INTERFACE PROTECTIONSYSTEM UNIT

COMPLIANT WITH STANDARD SHAMS DUBAI - DRRG (DEWA) SEC (Saudi Elect r icit y Company)

INTERFACE PROTECTION SYSTEM UNIT FOR LOW VOLTAGE

General characteristics

Operational characteristics

PMVF 60 interface protection (IP) system unit has been developed according to the Engineering recommendation SHAMS DUBAI - DRRG (DEWA) - SEC (Saudi Electricity Company) technical standard. Each is used when a local generating system is connected in parallel with the low and medium voltage electric utility. The controls refer to limits of voltage and frequency monitoring.In the case when either the voltage or the frequency are out of admissible limits, the IP must step in by de-energising a relay output so that the interface switch (IS) trips.PMVF 60 is equipped with 4 inputs having the following functions:– IS status feedback– External signal for frequency selection– Disabling signal– Remote tripping (forced IS opening, independent of

voltage and frequency values).Also, there are 2 relay outputs for:– IS opening and closing– Backup device opening (programmable: retentive

normally energised, retentive normally de-energised or adjustable pulse).

The backup device consists of a signal contemporary or with a 0.5s delay respect to the IS opening command, transmitted only if the IS failed and did not complete the disconnection.PMVF 60 also has 2 additional relay outputs to configure as:– Autonomous signalling in case of phase power

unbalance (LSP), only if three CTs are also installed– Programmable alarm.

Ordercodes

Rated voltage Qtyper pkg

WtControl Auxiliary

[V] [V] n° [kg]

Three-phase systems with or without neutral in low or medium voltage.Dual threshold minimum and maximum voltage and frequency protection. R.O.C.O.F and Vector shift. Modular type.

PMVF 60 230VAC400VAC

100...240VAC/110 ...250VDC

1 0.470

– Auxiliary voltage: 100...240VAC/110...250VDC– Voltage inputs: • 400VAC (three-phase connection) • 230VAC (single-phase connection)– Relay outputs 250VAC 5A (AC1) / 30VDC 5A– Relay can be password protected to prevent

parameters being altered– 4 digital inputs– Current inputs (optional): via CTs with selectable

/5A or /1A secondary– Programmable rated voltage, programmable voltage

and frequency thresholds and delays– Support of EXM series communications modules

(USB, RS232, RS485, Ethernet) – Modular housing: 6 modules– Parameter configuration and remote control (only

with comunication expansion module) with software and

– Degree of protection: IP40 on front; IP20 on terminals

– Predisposed for IEC/EN 61850 signal supervision using expansion or external module

– Autotest (Self-test) function.

Compliant with standards: SHAMS DUBAI - DRRG (DEWA) - SEC (Saudi Electricity Company), IEC/EN 60255-5, IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/EN 61000-6-4.

Reference standards

Voltage threshold

SHAMS DUBAIDefault (%)

SHAMS DUBAIDefault (s)

SECDefault (%)

SECDefault (s)

Vmax 59-2 (59 >>) 115% 0.20s 120% 0.20sVmax 59-Av (59 >) 110% 3.00s 110% 3.00sVmin 27-1 (27 <) 85% 0.40s 90% 0.40sVmin 27-2 (27 <<) 40% 0.20s 40% 0.20s

Order codes Description

Communication ports.EXM10 10 Opto-isolated USB interfaceEXM10 11 Opto-isolated RS232 interfaceEXM10 12 Opto-isolated RS485 interfaceEXM10 13 Opto-isolated Ethernet interfaceEXM10 18 IEC/EN 61850 interfaceInputs and outputs.EXM10 01 2 digital opto-isolated inputs and 2 relay outputs 5A 250VAC

Voltage threshold

Frequency threshold

EXPANSION MODULES

EXM 10...EXM 10...

63 (2.48”)43.8 (1.72”)

42.7(1.68”)

5(0.20”)

105.

4 (4

.15”

)90

(3.5

4”)

36.4(1.43”)

45 (1

.77”

)63

.5 (2

.50”

)

108 (4.25”) 35.8(1.41”)

35.8(1.41”)

I1

TA1

L1

V2V1 VNV3 S1I3I2

TA2

S2S2 S1 S1 S2

TA3

A1 A2--- +

A1

A2

14 11 12

DDI

24 21 22 IN1 IN2

100 - 240VAC110 - 250VDC

400VAC

OUT 1 OUT 2

IS

PMVF 60

L2 L3 N

EXM10 02

IS F

EED

BACK

FR

EQ. W

IND

OW

SELE

CTIO

N

OUT 3 OUT 4

DIS

ABLI

NG

SIG

NAL

REM

OTE

TR

IPPI

NG

INPU

T 1

INPU

T 2

A1 A1 A2 A214 11 12 24 21 22 + IN1 IN2 -A1 A1 A2 A2

COM IN3 IN4

INPU

T 3

INPU

T 4

VOLTAGE CURRENT INPUTS

GENERATION

AUXILIARYSUPPLY

INPUTS

BACK-UP LSP PROTECTION

GLOBALALARM

OPTIONAL EXM10 01

(OPTION)

LOVATO ELECTRIC S.P. A.via Don E. Mazza, 1224020 Gorle (Bergamo) ItalyTel +39 035 [email protected]

Follow us

DIMENSIONS [mm (in)]

WIRING DIAGRAMS

PD13

8 GB

07

20

External signal for SHAMS DUBAI

(do not consider for SEC)

Frequency threshold

SHAMS DUBAIDefault

(Hz)

SHAMS DUBAIDefault

(s)

SECDefault

(Hz)

SECDefault

(s)

ON 81>-2 (81>>) OFF 0.10s 62.50 Hz 0.10sOFF 81>-1 (81>) 52.50Hz 0.10s OFF 0.10sOFF 81<-1 (81<) 7.50Hz 4.00s 57.50 Hz 4.00sON 81<-2 (81<<) OFF 4.00s 57.00 Hz 0.10s