Upload
toing
View
65
Download
4
Embed Size (px)
DESCRIPTION
Instruction Manual of Capacitor Voltage Transformers
Citation preview
1
Instruction Manual of Capacitor Voltage Transformers 0GR.463.354-2010
1 Technical characteristics
Capacitor voltage tranformers (hereinafter referred to as “CVTs”) have the
following characteristics:
a)Iron core “C” technology makes CVTs more stable and reliable.
b)Rapid-saturable damp technique can effectively suppress ferro-resonance and keep
three-phase open-delta residual voltage below 1V.
c)Residual voltage of transient response can be below 5%. This is able to meet the
requirements of quick relay protection device.
d)The quality is reliable due to good dielectric and insulation material, advanced
design and vacuum impregnation, and excellent partial discharge.
e)CVTs do not need to be made maintenance, oil filter and oil change, oil sample
inspection during normal service.
2 Purpose and applicable range
2.1 Purpose
CVTs series is used for high-voltage, extra-high voltage, ultra-high voltage power
system at rated frequency 50Hz. They are intended to provide voltage signal for electrical
measurement instrument, protection and control device, and as a coupling capacitor for
carrier coupling device for power line.
2.2 Applicable range
CVTs are installed outdoor. Ambient air temperature for installation and operation
area is -40℃ to +55℃. Altitude does not exceed 2000m.(if altitude exceeds 2000m, CVTs
can be specially manufactured in accordance with the purchaser after agreed between the
purchaser and manufacturer). Wind velocity is not more than 150km/h. Earthquake
intensity does not exceed 8 without serious pollution, vibration and bump.
3 Type and main technical data
3.1 Description of type
When the subscript (serial number of design) is double-digit, it represents euipped with
2
intermediate earthing switch.
When the last letter is “TH” or “G”, it respectively represents damp tropics and plateau.
T YD 3 66/ 3 0.02 H F
non-effectively earthed neutral antipollution rated capacitance μF rated phase voltage kV serial number of design
capacitor voltage transformer equipment
Note: Serial number of design represents that number of secondary winding. In case of 3, represents
that number of secondary winding of the product is 3. In case of 13, represents that the product is
equipped with intermediate earthing switch and number of secondary winding is 3.
3.2 Main technical data
3.2.1 CVTs can continuoulsy operate at 1.2 times rated primary voltage. CVTs for
effectively earthed neutal system can operate for 30s at 1.5 times rated primary voltage.
CVTs for auto tripping non-earthed neutral system without earth fault can operate for 8h at
1.9 times rated primary voltage.
3.2.2 Connection group of intermediate transformer winding is 1/1/1-12-12 or
1/1/1/1-12-12-12 or 1/1/1/1/1-12-12-12-12。
3.2.3 Creepage distance of the product having a “H” in the type is not less than 25mm/kV
(calculated on system highest voltage). Special creepage distance is given in annotations of
certificate of product.
3.2.4 Insulation level of CVTs are given in Table 1.
3.2.5 Accuracy class and corresponding voltage error, phase angle error, and operating
conditions of CVTs are given in Table 2.
3
Table 1 Insulation Level of CVTs kV
Rated primary voltage 35/ 3 66/ 3 110/ 3 115/ 3 132/ 3 150/ 3 220/ 3 230/ 3 275/ 3 330/ 3 400/ 3 500/ 3 765/ 3 1000/ 3
System rated voltage 35 66 110 115 132 150 220 230 275 330 400 500 750 1000
System highest voltage 40.5 72.5 126 123 145 170 252 245 300 363 420 550 800 1100
Rated short duration
power-frequency withstand
voltage
(r.m.s)1min
95 160 200 230 275 325 395 460 460 510 520 740 9751300
(5 min)
Rated lightning impulse
withstand voltage
(peak)1.2/50μs
200 350 480 550 650 750 950 1050 1050 1175 1425 1675 2100 2400
Rated switching impusle
withstand voltage
(peak)250/2500μs
- - - - - - - - 850 950 1050 1175 1550 1800
Table 2 Operating Conditions and Error Limit Value of CVTs Measuring accuracy class Protection accuracy
Item 0.2 0.5 1.0 3.0 3P 6P
Voltage error(%) ±0.2 ±0.5 ±1.0 ±3.0 ±3.0 ±6.0 Error limit
value Phase displacement error(′)
±10 ±20 ±40 Not
specified±120 ±240
Voltage(%) 80~120 5~150 (or 5~190)Permissible frequency range(%)
99~101 96~102
Permissible temperature range
Lower to upper limit temperature of temperature category
Burden(%) 25~100
Operating
conditions
Burden power factor 0.8(lagging) Note:The value in brackets is applied to CVTs for neutral non-effectively earthed system.
