Upload
others
View
42
Download
4
Embed Size (px)
Citation preview
DK-SB-0002 / V03 / 08.04.2013
INTERFACE DESCRIPTION MIP 4000 V2.2 CABLING & SOFTWARE COMMUNICATON
For Type Series 4000
2 DK-SB-0002 / V03 / 08.04.2013
Pos: 1 /D okumentati on/OX-Organisatorische Module/OX-D okumentenanfang-0001 @ 18\mod_1331899290735_433021.docx @ 535008 @ 1 @ 1
©2013 MTU Onsite Energy GmbH
Original document was created in German.
This publication including all its parts is protected by copyright. Each instance of use requires the prior written consent of MTU Onsite Energy GmbH. This applies in particular to duplication, dissemination, editing, translation, microfilming, and storage and/or processing in electronic systems, including databases and online services.
Subject to technical alterations in the interest of further development.
Table of Contents
DK-SB-0002 / V03 / 08.04.2013 3
Table of Contents
Table of Contents ....................................................................................................................................................... 3
1 General .................................................................................................................................................... 7
1.1 Validity ...................................................................................................................................................... 7
2 Advantages - MIP 4000 .......................................................................................................................... 8
3 Scope of Service .................................................................................................................................... 9
4 Requirements of the Customer System ............................................................................................. 11
5 Hardware Signals ................................................................................................................................. 12
5.1 MIP - Digital inPuts ................................................................................................................................. 12
5.1.1 Emergency Stop of Customer System ................................................................................................... 12
5.1.2 GCB is On .............................................................................................................................................. 13
5.1.3 Grid failure from the Customer System .................................................................................................. 14
5.1.4 Checkback - Gas Valve 1 ....................................................................................................................... 16
5.1.5 Checkback - Gas Valve 2 ....................................................................................................................... 17
5.1.6 Checkback - Gas Pressure Min ............................................................................................................. 18
5.1.7 Checkback - Gas Pressure Max ............................................................................................................ 19
5.1.8 Checkback - Gas Leak Test OK............................................................................................................. 20
5.1.9 MCB is On .............................................................................................................................................. 21
5.2 MIP - Digital Outputs .............................................................................................................................. 22
5.2.1 Emergency Stop ..................................................................................................................................... 22
5.2.2 GCB Command Close ............................................................................................................................ 23
5.2.3 MCB Command Close ........................................................................................................................... 24
5.2.4 GCB Command Close ............................................................................................................................ 25
5.2.5 Backup Protection - GCB cannot be Opened ........................................................................................ 27
5.2.6 Request Auxiliary Drives ........................................................................................................................ 28
5.2.7 Request Lubricating Oil Solenoid Valves ............................................................................................... 29
5.2.8 Request Gas Leak Test ......................................................................................................................... 30
5.2.9 Request Gas Valve 1 ............................................................................................................................. 31
5.2.10 Request Gas Valve 2 ............................................................................................................................. 32
5.2.11 Checkback - Emergency Stop................................................................................................................ 33
5.3 MIP - Analog Inputs ................................................................................................................................ 34
5.3.1 Generator Winding Temperature - U1 ................................................................................................... 34
5.3.2 Generator Winding Temperature - V1 .................................................................................................... 34
5.3.3 Generator Winding Temperature - W1 ................................................................................................... 35
5.3.4 Generator Bearing Temperature - Drive Side ........................................................................................ 35
5.3.5 Generator Bearing Temperature - Non-Drive Side ................................................................................ 36
5.4 Manual Emergency Stop Buttons........................................................................................................... 36
5.5 MIP 4000 Supply Voltage - 24 VDC ....................................................................................................... 37
5.6 Ethernet Communication via RJ45 ........................................................................................................ 38
5.7 Generator Current Transformer 5 A ....................................................................................................... 39
5.8 Generator Voltage .................................................................................................................................. 40
5.9 Busbar Voltage ....................................................................................................................................... 41
5.10 Grid Voltage ........................................................................................................................................... 42
6 Generator - PFC and AVR .................................................................................................................... 43
6.1 Activation - Voltage Regulator ................................................................................................................ 43
7 Generator Anti-Condensation Heating .............................................................................................. 44
Table of Contents
4 DK-SB-0002 / V03 / 08.04.2013
8 Overview - Cabling ............................................................................................................................... 45
9 Overview - Gas System ........................................................................................................................ 46
10 Software Signals................................................................................................................................... 47
10.1 Signals to the Customer System ............................................................................................................ 47
10.1.1 Request Pre-Lubrication ......................................................................................................................... 47
10.1.2 Request Engine Pre-Heating .................................................................................................................. 47
10.2 Signals from the Customer System ........................................................................................................ 48
10.2.1 Engine Start ............................................................................................................................................ 48
10.2.2 Reset ...................................................................................................................................................... 48
10.2.3 Enable Synchronization (GCB) .............................................................................................................. 49
10.2.4 Enable Synchronization (MCB) .............................................................................................................. 49
10.2.5 Higher Speed .......................................................................................................................................... 50
10.2.6 Lower Speed .......................................................................................................................................... 50
10.2.7 Grid Backup Mode Active ....................................................................................................................... 51
10.2.8 Black Start GCB ..................................................................................................................................... 51
10.2.9 Lack of Cooling Water ............................................................................................................................ 52
10.2.10 Setpoint - Effective Power ...................................................................................................................... 52
10.2.11 Black Start MCB ..................................................................................................................................... 53
11 Start- / Stop Procedure ........................................................................................................................ 54
11.1 Start Sequence ....................................................................................................................................... 54
11.2 Stop Sequence ....................................................................................................................................... 56
11.3 Emergency Stop Sequence .................................................................................................................... 57
11.4 Mains Parallel Operation ........................................................................................................................ 58
11.4.1 Engine Start ............................................................................................................................................ 58
11.4.2 Stopping the Engine ............................................................................................................................... 58
11.4.3 Grid Failure in Mains Parallel Operation ................................................................................................ 59
11.5 Grid Backup Mode .................................................................................................................................. 60
11.5.1 Engine is at a Standstill and a Grid Failure Occurs ................................................................................ 60
11.5.2 Operating Mode: Interruption at Grid Failure - Machine is running and a Grid Disturbance Occurs ..... 62
11.5.3 Operating Mode: No Interruption at Grid Failure - Machine is running and a Grid Disturbance Occurs 64
12 Software Communication .................................................................................................................... 66
12.1 General ................................................................................................................................................... 66
12.2 Data Protocol .......................................................................................................................................... 67
12.3 Alarm Messages ..................................................................................................................................... 68
12.4 Status Messages .................................................................................................................................... 68
12.5 Scaling of Values .................................................................................................................................... 69
12.6 Error Evaluation - External Communication ........................................................................................... 69
12.7 Ethernet (RJ45) with UDP Protocol - Standard ...................................................................................... 70
12.7.1 Presentation - UDP Protocol .................................................................................................................. 71
12.7.2 RFC 768 - Standard: User Datagram Protocol (UDP) ........................................................................... 72
13 Configuration and Service Wizard ...................................................................................................... 73
Pos: 2 /OX- Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Table of Contents
DK-SB-0002 / V03 / 08.04.2013 5
Pos : 3 /OX- Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Table of Contents
6 DK-SB-0002 / V03 / 08.04.2013
Pos : 4 /OX- Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
General
DK-SB-0002 / V03 / 08.04.2013 7
Pos : 5 /D okumentati on/ÜB-Ü berschriften/1/ÜB- Allgemei n @ 2\mod_1231765055200_433021.docx @ 433448 @ 1 @ 1
1 General Pos: 6 /D okumentati on/Beschrei bung/SB/M IP 4000/TX-Allgemein- 001 @ 7\mod_1263819268820_433021.docx @ 436141 @ @ 1
MTU Onsite Energy is responsible for interface clarification between engine and customer system. All interface signals between engine and customer system are operated by the MIP 4000. Pos: 7 /D okumentati on/Beschrei bung/SB/M IP 4000/TX-Allgemein- 002 @ 8\mod_1265208460082_0.docx @ 441263 @ @ 1
Pos: 8 /D okumentati on/Beschrei bung/SB/M IP 4000/TX-Allgemein- 003 @ 8\mod_1265208564258_433021.docx @ 436382 @ @ 1
No. Description
A Genset
B Engine interface
C Customer interface
D Customer system controller
Pos : 9 /D okumentati on/ÜB-Ü berschriften/1.1/ÜB- Gültig keit @ 18\mod_1332506523064_433021.docx @ 535242 @ 2 @ 1
1.1 Validity Pos: 10 /D okumentation/Beschr eibung/SB/MIP 4000/TX-Gültigkeit- 001 @ 18\mod_1332506212246_433021.docx @ 535238 @ @ 1
This document, Interface Description - MIP 4000 is valid from circuit diagram version and software version V2.2.0.0 Pos: 11 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Advantages - MIP 4000
8 DK-SB-0002 / V03 / 08.04.2013
Pos : 12 /D okumentation/Ü B-Überschriften/1/Ü B-Vorteile M IP 4000 @ 7\mod_1263821544083_433021.docx @ 436142 @ 1 @ 1
2 Advantages - MIP 4000 Pos: 13 /D okumentation/Beschr eibung/SB/MIP 4000/TX-Vorteil e-001 @ 7\mod_1263821690062_433021.docx @ 436143 @ @ 1
Complete design expertise through MTU Onsite Energy
Interface changes on the motor side (MIS) will be handled by MTU Onsite Energy: Minimal changes are required on the customer side.
Customer desires (e.g. software communication) can be handled by MTU Onsite Energy.
Software communication via Ethernet: „Bidirectional”.
Complete genset and protection integrated in the MIP 4000 and MIS: No guarantee restrictions.
