Installation Test-Base Transceiver Station Equipment

Embed Size (px)

Citation preview

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    1/69

    Installation Test

    Base Transceiver Station Equipment

    ITMN:BTSE BS-41

    A30808-X3247-M282-05-7630

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    2/69

    2 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c6f19

    Copyright (C) Siemens AG 2006

    Issued by the Communications Group

    Hofmannstrae 51

    D-81359 Mnchen

    Technical modifications possible.

    Technical specifications and features are binding only insofar as

    they are specifically and expressly agreed upon in a written contract.

    Copyright (C) Siemens AG 2006

    Issued by the Communications Group

    Hofmannstrae 51

    D-81359 Mnchen

    Technical modifications possible.

    Technical specifications and features are binding only insofar as

    they are specifically and expressly agreed upon in a written contract.

    f Important Notice on Product Safety

    DANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION INSTRUCTIONS.

    The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the system must

    comply with the applicable safety standards.

    Hazardous voltages are present at the AC power supply lines in this electrical equipment. Some components may

    also have high operating temperatures.

    Failure to observe and follow all installation and safety instructions can result in serious personal injury

    or property damage.

    Therefore, only trained and qualified personnel may install and maintain the system.

    The same text in German:

    Wichtiger Hinweis zur Produktsicherheit

    LEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.

    Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen

    Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.

    In diesen Anlagen stehen die Netzversorgungsleitungen unter gefhrlicher Spannung. Einige Komponenten

    knnen auch eine hohe Betriebstemperatur aufweisen.

    Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Krperverletzungen oder

    Sachschden fhren.

    Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

    Caution:

    This equipment has been tested and found to comply with EN 301489. Its class of conformity is defined in table

    A30808-X3247-X910-*-7618, which is shipped with each product. This class also corresponds to the limits for aClass A digital device, pursuant to part 15 of the FCC Rules.

    These limits are designed to provide reasonable protection against harmful interference when the equipment is

    operated in a commercial environment.

    This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor-

    dance with the relevant standards referenced in the manual Guide to Documentation, may cause harmful inter-

    ference to radio communications.

    For system installations it is strictly required to choose all installation sites according to national and local require-

    ments concerning construction rules and static load capacities of buildings and roofs.

    For all sites, in particular in residential areas it is mandatory to observe all respectively applicable electromagnetic

    field / force (EMF) limits. Otherwise harmful personal interference is possible.

    Trademarks:

    All designations used in this document can be trademarks, the use of which by third parties for their own purposes

    could violate the rights of their owners.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    3/69

    A30808-X3247-M282-05-7630

    3

    ITMN:BTSE BS-41

    Id:0900d805800c6f19

    Table of ContentsThis document has 69 pages.

    Reason for Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.1 Aims of Installation and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.2 Pre-Commissioning and Pre-Acceptance. . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.3 Optional Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.4 Using the ITMN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.4.1 Required Knowledge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.4.2 Test Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.4.3 Installation Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.4.4 Procedure in the Event of Faults after Commissioning. . . . . . . . . . . . . . . . 11

    1.4.5 Procedure in the Event of Faults not Described in the Manuals . . . . . . . . . 121.4.6 Dealing with Defective Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.5 CE and UL Declaration of Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.6 LMT Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    1.6.1 LMT Graphic View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    1.6.2 LMT Tree View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    2.1 Electrostatically Sensitive Components . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    2.2 Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    2.3 Symbols Used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    2.4 System Voltages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202.5 Changing Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    2.6 Grounding of Modules / Racks / Shelters . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    2.7 Handling Moist Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3 Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.1 Visual Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.1.1 Visual Inspection of BTSE Mechanics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.1.1.1 Shelters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.1.1.2 Mounting and Installation of BTSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    3.1.1.3 Check of Base Transceiver Station BTSE . . . . . . . . . . . . . . . . . . . . . . . . . 24

    3.1.1.4 Check of BTSE Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    3.1.1.5 Antenna and Feeder Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    3.1.2 Visual Inspection of BTSE Electrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    3.1.2.1 Polarity of DC Input and Tolerance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    3.1.2.2 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    3.1.2.3 Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    3.1.2.4 DC Connector for Network Termination (NT) . . . . . . . . . . . . . . . . . . . . . . . 28

