47
SULTAN QABOOS UNIVERSITY Oman Eco-House Project Comfort Final Report ENGINEERING FACULTY & STUDENTS TEAM February 2016 www.oman-ecohouse-squ.com Al Khoudh, Muscat 123 SULTANATE OF OMAN

Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

S U L T A N Q A B O O S U N I V E R S I T Y

Oman Eco-House Project

Comfort Final Report

ENGINEERING FACULTY & STUDENTS TEAM

February 2016 www.oman-ecohouse-squ.com

Al Khoudh, Muscat 123

S U L T A N A T E O F O M A N

Page 2: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

i

Executive Summary

This report describes the building systems, the design features, and the implication on comfort.

Several passive and active systems have been installed in the SQU’s ecohouse during phase-1 of

the TRC’s ecofriendly house competition. Passive systems include building form and geometry,

courtyards on south and north sides, small and large windows opening for natural ventilation,

mechanically assisted fans for hybrid ventilation, water fountain in the south courtyard for

evaporation effect, double-shell wall and roof systems, shading systems using vertical and

horizontal canvas, date palm tree shading screens, bio-green wall, and the greenery landscape

that modifies the microclimate of the house. The passive systems have largely helped in reducing

the impact of the outside aggressive and harsh hot climate on indoor environment. Since they

consume energy and require continuous maintenance, installations of complementary active

systems were minimized at the SQU’s ecohuse. Mini-split air conditioning systems are provided

in each space for extreme control flexibility. LED lights are selected as a source of light. They

are installed indoor and outdoor to minimize power consumption, yet at higher lighting output.

For phase-2, mist spray system is proposed and installed on the east and west cavity areas inside

the double shell wall and in the south and north courtyards. This system is intended to reduce the

ambient air temperature by evaporation. Finally, the report outlines and describes the operation

strategies for all systems to maintain comfort at low energy consumption in the ecohouse.

Page 3: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

ii

Table of Contents

Executive Summary ......................................................................................................................... i

List of Figures ................................................................................................................................ iv

List of Tables ................................................................................................................................. vi

1 Building Systems in the SQU Ecohouse ..................................................................................1

1.1 Mist Spray System in the double-shell façade .....................................................................1

1.1.1 Background ..................................................................................................................1

1.1.2 Design of Mist spray system ........................................................................................2

1.1.3 Operation and control strategy .....................................................................................6

1.2 Air conditioning (AC) Systems ...........................................................................................7

1.2.1 AC description .............................................................................................................7

1.2.2 AC modes of operation ................................................................................................8

1.3 Ventilation Systems for cooling, thermal comfort and indoor air quality .........................11

1.3.1 Background ................................................................................................................11

1.3.2 Natural Ventilation.....................................................................................................13

1.3.3 Mechanically-assisted Ventilation .............................................................................15

1.3.4 Mechanical Exhaust fans ...........................................................................................16

1.4 Other systems used for thermal comfort ............................................................................18

1.4.1 Ceiling fans ................................................................................................................18

1.4.2 Water Fountain Heat Exchanger ................................................................................21

1.4.3 Double-Shell system concept .....................................................................................23

1.4.3.1 Double-roof design ............................................................................................23

1.4.3.2 Double-wall design ............................................................................................24

1.4.4 Shading systems attached to the double-shell system................................................25

1.4.4.1 Vertical Canvas ..................................................................................................25

1.4.4.2 Horizontal Canvas ..............................................................................................25

1.4.4.3 Date palm shading screens .................................................................................26

1.5 Building Illumination Systems ..........................................................................................27

1.5.1 Artificial lighting Systems .........................................................................................27

1.5.2 Daylighting Considerations .......................................................................................29

Page 4: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

iii

1.6 Building Acoustical Systems and Noise Control ...............................................................31

2 Operation Strategies for Comfort ...........................................................................................32

2.1 Thermal comfort ................................................................................................................32

2.1.1 Operation strategy #1: Natural ventilation .................................................................32

2.1.2 Operation strategy #2: Natural ventilation + Ceiling fans .........................................33

2.1.3 Operation strategy #3: Natural ventilation + Ceiling fans +mechanical ventilation

fans 33

2.1.4 Operation strategy #4: Mechanical cooling using AC systems .................................34

2.2 Indoor air quality................................................................................................................37

2.3 Visual Comfort...................................................................................................................37

2.3.1 Artificial lighting Systems .........................................................................................37

2.3.2 Daylighting control ....................................................................................................38

2.4 Acoustical comfort .............................................................................................................39

REFERENCES ..............................................................................................................................40

Page 5: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

iv

List of Figures

Figure 1.1 TRNSYS model and results for potential of evaporative cooling in Muscat ...............2

Figure 1.2 The double shell façade system in the SQU Ecohouse and the potential location to

alter the microclimate area ...............................................................................................................3

Figure 1.3 The proposed location of the mist nozzles in the double shell façade ..........................4

Figure 1.4 Schematic diagram showing the components of the proposed Mist system .................5

Figure 1.5 Air conditioning split systems in SQU Ecohouse .........................................................7

