Upload
mohamed-adel
View
222
Download
0
Embed Size (px)
Citation preview
8/20/2019 Installer s Handbook
1/32
Caradon Gent Limited
Waterside Road, Hamilton Industrial Park,
Leicester LE5 1TN.
INHB/2M/4/99
8/20/2019 Installer s Handbook
2/32
installer’sHANDBOOK
FIRE DETECTION SYSTEMS
8/20/2019 Installer s Handbook
3/32
Fire alarm systemsContents
I N T R O D U C T I O N
1
BS 5839 is a standard for Fire Detectionand Alarm Systems in Buildings. Part 1
of this standard is the code of practice for
installation and services.
It is important that any contractor or
installation engineer undertaking this
type of work is fully conversant with this
standard which covers systems from
simple manual installations to fullyautomatic fire detection systems. Whilst
the standard does make some reference
to fixed extinguishing systems the
protection of electronic data processing
installations is more fully covered by
BS 6266, 1982
This booklet, published by Caradon Gent
Limited - the UK’s largest manufacturerof fire alarm equipment - is intended to
be an installer’s guide which will offer
practical assistance. It is not intended to
replace BS 5839 Part 1.
Since the circumstances of installation of
a fire alarm system can vary, we recommend
that in cases of difficulty assistance is
sought by calling Caradon Gent Limited.Copies of British Standard BS 5839
Part 1, can be obtained from:-
The British Standards Institution,
Linford Wood, Milton Keynes,
MK14 6LE.
Page
System Design 2
Examples 13
False Alarms 15
Installation of Cables 16
Panel Installation 18
Check List 21
System Schematic 22
Fire Detection Circuits 23
Auxiliary Contacts 25
Commissioning 27
Installed System Tests 29
Trouble Shooting 30
8/20/2019 Installer s Handbook
4/32
S Y S T E M D E S I G N
2
The importance of pre-design planning cannot be overstated. Many parties are
likely to have an interest in a fire
detection and alarm system. Those who
should be consulted before the design is
finalised may include:
The System Installer
The Health & Safety Executive
The Building Control Officer
The Fire Insurer
The Local Fire Authority
Consultants (including architects andengineers) and perhaps:
The Communication Link Supplierand Central Alarm Receiving Station.
The considerations prior to design
which should also be detailed within the
specifications may include:
The purpose of the system
Occupant escape times
Fire Service attendance time
Other actions to be taken in theevent of a fire
Other occupants (particularly formultiple-occupancy)
Service and maintenancerequirements
System operation requirements andresponsibilities.
The two principal reasons for installing
a fire detection and alarm system are for
the protection of life and for the
protection of property. Each needs a
different approach to a system design
and equipment selection.Most buildings will need both life and
property protection to differing degrees.
There is a classification of systems in BS5839: Part 1: 1988 which is used in this
guide.
System for Protecting Property (P)
A satisfactory fire alarm system for the
protection of property will automatically
detect a fire at an early stage, indicate its
location and raise an effective alarm in
time to summon the fire-fighting forces
(both resident staff and the fire brigade).
Type P1 - A system covering all
parts of the premises.
Type P2 - A system covering only
those parts of a building
having a high fire risk.
Systems for Protecting Life (L, M)
A satisfactory fire alarm system for the
protection of life can be relied upon tosound a fire alarm while sufficient time
remains for the occupants to escape.
As a guide, an escape route may be
considered blocked once visibility drops
below 10 metres.
Type L1 - A system covering all parts
of the premises
Type L2 - A system covering only thoseparts of a building where
there is a high risk to life if
there is fire any where in the
building
Type L3 - A system covering only areas
critical to free passage along
escape routes.
Type M - A system that provides only
for manual initiation of analarm and therefore depends
on the presence of people.
Stage 1. Talk to interested parties
8/20/2019 Installer s Handbook
5/32
S Y S T E M D E S I G N
3
All manual call points whatever thesystem type should be sited:
On all escape routes and exits to the
open air.
So that nobody has to travel more
than 30 metres to reach one.
On floor landings and staircases.
In conspicuous and well-lit positions
against a contrasting background.
So that they can be seen easily. 1.4 metres above the floor.
Fixed Temperature Heat Detector
For protection of property, particularly
where temperature can fluctuate for
natural reasons:
Near large windows
Industrial heat producing processesBeam Detector
Although traditionally restricted to
specialist applications, beam detection
may provide more cost effective solutions
to point detection over long distances.
Corridors
Warehouses
Ceiling voids
Hangars Open shopping areas
Do not use in the direct line of sight of
an infra-red source such as tungsten or
high intensity arc lights.
Duct Detector
The duct housing unit is designed to
detect smoke in air conditioning
systems. It is fitted to the outside of theduct and has 2 probes that protrude
inside the duct to monitor the air.
Stage 2. Site Manual Call Points
It is important to have an adequate
number of detectors to fully cover the
areas requiring protection. Additionally
the type of detection must be matched to
the environment and the potential fire
hazards likely to be present.Optical Smoke Detectors
For slow smouldering fires.
Corridors or Escape Routes
Wood or paper stores
Do not use in steamy, dusty or smoky
areas such as kitchens, bathrooms etc
Ionisation Smoke Detectors
For fast burning, high energy fires.
Solvent stores
Switch rooms
A mixture of optical and ionisation
sensors can be used to ensure coverage in
areas of high value, like computer rooms.
Heat Detectors
Heat detectors are used where the
environment is subject to constant levels
of smoke or dirt. Boiler rooms
Busy kitchens and laundries
Stage 3. Select and site fire detectors
8/20/2019 Installer s Handbook
6/32
Under flat horizontal ceilings Diagram 1. Maximum dimensions:
Area covered by 1 detector:
Smoke 100m2 Heat 50m2
Distance between any part of the
wall and the nearest detector:
Smoke 7.5m Heat 5.3m
Distance between detector:
Smoke 15.0m Heat 10.6m
Diagram 2. Minimum dimensions: Distance between detector and
wall: 0.5m.