    3.1.3 Visual Inspection of BTSE Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    3.1.3.1 Abis Configurations to the BTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    3.1.3.2 Tower Mounted Amplifier (TMA) Connection . . . . . . . . . . . . . . . . . . . . . . . 29

    3.1.3.3 Adjustable Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    3.1.3.4 Antenna Combining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393.1.3.5 Antenna Multicoupling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    4/69

    4 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c6f19

    3.1.3.6 HPDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    3.2 Preparation for Offline Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    3.2.1 Recommended Test Equipment and Tools . . . . . . . . . . . . . . . . . . . . . . . . . 45

    3.2.1.1 Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453.2.1.2 Preparation and Presetting of Test Equipment . . . . . . . . . . . . . . . . . . . . . . 46

    3.2.2 BTSE Power-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.2.2.1 Check Polarity of DC Input and Tolerance. . . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.2.2.2 Breakers before BTSE Power-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.3 Checking the State of all Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    3.4 Checking the Environmental Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    3.5 Replacing Failed HW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    3.6 Generating BTS Backup Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    3.7 Remote Inventory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    3.8 Switch to Phase 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    3.9 SW Download and Activation (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . 633.10 Setting the Attributes for the BTSE (optional) . . . . . . . . . . . . . . . . . . . . . . . 65

    3.11 Setting BTSM (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    3.12 Closing the Rack/Shelter Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    4 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    4.1 Power/Level Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    4.2 Used Expressions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    4.3 Module Identification by Inventory Data and Label . . . . . . . . . . . . . . . . . . . 69

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    5/69

    A30808-X3247-M282-05-7630

    5

    ITMN:BTSE BS-41

    Id:0900d805800c6f19

    List of FiguresFigure 1 Installation Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Figure 2 CE and UL Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Figure 3 LMT Graphic View - Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Figure 4 LMT Graphic View lower level- Window . . . . . . . . . . . . . . . . . . . . . . . . 14

    Figure 5 Parameters and Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Figure 6 LMT Tree View Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Figure 7 LMT Tree View lower level - Window. . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Figure 8 ESD Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Figure 9 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Figure 10 Example for BTSE BS-41 (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Figure 11 Abis Connections to the BTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    Figure 12 TMA, e.g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Figure 13 COBA2P8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Figure 14 COBA4P12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    Figure 15 COSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    Figure 16 DIP Switches for Battery Type, Battery Capacities and Slot-ID. . . . . . . 38

    Figure 17 DIAMCO Antenna Connection and DIP Switches . . . . . . . . . . . . . . . . . 41

    Figure 18 (F)DUAMCO DIP Switch abd Antenna Connection, e.g. . . . . . . . . . . . . 43

    Figure 19 Setting the SBS Equipment Position . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    Figure 20 Editing Nob-RIU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

    Figure 21 Closing the Rack/Shelter Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    Figure 22 Labels and Inventory Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    6/69

    6 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c6f19

    List of TablesTable 1 BS-41 Shelter Numbering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Table 2 Adjustable Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Table 3 Boot Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    Table 4 Software Images SWI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    Table 5 Battery Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    Table 6 Battery Capacity DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Table 7 Slot-ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    Table 8 Switch Settings for DIAMCO / DUAMCO / FDUAMCO. . . . . . . . . . . . . . 41

    Table 9 Cascading of Multicouplers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Table 10 Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    Table 11 Power Conversion Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    7/69

    A30808-X3247-M282-05-7630

    7

    ITMN:BTSE BS-41 Reason for Update

    Id:0900d805800c6800

    Reason for Update

    Issue History

    Issue 05 for Release BR8.0(2006/20/11)

    Issue Date Summary

    01 01/2005 First edition for new release BR8.0

    02 04/2005 More instructions for adjusting of the DIAMCO,(F)DUAMCO.

    Revised tables.

    03 07/2005 Revised tables.

    04 03/2006 Minor changes.

