1
Model Ranges Keypad Display Backlight Bat. Hrs. Temp. Calibration Units Memory Auto Shutoff DPG2000B Vacuum to 1999 psi, absolute 1 button on/off 3.5 digit LCD, 0.5" H. none 1000 –40°F (–40°C) min. Top Zero, Span pots. Factory set none -5 5 min. factory set -10 10 min. factory set -30 30 min. factory set -ON on/off factory set DPG2000BBL Red LED hold button to activate 150-1000 DPG2000B____D4 Vacuum to 5000 psi, absolute, compound, ± bipolar 1 button on/off/ zero D4: 4 digit LCD, 0.5" H + 5 character lower display none 1000 –4°F (–20°C) min. Int. buttons & lockout sw., zero, span, linearity Internal button select Min/max Internal button select to desired minutes or hours, or on/off DPG2000BBL__D4 Red LED, 1 min., w. light sensor 150-750 DPG2000B____D4-M4 Vacuum to 5000 psi, absolute, compound, ± bipolar 3 button on/off, zero/ clear, memory , D4: 4 digit LCD, 0.5" H + 5 character lower display none 1000 –4°F (–20°C) min. Keypad + pass code with internal lockout switch, zero, span, linearity Keypad select M4 4 max readings Keypad select to desired minutes or hours, or on/off DPG2000BBL__D4-M4 Red LED, 1 min., w. light sensor 150-750 DPG2000B____D4-M6 none 1000 M6 6 max readings DPG2000BBL__D4-M6 Red LED, 1 min., w. light sensor 150-750 Intrinsically Safe Battery Powered Gauges Agency Approval Factory Mutual Approved Intrinsically Safe for Class I, Division 1, Groups, A, B, C, D Hazardous Locations Ranges and Resolution See range table for ranges and engineering units. Fixed resolution. Bipolar, compound, and 4-digit ranges require D4 model. Standard: Range, resolution, and units are factory set Select any 3½ digit (up to 1999) range. D4: Select default range and engineering units. Units may be changed to any equal to the sensor range. Display Standard: 3½ digit LCD, 0.5" H D4: 4 digit LCD, 0.5" H, 0.25" H alphanumeric lower BL: Red LED display backlight 3 readings per second nominal display update rate Accuracy ±0.25% of full scale ±1 least significant digit, includes linearity, hysteresis, repeatability Functions & Calibration Standard Front button turns gauge on or off Top-accessible calibration potentiometers Non-interactive zero and span, ±10% of range D4 without memory Front button turns gauge on or off, press and hold for zero at startup, display/clear min/max Internal buttons for set up and calibration Non-interactive zero and span, ±10% range Internal lockout switch to disable setup, calibration and for customer's calibration seal. D4 with M4 or M6 (3-button keypad) Center button turns gauge on or off Zero/clear button to zero display or clear memory Memory button to store readings Keypad for units selection, shutoff time, and calibration Non-interactive zero, span, linearity, ±10% range Internal lockout switch to disable setup, calibration, and for customer's calibration seal. M4, M6 Memory M4: Store 4 max readings, can be labelled as MEM 1 through MEM 4, or LF, RF, RR, LR M6: Store 6 max readings, can be labelled as MEM 1 through MEM 6, or as 6 wheel aircraft tire designations NLG 1, NLG 2, MLG 1, MLG 2, MLG 3, MLG 4 Batteries & Battery Life Two AAA alkaline See table below for battery life Low battery symbol on display when batteries must be replaced Class I, Division 1, Groups A, B, C, D All Metal Housing Digi-Max ® with Min/Max, Zero ±0.25% Accuracy, 316L SS Sensor Portable and Rugged Test Gauge Natural Gas Pipeline Pressures Aircraft Tire Pressure NEC Hazardous Areas Auto Shutoff Standard : Factory set to 5, 10, 30 min nute ut s, or on/ on/o off D4 : User settable 1 minute to 8 8 h hours or or on on/ /off Housing Epoxy powder coated aluminu n m case and b beze ezel, rubber front and rear gaskets 3.38" W x 2.88" H x 1 x .65" D Add approximately 0.75 " to height for pre essu ssure re fit fittin ting g 10 ounces (approx. weight) Pressure/Vacuum Connection & Material ¼ " NPT male fitting 316L SS wetted parts Overpressure & Burst 3000 psig range and metric equivalents: 5000 psig 5000 psig range and metric equivalents: 7500 psig All A others 2 times normal sensor pressure rating Bur urst: st: 4 4 times sensor pressure rating, or 10,000 psi, whi whiche chever is less Vac V uu um: Absolut te s e sens ensors ors, g , gauge reference 15, 100, 200 0 ps psi s i sens ensors ors only Operating Temperature Sta anda ndard : 40 4 to t 185 85°F °F (–4 (– 0 to 85°C) D4 D4 : 4 to 185° 8 F (–20 –20 to to 85°C) Compensated Temperature 32 to 158°F (0 ( to 70°C) C To Order Model Series See table below _______________ Range See range table _______________ Display-Memory See table below _______________ Auto Shutoff Time Default for D4 versions _______________ Options See options list _____________ DPG2000B DPG2000B___-D4 DPG2000B___-D4-Mx C US Info Quick Link cecomp.com/2000

