< PROJECT # > < PROJECT NAME > < DATE > SECTION 22 11 16 DOMESTIC WATER PIPING PART 1 GENERAL 1.1 SECTION INCLUDES .1 CPVC pipe, fittings, and valves for domestic water piping. 1.2 RELATED SECTIONS .1 Division 01 Section “Administrative Requirements” .1 Division 01 Section “Submittal Procedures” .2 Division 07 Section “Fire and Smoke Protection” DOMESTIC WATER PIPING 22 11 16 - NOTE TO SPECIFIER: This specification Section is provided as a sample and includes AquaRise® pipe, fittings, valves, and solvent cements. DO NOT use this Section until it has been reviewed and edited to meet specific project requirements by the Engineer of Record or qualified design professional. This specification includes editing notes, which can be accessed by going to the “File” tab and selecting “Options”, then “Display”. Once there, select the “Hidden text” box to turn on the specification notes. AquaRise® is a full piping system designed specifically for hot and cold potable water distribution. Complete with pipe, valves, fittings, cements, and accessories, AquaRise proves itself a strong, corrosion resistant, and highly-engineered solution for potable water installations.

IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

SECTION 22 11 16

DOMESTIC WATER PIPING

PART 1 GENERAL

1.1 SECTION INCLUDES

.1 CPVC pipe, fittings, and valves for domestic water piping.

1.2 RELATED SECTIONS

.1 Division 01 Section “Administrative Requirements”.1 Division 01 Section “Submittal Procedures”

.2 Division 07 Section “Fire and Smoke Protection”

.3 Division 22 Section “Plumbing”.1 Division 22 Section “Operation and Maintenance of Plumbing”.2 Division 22 Section “Common Work Results for Plumbing”.3 Division 22 Section “Schedules for Plumbing”.4 Division 22 Section “Plumbing Insulation”.5 Division 22 Section “Commissioning of Plumbing”

DOMESTIC WATER PIPING 22 11 16 -

NOTE TO SPECIFIER: This specification Section is provided as a sample and includes AquaRise® pipe, fittings, valves, and solvent cements. DO NOT use this Section until it has been reviewed and edited to meet specific project requirements by the Engineer of Record or qualified design professional.

This specification includes editing notes, which can be accessed by going to the “File” tab and selecting “Options”, then “Display”. Once there, select the “Hidden text” box to turn on the specification notes.

AquaRise® is a full piping system designed specifically for hot and cold potable water distribution. Complete with pipe, valves, fittings, cements, and accessories, AquaRise proves itself a strong, corrosion resistant, and highly-engineered solution for potable water installations.

Visit ipexaquarise.com

IPEX Inc. | 3 Place du Commerce, Suite 101 | Île-des-Soeurs, Verdun, QC H3E 1H7 | Toll Free (866) 473-9462

Page 2: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

.4 Division 22 Section “Plumbing Piping”.1 Division 22 Section “Facility Water Distribution”

1.3 CODES, STANDARDS, AND REFERENCES

.1 National Research Council (NRC):.1 National Plumbing Code of Canada (NPC)

.2 Ontario Building Code (OBC).

.3 < Insert additional Provincial, local Codes or Amendments >

.4 American Society of Mechanical Engineers (ASME):.1 ASME B1.20.1 - Pipe Threads, General Purpose, Inch..2 ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24

Metric/Inch Standard

.5 ASTM International: (ASTM).1 ASTM D1784 - Standard Specification for Rigid Poly (Vinyl Chloride) (PVC)

Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds..2 ASTM F402 - Standard Practice for Safe Handling of Solvent Cements,

Primers, and Cleaners Used for Joining Thermoplastic Pipe and Fittings.3 ASTM F438 - Standard Specification for Socket-Type Chlorinated Poly (Vinyl

Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40..4 ASTM F439 - Standard Specification for Chlorinated Poly (Vinyl Chloride)

(CPVC) Plastic Pipe Fittings, Schedule 80..5 ASTM F442 - Standard Specification for Chlorinated Poly (Vinyl Chloride)

(CPVC) Plastic Pipe (SDR-PR)..6 ASTM F1970 - Standard Specification for Special Engineered Fittings,

Appurtenances or Valves for use in Poly (Vinyl Chloride) (PVC) or Chlorinated Poly (Vinyl Chloride) (CPVC) Systems.

.6 Canadian Standards Association (CSA):.1 CSA B137 - Thermoplastic Pressure Piping Compendium..2 CSA B137.6 - Chlorinated Polyvinylchloride (CPVC) Pipe, Tubing, and

Fittings for Hot- and Cold-Water Distribution Systems.