    05 09/2006 The structure of the document adapted to Lean Implementa-

    tion.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    8/69

    8 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c6800

    Reason for Update

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    9/69

    A30808-X3247-M282-05-7630

    9

    ITMN:BTSE BS-41 Introduction

    Id:0900d8058006c54a

    1 Introduction

    1.1 Aims of Installation and CommissioningInstallation and commissioning is based on extensive, high quality final factory tests. In

    the factory, each module is tested during its production process; all Radio Frequency

    (RF) parameters such as the power and modulation spectrum are measured in the

    complete BTSE rack in customer configuration.

    The final Factory Tests comply with the tests and measurements required by GSM spec-

    ifications.

    The installation test can therefore concentrate on functional tests of the delivered

    hardware (HW).

    The installation and commissioning of a network element followed by unit acceptance is

    proof of: A correct and complete delivery according to the network planning and the customer

    order.

    A correct mechanical and electrical installation according to the installation docu-

    ments.

    The functional ability of the supplied Hardware (HW).

    (correct functioning of the NEs at an interface in relation to other network elements).

    The test subdivision in step, allows a quick, efficient and reliable commissioning proce-

    dure. The test steps are as follows:

    Final Factory Test

    Installation/commissioning (HW-test)

    Network integration (data base test)

    1.2 Pre-Commissioning and Pre-Acceptance

    The BTSE may also be delivered partly or completely pre-commissioned and pre-

    accepted.

    If the BTSE is pre-commissioned and pre-accepted, some procedures that usually are

    performed on site have already been performed in the factory. In this case, these par-

    ticular procedures do not need to be performed again during the installation test phase.

    It depends on the contract to what extent the BTSE is pre-commissioned and pre-

    accepted.

    All set parameters are listed in the Pre-Commissioning Paper. All executed tests andtheir results are documented in the Final Factory Test protocol. Both documents are

    delivered together with the site-specific documentation.

    Consult these documents to find out which procedures can be left out.

    g It is important, however, not to change the order of the remaining procedures.

    1.3 Optional Measurements

    Radio Frequency (RF) measurements can be performed by means of a spectrum

    analyzer or other test equipment. RF measurements may be used as an option for

    locating suspected faults.They do not need to be done in every BTSE as regular measurements.

    http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    10/69

    10 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d8058006c54a

    Introduction

    1.4 Using the ITMN

    1.4.1 Required Knowledge

    Only trained personnel should carry out the installation and installation tests.

    The SIEMENS training center offers the necessary courses.

    1.4.2 Test Equipment

    The test equipment and tools required for the tests are described in the corresponding

    chapter.

    1.4.3 Installation Test Sequence

    Installation test sequence is organized in tasks, as shown in Figure 1, Installation Test

    Sequence. Each single task is described in an own procedure, see Chapter Proce-dures. Perform procedures continuously.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    11/69

    A30808-X3247-M282-05-7630

    11

    ITMN:BTSE BS-41 Introduction

    Id:0900d8058006c54a

    Figure 1 Installation Test Sequence

    Execution of Function test (Offline) and On-Line Test are not included in this manual.

    1.4.4 Procedure in the Event of Faults after Commissioning

    If faults occur in on-line operation, they should be localized and cleared in accordance

    with the instructions in the Maintenance Manual.

    9LVXDO&KHFNRI

    %760HFKDQLFV

    9LVXDO&KHFNRI

    %76(OHFWULFV

    9LVXDO&KHFNRI

    %RDUGV

    3UHSDUDWLRQIRU

    )XQFWLRQ7HVW

    ([HFXWLRQRI

    )XQFWLRQ7HVW

    1SFQBSBUJPO&YFDVUJPO

    RI2QOLQH7HVWV

    67$57

    9

    ,

    6

    8

    $

    /

    &

    +

    (

    &.

    2

    )

    )

    /

    ,

    1

    (

    2

    1

    /

    ,

    1

    (

    (1'

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    12/69

    12 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d8058006c54a

    Introduction

    1.4.5 Procedure in the Event of Faults not Described in the Manuals

    First the specialist in the installation team should try to clear the fault. If the fault cannot

    be cleared, a fault report must be filled in, providing the following information in detail:

    Description of the test step attempted Description of the system response(s)

    Description of any system activities taking place at the same time, e.g. work done

    by other testers during modification of hardware or software.