Synchronization of generator circuit breakers (GCB) is integrated in the MIP 4000.
Synchronization of grid circuit breakers (MCB) integrated in the MIP 4000 - optional.
Grid monitoring integrated in the MIP 4000: (No protective function, without certificates for certain countries) - optional
Remote access for MTU Onsite Energy possible: Better product support. Pos: 14 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Scope of Service
DK-SB-0002 / V03 / 08.04.2013 9
Pos : 15 /D okumentation/Ü B-Überschriften/1/Ü B-Leistungsumfang @ 7\mod_1263822440722_433021.docx @ 436144 @ 1 @ 1
3 Scope of Service Pos: 16 /D okumentation/Beschr eibung/SB/MIP 4000/TX-Leistungsumfang-001 @ 18\mod_1333108024021_433021.docx @ 535858 @ @ 1
Communication with the Motor Interface Cabinet (MIS) via hardware signals and CAN Open.
Communication with the customer system via hardware signals and Ethernet.
Generator protection
Generator overvoltage / generator undervoltage
Generator over-frequency / generator under-frequency
Generator overcurrent / generator undercurrent - stage 1 and stage 2
Generator overload
Generator reverse power
Generator unbalanced load
Generator monitoring
Generator effective power - P (kW)
Generator reactive power - Q (kVAr)
Generator apparent power – S (kVA)
Generator frequency
Generator voltage U12, U23, U31
Generator current L1, L2, L3
Generator cos phi
Generator active energy (kWh)
Busbar monitoring
Busbar voltage U12, U23, U31
Busbar frequency
Grid monitoring
Grid voltage U12, U23, U31
Grid frequency
Synchronization
Generator circuit breaker (GCB): Only floating contacts, power section in the customer system.
Grid circuit breaker (MCB): Only floating contacts, power section in the customer system. Pos: 17 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Scope of Service
10 DK-SB-0002 / V03 / 08.04.2013
Pos : 18 /D okumentation/Beschr eibung/SB/MIP 4000/TX-Leistungsumfang-002 @ 18\mod_1333108121544_433021.docx @ 535887 @ @ 1
Generator temperature monitoring
Winding temperature monitoring and protection
Bearing temperature monitoring and protection
Gas system (monitoring and protection)
Gas pressure min / max (protection)
Activation of the gas leak test
Activation of the gas valves
General control functions - without power sections (only floating contacts or software signals)
Activation of the auxiliary drives
Activation of the lubricating oil solenoid valves
Activation of the pre-lubrication
Activation of the engine pre-warming Pos : 19 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Requirements of the Customer System
DK-SB-0002 / V03 / 08.04.2013 11
Pos : 20 /D okumentation/Ü B-Überschriften/1/Ü B-Anforderungen der Kundenanlage @ 7\mod_1263824492040_433021.docx @ 436146 @ 1 @ 1
4 Requirements of the Customer System Pos: 21 /D okumentation/Beschr eibung/SB/MIP 4000/TX-Anforderungen der Kundenanl age-001 @ 7\mod_1263824542961_433021.docx @ 436148 @ @ 1
Charging of the starter batteries (external location of the starter system, see installation guideline)
Provision of 24 VDC power supply for the MIP 4000 (a power failure under 21 V is not allowed; maximum voltage is 28.8 V. For rated voltage 24 VDC, 25 A must be made available).
Integration of safety relays (emergency stop buttons, safety transducers, etc.)
Integration of a grid protection device with the monitors
Grid over-frequency / grid under-frequency
Grid overvoltage / grid undervoltage
Vector shift
Asymmetry
Phase shift monitoring
Optional integration of a differential protection device
Optional integration of a ground fault protection device
Provision of the power sections for
Auxiliary drives
Lubricating oil solenoid valves
Fresh oil pump / old oil pump
Pre-lubrication
Engine pre-warming
Generator circuit breaker Pos: 22 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
12 DK-SB-0002 / V03 / 08.04.2013
Pos : 23 /D okumentation/Ü B-Überschriften/1/Ü B-Har dwaresignale @ 7\mod_1263825569147_433021.docx @ 436149 @ 1 @ 1
5 Hardware Signals Pos: 24 /D okumentation/Ü B-Überschriften/1.1/Ü B-MIP Digital e Eingänge @ 7\mod_1263825646772_433021.docx @ 436150 @ 2 @ 1
5.1 MIP - Digital inPuts Pos: 25 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Nothalt von Kundenanl age @ 7\mod_1263825722616_433021.docx @ 436151 @ 3 @ 1
5.1.1 Emergency Stop of Customer System
Pos: 26 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-012 @ 8\mod_1265712848474_433021.docx @ 436385 @ @ 1
A
B
C
A Digital input
B No emergency stop active
C Emergency stop active
Pos : 27 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-001 @ 7\mod_1263895591144_433021.docx @ 436155 @ @ 1
The machine will be stopped without delay. The auxiliary drives continue to remain activated. Pos: 28 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 13
Pos : 29 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-GLS ist Ein @ 7\mod_1263825785144_433021.docx @ 436152 @ 3 @ 1
5.1.2 GCB is On
Pos: 30 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-013 @ 8\mod_1265712971863_433021.docx @ 436386 @ @ 1
A
B
C
A Digital input
B Generator circuit breaker (GCB) opened
C Generator circuit breaker (GCB) closed
Pos : 31 /D okumentation/Sicher heit /SH- Sicherheitshinweise/SH-Hinweis /SH-H- 156 @ 13\mod_1307435849262_433021.docx @ 448466 @ @ 1
NOTICE
A fast, direct checkback is required from the generator circuit breaker (GCB).
SH
-H-1
56
Pos : 32 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
14 DK-SB-0002 / V03 / 08.04.2013
Pos : 33 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Netzstörung von Kundenanlage @ 7\mod_1263896367171_433021.docx @ 436157 @ 3 @ 1
5.1.3 Grid failure from the Customer System
Pos: 34 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-006 @ 7\mod_1263908708907_433021.docx @ 436171 @ @ 1
A
B
C
A Digital input
B No grid failure active
C Grid failure active
If a grid failure in grid backup operation is detected via this input, the generator circuit breaker (GCB) of the MIP 4000 will be opened.
Particularity in the event of grid disconnect via the grid circuit breaker (MCB) for uninterruptible grid backup operation:
The grid disconnect via the grid circuit breaker (MCB) occurs through the customer system. In this case the signal, "grid failure from the customer system" must not be activated, otherwise in grid backup operation the generator circuit breaker (GCB) will be opened without delay and uninterruptible grid backup operation is not possible. For this mode it must be ensured that the grid disconnect is provided via the grid circuit breaker (MCB) in the customer system. Malfunction can cause damage to the machine and the generator. Pos: 35 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 15
Pos : 36 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-002 @ 8\mod_1265717904918_433021.docx @ 436387 @ @ 1
No. Description
001 Digital input
002 Customer system
003 Enable grid backup operation = contact closed: Grid disconnect occurs through MCB in the customer system.
004 Grid monitoring device. Contact opens at grid failure.
005 Execution of pure grid backup operation or execution of grid backup operation with interruption.
006 Execution of grid backup mode without interruption. Important: For this mode it must be ensured that the grid disconnect is provided via the grid circuit breaker (MCB) in the customer system.
Pos : 37 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
16 DK-SB-0002 / V03 / 08.04.2013
Pos : 38 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Rückmel dung Gasventil 1 @ 7\mod_1263896422748_433021.docx @ 436158 @ 3 @ 1
5.1.4 Checkback - Gas Valve 1
Pos: 39 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-007 @ 7\mod_1263905587205_433021.docx @ 436169 @ @ 1
A
B
C
A Digital input
B Gas valve 1 closed
C Gas valve 1 open
After activation of the output "Request gas valve 1" this checkback must be signaled by the end position switch of the gas valve. Pos : 40 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 17
Pos : 41 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Rückmel dung Gasventil 2 @ 7\mod_1263896467342_433021.docx @ 436159 @ 3 @ 1
5.1.5 Checkback - Gas Valve 2
Pos: 42 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-008 @ 7\mod_1263905786550_433021.docx @ 436170 @ @ 1
A
B
C
A Digital input
B Gas valve 2 closed
C Gas valve 2 open
After activation of the output "Request gas valve 2" this checkback must be signaled by the end position switch of the gas valve. Pos : 43 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
18 DK-SB-0002 / V03 / 08.04.2013
Pos : 44 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Rückmel dung Gasdruck min @ 7\mod_1263903185651_433021.docx @ 436160 @ 3 @ 1
5.1.6 Checkback - Gas Pressure Min
Pos: 45 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-009 @ 7\mod_1263908964824_433021.docx @ 436172 @ @ 1
A
B
C
A Digital input
B Gas pressure OK active
C Gas pressure < min active
The gas pressure switch "min" must be installed upstream of the gas valves. Pos: 46 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 19
Pos : 47 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Rückmel dung Gasdruck max @ 7\mod_1263903243041_433021.docx @ 436163 @ 3 @ 1
5.1.7 Checkback - Gas Pressure Max
Pos: 48 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-010 @ 7\mod_1263909029008_433021.docx @ 436173 @ @ 1
A
B
C
A Digital input
B Gas pressure OK active
C Gas pressure > max active
The gas pressure switch "max" must be installed upstream of the gas valves. Pos: 49 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
20 DK-SB-0002 / V03 / 08.04.2013
Pos : 50 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Rückmel dung Gasdichtheitspr üfung ok @ 7\mod_1263903304790_433021.docx @ 436164 @ 3 @ 1
5.1.8 Checkback - Gas Leak Test OK
Pos: 51 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-011 @ 7\mod_1263909113659_433021.docx @ 436174 @ @ 1
A
B
C
A Digital input
B Gas leak test OK active
C Gas leak test not OK active
After request for the gas leak test by the MIP 4000, this checkback must be signaled within an adjustable time (e.g. 30 s, parameter is assigned in the MIP 4000) otherwise the start procedure will be interrupted. Pos: 52 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 21
Pos : 53 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-NLS is t Ei n @ 7\mod_1263903850146_433021.docx @ 436165 @ 3 @ 1
5.1.9 MCB is On
Pos: 54 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ei ngänge-014 @ 8\mod_1265718894374_433021.docx @ 436388 @ @ 1
A
B
C
A Digital input
B Main circuit breaker (MCB) open
C Main circuit breaker (MCB) closed
Pos : 55 /D okumentation/Sicher heit /SH- Sicherheitshinweise/SH-Hinweis /SH-H- 158 @ 13\mod_1307436833015_433021.docx @ 448524 @ @ 1
NOTICE
A fast, direct checkback is required from the main circuit breaker (MCB).