.7 National Sanitation Foundation (NSF):.1 NSF 14 - Plastics Piping System Components and Related Materials..2 NSF 61 - Drinking Water System Components - Health Effects..3 NSF 372 – Drinking Water System Components – Lead Content

.8 Underwriters Laboratories of Canada (ULC):.1 CAN/ULC-S102.2 - Surface Burning Characteristics of Flooring, Floor

Covering and Miscellaneous Materials and Assemblies..2 CAN/ULC-S115 - Standard Method of Fire Tests of Firestop Systems

1.4 DEFINITIONS

.1 CPVC: Chlorinated polyvinyl chloride.

.2 EPDM: Ethylene propylene diene monomer elastomer.

.3 IPS: Iron Pipe Size.

.4 PTFE: Polytetrafluoroethylene.

.5 SDR: Standard dimension ratio; used by plastic pipe manufacturers as a method of

DOMESTIC WATER PIPING 22 11 16 -

Page 3: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

rating pressure piping.

1.5 SUBMITTALS

.1 Submit under provisions of Division 01 Section “Administrative Requirements”.

.2 Product Data: Provide manufacturer’s product submittals.

1.6 QUALITY ASSURANCE

.1 Regulatory Requirements:.1 Authorities having jurisdiction:

.1 Potable-water piping.

.2 Piping: Labeled and marked as determined by agency approved by authorities having jurisdiction.

.3 Source Limitations: Obtain piping, fittings, valves and accessory equipment from a single manufacturer.

.4 Do not expose CPVC products to incompatible building materials or substances. Consult pipe manufacturer or building material manufacturer to determine chemical compatibility with specific building materials or substances.

.5 Installer Qualifications: Installer shall be experienced in performing work related to this section, and shall be specialized in installation of work similar to that required for this project. Installer shall be trained by a qualified manufacturers’ representative prior to installing and handling CPVC piping products.

1.7 DELIVERY, STORAGE, AND HANDLING

.1 CPVC Pipe, Fittings, and Valves: 1. Delivery, storage, and handling of products shall be in accordance with

manufacturer’s recommendations. 2. Deliver and store products in manufacturer's unopened packaging bearing the

brand name and manufacturer's identification until ready for installation.3. Store pipe indoors if possible.4. Pipe stored outside must be covered with a well-ventilated white tarp.5. Always keep pipe clean and covered in its original packaging.6. Always store pipe on a flat surface and never store other products on top of

pipe.7. Do not drop or drag pipe.8. Always store fittings and valves indoors in original packaging or repackage to

project from damage, dirt, and debris.9. Ensure pipe and piping components are not stored close to external sources

of heat such as boilers, steam lines, etc.

.2 CPVC Solvent Cements and Primers: 1. Handling of solvent cements and primers shall be in accordance with

manufacturer’s recommendations, product safety data sheets (SDS), and ASTM F402.

2. Avoid skin or eye contact with primers and cements.3. Wash immediately if contact occurs to avoid prolonged exposure.4. Use personal protection equipment (PPE) when handling primers and solvent

cements.5. Always store primer and cement indoors.6. For cold weather installation, store primer and cement in a warm location

DOMESTIC WATER PIPING 22 11 16 -

Page 4: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

above 40 degrees F (5 degrees C).7. For hot weather installation, store primer and cement in a cool, shaded

location.8. Never use primer or solvent cement that is older than its recommended shelf

life.9. Properly discard primer and cement that exceeds its recommended shelf life

or expiry date.10. Properly discard solvent cement that has hardened or jelled.11. Keep primer and cement away from open flames, sparks, and other sources

of ignition. 12. Tightly close partially used primer and cement containers.

PART 2 PRODUCTS

2.1 MANUFACTURER

.1 Acceptable Manufacturer: IPEX Inc., which is located at: 3 Place du Commerce, Suite 101, Île-des-Soeurs, Verdun, QC H3E 1H7; Toll Free Tel: 866-473-9462; Email: request info ([email protected]); Web: www.ipexna.com 1. < Substitutions: Not permitted. >2. < Acceptable manufacturer subject to compliance with requirements: >

.1 < Insert manufacturer’s name >

2.2 CPVC PIPE AND FITTINGS:

.1 Basis of Design: IPEX Inc.; AquaRise Potable Water Piping, Fittings, and Valves; NPS 1/2 to NPS 4 (DN 15 to DN 100).1. Material Requirements: ASTM D1784.

.1 Cell classification:.1 Pipe: 24448 for NPS 1/2 to NPS 4 (DN 15 to DN 100)..2 Fittings: 23447 for NPS 1/2 to NPS 4 (DN 15 to DN 100).