Intrinsically Safe Battery Powered Gauges …cecomp.com/pdf_old/cecomp_intrinsicallysafe.pdf±0.25% of full scale ±1 least significant digit, includes linearity, hysteresis, repeatability

Embed Size (px)

Citation preview

RangesSee range table for available engineering units

DPG1000L, F4L, DPG1000DRVacuum to 5000 psi, absolute, bipolar

F16L, F16DRVacuum to 5000 psi, absolute, bipolar, compound

F4DRVacuum, absolute, bipolar, pressure to 1999 psi

Accuracy±0.25% of full scale ±1 least significant digit, includes linearity, hysteresis, repeatability

DisplayRanges to 1999: DPG1000L, F4L, DPG1000DR, F4DR3½ digit LCD, 0.5" H digits3 readings per second nominal display update rate

Ranges 2000-up: DPG1000L, F4L, DPG1000DR4 digit LCD, 0.4" H digits3 readings per second nominal display update rate

F16L, F16DR4 digit LCD, 0.5" H, 0.25" H alphanumeric lower display4 readings per second nominal display update rate

BL: Red LED display backlight on when gauge is on

Controls & CalibrationRanges to 1999: DPG1000L, F4L, DPG1000DR, F4DRFront panel zero & span potentiometers, ±10% rangeFront panel output test potentiometer, 0-100% rangeFront panel output test buttonInternal potentiometers for retransmission zero and span

Ranges 2000-up: DPG1000L, F4L, DPG1000DRTop-mounted zero & span potentiometers, ±10% rangeTop-mounted output test potentiometer, 0-100% rangeFront panel output test buttonInternal potentiometers for retransmission zero and span

F16L, F16DRPassword protected keypad calibration, ±10% rangeOutput test, keypad programmable, 0-100% rangeFront panel output test buttonFront panel select and up/down button for setup

Output test allows testing of system operation by setting output and display to a test level, independent of pres-sure input.

PowerL models: 8 to 32 VDC, powered by current loop 2-wire, 3 ft long, 22 AWG cable

DR models: 8 to 24 VAC 50/60 Hz or 9 to 32 VDC, 1.0 watt maximum, 4-wire shielded, 3 ft long, 22 AWG cable for power and output

All models are designed for continuous operationGauges are reverse polarity protected

Transmitters with Local Display

4-20 mA 2 Wire Loop Powered Models

4 Wire w. 4-20 mA or Voltage Output

Output Test Function

Pressure/Vacuum Transmitters

RangesSee range table for available engineering units

DPG1000Vacuum to 5000 psi, absolute, bipolar

F16Vacuum to 5000 psi, absolute, bipolar, compound

Accuracy±0.25% of full scale ±1 least significant digit, includes linearity, hysteresis, repeatability

DisplayDPG1000 ranges to 19993 readings per second nominal display update rate3½ digit LCD, 0.5" H digits

DPG1000 ranges 2000-up3 readings per second nominal display update rate4 digit LCD, 0.4" H digits

F16ADA, F16DAR4 readings per second nominal display update rate4 digit LCD, 0.5" H digits, 0.25" H alphanumeric display

BL: Red LED display backlight on when gauge is on

Controls & CalibrationDPG1000ADATop-mounted zero & span potentiometers, ±10% rangeOutput test potentiometer, 0-100% rangeRelay set point potentiometers, 0-100% range

DPG1000DARTop-mounted zero & span potentiometers, ±10% rangeOutput test potentiometer, 0-100% rangeRelay set point potentiometers, 0-100% rangeInternal potentiometers for retransmission zero and span

F16ADA, F16DARKeypad calibration, ±10% range, pass code protectedKeypad programmable relay set points, alarm configura-tion, and output test function, 0-100% range

Output test button allows testing of system operation by toggling relays, setting output (DAR models) and display to test level, independent of pressure input.

