6
1600AF MCCB For power distribution - The highest breaking capacity - Optimum coordination technique (Cascading & discrimination) - Powerful engineering tools For protection of motor & its control device - Optimal overload protection For controlling and disconnecting circuits For extensive applications - Wide range of optimized auxiliaries and accessories Introduction of New Product 1600AF, 3&4pole Icu: 50/70/150kA Ics: 100(75)%Icu Icw: 25kA/1s Ui: 1000V Uimp: 8kV Cat. A, B N, A, P, S type L / S / I / G Thermal, Ammeter, Power, Harmonic Outer: 16 type Inner: 5 type Easy connection MCCB OCR Accessory

Introduction of New Product - Elinexmccb.pdfSusol 1600AF MCCB / October.2010 Printed in korea STAFF 4- 5.5 or M5 3P 4P 199 4- 5.5 or M5 269 CL CL CL CL CL CL CL CL CL 199 210 212 258

  • Upload
    others

  • View
    13

  • Download
    0

Embed Size (px)

Citation preview

  • 1600AF MCCB

    ●●For power distribution- The highest breaking capacity- Optimum coordination technique (Cascading & discrimination)- Powerful engineering tools

    ●●For protection of motor & its control device- Optimal overload protection

    ●●For controlling and disconnecting circuits

    ●●For extensive applications- Wide range of optimized auxiliaries and accessories

    Introduction of New Product

    ●1600AF, 3&4pole

    ● Icu: 50/70/150kA

    ● Ics: 100(75)%Icu

    ● Icw: 25kA/1s

    ●Ui: 1000V

    ●Uimp: 8kV

    ● Cat. A, B

    ●N, A, P, S type

    ●L / S / I / G

    ●Thermal, Ammeter,

    Power, Harmonic

    ●Outer: 16 type

    ● Inner: 5 type

    ●Easy connection

    MCCB OCR Accessory

  • TS1600 Rating

    Ordering

    Ampere frame

    1000

    TS 12501600

    Type

    N NormalH HighL Current Limiting

    NASwitch-disconnector

    Rated current

    800A

    1000A

    1250A

    1600A

    Poles

    3P 3Pole4P 4Pole

    Connection type

    - Standard

    REAR RearConnection

    Trip relay

    N NormalA AmmeterP Power meterS Supreme meter

    ■■MCCB

    N phase way (4Pole)

    L N-R-S-TR R-ST-N

    TS1600 1600AN A 3P - -

    Type TS1000 TS1250 TS1600

    Ampere frame 1000 1250 1600

    Pole 3, 4 3, 4 3, 4

    Rated current,(A) In -5~40°C 800, 1000 1250 1600

    50°C 800, 1000 1250 1560

    65°C 800, 1000 1240 1420

    Rated insulation voltage, (V) Ui 1000 1000 1000

    Rated impulse withstand voltage, (kV) Uimp 8 8 8

    Rated operational Ue AC50/60Hz 690 690 690

    voltage, (V) DC - - -

    Rated short-circuit breaking capacity N H L N H N H

    IEC60947-2 Rated ultimate short-circuit AC50/60Hz 220/240V 55 75 200 55 75 55 75

    (sym) breaking capacity, (kA) (Icu) 380/415V 50 70 150 50 70 50 70

    440V/460V 50 65 130 50 65 50 65

    480/500V 40 50 100 40 50 40 50

    660/690V 35 45 50 35 45 35 45

    DC 250V 2P - - - - - - -

    500V 2P - - - - - - -

    750V 3P - - - - - - -

    Rated service breaking capacity, %Icu100% 75% 100% 100% 75% 100% 75%

    (Ics)

    Rated short-circuit making capacity, AC50/60Hz 1s 25 25 12 25 25 25 25

    (kA) (Icw) 3s - - - - - -

    Overriding instantaneous protection kA peak 50 50 - 50 50 50 50

    Isolation ○ ○ ○

    Category B B A B B B B

    Mechanical life (operations) 10000 10000 10000

    (Life cycle) Electrical life (operations) 440V In/2 6000 6000 4000 5000 5000 5000 5000