2. Flame and Smoke Listing:.1 Pipe and fittings shall be listed to CAN/ULC S102.2, exhibiting a Flame

Spread Value (FSV) of not more than 25 and a Smoke Developed Value (SDV) of not more than 50.

3. SDR 11 Pipe (Hot and Cold Water): NPS 1/2 to NPS 4 (DN 15 to DN 100)..1 Pressure Rating: 400 psi at 73 degrees F (23 degrees C) and 150 psi

at 160 degrees F (71 degrees C). .2 Standards:

.1 CSA B137.6.

.2 ASTM F442.

.3 NSF 14.

.4 NSF 61..3 Dimensions:

.1 IPS outer diameters.

.2 SDR: 11.

.3 Standard Lengths: 10 ft (3 m).4. SDR 21 Pipe (Cold Water Only): NPS 1-1/2 to NPS 4 (DN 40 to DN 100).

.1 Pressure Rating: 200 psi at 73 degrees F (23 degrees C)

.2 Standards:.1 CSA B137.6..2 ASTM F442..3 NSF 14..4 NSF 61.

.3 Dimensions:.1 IPS outer diameters..2 SDR: 21.

DOMESTIC WATER PIPING 22 11 16 -

Page 5: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

.3 Standard Lengths: 10 ft (3 m).

5.Fittings: NPS 1/2 to NPS 4 (DN 15 to DN 100); Socket-type (couplings, tees, elbows, bushings, caps, manifolds)..1 Pressure Rating: 400 psi at 73 degrees F (23 degrees C) and 150 psi

at 160 degrees F (71 degrees C). .2 Standards:

.1 CSA B137.6.

.2 ASTM F438.

.3 ASTM F439.

.4 NSF 14.

.5 NSF 61. .3 Dimensions:

.1 NPS 1/2 to 1 (DN 15 to DN 25) socket type; CSA B137.6 and ASTM F438.

.2 NPS 1-1/4 to 4 (DN 32 to DN 100) socket type; CSA B137.6 and ASTM F439.

6. Unions: NPS 1/2 to NPS 4 (DN 15 to DN 100)..1 Pressure Rating: 150 psi at 73 degrees F (23 degrees C) and 57 psi at

160 degrees F (71 degrees C)..2 Standards:

.1 ASTM F1970.

.2 NSF 14.

.3 NSF 61..3 Socket dimensions conform to ASTM F438 or ASTM F439, depending

on size.

2.3 CPVC TRANSITION FITTINGS:

.1 Transition fittings shall be AquaRise, supplied by IPEX Inc.1. Bronze Threaded Adapters: NPS 1/2 to NPS 2 (DN 15 to DN 50), male and

female threads..1 Threaded adapters shall be manufactured from dezincification resistant

C90300 bronze alloy. .2 Pressure Rating: 400 psi at 73 degrees F (23 degrees C) and 150 psi

at 160 degrees F (71 degrees C)..3 Standards:

.1 CSA B137.6.

.2 ASTM F1970.

.3 NSF 14.

.4 NSF 61.

.5 Certified as lead free to NSF 372..4 Socket dimensions conform to ASTM F438 or F439, depending on the

size..5 Thread dimensions conform to ASME B1.20.1.

2. Flanges: NPS 1/2 to NPS 4 (DN 15 to DN 100).1 Pressure Rating: 150 psi at 73 degrees F (23 degrees C) and 57 psi at

160 degrees F (71 degrees C)..2 Standards:

.1 ASTM F1970.

.2 NSF 14.

.3 NSF 61..3 Socket dimensions conform to ASTM F439.4 150 lb bolt pattern per ASME B16.5.

3. Full-Pressure Flange Kit: AquaRise, NPS 2-1/2 to NPS 4 (DN 65 to DN 100)..1 Pressure Rating: 400 psi at 73 degrees F (23 degrees C) and 150 psi

DOMESTIC WATER PIPING 22 11 16 -

Page 6: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

at 160 degrees F (71 degrees C)..2 Standards:

.1 CSA B137.6.

.2 ASTM F1970.

.3 NSF 14.

.4 NSF 61..3 Socket dimensions conform to ASTM F439.4 Elastomeric Gasket: Durometer Hardness: 70..5 Steel Backing Ring: Two-piece, zinc plated..6 Hardware: Grade 8, yellow zinc plated, hex bolts, hex nuts, and heavy-

duty flat washers..7 Installation instructions shall be supplied with the Flange Kit..8 The AquaRise Full-Pressure Flange Kit shall be installed using all the

components supplied. Any substitution of components, such as longer bolts or a replacement gasket shall comply with the original kit specification.