Relay Outputs2 form C (SPDT) relay contacts1 A at 24 VDC, 0.5 A at 115 VAC, non-inductiveBi-color (red/green) LEDs indicators100 milliseconds typical relay response time6-wire, 3 ft long, 22 AWG cable

Alarm ConfigurationDPG1000ADA, DPG1000DAR1% of full scale deadband, factory setSpecify alarm type when ordering

F16ADA, F16DARKeypad programmable alarm mode, select1% deadband or set/reset with adjustable hysteresis

Pressure/Vacuum Alarms, and Alarms with Retransmission OutputLow Voltage Powered Gauges

RangesSee range table for available engineering units

DPG1000, F4: Vacuum to 5000 psi, absolute, bipolar, compoundARM760: 760 torr absoluteF18: Selectable engineering units via internal buttons

Accuracy±0.25% of full scale ±1 least significant digit, includes linearity, hysteresis, repeatability

DisplayDPG1000 & F4 ranges to 1999, ARM7603 readings per second nominal display update rate3½ digit LCD, 0.5" H digits

DPG1000 & F4 ranges 2000-up, all F16, F183 readings per second nominal display update rate4 digit LCD, 0.5" H, 0.25" H alphanumeric lower display

BL: Red LED display backlight on when gauge is on

Controls & CalibrationDPG1000 & F4 ranges to 1999, ARM760Front on/off buttonFront zero and span potentiometers, ±10% range

DPG1000 & F4 ranges 2000-upFront on/off button, zeroes display at power-upInternal calibration buttons, zero, mid, span, ±10% range

F16, F18Front button for zero at power-up and min/maxInternal calibration buttons, zero, mid, span, ±10% range

PowerAD: 8-24 VAC or 9-32 VDC, approx. 5 mAADBL: 8-24 VAC or 9-32 VDC, approx. 80 mAARM760: 115 VAC/12 VDC plug-in power supply included, 5 ft cable

2-wire , 3 ft long, 22 AWG cableAll models are designed for continuous operationGauges are reverse polarity protected

HousingsStandard: 3.38" W x 2.88" H x 1.65" DEpoxy powder coated aluminum case, ABS/polycarbonate bezel, front and rear gaskets

NEMA 4X: 3.5" W x 3.0" H x 2.0" D UV stabilized ABS/polycarbonate case, polycarbonate window, rear gasket

Add approximately 0.75" to height for pres-sure fitting and 1" to depth for strain relief

Connection & Material¼" NPT male, 316L SS wetted parts

Overpressure & Burst3000 psig range and metric equivalents: 5000 psig5000 psig range and metric equivalents: 7500 psigAll others 2 times sensor pressureBurst: 4 times sensor pressure rating, or 10,000 psi, whichever is less

Ideal for Permanent Installations

8-24 VAC or 9-32 VDC Input Power

Digi-Max® with Min/Max, Zero

±0.25% Accuracy, 316L SS Sensor

F4AD, NEMA 4X

DPG1000ADA

F4DR, NEMA 4X

F16ADN, F18ADN NEMA 4X

To OrderModel SeriesSee table below

_______________

RangeSee range table

_______________

Relay ActionDPG1000 models only_______________

Analog OutputDAR models only

_______________

OptionsSee options list

_______________

F16DAR

DPG1000AD

Engine Assembly Leakdown Testing

Hydraulic System

Model Ranges NEMA Backlight Calibration Setup Alarm Type and Options Analog Output

DPG1000ADAVacuum to 5000 psi, absolute, ± bipolar

Top zero, span pots.

Pot. for each setpointPot. for test level

2 SPDT, specify relay action -1N Hi/Lo Normal -1R Hi/Lo Reverse -2N Hi/Hi Normal -2R Hi/Hi Reverse -3N Lo/Lo Normal -3R Lo/Lo Reverse

none

F16ADAVacuum to 5000 psi, absolute, compound,

± bipolar

Via keypad with

pass code protection

Keypad programmable alarm configuration, setpoints, test level

2 SPDT field programmable configuration1% deadband or adjustable hysteresis

noneF16ADABL Red LEDF16ADAN 4XF16ADANBL 4X Red LED

DPG1000DARVacuum to 5000 psi, absolute, ± bipolar

Top zero, span pots.