Maximum spacings between
detectors are reduced when
obstructions are present.
Spacing for Smoke Detectors
S Y S T E M D E S I G N
4
Stage 3. Site fire detectors (cont.)
End View
If less than150mm ignore
If greater than10% of ceilingheight treat aswall
0.5mMin
0.5mMin
Obstacle
Diagram 2.
MID POINT
OF AREA
MID POINT
OF AREA
7.5m 7.5m
7.5m
7.5m7.5m
5.3m 5.3m
5.3m
5.3m5.3m
Spacing for Heat Detectors
8/20/2019 Installer s Handbook
7/32
CorridorsDetectors in corridors may
generally be spaced more widely.
This is NOT applicable to
life safety applications unless all
adjoining rooms have smoke
detection.
This is NOT applicable to
corridors greater than 5 metres
wide (treat as for flat horizontal
ceilings)
Detectors may be placed at
horizontal distances extended
up to 50% of the difference
between the actual corridor
width and 5 metres (see table).
E.g. (5-2) x 0.5=1.5m.
Stage 3. Fire Detectors (cont).
S Y S T E M D E S I G N
5
Corridor Spacing between Detectors (max) width
(m) Smoke (m) Heat (m)
1.2 18.8 14.4
1.6 18.3 14.02.0 17.9 13.5
2.4 17.4 13.0
2.8 17.0 12.5
3.2 16.5 12.0
3.6 16.0 11.5
4.0 15.5 10.9
4.4 15.0 10.3
4.8 14.4 9.7
S S
H H
Plan View
SmokeDetector
SmokeDetector
HeatDetector
HeatDetector
7 . 5 + 1 . 5 m
7 . 5 + 1 . 5 m
7 . 5 + 1 . 5 m
7. 5 +
1. 5 m
7. 5 +
1. 5 m
7. 5 +
1. 5 m
17.9 m
5 . 3 + 1 . 5 m
5 . 3 + 1 . 5 m
5 . 3 + 1 . 5 m 5. 3 +
1. 5 m
5. 3 +
1. 5 m
5. 3 +
1. 5 m
13.5 m
2 m
2 m
Wall
Wall
Detector spacing along corridors.
8/20/2019 Installer s Handbook
8/32
S Y S T E M D E S I G N
6
Siting limits for Smoke Beam Detectors
Detector/ General applications Automatic link to a mannedSensor type centre. Fire brigade response is
normally within 5 minutes.
(m) (m)
Smoke 10.5 15.0
Heat grade 1 9.0 13.5
Heat grade 2 7.5 12.0
Heat high temp. 6.0 10.5
Beam 25 40
Minimum (m) Maximum (m)
Height of optical beam above floor 2.7 25*Optical beam length 1 100
Distance of optical beam from a flat ceiling or apex 0.3 0.6
Horizontal distance between optical beams measured at - 14right angles to a beam
Horizontal distance between optical beam and an adjacent See Notes 8 wall or partition
* The height may be increased to 40m provided that the general height to which combustibles are stored in thebuilding does not exceed 5m and that the fire brigade can attend within 5 minutes.
NOTE: Generally the beam should not pass closer, to a wall or partition, than 500mm and not closer to an obstruction,than 600mm. However, up to 3m of the beam may be closer than this. Always consult Gent if in doubt.
Where the beam detec tor is mounted in the apex of a pitched or ‘north-light’ roof the horizontal distance can be increasedby 1% for each degree of slope up to a maximum of 25% (eg 20º slope of roof 20% of 7.5m = 1.5m).
Pitched roofs
A row of sensors should be installed
along the apex of any pitched roof or
‘north-light’ roof. Smoke sensors should
be not more than 600mm from the apex
of the roof. Horizontal spacing between
sensors may be extended when used
under pitched roofs.
The horizontal distance may be extended
by up to 1% for each degree of slope of
the roof (relative to horizontal) up to a
maximum of 25%.
Wall
Roof Roof
600mmMax
20º pitch allows spacingto be extended 20% forexample from 7.5m to9.0m
20º
Heights
Maximum heights of detectors are dependant on the fire brigade response available:
8/20/2019 Installer s Handbook
9/32
Further considerations (checklist) For a Type P1 system every part of
the building should be suitably
protected. For this purpose each
effectively enclosed space should be
considered separately.
Areas covered by a Type P2 system
should be separated from unprotected
areas by a fire resisting construction.
Voids not more than 800mm deep
need not be protected unless fire can
spread through them from one to
the other.
Where rooms are divided by
partitions or storage racks reaching to
within 300mm of the ceiling each
section should be protected separately.
Shafts for elevators, lifts, hoists,
escalators and enclosed chutes
through floors and stairways should
be protected by detectors at the top
of the shaft and within 1.5m of
openings on to each floor.
Where an escalator or staircase has a
sloping ceiling a detector may need
to be sited on that ceiling. Enclosed staircases should be
protected by detectors on each main
landing within the staircase.
Lantern lights should be protected
by a detector unless they are less
than 800mm in height above the
ceiling and are not used as ventilation.
Extra detectors may be needed tocope with structural features within a
room. Consideration must be given
to possible adverse air flows when airconditioning and ventilation systems
are in use.
If a detector is concealed, it may be
desirable to provide a remote visible
indication of its operation.
Care should be taken when siting to
ensure that adverse conditions such
as high levels of shock or vibration
are not encountered.
Stage 3. Fire Detectors (cont).
S Y S T E M D E S I G N
7
Design Tip! It is good practice to site
detectors in toilets, however they
need not haveindependent coverage if cover is
provided in a common lobby.
