Installer s Handbook

Embed Size (px)

Citation preview

  • 8/20/2019 Installer s Handbook

    1/32

    Caradon Gent Limited

    Waterside Road, Hamilton Industrial Park,

    Leicester LE5 1TN.

    INHB/2M/4/99

  • 8/20/2019 Installer s Handbook

    2/32

    installer’sHANDBOOK 

    FIRE DETECTION SYSTEMS

  • 8/20/2019 Installer s Handbook

    3/32

    Fire alarm systemsContents

    I N T R O D U C T I O N

    1

    BS 5839 is a standard for Fire Detectionand Alarm Systems in Buildings. Part 1

    of this standard is the code of practice for

    installation and services.

    It is important that any contractor or

    installation engineer undertaking this

    type of work is fully conversant with this

    standard which covers systems from

    simple manual installations to fullyautomatic fire detection systems. Whilst

    the standard does make some reference

    to fixed extinguishing systems the

    protection of electronic data processing 

    installations is more fully covered by

    BS 6266, 1982

    This booklet, published by Caradon Gent

    Limited - the UK’s largest manufacturerof fire alarm equipment - is intended to

    be an installer’s guide which will offer

    practical assistance. It is not intended to

    replace BS 5839 Part 1.

    Since the circumstances of installation of 

    a fire alarm system can vary, we recommend

    that in cases of difficulty assistance is

    sought by calling Caradon Gent Limited.Copies of British Standard BS 5839

    Part 1, can be obtained from:-

    The British Standards Institution,

    Linford Wood, Milton Keynes,

    MK14 6LE.

    Page

    System Design 2

     Examples 13

    False Alarms 15

    Installation of Cables 16

    Panel Installation 18

    Check List 21

    System Schematic 22

    Fire Detection Circuits 23

     Auxiliary Contacts 25

    Commissioning 27

    Installed System Tests 29

    Trouble Shooting 30

  • 8/20/2019 Installer s Handbook

    4/32

    S Y S T E M D E S I G N

     2

    The importance of pre-design planning cannot be overstated. Many parties are

    likely to have an interest in a fire

    detection and alarm system. Those who

    should be consulted before the design is

    finalised may include:

    The System Installer

    The Health & Safety Executive

    The Building Control Officer

    The Fire Insurer

    The Local Fire Authority 

    Consultants (including architects andengineers) and perhaps:

    The Communication Link Supplierand Central Alarm Receiving Station.

    The considerations prior to design

     which should also be detailed within the

    specifications may include:

    The purpose of the system

    Occupant escape times

    Fire Service attendance time

    Other actions to be taken in theevent of a fire

    Other occupants (particularly formultiple-occupancy)

    Service and maintenancerequirements

    System operation requirements andresponsibilities.

    The two principal reasons for installing

    a fire detection and alarm system are for

    the protection of life and for the

    protection of property. Each needs a

    different approach to a system design

    and equipment selection.Most buildings will need both life and

    property protection to differing degrees.

    There is a classification of systems in BS5839: Part 1: 1988 which is used in this

    guide.

    System for Protecting Property (P)

     A satisfactory fire alarm system for the

    protection of property will automatically 

    detect a fire at an early stage, indicate its

    location and raise an effective alarm in

    time to summon the fire-fighting forces

    (both resident staff and the fire brigade).

    Type P1 - A system covering all

    parts of the premises.

    Type P2 - A system covering only

    those parts of a building

    having a high fire risk.

    Systems for Protecting Life (L, M)

     A satisfactory fire alarm system for the

    protection of life can be relied upon tosound a fire alarm while sufficient time

    remains for the occupants to escape.

     As a guide, an escape route may be

    considered blocked once visibility drops

    below 10 metres.

    Type L1 - A system covering all parts

    of the premises

    Type L2 - A system covering only thoseparts of a building where

    there is a high risk to life if

    there is fire any where in the

    building 

    Type L3 - A system covering only areas

    critical to free passage along

    escape routes.

    Type M - A system that provides only

    for manual initiation of analarm and therefore depends

    on the presence of people.

    Stage 1. Talk to interested parties

  • 8/20/2019 Installer s Handbook

    5/32

    S Y S T E M D E S I G N

     3

     All manual call points whatever thesystem type should be sited:

    On all escape routes and exits to the

    open air.

    So that nobody has to travel more

    than 30 metres to reach one.

    On floor landings and staircases.

    In conspicuous and well-lit positions

    against a contrasting background.

    So that they can be seen easily. 1.4 metres above the floor.

    Fixed Temperature Heat Detector

    For protection of property, particularly 

     where temperature can fluctuate for

    natural reasons:

    Near large windows

    Industrial heat producing processesBeam Detector

     Although traditionally restricted to

    specialist applications, beam detection

    may provide more cost effective solutions

    to point detection over long distances.

    Corridors

     Warehouses

    Ceiling voids

    Hangars Open shopping areas

    Do not use in the direct line of sight of 

    an infra-red source such as tungsten or

    high intensity arc lights.

    Duct Detector

    The duct housing unit is designed to

    detect smoke in air conditioning

    systems. It is fitted to the outside of theduct and has 2 probes that protrude

    inside the duct to monitor the air.

    Stage 2. Site Manual Call Points

    It is important to have an adequate

    number of detectors to fully cover the

    areas requiring protection. Additionally 

    the type of detection must be matched to

    the environment and the potential fire

    hazards likely to be present.Optical Smoke Detectors

    For slow smouldering fires.

    Corridors or Escape Routes

     Wood or paper stores

    Do not use in steamy, dusty or smoky 

    areas such as kitchens, bathrooms etc

    Ionisation Smoke Detectors

    For fast burning, high energy fires.

    Solvent stores

    Switch rooms

     A mixture of optical and ionisation

    sensors can be used to ensure coverage in

    areas of high value, like computer rooms.

    Heat Detectors

    Heat detectors are used where the

    environment is subject to constant levels

    of smoke or dirt. Boiler rooms

    Busy kitchens and laundries

    Stage 3. Select and site fire detectors

  • 8/20/2019 Installer s Handbook

    6/32

    Under flat horizontal ceilings Diagram 1. Maximum dimensions:

     Area covered by 1 detector:

    Smoke 100m2 Heat 50m2

    Distance between any part of the

     wall and the nearest detector:

    Smoke 7.5m Heat 5.3m

    Distance between detector:

    Smoke 15.0m Heat 10.6m

     Diagram 2. Minimum dimensions: Distance between detector and

     wall: 0.5m.

    Maximum spacings between

    detectors are reduced when

    obstructions are present.