2.4 CPVC VALVES:

.1 Valves shall be AquaRise, made of the same material as the attached piping, and supplied by IPEX Inc.1. Ball Valves: NPS 1/2 to NPS 2 (DN 15 to DN 50).

.1 Pressure Rating: 232 psi at 73 degrees F (23 degrees C) and 72 psi at 160 degrees F (71 degrees C).

.2 Standards:.1 NSF 61.

.3 Body Material: AquaRise CPVC, cell classification 23447 per ASTM D1784

.4 Design: Union type.

.5 Ends: Detachable, socket.

.6 Ball and stem:.1 Material: AquaRise CPVC..2 Machined smooth.

.7 Port: Full.

.8 Seats: PTFE.

.9 Seals: EPDM.

.10 Unions: Double-blocking.

.11 Handle: Tee shaped, built-in to tool to adjust seat carrier.

2.5 CPVC SOLVENT CEMENTS:

.1 Solvent cements shall be AquaRise, supplied by IPEX Inc.1. One-Step Cement: NPS 1/2 to NPS 2 (DN 15 to DN 50):

.1 Certified to CSA B137.6.

.2 NSF 14 & 61 certified for potable water.

.3 Colour: Yellow with optical brightener.2. Two-Step Cement and Primer: NPS 2-1/2 to NPS 4 (DN 65 to DN 100):

.1 Certified to CSA B137.6.

.2 NSF 14 & 61 certified for potable water.

.3 Colour: Yellow (cement) with optical brightener.

.4 Colour: Clear (primer).3. CPVC solvent cements volatile organic compound (VOC) emissions shall not

exceed 490 g/L and meet South Coast Air Quality Management District (SCAQMD) Rule 1168/316A.

4. CPVC primers volatile organic compound (VOC) emissions shall not exceed 550 g/L and meet South Coast Air Quality Management District (SCAQMD)

DOMESTIC WATER PIPING 22 11 16 -

Page 7: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

Rule 1168/316A.

2.6 REPAIR COUPLINGS:

.1 Repair couplings shall be AquaRise, supplied by IPEX Inc.1. AquaRise Maintenance Couplings - NPS 1 to NPS 4 (DN 25 to DN 100):

.1 Couplings shall be used for maintenance and repairs only.

.2 Couplings shall be suitable for pipe-to-pipe repair connections only and not suitable for use with any spigot ends of molded fittings.

.3 Pressure Rating: 400 psi at 73 degrees F (23 degrees C) and 150 psi at 160 degrees F (71 degrees C).

.4 Standards:.1 NSF 61.

.5 Body Material: 304 stainless steel.

.6 Sealing gasket: PTFE coated EPDM.

PART 3 EXECUTION

3.1 EXAMINATION

.1 Site Verification of Conditions: Verify that site conditions are acceptable for installation of domestic water piping. Do not proceed with installation until unsatisfactory conditions have been corrected.

3.2 PIPING INSTALLATION

.1 Install CPVC products in accordance with manufacturer’s instructions and technical manuals, approved submittals, and in proper relationship with adjacent construction.1. Inspect all products prior to installation.2. Never install products that are damaged.3. Always use proper ventilation when applying primers and solvent cements.4. Do not solvent weld near open flames or soldering torches.5. Do not solvent weld joints when pipe, fitting, valve or installation temperatures

are less than 40 degrees F (5 degrees C).

.2 Prior to installation, installers shall be trained by a qualified manufacturer’s representative on the installation and handling of CPVC products.

.3 Install in accordance with the requirements of the National Plumbing Code of Canada (NPC) and the local plumbing Authority Having Jurisdiction.

.4 CPVC Pipe Joints to dissimilar materials1. Join dissimilar pipe materials with CPVC transition fittings; bronze threaded

adapters, flanges, or full-pressure flange kits.2. Use PTFE tape only when connecting to bronze threaded adapters.

.5 Penetrations through structure shall be such that structural loads are not transferred to pipes.

.6 Provide support of pipe in accordance with requirements of the local plumbing Authority Having Jurisdiction, the National Plumbing Code of Canada (NPC), and the manufacturer’s recommendations.

.7 It is the responsibility of the installer to ensure that all CPVC piping is installed with adequate expansion loops, offsets, and changes in direction, so that the piping and equipment will in no way be strained or distorted by expansion and contraction due

DOMESTIC WATER PIPING 22 11 16 -

Page 8: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

to changes in service temperatures. 1. Consult Engineer of Record for details regarding expansion and contraction

accommodation specific to this project.2. Consult pipe manufacturer for general guidelines regarding expansion and

contraction accommodation.