8/20/2019 Installer s Handbook
10/32
S Y S T E M D E S I G N
8
Life ProtectingThe minimum sound levels must be
produced in all occupiable parts of the
building. Occupiable parts include
restricted areas such as service ducts
where people could be working on
occasion. As audible alarms are essential
for the protection of life, a minimum of
two independent sounders must always
be provided to guard against the failureof one. A minimum of
one sounder should be
provided in each fire
compartment.
Property Protection
In Type P systems the
minimum sound levels
must be produced in
the areas required tosummon fire fighting
assistance. A sounder
should also be provided
close to the control and
indicating equipment
and there should be
one outside to direct
services to the correct
entrance.In practice most fire
detection and alarm
systems involve
elements of both
property and life
protection.
Most systems should
therefore meet all the
above requirements.In general fire alarm sounders must not
be used for any other purpose, with the
established exception of class changes inschools where coded signals of not more
than five seconds duration can be used.
Public address equipment can be used to
give warning of fire subject to certain
conditions. Visual alarm signals should
be considered to complement alarm
sounders where there is a high level of
noise or the occupants may be hearing-
impaired.
Stage 4. Site Alarm Sounders
Conversationat 1m
Thresholdof Pain
Hammeringon Steel
HeavyMachine
Noise
BoilerFactory Noise
Punch Press
Room Noise
LightMachine
Noise
Heavy AssemblyRoom Noise
Heavy StreetNoise
Dispatch RoomNoise
Light AssemblyRoom Noise
Stock RoomNoise
Average OfficeNoise
Light StreetNoise
Typical ambient noise levels dB (A)
Whisper at1m
40 50 60 70 80 90 100 110 120 130 14030
dB(A)
8/20/2019 Installer s Handbook
11/32
Sound output All sounders in a building should be of a
similar type, do not mix electronic
sounders and bells.
The sound level will reduce by 6dB every
time the distance from the sounder is
doubled. Sound levels are normally
quoted on-axis, ie. directly in-line with
the middle of the sounder.
This is normally the loudest position.
In order to assess the sound level at any
particular point it is necessary to allow
for the distance from the sounder AND
the angle off-axis.
Sounders should produce:
Minimum sound level of 65 dB or
at least 5 dB greater than any
background noise that is likely to
persist for more than 30 seconds 75 dB is required at the bedhead
of a sleeping person
Note: The sound level near the control
panel should not be so high that a
telephone cannot be used to summon
help from the fire brigade.
Attenuation
Fire alarm sounders may often be heard
in adjacent rooms but the sound level will be attenuated by any door.
Typical attenuation figures are:
20 dB by an internal door
30 dB by a fire door
It is also important to consider the
room’s use. Are there any obstacles
(including furniture) to the sound, and
how many people will be present in theroom? Both people and furnishings will
attenuate the sound level.
Stage 4. Site Alarm Sounders (cont).
S Y S T E M D E S I G N
9
Design Tips!1. Use sensor sounders in small rooms
where the sound level has been
attenuated by door partitioning
(32000/Vigilon systems only).
2. Always site sounders in
toilets and bedrooms.
3. “Back-to-back” sounders wherever
possible to reduce wiring costs.
Sensor Sounder in a small office.
100dB(1m)
85dB(1m)
8/20/2019 Installer s Handbook
12/32
S Y S T E M D E S I G N
10
It is now possible to obtain bothconventional and analogue addressable
control panels to suit a wide variety of
building sizes and types.
There should be a plan of the building,
showing at very least the entrances, to be
placed on or near the control equipment.
If there are several entrances,
consideration should be given to the
provision of a repeat panel at eachentrance.
When selecting the control equipment
the current consumption of both
detection circuits and alarm circuits must
be considered, this will be found in the
relevant product literature.
Many control and indicating panels
include an integral power supply unit but
in the larger systems it may be
necessary to provide an external unit
either in place of or in addition to the
internal unit. The need for extra
standby power can be determined from
the total current consumption of the
system and the specification of the
supply.
Standby PeriodIn the event of a mains failure, the
minimum standby period is 24 hours in
normal conditions followed by 30
minutes at full alarm load. In special
circumstances, such as the availability of
a standby generator, these periods can be
reduced.
When a building is unoccupied for
significant periods, the normalcondition standby period should be
extended to 24 hours longer than the
period of non-occupation. For example,if a building is unoccupied from 6.00 p.m.
Friday to 8.00 a.m. Monday, the fire
system should have a standby period of
86 hours normal condition, followed by
an alarm period of 30 minutes.
Siting control and indicating equip-
ment
Control and indicating equipment should
be sited:
In an area of low fire risk.
On the ground floor in the vicinity of
an entrance used by the fire brigade.
In an area common to all building
users.
Where automatic detectors are in use,
the control equipment area must be
protected.
Where ambient light levels are such
that visual indications can be clearly
seen.
With a first alarm sounder sited
adjacent.
Stage 5. Select Control & Indicating Equipment
Design Tip! For minimum standby period it is
important to consider the worst case.
For instance, is there cover for
weekends and bank holidays?
Most reputable manufacturers design
control panels with 48 hour standby,
however 72 hours or longer may be
required.
8/20/2019 Installer s Handbook
13/32
Door Retainers and RelaysDoor retainers will hold doors open
during normal conditions but allow them
to close in the event of fire.
A manually operated switch may also be
included if required.
The mechanism comprises a powerful
electromagnet and a door plate.
The electromagnet may be wall or floor
mounted.Batteries
Most internal and external power supply
units will normally be supplied with (or
have provision for) sealed lead-acid cells
as they need a minimum of
maintenance.
System Interfaces
While a fire detection and alarm systemmust be capable of operating in isolation,
other building systems may need to
receive a signal when a fire alarm is
activated - or may need to activate the
fire alarm system when they are operated.
For example, a fire detection system may
need to shut down the normal ventilation
system or to activate a fixed extinguishing
system.Conversely, if a fixed extinguishing
system is manually operated or a gas
detection system is activated, the fire
alarms may need to be sounded.