Figure 1.6 Main components of the indoor unit of AC split system in the SQU Ecohouse ...........9

Figure 1.7 Available mode of settings and operations of the AC split system in the Ecohouse ..11

Figure 1.8 Climate analysis of Muscat city using TMY weather file from Meteonorm ...............12

Figure 1.9 Passive and active ventilation systems in the ecohouse ..............................................13

Figure 1.10 Natural ventilation concept in SQU ecohouse ...........................................................14

Figure 1.11 Mechanical Ventilation systems in the SQU ecohouse .............................................15

Figure 1.12 Fan model used for ventilation system installed at first floor ...................................16

Figure 1.13 Fan models used for exhaust in the kitchen and toilets .............................................17

Figure 1.14 Fan model used for ventilation installed in the control room at ground floor ...........18

Figure 1.15 Locations of ceiling fans in the SQU ecohouse .........................................................20

Figure 1.16 A ceiling fan model similar to those installed in the SQU ecohouse ........................21

Figure 1.17 Water fountain located in the South courtyard of the house ....................................22

Figure 1.18 Roof shade using PV panels ......................................................................................23

Figure 1.19 Bio-wall system on east and west side of the ground floor level ..............................24

Figure 1.20 Vertical canvas as a shading system on outer wall shell at first floor level ..............25

Figure 1.21 Horizontal canvas as a shading device on outer south wall shell at first floor level .26

Figure 1.22 Date palm shading screens on external walls shell and roof periphery .....................27

Figure 1.23 Lighting layout in ground and first floor of the SQU ecohouse ................................28

Figure 1.24 Candle power distribution curve for the LED lighting luminaire .............................28

Figure 1.25 Daylighting systems in SQU Ecohouse .....................................................................30

Figure 1.26 Outside fence and landscape for noise control in SQU Ecohouse ............................31

Figure 2.1 Operation strategy#1: Natural ventilation ...................................................................33

Figure 2.2 Different operation modes for mechanical and natural ventilation in the family area 34

Page 6: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

v

Figure 2.3 Thermal comfort evaluation in Majles room based on measurements from 1st-8th Sep

2015 36

Page 7: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

vi

List of Tables

Table 1-1 Characteristics and features of the Mist spray Pump ......................................................6

Table 1-2 Schedule of air conditioning system ...............................................................................8

Table 1-3 Measured power consumption of the ceiling fan in the Majles ....................................19

Table 2-1 Schedule of operations for AC systems ........................................................................35

Table 2-2 Target illumination level and the measured lighting level in different spaces .............38

Page 8: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

1

1 Building Systems in the SQU Ecohouse

1.1 Mist Spray System in the double-shell façade

1.1.1 Background

Evaporative cooling using mist spray has been known for reducing the ambient air in hot

climates. Although Muscat’s climate is known to be humid in summer, evaporative cooling can

potentially be used in some summer months. This is true in outskirt of Muscat especially in the

SQU’s campus where it is located few kilometers away from the coastline. The climate in this

area tends to be dryer than the coastal area due to the close vicinity of the mountains on the south

of Muscat city and close to the interior side of Oman. The potential of evaporative cooling in

Muscat city was evaluated using a weather file, a TMY2 format, generated by the Meteonorm

software [1]. This weather file was utilized in TRNSYS [2]. TYPE506, a component for

evaporative cooling device, was subsequently used within TRNSYS simulation package. The

implementation in TRNSYS and the results are shown in Figure 1.1. Regardless of air flow, the

ambient air temperature can be reduced by as much as 10 K in a hot day if the saturation

efficiency is 90%. This approximation methodology shows that there is a potential in using

evaporative cooling in Muscat city.

Page 9: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

2

a) TRNSYS model

b) The correlation between inlet and outlet air temperature across the evaporative cooling

device

Figure 1.1 TRNSYS model and results for potential of evaporative cooling in Muscat

1.1.2 Design of Mist spray system

The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is

featured with shaded courtyards on south and north side. Using mist system, this area can be

utilized to alter the microclimate of the house as illustrated in Figure 1.2.

y = 0.5441x + 9.6092R² = 0.891

0

5

10

15

20

25

30

35

40

0 10 20 30 40 50

Outle

t Tem

pera

ture

[°C]

Inlet Temperature [°C]

Page 10: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

3

Figure 1.2 The double shell façade system in the SQU Ecohouse and the potential location to

alter the microclimate area

Figure 1.3 shows the location of the mist nozzles in the double shell façade. The nozzles are of a

size of 0.2 mm spaced between 0.80 to 1.0 meters. It is also important to mention that each

outdoor condenser unit will have one nozzle to spray water at the inlet hot air. The inlet air

temperature will be reduced and subsequently the coefficient of performance (COP) of the unit

will increase.

