Effective 7/09 Table 2-1 UVR application and electrical operating rating data Figure 1-1 UVR kit Figure 2-1 UVR connection diagram Instruction Leaflet for Undervoltage Release (UVR) for EG/JG/LG Circuit Breakers and Motor Circuit Protectors The Undervoltage Release (UVR) monitors a voltage (typically a line voltage) and trips the circuit breaker when the voltage at the wire leads falls to between 70 and 35 percent of the solenoid coil rating. The UVR consists of a continuous rated solenoid with a plunger and tripping lever. The UVR is reset when normal voltage is restored and the circuit breaker handle is moved to the reset (OFF) position. Application Ratings Electrical Operating Ratings Dropout Voltage Catalog Number Voltage, Ue Frequency Supply Voltage, Us Min. Max. Pickup Voltage Max. VA One Minute Dielectric Withstand Voltage, Ui 50-60 Hz 12 4.2 8.4 10.2 0.95 1024 UVR012APK DC 12 4.2 8.4 10.2 0.88 1024 50-60 Hz 24 8.4 16.8 20.4 0.72 1048 UVR024APK 24 DC 24 8.4 16.8 20.4 0.70 1048 UVR048APK 48-60 50-60 Hz 48 60 21.0 33.6 40.8 1.15 1.78 1120 UVR048DPK 48-60 DC 48 60 21.0 33.6 40.8 1.12 1.76 1120 UVR120APK 110-127 50-60 Hz 110 120 127 44.5 77.0 93.5 0.96 1.13 1.25 1254 UVR125DPK 110-125 DC 110 120 125 43.8 77.0 93.5 0.94 1.12 1.21 1250 UVR240APK 208-240 50-60 Hz 208 220 240 85.0 146 177 1.28 1.42 1.68 1480 UVR250DPK 220-250 DC 220 250 87.5 154 187 1.45 1.86 1500 UVR480APK 380-500 50-60 Hz 380 415 440 480 500 175 266 323 2.2 2.7 3.0 3.6 3.9 2000 UVR600APK 525-600 50-60 Hz 525 550 600 210 367 446 3.4 3.7 4.3 2200 UV ORG BRN I.L 29C155D Accessory Identification Label UVR Connection Diagram Label L Reset Actuator (tan) UVR012DPK 12 12 UVR024DPK 24

Instruction Leaflet for Undervoltage Release (UVR) for EG

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Instruction Leaflet for Undervoltage Release (UVR) for EG

Effective 7/09

Table 2-1 UVR application and electrical operating rating data

Figure 1-1 UVR kit

Figure 2-1 UVR connection diagram

Instruction Leaflet for Undervoltage Release (UVR) for EG/JG/LG Circuit Breakers and Motor Circuit Protectors

The Undervoltage Release (UVR) monitors a voltage(typically a line voltage) and trips the circuit breakerwhen the voltage at the wire leads falls to between

70 and 35 percent of the solenoid coil rating. The UVRconsists of a continuous rated solenoid with a plungerand tripping lever. The UVR is reset when normal voltageis restored and the circuit breaker handle is moved to thereset (OFF) position.

Application Ratings Electrical Operating RatingsDropout Voltage

CatalogNumber Voltage, Ue Frequency

SupplyVoltage, Us Min. Max.

PickupVoltage

Max. VAOne Minute DielectricWithstand Voltage, Ui

50-60 Hz 12 4.2 8.4 10.2 0.95 1024UVR012APKDC 12 4.2 8.4 10.2 0.88 1024

50-60 Hz 24 8.4 16.8 20.4 0.72 1048UVR024APK24 DC 24 8.4 16.8 20.4 0.70 1048

UVR048APK 48-60 50-60 Hz 4860 21.0 33.6 40.8 1.15

1.78 1120

UVR048DPK 48-60 DC 4860 21.0 33.6 40.8 1.12

1.76 1120

UVR120APK 110-127 50-60 Hz110120127

44.5 77.0 93.50.961.131.25

1254

UVR125DPK 110-125 DC110120125

43.8 77.0 93.50.941.121.21

1250

UVR240APK 208-240 50-60 Hz208220240

85.0 146 1771.281.421.68

1480

UVR250DPK 220-250 DC 220250 87.5 154 187 1.45

1.86 1500

UVR480APK 380-500 50-60 Hz

380415440480500

175 266 323

2.22.73.03.63.9

2000

UVR600APK 525-600 50-60 Hz525550600

210 367 4463.43.74.3

2200

U V

O R G B R N

I.L 29C155D

AccessoryIdentificationLabel

UVR ConnectionDiagram Label

L Reset Actuator (tan)

UVR012DPK1212

UVR024DPK24

Page 2: Instruction Leaflet for Undervoltage Release (UVR) for EG

WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED.DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. ALWAYS FOLLOW SAFETYPROCEDURES. CUTLER-HAMMER IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OFITS PRODUCTS.

3.0 INSTALLATION

Remove the breaker cover and sleeve.

REMOVE

REMOVE

Remove

Remove hex nut and install UVR (left pole only).

Remove the breaker cover and sleeve.

Remove the breaker cover and sleeve.

Install UVR (left pole only).

Install LG Actuator and UVR (left pole)

Effective 7/09

FrameLG

FrameJG

FrameEG

1

1

1

2

2

2

Page 2

I.L 29C155D

2 1

TOGGLEHANDLETO TRIPPOSITION.

CASEYLL
CASEYLL
CASEYLL
E0033747
REMOVE
E0033747
E0033747
E0033747
E0033747
E0033747
E0033747
E0033747
E0033747
Page 3: Instruction Leaflet for Undervoltage Release (UVR) for EG

Effective 7/09

0.45 - 0.56 Nm

Wire routing options. Re-install breaker cover.

Re-install breaker cover.

Re-install breaker cover.

Route wires.

Route wires.

.79 - .90 Nm(7-8 in-lb)

(4-5 in-lb)

.90 -1.13 Nm (8-10 in-lb)

3

3

3

4

4

4

NOTE: Break off side tab on cover if routingwires through side opening.

I.L 29C155D

Page 3

CASEYLL
E0033747
E0033747
E0033747
E0033747
E0033747
E0033747
E0033747
E0033747
Page 4: Instruction Leaflet for Undervoltage Release (UVR) for EG

4.0 TESTING

Refer to figure 4-1.

Step 1: With no voltage applied to UVR, ensure that thebreaker handle cannot be set to the Closed (ON)position.

Step 2: Set Breaker to Reset position. After taking all necessary precautions , apply rated voltage to UVR, and ensure that breaker handle can be set to the

Figure 4-1 Circuit Breaker/Motor Circuit Protector handleOpen (OFF), Closed (ON), and TRIP positions

5.0 REMOVAL

Removal is the reverse of the installation procedure.Remove the UVR by pulling straight up on pull tab (seeFigure 5-1). Be sure to reinstall the sleeve removed inSection 3.0, step 1.

Apply labels.

ON

TR IP

OFF

RESE T

Figure 3-5 Accessory Identification Label and CircuitDiagram Label application Figure 5-1 UVR removal

5

I.L 29C155D

©2001 Eaton CorportionAll Rights ReservedPrinted in U.S.A./TQCPublicaiton No. 66C1577H05

Effective 7/09

breaker handle moves to the TRIP position.Step 3: Disconnect voltage from UVR and ensure thatClosed (ON) position.

CASEYLL
CASEYLL
CASEYLL