In such cases, a system interface is
needed, which may be a simple relay for
a conventional system or a number of
addressable inputs and outputs for an
addressable system.
Power Supply UnitsGent control and indicating panels
include a stand-by power supply unit
complete with batteries. However, in
larger systems the current requirements
are often very different and therefore a
separate power supply unit, external to
the control panel, may be needed.
Manned Centre Links
Where the system includes the need forrapid fire service attendance an automatic
link to a permanently staffed centre can
be provided. There are several methods
available and before selecting one it is
recommended that the matter be
discussed with the Gent Technical
Hotline on 0800 064 3344
Fixed Extinguishing Systems Where the protection of property is
important and a rapid attendance cannot
be guaranteed, the provision of a fixed
extinguishing system should be considered.
Gent can supply a range of gaseous
extinguishing systems which are ideal
when a liquid extinguishant, such as
water, might itself cause extensive damage.
Stage 5. Select Control & Indicating Equipment (cont.)
S Y S T E M D E S I G N
11
8/20/2019 Installer s Handbook
14/32
S Y S T E M D E S I G N
12
ZoningFor several reasons a building must be
split into a number of fire detection and
alarm zones.
The prime purpose of zoning is to
identify the location of a fire or fault:
The following criteria govern the
number and size of zones:
The floor area of a single zone should
not exceed 2000m2.
No person in a zone should have to
travel more than 30m to visually
determine the position of a fire.
The zone should not cover more
than one storey unless the total
building area is less than 300m2.
Stairwells, lift shafts and flue-like
openings should be treated asseparate zones.
It is permissible for a zone to cover a
whole number of fire compartments,
or for a fire compartment to contain a
whole number of zones, but a zone
cannot extend over parts of two or
more fire compartments.
For multiple-occupancy buildings the
occupancy boundaries shouldcoincide with zone boundaries.
If there is an area of special fire risk,
consideration should be given to
setting up a separate zone for rapid
identification of a fire in that risk
area.
Notes:1. A fire compartment is an area
bordered by a fire-resisting structure
usually at least 30 minutes resistance.
2. Zone limits can be relaxed only in
certain Type M systems.
3. To avoid misleading indication of the
position of a fire, consideration
should be given to the separate
zoning of manual call points,particularly those on staircase
landings. This can be achieved by
indicating automatic detectors and
manual call points separately.
Stage 6. Zoning
Design Tip! Remote indicator lamps can be used
to reduce the need for small complex
zones.
They are also useful for voids and
locked cupboards.
8/20/2019 Installer s Handbook
15/32
Stage 2. Site Manual Call Points
Stage 3. Site Fire Detectors
E X A M P L E S
13
S
SS
S S
S
S
S S S
SSS
S
H
H
H
H
BB
S
H
On escape routes and exits tothe open air.
So that no one has to travelmore than 30m to reach one.
On floor landings and staircases.
Area covered by smoke detector= 100m2 max.
Area covered by heat detector= 50m2 max.
Distance between smokedetectors = 15m max.
Distance between heat detectors= 10.6m max.
Check special rules for corridorsless than 5m wide.
Maximum beam length =100m.
Cover toilets and stairways.
Optical smoke detector
Heat detector
Beam detector
S
H
> 1 7 .5 m
approx 550m2
Stores
Assembly Area
Warehouse
BoilerRoom
Office
Reception
Canteen
OfficeWC WC WC
WC
Stores
Assembly Area
Warehouse
BoilerRoom
Office
Reception
Canteen
OfficeWC WC WC
WC
Manual Call Point
B
Travel distances >30m require a call point.
8/20/2019 Installer s Handbook
16/32
E X A M P L E S
14
Stage 4. Site Alarm Sounders
Stage 6. Zoning
Minimum 65 dB required or 5dBgreater than background noise.
75 dB required at bedheads.
Sound level reduces by 6 dB forevery time the distance fromthe sounder is doubled ie.100 dB - 1m94 dB - 2m88 dB - 4m82 dB - 8m76 dB - 16m
Sound level is attenuated by30dB for fire doors and 20 dBfor internal doors.
Stage 5. Site ControlEquipment
For ease of access by fire brigade.
Floor areas should not exceed2000m2.
Stores
Assembly Area
Warehouse
BoilerRoom
Office
Reception
Canteen
OfficeWC WC WC
WC
Stores
Assembly Area
Warehouse
BoilerRoom
Office
Reception
Canteen
Office
WC WC WC
WC
Remote LEDs.
Zone 1
Zone 2
Zone 3
Zone 4
Fire panel.
8/20/2019 Installer s Handbook
17/32
Many false alarms result from causes that were not considered at design or
installation stages and could otherwise
have been avoided. Common causes of
false alarms include:
Electrical or mechanical faults,
perhaps caused by vibration,
impact or corrosion.
Heat, flames or smoke
generated from industrialprocesses or cooking.
Fumes from engine or
machine exhausts.
High air velocities caused
by strong draughts or air
conditioning.
Work being carried out in
the protected area withoutthe necessary precautions
being taken.
Servicing or testing
equipment without prior
notification to those likely
to receive indication.
Electrical transients or radio
interference.
Inadequate servicing.
The build-up of dust or dirt or the
presence of insects within a detector.
Changes, including change of use
within the building.
Accidental or malicious operation.
Fire detection and alarm equipment isdesigned to minimise false alarms,
particularly with the introduction of
advanced, analogue systems. However,
even very sophisticated equipment
cannot compensate for a badly designed
system or a poor installation.
It is therefore vital that potential causes
of false alarms are considered and the
risks minimised at the design stage.
F A L S E A L A R M S
15
8/20/2019 Installer s Handbook
18/32
I N S T A L L A T I O N O F C A B L E S
16
Since every site is different, it is only possible to give general guidance, refer to
BS 5839 for more details.
A fire alarm system depends on its
wiring. There are 2 group classes of
cable:
Cables NOT required to operate
after a fire has been detected e.g.
detectors and manual call points
(group 1). Cables required to operate during a
fire, e.g. power supplies and sounders
(group 2).