SH
-H-1
58
Pos : 56 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
22 DK-SB-0002 / V03 / 08.04.2013
Pos : 57 /D okumentation/Ü B-Überschriften/1.1/Ü B-MIP Digital e Ausg äng e @ 7\mod_1263910425059_433021.docx @ 436179 @ 2 @ 1
5.2 MIP - Digital Outputs Pos: 58 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-NOT-H ALT @ 7\mod_1263910190529_433021.docx @ 436176 @ 3 @ 1
5.2.1 Emergency Stop
Pos: 59 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 001 @ 18\mod_1332507784647_433021.docx @ 535296 @ @ 1
B
C
A
Max. contact current capacity:
24 VDC 10 A
220 VDC 0.22 A
230 VAC 6 A
B Emergency stop active
C No emergency stop active
In the event of an active emergency stop the generator circuit breaker (GCB) will be opened automatically by the MIP 4000. Pos : 60 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 23
Pos : 61 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-GLS Befehl schließen @ 7\mod_1263910230529_433021.docx @ 436177 @ 3 @ 1
5.2.2 GCB Command Close
Pos: 62 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 002 @ 7\mod_1263910716385_433021.docx @ 436181 @ @ 1
B
C
A
Max. contact current capacity:
24 VAC 8 A
220 VDC 0.12 A
230 VAC 8 A
B No "close" command is active
C "Close" command is active
After satisfying the connection requirements the MIP 4000 outputs a close pulse for the generator circuit breaker (GCB). Parameters can be assigned for the pulse length of the close contact (standard: 250 milliseconds). Pos: 63 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
24 DK-SB-0002 / V03 / 08.04.2013
Pos : 64 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-NLS Befehl schließen @ 7\mod_1263910297247_433021.docx @ 436178 @ 3 @ 1
5.2.3 MCB Command Close
Pos: 65 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 003 @ 7\mod_1263910856540_433021.docx @ 436182 @ @ 1
B
C
A
Max. contact current capacity:
24 VAC 8 A
220 VDC 0.12 A
230 VAC 8 A
B No "close" command is active
C "Close" command is active
After satisfying the connection requirements the MIP 4000 outputs a close pulse for the main circuit breaker (MCB). Parameters can be assigned for the pulse length of the close contact (standard: 250 milliseconds). This signal is required for a grid backup system for the return-synchronization of the MCB. A black start for the MCB is possible from MIP 4000 version 2. Pos: 66 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 25
Pos : 67 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-GLS Befehl öffnen @ 7\mod_1263911051305_433021.docx @ 436183 @ 3 @ 1
5.2.4 GCB Command Close
Pos: 68 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 004 @ 7\mod_1263911134461_433021.docx @ 436184 @ @ 1
Switch with undervoltage tripping device (UTD)
No. Description
A
Max. contact current capacity:
24 VDC 5.8 A
220 VDC 0.12 A
230 VAC 6 A
001 GCB "open" command active
002 No GCB "open" command active
Pos : 69 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
26 DK-SB-0002 / V03 / 08.04.2013
Pos : 70 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 005 @ 7\mod_1263911284756_433021.docx @ 436185 @ @ 1
Switch with undervoltage tripping device (UTD) and work current tripping device (WCTD)
No. Description
A
Max. contact current capacity:
24 VDC 5.8 A
220 VDC 0.12 A
230 VAC 6 A
001 GCB "open" command active
002 No GCB "open" command active
Pos : 71 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 006 @ 7\mod_1263911378318_433021.docx @ 436186 @ @ 1
The GCB will be opened by the MIP 4000 at the conditions specified below:
No. Description
1 A generator protection monitor has been activated.
1 Input "grid failure from the customer system" has been opened in grid backup mode.
2 In grid backup mode the software signal "engine start" has been reset and the electrical power drops below a minimum value for which parameters can be assigned (default: 1%).
2 Red alarm (immediate stop) without ramp active.
2 Red alarm (controlled stop) with ramp active. Electrical power drops below a minimum value for which parameters can be set (default: 1%).
2 Software signal "enable synchronization GCB" has been reset.
Pos : 72 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 27
Pos : 73 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Backupschutz @ 7\mod_1263911916627_433021.docx @ 436187 @ 3 @ 1
5.2.5 Backup Protection - GCB cannot be Opened
Pos: 74 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 007 @ 7\mod_1263994977827_433021.docx @ 436194 @ @ 1
B
C
A
Max. contact current capacity:
24 VDC 5.8 A
220 VDC 0.18 A
230 VAC 6 A
B No backup protection active
C Backup protection active
Backup protection is activated when the generator circuit breaker (GCB) cannot be opened by the MIP 4000. In this case the customer system controller must open a higher-level switch. Pos: 75 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
28 DK-SB-0002 / V03 / 08.04.2013
Pos : 76 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Anforderung Hilfsantriebe @ 7\mod_1263994247926_433021.docx @ 436188 @ 3 @ 1
5.2.6 Request Auxiliary Drives
Pos: 77 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 008 @ 7\mod_1263995128404_433021.docx @ 436195 @ @ 1
B
C
A
Max. contact current capacity:
24 VDC 5.8 A
220 VDC 0.18 A
230 VAC 6 A
B No request
C Request for auxiliary drives active
The contact is closed at a start command and will only be opened when the engine is at a standstill and the afterrun time has elapsed.
The customer system controller must activate the appropriate auxiliary drives (pumps, room ventilation, etc.). Pos: 78 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 29
Pos : 79 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Anforderung Schmi eröl magnetventil e @ 7\mod_1263994301785_433021.docx @ 436189 @ 3 @ 1
5.2.7 Request Lubricating Oil Solenoid Valves
Pos: 80 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 009 @ 7\mod_1263995263463_433021.docx @ 436196 @ @ 1
B
C
A
Max. contact current capacity:
24 VDC 5.8 A
220 VDC 0.18 A
230 VAC 6 A
B No request
C Request for top up active
The request for the lubricating oil solenoid valves is activated, if the oil top-up trips due to reduced oil level. The machine must be in operation for at least 5 minutes.
If the request for the lubricating oil solenoid valves is set too often, an alarm becomes active. The request is activated in a pulse/pause ratio (adjustable in the MIP 4000). The oil is topped up via a fresh oil pump or from a fresh oil tank in the appropriate installed height. Pos: 81 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
30 DK-SB-0002 / V03 / 08.04.2013
Pos : 82 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Anforderung Gasdichtheits tes t @ 7\mod_1263994401753_433021.docx @ 436190 @ 3 @ 1
5.2.8 Request Gas Leak Test
Pos: 83 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 010 @ 7\mod_1263995634733_433021.docx @ 436197 @ @ 1
B
C
A
Max. contact current capacity:
24 VAC 8 A
220 VDC 0.12 A
230 VAC 8 A
B No request
C Request gas leak test active
The request is activated at every start. Pos: 84 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 31
Pos : 85 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Anforderung Gasmagnetventil 1 @ 7\mod_1263994457503_433021.docx @ 436191 @ 3 @ 1
5.2.9 Request Gas Valve 1
Pos: 86 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 011 @ 18\mod_1332508235492_433021.docx @ 535325 @ @ 1
B
C
A
Max. contact current capacity:
24 VAC 20 A
110 VDC 0.15 A
400 VAC 9 A
B No request
C Request gas valve 1 active
With request the gas valve 1 must open. Pos: 87 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
32 DK-SB-0002 / V03 / 08.04.2013
Pos : 88 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Anforderung Gasmagnetventil 2 @ 7\mod_1263994509783_433021.docx @ 436192 @ 3 @ 1
5.2.10 Request Gas Valve 2
Pos: 89 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 012 @ 18\mod_1332508446892_433021.docx @ 535354 @ @ 1
B
C
A
Max. contact current capacity:
24 VAC 20 A
250 VDC 0.5 A
440 VAC 12 A
B No request
C Request gas valve 2 active
With request the gas valve 2 must open. Pos: 90 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 33
Pos : 91 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Rückmel dung NOT-HALT @ 18\mod_1332508884643_433021.docx @ 535412 @ 3 @ 1
5.2.11 Checkback - Emergency Stop
Pos: 92 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 015 @ 18\mod_1332509158072_433021.docx @ 535441 @ @ 1
B
C
A
Max. contact current capacity:
24 VDC 10 A
220 VDC 0.22 A
230 VAC 6 A
B Emergency stop active
C No emergency stop active
This signal indicates the status of the emergency stop of the customer system.