3.2.6 Carrier capacitance of capacitor divider C, and tolerance of high-voltage capacitance
C1 and intermediate capacitance C2 shall be -5% to +10% of ratings. The error between
tolerance of C1 and C2 does not exceed 5%.
3.2.7 Tangent of loss angle of capacitor divider ( tanδ) is not more than 0.0012.
3.2.8 CVTs shall conform to GB/T 4703《Capacitor Voltage Transformers》.
3.2.9 Main technical data of CVTs are given in Table 3.
4 Operating theory and main structure
4.1 Operating theory
CVT is divided voltage by capacitor divider. Intermediate transformer changes intermediate
4
voltage to secondary voltage. The sum of reactance of compensation reactor and leakage
reactance of CVT, and equivalent capacitive reactance [)C(C
121+ω] in serial resonance can
eliminate voltage variation due to capacitive reactance voltage drop with the change of
secondary burden. This can make voltage stable. The electrical principle diagram is given in
Figure 1.
4.2 Main structure
CVTs have two kinds of structure of combination single stack and separation. Both of them
consist of capacitor divider and electromagnetic unit. The capacitor divider consists of one or
more section capacitors in series. Line terminals are on the top of capacitor divider.
Figure 1 Electrical principle diagram Where, C —— Carrier capacitance
1a1n——Secondary 1a1n winding terminal C1 —— High-voltage capacitance 2a2n—— Secondary 2a2n winding terminal C2 —— Intermediate capacitance dadn —— Residual voltage winding terminal
Up —— Primary voltage XL—— Low-voltage terminal of compensation reactor
A′—— Intermediate terminal —— Earthing terminal
T—— Intermediate transformer N—— Carrier communication terminal(low-voltage terminal,not exposed weather) L—— Compenstiaon reactor D —— Damp device P—— Protection device J—— Carrier combination device with arresters(provided by purchaser)
S—— Intermediate earthing switch (distribute when the purchaser requires)
5
The electromagnetic unit consists of intermediate transformer, compensation reactor
and damp device(ferro-resonance suppression) mounted in the tank. Secondary winding
terminals and carrier communication terminals are leaded by outgoing terminal box on the
face of the tank.
CVTs equipped with intermediate earthing switch belong to special products. Please
specify them when ordering. Intermediate earthing switch is mounted on the wall of the tank.
5 Lifting and storage
5.1 Lifting single section capacitor is necessary during packing, devanning, testing and
erection, etc. For CVTs having a 220kV and up to 220kV, it is not permissible that more
section capacitors are stacked to lift.
5.2 During transportation and storage, CVTs have to keep right side up, preventing from
collision and other mechanical hurt. CVTs shall be stored a place where ambient air
temperature is -40℃ to +55℃, without flammability, explosion, corrosion and vibration.
6 Installation and commissioning
6.1 CVTs shall be mounted on solid horizontal base in accordance with clause 2.2.
Connection between CVTs and the base is fixed by screws, nuts and washers. Connection
between capacitors is also fixed by screws, nuts and washers.
6.2 Line terminals on primary side of CVTs is connection board on the top cover of
capacitor divider. Terminal N, in secondary outgoing box, is connected with carrier coupling
device or directly “ ”. (During operation, this terminal has to directly connected with “ ”
by connection sheets provided by manufacturer. As carrier communication, this terminal is
connected in series to the carrier coupling device, then disconnect connection sheets). The
tank must be solidly directly connected to the ground. Secondary circuit is made an electrical
joint by secondary outgoing terminals in outgoing box.