    Send the fault report to the Technical Assistance Center TAC.

    g Always write a fault report, if a software error occurs.

    1.4.6 Dealing with Defective Modules

    If a module proves to be defective, send it in an appropriate packaging to the repair

    center with the following information:

    Name and code of the site Name and code number of the module

    Description of the fault

    1.5 CE and UL Declaration of Conformity

    Figure 2 CE and UL Symbol

    The CE and UL declaration of conformity for the product will be fulfilled if you setup and

    cable, according to the specification in the manual. See mounting instructions, cable

    lists. If it is necessary take description of project-specific documentation.

    Deviations from the specifications or independent changes during setup, such as use of

    cable types with lower screening values, for example, can lead to the violation of CE

    requirements. In such cases the CE declaration of conformity is invalidated and the

    responsibility passes to the person who caused the deviations.

    http://a200.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    13/69

    A30808-X3247-M282-05-7630

    13

    ITMN:BTSE BS-41 Introduction

    Id:0900d8058006c54a

    1.6 LMT Use

    The following chapter LMT Use is a limited LMT description. The purpose of this chapter

    is to explain the procedures use in this manual. For a detailed explanation about LMT

    see the OLG:LMT.

    If the BTSE is not pre-commissioned and not pre-accepted, some tasks have to be per-

    formed on site. Every single task is described in a procedure which is organized in steps.

    Procedures start with common part, including notes or other information. To perform the

    taks use the current LMT software release.

    There are two ways to perform the task using the LMT:

    1. Tree View

    2. Graphic View

    In procedures of this document the Graphic View will be used.

    1.6.1 LMT Graphic View

    In the LMT Evolution online window choose the menu File. In the menu File start

    the Training Script. It pops up the Start Training Script window. Click the Family:

    BTS. Select the right BTS type and the available, corresponding BTS profile. It pops up

    the LMT Evolution Start Training Script window, the Graphic View. See Figure 3,

    LMT Graphic View - Window.

    Figure 3 LMT Graphic View - Window

    In order to perform the command consider following instructions:

    Select BTS module by double left-click (e.g COSA:0)

    Perform command by double right-click (e.g. LOCK)

    PHQXEDUWRROEDU

    ZLWKLFRQV

    JUDSKLFYLHZ

    PHQX

    VXEGLUHFWRU\

    FRPPDQG

    %76W\SH

    http://ogllmtev.pdf/http://ogllmtev.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    14/69

    14 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d8058006c54a

    Introduction

    If the module is not located at the upper level, select the corresponding module by the

    double left-click (e.g FLEXCU:0). It pops up the LMT Evolution Start Training Script

    window - lower level. See Figure 4, LMT Graphic View lower level- Window.

    Perform command by double right-click (e.g.LOCK)

    Figure 4 LMT Graphic View lower level- Window

    After performing the task, the system may give test outcome. In that case note the test

    outcome, because it could be important for the next task.

    Parameters and Parameter Values

    Afterwards set the parameters and parameter values if necessary.

    A Select the Parameter Value window pops up.

    Enter the parameter values (RXLEVADJ(-24.0 ... 24.0 step 1.0), e.g. 15), see Figure5, Parameters and Parameter Values.

    Click on the Submit button

    %76PRGXOH

    FRPPDQG

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    15/69

    A30808-X3247-M282-05-7630

    15

    ITMN:BTSE BS-41 Introduction

    Id:0900d8058006c54a

    Figure 5 Parameters and Parameter Values

    Procedures are organized in steps. See an example of a possible procedure in this

    manual.

    If the module is located at the upper level of Graphic View, step 2 will be used in the

    procedure. If the module is not located at the upper level of Graphic View, step 3 will be

    used in the procedure.

    1 Log on LMT

    Connect the LMT to the BTSE and start the log on procedure.

    2 Lock Suspected Module

    b LOCK COSA

    3 Lock Suspected Module

    b FLEXCU LOCK FCUMAIN1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter values. (RXLEVADJ(-24.0 ... 24.0 step 1.0), e.g. 15)

    2. Click on the Submit button

    4 END

    SDUDPHWHU SDUDPHWHUYDOXHV

    http://bsplcml.pdf/http://bsplcml.pdf/http://bsplcml.pdf/http://bsplcml.pdf/http://bsplcml.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    16/69

    16 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d8058006c54a

    Introduction

    1.6.2 LMT Tree View

    The following chapter explains the using of LMT Tree View.