    Spacing for Smoke Detectors

    S Y S T E M D E S I G N

    4

    Stage 3. Site fire detectors (cont.)

    End View

    If less than150mm ignore

    If greater than10% of ceilingheight treat aswall

    0.5mMin

    0.5mMin

    Obstacle

     Diagram 2.

    MID POINT

    OF AREA

    MID POINT

    OF AREA

    7.5m 7.5m

    7.5m

    7.5m7.5m

    5.3m 5.3m

    5.3m

    5.3m5.3m

    Spacing for Heat Detectors

  • 8/20/2019 Installer s Handbook

    7/32

    CorridorsDetectors in corridors may

    generally be spaced more widely.

    This is NOT applicable to

    life safety applications unless all

    adjoining rooms have smoke

    detection.

    This is NOT applicable to

    corridors greater than 5 metres

     wide (treat as for flat horizontal

    ceilings)

    Detectors may be placed at

    horizontal distances extended

    up to 50% of the difference

    between the actual corridor

     width and 5 metres (see table).

     E.g. (5-2) x 0.5=1.5m.

    Stage 3. Fire Detectors (cont).

    S Y S T E M D E S I G N

     5

    Corridor Spacing between Detectors (max) width

    (m) Smoke (m) Heat (m)

    1.2 18.8 14.4

    1.6 18.3 14.02.0 17.9 13.5

    2.4 17.4 13.0

    2.8 17.0 12.5

    3.2 16.5 12.0

    3.6 16.0 11.5

    4.0 15.5 10.9

    4.4 15.0 10.3

    4.8 14.4 9.7

    S S

    H H

    Plan View

    SmokeDetector

    SmokeDetector

    HeatDetector

    HeatDetector

    7   . 5   + 1  . 5   m  

    7   . 5   + 1  . 5   m  

    7   . 5   + 1  . 5   m  

        7.   5  +

       1.   5  m

        7.   5  +

       1.   5  m

        7.   5  +

       1.   5  m

    17.9 m

    5   . 3  + 1  . 5   m  

    5   . 3  + 1  . 5   m  

    5   . 3  + 1  . 5   m     5.   3  +

       1.   5  m

       5.   3  +

       1.   5  m

       5.   3  +

       1.   5  m

    13.5 m

       2  m

       2  m

    Wall

    Wall

     Detector spacing along corridors.

  • 8/20/2019 Installer s Handbook

    8/32

    S Y S T E M D E S I G N

    Siting limits for Smoke Beam Detectors

    Detector/ General applications Automatic link to a mannedSensor type centre. Fire brigade response is

    normally within 5 minutes.

    (m) (m)

    Smoke 10.5 15.0

    Heat grade 1 9.0 13.5

    Heat grade 2 7.5 12.0

    Heat high temp. 6.0 10.5

    Beam 25 40

    Minimum (m) Maximum (m)

    Height of optical beam above floor 2.7 25*Optical beam length 1 100

    Distance of optical beam from a flat ceiling or apex 0.3 0.6

    Horizontal distance between optical beams measured at - 14right angles to a beam

    Horizontal distance between optical beam and an adjacent See Notes 8 wall or partition

    * The height may be increased to 40m provided that the general height to which combustibles are stored in thebuilding does not exceed 5m and that the fire brigade can attend within 5 minutes.

    NOTE: Generally the beam should not pass closer, to a wall or partition, than 500mm and not closer to an obstruction,than 600mm. However, up to 3m of the beam may be closer than this. Always consult Gent if in doubt.

     Where the beam detec tor is mounted in the apex of a pitched or ‘north-light’ roof the horizontal distance can be increasedby 1% for each degree of slope up to a maximum of 25% (eg 20º slope of roof 20% of 7.5m = 1.5m).

    Pitched roofs

     A row of sensors should be installed

    along the apex of any pitched roof or

    ‘north-light’ roof. Smoke sensors should

    be not more than 600mm from the apex 

    of the roof. Horizontal spacing between

    sensors may be extended when used

    under pitched roofs.

    The horizontal distance may be extended

    by up to 1% for each degree of slope of 

    the roof (relative to horizontal) up to a

    maximum of 25%.

    Wall

    Roof Roof

    600mmMax

    20º pitch allows spacingto be extended 20% forexample from 7.5m to9.0m

    20º

    Heights

    Maximum heights of detectors are dependant on the fire brigade response available:

  • 8/20/2019 Installer s Handbook

    9/32

    Further considerations (checklist) For a Type P1 system every part of

    the building should be suitably

    protected. For this purpose each

    effectively enclosed space should be

    considered separately.

     Areas covered by a Type P2 system

    should be separated from unprotected

    areas by a fire resisting construction.

     Voids not more than 800mm deep

    need not be protected unless fire can

    spread through them from one to

    the other.

     Where rooms are divided by

    partitions or storage racks reaching to

     within 300mm of the ceiling each

    section should be protected separately.

    Shafts for elevators, lifts, hoists,

    escalators and enclosed chutes

    through floors and stairways should

    be protected by detectors at the top

    of the shaft and within 1.5m of

    openings on to each floor.

     Where an escalator or staircase has a

    sloping ceiling a detector may need

    to be sited on that ceiling.  Enclosed staircases should be

    protected by detectors on each main

    landing within the staircase.

    Lantern lights should be protected

    by a detector unless they are less

    than 800mm in height above the

    ceiling and are not used as ventilation.

     Extra detectors may be needed tocope with structural features within a

    room. Consideration must be given

    to possible adverse air flows when airconditioning and ventilation systems

    are in use.

    If a detector is concealed, it may be

    desirable to provide a remote visible

    indication of its operation.

    Care should be taken when siting to

    ensure that adverse conditions such

    as high levels of shock or vibration

    are not encountered.

    Stage 3. Fire Detectors (cont).

    S Y S T E M D E S I G N

    7

     Design Tip! It is good practice to site

    detectors in toilets, however they

    need not haveindependent coverage if cover is

     provided in a common lobby.

  • 8/20/2019 Installer s Handbook

    10/32

    S Y S T E M D E S I G N

    8

    Life ProtectingThe minimum sound levels must be

    produced in all occupiable parts of the

    building. Occupiable parts include

    restricted areas such as service ducts

     where people could be working on

    occasion. As audible alarms are essential

    for the protection of life, a minimum of 

    two independent sounders must always

    be provided to guard against the failureof one. A minimum of 

    one sounder should be

    provided in each fire

    compartment.

    Property Protection

    In Type P systems the

    minimum sound levels

    must be produced in

    the areas required tosummon fire fighting 

    assistance. A sounder

    should also be provided

    close to the control and

    indicating equipment

    and there should be

    one outside to direct

    services to the correct

    entrance.In practice most fire

    detection and alarm

    systems involve

    elements of both

    property and life

    protection.