North

Courtyard

Microclimate Area

Courtyard

Page 11: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

4

Figure 1.3 The proposed location of the mist nozzles in the double shell façade

Figure 1.4 shows the schematic plan of the proposed mist system in the SQU’s Ecohouse. The

water from the main city line can be used directly without treatment provided that appropriate

filters are utlized. Mist pump is needed to increase the water pressure to 70-105 Bar. The

maximum total daily water consumption is estimated to be 1864 gal (i.e., 9.8 l/min x 12 hr x 60

min x 0.2641721 gal/l). The characteristics and the main features of the mist system are provided

in Table 1-1. The mist pump can work up to a maximum of 12 hours per day and can be

controlled by a scheduled intermittent timer or using temperature/humidity sensor through

embedded controller. The temperature/humidity sensor will be installed in the south courtyard.

Mist Nozzle

North

Courtyard

Courtyard

Page 12: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

5

a) Schematic of the mist system

b) Mist distribution from a 0.2 mm nozzle

Figure 1.4 Schematic diagram showing the components of the proposed Mist system

Page 13: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

6

Table 1-1 Characteristics and features of the Mist spray Pump

Model E216

Pressure (Bar) 70-105

Nozzles Number (0.2 mm) 20-150

Pump SIMMM AXA

Min Flow Rate (l/min) 1.9

Max Flow Rate (l/min) 9.8

Motor Speed (RPM) 900

Voltage (Volts) 230/50Hz

Power (kW) 0.92

Max daily use (hours) 12

1.1.3 Operation and control strategy

Due to the cost implication, one temperature/humidity sensor is installed in the south courtyard.

This sensor controls the operation of the mist pump based on the humidity/temperature values in

the courtyard. The pump can work up to a maximum of 12 hours in a day. The temperature rises

during the day time at which the relative humidity is low. During this time, the mist system is

utilized to reduce the microclimate environment of the house. The pump will be controlled to

Page 14: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

7

regulate the water flow to the nozzles. No major intervention is expected from the occupants

except switching on/off the electrical switch in the pump room.

1.2 Air conditioning (AC) Systems

1.2.1 AC description

The SQU Ecohouse is divided into 10 thermal zones based on many factors such as the

occupant’s activity, orientation, the level of system control as illustrated in Figure 1.5.

a) Ground floor indoor units b) First floor indoor units

c) Roof plan showing the corresponding

outdoor units

d) Indoor and outdoor units connection in a

typical zone

Figure 1.5 Air conditioning split systems in SQU Ecohouse

1

2

3

4

56

7

8

910

1

6

2

7

8

4

10

9

3

5

Page 15: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

8

Each zone is equipped with 1 Ton split system except the familyroom where 1.5 tons of air

conditioning is installed as summarized in Table 1-2. The COP of the split AC system is

calculated using the following equation:

Equation 1-1

Table 1-2 Schedule of air conditioning system

Location Thermal

Zone

Cooling Capacity

[kW]

Model COP

Majles (GF) 1 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Dining Area (GF) 2 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Family Area (GF) 3 5.28 CS/CU PC18MKF 2.65-2.58

Guest Room (GF) 4 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Kitchen(GF) 5 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Master Bedroom (FF) 6 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Living Room (FF) 7 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Girls Room (FF) 8 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Lobby Area (FF) 9 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Boys Room (FF) 10 3.52-3.54 CS/CU PC12MKF 2.85-2.91

Notes: GF: ground floor, FF: First floor, All units are split AC Manufactured by Panasonic,

Malaysia

1.2.2 AC modes of operation

All AC split systems are controlled using an ON/Off controller. A typical schematic of Panasanic

indoor unit is illustrated in Figure 1.6. The occupants can use the wall-mounted controller to set

the desired operation mode. For the controller to work properly, it has to be within 8 meters

distance from the indoor unit. To maintain acceptable indoor air quality, air filters are to be

cleaned every two weeks. The Panasanic AC split system in SQU ecohouse has several modes of

operation. When ECONAVI mode of operation is selected, a human activity sensor is activated

and the source of heat inside the space is tracked. This will maintain the indoor air temperature to

the setpoint temperature. When no source of heat is detected, the air temperature will gradually

increase to 2°C above the setpoint temperature, subsequently saving energy consumption. If

Page 16: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

9

thermal comfort is of importance, the occupant can select the AutoComfort mode. A maximum

thermal comfort level will be maintained. More settings and configurations are fully described as

illustrated in Figure 1.7.

Figure 1.6 Main components of the indoor unit of AC split system in the SQU Ecohouse

Page 17: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

10

Page 18: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

11

Figure 1.7 Available mode of settings and operations of the AC split system in the Ecohouse

1.3 Ventilation Systems for cooling, thermal comfort and indoor air quality

1.3.1 Background

Using the free outside cooled air has an impact on thermal comfort, energy consumption and

indoor air quality. When adaptive thermal comfort criteria is used, natural ventilation can be

utilized for 29% of the time for thermal comfort (i.e., 2576 hrs of the 8760 hrs) for Muscat city

as show in Figure 1.8. The figure shows that in almost every month, outside air can be used. The

utilization of outside air for natural ventilation is however a challenging task for this climate.