The signal is intended for the return circuit of the emergency stop customer system controller. Pos : 93 /OX-Seitenumbruch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
34 DK-SB-0002 / V03 / 08.04.2013
Pos : 94 /D okumentation/Ü B-Überschriften/1.1/Ü B-MIP Analoge Ei ngänge @ 7\mod_1263996826207_433021.docx @ 436202 @ 2 @ 1
5.3 MIP - Analog Inputs Pos: 95 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Generator wickl ungstemperatur U 1 @ 7\mod_1263997569874_433021.docx @ 436206 @ 3 @ 1
5.3.1 Generator Winding Temperature - U1
Pos: 96 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 97 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Anal oge Eing äng e-001 @ 7\mod_1263996962456_433021.docx @ 436203 @ @ 1 */
The generator winding temperature U1 can be designed as PT1000 or PT100 and is monitored for limit value overshoot and wire break. Pos: 98 /D okumentation/Ü B-Überschriften/1.1.1/Ü B-Generator wickl ungstemperatur V1 @ 7\mod_1263997649014_433021.docx @ 436207 @ 3 @ 1 2
5.3.2 Generator Winding Temperature - V1
Pos: 99 /D okumentation/Beschr eibung/SB/MIP 4000/TX-MIP Digitale Ausgänge- 013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 100 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Analog e Eingänge- 002 @ 7\mod_1263997163908_433021.docx @ 436204 @ @ 1
The generator winding temperature V1 can be designed as Pt1000 or Pt100 and is monitored for limit value overshoot and wire break. Pos: 101 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 35
Pos : 102 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Generator wickl ungstemper atur W1 @ 7\mod_1263997717733_433021.docx @ 436208 @ 3 @ 1
5.3.3 Generator Winding Temperature - W1
Pos: 103 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Digital e Ausgänge-013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 104 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Analog e Eingänge- 003 @ 7\mod_1263997396422_433021.docx @ 436205 @ @ 1
The generator winding temperature W1 can be designed as PT1000 or PT100 and is monitored for limit value overshoot and wire break. Pos: 105 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Generatorlag ertemperatur Antriebssei te @ 7\mod_1263997998465_433021.docx @ 436209 @ 3 @ 1
5.3.4 Generator Bearing Temperature - Drive Side
Pos: 106 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Digital e Ausgänge-013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 107 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Analog e Eingänge- 004 @ 7\mod_1263998619877_433021.docx @ 436210 @ @ 1
The generator winding temperature - drive side - can be designed as PT1000 or PT100 and is monitored for limit value overshoot and wire break. Pos: 108 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
36 DK-SB-0002 / V03 / 08.04.2013
Pos : 109 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Generatorlag ertemperatur Nichtantriebssei te @ 7\mod_1264069585386_433021.docx @ 436215 @ 3 @ 1
5.3.5 Generator Bearing Temperature - Non-Drive Side
Pos: 110 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Digital e Ausgänge-013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 111 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Analog e Eingänge- 005 @ 7\mod_1264068165447_433021.docx @ 436211 @ @ 1
The generator winding temperature - non-drive side - can be designed as Pt1000 or Pt100 and is monitored for limit value overshoot and wire break. Pos: 112 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Hand-N OT-HALT-Tas ter @ 7\mod_1264068428227_433021.docx @ 436212 @ 2 @ 1
5.4 Manual Emergency Stop Buttons Pos: 113 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-H andnotaustaster-001 @ 7\mod_1264069129800_433021.docx @ 436213 @ @ 1
A manual emergency stop button is attached on the MIP 4000. The customer system controller must integrate this emergency stop switch in a tested safety chain. By activating the emergency stop button the safety chain must be tripped without delay. The digital "emergency stop from customer system" must also be opened. Pos: 114 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 37
Pos : 115 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-MIP 4000 Versorgungsspannung 24 VDC @ 7\mod_1264069498427_433021.docx @ 436214 @ 2 @ 1
5.5 MIP 4000 Supply Voltage - 24 VDC Pos: 116 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Versorgungsspannung 24 VDC- 001 @ 7\mod_1264069922532_433021.docx @ 436217 @ @ 1
A voltage drop under 21 VDC is not permitted; the maximum permissible voltage is 28.8 VDC.
It must be provided at rated voltage 24 VDC 25 A. Pos: 117 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
38 DK-SB-0002 / V03 / 08.04.2013
Pos : 118 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Ethernet-Kommuni kation über R J45 @ 7\mod_1264069815616_433021.docx @ 436216 @ 2 @ 1
5.6 Ethernet Communication via RJ45 Pos: 119 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Ether net-Kommuni kation über RJ45-001 @ 7\mod_1264070020934_433021.docx @ 436218 @ @ 1
No. Description
001 Crossed cable - CAT5
002 Customer CPU
For direct cabling: Use CAT5, crossed cable
No. Description
001 Switch
002 Customer CPU
003 1:1 cable CAT5
Cabling via switch: Use CAT5, 1:1 cable Pos: 120 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 39
Pos : 121 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Generatorstr ommesswandler 5 A @ 7\mod_1264070231584_433021.docx @ 436219 @ 2 @ 1
5.7 Generator Current Transformer 5 A Pos: 122 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Digital e Ausgänge-013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 123 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Gener atorstrommesswandl er-001 @ 7\mod_1264070455283_433021.docx @ 436221 @ @ 1
The current transformer terminals K are only grounded at a voltage greater than 1 kV.
Version 5 A or 1 A can be used as generator current transformers. Standard is 5 A.
If the current transformer is changed from 5 A to 1 A, cabling and parameters must be adapted in the MIP 4000.
The generator current converters are used to calculate the electrical effective power and for generator protection. Pos: 124 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
40 DK-SB-0002 / V03 / 08.04.2013
Pos : 125 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Generatorspannung @ 7\mod_1264070310645_433021.docx @ 436220 @ 2 @ 1
5.8 Generator Voltage Pos: 126 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Gener atorspannung-001 @ 7\mod_1264070609624_433021.docx @ 436224 @ @ 1
Version 400 VAC or 100 VAC can be used as generator voltage.
If the measurement voltage is changed from 400 VAC to 100 VAC, the parameters in the MIP 4000 must be adjusted.
The generator voltage is used to synchronize the generator circuit breaker (GCB) and for generator protection.
Synchronization - GCB: Busbar voltage ↔ generator voltage Pos: 127 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
DK-SB-0002 / V03 / 08.04.2013 41
Pos : 128 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Sammelschienenspannung @ 7\mod_1264070885198_433021.docx @ 436226 @ 2 @ 1
5.9 Busbar Voltage Pos: 129 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Sammelschienenspannung-001 @ 7\mod_1264070757512_433021.docx @ 436225 @ @ 1
Version 400 VAC or 100 VAC can be used as busbar voltage.
If the measurement voltage is changed from 400 VAC to 100 VAC, the parameters in the MIP 4000 must be adjusted.
The busbar voltage is used to synchronize the generator circuit breaker (GCB) and for the grid circuit breaker (MCB).
Synchronization GCB: Busbar voltage ↔ generator voltage
Synchronization MCB: Busbar voltage ↔ grid voltage Pos: 130 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Hardware Signals
42 DK-SB-0002 / V03 / 08.04.2013
Pos : 131 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Netzspannung @ 7\mod_1264070978400_433021.docx @ 436227 @ 2 @ 1
5.10 Grid Voltage Pos: 132 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-N etzspannung-001 @ 7\mod_1264071052727_433021.docx @ 436228 @ @ 1
Version 400 VAC or 100 VAC can be used as grid voltage.
If the measurement voltage is changed from 400 VAC to 100 VAC, the parameters in the MIP 4000 must be adjusted.
The grid voltage is used to synchronize the grid circuit breaker (MCB).
Synchronization MCB: Busbar voltage ↔ grid voltage Pos: 133 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Generator - PFC and AVR
DK-SB-0002 / V03 / 08.04.2013 43
Pos : 134 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Generator PFC und AVR @ 7\mod_1264071282553_433021.docx @ 436229 @ 1 @ 1
6 Generator - PFC and AVR Pos: 135 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Gener ator PFC und AVR- 001 @ 18\mod_1334065105079_433021.docx @ 536088 @ @ 1
The generator is equipped with a voltage regulator and a cos phi regulator (AVR and PFC).
The connection between cos phi regulator (PFC) and voltage regulator (AVR) is disconnected. Thus the cos phi regulator no longer has a function. The voltage regulator (AVR) gets the setpoint via an analog output of the MIP. Pos: 136 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Ansteuerung Spannungssr egler @ 18\mod_1332744899858_433021.docx @ 535537 @ 2 @ 1
6.1 Activation - Voltage Regulator Pos: 137 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-MIP Digital e Ausgänge-013 @ 7\mod_1263995922595_433021.docx @ 436200 @ @ 1
Cabled in the MIP 4000 scope of delivery! Pos: 138 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Ans teuerung Spannungsregler-001 @ 18\mod_1334065657870_433021.docx @ 536117 @ @ 1
The voltage and the cos phi can be variably changed by the MIP. The MIP regulates the voltage or the cos phi of the generator with an analog signal. The setpoints for the regulator and the appropriate control parameters can be set via the MIP. Pos : 139 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Generator Anti-Condensation Heating
44 DK-SB-0002 / V03 / 08.04.2013
Pos : 140 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Generatorstillstandsheizung @ 7\mod_1264082109991_433021.docx @ 436235 @ 1 @ 1
7 Generator Anti-Condensation Heating Pos: 141 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Gener atorstillstandsheizung-001 @ 7\mod_1264082378216_433021.docx @ 436237 @ @ 1
The generator is equipped with a heater (230 VAC, fuse: B6A). This heater must be activated under the following conditions:
Generator circuit breaker GCB opened
and machine at a standstill.