    Most systems should

    therefore meet all the

    above requirements.In general fire alarm sounders must not

    be used for any other purpose, with the

    established exception of class changes inschools where coded signals of not more

    than five seconds duration can be used.

    Public address equipment can be used to

    give warning of fire subject to certain

    conditions. Visual alarm signals should

    be considered to complement alarm

    sounders where there is a high level of 

    noise or the occupants may be hearing-

    impaired.

    Stage 4. Site Alarm Sounders

    Conversationat 1m

    Thresholdof Pain

    Hammeringon Steel

    HeavyMachine

    Noise

    BoilerFactory Noise

    Punch Press

    Room Noise

    LightMachine

    Noise

    Heavy AssemblyRoom Noise

    Heavy StreetNoise

    Dispatch RoomNoise

    Light AssemblyRoom Noise

    Stock RoomNoise

    Average OfficeNoise

    Light StreetNoise

    Typical ambient noise levels dB (A)

    Whisper at1m

    40 50 60 70 80 90 100 110 120 130 14030

    dB(A)

  • 8/20/2019 Installer s Handbook

    11/32

    Sound output All sounders in a building should be of a

    similar type, do not mix electronic

    sounders and bells.

    The sound level will reduce by 6dB every 

    time the distance from the sounder is

    doubled. Sound levels are normally

    quoted on-axis, ie. directly in-line with

    the middle of the sounder.

    This is normally the loudest position.

    In order to assess the sound level at any 

    particular point it is necessary to allow

    for the distance from the sounder AND

    the angle off-axis.

    Sounders should produce:

    Minimum sound level of 65 dB or

    at least 5 dB greater than any

    background noise that is likely to

    persist for more than 30 seconds 75 dB is required at the bedhead

    of a sleeping person

    Note: The sound level near the control

    panel should not be so high that a

    telephone cannot be used to summon

    help from the fire brigade.

     Attenuation

    Fire alarm sounders may often be heard

    in adjacent rooms but the sound level will be attenuated by any door.

    Typical attenuation figures are:

    20 dB by an internal door

    30 dB by a fire door

    It is also important to consider the

    room’s use. Are there any obstacles

    (including furniture) to the sound, and

    how many people will be present in theroom? Both people and furnishings will

    attenuate the sound level.

    Stage 4. Site Alarm Sounders (cont).

    S Y S T E M D E S I G N

    9

     Design Tips!1. Use sensor sounders in small rooms

     where the sound level has been

     attenuated by door partitioning

    (32000/Vigilon systems only).

     2. Always site sounders in

    toilets and bedrooms.

     3. “Back-to-back” sounders wherever

     possible to reduce wiring costs.

    Sensor Sounder in a small office.

    100dB(1m)

    85dB(1m)

  • 8/20/2019 Installer s Handbook

    12/32

    S Y S T E M D E S I G N

    10

    It is now possible to obtain bothconventional and analogue addressable

    control panels to suit a wide variety of

    building sizes and types.

    There should be a plan of the building,

    showing at very least the entrances, to be

    placed on or near the control equipment.

    If there are several entrances,

    consideration should be given to the

    provision of a repeat panel at eachentrance.

     When selecting the control equipment

    the current consumption of both

    detection circuits and alarm circuits must

    be considered, this will be found in the

    relevant product literature.

    Many control and indicating panels

    include an integral power supply unit but

    in the larger systems it may be

    necessary to provide an external unit

    either in place of or in addition to the

    internal unit. The need for extra

    standby power can be determined from

    the total current consumption of the

    system and the specification of the

    supply.

    Standby PeriodIn the event of a mains failure, the

    minimum standby period is 24 hours in

    normal conditions followed by 30

    minutes at full alarm load. In special

    circumstances, such as the availability of 

    a standby generator, these periods can be

    reduced.

     When a building is unoccupied for

    significant periods, the normalcondition standby period should be

    extended to 24 hours longer than the

    period of non-occupation. For example,if a building is unoccupied from 6.00 p.m.

    Friday to 8.00 a.m. Monday, the fire

    system should have a standby period of 

    86 hours normal condition, followed by 

    an alarm period of 30 minutes.

    Siting control and indicating equip-

    ment

    Control and indicating equipment should

    be sited:

    In an area of low fire risk.

    On the ground floor in the vicinity of 

    an entrance used by the fire brigade.

    In an area common to all building 

    users.

     Where automatic detectors are in use,

    the control equipment area must be

    protected.

     Where ambient light levels are such

    that visual indications can be clearly

    seen.

     With a first alarm sounder sited

    adjacent.

    Stage 5. Select Control & Indicating Equipment

     Design Tip! For minimum standby period it is

    important to consider the worst case.

     For instance, is there cover for

     weekends and bank holidays?

     Most reputable manufacturers design

     control panels with 48 hour standby,

     however 72 hours or longer may be

    required.

  • 8/20/2019 Installer s Handbook

    13/32

    Door Retainers and RelaysDoor retainers will hold doors open

    during normal conditions but allow them

    to close in the event of fire.

     A manually operated switch may also be

    included if required.

    The mechanism comprises a powerful

    electromagnet and a door plate.

    The electromagnet may be wall or floor

    mounted.Batteries

    Most internal and external power supply 

    units will normally be supplied with (or

    have provision for) sealed lead-acid cells

    as they need a minimum of

    maintenance.

    System Interfaces

     While a fire detection and alarm systemmust be capable of operating in isolation,

    other building systems may need to

    receive a signal when a fire alarm is

    activated - or may need to activate the

    fire alarm system when they are operated.

    For example, a fire detection system may 

    need to shut down the normal ventilation

    system or to activate a fixed extinguishing 

    system.Conversely, if a fixed extinguishing

    system is manually operated or a gas

    detection system is activated, the fire

    alarms may need to be sounded.

    In such cases, a system interface is

    needed, which may be a simple relay for

    a conventional system or a number of 

    addressable inputs and outputs for an

    addressable system.

    Power Supply UnitsGent control and indicating panels

    include a stand-by power supply unit

    complete with batteries. However, in

    larger systems the current requirements

    are often very different and therefore a

    separate power supply unit, external to

    the control panel, may be needed.

    Manned Centre Links

     Where the system includes the need forrapid fire service attendance an automatic

    link to a permanently staffed centre can

    be provided. There are several methods

    available and before selecting one it is

    recommended that the matter be

    discussed with the Gent Technical

    Hotline on 0800 064 3344

    Fixed Extinguishing Systems Where the protection of property is

    important and a rapid attendance cannot

    be guaranteed, the provision of a fixed

    extinguishing system should be considered.