6.3 Capcitor divider and electromagnetic unit of each ex-factory CVT have been adjusted
the error, so the CVT shall not be exchangeable each other.
6.4 Intermediate earthing switch is short-circuited connected with intermediate transformer
for the CVT testings at site. The handle of intermediate earthing switch during CVT service
6
has to fix at “normal operation”, otherwise intermediate transformer is short-circuited
connected. It is prohibited from using intermediate earthing switch at energization.
Schematic diagram of the handle is given in Figure 8.
6.5 CVTs are energized as long as mechanical and electrical joints are correct and reliable.
6.6 Internal terminal “ ” in secondary outgoing terminal box has connected with the tank.
7 Service and safety
7.1 Service conditions of CVTs shall be in accordance with clause 2.2, 3.2.4, 3.2.5.
7.2 When communication terminal N is regarded as carrier communication, it is
earthed through carrier combination device. Otherwise, it is directly connected to the
ground not to open circuit. When low-voltage terminal XL of compensation reactor is
operating, it must directly be connected to the ground to prohibit open circuit except
energization inspection.
7.3 After CVTs are cut off power supply to remove service, touch them after the electrical
conductive part is discharged many times by earth rod.
8 Maintenance
8.1 It is suggested that capacitance and tanδ value are checked once each year. During
inspection, ambient air temperature is 25℃±10℃. The device of capacitance and dielectric
loss measurement is higher than class 3. When the tolerance between capacitance and
measured value in certificate of product exceeds ±5% or tanδ exceeds 0.3%, CVTs shall
be stopped service.
8.2 CVTs are hermetically internally filled in insulating oil. Sealing state of CVTs is usually
checked during service. Inspection location is joint position among upper and lower cover
plate of the capacitor and porcelain bushings, and joint position between outgoing plate
inner secondary outgoing box and the tank. In case of leakage, CVTs shall be stopped
service.
8.3 Oil level in a visual window shall be usually checked during service. When CVTs are
operating at maximum ambient air temperature +55℃, it is natural that oil level does not
exceed maximum position of the window. When CVTs are operating at minimum ambient
7
air temperature -40℃, it is natural that oil level does not exceed minimum position of the
window. Once oil level exceeds maximum or mimimum position of the window, detect
whether capacitance and temperature rise of CVTs are abnormal. If the tolerance between
two measured capacitance of single section capacitor is 1%, CVTs shall be removed service
to make an inspection. Temperature rise of the same capacitor and electromagnetic unit of
the same product is compared, using infrared temperature measurement device. In case of
abnormal, CVTs shall be removed service to make an inspection.
During service, do not need to make oil filter, oil change and oil sample inspection.
8.4 Testing principle diagram of capacitance and tanδ measurement are given in Figure 9
to11. Capacitance and tanδ inspection are carried out by other correct methods.
Electrical principle diagram of capacitance and tanδ measurement on CVTs equipped
with intermediate earthing switch are made according to Figure 9 and 10. Electrical
principle diagram of capacitance and tanδ measurement on CVTs without intermediate
earth switch is given in Figue11. The measurement is carried out by other correct
methods.
At measurement, strictly conform to testing principle diagram and explanation.
8.5 CVTs are enclosed products, capacitor divider can not be separated from electromagnetic
unit unless the manufacturer agrees. During acceptance and service, do not make a withstand
voltage test on forming the whole of connecting lower section capacitor and electromagnetic
unit.
8.6 Burden of secondary windings shall be in the range of 25% to 100% of corresponding
rated burden. Residual voltage windings shall be equipped without burdens during normal
operation, otherwise error limit value of secondary output voltage do not guarantee a
specified range in Table 2.
8.7 During service, usually check whether mechanical and electrical joints of CVTs are
normal and reliable.
8.8 After CVTs are cut off power supply to remove service, touch them after the electrical
conductive part is discharged many times by earth rod.