The cabling is not included in the MIP 4000: Execution occurs in the customer system! Pos: 142 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Overview - Cabling
DK-SB-0002 / V03 / 08.04.2013 45
Pos : 143 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Übersicht Ver kabelung @ 7\mod_1264084128083_433021.docx @ 436238 @ 1 @ 1
8 Overview - Cabling Pos: 144 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-Ü bersicht Ver kabelung-001 @ 8\mod_1265724658300_433021.docx @ 436390 @ @ 1
No. Description
A Remote access (DSL)
B Customer system controller
Pos : 145 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-Ü bersicht Ver kabelung-002 @ 8\mod_1265724759486_433021.docx @ 436391 @ @ 1
No. Description
A Customer interface
A Grid voltage, generator voltage, busbar voltage (100 VAC or 400 VAC)
A 24 VDC supply
A Software communication (Ethernet)
A Checkbacks / specifications (from the customer)
A Requests (to the customer)
B Generator
B Generator current transformers (1 A or 5 A)
B Winding temperatures (U, V, W)
B Bearing temperatures
B Generator anti-condensation heater (230 VAC)
Pos : 146 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Overview - Gas System
46 DK-SB-0002 / V03 / 08.04.2013
Pos : 147 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Übersicht Gassystem @ 7\mod_1264084483909_433021.docx @ 436239 @ 1 @ 1
9 Overview - Gas System Pos: 148 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-Ü bersicht Gassys tem- 001 @ 8\mod_1265725200731_433021.docx @ 436392 @ @ 1
No. Description
001 Customer
002 Checkback - gas valve V1 (open)
003 Checkback - gas pressure min.
004 Checkback - leak test OK
005 Request leak test
006 Checkback - gas valve V2 (open)
007 Checkback - gas pressure max.
Pos : 149 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
DK-SB-0002 / V03 / 08.04.2013 47
Pos : 150 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Softwaresig nal e @ 7\mod_1264084604642_433021.docx @ 436240 @ 1 @ 1
10 Software Signals Pos: 151 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Signale zur Kundenanl age @ 7\mod_1264084686283_433021.docx @ 436241 @ 2 @ 1
10.1 Signals to the Customer System Pos: 152 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Anfor derung Vorschmi erung @ 7\mod_1264085043155_433021.docx @ 436244 @ 3 @ 1
10.1.1 Request Pre-Lubrication
Pos: 153 /Dokumentati on/Besc hrei bung/SB/MIP 4000/TX- Signal e zur Kundenanl age-001 @ 7\mod_1264084936734_433021.docx @ 436243 @ @ 1
High signal: Request pre-lubrication
Pos : 154 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Anfor derung Motor vorwär mung @ 7\mod_1264085132498_433021.docx @ 436245 @ 3 @ 1
10.1.2 Request Engine Pre-Heating
Pos: 155 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e zur Kundenanl age-002 @ 7\mod_1264085216373_433021.docx @ 436246 @ @ 1
High signal: Request engine pre-heating
The request for engine pre-heating is set depending on the engine cooling water exit temperature. The engine pre-warming is activated when the temperature limit value is underranged. The customer system controller must activate the cooling water pump, so that a cooling water differential pressure of 0.7 bar is built up after 10 seconds. If this differential pressure is not built up the alarm "fault engine oil pre-warming" will be output and the request for engine oil pre-warming will be reset.
After a time for which parameters can be assigned, the request for engine pre-warming will be reactivated. Pos: 156 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
48 DK-SB-0002 / V03 / 08.04.2013
Pos : 157 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Signale von Kundenanl age @ 7\mod_1264084850078_433021.docx @ 436242 @ 2 @ 1
10.2 Signals from the Customer System Pos: 158 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Motorstart @ 7\mod_1264162331631_433021.docx @ 436247 @ 3 @ 1
10.2.1 Engine Start
Pos: 159 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-001 @ 7\mod_1264162848988_433021.docx @ 436250 @ @ 1
High signal: Start command
Low signal: No start command, stop procedure is activated.
To enable grid backup mode, in addition the "grid backup mode active" signal is required. Pos: 160 /Dokumentati on/Sicherheit/SH-Sicher heitshi nweise/SH-Hinweis/SH-H-159 @ 13\mod_1307436906137_433021.docx @ 448553 @ @ 1
NOTICE
The start procedure will not be executed if stop messages from the engine (red alarm) are active.
The start procedure will not be executed if the digital input "emergency stop from customer system" is activated. S
H-H
-159
Pos : 161 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Reset @ 7\mod_1264162387584_433021.docx @ 436248 @ 3 @ 1
10.2.2 Reset
Pos: 162 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-002 @ 7\mod_1264163417781_433021.docx @ 436251 @ @ 1
High signal: To acknowledge active alarms, a pulse with a pulse length of at least 1 second is expected.
Pos : 163 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
DK-SB-0002 / V03 / 08.04.2013 49
Pos : 164 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Freigabe Synchronisier ung ( GLS) @ 7\mod_1264164834899_433021.docx @ 436254 @ 3 @ 1
10.2.3 Enable Synchronization (GCB)
Pos: 165 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-003 @ 7\mod_1264164108777_433021.docx @ 436252 @ @ 1
High signal: Enable synchronization
Pos : 166 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-004 @ 7\mod_1264164164429_433021.docx @ 436253 @ @ 1
After the machine has reached rated speed and is stabilized, synchronization will be started with the signal "enable synchronization (GCB). The triggered synchronization can also be stopped again by the customer system controller by setting the signal to low. If this signal is reset while the generator circuit breaker (GCB) is closed, then the GCB will be opened. Pos: 167 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Freigabe Synchronisier ung (N LS) @ 7\mod_1264165033835_433021.docx @ 436255 @ 3 @ 1
10.2.4 Enable Synchronization (MCB)
Pos: 168 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-005 @ 7\mod_1264167035026_433021.docx @ 436263 @ @ 1
Is only required for a grid backup system! Pos: 169 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-006 @ 7\mod_1264167209431_433021.docx @ 436264 @ @ 1
High signal: Enable synchronization (MCB)
Pos : 170 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-007 @ 7\mod_1264167343680_433021.docx @ 436265 @ @ 1
The machine is in grid backup mode (GCB is closed, MCB is opened), no grid failure is active: The return synchronization of the MCB will be triggered with the signal "enable synchronization (MCB)". This sequence corresponds to the return synchronization without interruption. The triggered synchronization can also be stopped again by the customer system controller by setting the signal to low. Pos: 171 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
50 DK-SB-0002 / V03 / 08.04.2013
Pos : 172 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Drehzahl höher @ 7\mod_1264165095679_433021.docx @ 436256 @ 3 @ 1
10.2.5 Higher Speed
Pos: 173 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-008 @ 7\mod_1264167464320_433021.docx @ 436266 @ @ 1
High signal: Higher speed (minimum pulse length 100 ms)
Pos : 174 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-009 @ 7\mod_1264167542476_433021.docx @ 436267 @ @ 1
In grid backup mode the speed specification can be influenced by the customer system controller. This is typically used for effective load distribution in isolated parallel operation or for return synchronization of higher-level circuit breakers. The engine speed is increased automatically if this signal is activated. Pos: 175 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Drehzahl ti efer @ 7\mod_1264165386521_433021.docx @ 436257 @ 3 @ 1
10.2.6 Lower Speed
Pos: 176 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-010 @ 7\mod_1264167641162_433021.docx @ 436268 @ @ 1
High signal: Lower speed (minimum pulse length 100 ms)
Pos : 177 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-011 @ 7\mod_1264167734615_433021.docx @ 436269 @ @ 1
In grid backup mode the speed specification can be influenced by the customer system controller. This is typically used for effective load distribution in isolated parallel operation or for return synchronization of higher-level circuit breakers. The engine speed is decreased automatically if this signal is activated. Pos: 178 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
DK-SB-0002 / V03 / 08.04.2013 51
Pos : 179 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Netzersatzbetrieb akti v @ 7\mod_1264165465989_433021.docx @ 436258 @ 3 @ 1
10.2.7 Grid Backup Mode Active
Pos: 180 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-005 @ 7\mod_1264167035026_433021.docx @ 436263 @ @ 1
Is only required for a grid backup system! Pos: 181 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-012 @ 7\mod_1264167811989_433021.docx @ 436270 @ @ 1
High signal: Grid backup mode is activated.
Pos : 182 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-013 @ 7\mod_1264167913833_433021.docx @ 436271 @ @ 1
To enable grid backup mode this signal must be activated. To trigger grid backup mode, in the event of grid failure the signal, "grid backup mod active" and "engine start" are used as the start command. Pos: 183 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-014 @ 7\mod_1264168019018_433021.docx @ 436272 @ @ 1
Additional functions:
If grid backup mode is triggered by engine standstill, then the auxiliary drives (cooling water pump, etc.) will not be supplied for certain time due to a lack of generator voltage / busbar voltage.
Consequently with this signal, certain alarms will be delayed for parameter-assignable time, to prevent engine shut-off due to temperature monitors / pressure monitors. Pos: 184 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Schwarzs tart GLS @ 7\mod_1264165521567_433021.docx @ 436259 @ 3 @ 1
10.2.8 Black Start GCB
Pos: 185 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-005 @ 7\mod_1264167035026_433021.docx @ 436263 @ @ 1
Is only required for a grid backup system! Pos: 186 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-015 @ 7\mod_1264168161949_433021.docx @ 436273 @ @ 1
High signal: Black start GCB active
Pos : 187 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-016 @ 7\mod_1264168219477_433021.docx @ 436274 @ @ 1
The following conditions must be satisfied to close the generator circuit breaker (GCB) without synchronization:
Busbar is de-energized.
MCB is open.
GCB is open.
Signal "enable synchronization (GCB)" is activated.
Signal "black start GCB" is activated.
