saturated steam at its outlet; second, the metal temperature in one of the intermediate superheater sections would be above the allowable design temperature unless the inlet temperature of that section is controlled by spray.

Control of two-stage attemperators is more complex than a single attemperator because the action of the first spray stage affects the second stage. The coupling of the two stages makes tuning any control strategy more difficult.

One consideration in developing an appropriate strategy is the difference in the time responses of the first-stage spray and the second-stage spray. Since the second-stage spray is closer to the outlet of the boiler, its effect on the outlet temperature is faster than the first-stage spray. Better dynamic response of the final outlet temperature is possible if the second-stage spray is the main control parameter for the final temperature. The primary objective for steady state operation is providing maximum attemperation to the first stage to achieve maximum cooling of the platen or radiant superheater while controlling outlet steam temperature.B.7 Use of cascade spray valve control

In a cascade control strategy, when the output of one controller is used to manipulate the setpoint of another, the two controllers are said to be cascaded. Although each controller will have its own measurement input, only the primary controller (outer loop) can have an independent setpoint, and only the secondary controller (inner loop) has an output to the process.

Steam temperature control strategies assume a predictable relationship between the spray water control valve position and the spray water flow. If this is not the case, a cascade spray water flow control strategy should be considered. With the cascade control strategy, the output of the temperature controller establishes the required spray flow setpoint for the spray water flow controller. In the cascade control arrangement, the temperature controller is the primary controller, and the spray flow controller is the secondary controller.

B.8 NOx control

The nitrogen and oxygen in the combustion air and fuel form oxides of nitrogen (NO() during the combustion process. The rate of NOx formation is dependent on high temperature, stoichiometric conditions, resident combustion time, and the amount of nitrogen in the fuel. To suppress the formation of NO(, the combustion conditions and control strategy must be altered to decrease 02 level at the flame zone, stage combustion or both and to decrease combustion gas temperature in the furnace and, hence, the time of exposure of the products of combustion to high temperature.

Air that bypasses the burner combustion can suppress the formation of NO( by reducing the 02 level and temperature at the primary combustion zone. This option is possible if the boiler design allows the use of burner out-of-service or overfire air ports, or both to achieve the second stage of combustion. The out-of-service burners and overfire air ports provide means of introducing staged combustion air downstream of the furnace combustion zone. Excess air used for steam temperature control also must bypass the burner combustion zone.

Flue gas recirculation can suppress the formation of NO( by reducing the combustion temperature if the boiler design allows introduction of flue gas recirculation into the secondary air stream.

Flue gas recirculation can be used for suppressing the formation of NOx and controlling reheat steam temperatures if the boiler design allows the introduction of flue gas recirculation into both the secondary air stream and the furnace hopper. These boilers have a gas recirculation distribution damper for regulating the gas recirculation flow path.

B.9 Redundancy

Redundancy is employed when system reliability will be seriously affected by a component failure. Redundancy also permits on-line maintenance of components. For maximum availability, redundancy should always be considered. Deviation alarms and automatic failure detection/transfer should be considered, in order to maximize the usefulness of the application of redundancy.

B.10 Reset windup prevention

Any control loop in which the controller has integral action and the final control element is likely to be fully open or fully closed during routine plant operation should have a provision to prevent reset windup. Steam temperature controls frequently fall into this category because boiler designers usually try to minimize the amount of spray flow required throughout the load range. This frequently leads to times when the spray valve is fully closed during normal operation and, therefore, to the need to reset windup prevention.

For conventional single loop controls, reset windup prevention is relatively simple to implement. As soon as the final control element reaches one of its endpoints of travel (0% closed or 100% open), the integral (reset) action or the entire controller is disabled. For a simple control loop, the integral limits on the final control element correspond to the high and low limits on the controller output. Most controllers have automatic reset windup prevention when the controller output reaches a limit. Provided everything is calibrated correctly, the reset windup prevention will begin when the final control element reaches a travel limit.

For a cascade loop or cascade loop with feedforward controls, reset windup prevention becomes slightly more complicated. Now two controllers must both stop integrating to prevent reset windup. The inner or secondary controller operates the same as a single loop controller described above. The primary controller must also have its integral or reset action disabled when the final control element reaches a limit. The output of the primary controller is not always at the same value when the final control element reaches a limit, so a different mechanism must be used to implement the windup prevention. On pneumatic and analog electronic controllers, it may not be practical to implement a reset windup prevention scheme such as is required in this situation. On a digital system, however, there are several ways to do this. The integral gain of the controller may be adaptively tuned to zero when the limit is reached or the high or low limit of the controller may be adjusted to the controller output value when the limit is reached. This prevents the primary controller from winding up the setpoint for the secondary controller when the final control element is at a limit.