While mineral insulated cables are
preferable for all fire alarm applications
the following cables can be used for the
two groups:
Group 11. MICC to BS 6207: Part 1 (with or
without sheath)
2. Cables complying with BS 6387categories AWX, SWX, A or S.
3. PVC - insulated to BS 6004 sheathedor non-sheathed with mechanicalprotection.
4. Rubber insulated to BS 6007
5. PVC single type BK, BR and BU toBS 6231
6. PVC insulated SWA to BS 6346
7. Cross-linked polyethylene or hardethylene-propylene rubber insulatedSWA to BS 5467
8. Polyethylene insulated PVC sheathedcoaxial cable to the dimensional
requirements of BS 2316: Part 3 but with a minimum of 16 strands /0.2mm diameter central conductor.
9. Cables designed for the detection ofheat must be configured to initiatethe alarm system should a fire occuralong the cable.
Group 2
Cables 1 or 2 from group 1.
Cables 3 to 9 from group 1, providing
that they are protected either by burying
them in a wall and covering them with
12mm of plaster or equivalent, orprotecting them from a significant fire
risk by shielding them with a wall,
partition or floor having a minimum
demonstrable 30 minutes fire resistance.
These requirements may in some cases
be reduced when included in areas of low
fire risk or when covered by an automatic
extinguishing system.
Certain cables may also need mechanical
protection against impact, abrasion or
rodent attack. As a guide, cables 1, 6 and
7 will not need further protection but all
others may in risk circumstances.
BS 5839: Part 1 gives full details.
Other types of cables can be used
provided that their suitability can be
demonstrated.Conductors carrying fire alarm power or
signals should be separated from
conductors used for other systems.
Wiring
8/20/2019 Installer s Handbook
19/32
Cables should be installed in accordance
with the good practices recommended in
the 16th Edition of the IEE Wiring
Regulations (BS 7671).
Other than the segregation of cables the
regulations exclude fire alarms if they are
fed from a safety source. In effect this
applies to extra low voltage systems,
which include systems in general use for
fire alarm circuits. All cables and apparatus directly
connected to a public supply 240V a.c.
(low voltage) such as supplies to
indicators, power supplies and mains
operated door holders must comply with
the 16th Edition in respect of the
installation of cables and the provision of
isolation and switching.
Connection to mains supply should be via an isolating switch fuse reserved
solely for the purpose. Its cover must be
painted red and labelled FIRE ALARM -
DO NOT SWITCH OFF.
If required a separate RCCB should be
used for fire alarm systems. Fire alarm
cables are defined as ‘Category 3 Circuit’.
Cables of Category 1 Circuits (low voltage and connected directly to a mains
supply) must not be drawn into the same
conduit, duct or ducting as Category 3
(fire alarm circuits).
Where Category 3 Circuits are installed
in a channel of trunking containing
circuits of any other category, these
circuits must be segregated from the
latter by continuous partitions, such thatthe integrity of the Category 3 (fire alarm
circuits) is not reduced.
In effect these regulations mean that
unless MICC is used, fire alarm cable
circuits must never be mixed with any
other circuits; neither should they be
mixed with any other circuits in a multi-
core cable.
Conductor size should take voltage drop
into account. In any case conductors
should have a cross-sectional area of not
less than 1mm2
or if stranded of not lessthan 0.5mm2.
Where possible cables should be routed
through areas of low fire risk.
Cables installed in damp, corrosive or
underground locations should be PVC
sheathed. Where there is a risk of
mechanical damage, cables should be
protected accordingly.
Cables in cavities or voids should be
separated from other cables by 300mm
unless enclosed in a conduit, ducting or
trunking.
I N S T A L L A T I O N O F C A B L E S
17
8/20/2019 Installer s Handbook
20/32
P A N E L I N S T A L L A T I O N
18
Dedicatedmains
cableentry points
Panel size395mm wide x 274mm high x 87mm deep
89mm 89mm
1 9 m m
1 9 7 m m
111mm4-off earth points
How to knock-ina cable entry point
Knock here to openthe entry point
Red
Battery connectionsBlack
Fixing pointsfor theelectronicassembly
Electronic assembly
Panel Backbox
Transformercables
to electronicassembly
Earth connectionto the electronic
assembly
NB: The following installation method
is based on the Xenex panel.
Panel Fixing
a) Remove panel from its packing, but
retain the carton for storage of spare
parts and loose items.
b) Remove the top and bottom inner plates.
c) Check the spares parts supplied with
those listed in installation manual. If
replacement parts are required at anytime, only spares that are of the same
specification should be used.
d) Remove the transformer and earth
connections from the electronic
assembly, and then remove the
electronic assembly from the panel.Store the electronic assembly in a safeplace until required.
e) Remove the appropriate knock-in onthe panel case for cable entry.
f) Hold the panel on the wall in thedesired mounting position and markthe positions of the fixing holes.
g) Secure the panel to the wall using
suitable fixing such that adequatesupport is provided to the controlpanel assembly. A top centre keyholefixing is provided on the case to allow the panel to be hooked whilst thebottom two fixing points are located.
Panel fixing
8/20/2019 Installer s Handbook
21/32
P A N E L I N S T A L L A T I O N
19
h) Connect the mains supply cable to
the panel .The cable:
must be through one of the dedicated
cable entry into the panel.
via an unswitched fused spur unit,
rated 5A for the 1 & 2 Zone Control
and Repeat panels and 7A for 4 & 8
Zone panels.
The fused spur isolator cover should be
red and marked:
FIRE ALARM - DO NOT SWITCH
OFF
The fused spur units must be fed from a
dedicated switch or protective device at
the local mains supply distribution
board.
i) Wire the system. With the exception
of the mains cable, all cables should
remain unconnected at the panel
leaving 300mm tail. Mark each core
identifying its final point of connection.