8
9 Common faults and solution
9.1 The tank oil leakage of electromagnetic unit of CVTs. The tank oil leakage is usually
appeared on the edge around insulation board inner secondary outgoing box. The
solution is that tighten surrounding sealing screws.
9.2 Terminal N on the insulation board has discharged to the earthing tank. Burning
insulation board is not directly connected to “ ” because terminal N is not regarded as
carrier communication.
10 List of supply of CVTs is given in Table 4.
11 Type selection of CVTs
If only rated primary voltage, rated capacitance, number of secondary winding, voltage
and accuracy class/burden of each secondary winding are determined, type of CVTs is
selected.
For example, known rated primary voltage of 110/ 3 kV, rated capacitance of
0.01μF, 3 secondary windings, respective voltage of 0.1/ 3 kV, 0.1/ 3 kV, 0.1 kV,
corresponding accuracy class/burden: 0.2/50VA, 0.5/50VA, 3P/50V,then item 11 CVT
TYD3110/√3-0.01H in Table 3 can satisfy the requirments. In case of equipped with
intermediate earthing switch, please select TYD13110/ 3 -0.01H.
Special design is able to be carried out in accordance with the purchaser.
9
Table 3 Main Technical Data of CVTs
SN Type
Rated
voltage
kV
Rated
capacitance
μF
Accuracy
class/
secondary
burden VA
Outline and
installation
(hole)
dimension(mm)
L×W1×H,
ΦA,L1×W2
Outline
drawing
Weight
kg
CG
H Height
h
mm
1* TYD235/ 3 -0.01HF
35/ 3
0.1/ 3
0.1/3
0.01 1a1n:0.2/20
dadn:3P/100
2* TYD335/ 3 -0.01HF
35/ 3
0.1/ 3
0.1/ 3
0.1/3
0.01
1a1n:0.2/10
2a2n:0.5/20
dadn:3P/100
3 TYD235/ 3 -0.02HF
35/ 3
0.1/ 3
0.1/3
0.02 1a1n:0.2/30
dadn:3P/100
4
TYD335/ 3 -0.02HF
35/ 3
0.1/ 3
0.1/ 3
0.1/3
0.02
1a1n:0.2/20
2a2n:0.5/20
dadn:3P/100
760×φ685×1490
4×φ25
Pitch of holes
500×500
480 610
5*
TYD366/ 3 -0.01HF
66/ 3
0.1/ 3
0.1/ 3
0.1/3
0.01
1a1n:0.2/10
2a2n:0.5/20
dadn:3P/100
6*
TYD366/ 3 -0.015HF
66/ 3
0.1/ 3
0.1/ 3
0.1/3
0.015
1a1n:0.2/20
2a2n:0.5/20
dadn:3P/100
7
TYD366/ 3 -0.02HF
66/ 3
0.1/ 3
0.1/ 3
0.1/3
0.02
1a1n:0.2/20
2a2n:0.5/20
dadn:3P/100
760×φ685×2100
4×φ25
Pitch of holes
500×500
642 800
8*
TYD2110/ 3 -0.007H
TYD12110/ 3 -0.007H
110/ 3
0.1/ 3
0.1 0.007
an:0.2/50
dadn:3P/100
670×φ590×2040
4×φ25
Pitch of holes
480×480
480
800
9*
TYD3110/ 3 -0.007H
TYD13110/ 3 -0.007H
110/ 3
0.1/ 3
0.1/ 3
0.1
0.007
1a1n:0.2/50
2a2n:0.5/75
dadn:3P/100
760×φ685×2100
4×φ25
Pitch of holes
550×550
490
800
10
TYD2110/ 3 -0.01H
TYD12110/ 3 -0.01H
110/ 3
0.1/ 3
0.1 0.01
an:0.2/50
dadn:3P/100
670×φ590×2040
4×φ25
Pitch of holes
480×480
480
800
11
TYD3110/ 3 -0.01H
TYD13110/ 3 -0.01H
110/ 3
0.1/ 3
0.1/ 3
0.1
0.01
1a1n:0.2/50
2a2n:0.5/75
dadn:3P/100
490
800
12 TYD4110/ 3 -0.01H
TYD14110/ 3 -0.01H
110/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.01