The machine has reached rated speed and is stabilized. Pos: 188 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
52 DK-SB-0002 / V03 / 08.04.2013
Pos : 189 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Kühl wassermangel @ 7\mod_1264165569066_433021.docx @ 436260 @ 3 @ 1
10.2.9 Lack of Cooling Water
Pos: 190 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-017 @ 7\mod_1264168765762_433021.docx @ 436275 @ @ 1
High signal: There is a lack of cooling water
The cooling water level drops under minimum. The machine will be stopped. Pos: 191 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Sollwert Wir kleis tung @ 7\mod_1264165619285_433021.docx @ 436261 @ 3 @ 1
10.2.10 Setpoint - Effective Power
Pos: 192 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-018 @ 7\mod_1264168874620_433021.docx @ 436276 @ @ 1
Range: 0.0 to 100.0%
In grid backup mode a setpoint is expected for the electrical effective power. After the GCB is closed, the power ramp becomes active. The parameters of the power ramp (load / offload in % / s) can be set in the MIP 4000. A power ramp is not required in the customer system.
Monitor - minimum power:
It is not permitted to operate the machine for a longer period of time under minimum power (default is 30%). If the external setpoint is specified under this minimum power, then after a period of time, the alarm "LO minimum load" will be active. In this case the customer system must then specify a setpoint above the minimum power.
Stop activated:
At an activated stop the setpoint must not be set to 0%. Offloading of the power ramp will be executed automatically by the MIP 4000. Pos: 193 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Signals
DK-SB-0002 / V03 / 08.04.2013 53
Pos : 194 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Schwarzs tart NLS @ 7\mod_1264165682144_433021.docx @ 436262 @ 3 @ 1
10.2.11 Black Start MCB
Pos: 195 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-005 @ 7\mod_1264167035026_433021.docx @ 436263 @ @ 1
Is only required for a grid backup system! Pos: 196 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-019 @ 7\mod_1264416634546_433021.docx @ 436277 @ @ 1
Possible from MIP 4000 version 2!
High signal: Black start MCB active
Pos : 197 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Signal e von Kundenanlag e-020 @ 7\mod_1264416743171_433021.docx @ 436278 @ @ 1
The following conditions must be satisfied to close the main circuit breaker (MCB) without synchronization:
Busbar is de-energized.
MCB is open.
GCB is open.
Signal "enable synchronization (MCB)" is activated.
Signal "black start MCB" is activated.
No grid failure active Pos: 198 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
54 DK-SB-0002 / V03 / 08.04.2013
Pos : 199 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Start- / Stoppablauf @ 2\mod_1231512970323_433021.docx @ 433447 @ 1 @ 1
11 Start- / Stop Procedure Pos: 200 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Startabl auf @ 7\mod_1264417196902_433021.docx @ 436279 @ 2 @ 1
11.1 Start Sequence Pos: 201 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Startablauf- 001 @ 8\mod_1268136046849_433021.docx @ 436523 @ @ 1
Start preconditions 1
Grid backup mode: Start command with signal "engine start" No engine stop message (red alarm) is active
Grid backup mode: If there is a grid fault "start command", the signal "grid backup mode active", and "engine start" are required to trigger grid backup mode.
No engine stop message (red alarm) is active
No start
Phase 1
Activate auxiliary drives with signal "request auxiliary drives".
Start gas leak test with signal "request gas leak test".
Start preconditions 2 Gas leak test OK with signal "checkback gas leak
test OK.
Start abort
Phase 2 Gas valves open with signal "request gas valve 1"
and "request gas valve 2".
Concerning start condition 3
Start- / Stop Procedure
DK-SB-0002 / V03 / 08.04.2013 55
Start preconditions 3 Gas valves are opened with signal "checkback gas
valve 1" and "checkback gas valve 2".
Start abort
Phase 3
Rated speed is reached
Monitoring of generator voltage and generator frequency
Activate run-on time for auxiliary drives
Start preconditions 4 (Generator voltage > limit value) and (Generator
frequency > limit value)
Start abort
Phase 4
Enable synchronization GCB with signal "enable synchronization (GCB)"
In addition grid backup mode and de-energized busbar the signal "black start GCB" is also required.
Start preconditions 5 Generator circuit breaker must be on and the time
monitor must not yet have elapsed
Start abort
Grid parallel: Monitoring of power regulation, ramp
Island operation: Activate island mode (frequency controller)
Pos : 202 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
56 DK-SB-0002 / V03 / 08.04.2013
Pos : 203 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Stoppabl auf @ 7\mod_1264417310198_433021.docx @ 436280 @ 2 @ 1
11.2 Stop Sequence Pos: 204 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Stoppabl auf-001 @ 8\mod_1268139142461_433021.docx @ 436524 @ @ 1
Phase 0
Genset in operation and stop pending.
Stop at:
Signal "engine start" has been reset (controlled stop)
Red alarm via ramp (controlled stop)
Red alarm without ramp (immediate stop)
Stop condition 0 Slow stop (ramp function) or
Fast stop (open switch)
Fast stop: Jump to phase 2 immediately
Slow stop:
Phase 1 Genset is relieved of load (ramp function)
Stop condition 1 Minimum power underranged
Remains in phase 1
To phase 2
Start- / Stop Procedure
DK-SB-0002 / V03 / 08.04.2013 57
Phase 2
Open generator circuit breaker with signal "GCB open".
Activate speed control.
Gas valves close with signal "request gas valve 1" and "request gas valve 2".
Start afterrun time for auxiliary drives (signal "request auxiliary drives)
Genset ready to start
Pos : 205 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-NOT-Hal t-Ablauf @ 7\mod_1264417382416_433021.docx @ 436281 @ 2 @ 1
11.3 Emergency Stop Sequence Pos: 206 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-N otstoppablauf-001 @ 8\mod_1268139755743_433021.docx @ 436526 @ @ 1
Phase 1
Genset in operation and emergency stop pending. Emergency stop if:
Emergency stop button has been activated
Emergency stop of the engine is active
Signal "emergency stop from customer system" is activated.
Gas valves close with signal "request gas valve 1" and "request gas valve 2".
Open generator circuit breaker with signal "GCB command open".
Activate speed control.
Start afterrun time for auxiliary drives (signal "request auxiliary drives).
Pos : 207 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
58 DK-SB-0002 / V03 / 08.04.2013
Pos : 208 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Netzparall elbetrieb @ 7\mod_1264417448588_433021.docx @ 436282 @ 2 @ 1
11.4 Mains Parallel Operation Pos: 209 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Motorstart @ 7\mod_1264162331631_433021.docx @ 436247 @ 3 @ 1
11.4.1 Engine Start
Pos: 210 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-N etzpar allel betrieb-001 @ 7\mod_1264421952510_433021.docx @ 436285 @ @ 1
1. To start, the signal "engine start" must be set to high.
2. After the genset has reached the rated speed, the signal, "enable GCB" must be set to high. The generator circuit breaker will then be synchronized. The triggered synchronization can also be stopped again by the customer system controller by setting the signal to low. If this signal is reset when the generator circuit breaker (GCB) is closed, then the GCB opens.
3. After the generator circuit breaker closes mains parallel operation is immediately active. The electrical effective power is specified via the signal, "setpoint effective power".
Pos : 211 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Abstellen des Motors @ 7\mod_1264421776114_433021.docx @ 436283 @ 3 @ 1
11.4.2 Stopping the Engine
Pos: 212 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-N etzpar allel betrieb-002 @ 7\mod_1264423714939_433021.docx @ 436286 @ @ 1
1. In mains parallel operation, the signal "engine start" must be set to low. The engine will now be
offloaded via power ramp. Important: The signal "enable synchronization (GCB)" must continue to remain on high, otherwise the generator circuit breaker GCB will be activated.
2. With a parameter-assignable power value (default 1%) the generator circuit breaker GCB will be opened. After the generator circuit breaker has been opened, the signal, "enable GCB" must be set to low. The engine will be stopped.
Pos : 213 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
DK-SB-0002 / V03 / 08.04.2013 59
Pos : 214 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Netzstörung im Netzpar allelbetri eb @ 7\mod_1264421832908_433021.docx @ 436284 @ 3 @ 1
11.4.3 Grid Failure in Mains Parallel Operation
Pos: 215 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-N etzpar allel betrieb-003 @ 7\mod_1264423923406_433021.docx @ 436287 @ @ 1
The following procedure applies when grid backup mode is not enabled via the signal "grid backup mode active".
1. In mains parallel operation the signals "engine start" and "enable GCB" are set to high.
A grid failure is detected via the signal "grid failure from customer system". The generator circuit breaker (GCB) will be opened.
2. If this only involves a brief interruption (SI), then the generator circuit breaker GCB will connected resynchronized. If an actual grid failure is involved the engine will be stopped. After the grid failure has ended, the grid stabilization timer is started (adjustable timer). After the grid stabilization timer has elapsed, the engine is enabled.
Pos : 216 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
60 DK-SB-0002 / V03 / 08.04.2013
Pos : 217 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Netzersatzbetrieb @ 15\mod_1319535872740_433021.docx @ 488264 @ 2 @ 1
11.5 Grid Backup Mode Pos: 218 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Motor steht und Netzstörung tritt auf @ 7\mod_1264424784885_433021.docx @ 436288 @ 3 @ 1
11.5.1 Engine is at a Standstill and a Grid Failure Occurs
Pos: 219 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX-N etzersatzbetri eb- 001 @ 8\mod_1268140154649_433021.docx @ 436527 @ @ 1
Machine is at a standstill phase 0
Signal "engine start" = high
Signal "enable GCB" = low
Grid backup enabled via signal "enable grid backup mode" (= high).
The engine will be started.
Machine is at a standstill phase 1
If the rated speed is reached, the grid circuit breaker (MCB) must be opened by the customer system controller.