Pot. for each setpointPot. for test level

2 SPDT, specify relay action -1N Hi/Lo Normal -1R Hi/Lo Reverse -2N Hi/Hi Normal -2R Hi/Hi Reverse -3N Lo/Lo Normal -3R Lo/Lo Reverse

-I 4-20 mA -V 0-2 VDC

F16DARVacuum to 5000 psi, absolute, compound,

± bipolar

Via keypad with

pass code protection

Keypad programmable alarm configuration, setpoints, test level

2 SPDT field programmable configuration1% deadband or adjustable hysteresis

-I 4-20 mA -V 0-2 VDC -BV ±2 VDC

F16DARBL Red LEDF16DARN 4XF16DARNBL 4X Red LED

Low Voltage AC/DC Powered

0.5 A Relays with Status LEDs

Analog Output Available

Output Test Function

DPG1000DARAnalog output, 50 milliseconds typical response time

F16DARApprox. 12,000 count analog output, updated 4 times per second

DPG1000DAR, F16DAR analog output options-I: Powered 4-20 mADC output

Output drive (compliance) determined bd by y power source

-V: 0 to 2 VDC into 5K ohm or greater

-BV: ±2 VDC into 5K ohm or greater Optional on F16DAR with bipolp ar ranngesges

Power8 to 24 VAC 50/60 Hz or 9 to 32 VDC, 1.1.0 w0 wattt mamax.x.4-wire, 3 ft long, 22 AWG cable for powwer e and ou outputputt

All models are designed for continuououus opeoperationonGauges are reverse polarity protectetedd

HousingsStandard: 3.38" W x 2.88" H x 1.65" " DDEpoxy powder coated ad luminum casease, ABS/BS/polycarbonate bezel, front and rear gasgasketts

NEMA 4X: 3.5" W x x 3.03 " H x 2.0" D UV stabilized ABS/polycarbonate casese, p, polyolycarbonatete window, rear gasket

Add approximately 0.75" to height for preressussure re fitf ting and 1" to depth for strain relief

Connection & Material¼" NPT male, 316 L stainless steel wetted ppartartss

Overpressure & Burst3000 p0 sig range and metric eququivavalents: 5000 0 psipsigg500000 p0 psigsig range and metric equuivaivallents: 7500 psigAlll ot otherhers 2s 2 ti timesmes sensor pressurreeBurBurst:st 4 4 timtimees sensor pressure rating, or 10,000 pssi, whiwhiccheverr is is le less

Operating Temperature–4 to 185°F (–20 to 85°C)

Compensated Temperature32 to 158°F (0 to 70°C)

High or Low Pump Pressure Alarm

Tank Level Monitor Plus Alarm

Automated Leak-Down Testing

Vacuum Pump Alarm

Model Power Ranges NEMA Backlight Calibration Output Test Analog OutputDPG1000L 8-32 VDC

2-wire loop-poweredVacuum to 1999 psi, absolute, ± bipolar

Front zero, span pots. Front pot. for test level 4-20 mAF4L 4XF16L 8-32 VDC

2-wire loop-poweredVac to 5000 psi, absolute,

compound, ± bipolarVia keypad with

pass code protectionKeypad programmable

test level4-20 mA

F16LN 4XDPG1000DR 8-24 VAC or

9-32 VDCVacuum to 5000 psi, absolute, ± bipolar

Front zero, span pots. Front pot. for test level -I 4-20 mA -V 0-2 VDC

DPG1000DRBL Red LEDF4DR 8-24 VAC or

9-32 VDCVacuum to 1999 psi, absolute, ± bipolar

4XF4DRBL 4X Red LEDF16DR

8-24 VAC or 9-32 VDC

Vacuum to 5000 psi, absolute, compound,

± bipolar

Via keypad withpass code protection

Keypad programmable test level

-I 4-20 mA -V 0-2 VDC -BV ±2 VDC

F16DRBL Red LEDF16DRN 4XF16DRNBL 4X Red LED

Pressure Input to PLC

Tank Level Transmitter

Pump Pressure Transmitter

Pressure Transmitter to Datalogger

To OrderModel SeriesSee table below

_______________

RangeSee range table

_______________

Analog Output TypeSpecify for DR models

_______________

OptionsSee options list

_______________

OutputDPG1000L, F4L, DPG1000DR, F4DRAnalog output, 50 milliseconds typical

F16L, F16DRAnalog output, approximately 12,000 counts over gauge range. Updated approximately 16 times per sec.