1a1n:0.2/50
2a2n:0.5/50
3a3n:0.5/50
dadn:3P/100
510
800
13*
TYD3110/ 3 -0.015H
TYD13110/ 3 -0.015H
110/ 3
0.1/ 3
0.1/ 3
0.1
0.015
1a1n:0.2/75
2a2n:0.5/100
dadn:3P/100
760×φ685×2100
4×φ25
Pitch of holes
550×550
Figure 2
500 800
10
Table 3(continued)
SN Type
Rated
voltage
kV
Rated
capacitance
μF
Accuracy class/
secondary burden
VA
Outline and
installation
(holes)
dimension(mm)
L×W1×H,
ΦA,L1×W2
Outline
drawing
Weight
kg
CG
Height
h
mm
14
TYD3110/ 3 -0.02H
TYD13110/ 3 -0.02H
110/ 3
0.1/ 3
0.1/ 3
0.1
0.02
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
760×φ685×2100
4×φ25
Pitch of holes
550×550
610
800
15 TYD4110/ 3 -0.02H
TYD14110/ 3 -0.02H
110/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.02
1a1n:0.2/50
2a2n:0.5/50
3a3n:0.5/50
dadn:3P/100
760×φ685×2120
4×φ25
Pitch of holes
550×550
715
800
16*
TYD3110/ 3 -0.025H
TYD13110/ 3 -0.025H
110/ 3
0.1/ 3
0.1/ 3
0.1
0.025
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
760×φ685×2100
4×φ25
Pitch of holes
550×550
610
800
17*
TYD4110/ 3 -0.025H
TYD14110/ 3 -0.025H
110/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.025
1a1n:0.2/75
2a2n:0.5/75
3a3n:3P/75
dadn:3P/100
760×φ685×2080
4×φ25
Pitch of holes
550×550
715
800
18*
TYD3110/ 3 -0.04H
TYD13110/ 3 -0.04H
110/ 3
0.1/ 3
0.1/ 3
0.1
0.04
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
760×φ685×2130
4×φ25
Pitch of holes
550×550
740
1000
19* TYD2115/ 3 -0.01H
115/ 3
0.1/ 3
0.1
0.01 an:0.2/50
dadn:3P/100
670×φ590×2000
4×φ25
Pitch of holes
480×480
460
800
20* TYD3132/ 3 -0.015H
132/ 3
0.1/ 3
0.1/ 3
0.1
0.015
1a1n:0.2/75
2a2n:0.5/100
dadn:3P/100
760×φ685×2335
4×φ30
Pitch of holes
550×550
Figure 2
740
1100
21*
TYD2220/ 3 -0.0035H
TYD12220/ 3 -0.0035H
220/ 3
0.1/ 3
0.1
0.0035 an:0.2/50
dadn:3P/100
670×φ590×3354
4×φ25
Pitch of holes
480×480
668
1340
22*
TYD3220/ 3 -0.0035H
TYD13220/ 3 -0.0035H
220/ 3
0.1/ 3
0.1/ 3
0.1
0.0035
1a1n:0.2/50
2a2n:
0.5/100
dadn:3P/100
760×φ685×3390
4×φ25
Pitch of holes
550×550
780
1375
23
TYD2220/ 3 -0.005H
TYD12220/ 3 -0.005H
220/ 3
0.1/ 3
0.1
0.005 an:0.2/50
dadn:3P/100
660×φ590×3354
4×φ25
Pitch of holes
480×480
668
1340
24
TYD3220/ 3 -0.005H
TYD13220/ 3 -0.005H
220/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/50
2a2n:0.5/75
dadn:3P/100
760×φ685×3390
4×φ25
Pitch of holes
550×550
780
1375
25
TYD4220/ 3 -0.005H
TYD14220/ 3 -0.005H
220/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/50
2a2n:0.5/50
3a3n:0.5/50
dadn:3P/100
760×φ685×3390
4×φ25
Pitch of holes
550×550
Figure 3
780
1375
11
Table 3(continued)
SN Type
Rated
voltage
kV
Rated
capacitance
μF
Accuracy
class/
secondary
burden VA
Outline and
installation
(holes)
dimension(mm)
L×W1×H,
ΦA,L1×W2
Outline
drawing
Weight