    In 5000 5000 3000 4000 4000 2000 2000

    690V In/2 4000 4000 3000 3000 3000 2000 2000

    In 2000 2000 2000 2000 2000 1000 1000

    Pollution degree 3 3 3

    Dimension (mm) a (3p/4p) 210/280

    b 327

    c1 155.5

    c2 162.7

    d 185.3

    Weight (kg) 3P 13

    4P 16.8

    a

    b

    dc2c1

  • Trip relay types

    Classification N type A type P type S type

    Externals

    Current �L / S / I / G / Thermal �L / S / I / G / Thermal �L / S / I / G / Thermal(Continuous) �P typeprotection �ZSI(Protective coordination) �ZSI(Protective coordination)

    � Earth leakage (Option) �Earth leakage(Option) �P type

    Other�Over/Under current

    protection�Over/Under frequency

    �Unbalance(Voltage/Current)

    �Reverse power

    �Current (R / S / T / N) �3 Phase Voltage/Current �3 Phase Voltage/Current

    RMS/Vector RMS/Vector

    �Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase)

    �Energy(Positive/Negative) �Energy(Positive/Negative)

    Measurement �Frequency, Demand �Frequency, Demandfunction �Voltage/Current harmonics

    (1st~63th)

    �3 Phase Waveforms

    �THD, TDD, K-Factor

    Fine adjustment�Fine adjustment for long/short �P type

    time delay/instantaneous/ ground

    �Overload protection relays �P type

    Pre Trip Alarm: DO (Alarm)

    (Ground fault is not available

    when using Pre trip alarm)

    Digital Output�3DO (Fixed) �3DO (Programmable) �P type

    �L, S/I, G Alarm �Trip, Alarm, General

    IDMTL setting�Compliance with IEC60255-3 �P type

    SIT, VIT, EIT, DT

    Communication�Modbus/RS-485 �Modbus / RS-485 �Modbus / RS-485

    �Profibus-DP �Profibus-DP �Profibus-DP

    �Self Power �Self Power �AC/DC 100~250V �AC/DC 100~250V

    - Power source works over 30% - Power source works over 30% �DC 24~60V �DC 24~60V

    current of In (one pole) current of In (one pole)

    Power supply - External power source arerequired for comm.

    �AC/DC 100~250V

    �DC 24~60V

    RTC timer �Available �Available �Available �Available

    LED for�Long time delay �N type �N type �N type

    trip info.�Short time delay/

    Instantaneous

    �Ground fault

    �10 records �256 records �256 records

    Fault recording (Fault/Current/Date and Time) (Fault/Current/Date and Time) �Last fault waverecording (3 Phase)

    Event recording �256 records(Content, Status, Date) �P typeOperating �Reset button �Reset, Menu �A type �A type

    button Up/Down, Left/Right, Enter

    Basic protection function(L / S / I / G)is still under normal operation

    without control power.

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

  • Trip relay

    000 Without trip relay

    N

    Trip relay type

    G 0

    N

    N Normal

    A Ammeter

    A

    G Ground fault

    Z Without comm. + Earth leakage (30A)

    C Comm.

    K Comm. + Earth leakage (30A)

    G

    0 Self-Power, 60Hz

    1 AC/DC 100V~250V, 60Hz

    2 DC 24V~60V, 60Hz

    5 Self-Power, 50Hz

    6 AC/DC 100V~250V, 50Hz

    7 DC 24V~60V, 50Hz

    0

    P Power meter

    P

    C Ground fault + Com

    K Comm. + Earth leakage (30A)

    A Comm. + Pre-trip alarm

    C

    1 AC/DC 100V~250V, 60Hz

    2 DC 24V~60V, 60Hz

    6 AC/DC 100V~250V, 50Hz

    7 DC 24V~60V, 50Hz

    1

    S Supreme meter

    S

    C Ground fault + Com

    K Comm. + Earth leakage (30A)

    A Comm. + Pre-trip alarm

    C

    1 AC/DC 100V~250V, 60Hz

    2 DC 24V~60V, 60Hz

    6 AC/DC 100V~250V, 50Hz

    7 DC 24V~60V, 50Hz

    1

    * L/S/I/G configuration as standard-with LED indicators-without output contacts

    * Ground fault system by vector sum

    * L/S/I/G configuration as standard* Ground fault system by vector sum* Earth leakage system

    - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)- X: External CT - Private ZCT applied(faullt current >30A)

    * Applicable to generator protection purpose

    * L/S/I/G configuration as standard* Ground fault system by vector sum* Earth leakage system

    - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)- X: External CT - Private ZCT applied(faullt current >30A)

    * Applicable to generator protection purpose

    Note) 1. L/S/I/G configuration as standard2. Ground fault, earth leakage and pre-trip alarm functions are alternative.3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition.4. Voltage module should be required for P and S types(supplied seperately)

    * L/S/I/G configuration as standard* Ground fault system by vector sum(G,C)* Earth leakage system

    - Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)- E,X: External CT - Private ZCT applied(faullt current >30A)

    * Comm. and output contacts DO NOT work under self-power condition.