4-off earth points
13-back13-topcable entry points
Gland
Earth
drain
Cable
Cable termination
Panel backboxElectronic assembly
Panel Fixing (Wiring)
Cable entry &earth points
CAUTION: DO NOT undertake high
voltage insulation tests WITH THE
CABLES CONNECTED to their
terminals. Such a test may damage the
electronic circuitry in the system equipment.
j) Refit the electronic assembly into the
panel and connect the transformer and
earth cables previously removed.
Note: Each terminal in a panel will accept a
maximum conductor size of 2.5mm
square.
Note: The installation of all out standing
parts are usually carried out during
Commissioning of the System.
Store all spare parts and loose components
including the batteries inside the panel
carton and keep in a safe place until
required.
8/20/2019 Installer s Handbook
22/32
P A N E L I N S T A L L A T I O N
20
For the wiring of:
Length per circuit Type of circuit Recommended cables, alsosee BS5839:Part 1 guidance
2m Mains power supply cord see power supply cord
1Km Zone circuit
1km Sounders circuit
100m Auxiliary circuit
l00m Common fire and fault circuit
l00m Class change circuit
500m Repeat panel link Belden type screened 2-coretwisted pair
The guidance of BS5839: Part 1:1988
should be followed. The use of cables
such as (MICC or Belden) are
recommended.
Generally available electrical installationcable may be used, providing the cable is:
to BS6387
with no more than 2 - cores
each core having no less than 1.5mm2
cross section area
with an inherent or through metal
conduit screen for earth continuity in
order to produce electrical productionand screening
having protection from heat and
mechanical damage
Power supply cord
This should be a 3-core cord having a
rated current of:
5A with a nominal core cross sectional
area of 0.75mm2
provided the lengthof the cord does not exceed 2m
Cables
Power Supply
See BS5839: Part 1 guidance
Standby Supply
With the recommended battery and zone
loading the control panel will provide a
standby supply under mains failureconditions, for a period of 72 hours
followed by 30 minutes of alarm load.
24V Supply
The power supply terminals ‘24 + and 0’
may drive external ancillary equipment
and is designed to be used in conjunction
with auxiliary contacts and common fire
and fault outputs.
Note: The use of the 24V supply will
affect the panel standby capability.
8/20/2019 Installer s Handbook
23/32
C H E C K L I S T
21
Notes to the Installer - Checks
The power-up and commissioning isdone by the servicing organisation.
The wires between the termination
point and terminals should be short
and straight as possible.
The cables of the fire detection and
alarm system and other systems
should usually be separated by at least
160mm, unless dedicated conduit or
ducting is used.
Do not use any part of building
structure for earthing.
The cable length between the Repeat
LED unit and respective fire detector
where used, should not exceed l0m
Cable Glands should be used on the
equipment for the mains supply cable.
Unused knockouts on productenclosure that have been removed,
should not be left open.
Requirements
It is recommended that the installer
follow the general requirements of:
BS5839:Part 1:1988, which is the code
of practice relating to the fire
detection and alarm Systems forbuildings.
the relevant parts of the BS 7671
Requirements for Electrical
Installation Institute of Electrical
Engineers Wiring Regulations l6th
edition
Second fix installation
To prevent the possibility of damage or
dirt.degrading the performance orappearance of the System Products,
the installation of second fix items should
be delayed until all major building work
in the area is complete.
Fixtures and fittings
It is the installers responsibility to
provide:
adequate fixtures and fittings for the
type of construction surface onto
which a product is to be installed.
as an aid to this decision, the weightand overall size of each full assembly
together with implications on cable
entries and routing should be taken
into consideration.
Note: All these procedures assume that
the cable, gland, steel box (BESA box)
and other related accessories are provided
by the installer
As Fitted wiring drawings
The installer should acquire:
site specific information from the
interested parties, for details on the
location of products for installation
the acquired information together
with the relevant standards should be
used to assist the work.
Earth continuity
To maintain earth continuity, the cable
screen must be continued through each
system device, whether the earth is
connected to a device or not.
8/20/2019 Installer s Handbook
24/32
S Y S T E M S C H E M A T I C
22
E N
D O F
L I N
E
R E S I S T O R
1 0 K
O h m s
A L A R M
S O U N D E R C I R C U I T
I n i t i a t i n g c o n t a c t s t o
a u x i l i a r y e q u i p m
e n t ,
s u c h a s m a n n e d
c e n t r e l i n k
a n d m a g e n e t i c
d o o r h o l d e r s
T o
d e d i c a t e d
m
a i n s i s o l a t i n g
p r o t e c t i o n u n i t
N
E
L
M A I N S
T E R M I N A L
N C
T A
T B
E
N C N 0 N 0
A u x i l i a r y
c o n t a c t s
T o
T r a n s f o r m e r ( s )
B
o a r d
Z o n e
S o u n d e r
Z o n e
S o u n d e r
T h e r e c a n b e u p t o 8
F i r e d e t e c t i o n ( z o n e ) c i r c u i t
a n d s o u n d e r c i r c u i t d e p e n d i n g
o
n t h e p a n e l s i z e
C l a s s
c h a n g e
R e p e a t
p a n e l
P u s h b u t t o n s w i t c h
f o r c l a s s c h a n g e a p p l i c a t i o n
E N D O F
L I N E
C A P A C I T O R
U N I T
R E D
B L A C K
F I R E D E T E C T I O N
( Z O N E ) C I R C U I T
F I R E
D E T E C T O R
M A N U A L
C A L L
P O
I N T
A l a r m s o u n d e r s
b e p o l a r i s e d
.
m u s t
: S p u r w i r i n g i s n o t p e r m i t t e d o f f f i r e d e t e c t i o n
c i r c u i t s .
