Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Introduction of NABCO hermetic door
Accessibility Innovations Company
Necessity of hermetic door
1. Rooms in healthcare facilities which may require hermetic doors
Operating room Hybrid operating room
ICU room
Radiotherapy room X-ray room
Necessity of Hermetic door
Necessity of Hermetic door
2. For operating room/ICU room (general)
-There is a higher risk for patients to have a secondary disease caused by air-borne infection or dust. *Examples of air-borne infection: tuberculosis(T.B.) , measles, Chicken pox, SARS……
-Temperature and humidity should be appropriate.
⇒Hermetic door can help to reduce the risk and keep the good air-condition.
Temperature(℃) Humidity(%) General surgery 22~26
45~60 Child surgery 22~30 Heart surgery 18~30 *Refer to the guidance of Healthcare Engineering of Association of Japan
Necessity of Hermetic door
3. For operating room/ICU room (with high function)
⇒Hermetic door can keep the good environment with an air-conditioning facility system
◎Pressurized room ⇒ to prevent the virus from outside to inside
Pressurized room (provided air>exhaust air)
Depressurized room (provided air<exhaust air)
◎Depressurized room ⇒ to prevent the virus from inside to outside
-Air-conditioning facility system is installed to make the room pressurized/depressurized.
Air flow
*Example: Operating room ICU room
*Example: Isolation room
Air flow
Necessity of Hermetic door 4. For Radiotherapy room/X-ray room/Hybrid operating room
⇒Hermetic door with Lead (PB) can help to block X-ray.
-Radiation has to be blocked in order to prevent the harm to people.
◎Hybrid operating room Basically, radiography devices are installed in a laboratory such as X-ray room. Hybrid operating room is an operating room with the radiography devices.
NABCO hermetic door
NABCO Hermetic door
1. Types of NABCO hermetic door
Name : NAX (NABCO Airtight eXtension) Types : NAX-SN 【Air tightness + sound insulation (flush type)】 NAX-SG 【Air tightness + sound insulation (Glass type)】 NAX-SX 【Air tightness + radiation shield (flush type)】
≪Aluminum flush≫ ≪Stainless steel flush≫ ≪Glass≫
Glass type may be able to meet the request of ICU room because medical staff can check patients in the room
NABCO Hermetic door
(1) Hermetic function
-The door panel is dropped and pushed onto the wall. ⇒Easy to install and able to keep air tightness even in case of a blackout
2. Features of NAX
≪Outline≫ ≪Detail of the rail≫
NABCO Hermetic door
(2) Header box
-The header box is very small and can be installed as surface mount. ⇒The height is smaller than the other brand’s header box
≪NABCO(NAX)≫
NABCO Hermetic door (3) Door handle
-In case of a blackout, the door can be opened easily by hand with a door handle (3 types of the door handles can be chosen) ⇒ The door can be opened fully if the recessed handle is chosen ≪Recessed handle≫ ≪Tubular handle≫ ≪Lever handle≫
Recommendation
≪ Spring in the operator≫
The spring makes it easily to open manually
(4) Flat floor
-The floor should be flat for stretchers ⇒Barrier free can be realized as flat floor designing.
NABCO Hermetic door
-Foot switch or Touch less sensor can be suitable with the hermetic door.
(6) Detection devices
≪Foot switch≫ ≪Touch less sensor≫
-3 types of windows are selectable for the flush door panel. Flat frame structure can prevent the accumulation dust.
(5) Windows for door leaf
≪Flat frame for both side≫
Both side Inside Outside Inside Outside
≪Flat frame for one side≫ ≪Flat frame for one side≫
NABCO Hermetic door
3. Specification of NAX
(1)Air tightness/Sound insulation/Radiation shield
class Air permeability 10Pa
(m3/h・m2)
0 10.5 <q ≦12
・・・ ・・・
6 3.0 < q ≦ 4.5
7 1.5 < q ≦3.0
8 q ≦1.5
Class Air permeability 100Pa
(m3/h・m2)
0 Without testing
1 ≦50
2 ≦27
3 ≦9
4 ≦3
≪ JIS A 4702 A-4 ≫ ≪ GB/T 7106-2008≫ ≪ UNE-EN 12207 ≫
①Air tightness: the highest class (A-4) of JIS A4702 (Equivalent of GB-T 7106 2008 class 8/UNE-EN 12207class 4 )
China Europe
②Sound insulation: 【Glass】 Class (T-2) of JIS A4702 【Flush】 Class (T-1) of JIS A4702
③Radiation shield: 2mm of lead(PB)
NABCO Hermetic door
(2)Specification table
Reference (comparison with the other brands)
1. Line-up of hermetic door
Flush type (NABCO) : Aluminum or Stainless steel
Air tightness (Flush)
Air tightness (Glass)
Sound insulation (Flush)
X-ray shield (Flush)
Single Bi-parting Single
Bi-parting
Single
Bi-parting
Single Bi-parting
NABCO ○ ○ ○ ○ ○ ○ ○ ×
Manusa ○ ○ ○ ○ ○ ○ ○ ○
Besam ○ × × × × × ? ?
Record ○ △ × × × × ? ?
Flush type (European brands) : HPL(high pressure laminate) or Stainless steel
Comparison with the other brands
Comparison with the other brands
2. Hermetic function
-Hermetic door of other brands are almost same function (the door panel is dropped and pushed onto the wall). ⇒installation skill is very important
≪NABCO(NAX)≫
≪Besam≫ ≪Record≫
≪Manusa≫
3. Header box
- The height is smaller than the other brand’s header box
≪NABCO(NAX)≫ ≪Manusa≫
≪Besam≫ ≪Record≫
Comparison with the other brands
4. Door handle
Besam ’s and Record’s hermetic door has to be used a lever handle for opening manually. ⇒The door can’t be opened fully
≪NABCO(NAX)≫ ≪Manusa≫
≪Besam≫ ≪Record≫
Selectable for recessed type
Comparison with the other brands
5. Specification of air tightness
NABCO hermetic door (NAX) has same level of class 4 of UNE EN-12207.
Comparison with the other brands
Class Air permeability 100Pa
(m3/h・m2)
0 Without testing
1 ≦50
2 ≦27
3 ≦9
4 ≦3
≪ UNE-EN 12207 ≫ Europe
Introduction of NABCO�hermetic door スライド番号 2スライド番号 3スライド番号 4スライド番号 5スライド番号 6スライド番号 7スライド番号 8スライド番号 9スライド番号 10スライド番号 11スライド番号 12スライド番号 13スライド番号 14スライド番号 15スライド番号 16スライド番号 17スライド番号 18スライド番号 19スライド番号 20