Page 19: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

12

a) Dry bulb Temperature Versus Relative humidity using adaptive thermal comfort criteria

b) Design Strategies when using adaptive thermal comfort criteria

Figure 1.8 Climate analysis of Muscat city using TMY weather file from Meteonorm

Page 20: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

13

The SQU ecohouse provides a variety of passive and active means for full harvesting of outside

cooled air for cooling purposes, maintaining the thermal comfort and providing an acceptable

indoor air quality as shown in Figure 1.9. To meet the ventilation requirement of ASHRAE 62.2

(Table 4.1a of 2013 version), the SQU’s ecohouse needs between 135-150 CFM of fresh air [3].

This rate can easily be achieved by the current passive and active systems in the ecohouse. The

following sections provide further details about these passive and active systems.

a) Ground Floor ventilation systems b) First Floor ventilation systems

Figure 1.9 Passive and active ventilation systems in the ecohouse

1.3.2 Natural Ventilation

In the SQU’s ecohouse, natural ventilation can be achieved using windows and doors that are

located in strategic locations. Cross natural ventilation is promoted due to differential pressure

between windward and leeward sides that can be created by closing and opening windows and

doors at ground and first floor. Lessons are learned from traditional Omani architecture in which

natural ventilation was achieved by long vertical windows that contained lower openings to inlet

Exhaust Fans

Ventilation Fans

Ceiling Fans

Windows

Doors

Exhaust Fans

Ventilation Fans

Ceiling Fans

Windows

Doors

Page 21: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

14

cool breeze, and upper openings to exhaust hot air. The windows and doors are located on North

and South walls that respond to day and night variations of Muscat prevailing wind and sea

breeze as previously shown in Figure 1.9. Outside landscape is designed so that outside air is

directed toward the house as shown in Figure 1.10.

Figure 1.10 Natural ventilation concept in SQU ecohouse

Page 22: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

15

1.3.3 Mechanically-assisted Ventilation

When the outside air can’t be driven naturally using passive means, the ecohouse has 5

ventilation fans on the first floor to promote air flow as clearly shown in Figure 1.9 and Figure

1.11. These fans are mainly installed to drive the air flow in the family area located in the ground

floor. As per the manufacturer data sheet provided in Figure 1.12 , each fan can provide a total

flow rate of 550 CFM with a fixed speed. Since both ground and first floor are connected

through the void in the core of the house, the fans serve a total volume of 345.8 m3 (floor

area=52 m2, height for the two floors= 6.65 m). All five fans can provide a total of 13.5 ACH

(i.e., every fan can achieve 2.7 ACH).

North Courtyard South Courtyard

Cross Section Inside photo

Figure 1.11 Mechanical Ventilation systems in the SQU ecohouse

Ventilation fans Ventilation fans

Ventilation fans

Page 23: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

16

Model: 30 ALFT (50 Hz) used

for ventilation located at first

floor

Figure 1.12 Fan model used for ventilation system installed at first floor

1.3.4 Mechanical Exhaust fans

Indoor air quality is an important factor for the residents. One source of odors is generated in

toilets and kitchen. ASHRAE 62.2 [3] mandates acceptable ventilation rates for residential

buildings. According to the ASHRAE standard, local mechanical exhaust shall be installed in

each kitchen and bathroom. This local exhaust can either be based on a demand-controlled which

should be operated as needed by the occupants or should be operated continuously. The local

exhaust system at the SQU ecohouse is designed to be operated by occupants as needed.

Page 24: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

17

According to ASHRAE 62.2 (Table 5.1 demand-controlled local ventilation), an air flow of 100

CFM (50 L/s) and 50 CFM (25 L/s) for kitchen and bathroom should be provided respectively.

All toilets and the kitchen in the SQU ecohouse are equipped with exhaust fans as shown in

Figure 1.13. The kitchen and all first floor toilets are provided with wall mounted fans; model

20AUHT-50 Hz. Each fan delivers a flow rate of 341 CFM. All ground floor toilets are using

glass mounted fans with model 20WUD-50Hz. Each fan provides 212 CFM. Therefore, all local

exhaust ventilation provided by these fans meet the air flow rate recommended by ASHRAE

62.2 for residential buildings.

Wall mounted: 20AUHT-50 Hz

(Kitchen and first floor toilets)

Glass mounted model: 20WUD-

50Hz (ground floor toilets)

Figure 1.13 Fan models used for exhaust in the kitchen and toilets

The control room in the ground floor is provided with fan model 30KQT 50 Hz that delivers 718

CFM as shown in Figure 1.14. The distribution panel board (DP), PV invertor and data

acquisition system (DAS) are all located in this room. A total of 62 ACH can be provided by this

Page 25: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

18

fan which deemed satisfactory (i.e., 3.2 m height x 1.8 m width x 3.4 m length = 19.584 m3=

691.6024 ft3, flow rate= 718 CFM, ACH=718(ft

3/min)/691.6024(ft

3) x (60 min/hr) = 62.3 ACH).

Model: 30KQT

Control room

Figure 1.14 Fan model used for ventilation installed in the control room at ground floor

1.4 Other systems used for thermal comfort

Thermal comfort and indoor air quality can also be influenced by many other systems installed in

the SQU’s ecohouse. Examples include ceiling fans, outdoor water fountain in the south

courtyard, shading system, double shell systems, and green bio-wall. The following sections

provide further details about these systems.