Machine is at a standstill phase 2
If both switches (GCB and MCB) are opened, the generator circuit breaker will be switched to de-energized busbar, if the signal "enable synchronization (GCB)" (= high) and "black start GCB" (= high) is activated. If the busbar is not de-energized, because it is already supplied by a different genset, the generator circuit breaker will be connected synchronized.
Concerning machine is at a standstill phase 3
Start- / Stop Procedure
DK-SB-0002 / V03 / 08.04.2013 61
Machine is at a standstill phase 3
Grid backup mode is active if the grid circuit breaker GCB is open and the generator circuit breaker (GLS) is closed => frequency regulation in the MIP 4000 is activated.
Via the signals "higher speed" and "lower speed" load balancing can be executed in island parallel mode with multiple engines.
Mode interruption at grid failure
No interruption at grid failure Machine running phase 2
No interruption at grid failure Machine running phase 4
Pos : 220 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
62 DK-SB-0002 / V03 / 08.04.2013
Pos : 221 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Betriebsart U nterbrechung bei Netzaus fall @ 7\mod_1264424862353_433021.docx @ 436289 @ 3 @ 1
11.5.2 Operating Mode: Interruption at Grid Failure - Machine is running and a Grid Disturbance Occurs
Pos: 222 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Betriebsart Unter brechung bei Netzausfall-001 @ 8\mod_1268141454065_433021.docx @ 436529 @ @ 1
Machine running phase 0
Signal "engine start" = high
Signal "enable synchronization (GCB)" = high
Grid backup enabled via signal "grid backup operation active" (= high).
Grid failure active via the signal "grid failure from customer system":
Generator circuit breaker will be opened.
Machine running phase 1
Generator circuit breaker (GCB) is opened. If this only involves a brief interruption (SI), then the generator circuit breaker GCB will connected resynchronized.
If a real grid failure is involved, the grid circuit breaker (MCB) must be opened by the customer system controller.
Machine running phase 2
If both switches (GCB + MCB) are opened, the generator circuit breaker will be switched to de-energized busbar, if the signal "enable synchronization (GCB)" (= high) and "black start GCB" (= high) is activated. If the busbar is not de-energized, because it is already supplied by a different genset, then the generator circuit breaker will be connected synchronized.
Machine running phase 3
Grid backup mode is active if the grid circuit breaker MCB is open and the generator circuit breaker (GCB) is closed: Frequency regulation in the MIP 4000 is activated.
Via the signals "higher speed" and "lower speed" load balancing can be executed in island parallel mode with multiple engines.
Continue with machine running phase 4
Start- / Stop Procedure
DK-SB-0002 / V03 / 08.04.2013 63
Machine running phase 4
Grid failure no longer active via the signal "grid failure from customer system":
Return synchronization of the grid circuit breaker MCB occurs in two ways:
Interruption-free
Variant 1: When the grid failure is resolved, the grid stabilization time will be started (adjustable timer). After the grid stabilization time has elapsed and the signal "enable synchronization (MCB)" (= high) has been activated, the grid circuit breaker (MCB) will be synchronized. If within this time another grid failure occurs, the return synchronization will be interrupted and grid backup mode will be continued. After the generator circuit breaker has been opened, the signal, "enable synchronization (GCB)" must be set to low.
Variant 2: The grid circuit breaker MCB can be return synchronized by the customer system controller. To do this, the signals "higher speed" and "lower speed" must be used.
With interruption:
When the grid failure is resolved, the grid stabilization time will be started (adjustable timer). After the grid stabilization timer has elapsed, the signal, "enable synchronization (GCB)" (= low) must be withdrawn. The generator circuit breaker (GCB) will be opened through this measure.
Variant 1: With activated signal "enable synchronization (MCB)" (= high) and "black start MCB" (= high) the grid circuit breaker MCB will be closed if the busbar is de-energized. If the grid circuit breaker MCB is closed, the signal, "enable synchronization (MCB)" must be set to low.
Variant 2: The grid circuit breaker MCB can be closed by the customer system controller.
The generator circuit breaker MCB will now be re-synchronized with the signal "enable synchronization (MCB)" (= high).
Grid backup mode
If both circuit breakers (GCB + MCB) are closed, at activated signals ("engine start" (= high) and signal "enable synchronization (GCB)" (= high), grid backup mode will be continued.
Pos : 223 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Start- / Stop Procedure
64 DK-SB-0002 / V03 / 08.04.2013
Pos : 224 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Betriebsart Kei ne Unter brechung bei N etzausfall @ 7 \mod_1264424974727_433021.docx @ 436290 @ 3 @ 1
11.5.3 Operating Mode: No Interruption at Grid Failure - Machine is running and a Grid Disturbance Occurs
Pos: 225 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Betriebsart Keine U nterbr echung bei N etzausfall-001 @ 8\mod_1268143759868_433021.docx @ 436532 @ @ 1
Machine running phase 0
Signal "engine start" = high
Signal "enable synchronization (GCB)" = high
Grid backup enabled via signal "grid backup operation active" (= high).
A grid fault is detected by the customer system controller: The grid circuit breaker MCB must be closed by the customer system controller. The signal "grid fault from customer system" must not be activated. Otherwise the generator circuit breaker GCB will be opened without delay and interruption-free grid backup mode is not possible.
Machine running phase 1
Grid backup mode is active if the grid circuit breaker MCB is open and the generator circuit breaker (GCB) is closed: Frequency regulation in the MIP 4000 is activated.
Via the signals "higher speed" and "lower speed" load balancing can be executed in island parallel mode with multiple engines.
Machine running phase 2
Return synchronization of the grid circuit breaker MCB occurs in two ways:
Interruption-free
Variant 1: When grid power is restored, the signal "enable synchronization (MCB)" (=high) is activated, this synchronizes the grid circuit breaker (MCB). If the generator circuit breaker is closed, the signal, "enable synchronization (MCB)" must be set to low.
Variant 2: The grid circuit breaker MCB can be return synchronized by the customer system controller. To do this, the signals "higher speed" and "lower speed" must be used.
With interruption:
At return of grid power the signal "Enable synchronization (MCB)" (= low) must be withdrawn. The generator circuit breaker (GCB) will be opened through this measure.
Variant 1: With activated signal "enable synchronization (MCB)" (= high) and "black start MCB" (= high) the grid circuit breaker MCB will be closed if the busbar is de-energized. If the generator circuit breaker is closed, the signal, "enable synchronization (MCB)" must be set to low.
Variant 2: The grid circuit breaker MCB can be closed by the customer system controller.
Start- / Stop Procedure
DK-SB-0002 / V03 / 08.04.2013 65
The generator circuit breaker MCB will now be re-synchronized with the signal "enable synchronization (MCB)" (= high).
Grid parallel mode
If both circuit breakers (GCB + MCB) are closed, at activated signals ("engine start" (= high) and signal "enable synchronization (GCB)" (= high), grid backup mode will be continued.
Pos : 226 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
66 DK-SB-0002 / V03 / 08.04.2013
Pos : 227 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Softwarekommuni kati on @ 7\mod_1264425173632_433021.docx @ 436291 @ 1 @ 1
12 Software Communication Pos: 228 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Allgemei n @ 3\mod_1234366181035_433021.docx @ 434398 @ 2 @ 1
12.1 General Pos: 229 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-001 @ 18\mod_1332753314388_433021.docx @ 535628 @ @ 1
All data (temperatures, alarm messages, status messages, etc.) is available in the interface protocol. The communication interfaces are set up to bidirectional operation.
Deviations from the standard protocol (e.g. special commands, setpoint specifications, etc.) must be clarified as needed. Adaptations will be billed based on time and materials.
The software in the external system will not be adjusted by MTU Onsite Energy.
The data length in MIP 4000 interface protocol version 1 is 320 bytes.
The data length in MIP 4000 interface protocol version 2 is 640 bytes.
All data is data type "INTEGER (-32768 to + 32767). For the binary values, the data point is queried for status 0/1 bit by bit: 16 binary values (BOOL) per data point.
Pos: 230 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
DK-SB-0002 / V03 / 08.04.2013 67
Pos : 231 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Datenpr otokoll @ 7\mod_1264425854534_433021.docx @ 436292 @ 2 @ 1
12.2 Data Protocol Pos: 232 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-002 @ 18\mod_1332753413309_433021.docx @ 535657 @ @ 1
The protocol is divided into several areas:
MIP 4000 interface protocol version 1:
Actual values (status) - 280 bytes (140 words):
Alarm messages
Status messages
Analog values / process values (actual values)
Control values to the outside
Setpoints (control) - 40 bytes (20 words):
Control values from the outside
Setpoints / actual values from the outside
MIP 4000 interface protocol version 2:
Actual values (status) - 600 bytes (300 words):
Alarm messages
Status messages
Analog values / process values (actual values)
Control values to the outside
Setpoints (control) - 40 bytes (20 words):
Control values from the outside
Setpoints / actual values from the outside
The data protocol is provided in a separate Excel list! Pos: 233 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
68 DK-SB-0002 / V03 / 08.04.2013
Pos : 234 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Stör mel dungen @ 2\mod_1233674518766_433021.docx @ 433752 @ 2 @ 1
12.3 Alarm Messages Pos: 235 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-003 @ 18\mod_1332753543744_433021.docx @ 535686 @ @ 1
The alarm messages are evaluated via the status 0/1. If there is a queued alarm message the appropriate bit is set to "1".
Example: Fault messages 8 and 14 are active: The data point has the status "00100000 10000000". Thus the individual fault messages can be easily masked (AND link).