DR series analog output options-I: Powered 4-20 mADC output

Output drive (compliance) determined by power source

-V: 0 to 2 VDC into 5K ohm or greater

-BV: ±2 VDC into 5K ohm or greater Optional on F16DR with bipolar ranges

HousingsStandard: 3.38" W x 2.88" H x 1.65" DEpoxy powder coated aluminum case, ABS/polycarbonate bezel, front and rear gaskets

NEMA 4X: 3.5" W x 3.0" H x 2.0" D UV stabilized ABS/polycarbonate case, polycarbonate window, rear gasket

Add approximately 0.75" to height for pressure fittingand 1" to depth for strain relief

Pressure/Vacuum Connection & Material¼" NPT male, 316L SS wetted parts

Overpressure & Burst3000 psig range and metric equivalents: 5000 psig5000 psig range and metric equivalents: 7500 psigAll others 2 times sensor pressureBurst: 4 times sensor pressure rating, or 10,000 psi, whichever is less

Operating Temperature–4 to 185°F (–20 to 85°C)

Compensated Temperature32 to 158°F (0 to 70°C)

F16L

Pipe Pressure Testing System

Model Power Ranges NEMA Backlight Zero Calibration Units MemoryARM760AD

115V/12VDC included 760 Torr absolute Front zero pot.Front zero, span pots.

Factory set noneARM760ADBL Red LEDDPG1000AD

8-24 VAC or 9-32 VDCVacuum to 5000 psi, absolute, compound,

± bipolarFront zero pot.

Front zero, span pots.

Factory set noneDPG1000ADBL Red LEDF4AD 4XF4ADBL 4X Red LEDF16AD

8-24 VAC or 9-32 VDCVacuum to 5000 psi, absolute, compound,

± bipolar

Hold button at startup

Internal buttons

Factory set Min/maxF16ADBL Red LEDF16ADN 4XF16ADNBL 4X Red LEDF18AD

8-24 VAC or 9-32 VDCVacuum to 5000 psi, absolute, compound,

± bipolar

Hold button at startup

Internal buttons

Internal button select

Min/maxF18ADBL Red LEDF18ADN 4XF18ADNBL 4X Red LED

–4 to 185°F (–20 to 85°C)

Compensated Temperature32 to 158°F (0 to 70°C)

Plant Compressed Air Pressure

Pneumatic Machinery Monitoring

ARM Replaces Mercury Manometers

Monitor Vacuum Pumps

s-f

ARM760AD

To OrderModel SeriesSee table below_____________

RangeSee range table

_____________

OptionsSee options list

_____________

F16ADF18AD

Model Ranges Keypad Display Backlight Bat. Hrs. Temp. Calibration Units Memory Auto Shutoff

DPG2000BVacuum to 1999

psi, absolute1 button

on/off3.5 digit LCD,

0.5" H.

none 1000 –40°F(–40°C)

min.

Top Zero, Span pots.

Factory set none

-5 5 min. factory set -10 10 min. factory set -30 30 min. factory set -ON on/off factory setDPG2000BBL Red LED hold

button to activate 150-1000

DPG2000B____D4 Vacuum to 5000 psi, absolute, compound, ± bipolar

1 buttonon/off/zero

D4: 4 digit LCD, 0.5" H

+ 5 character lower display

none 1000 –4°F (–20°C)

min.

Int. buttons & lockout sw., zero, span,

linearity

Internal button select

Min/maxInternal button select to

desired minutes or hours, or on/offDPG2000BBL__D4 Red LED, 1 min.,

w. light sensor 150-750

DPG2000B____D4-M4

Vacuum to 5000 psi, absolute, compound, ± bipolar

3 buttonon/off,zero/clear,

memory,

D4: 4 digit LCD, 0.5" H

+ 5 character lower display

none 1000

–4°F (–20°C)

min.