    Gent can supply a range of gaseous

    extinguishing systems which are ideal

     when a liquid extinguishant, such as

     water, might itself cause extensive damage.

    Stage 5. Select Control & Indicating Equipment (cont.)

    S Y S T E M D E S I G N

    11

  • 8/20/2019 Installer s Handbook

    14/32

    S Y S T E M D E S I G N

    12

    ZoningFor several reasons a building must be

    split into a number of fire detection and

    alarm zones.

    The prime purpose of zoning is to

    identify the location of a fire or fault:

    The following criteria govern the

    number and size of zones:

    The floor area of a single zone should

    not exceed 2000m2.

    No person in a zone should have to

    travel more than 30m to visually

    determine the position of a fire.

    The zone should not cover more

    than one storey unless the total

    building area is less than 300m2.

    Stairwells, lift shafts and flue-like

    openings should be treated asseparate zones.

    It is permissible for a zone to cover a

     whole number of fire compartments,

    or for a fire compartment to contain a

     whole number of zones, but a zone

    cannot extend over parts of two or

    more fire compartments.

    For multiple-occupancy buildings the

    occupancy boundaries shouldcoincide with zone boundaries.

    If there is an area of special fire risk,

    consideration should be given to

    setting up a separate zone for rapid

    identification of a fire in that risk

    area.

    Notes:1. A fire compartment is an area

    bordered by a fire-resisting structure

    usually at least 30 minutes resistance.

    2. Zone limits can be relaxed only in

    certain Type M systems.

    3. To avoid misleading indication of the

    position of a fire, consideration

    should be given to the separate

    zoning of manual call points,particularly those on staircase

    landings. This can be achieved by

    indicating automatic detectors and

    manual call points separately.

    Stage 6. Zoning

     Design Tip! Remote indicator lamps can be used

    to reduce the need for small complex

     zones.

    They are also useful for voids and

    locked cupboards.

  • 8/20/2019 Installer s Handbook

    15/32

    Stage 2. Site Manual Call Points

    Stage 3. Site Fire Detectors

    E X A M P L E S

    13

    S

    SS

    S   S

    S

    S

    S S   S

    SSS

    S

    H

    H

    H

    H

    BB

    S

    H

    On escape routes and exits tothe open air.

    So that no one has to travelmore than 30m to reach one.

    On floor landings and staircases.

     Area covered by smoke detector= 100m2 max.

     Area covered by heat detector= 50m2 max.

    Distance between smokedetectors = 15m max.

    Distance between heat detectors= 10.6m max.

    Check special rules for corridorsless than 5m wide.

    Maximum beam length =100m.

    Cover toilets and stairways.

    Optical smoke detector 

     Heat detector 

     Beam detector 

    S

    H

    > 1 7  .5  m 

    approx 550m2

    Stores

    Assembly Area

    Warehouse

    BoilerRoom

    Office

    Reception

    Canteen

    OfficeWC WC WC

    WC

    Stores

    Assembly Area

    Warehouse

    BoilerRoom

    Office

    Reception

    Canteen

    OfficeWC WC WC

    WC

     Manual Call Point

    B

    Travel distances >30m require a call point.

  • 8/20/2019 Installer s Handbook

    16/32

    E X A M P L E S

    14

    Stage 4. Site Alarm Sounders

    Stage 6. Zoning

    Minimum 65 dB required or 5dBgreater than background noise.

    75 dB required at bedheads.

    Sound level reduces by 6 dB forevery time the distance fromthe sounder is doubled ie.100 dB - 1m94 dB - 2m88 dB - 4m82 dB - 8m76 dB - 16m

    Sound level is attenuated by30dB for fire doors and 20 dBfor internal doors.

    Stage 5. Site ControlEquipment

    For ease of access by fire brigade.

    Floor areas should not exceed2000m2.

    Stores

    Assembly Area

    Warehouse

    BoilerRoom

    Office

    Reception

    Canteen

    OfficeWC WC WC

    WC

    Stores

    Assembly Area

    Warehouse

    BoilerRoom

    Office

    Reception

    Canteen

    Office

    WC WC WC

    WC

     Remote LEDs.

     Zone 1

     Zone 2

     Zone 3

     Zone 4

     Fire panel.

  • 8/20/2019 Installer s Handbook

    17/32

    Many false alarms result from causes that were not considered at design or

    installation stages and could otherwise

    have been avoided. Common causes of 

    false alarms include:

     Electrical or mechanical faults,

    perhaps caused by vibration,

    impact or corrosion.

    Heat, flames or smoke

    generated from industrialprocesses or cooking.

    Fumes from engine or

    machine exhausts.

    High air velocities caused

    by strong draughts or air

    conditioning.

     Work being carried out in

    the protected area withoutthe necessary precautions

    being taken.

    Servicing or testing

    equipment without prior

    notification to those likely

    to receive indication.

     Electrical transients or radio

    interference.

    Inadequate servicing.

    The build-up of dust or dirt or the

    presence of insects within a detector.

    Changes, including change of use

     within the building.

     Accidental or malicious operation.

    Fire detection and alarm equipment isdesigned to minimise false alarms,

    particularly with the introduction of 

    advanced, analogue systems. However,

    even very sophisticated equipment

    cannot compensate for a badly designed

    system or a poor installation.

    It is therefore vital that potential causes

    of false alarms are considered and the

    risks minimised at the design stage.

    F A L S E A L A R M S

    15

  • 8/20/2019 Installer s Handbook

    18/32

    I N S T A L L A T I O N O F C A B L E S

    16 

    Since every site is different, it is only possible to give general guidance, refer to

    BS 5839 for more details.

     A fire alarm system depends on its

     wiring. There are 2 group classes of 

    cable:

    Cables NOT required to operate

    after a fire has been detected e.g.

    detectors and manual call points

    (group 1). Cables required to operate during a

    fire, e.g. power supplies and sounders

    (group 2).

     While mineral insulated cables are

    preferable for all fire alarm applications

    the following cables can be used for the

    two groups:

    Group 11. MICC to BS 6207: Part 1 (with or

     without sheath)

    2. Cables complying with BS 6387categories AWX, SWX, A or S.

    3. PVC - insulated to BS 6004 sheathedor non-sheathed with mechanicalprotection.

    4. Rubber insulated to BS 6007

    5. PVC single type BK, BR and BU toBS 6231

    6. PVC insulated SWA to BS 6346

    7. Cross-linked polyethylene or hardethylene-propylene rubber insulatedSWA to BS 5467

    8. Polyethylene insulated PVC sheathedcoaxial cable to the dimensional

    requirements of BS 2316: Part 3 but with a minimum of 16 strands /0.2mm diameter central conductor.

