57
IS 802 RECOMMENDATIONS ON WIND LOAD ON TRANSMISSION LINE TOWERS

Is 802 Recommendations on Wind Load on Transmission

Embed Size (px)

DESCRIPTION

is 802

Citation preview

Page 1: Is 802 Recommendations on Wind Load on Transmission

IS 802 RECOMMENDATIONS ON WIND LOAD ON

TRANSMISSION LINE TOWERS

Page 2: Is 802 Recommendations on Wind Load on Transmission
Page 3: Is 802 Recommendations on Wind Load on Transmission

(IS802 (Partl/Sec 1):1995)

Indian StandardUSE OF STRUCTURAL STEEL IN

OVERHEADTRANSMISSION LINE TOWERS -

CODE OF PRACTICEPART 1 MATERIALS, LOADS AND

PERMISSIBLE STRESSES

Section 1 Materials and Loads

Page 4: Is 802 Recommendations on Wind Load on Transmission

Basic Wind Speed, Vb

• Ref: IS 875 (3) – WIND MAP

Page 5: Is 802 Recommendations on Wind Load on Transmission

Meteorological Reference Wind Speed, VR

Page 6: Is 802 Recommendations on Wind Load on Transmission

Design Wind Speed, Vd

Page 7: Is 802 Recommendations on Wind Load on Transmission

• Risk coefficient K1 depends on the basic wind speed Vb (or wind zone) and the reliability level

Page 8: Is 802 Recommendations on Wind Load on Transmission

• Reliability level 1 shall be adopted for EHV transmission lines up to 400 kV class.

• Reliability level 2 shall be adopted for EHV transmission lines above 400 kV class. Triple and quadruple circuit towers up to 400 kV lines shall be designed corresponding to the reliability level 2.

• Reliability level 3 shall be adopted for tall river crossing towers and special towers

Page 9: Is 802 Recommendations on Wind Load on Transmission

Terrain Roughness Coefficient, K2

Page 10: Is 802 Recommendations on Wind Load on Transmission
Page 11: Is 802 Recommendations on Wind Load on Transmission
Page 12: Is 802 Recommendations on Wind Load on Transmission
Page 13: Is 802 Recommendations on Wind Load on Transmission

Design Wind Pressure, Pd

• The design wind pressure on towers, conductors and insulators shall be obtained by the following relationship :

Page 14: Is 802 Recommendations on Wind Load on Transmission

Wind Load on Tower• the tower is divided into different panels

having a height ‘h’. (normally be taken between the intersections of the legs and bracings).

• For a lattice tower of square cross section, the resultant wind load Fwt in Newtons, for wind normal to the longitudinal face of tower, on a panel height ‘h’ applied at the centre of gravity of this panel is:

Page 15: Is 802 Recommendations on Wind Load on Transmission

Pd = design wind pressure, in N/m2

Cdt = drag coefficient for panel under consideration against which the wind is blowing.

Page 16: Is 802 Recommendations on Wind Load on Transmission

Ae = total net surface area of the legs, bracings, cross arms and secondary members of the panel projected normal to the face in m2

GT = gust response factor,

Page 17: Is 802 Recommendations on Wind Load on Transmission

Wind Load on Conductor and Ground wire

Page 18: Is 802 Recommendations on Wind Load on Transmission
Page 19: Is 802 Recommendations on Wind Load on Transmission

WIND LOAD ON ROAD BRIDGES

(IRC 6 Section II – 1966)

Page 20: Is 802 Recommendations on Wind Load on Transmission
Page 21: Is 802 Recommendations on Wind Load on Transmission
Page 22: Is 802 Recommendations on Wind Load on Transmission
Page 23: Is 802 Recommendations on Wind Load on Transmission

• The lateral wind force against any exposed moving live load shall be considered as acting at 1.5 m above the roadway and shall be assumed to have the following values

While calculating the wind force on live load, the clear distance between the trailers of a train of vehicles shall not be omitted.