Only MIP 4000 interface protocol version 1:
There are up to 1232 fault messages. These are transferred in 24 data words. 24 words for the fault messages and 1 word for the multiplexer are necessary to transfer all 1232 alarm messages:
Value - multiplexer (word 0)
Alarm message number (word 1 - 24)
1 1 - 384
2 385 - 768
3 769 - 1152
4 1153 - 1232
Pos : 236 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Betriebsmeldung en @ 15\mod_1319721818059_433021.docx @ 489948 @ 2 @ 1
12.4 Status Messages Pos: 237 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-004 @ 7\mod_1264427978630_433021.docx @ 436298 @ @ 1
The status messages are evaluated via the status 0/1. If there is a queued status message the appropriate bit is set to "1".
Example: Status messages 8 and 14 are active: The data point has the status "00100000 10000000". Thus the individual status messages can be easily masked (AND link). Pos: 238 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
DK-SB-0002 / V03 / 08.04.2013 69
Pos : 239 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Skalierung von Werten @ 7\mod_1264426932621_433021.docx @ 436295 @ 2 @ 1
12.5 Scaling of Values Pos: 240 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-005 @ 7\mod_1264498984346_433021.docx @ 436299 @ @ 1
Most values are provided with a so-called "scaling factor" (e.g. x 10). Thus it is possible to simulate a real number (floating point) on the opposite station.
Example:
Grid frequency 49.99 Hz
Unit / scaling factor Hz x 100
Data value: 4999
The receiving station reads out the value and must divide it by 100. Then the system can continue to work with a real number. Pos: 241 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Fehler auswertung exter ne Kommuni kation @ 7\mod_1264426990340_433021.docx @ 436296 @ 2 @ 1
12.6 Error Evaluation - External Communication Pos: 242 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-006 @ 18\mod_1332753787922_433021.docx @ 535715 @ @ 1
MIP 4000 interface protocol version 1:
To check the function of the interface, in the last status value (word 140), a value is written cyclically that is expected back on the setpoints in the last word (word 20). If this does not happen, after approx. 1 second the controller will be deactivated via the interface and a alarm message will be output.
MIP 4000 interface protocol version 2:
To check the function of the interface, in the last status value (word 300), a value is written cyclically that is expected back on the setpoints in the last word (word 20). If this does not happen, after approx. 1 second the controller will be deactivated via the interface and a alarm message will be output. Pos: 243 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
70 DK-SB-0002 / V03 / 08.04.2013
Pos : 244 /Dokumentati on/ÜB-Ü berschrif ten/1.1/Ü B-Ethernet RJ45 mit UD P-Pr otokoll - Standard @ 7\mod_1264500002114_433021.docx @ 436301 @ 2 @ 1
12.7 Ethernet (RJ45) with UDP Protocol - Standard Pos: 245 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-007 @ 18\mod_1332754320178_433021.docx @ 535744 @ @ 1
With this interface data can be read from an Ethernet UDP station or data can be sent to an Ethernet UDP station.
As opposed to the other interfaces for Ethernet UDP at the beginning of the send and receive telegram a header with 2 bytes is added.
This headed contains the number of the module (module 1 has the number 1; module 2 has the number 2, etc.)
Designation Standard set value
Baud rate (external): e.g. 100 Mbit/s
Protocol: UDP (User Datagram Protocol) in accordance with RFC 768, Internet protocol
Transmission mode (viewed from the MMC)
1 = receive mode 2 = transmit mode 3 = receive and transmit mode The MIP uses receive and transmit mode.
Cable: CAT 5 Cable 1:1: A switch must be used. Direct communication with external CPU: A crossed cable must be used.
IP address (B&R CPU): 192.168.10.211. Additional CPUs have an offset of 1 (e.g. 192.168.10.212).
Port (B&R CPU): 21101 Additional CPUs have an offset of 1 (e.g. 21102).
IP address (receiving station): Must be reachable with the subnet mask 255.255.254.0.
Port (receiving station): Same port as for CPU (21101)
Telegram header: 2 bytes (module number)
Receive data as viewed from the MMC:
MIP interface protocol version 1: 280 bytes (data is written from the MIP) + 2 byte header.
MIP interface protocol version 2: 600 bytes (data is written from the MIP) + 2 byte header.
Transmission data as viewed from the MMC:
40 bytes (data is written from the MIP) + 2 byte header.
Send/transmit cycle: 50 ms
Pos : 246 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
DK-SB-0002 / V03 / 08.04.2013 71
Pos : 247 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-Darstellung UDP- Protokoll @ 7\mod_1264508592266_433021.docx @ 436303 @ 3 @ 1
12.7.1 Presentation - UDP Protocol
Pos: 248 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-008 @ 18\mod_1332754480936_433021.docx @ 535773 @ @ 1
Receive data as viewed from the MMC:
MIP 4000 interface protocol version 1:
Payload data bytes (282 bytes)
Telegram header (2 byte)
Fault messages (50 bytes)
Status messages (30 bytes)
Analog values / process values (196 bytes)
Control commands to the outside (4 bytes)
MIP 4000 interface protocol version 2:
Payload data bytes (602 bytes)
Telegram header (2 byte)
Fault messages (154 bytes)
Status messages (30 bytes)
Analog values / process values (410 bytes)
Control commands to the outside (6 bytes)
Pos : 249 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-009 @ 7\mod_1264509064216_433021.docx @ 436305 @ @ 1
Transmission data as viewed from the MMC:
Payload data bytes (42 bytes)
Telegram header (2 bytes)
Control commands to the MIP (4 bytes)
Setpoints to the MIP (36 bytes)
Data stream:
Low byte High byte Low byte High byte
Binary signal
Low byte High byte
BIT BIT
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Pos : 250 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Software Communication
72 DK-SB-0002 / V03 / 08.04.2013
Pos : 251 /Dokumentati on/ÜB-Ü berschrif ten/1.1.1/Ü B-RFC 768 - Standar d: User D atagram Protocol (UD P) @ 7\mod_1264509258934_433021.docx @ 436306 @ 3 @ 1
12.7.2 RFC 768 - Standard: User Datagram Protocol (UDP)
Pos: 252 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-010 @ 7\mod_1264509361246_433021.docx @ 436307 @ @ 1
The User Datagram Protocol (UDP) enables packet-switched communication in a contiguous computer network. The prerequisite for this protocol is that the Internet protocol (IP) must be used as the underlying protocol. With this protocol messages from user programs can be sent to other programs; in this process only a minimum protocol is used. The protocol works without connection. There is no guarantee that packet, once sent, will also arrive. Applications that require a reliable provision of data streams should use the transmission control protocol, (TCP).
0 78 15 16 23 24 31
Source port Destination port
Length Checksum
Data ....
User data header format
Pos : 253 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Softwarekommuni kation-011 @ 7\mod_1264509502963_433021.docx @ 436308 @ @ 1
Fields:
Source port: The source port indicates the port number of the sending process. This information is required so that the receiver can respond to the packet. Because UDP is connectionless, the source port is optional and can be set to the value "0".
Destination port: The destination port specifies which process the packet should receive.
Length: The length indicates the size of the packet, consisting of the data and the header, in octets. The smallest possible value is 8 octets.
Checksum The checksum is a 16-bit checksum and is formed via the so-called pseudo header and the data.
The pseudo header is conceptually placed in front of the UDP header and contains the source address, the destination address and the UDP length. This information provides protection against incorrectly routed packets. This checksum procedure is the same as used in TCP.
0 7 8 15 16 23 24 31
Source address
Destination address
Zero Protocol UDP length
Pos : 254 /OX-Seitenumbr uch @ 0\mod_1218433559331_0.docx @ 441052 @ @ 1
Configuration and Service Wizard
DK-SB-0002 / V03 / 08.04.2013 73
Pos : 255 /Dokumentati on/ÜB-Ü berschrif ten/1/Ü B-Konfigurati on und Ser vice Wizard @ 7\mod_1264509878914_433021.docx @ 436309 @ 1 @ 1
13 Configuration and Service Wizard Pos: 256 /Dokumentati on/Beschrei bung/SB/MIP 4000/TX- Konfigur ati on und Ser vice Wizar d-001 @ 7\mod_1264509952492_433021.docx @ 436310 @ @ 1
No. Description
A MIP-CPU with 2 Ethernet interfaces
B Engine interface
C Customer interface
D
Customer PC / wizard
Setting the Ethernet IP address
Setting MIP values (parameters, time, etc.)
Online values
Alarm logger
etc.
There are 2 Ethernet interfaces available on the CPU:
The first interface is provided for communication with the customer system controller.
The second interface can be used for remote access.
The wizard pages can be called up via the installed VNC server in the MIP CPU. For this shared use of the first interface via a switch is standard. On the customer side, a VNC viewer is required on the computer. === Ende der Liste für Textmar ke Inhalt ===
74 DK-SB-0002 / V03 / 08.04.2013
DK-SB-0002 / V03 / 08.04.2013 75
76 DK-SB-0002 / V03 / 08.04.2013
MTU Onsite Energy GmbH Postfach 10 21 30 • 86011 Augsburg Dasinger Str. 11 • 86165 Augsburg Tel.: +49 (0)821 / 7480-0 Fax: +49 (0)821 / 7480-2119 Internet: http://www.mtu-online.com
Europe / Middle East / Africa / Latin America Asia / Australia / Pacific USA / Canada / Mexico
MTU Friedrichshafen GmbH 88040 Friedrichshafen Germany Phone +49 7541 90 7001 Fax +49 7541 90 7081 [email protected] www.mtu-online.com
MTU Asia Pte. Ltd. 1, Benoi Place Singapore 629923, Republic of Singapore Phone +65 6861 5922 Fax +65 6861 3615 [email protected] www.mtu-online.com
MTU Detroit Diesel, Inc. 13400 Outer Drive West Detroit, Michigan 48239, USA Phone +1 313 592 7000 Fax +1 313 592 7788 [email protected] www.mtu-online.com