.8 The need for external pipe insulation shall be determined by the requirements of the local Plumbing or Energy Code and the Engineer of Record. 1. External pipe insulation must always be chemically compatible with the piping

material.

.9 Provide fire-stop systems for all piping, at all penetrations through fire-rated separations tested and listed in accordance with CAN/ULC-S115.1. Fire-stop products must always be chemically compatible with the piping

material.

3.3 VALVE INSTALLATION

.1 Install products in accordance with manufacturer's instructions, approved submittals, and in proper relationship with adjacent construction.1. Valves in horizontal piping to have stems at or above pipe center.2. Valves to be positioned allowing full stem movement.3. Valves with threaded connections to have unions at each piece of equipment.

.1 Arrange to allow easy access, service, maintenance, and equipment removal without system shutdown. Provide separate support where necessary.

4. Valve tags and signage:.1 Comply with Division 22 “Identification for Plumbing Piping and

Equipment" for valve tags, schedules and signs on surfaces concealing valves.

3.4 FIELD QUALITY CONTROL

.1 Installer shall consult with manufacturer’s technical manuals and installation instructions for guidance on support spacing, accommodation of expansion/contraction and proper solvent welding procedure.

3.5 TESTING

.1 Test per authorities having jurisdiction to a maximum pressure of the lowest pressure-rated piping component or appurtenance in the system.

.2 Pressure test underground piping systems before backfilling in accordance with requirements of the National Plumbing Code of Canada (NPC) and the local plumbing Authority Having Jurisdiction.

.3 Pressure test aboveground piping systems in accordance with requirements of the National Plumbing Code of Canada (NPC) and the local plumbing Authority Having Jurisdiction.

.4 CPVC Piping Tests: After all solvent welded joints in the section to be tested have been allowed to cure fully per the manufacturer’s recommendations, fill and pressurize pipeline to test pressure a minimum of 24 hours before testing.1. Use potable water only.

DOMESTIC WATER PIPING 22 11 16 -

Page 9: IPEX AquaRise - 22 11 16 Domestic Water · Web view2016/11/22  · ASME B1.20.1 - Pipe Threads, General Purpose, Inch. ASME B16.5 - Pipe Flanges and Flanged Fittings: NPS 1/2 through

< PROJECT # > < PROJECT NAME > < DATE >

.5 CPVC Hydrostatic Testing, Single-Wall Pressure Piping:1. Hydrostatic testing shall be performed in accordance with manufacturer’s

recommendations.2. Test Pressure: One-and-one-half times (1.5x) the working pressure up to the

maximum pressure of the lowest pressure-rated piping component or appurtenance in the system.DO NOT test with compressed air or other gases.DO NOT test with air-over-water..1 Fully inspect installed piping for evidence of mechanical abuse and/or

suspect joints..2 Slowly fill the pipe section with water, at a velocity of 1.0 ft/s (0.3 m/s)

or less..3 Any entrapped air must be evacuated by venting from the high points.

Do not pressurize at this stage..4 Leave the section for at least one (1) hour to allow equilibrium

temperature to be achieved..5 Visually check the test section for leaks. If clear, check for and remove

any remaining air, and increase pressure up to 50 psi. Do not pressurize further at this stage.

.6 Leave section pressurized for 10 minutes..1 If the pressure drops, inspect for leaks..2 If the pressure remains constant, slowly increase the hydrostatic

pressure to one-and-one-half times (1.5x) the nominal working pressure up to the maximum pressure of the lowest pressure-rated piping component or appurtenance in the system.

.7 Leave the section pressurized for a period not exceeding 1 hour. During this time, the pressure should remain constant..1 If there is a significant drop in static pressure or extended times

are required to achieve pressure, either joint leakage has occurred or air remains in the line..1 Inspect for leakage and if none is apparent, reduce the

pressure and check for trapped air..1 Trapped air must be removed before further testing..2 Repair joint leaks and allow to cure fully before re-

pressurizing.

.6 Prepare test and inspection reports.

3.6 IDENTIFICATION

.1 Comply with requirements for identification specified in Division 22 “Identification for Plumbing Piping and Equipment”.

3.7 PERFORMANCE VERIFICATION

.1 Affix applicable label with directional arrows in accordance with in Division 22 “Identification for Plumbing Piping and Equipment”.

.2 Provide copies of test reports for Commissioning Manuals.

.3 Provide copies of Inspection Reports from the local plumbing Authority Having Jurisdiction.

END OF SECTION

DOMESTIC WATER PIPING 22 11 16 -