Page 24: Is 802 Recommendations on Wind Load on Transmission

WIND LOAD ON COOLING TOWERS

Page 25: Is 802 Recommendations on Wind Load on Transmission
Page 26: Is 802 Recommendations on Wind Load on Transmission

IS : 11504 - 1985

Indian StandardCRITERIA FOR STRUCTURAL

DESIGN OFREINFORCED CONCRETE

NATURALDRAUGHT COOLING TOWERS

Page 27: Is 802 Recommendations on Wind Load on Transmission

Wind Pressure• The basic wind pressure shall, in general, conform

to IS : 875-1964* excepting in places where local conditions warrant special investigations

• The wind pressure coefficient distribution on the shell should preferably be derived from wind tunnel tests of a model of the proposed tower shell shape

• the wind pressure distribution for cooling towers not more than 100 m in height and not more than 120 m in base diameter built singly or in groups spaced at clear distance of not less than 0.5 times the base diameter of the largest cooling tower in the group can be computed as follows

Page 28: Is 802 Recommendations on Wind Load on Transmission

• The wind pressure distribution on the outside of the shell is assumed to be symmetrical about the centre line in the direction of wind.

• For practical design these values may be increased by 10 percent to take into account geometrical imperfections

Page 29: Is 802 Recommendations on Wind Load on Transmission
Page 30: Is 802 Recommendations on Wind Load on Transmission

• The wind pressure coefficient distribution around the shell is defined by the following equation

Page 31: Is 802 Recommendations on Wind Load on Transmission
Page 32: Is 802 Recommendations on Wind Load on Transmission

Pressure FluctuationsThe steady pressure coefficients discussed

earlier are for uniform pressure distribution in laboratory conditions and further allowances should be made in assessing the wind loading for

• load intensification due to natural turbulence in the incident wind, and

• load intensification due to turbulence induced in the incident wind by adjacent cooling towers in a group or of the structures of significant dimension in the vicinity

Page 33: Is 802 Recommendations on Wind Load on Transmission

WIND LOAD ON RC CHIMNEYS

IS 4998 ( Part 1) : 1992

Indian StandardCRITERIA FOR DESIGN OF

REINFORCEDCONCRETE CHIMNEYS

PART 1 ASSESSMENT OF LOADS

Page 34: Is 802 Recommendations on Wind Load on Transmission
Page 35: Is 802 Recommendations on Wind Load on Transmission

ESTIMATION OF WIND LOADSTWO METHODS• The first is a simplified method and is likely

to yield slightly conservative results as far as across wind loads are concerned.

• The second method is based on random response method.The wind loads shall be estimated by

both the methods and the loading which yields higher moments shall be

considered for design of chimneys.

Page 36: Is 802 Recommendations on Wind Load on Transmission

SIMPLIFIED METHOD1. Along-Wind Load or Drag ForceThe along-wind load or drag force per unitheight of the chimney at any level shall becalculated from the equation

Page 37: Is 802 Recommendations on Wind Load on Transmission

• The design wind pressure ( pz ), for the along wind response, shall be obtained in accordance with IS 875 ( Part 3 ) ; 1987, taking the appropriate factor depending upon the class of the structure as defined in that standard.

• The chimney shall be divided into ten or more sections along its height and the load at any section shall be calculated by suitably averaging the loads above and below it.

Page 38: Is 802 Recommendations on Wind Load on Transmission

The moments are calculated from the sectional forces treating the chimney as a free standing structure

Page 39: Is 802 Recommendations on Wind Load on Transmission

RANDOM RESPONSE METHODAlong-Wind Load on a Chimney• along-wind response of a chimney shall

also be calculated by the Gust Factor method

• The use of the Gust Factor method requires a knowledge of Hourly Mean Wind Speed ( HMW ).