1.4.1 Ceiling fans

Ceiling fans are very common in residential buildings in Oman. They are installed in the ceiling

of every space. The speed of the ceiling fan can be controlled using a wall mounted electronic

regulator where occupants can manually select the desirable speed. The fans provide a good

means to mix room air and as well as increases the air speed. Since the air velocity is one

important factor for thermal comfort, the thermal comfort can be achieved at higher temperature.

Page 26: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

19

For the SQU’s ecohouse, the ceiling fans are installed in Majles, Dining room, Kitchen, Guest

room, all bedrooms on the first floor, and the living room in the first floor as shown in Figure

1.15. The ceiling fans have 5 speeds where the number of rotation varies according to the

selected speed. The ceiling fan model is AX56XK from KDK. A similar model type (M56XG 50

HZ) is found from the KDK website and shown in Figure 1.16 for illustration purposes. The

power consumption of the installed model was measured using the real time data acquisition

system as shown in Table 1-3 which is closer to the model provided as per Figure 1.16.

Table 1-3 Measured power consumption of the ceiling fan in the Majles

Fan Speed Electrical Power (Watts) Difference between speeds (Watts)

1 (Low) 18

2 29 11

3 42 13

4 56 14

5 (High) 73 17

Page 27: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

20

a) Ceiling fans in Ground Floor

b) Ceiling fans in First Floor

Figure 1.15 Locations of ceiling fans in the SQU ecohouse

Ceiling Fans

Ceiling Fans

Page 28: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

21

Figure 1.16 A ceiling fan model similar to those installed in the SQU ecohouse

1.4.2 Water Fountain Heat Exchanger

Heat exchanger water fountain is located in South courtyard as shown in Figure 1.17. It has a

deep water reservoir that dissipates heat from water to deep soil. The cooled water is pumped up

to the fountain to cool air that flows into lower inlets of the house.

Page 29: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

22

Figure 1.17 Water fountain located in the South courtyard of the house

Water Fountain

North

Page 30: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

23

1.4.3 Double-Shell system concept

External surfaces of buildings get heated due to the combination of air temperature and solar

radiation. For example, when the surface temperature in the shade is 40°C, the exposed surface

to the sun could be few degrees. These extra heat could add considerable thermal load to the

building with consequences of added AC load and cost. Conventional design concepts are to

shade window to prevent sun rays from penetration through glass, while the concept double-shell

system is to shade all the building. A secondary light shell wraps around the house providing full

shade of all external surfaces (i.e., roof and walls). It intercepts solar radiation and removes its

thermal load before it reaches the building. The outer shell must be of light weight material, and

air currents in the interim space are maximized to avoid stagnation of hot air.

1.4.3.1 Double-roof design

The roof is shaded by a shell lifted up from the roof with 60cm cavity space, and the upper shell

comprises Photovoltaic (PV) panels tilted at 23.5° oriented towards the South to maximize the

received solar radiation. This tilt could also help to scoop prevailing North-Easterly wind and

directed towards roof cavity to maximizing cooling effect. Wooden lattice are inserted between

PV panels to complement roof shading, and to be used as walkways for maintenance as shown in

Figure 1.18.

a) Snapshot on the wooden walkway b) Snapshot from the roof cavity below the PVs

Figure 1.18 Roof shade using PV panels

Page 31: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

24

1.4.3.2 Double-wall design

Walls are surrounded and shaded by date palm wood screens, canvas vertical strips, and climber

plant trellises. Two types of spaces are designed in this Eco-house. On the East and West are 80

cm wide colonnades. The South space extends into lively courtyard surrounded by plants and

flowers, with a central fountain that cools the space and introduces cool breeze to the living

room. It is shaded like the above plus a roof plate extended southwards. Climber plants on

trellises surround East and West colonnades providing full shade all year round. The plants climb

on vertical cords to a height of one floor only creating a bio-wall system as shown in Figure

1.19.

Figure 1.19 Bio-wall system on east and west side of the ground floor level

Page 32: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

25

1.4.4 Shading systems attached to the double-shell system

1.4.4.1 Vertical Canvas

Canvas strips are used as vertical shading devices on the East and West colonnades. But they are

floppy and they get wing flutter. They were therefore stretched vertically in order to gain

maximum stability as illustrated in Figure 1.20. The end of each strip is wrapped around a

galvanized hollow metal bar. A screw bar connects the middle of each bar to support channel

being anchored to the beams. The screw is tightened by nuts into final stretching positions.

Figure 1.20 Vertical canvas as a shading system on outer wall shell at first floor level

1.4.4.2 Horizontal Canvas

Canvas strips are use as horizontal shading devices to protect South courtyard as illustrated in

Figure 1.21. Horizontal canvas strips in horizontal position sag and cannot be used as horizontal

shading devices. A curved galvanized hollow tube is therefore introduced at which the end of

each strip is wrapped around. Two screw bars connect the curved tube it to support anchor which

in turn is anchored to the columns. The screws are tightened by nuts into final stretching

Page 33: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

26

positions. Three caved tubes are also introduced along the horizontal strip to maintain its

curvature.