    In the LMT Evolution online window choose the menu File. In the menu File start

    the Training Script. It pops up the Start Training Script window. Click the Family:BTS. Select the right BTS type and the available, corresponding BTS profile. It pops up

    the LMT Evolution Start Training Script window. Click on the Tree View. See Figure

    6, LMT Tree View Window.

    Figure 6 LMT Tree View Window

    PHQXEDU

    WRROEDU

    ZLWKLFRQV

    JUDSKLFYLHZ

    PHQX

    %76W\SH

    VXEGLUHFWRU\

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    17/69

    A30808-X3247-M282-05-7630

    17

    ITMN:BTSE BS-41 Introduction

    Id:0900d8058006c54a

    Figure 7 LMT Tree View lower level - Window

    In order to perform the command consider following instructions:

    Select BSS- EQUIPMENT or BSS-FUNCTIONAL by double left-click

    Select a BTS by double left-click (e.g. BTSEP)

    Select BTS relevant subdirectory by double left-click (e.g RACK)

    Select BTS module by double left-click (e.g FCUMAIN:0), see Figure 7, LMT Tree

    View lower level - Window.

    Perform command by double right-click (e.g. LOCK)

    After performing the task, the system may give test outcome. In that case note the test

    outcome, because it could be important for the next task.

    Parameters and Parameter Values

    Afterwards set the parameters and parameter values if necessary. See , Parameters

    and Parameter Values.

    Procedures are organized in steps. See an example of a possible procedure in this

    manual.

    1 Log on LMT

    Connect the LMT to the BTSE and start the log on procedure.

    %76PRGXOH

    FRPPDQG

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    18/69

    18 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d8058006c54a

    Introduction

    2 Lock Suspected Module

    b ManagedElement BSS-EQUIPMENT BTSEP BTSEP: RACK

    FCUMAIN

    FCUMAIN:

    LOCK FCUMAIN1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter values (RXLEVADJ(-24.0 ... 24.0 step 1.0), e.g. 15)

    2. Click on the Submit button

    3 END

    http://bsplcml.pdf/http://bsplcml.pdf/http://bsplcml.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    19/69

    A30808-X3247-M282-05-7630

    19

    ITMN:BTSE BS-41 Safety Instructions

    Id:0900d8058006eaf5

    2 Safety Instructions

    2.1 Electrostatically Sensitive ComponentsGeneral

    Handel all modules with extreme care, bacause each one contains many electrostati-

    cally sensitive devices (ESD).

    All modules which contain ESD are marked with the ESD symbol on the faceplate or

    inside.

    Figure 8 ESD Symbol

    Rules for Handling

    Observe the following safety instructions:

    Personnel should avoid wearing synthetic clothing and shoes with plastic soles, as

    these encourage the build-up of electrostatic charge.

    Before handling modules, personnel should be discharged of electrostatic charging.

    For this reason personnel should always put on a grounded wrist strap before

    changing a module. ESDs should not be brought in contact with electrostatically charged or chargeable

    objects.

    ESDs should only come in contact with high valued discharging material ("gentle"

    discharging), i.e., should not be made subject to "harsh" discharging with, for

    example, a metal plate.

    ESDs should be set down on grounded surfaces only (flexible bases with a ground-

    ing connection for servicing purposes)

    ESDs should not be brought into the vicinity of strong DC electrical fields, e.g.

    cathode ray tubes/monitors (safety distance at least 10 cm/~4 inches).

    All tools and test equipment should be discharged of electrostatic charging before

    handling modules.

    ESDs should only be transported in appropriate packing. A grounded wrist strap

    must be put on before removing ESDs.