    G

    G Ground fault + L/S/I/G

    Communication & protection Control voltage & frequency

    0

    0 Self-Power, 60Hz

    5 Self-Power, 50Hz

  • Characteristic curves

    Long-time delay (L) Short-time delay (S)

    Instantaneous (I)Ground fault (G) IDMTL

    × Ir

    5000

    2000

    1000

    500

    200

    100

    50

    3040

    20

    10

    345

    2

    1

    0.40.3

    0.2

    0.1

    0.05

    0.02

    0.01

    20107543210.7

    0.5

    t(s)

    tr = 0.5...20s

    20

    8

    4

    2

    1

    0.5

    12

    Ir = 0.4...1 In

    5000

    2000

    1000

    500

    200

    100

    50

    30

    20

    40

    10

    45

    3

    2

    1

    0.40.3

    0.2

    0.1

    0.05

    0.02

    0.011

    0.7

    0.5

    t(s)

    × Ir

    201075432

    Isd = 1.5...10 Ir

    0.4

    0.3

    0.2

    0.1

    0.4

    0.3

    0.2

    0.1

    0.05

    I2t OFF

    I2t ON

    × In

    100

    50

    40

    30

    20

    10

    5

    4

    3

    2

    1

    0.4

    0.3

    0.2

    0.1

    0.05

    0.02

    0.01

    321

    0.7

    0.5

    0.4

    0.3

    0.2 10754320.1

    0.07

    0.05

    t(s)

    Ig = 0.2...1 In

    Ii = 2...15 In

    0.4

    0.3

    0.2

    0.1

    0.4

    0.3

    0.2

    0.1

    0.05

    I2t OFF

    I2t ON

    × Ir

    10000

    5000

    2000

    1000

    500

    200

    100

    50

    20

    10

    5

    2

    1

    0.05

    20107543210.7

    0.5

    t(s)

    EIT

    VIT

    SIT

    DT

  • Dimensions

    ■ HEAD OFFICELS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang, Kyonggi-Do, 431-848, KoreaTel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648

    LS constantly endeavor to improve our products so that information in thiscatalog is subject to change without notice.

    Susol 1600AF MCCB / October.2010 Printed in korea STAFF

    4- 5.5 or M5

    3P 4P

    199

    4- 5.5 or M5

    269

    CL

    CL CL CL

    CL CL CL

    CLCL

    199210

    212

    258

    1443.5

    1513

    5

    269280

    212

    258

    190.6

    115.7149.8152.5155.5162.7

    114.7 84

    372

    42

    37.2

    283.

    5

    4470 70 70

    31

    70 7044

    25

    31

    212

    212

    3P 4P 3P 4P

    119

    67

    15

    199

    200

    95

    119

    15

    67

    199

    200

    951111

    212

    19970 70

    210

    327

    404

    374

    5077

    252577

    267

    270

    16.515

    190.6

    115.7149.8152.5

    47.5

    155.5162.7

    212

    26970 70

    280

    327

    404

    374

    252577

    362

    270

    252577

    70

    18

    37.2

    25

    25115.7

    283.

    5

    307 404

    5.55.5

    11 11

    212

    19970 70

    210

    327

    270

    190.6

    115.7149.8152.5

    47.5

    155.5162.7

    212

    26970 70

    280

    327

    270

    70

    25

    115.7

    16.5

    320250Insulation barrier

    Insulation barrier

    Plate protection

    Plate protection

    Insulation barrier

    Mounting hole

    Mounting hole

    Trip button

    Trip button

    Insulation barrier

    Mounting hole

    Trip button

    25

    37.2

    283.

    5

    16.5

    5.5 5.5

    11

    25

    ■■Front panel cutting

    ■■Panel drilling■■Rear Type

    ■■Front Type ■■Front Type Busbar