Figure 1.21 Horizontal canvas as a shading device on outer south wall shell at first floor level

1.4.4.3 Date palm shading screens

Date palm wood screens are applied at the external wall shell and roof periphery as shown in

Figure 1.22. Local craftsmen were employed for on-site manufacturing and construction of these

screens. Research is to be conducted to treat date palm wood with protective materials to

improve durability. Study is conducted on accumulated heritage of handcraft of date palm

products to develop it into modern production processes in order to obtain economically feasible

products and promote them as viable sustainable building material.

Page 34: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

27

Figure 1.22 Date palm shading screens on external walls shell and roof periphery

1.5 Building Illumination Systems

1.5.1 Artificial lighting Systems

The lights in the SQU’s Ecohouse are of LED type; model Portland 15W LED IP54 white Opal

(NPO15LED/WH/O/850), from NVC lighting UK. Each lighting luminaire produces 1040

lumens and the color rendering index (CRI) is 80% with a nominal correlated color temperature

(CCT) of 5000 K (measured CCT is 4134 k). Each LED lighting fixture has a 64 PC LED light.

The lights can be switched on/off using wall mounted switches in each space as shown in Figure

1.23. The candlepower distribution curve for this lighting luminaire is shown in Figure 1.24.

Page 35: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

28

a) Ground floor b) First floor

Figure 1.23 Lighting layout in ground and first floor of the SQU ecohouse

Figure 1.24 Candle power distribution curve for the LED lighting luminaire

Page 36: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

29

1.5.2 Daylighting Considerations

Daylighting can better be introduced to the indoor space in a diffuse form. No shading is

provided on north side of the house allowing the diffuse north light to enter the spaces on this

side easily. On other sides of the house, the double skin façade of the SQU’s ecohouse is

rationally designed to block all direct sunlight. The shading systems attached to the double skin

façade (vertical, horizontal canvas, GRC screens, bio-wall, and date palm screens) allow the

direct and diffuse light to penetrate into the south courtyard, east and west cavities. The lights are

then introduced to the interior spaces through clear glass windows and glass doors distributed in

all zones as shown in Figure 1.25. Moveable cloth curtains are provided in all transparent

envelope system where occupants can manually open and close them as needed.

Page 37: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

30

a) Windows and glass doors in ground floor

b) Windows and glass doors in first floor

Figure 1.25 Daylighting systems in SQU Ecohouse

Windows

Glazed Doors

Windows

Glazed Doors

Page 38: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

31

1.6 Building Acoustical Systems and Noise Control

In interior spaces, is generated from different sources such as equipment and appliances. The

ecohouse is designed with interior walls that are composed of 200 mm hollow block. In addition,

thick wooden doors are used in interior spaces. Inside the rooms, wide closets are attached to the

exterior walls providing another means for noise mitigation. Main source of noise comes from

mechanical and electrical systems. The systems are located away and isolated from the quite

area. For example, the noisy compressor units of the air conditioning systems are located on the

roof. Fountain pumps in the south courtyard are located in a special slump below the ground.

Special room is designed for mist pump system. Double skin façade in the SQU ecohouse is also

a helpful design feature to mitigate the propagation of exterior noise. Climbing trees and the soft

canvas on the exterior side of the double-shell can absorb significant amount of noise. In

addition, the ecohouse is surrounded by a concrete block fence of a 2 m height. This fence is

helpful to reduce the noise that comes from the nearby road. Tall trees are planted in the

landscape of the ecohouse as shown in Figure 1.26. These trees will absorb significant amount

of noise that comes from exterior environment.

Figure 1.26 Outside fence and landscape for noise control in SQU Ecohouse

Page 39: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

32

2 Operation Strategies for Comfort

2.1 Thermal comfort

Thermal comfort is a basic requirement for occupants to perform their day to day activities.

According to ASHRAE 55, thermal comfort is defined as “that condition of mind which

expresses satisfaction with the thermal environment” [4]. It is influenced by many variables that

can be divided into environmental parameters: air temperature, mean radiant temperature,

humidity, relative air velocity and personal parameters: clothing and activity level [5]. Proper

combinations of these variables have to be sought to provide a thermally comfortable

environment. Several strategies using passive and active systems are available to maintain

thermal comfort. However, the thermal comfort criteria will change based on what system or

combination of systems is used. The following sections provide further details on operation

strategies to achieve thermal comfort.

2.1.1 Operation strategy #1: Natural ventilation

Natural ventilation can provide outside free cooled air that flushes and dissipates the internal

generated heat. Cross ventilation can be achieved by opening exterior and interior doors and

windows in the house. Under this scenario, the thermal conditions can be regulated primarily by

the occupants through opening and closing of doors and windows. All spaces in the house are

equipped with operable windows which can primarily be regulated by occupants. If occupants

are uncomfortable, they should open the windows and doors at both north and south side for

cross ventilation as shown in Figure 2.1.