    9. Cables designed for the detection ofheat must be configured to initiatethe alarm system should a fire occuralong the cable.

    Group 2

    Cables 1 or 2 from group 1.

    Cables 3 to 9 from group 1, providing

    that they are protected either by burying 

    them in a wall and covering them with

    12mm of plaster or equivalent, orprotecting them from a significant fire

    risk by shielding them with a wall,

    partition or floor having a minimum

    demonstrable 30 minutes fire resistance.

    These requirements may in some cases

    be reduced when included in areas of low 

    fire risk or when covered by an automatic

    extinguishing system.

    Certain cables may also need mechanical

    protection against impact, abrasion or

    rodent attack. As a guide, cables 1, 6 and

    7 will not need further protection but all

    others may in risk circumstances.

    BS 5839: Part 1 gives full details.

    Other types of cables can be used

    provided that their suitability can be

    demonstrated.Conductors carrying fire alarm power or

    signals should be separated from

    conductors used for other systems.

    Wiring

  • 8/20/2019 Installer s Handbook

    19/32

    Cables should be installed in accordance

     with the good practices recommended in

    the 16th Edition of the IEE Wiring 

    Regulations (BS 7671).

    Other than the segregation of cables the

    regulations exclude fire alarms if they are

    fed from a safety source. In effect this

    applies to extra low voltage systems,

     which include systems in general use for

    fire alarm circuits. All cables and apparatus directly

    connected to a public supply 240V a.c.

    (low voltage) such as supplies to

    indicators, power supplies and mains

    operated door holders must comply with

    the 16th Edition in respect of the

    installation of cables and the provision of 

    isolation and switching.

    Connection to mains supply should be via an isolating switch fuse reserved

    solely for the purpose. Its cover must be

    painted red and labelled FIRE ALARM -

    DO NOT SWITCH OFF.

    If required a separate RCCB should be

    used for fire alarm systems. Fire alarm

    cables are defined as ‘Category 3 Circuit’.

    Cables of Category 1 Circuits (low voltage and connected directly to a mains

    supply) must not be drawn into the same

    conduit, duct or ducting as Category 3

    (fire alarm circuits).

     Where Category 3 Circuits are installed

    in a channel of trunking containing 

    circuits of any other category, these

    circuits must be segregated from the

    latter by continuous partitions, such thatthe integrity of the Category 3 (fire alarm

    circuits) is not reduced.

    In effect these regulations mean that

    unless MICC is used, fire alarm cable

    circuits must never be mixed with any 

    other circuits; neither should they be

    mixed with any other circuits in a multi-

    core cable.

    Conductor size should take voltage drop

    into account. In any case conductors

    should have a cross-sectional area of not

    less than 1mm2

    or if stranded of not lessthan 0.5mm2.

     Where possible cables should be routed

    through areas of low fire risk.

    Cables installed in damp, corrosive or

    underground locations should be PVC

    sheathed. Where there is a risk of 

    mechanical damage, cables should be

    protected accordingly.

    Cables in cavities or voids should be

    separated from other cables by 300mm

    unless enclosed in a conduit, ducting or

    trunking.

    I N S T A L L A T I O N O F C A B L E S

    17

  • 8/20/2019 Installer s Handbook

    20/32

    P A N E L I N S T A L L A T I O N

    18

    Dedicatedmains

    cableentry points

    Panel size395mm wide x 274mm high x 87mm deep

    89mm 89mm

       1   9  m  m

       1   9   7  m  m

    111mm4-off earth points

    How to knock-ina cable entry point

    Knock here to openthe entry point

    Red

    Battery connectionsBlack

    Fixing pointsfor theelectronicassembly

    Electronic assembly

    Panel Backbox

    Transformercables

    to electronicassembly

    Earth connectionto the electronic

    assembly

    NB: The following installation method

    is based on the Xenex panel.

    Panel Fixing

    a) Remove panel from its packing, but

    retain the carton for storage of spare

    parts and loose items.

    b) Remove the top and bottom inner plates.

    c) Check the spares parts supplied with

    those listed in installation manual. If

    replacement parts are required at anytime, only spares that are of the same

    specification should be used.

    d) Remove the transformer and earth

    connections from the electronic

    assembly, and then remove the

    electronic assembly from the panel.Store the electronic assembly in a safeplace until required.

    e) Remove the appropriate knock-in onthe panel case for cable entry.

    f) Hold the panel on the wall in thedesired mounting position and markthe positions of the fixing holes.

    g) Secure the panel to the wall using

    suitable fixing such that adequatesupport is provided to the controlpanel assembly. A top centre keyholefixing is provided on the case to allow the panel to be hooked whilst thebottom two fixing points are located.

    Panel fixing

  • 8/20/2019 Installer s Handbook

    21/32

    P A N E L I N S T A L L A T I O N

    19

    h) Connect the mains supply cable to

    the panel .The cable:

    must be through one of the dedicated

    cable entry into the panel.

     via an unswitched fused spur unit,

    rated 5A for the 1 & 2 Zone Control

    and Repeat panels and 7A for 4 & 8

    Zone panels.

    The fused spur isolator cover should be

    red and marked:

    FIRE ALARM - DO NOT SWITCH

    OFF

    The fused spur units must be fed from a

    dedicated switch or protective device at

    the local mains supply distribution

    board.

    i) Wire the system. With the exception

    of the mains cable, all cables should

    remain unconnected at the panel

    leaving 300mm tail. Mark each core

    identifying its final point of connection.

    4-off earth points

    13-back13-topcable entry points

    Gland

    Earth

    drain

    Cable

    Cable termination

    Panel backboxElectronic assembly

    Panel Fixing (Wiring)

    Cable entry &earth points

    CAUTION: DO NOT undertake high

     voltage insulation tests WITH THE

    CABLES CONNECTED to their

    terminals. Such a test may damage the

    electronic circuitry in the system equipment.

     j) Refit the electronic assembly into the

    panel and connect the transformer and

    earth cables previously removed.

    Note: Each terminal in a panel will accept a

    maximum conductor size of 2.5mm

    square.

    Note: The installation of all out standing 

    parts are usually carried out during 

    Commissioning of the System.

    Store all spare parts and loose components

    including the batteries inside the panel

    carton and keep in a safe place until

    required.