    Modules should only be touched by their edges. Components or printed circuits

    should not be touched.

    http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    20/69

    20 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d8058006eaf5

    Safety Instructions

    2.2 Warnings

    The following warnings appear in the document:

    2.3 Symbols Used

    The following symbols are used in this manual:

    Figure 9 Symbols Used

    2.4 System Voltages

    In case of: BS-240/240 II/240XL/240XL II, BS-241, BS-40, BS-41, BS-240XS and

    BS-288 all system units require a power supply of 230V AC, which are converted to

    -48V DC (positive pole grounded).

    In case of: 240U II/240XLU/240XLU II, BS-241U, BS-40U, BS-41U all system units

    require a power supply of 207V AC.

    In case of: BS-82 II eMicro all the system units require a power supply between

    88V-300V AC, which are converted to -48V DC (positive pole grounded).

    In case of: BS-82 eMicro the following types of power supply are available: -115 V

    AC (ACPSC/U) -230V AC (ACPSC) or -48V DC (DCPSC)

    Some parts are supplied with the line voltage directly and are to be handled with safety

    tools with extreme care. Only trained personnel should carry out those jobs.

    Take care, some parts produce a high operating temperature.

    This warning must appear in the original German text:

    Alle Systemeinheiten bentigen eine Wechselspannung von 230V AC, die in eine Gle-

    ichspannung von -48V DC (positiver Pol an Masse) umgesetzt wird.Einige Teile fhren Netzspannung und sind mit besonderer Sorgfalt zu behandeln. Nur

    ! CAUTION Electrostatically Sensitive ComponentsModules are susceptible to damage by electrostatic discharge.

    Follow ESD precautions when removing and inserting modules. Refer to Chapter 2.1,

    Electrostatically Sensitive Components.

    Symbol Meaning

    Reference to another procedure/procedure step

    Safety note; the notes given here are to be followed with care.

    Non-observance can lead to personal injury and property damage.

    ESD (Electrostatic Sensitive Device) precautions to be taken

    Note; important information

    Use the LMT to enter commands

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    21/69

    A30808-X3247-M282-05-7630

    21

    ITMN:BTSE BS-41 Safety Instructions

    Id:0900d8058006eaf5

    ausgebildetes Personal darf entsprechende Arbeiten bernehmen.

    Weiterhin ist zu beachten, dass sich einige Bauteile stark erhitzen.

    2.5 Changing BreakersBreakers may only be changed by operator. Only allowed breakers, as given in the

    manual may be used. Change the breakers as described in this manual.

    2.6 Grounding of Modules / Racks / Shelters

    Before you switch the power on, plug in all modules to ground correctly. Also plug in

    ground connections between the racks/shelters correctly.

    2.7 Handling Moist Modules

    After storage in an humid environment, dry the modules with condensation moisture,

    before the used. This is necessary, otherwise the modules could be damaged or

    destroyed.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    22/69

    22 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3 ProceduresPerform procedures continuously.

    3.1 Visual Inspection

    3.1.1 Visual Inspection of BTSE Mechanics

    Make a visual inspection of all delivered shelters. Check the shelters of damage,

    quantity and location of the modules.

    3.1.1.1 Shelters

    BS-41

    The BS-41U consists of only one shelter, the number of Base Shelter is 0.

    A BS-41 consists of:

    1 Base Shelter

    1-4 Service Shelter(s)

    The numbering of the shelters is shown in the following table:.

    g The numbering of the Service Shelter always begins with 4.For setting the correct shelter number, refer to Hardware Manual (see HW:BTSE

    Modules, ACTP Switch Settings).

    Shelter Numbering Type of Shelter

    0 Base Shelter

    47 Service 2 Shelter with link equipment and backup batteries

    (not BS-41U)

    Table 1 BS-41 Shelter Numbering

    http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    23/69

    A30808-X3247-M282-05-7630

    23

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Figure 10 Example for BTSE BS-41 (Front View)

    For more detailed information about shelter, refer to HW:BTSE Shelters.