Keypad +pass code with

internal lockout switch,

zero, span, linearity

Keypad select

M44 max

readings Keypad select to desired minutes or hours, or

on/off

DPG2000BBL__D4-M4 Red LED, 1 min., w. light sensor 150-750

DPG2000B____D4-M6 none 1000 M66 max

readingsDPG2000BBL__D4-M6 Red LED, 1 min., w. light sensor 150-750

Intrinsically Safe Battery Powered Gauges

Agency ApprovalFactory Mutual Approved Intrinsically Safe for Class I, Division 1, Groups, A, B, C, D Hazardous Locations

Ranges and ResolutionSee range table for ranges and engineering units. Fixed resolution. Bipolar, compound, and 4-digit ranges require D4 model.

Standard: Range, resolution, and units are factory setSelect any 3½ digit (up to 1999) range.

D4: Select default range and engineering units. Units may be changed to any equal to the sensor range.

DisplayStandard: 3½ digit LCD, 0.5" H

D4: 4 digit LCD, 0.5" H, 0.25" H alphanumeric lower

BL: Red LED display backlight

3 readings per second nominal display update rate

Accuracy±0.25% of full scale ±1 least significant digit, includes linearity, hysteresis, repeatability

Functions & CalibrationStandardFront button turns gauge on or offTop-accessible calibration potentiometersNon-interactive zero and span, ±10% of range

D4 without memoryFront button turns gauge on or off, press and hold for zero at startup, display/clear min/max

Internal buttons for set up and calibrationNon-interactive zero and span, ±10% range

Internal lockout switch to disable setup, calibration and for customer's calibration seal.

D4 with M4 or M6 (3-button keypad)Center button turns gauge on or offZero/clear button to zero display or clear memory Memory button to store readings

Keypad for units selection, shutoff time, and calibrationNon-interactive zero, span, linearity, ±10% range

Internal lockout switch to disable setup, calibration, and for customer's calibration seal.

M4, M6 MemoryM4: Store 4 max readings, can be labelled as MEM 1 through MEM 4, or LF, RF, RR, LR

M6: Store 6 max readings, can be labelled as MEM 1 through MEM 6, or as 6 wheel aircraft tire designations NLG 1, NLG 2, MLG 1, MLG 2, MLG 3, MLG 4

Batteries & Battery LifeTwo AAA alkalineSee table below for battery lifeLow battery symbol on display when batteries must be replaced

Class I, Division 1, Groups A, B, C, D

All Metal Housing

Digi-Max® with Min/Max, Zero

±0.25% Accuracy, 316L SS Sensor

Portable and Rugged Test Gauge

Natural Gas Pipeline Pressures

Aircraft Tire Pressure

NEC Hazardous Areas

Auto ShutoffStandard: Factory set to 5, 10, 30 minnuteut s, or on/on/ooffD4: User settable 1 minute to 88 h hours oror on on//off

HousingEpoxy powder coated aluminun m case and bbezeezel, rubber front and rear gaskets

3.38" W x 2.88" H x 1x .65" DAdd approximately 0.75" to height for preessussure re fitfittintingg

10 ounces (approx. weight)

Pressure/Vacuum Connection & Material¼" NPT male fitting316L SS wetted parts

Overpressure & Burst3000 psig range and metric equivalents: 5000 psig5000 psig range and metric equivalents: 7500 psigAllA others 2 times normal sensor pressure rating

Bururst:st: 4 4 times sensor pressure rating, or 10,000 psi, whiwhichechever is less

VacV uuum: Absolutte se sensensorsors, g, gauge reference 15, 100, 2000 ps psi si sensensorsors only

Operating TemperatureStaandandard: –40 4 to t 18585°F °F (–4(– 0 to 85°C)D4D4: –4 to 185°8 F (–20–20 to to 85°C)

Compensated Temperature32 to 158°F (0 ( to 70°C)C

To OrderModel SeriesSee table below

_______________

RangeSee range table

_______________

Display-MemorySee table below

_______________

Auto Shutoff TimeDefault for D4 versions

_______________

OptionsSee options list

_____________

DPG2000B

DPG2000B___-D4

DPG2000B___-D4-Mx

C US

DPG1000AD

Info Quick Linkcecomp.com/alarms

Info Quick Linkcecomp.com/trans

F16DR

Info Quick Linkcecomp.com/ad

Info Quick Linkcecomp.com/2000

g

e

DPG1000L

DPG1000DR, 4-Digit Range

Cecomp8_2010.indd 2 8/31/2010 10:28:20 AM