kg
CG
Height
h
mm
26*
TYD3220/ 3 -0.0075H
TYD13220/ 3 -0.0075H
220/ 3
0.1/ 3
0.1/ 3
0.1
0.0075
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
785
1375
27
TYD3220/ 3 -0.01H
TYD13220/ 3 -0.01H
220/ 3
0.1/ 3
0.1/ 3
0.1
0.01
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
760×φ685×3440
4×φ25
Pitch of holes
550×550
860
1375
28
TYD4220/ 3 -0.01H
TYD14220/ 3 -0.01H
220/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.01
1a1n:0.2/50
2a2n:0.5/50
3a3n:0.5/50
dadn:3P/100
760×φ685×3410
4×φ25
Pitch of holes
550×550
1025
1375
29*
TYD3220/ 3 -0.0125H
TYD13220/ 3 -0.0125H
220/ 3
0.1/ 3
0.1/ 3
0.1
0.0125
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
760×φ685×3440
4×φ25
Pitch of holes
550×550
860
1375
30*
TYD4220/ 3 -0.0125H
TYD14220/ 3 -0.0125H
220/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.0125
1a1n:0.2/100
2a2n:3P/100
3a3n:3P/100
dadn:3P/100
760×φ685×3410
4×φ25
Pitch of holes
550×550
1025
1375
31*
TYD3220/ 3 -0.02H
220/ 3 0.1/ 3
0.1/ 3
0.1
0.02
1a1:0.2/100
2a2:0.5/100
dadn:3P/100
760×φ685×3530
4×φ25
Pitch of holes
550×550
1100
1580
32* TYD2230/ 3 -0.005H
230/ 3
0.1/ 3
0.1
0.005 an:0.2/50
dadn:3P/100
660×φ590×3340
4×φ25
Pitch of holes
480×480
Figure 3
668
1340
33*
TYD3275/ 3 -0.0075H
275/ 3
0.1/ 3
0.1/ 3
0.1
0.0075
1a1n:0.2/75
2a2n:0.5/75
dadn:3P/100
34
TYD3330/ 3 -0.005H
TYD13330/ 3 -0.005H
330/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/100
dadn:3P/100
35
TYD4330/ 3 -0.005H
TYD14330/ 3 -0.005H
330/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/50
2a2n:0.5/50
3a3n:3P/50
dadn:3P/100
36*
TYD3330/ 3 -0.0075H
TYD13330/ 3 -0.0075H
330/ 3
0.1/ 3
0.1/ 3
0.1
0.0075
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
37*
TYD3330/ 3 -0.01H
TYD13330/ 3 -0.01H
330/ 3
0.1/ 3
0.1/ 3
0.1
0.01
1a1n:0.2/100
2a2n:0.5/100
dadn:3P/100
760×φ685×4770
4×φ30
Pitch of holes
550×550
Figure 4
1441
2230
12
Table 3(continued)
SN Type
Rated
voltage
kV
Rated
capacitance
μF
Accuracy class/
secondary burden
VA
Outline and
installation
(holes)
dimension(mm)
L×W1×H,
ΦA,L1×W2
Outline
drawing
Weight
kg
CG
Height
h
mm
38
TYD3400/ 3 -0.005H
400/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
dadn:3P/75
760×φ685×5490
4×φ30
Pitch of holes
550×550
1825 2400
39
TYD3500/ 3 -0.005H
TYD13500/ 3 -0.005H
500/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
dadn:3P/75 2020 2800
40
TYD4500/ 3 -0.005H
TYD14500/ 3 -0.005H
500/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
3a3n:3P/75
dadn:3P/100
2020 2800
41
TYD3525/ 3 -0.005H
TYD13525/ 3 -0.005H
525/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
dadn:3P/75 2360 2800
42
TYD4525/ 3 -0.005H
TYD14525/ 3 -0.005H
525/ 3
0.1/ 3
0.1/ 3 0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