Page 40: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

33

Figure 2.1 Operation strategy#1: Natural ventilation

2.1.2 Operation strategy #2: Natural ventilation + Ceiling fans

When operation strategy #1 is not sufficient for thermal comfort, operation strategy #2 using

ceiling fans can alternatively be followed by occupants. The ceiling fans are provided in every

space in the house except in the family room at ground floor. Occupants can select between 1-5

speed levels of ceiling fans. This strategy will alter the air velocity inside the space and therefore

thermal comfort is enhanced.

2.1.3 Operation strategy #3: Natural ventilation + Ceiling fans +mechanical

ventilation fans

Mechanically assisted fans installed on the upper level (i.e., first floor) can be operated to create

negative pressure inside the house and promote the air flow movement. Occupants can primarily

operate the mechanical fans and open/close windows based on the wind direction, speed and the

desirable thermal comfort level. Figure 2.2 illustrates the concept of this strategy where

occupants have to select which mode is favorable as per the weather conditions.

Courtyard

North

Page 41: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

34

a) Natural ventilation only b) Mechanical and natural ventilation are both

on from both sides

c) Mechanical ventilation on south and

natural ventilation on north

d) Mechanical ventilation on north and natural

ventilation on south

Figure 2.2 Different operation modes for mechanical and natural ventilation in the family area

2.1.4 Operation strategy #4: Mechanical cooling using AC systems

In hot climates, air conditioning systems are commonly used by occupants to achieve thermal

comfort. AC systems can be used to manipulate few of the environmental parameters; air

temperature, humidity and air velocity. Ten AC units, one in each space, manufactured by

Panasonic are provided for extreme control flexibility in the SQU’s ecohouse. Different

operation modes are available as described previously in section 1.2.2. In order to define the

optimal operation mode to maintain the desirable thermal comfort (-0.5<PMV<+0.5), site

measurements were performed in the Majles area from 1st -8

th of September 2015 using HD32.1

Thermal Microclimate instrument from Delta OHM as illustrated in Figure 2.3 (a) [6]. The

Courtyard

on

on

Courtyard

off on

off

Courtyard

offon

off

Courtyard

Page 42: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

35

measurements for air temperature, relative humidity, air velocity and globe temperature were

taken at 15 minutes time interval for this week interval. Predicted Mean Vote (PMV) values were

calculated based on a clothing level of 0.5 clo and various activity levels, typical domestic values

for tropical climate similar to that experienced in Oman is provided by Mallick as depicted in

Figure 2.3 (b) [7].

The room air temperature was set at 24°C, cool mode was selected (refer to Figure 1.7 for

available modes), and the indoor unit fan was set to single speed by utilizing the wall mounted

controller. In all cases, the ceiling fan was operated at 1st speed to mix the air inside the space.

The results of PMV are shown in Figure 2.3 (c). It is clear from the figure that as the activity

level increases above 1.2 MET (i.e., to 1.5 MET) or decreases below 1.2 MET (i.e., to 1.0 MET),

the thermal comfort (-0.5<PMV<+0.5) is slightly out of range. The occupants in this case should

change the temperature setpoint or/and the ceiling fan speeds as desirable until thermal comfort

is achieved. Clothing level could also be reduced or increased as a way to achieve thermal

comfort. This strategy should be used throughout the house. It is also found through trial and

error that not all ACs in the house are necessary but ceiling fans are needed at 1st speed setting.

Table 2-1 provides the schedule of operations and conditions to operate the ACs in the ecohouse.

Table 2-1 Schedule of operations for AC systems

Location Thermal Zone Operation

[yes or no]

Comments

Majles (GF) 1 Yes When Majles/dining and/or living

rooms are occupied or under testing.

Dining Area (GF) 2 No When needed only.

Family Area (GF) 3 No When needed only.

Guest Room (GF) 4 Yes When occupied or under testing.

Kitchen(GF) 5 Yes When occupied or under testing.

Master Bedroom (FF) 6 Yes When occupied or under testing.

Living Room (FF) 7 No When needed only.

Girls Room (FF) 8 Yes When occupied or under testing.

Lobby Area (FF) 9 Yes When occupied or under testing.

Boys Room (FF) 10 Yes When occupied or under testing.

Page 43: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

36

a) HD32.1 Thermal Microclimate

instrument from Delta OHM

b) Typical domestic activity and clothing values [7]

c) PMV calculations for a clothing level of 0.5 CLO and various activity levels

Figure 2.3 Thermal comfort evaluation in Majles room based on measurements from 1st-8th Sep

2015

0 96 192 288 384 480 576-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

Time [minutes]

PMV

[-]

Activity Level=1.5 MET

Activity Level=2.0 MET

Activity Level=1.2 MET

Activity Level=1.0 MET

Page 44: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

37

2.2 Indoor air quality

Indoor air quality is an important factor for occupants’ health and wellbeing. There are many

sources of contaminants inside the house. Occupants produce moisture and CO2 through

inhalation and exhalation. Cooking produces many gases and contaminants. Toilets are also

another source of contaminants. Due to the construction quality, fresh outside air can be

introduced through air infiltration to maintain good indoor air quality. Although air infiltration is

not measured, it is expected that a value from 0.35 to 0.5 ACH of infiltration is possible. In

addition to uncontrolled fresh air entrainment, controlled air ventilation can be supplied through

either natural or mechanical ventilation or a combination of both as described previously in

section 1.3. Exhaust fans are installed in all toilets and kitchen at source generation. The fans

should be operated when these spaces are occupied or when specific activity is in operation.