B.11 Advanced steam temperature control

Steam temperature control is one of the most difficult control loops in the boiler control system. There are several factors that make the control difficult.

The time response of the final steam temperatures is generally very slow and has a considerable deadtime response. This is due to the large mass of metal in the superheater sections of the boiler, which are slow to change temperature. Slow response and deadtime responses are both tough to handle well with conventional control strategies.

Steam temperature can be upset by almost any disturbance in the boiler. These upsets continually challenge the control system and when combined with the slow temperature response make good control tough. Some of the more common upsets are load changes, fuel variations, boiler slag, pressure changes, pulverizer upsets, and sootblowing.

Spray valves that are usually the primary control means for final steam temperature control sometimes go closed during certain load ranges or transients. Any time a final control element goes into saturation such as fully closed or fully open, it introduces a large nonlinearity into the control loop. Conventional control strategies do not cope with such nonlinear responses well.

There are usually two methods of controlling reheat temperature. One is a spray valve and the other is some method of controlling heat distribution such as burner tilts, pass dampers, or gas recirculation. The action of these two control variables must be coordinated, and this adds some complexity to the control strategy.

With all of these factors making steam temperature control difficult, it is easy to understand why it is a frequent target of advanced control techniques. There are a variety of advanced control techniques, which can be used. They range from relatively simple modifications such as better feedforward signals or deadtime compensation to full-blown multivariable optimal control systems. Many of the advanced control techniques can improve steam temperature control, but they generally involve added complexity in the control system. The added complexity in the control system can require a higher level of support by the plant staff.

Although this standard describes the minimum requirements for steam temperature control, the reader should be aware that more advanced control techniques are available and can frequently provide better control performance.

Annex C Figures

Figure C.1a Typical superheater single-stage attemperator arrangement

Figure C.1b Typical superheater two-stage attemperator arrangement

Figure C.1c Typical universal pressure once-through boiler

Figure C.1d Typical once-through boiler

Figure C.1e Typical combined circulation once-through boiler

Figure C.1f Typical two stage attemperator once-through boiler

Figure C.2 Typical single loop superheat steam temperature control

Figure C.3 - Typical single loop with feedforward superheat steam temperature control

Figure C.4a Typical cascade loop with feedforward superheat steam temperature control with temperature inner loopFigure C.4b Typical cascade loop with feedforward superheat steam temperature control with flow inner loop

Figure C.5 Typical two-stage attemperation superheat steam temperature control

Figure C.6 Typical single loop with feedforward fuel nozzle tilt control

Figure C.7 Typical single loop with feedforward flue gas pass damper control

Figure C.8 Typical single loop with feedforward flue gas recirculation control

Figure C.9 Typical single loop reheat steam temperature control

Figure C.10 Typical firing rate feedwater ratio control

Developing and promulgating sound consensus standards, recommended practices, and technical reports is one of ISAs primary goals. To achieve this goal the Standards and Practices Department relies on the technical expertise and efforts of volunteer committee members, chairmen and reviewers.

ISA is an American National Standards Institute (ANSI) accredited organization. ISA administers United States Technical Advisory Groups (USTAGs) and provides secretariat support for International Electrotechnical Commission (IEC) and International Organization for Standardization (ISO) committees that develop process measurement and control standards. To obtain additional information on the Societys standards program, please write:

ISA

Attn: Standards Department

67 Alexander Drive

P.O. Box 12277

Research Triangle Park, NC 27709

ISBN:

EMBED Visio.Drawing.5

EMBED Visio.Drawing.5

EMBED Visio.Drawing.5

EMBED Visio.Drawing.5

EMBED Visio.Drawing.5

EMBED Visio.Drawing.5

EMBED Visio.Drawing.6

EMBED Visio.Drawing.5

EMBED Visio.Drawing.5

_1197452923.vsd

_1202728770.vsd

_1215490059.vsd

_1228741995.vsd

_1215489968.vsd

_1197453127.vsd

_1197455332.vsd

_1197449933.vsd

_1197452170.vsd

_1197452357.vsd

_1197451881.vsd

_1197451312.vsd

_1190658167.vsd

_1190658445.vsd

_1190657614.vsd

_1015573605.vsd