3a3n:3P/75
dadn:3P/100
2020 2800
43
TYD3550/ 3 -0.005H
TYD13550/ 3 -0.005H
550/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
dadn:3P/75
2020 2800
44
TYD4550/ 3 -0.005H
TYD14550/ 3 -0.005H
550/ 3
0.1/ 3
0.1/ 3 0.1/ 3
0.1
0.005
1a1n:0.2/75
2a2n:0.5/75
3a3n:3P/75
dadn:3P/100
760×φ685×6185
4×φ30
Pitch of holes
550×550
Figure 5
2020 2800
45 TYD13765/ 3 -0.005H
765/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/50
2a2n:0.5/50
dadn:3P/50
46
TYD14765/ 3 -0.005H 765/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/30
2a2n:0.5/50
3a3n:0.5/50
dadn:3P/50
1007×φ710×8265
6 × φ 34 evenly
distributed on
the circle φ805
Figure 6 3220 3900
13
Table 3 (end)
SN Type
Rated
voltage
kV
Rated
capacitance
μF
Accuracy class/
secondary burden
VA
Outline and
installation
(holes)
dimension(mm)
L×W1×H,
ΦA,L1×W2
Outline
drawing
Weight
kg
CG
Height
h
mm
47
TYD 1000/ 3 -0.005H
(separation)
1000/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
0.005
1a1n:0.2/15
2a2n:0.5/15
3a3n:0.5/15
dadn:3P/15
Capacitor divider:
1035×φ710×12600
6 × φ 34 evenly
distributed on
the circleφ805
electromagnetic unit:
1215×810×645
4×φ25
Pitch of holes
550×550
Figure 7 5880 5520
Note:① CG: centre of gravity.
② Type with “*”in SN is irregular product, which is not recommended.
③ Accuracy class/secondary burden is made a commissioning in accordance with the purchaser.
14
Table 4 List of Supply of CVTs Parts of each CVT
Electromagnetic unit capacitor
divider①
connector
Single stack Separation SN Type
Whole Electromagnetic
unit
Lower section
capacitor
divider
Middle
section
Upper
section
corona
stud②
nutSpring
washer
Flat
washer
Line
terminal③
Package
case
Instruction
manual
1 TYD□35 1 1 1 1
2 TYD□66 1 1 1 1
3 TYD□110 1 1 1 1
4 TYD□115 1 1 1 1
5 TYD□132 1 1 1 1
6 TYD□220 1 1 8 16 16 16 1 2 1
7 TYD□230 1 1 8 16 16 16 1 2 1
8 TYD□275 1 1 1 1 16 32 32 32 1 4 1
9 TYD□330 1 1 1 1 16 32 32 32 1 4 1
10 TYD□400 1 1 1 1 20 40 40 40 1 4 1
11 TYD□500 1 1 1 1 20 40 40 40 1 4 1
12 TYD□500 1 1 1 1 1 30 60 60 60 1 5 1
13 TYD□765 1 2 1 1 30 60 60 60 1 5 1
14 TYD□1000 1 1 3 1 4 40 80 80 80 1 9 1
15
Note:① Each section capacitor is assembled on the basis of capacitor number and sequence on nameplate.
② Stud of product 220kV is GB/T 901(line:M12×120,busbar:M14×130). Stud of product 330kV is GB/T 901(M14×130). Stud of 500kV product is GB/T 901(M14
×140). Stud of product 765kV is GB/T 901(M16×140).Stud of 1000kV product is GB/T 901(M20×160). Nuts and washers match to corresponding studs
③ Ex-factory line terminals has been mounted on the cover on upper section capacitor divider or put in the package case of corona.
④ Serial number of design is filled in □. Please see clause 3.1 for details.