  • 8/20/2019 Installer s Handbook

    22/32

    P A N E L I N S T A L L A T I O N

     20

    For the wiring of:

    Length per circuit Type of circuit Recommended cables, alsosee BS5839:Part 1 guidance

    2m Mains power supply cord see power supply cord

    1Km Zone circuit

    1km Sounders circuit

    100m Auxiliary circuit

    l00m Common fire and fault circuit

    l00m Class change circuit

    500m Repeat panel link Belden type screened 2-coretwisted pair

    The guidance of BS5839: Part 1:1988

    should be followed. The use of cables

    such as (MICC or Belden) are

    recommended.

    Generally available electrical installationcable may be used, providing the cable is:

    to BS6387

     with no more than 2 - cores

    each core having no less than 1.5mm2

    cross section area

     with an inherent or through metal

    conduit screen for earth continuity in

    order to produce electrical productionand screening 

    having protection from heat and

    mechanical damage

    Power supply cord

    This should be a 3-core cord having a

    rated current of:

    5A with a nominal core cross sectional

    area of 0.75mm2

    provided the lengthof the cord does not exceed 2m

    Cables

    Power Supply

    See BS5839: Part 1 guidance

    Standby Supply 

     With the recommended battery and zone

    loading the control panel will provide a

    standby supply under mains failureconditions, for a period of 72 hours

    followed by 30 minutes of alarm load.

    24V Supply 

    The power supply terminals ‘24 + and 0’

    may drive external ancillary equipment

    and is designed to be used in conjunction

     with auxiliary contacts and common fire

    and fault outputs.

    Note: The use of the 24V supply will

    affect the panel standby capability.

  • 8/20/2019 Installer s Handbook

    23/32

    C H E C K L I S T

     21

    Notes to the Installer - Checks

    The power-up and commissioning isdone by the servicing organisation.

    The wires between the termination

    point and terminals should be short

    and straight as possible.

    The cables of the fire detection and

    alarm system and other systems

    should usually be separated by at least

    160mm, unless dedicated conduit or

    ducting is used.

    Do not use any part of building

    structure for earthing.

    The cable length between the Repeat

    LED unit and respective fire detector

     where used, should not exceed l0m

    Cable Glands should be used on the

    equipment for the mains supply cable.

    Unused knockouts on productenclosure that have been removed,

    should not be left open.

    Requirements

    It is recommended that the installer

    follow the general requirements of:

    BS5839:Part 1:1988, which is the code

    of practice relating to the fire

    detection and alarm Systems forbuildings.

    the relevant parts of the BS 7671

    Requirements for Electrical

    Installation Institute of Electrical

     Engineers Wiring Regulations l6th

    edition

    Second fix installation

    To prevent the possibility of damage or

    dirt.degrading the performance orappearance of the System Products,

    the installation of second fix items should

    be delayed until all major building work 

    in the area is complete.

    Fixtures and fittings

    It is the installers responsibility to

    provide:

    adequate fixtures and fittings for the

    type of construction surface onto

     which a product is to be installed.

    as an aid to this decision, the weightand overall size of each full assembly

    together with implications on cable

    entries and routing should be taken

    into consideration.

    Note: All these procedures assume that

    the cable, gland, steel box (BESA box)

    and other related accessories are provided

    by the installer

     As Fitted wiring drawings

    The installer should acquire:

    site specific information from the

    interested parties, for details on the

    location of products for installation

    the acquired information together

     with the relevant standards should be

    used to assist the work.

    Earth continuity 

    To maintain earth continuity, the cable

    screen must be continued through each

    system device, whether the earth is

    connected to a device or not.

  • 8/20/2019 Installer s Handbook

    24/32

    S Y S T E M S C H E M A T I C

     22

       E   N

       D   O   F

       L   I   N

       E

       R   E   S   I   S   T   O   R

       1   0   K

       O   h  m  s

       A   L   A   R   M

        S   O   U   N   D   E   R   C   I   R   C   U   I   T

       I  n   i   t   i  a   t   i  n  g  c  o  n   t  a  c   t  s   t  o

      a  u  x   i   l   i  a  r  y  e  q  u   i  p  m

      e  n   t ,

      s  u  c   h  a  s  m  a  n  n  e   d

      c  e  n   t  r  e   l   i  n   k

      a  n   d  m  a  g  e  n  e   t   i  c

       d  o  o  r   h  o   l   d  e  r  s

       T  o

       d  e   d   i  c  a   t  e   d

      m

      a   i  n  s   i  s  o   l  a   t   i  n  g

      p  r  o   t  e  c   t   i  o  n  u  n   i   t

       N

       E

       L

       M   A   I   N   S

       T   E   R   M   I   N   A   L

       N   C

        T     A

        T    B

        E

       N   C   N  0   N  0

       A  u  x   i   l   i  a  r  y

      c  o  n   t  a  c   t  s

       T  o

       T  r  a  n  s   f  o  r  m  e  r   (  s   )

       B

      o  a  r   d

       Z  o  n  e

       S  o  u  n   d  e  r

       Z  o  n  e

       S  o  u  n   d  e  r

       T   h  e  r  e  c  a  n   b  e  u  p   t  o   8

       F   i  r  e   d  e   t  e  c   t   i  o  n   (  z  o  n  e   )  c   i  r  c  u   i   t

      a  n   d  s  o  u  n   d  e  r  c   i  r  c  u   i   t   d  e  p  e  n   d   i  n  g

      o

      n   t   h  e  p  a  n  e   l  s   i  z  e

       C   l  a  s  s

      c   h  a  n  g  e

       R  e  p  e  a   t

      p  a  n  e   l

       P  u  s   h   b  u   t   t  o  n  s  w   i   t  c   h

       f  o  r  c   l  a  s  s  c   h  a  n  g  e  a  p  p   l   i  c  a   t   i  o  n

       E   N   D   O   F

       L   I   N   E

       C   A   P   A   C   I   T   O   R

       U   N   I   T

       R   E   D

       B   L   A   C   K

       F   I   R   E   D   E   T   E   C   T   I   O   N

       (   Z   O   N   E   )   C   I   R   C   U   I   T

       F   I   R   E

       D   E   T   E   C   T   O   R

       M   A   N   U   A   L

       C   A   L   L

       P   O

       I   N   T

       A   l  a  r  m   s  o  u  n   d  e  r  s

       b  e  p  o   l  a  r   i  s  e   d

     .

      m  u  s   t

      :   S  p  u  r  w   i  r   i  n  g   i  s  n  o   t  p  e  r  m   i   t   t  e   d  o   f   f   f   i  r  e   d  e   t  e  c   t   i  o  n

      c   i  r  c  u   i   t  s .