N O T E
a n d a l a r m s
o u n d e r
F i r e a l a r m c o n t r o l p a n e l
C C 1
C C 1
2 4 +
2 4 V + s u p p l y
0 V s u p p l y
C o m m o n f a u l t
C o m m o n f i r e
C F T
C F R
R +
R -
0
Z 1 +
Z n +
Z 1 -
Z n -
S 1 +
S n +
S 1 -
S n -
8/20/2019 Installer s Handbook
25/32
F I R E D E T E C T I O N C I R C U I T S
23
Each zone circuit can have up to 2mA
load. An end-of-line
capacitor unit is required for zone
circuit monitoring, which must be fitted
after the last detector or manual call
point on the circuit.
All manual call points used must
have a 470 ohms series resistor.
Note: If a Beam detector is used, then it
must be powered from an independentsupply.
Zone circuit connections
END OF
LINE
CAPACITOR
UNIT Unused Zone circuits mustbe terminated with anend-of-line Capacitor unitor bipolar capacitor
RED
BLACK
FIRE DETECTION (ZONE) CIRCUIT
FIREDETECT OR
A fire detector headmay be fitted
to a diode-base forcontinuity when a detector
head is removedand there can be
a maximum of up to20 diode-basesper zone circuit
MANUALCALLPOINT
NOTE: Spur wiring is not permittedoff zone circuits.
ZoneCircuit
ZoneCircuit
Contol panel
Z1+ Z2+Z1- Z2-
BLACK RED
Where a zone circuit is not being used,
the end-of-line capacitor unit must be
fitted across its terminals
in the panel.
24
8/20/2019 Installer s Handbook
26/32
F I R E D E T E C T I O N C I R C U I T S
24
Sounder circuit that isnot used is terminatedwith an end-of line resistor
END OF
LINERESISTOR
ALARM SOUNDER CIRCUIT
Sounder Sounder
Control panel
Alarm sounders must bepolarised and suppressed.
NOTE: Spur wiring is not permittedoff alarm sounder circuits.
S1+ Sn+S1- Sn-
Alarm sounder connections
Note: All sounder circuits (sectors) will
always operate together in the event of a
fire condition.
To comply with the requirements of BS
5839: Part 1:1988, a minimum of two
alarm sounder circuits should be used on
all installations.
1 & 2 Zone 4 & 8 Zone
Panel Panel
1A maximum 1.5A maximum Alarm sounder Alarm sounder
load per panel load per panel
The load must be shared between the
sounder circuits.
The alarm sounder circuits are regularly
pulse monitored for failure. It is important
that the last alarm sounder is fitted with
an end-of-line resistor.
Where a sounder circuit is not being used,the end-of-line resistor must be fitted
across its terminals in the control panel.
25
8/20/2019 Installer s Handbook
27/32
A U X I L I A R Y C O N T A C T S
25
These are normally
open (NO) and
normally closed (NC)
contacts that switch
over when the panel
goes into a fire
condition.
The contacts are rated
at 24V d.c. 1A for a
resistive load and
should not be used
to switch voltages in
excess of 50V.
The auxiliary circuits
should be powered
from an independent
power supply.
Class Change A pair of unmonitored
terminals allow only
the system alarm
sounders to be actuated
from a remote position.
It is considered that
the major use for
these will be for class
change functions inschools and colleges.
Note:There is no
indication at the panel
of class change push
button operation.
Initiating contacts toauxiliary equipment such as:Manned centre linkMagnetic door holders
Contacts change over occurwith a fire condition
N C
N C
N 0
N 0
Auxiliarycontacts
Control panel
100m maximumcable distance
Class change
100m maximumCable distance
Push button switch or relay pulsedat 1 second interval (maximum)for class change application
CC1 Cc2
Control panel
Auxiliary contact circuit
Class change circuit
26
8/20/2019 Installer s Handbook
28/32
A U X I L I A R Y C O N T A C T S
26
Common Fire and
Fault
The common fault
output is a normally
closed electronic
switch, which opens
with a fault condition,
this is for a fail safe
operation.
The common fireoutput is normally
open electronic switch
that closes with a fire
condition.
Note: Each electronic
switch has an in-line
1K ohms resistor.
The +24V & 0V is a
power supply for use with auxiliary contacts,
common fire and
common fault circuits.
Repeat Panel
There can be up to 6
repeat panels series
connected from the
control panel.
A repeat panelduplicates fire and
fault indications
together with system
controls.
CommonFire
Relay
CommonFaultRelay
CFT
CFR
Fire fault relay unit Panel outputs
24V + Supply
Common Fault
Common Fire
24+
CFR
CFT
R+R-
Control panel Repeat panel 1
Screen must beconnected to panel
Screen linked
R+R-
Fire fault & 24V outputs
Control to repeat panel connections
27
8/20/2019 Installer s Handbook
29/32
C O M M I S S I O N I N G
27
The total system should be tested in
accordance with the commissioning
requirements of BS5839:Part 1:1988 or
other standard specified by the system
purchaser.
Note: The commissioning procedures
assume that the system has been installed
as per manufacturers instructions.
System checks
Acquire as fitted drawings
Check the system has been installed
to the project requirements.
If appropriate, action the installer to
carry out changes to the system.
+
-
Control panel
Connection for 12V 2.1Ah BatteriesFor 1, 2 and 4 zone panels + repeat panel
a) Open thelower outer cover
b) Remove thelower inner plate
Instructions + Zone designation
c) Fit the batteries andconnect the battery cables
+ -
Connection for 12V 2.8Ah BatteriesFor 8 zone panels
+
-
+-
Zones
FIRE
Faults
System
Power
Earth
Sounder
DisabledSoundAlarms
SilenceAlarms
1 2 3
4 5 6
7 8 9
0 v
Test
Access/Function
1 2 3 4 5 6 7 8
CancelBuzzer
ResetSystem
Power
ShiftDisplay
Day/Night
Initial power up
a) Disconnect cables to terminals of zone,
sounder, class change, auxiliary,
common fire and fault circuits. Ensure
each cable is marked for reconnection
to respective terminals later.
b) Connect end-of-line units to zones and
sounder circuits for initial power up.
c) Check mains connection and switch on
the mains power to the control panel.d) Now connect the battery supply, see
below.
e) Check the panel provides a normal
healthy indication, with the green light
lit.