15
Figure 2
1 High-voltage capacitance C1 2 Intermediate voltage capacitance C2
3 Intermediate-voltage bushing 4 Secondary outgoing box
5 Connection board 6 Electromagnetic unit
7 Low-voltage bushing 8 Line terminal
9 Connection sheet D Damp device
N Carrier communication terminal L Compensation reactor
P Protection device T Intermediate transformer
XL Low-voltage terminal of compensation reactor
1a1n Secondary 1a1n winding terminal
2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
16
Figure 3
1 High-voltage capacitance C1 2 Intermediate voltage capacitance C2
3 Intermediate-voltage bushing 4 Secondary outgoing box
5 Connection board 6 Electromagnetic unit
7 Low-voltage bushing 8 Line terminal
9 Connection sheet D Damp device
N Carrier communication terminal L Compensation reactor
P Protection device T Intermediate transformer
XL Low-voltage terminal of compensation reactor
1a1n Secondary 1a1n winding terminal
2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
17
Figure 4
1 Corona 2 High-voltage capacitance C1
3 Intermediate capacitance C2 4 Intermediate-voltage bushing
5 Secondary outgoing box 6 Connection board
7 Electromagnetic unit 8 Low-voltage bushing
9 Line terminal 10 Connection sheet
D Damp device N Carrier communication terminal
L Compensation reactor P Protection device
T Intermediate transformer XL Low-voltage terminal of compensation reactor
1a1n Secondary 1a1n winding terminal
2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
18
Figure 5
1 Corona 2 High-voltage capacitance C1
3 Intermediate capacitance C2 4 Intermediate-voltage bushing
5 Secondary outgoing box 6 Connection board
7 Electromagnetic unit 8 Low-voltage bushing
9 Line terminal 10 Connection sheet
D Damp device N Carrier communication terminal
L Compensation reactor P Protection device
T Intermediate transformer XL Low-voltage terminal of compensation reactor
1a1n Secondary 1a1n winding terminal
2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
19
Figure 6
1 Corona 2 High-voltage capacitance C1 3 Intermediate capacitance C2 4 Intermediate-voltage bushing 5 Secondary outgoing box 6 Connection board 7 Electromagnetic unit 8 Low-voltage bushing 9 Line terminal 10 Connection sheet D Damp device N Carrier communication terminal L Compensation reactor P Protection device T Intermediate transformer XL Low-voltage terminal of compensation reactor 1a1n Secondary 1a1n winding terminal 2a2n Secondary 2a2n winding terminal 3a3n Secondary 3a3n winding terminal dadn Residual voltage winding terminal
20
Figure 7 1 Corona 2 Line terminal 3 High-voltage capacitance C1 4 Intermediate capacitance C2 5 Low-voltage bushing 6 Pedestal 7 Intermediate-voltage bushing 8 Electromagnetic unit 9 Secondary outgoing box 10 Earthing board 11 Connection wire P Protection device L Compensation reactor T Intermediate transformer D Damp device N Carrier communication terminal A2 Primary voltage terminal of electromagnetic unit XL Low-voltage terminal of compensation reactor A1 Intermediate terminal of capacitor divider 1a1n Secondary 1a1n winding terminal 2a2n Secondary 2a2n winding terminal 3a3n Secondary 3a3n winding terminal dadn Residual voltage winding terminal
21
Figure 8 Schematic diagram of earthing switch handle position
Figure 9-1 Principle diagram Figure 9-2 Principle diagram
of C1 and tanδ measurement of C2 and tanδ measurement
Figure 9 Principle diagram of capacitance and tanδ anti-connection measurement of
auto anti-interference dielectric loss instrument
Figure 10-1 Principle diagram Figure 10-2 Principle diagram
of C1 and tanδ measurement of C2 and tanδ measurement
Figure 10 Principle diagram of capacitance and tanδ self-excitation measurement of
auto anti-interference dielectric loss instrument
22
Figure 11-1 Principle diagram of capacitance C1 and tanδ self-excitation measurment of auto
anti-interference dielectric loss instrument
Figure 11-2 Principle diagram of capacitance C2 and tanδ self-excitation measurement of auto anti-interference dielectric loss instrument
Figure 11 Principle diagram of capacitance and tanδ self-excitation measurement of
auto anti-interference dielectric loss instrument