       N   O   T   E

      a  n   d  a   l  a  r  m   s

      o  u  n   d  e  r

       F   i  r  e  a   l  a  r  m   c  o  n   t  r  o   l  p  a  n  e   l

       C   C   1

       C   C   1

       2   4   +

      2  4   V   +  s  u   p   p l  y

      0   V  s  u   p   p l  y

       C  o   m   m  o  n  f  a  u l  t

       C  o   m   m  o  n  f i  r  e

       C   F   T

       C   F   R

       R   +

       R -

       0

       Z   1   +

       Z  n   +

       Z   1 -

       Z  n -

       S   1   +

       S  n   +

       S   1 -

       S  n -

  • 8/20/2019 Installer s Handbook

    25/32

    F I R E D E T E C T I O N C I R C U I T S

     23

     Each zone circuit can have up to 2mA 

    load. An end-of-line

    capacitor unit is required for zone

    circuit monitoring, which must be fitted

    after the last detector or manual call

    point on the circuit.

     All manual call points used must

    have a 470 ohms series resistor.

    Note: If a Beam detector is used, then it

    must be powered from an independentsupply.

    Zone circuit connections

    END OF

    LINE

    CAPACITOR

    UNIT Unused Zone circuits mustbe terminated with anend-of-line Capacitor unitor bipolar capacitor

    RED

    BLACK 

    FIRE DETECTION (ZONE) CIRCUIT

    FIREDETECT OR

    A fire detector headmay be fitted

    to a diode-base forcontinuity when a detector

    head is removedand there can be

    a maximum of up to20 diode-basesper zone circuit

    MANUALCALLPOINT

    NOTE: Spur wiring is not permittedoff zone circuits.

    ZoneCircuit

    ZoneCircuit

    Contol panel

    Z1+ Z2+Z1- Z2-

    BLACK RED

     Where a zone circuit is not being used,

    the end-of-line capacitor unit must be

    fitted across its terminals

    in the panel.

    24

  • 8/20/2019 Installer s Handbook

    26/32

    F I R E D E T E C T I O N C I R C U I T S

     24

    Sounder circuit that isnot used is terminatedwith an end-of line resistor

    END OF

    LINERESISTOR

    ALARM SOUNDER CIRCUIT

    Sounder Sounder

    Control panel

    Alarm sounders must bepolarised and suppressed.

    NOTE: Spur wiring is not permittedoff alarm sounder circuits.

    S1+ Sn+S1- Sn-

    Alarm sounder connections

    Note: All sounder circuits (sectors) will

    always operate together in the event of a

    fire condition.

    To comply with the requirements of BS

    5839: Part 1:1988, a minimum of two

    alarm sounder circuits should be used on

    all installations.

    1 & 2 Zone 4 & 8 Zone

    Panel Panel

    1A maximum 1.5A maximum Alarm sounder Alarm sounder

    load per panel load per panel

    The load must be shared between the

    sounder circuits.

    The alarm sounder circuits are regularly 

    pulse monitored for failure. It is important

    that the last alarm sounder is fitted with

    an end-of-line resistor.

     Where a sounder circuit is not being used,the end-of-line resistor must be fitted

    across its terminals in the control panel.

    25

  • 8/20/2019 Installer s Handbook

    27/32

    A U X I L I A R Y C O N T A C T S

     25

    These are normally 

    open (NO) and

    normally closed (NC)

    contacts that switch

    over when the panel

    goes into a fire

    condition.

    The contacts are rated

    at 24V d.c. 1A for a

    resistive load and

    should not be used

    to switch voltages in

    excess of 50V.

    The auxiliary circuits

    should be powered

    from an independent

    power supply.

    Class Change A pair of unmonitored

    terminals allow only 

    the system alarm

    sounders to be actuated

    from a remote position.

    It is considered that

    the major use for

    these will be for class

    change functions inschools and colleges.

    Note:There is no

    indication at the panel

    of class change push

    button operation.

    Initiating contacts toauxiliary equipment such as:Manned centre linkMagnetic door holders

    Contacts change over occurwith a fire condition

          N      C

          N      C

          N      0

          N      0

    Auxiliarycontacts

    Control panel

    100m maximumcable distance

    Class change

    100m maximumCable distance

    Push button switch or relay pulsedat 1 second interval (maximum)for class change application

    CC1 Cc2

    Control panel

    Auxiliary contact circuit

    Class change circuit

    26

  • 8/20/2019 Installer s Handbook

    28/32

    A U X I L I A R Y C O N T A C T S

     26 

    Common Fire and

    Fault

    The common fault

    output is a normally 

    closed electronic

    switch, which opens

     with a fault condition,

    this is for a fail safe

    operation.

    The common fireoutput is normally 

    open electronic switch

    that closes with a fire

    condition.

    Note: Each electronic

    switch has an in-line

    1K ohms resistor.

    The +24V & 0V is a

    power supply for use with auxiliary contacts,

    common fire and

    common fault circuits.

    Repeat Panel

    There can be up to 6

    repeat panels series

    connected from the

    control panel.

     A repeat panelduplicates fire and

    fault indications

    together with system

    controls.

    CommonFire

    Relay

    CommonFaultRelay

    CFT

    CFR

    Fire fault relay unit Panel outputs

    24V + Supply

    Common Fault

    Common Fire

    24+

    CFR

    CFT

    R+R-

    Control panel Repeat panel 1

    Screen must beconnected to panel

    Screen linked

    R+R-

    Fire fault & 24V outputs

    Control to repeat panel connections

    27

  • 8/20/2019 Installer s Handbook

    29/32

    C O M M I S S I O N I N G

     27

    The total system should be tested in

    accordance with the commissioning 

    requirements of BS5839:Part 1:1988 or

    other standard specified by the system

    purchaser.

    Note: The commissioning procedures

    assume that the system has been installed

    as per manufacturers instructions.

    System checks

     Acquire as fitted drawings

    Check the system has been installed

    to the project requirements.

    If appropriate, action the installer to

    carry out changes to the system.

    +

    -

    Control panel

    Connection for 12V 2.1Ah BatteriesFor 1, 2 and 4 zone panels + repeat panel

    a) Open thelower outer cover

    b) Remove thelower inner plate

    Instructions + Zone designation

    c) Fit the batteries andconnect the battery cables

    +   -

    Connection for 12V 2.8Ah BatteriesFor 8 zone panels

    +

    -

    +-

    Zones

    FIRE

    Faults

    System

    Power

    Earth

    Sounder

    DisabledSoundAlarms

    SilenceAlarms

    1 2 3

    4 5 6

    7 8 9

    0   v

    Test

    Access/Function

    1 2 3 4 5 6 7 8

    CancelBuzzer

    ResetSystem

    Power

    ShiftDisplay

    Day/Night

    Initial power up

    a) Disconnect cables to terminals of zone,

    sounder, class change, auxiliary,

    common fire and fault circuits. Ensure

    each cable is marked for reconnection

    to respective terminals later.

    b) Connect end-of-line units to zones and

    sounder circuits for initial power up.

    c) Check mains connection and switch on

    the mains power to the control panel.d) Now connect the battery supply, see

    below.

    e) Check the panel provides a normal

    healthy indication, with the green light

    lit.