• Hourly mean wind speed at any height (z), shall be obtained as per IS 875 ( Part 3 ) : 1987

Page 40: Is 802 Recommendations on Wind Load on Transmission
Page 41: Is 802 Recommendations on Wind Load on Transmission
Page 42: Is 802 Recommendations on Wind Load on Transmission
Page 43: Is 802 Recommendations on Wind Load on Transmission
Page 44: Is 802 Recommendations on Wind Load on Transmission
Page 45: Is 802 Recommendations on Wind Load on Transmission

IS 6533 (Part 2) : 1989

Indian StandardCODE OF PRACTICE FOR DESIGN ANDCONSTRUCTION OF STEEL CHIMNEY

PART 2 STRUCTURAL ASPECT

WIND LOAD ON STEEL CHIMNEYS

Page 46: Is 802 Recommendations on Wind Load on Transmission
Page 47: Is 802 Recommendations on Wind Load on Transmission

• The wind loads shall be calculated in accordance with the provisions contained in IS 875 (Part 3) : 1987

• Wind force on ladders and other fixtures fixed to a chimney shall be determined and added to the force on the chimney

Page 48: Is 802 Recommendations on Wind Load on Transmission

Calculation of Static Wind Load• Static wind pressure, q, acting normal to

the surface of chimney shall be taken as specified in IS 875 (Part 3) : 1987 for the appropriate wind zone, terrain and topography

• the chimney height shall be divided into a number of convenient zones such that the number of zones shall not be less than three and the zone height shall not exceed 10 m

Page 49: Is 802 Recommendations on Wind Load on Transmission

• Static wind force acting at the midpoint of Kth zone ( K varying from 1 to r ) shall be calculated from the formula

Page 50: Is 802 Recommendations on Wind Load on Transmission
Page 51: Is 802 Recommendations on Wind Load on Transmission

Calculation of Dynamic Wind Loads• Dynamic effect of wind is influenced by a

number of factors, such as, mass and its disposition along chimney height, period and mode of natural oscillation, Logarithmic decrement of dampening, pulsation of velocity thrust, etc.

• Values of dynamic components of wind load should be determined for each mode of oscillation of the chimney as a system of inertia forces acting at the centre of the zone being considered.

Page 52: Is 802 Recommendations on Wind Load on Transmission

WIND LOAD ON RAILWAY BRIDGESBRIDGE RULES

(IN SI UNITS) RULES SPECIFYING THE LOADS FOR

DESIGN OF SUPER-STRUCTURE AND SUB-STRUCTURE OF BRIDGES AND FOR ASSESSMENT

OF THE STRENGTH OF EXISTING BRIDGES

Page 53: Is 802 Recommendations on Wind Load on Transmission

• For purposes of design where no meteorological records are available, the Map as given in IS: 875 (Part 3) in conjunction with the Table therein, may be used for determining the basic wind pressures.

Page 54: Is 802 Recommendations on Wind Load on Transmission

• The wind pressure specified above shall apply to all loaded or unloaded bridges provided that a bridge shall not be considered to be carrying any live load when the wind pressure at deck level exceeds the following limits:

Page 55: Is 802 Recommendations on Wind Load on Transmission

• The wind load shall be computed from the appropriate basic wind pressure and the exposed area

exposed area• For unloaded spans net exposed area

shall be considered as one and half times the projected area of the span, except for plate girders for which the area of the leeward girder shall be multiplied by the factors based on its depth and the distance from the windward girder

Page 56: Is 802 Recommendations on Wind Load on Transmission
Page 57: Is 802 Recommendations on Wind Load on Transmission

• For loaded spans the net exposed area shall be computed as the sum of (i) and (ii)(i) as detailed above(ii) The projected area of the moving load

• In the case of railway bridges: the area of the moving load shall be taken as from 600mm above rail level to the top of the highest stock for which the bridge is designed

• In the case of foot bridges: the height of the moving load is to be taken as 2m throughout the length of the span