2.3 Visual Comfort

2.3.1 Artificial lighting Systems

Illumination is important for occupant’s visual task. IESNA (Illuminating Engineering Society of

North America) has a set of requirements for building illumination. Illumination level generated

by artificial ambient lights has been measured at 60 cm x 60 cm grids in all spaces at 0.8 m

above finished floor (AFF) as shown in Table 2-2. In general, the ambient lights using the

ceiling LED luminaires meet the target illumination level mandated by IESNA. However, the

shaded cells in Table 2-2 shows that these spaces need task lighting to meet the IESNA target

level. Ceiling LED lights shall be operated when spaces are occupied. Task lights should be

operated when specific task is done in the space to complement the ambient lighting.

Page 45: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

38

Table 2-2 Target illumination level and the measured lighting level in different spaces

Floor Space name Target Illumination Level

according to IES 10th Edition

Table 33.2 [Lux]

Average measured

Illumination at 0.80

m AFF [Lux]

Window

area [m2]

Gro

un

d F

loo

r

Majlis 100 at 1.5 m AFF (similar to

family room) 120 1.8

Dining room Formal: 50 at table plane

Informal: 100 at table plane 96 1.2

Family room 100 at 1.5 m AFF 100 4.625

Guest room General: 50 at 1.2 m AFF

Bedhead=200 168 1.2

Guest

Bathroom

Showers/Tubs=50

Toilets and Bidets=100 at top of

plumbing fixture

136 0.263

Kitchen

General: 50 at 1.5 m AFF

Counters= 500

Sink, cooktop= 300

65 1.2

Control room Storage frequent use: 50 at 1.2 m

AFF 144 0.6

Majles

Bathroom

Showers/Tubs=50

Toilets and Bidets=100 at top of

plumbing fixture

180 0.263

Staircase 50 at treads 79 0.6

Fir

st f

loo

r

Master

Bedroom

General: 50 at 1.2 m AFF

Bedhead=200 Not measured

Lobby Circulation Corridors: 30 at 1.5

m AFF 88 0.96

Living room 30 at 1.2 m AFF 62 1.2

Girls Bedroom General: 50 at 1.2 m AFF

Bedhead=200 62 1.2

Boys Bedroom General: 50 at 1.2 m AFF

Bedhead=200 67 1.86

Bathroom

Showers/Tubs=50

Toilets and Bidets=100 at top of

plumbing fixture

71 0.263

2.3.2 Daylighting control

In addition to artificial lighting, daylighting can be utilized as a complementary lighting source

when cloth curtains are fully open. During the measurements performed in November 2015,

daylighting was able to provide an extra average value of 40 lux.

Page 46: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

39

2.4 Acoustical comfort

Appliances and electrical equipment can be a source of noise. The possible sources of noise in

the ecohouse are the PV invertor in the control room, exhaust and mechanical ventilations, fans

of the indoor units of AC, water fountains and water pumps. While the noises from many of

these systems are typical and unavoidable, the noise from the PV invertor in the control room is

significant and can be reduced by closing the control room’s door. The door of the control room

shall always be kept closed. Exterior doors and windows shall be kept close if the source of noise

is from exterior environment.

Page 47: Introduction to Building Physics - Comfort Final Report · 2016. 2. 28. · The SQU’s ecohouse is equipped with a double shell façade on east and west sides. The house is featured

40

REFERENCES

[1] Meteonorm 7, URL: http://meteonorm.com/, [Accessed: May/23/2015], (2015).

[2] Thermal Energy System Specialists LLC -TESS Libraries - Individual Component Libraries,

URL: http://www.trnsys.com/tess-libraries/individual-components.php [Accessed:

October/23/2012].

[3] ASHRAE, Ashrae Standard 62.2-2013: Ventilation and Acceptable Indoor Air Quality in

Low-rise, Ashrae, 2013.

[4] American Society of Heating Refrigerating Air-Conditioning Engineers (ASHRAE), A.N.S.I.

(ANSI), Thermal Environmental Conditions for Human Occupancy, American Society of

Heating, Refrigerating and Air-Conditioning Engineers, 2004.

[5] P.O. Fanger, Thermal comfort: analysis and applications in environmental engineering,

McGraw-Hill, 1970.

[6] Delta OHM, URL: http://www.deltaohm.com/ver2012/download/HD32.1_D_uk.pdf,

[Accessed: Jan/30/2016], (2016).

[7] F.H. Mallick, Thermal comfort and building design in the tropical climates, Energy and

Buildings, 23 (3) (1996) 161-167.