Battery installation
28
8/20/2019 Installer s Handbook
30/32
C O M M I S S I O N I N G
28
Panel terminals
Zones
FIRE
Faults
System
Power
Earth
Sounder
DisabledSoundAlarms
SilenceAlarms
1 2 3
4 5 6
7 8 9
0 v
Test
Access /Function
1 2 3 4 5 6 7 8
CancelBuzzer
ResetSystem
C N5 C N6 C N7 C N8 C N9 C N1 0 C N 11 C N1 2 C N 13 C N14 C N1 5 C N1 6 C N 17 C N18 C N1 9 C N2 0 C N2 1 C N2 2 C N2 3 C N2 4 C N2 5 C N26 C N27 C N 2 8CN 29 C N3 0
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11SEC TOR 1 S EC TOR 2 S ECTOR 3 SEC TO R 4 S EC TO R5 S EC TOR6 SECTO R7 SECTO R 8BATTERIES
T1 A T1 B T 2BT2AE NC N C NO NO Z 1+ Z 1- S1-S 1+ Z 2+ Z 2 - S 2-S2+ Z3+ Z 3 - S 3-S3+ Z4-Z 4+ S 4+ S 4- Z 5 + Z 5- S5-S 5+ Z 6+ Z 6 - S 6-S 6+ Z 7+ Z 7- S7-S 7+ Z 8-Z8+ S8+ S 8- C C 1 CC 2 24 + 0C FT C F R R + R -
PO WER 1 PO WER2
Fuses
T1AT1B
E
CFR24+CFT
0CC1CC2
R+ R-
NCNC NO
NO
Zn+Zn-
To Zone and SounderCircuits, where `n' signifies
circuit number 1 to 8Sn-
Sn+Auxiliary contacts1A at 24Vdc resistive
To transformer
Softwareversion
label
P1
P3 to P6
P7
Class change,Common fault,
Common FireRepeat panel
Panel
Power
ShiftDisplay
N E L
The terminal blocksare not fitted on the
shadedRepeat panel.
Day/Night
Zone circuit tests
a) Transfer the end-of-line capacitor unit
to the last device (detector or manual
call point) on a zone circuit.
b) Connect the zone cable to the zone
circuit terminals.
c) Carry out zone open circuit and short
circuit tests and check appropriate
indications are given.
d) Repeat the above for other zonecircuits.
Sounder circuit tests
a) Transfer the end-of-line resistor unit to
the last device on a sounder circuit.
b) Connect the sounder circuit cable to
the sounder circuit terminals.
c) Carry out sounder open and short
circuit tests and check appropriate
indications are given.
d) Repeat the above for other sounder
circuits.
29
8/20/2019 Installer s Handbook
31/32
The fire detection and alarm system should
be tested to ensure it operates to meet thestandards and project requirements.
Configuration
The control and repeat panels are factory
set to requirements of EN54 Parts 2 and 4.
The operation of the control and repeat
panels and the system may be
re-configured to site specific needs.
CAUTION: Any special configurationsmay cause the system and equipment to
operate outside the requirements of
European standards.
Test mode A or B operation
To facilitate tests on the fire detection
and alarm system the control panel can
be set to operate in a test mode.
With Test mode A or B active: a triggered
manual call point or fire detector in thetest zone will give:
Test A Test B
Fire indication System alarmfor 10 seconds sounds for the firstduration 2 seconds and at thefollowed by a same time a Firesystem reset indication is
given for l0 seconds
duration followedby a system reset
Note: A detector that is still full of
smoke or heat will retrigger into a fire
condition until the smoke or heat in the
area is cleared.
Repeat panel configuration
Each repeat panel connected to the
system is required to be given an address
at both the control and repeat panels, seePanel configuration section.
I N S T A L L E D S Y S T E M T E S T S
29
Sound level test
Sound level tests should be conducted to
standard requirements and to customer
satisfaction.
Other equipment tests
Where external equipment is connected to
the control panel using auxiliary, common
fire and fault terminals, then these must
be tested to project requirements.
Log book Fill in system details on the first three
pages of the log book.
On completion
Ensure the persons responsible for the
system are made aware of:
system operation
access codes to controls
basic controls
their responsibility
and the need to log system events in
the log book.
30
8/20/2019 Installer s Handbook
32/32
T R O U B L E S H O O T I N G
30
1 Zone fault light on panel, check:
a) incorrect wiring polarity.
b) open circuit on wiring.
c) end of line device not fitted on
open circuit.
If fault does not clear, remove end of line
devices from end of each circuit in turn,
and fit across terminals of panel. If fault
then clears this proves fault is external to
panel. If fault persists, call Gent Service
Engineer.
2. Bell(s) (or Sounders) do not
operate, check:
a) Incorrect polarity.
b) faulty sounder.
If a) rectify - if b) call Engineer.
3. Sounder fault on panel, check:
1a and 1b as above and also for existence
of unpolarised bell on alarm circuit. Also
transfer end of line device to terminals
on panel to determine whether fault
internal or external as 1.
4. Supply lamps (green) not
illuminated, check:
Mains supply to control or charger unit,
if batteries are connected, buzzer shouldbe sounding.
5. Power fault on panel, check:
If green lights are on, buzzer should be
sounding.
a) Battery connections.
b) Panel fuses.
c) 24V Output.
If fault persists after these checks, call
Service Engineer.
Alarm condition on panel when
powered up, check:
for broken glass on call points.
for short circuit on trigger circuits. for
detector in alarm state (LED on).
If control unit can still not be reset call
Gent Engineer
SERVICE HOTLINE
0500 334455