    Battery installation

    28

  • 8/20/2019 Installer s Handbook

    30/32

    C O M M I S S I O N I N G

     28

    Panel terminals

    Zones

    FIRE

    Faults

    System

    Power

    Earth

    Sounder

    DisabledSoundAlarms

    SilenceAlarms

    1 2 3

    4 5 6

    7 8 9

    0   v

    Test

    Access /Function

    1 2 3 4 5 6 7 8

    CancelBuzzer

    ResetSystem

    C N5 C N6 C N7 C N8 C N9 C N1 0 C N 11 C N1 2 C N 13 C N14 C N1 5 C N1 6 C N 17 C N18 C N1 9 C N2 0 C N2 1 C N2 2 C N2 3 C N2 4 C N2 5 C N26 C N27 C N 2 8CN 29 C N3 0

    F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11SEC TOR 1 S EC TOR 2 S ECTOR 3 SEC TO R 4 S EC TO R5 S EC TOR6 SECTO R7 SECTO R  8BATTERIES

    T1 A T1 B T 2BT2AE NC N C NO NO Z 1+ Z 1- S1-S 1+ Z 2+ Z 2 - S 2-S2+ Z3+ Z 3 - S 3-S3+ Z4-Z 4+ S 4+ S 4- Z 5 + Z 5- S5-S 5+ Z 6+ Z 6 - S 6-S 6+ Z 7+ Z 7- S7-S 7+ Z 8-Z8+ S8+ S 8- C C 1 CC 2 24 + 0C FT C F R R + R -

    PO WER 1 PO WER2

    Fuses

    T1AT1B

    E

    CFR24+CFT

    0CC1CC2

    R+ R-

    NCNC NO

    NO

    Zn+Zn-

    To Zone and SounderCircuits, where `n' signifies

    circuit number 1 to 8Sn-

    Sn+Auxiliary contacts1A at 24Vdc resistive

    To transformer

    Softwareversion

    label

    P1

    P3 to P6

    P7

    Class change,Common fault,

    Common FireRepeat panel

    Panel

    Power

    ShiftDisplay

    N E L

    The terminal blocksare not fitted on the

    shadedRepeat panel.

    Day/Night

    Zone circuit tests

    a) Transfer the end-of-line capacitor unit

    to the last device (detector or manual

    call point) on a zone circuit.

    b) Connect the zone cable to the zone

    circuit terminals.

    c) Carry out zone open circuit and short

    circuit tests and check appropriate

    indications are given.

    d) Repeat the above for other zonecircuits.

    Sounder circuit tests

    a) Transfer the end-of-line resistor unit to

    the last device on a sounder circuit.

    b) Connect the sounder circuit cable to

    the sounder circuit terminals.

    c) Carry out sounder open and short

    circuit tests and check appropriate

    indications are given.

    d) Repeat the above for other sounder

    circuits.

    29

  • 8/20/2019 Installer s Handbook

    31/32

    The fire detection and alarm system should

    be tested to ensure it operates to meet thestandards and project requirements.

    Configuration

    The control and repeat panels are factory 

    set to requirements of EN54 Parts 2 and 4.

    The operation of the control and repeat

    panels and the system may be

    re-configured to site specific needs.

    CAUTION: Any special configurationsmay cause the system and equipment to

    operate outside the requirements of 

     European standards.

    Test mode A or B operation

    To facilitate tests on the fire detection

    and alarm system the control panel can

    be set to operate in a test mode.

     With Test mode A or B active: a triggered

    manual call point or fire detector in thetest zone will give:

    Test A Test B

    Fire indication System alarmfor 10 seconds sounds for the firstduration 2 seconds and at thefollowed by a same time a Firesystem reset indication is

    given for l0 seconds

    duration followedby a system reset

    Note: A detector that is still full of 

    smoke or heat will retrigger into a fire

    condition until the smoke or heat in the

    area is cleared.

    Repeat panel configuration

     Each repeat panel connected to the

    system is required to be given an address

    at both the control and repeat panels, seePanel configuration section.

    I N S T A L L E D S Y S T E M T E S T S

     29

    Sound level test

    Sound level tests should be conducted to

    standard requirements and to customer

    satisfaction.

    Other equipment tests

     Where external equipment is connected to

    the control panel using auxiliary, common

    fire and fault terminals, then these must

    be tested to project requirements.

    Log book Fill in system details on the first three

    pages of the log book.

    On completion

     Ensure the persons responsible for the

    system are made aware of:

    system operation

    access codes to controls

    basic controls

    their responsibility 

    and the need to log system events in

    the log book.

    30

  • 8/20/2019 Installer s Handbook

    32/32

    T R O U B L E S H O O T I N G

     30

    1 Zone fault light on panel, check:

    a) incorrect wiring polarity.

    b) open circuit on wiring.

    c) end of line device not fitted on

    open circuit.

    If fault does not clear, remove end of line

    devices from end of each circuit in turn,

    and fit across terminals of panel. If fault

    then clears this proves fault is external to

    panel. If fault persists, call Gent Service

     Engineer.

    2. Bell(s) (or Sounders) do not

    operate, check:

    a) Incorrect polarity.

    b) faulty sounder.

    If a) rectify - if b) call Engineer.

    3. Sounder fault on panel, check:

    1a and 1b as above and also for existence

    of unpolarised bell on alarm circuit. Also

    transfer end of line device to terminals

    on panel to determine whether fault

    internal or external as 1.

    4. Supply lamps (green) not

    illuminated, check:

    Mains supply to control or charger unit,

    if batteries are connected, buzzer shouldbe sounding.

    5. Power fault on panel, check:

    If green lights are on, buzzer should be

    sounding.

    a) Battery connections.

    b) Panel fuses.

    c) 24V Output.

    If fault persists after these checks, call

    Service Engineer.

     Alarm condition on panel when

    powered up, check:

    for broken glass on call points.

    for short circuit on trigger circuits. for

    detector in alarm state (LED on).

    If control unit can still not be reset call

    Gent Engineer

    SERVICE HOTLINE

    0500 334455