    Base Shelter Service2 Shelter(not BS-41U)

    LMT

    DIAMCO#0

    Battery

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    CU#0

    CU#1

    CU#2

    CU#3

    CORE#0

    CORE#2

    CORE#1

    CORE#3

    DC

    BCTRL#0

    AC-Panel

    AC/DC

    #02

    AC/DC

    #01

    AC/DC

    #00

    LE#1

    LE#0

    Plinth

    LE #5

    LE #4

    LE #3

    LE #2

    LE #1

    LE #0

    FAN #1FAN #0

    DCP

    BS-41

    Plinth

    BS-41

    DCP

    OVPTOVPT

    HPDU

    H

    PDU

    (F)DUAMCO#0

    orFICOM#0

    (F)DUAMCO#1

    orFICOM#1

    0

    TMA

    1

    TMA

    2

    TMA

    3

    TMA

    Battery Battery Battery Battery

    Battery Battery Battery Battery

    http://hwmnbtseracks.pdf/http://hwmnbtseracks.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    24/69

    24 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3.1.1.2 Mounting and Installation of BTSE

    Check the internal/external interfaces and least replaceable units (LRU). For more

    detailed information, refer to the MMN:BTSE BS-41.

    3.1.1.3 Check of Base Transceiver Station BTSE

    Check for delivery quality and quantity on site:

    Installation of BTS shelter (shelter fixing, fixed boards)

    Damage to shelter (paintwork, dents)

    Correct insertion of modules

    System cabling (shelter cabling)

    Grounding, earthing

    Main breakers

    External interfaces: power supply, antenna and Abis wiring

    3.1.1.4 Check of BTSE Modules

    Modules in the Shelter

    You can find an overview of possible installed modules in the rack type of:

    BS-41: refer to TED:BS-40/41

    For more about modules identification see Chapter 4.3, Module Identification by Inven-

    tory Data and Label.

    http://a200.pdf/http://mmnbs41.pdf/http://tedbs4x.pdf/http://tedbs4x.pdf/http://mmnbs41.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    25/69

    A30808-X3247-M282-05-7630

    25

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    BTSE Modules

    The entire BTSE contains several cells called BTS.

    Up to 3 cells are available for BS-41.

    Check whether the BTSE modules are configured correctly.

    Redundancy

    CORE redundancy can be installed. In the CORE, the functionality of clock genera-

    tion, link interface, and Call Control is implemented.

    The BCCH redundancy is matter of software. The task "BCCH reconfiguration" runs

    in the BTSEplus and the functionality is independent of the type of antenna combin-

    ing.

    AC/DC redundancy is carried out as n+1 redundancy. N+1 AC/DC Converters

    operate in load sharing, but n AC/DCs are able to supply the whole BTSEplus.

    Hardware (HW) related modules:

    Per CELL:

    (F)DUAMCO (Flexible)Duplexer Amplifier Multicoupler

    DIAMCO Dual Integrated Amplifier Multicoupler

    FICOM Filter Combiner

    TMA Tower Mounted Amplifier

    HPDU High Power Duplexer

    Per Transceiver TRX:

    CU Carrier Unit

    FlexCU Flexible Carrier Unit

    In addition there are common modules:

    COBA Core Basis

    COSA Core Satellite

    ACT Alarm Collection Terminal

    Basic-Modules:

    DCP DC Panel

    FAN Fan

    OVPT Overvoltage Protection

    AC/DC AC/DC converter (rectifier)

    DCBCTRL DC and Battery ControllerBB Backup Battery

    http://a200.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    26/69

    26 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3.1.1.5 Antenna and Feeder Cable

    Test all antennas and feeder cables in advance.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    27/69

    A30808-X3247-M282-05-7630

    27

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.1.2 Visual Inspection of BTSE Electrics

    3.1.2.1 Polarity of DC Input and Tolerance

    The BTSE requires -48 V DC with a tolerance of -15% to +20% (-40,8 V/-57,6 V) for

    correct operation (positive pole is grounded). Use the SIEMENS Multimeter to check the

    voltage.

    3.1.2.2 Circuit Breakers

    Shelter internal breakers are available at the DC Panel in order to supply direct current

    (DC) to the several modules.

    The breakers are mounted at the DC Panel on the top of the shelter.

    There are different types of DC Panel for Base Shelter, Extension Shelter, Service1 and

    Service2 Shelter. There also could be different types of DC Panels for every BS.

    Check for fully equipped breakers and that all breakers are switched off.

    For more detailed information about DC Breakers for BS-41 to the HW:BTSE

    Frames/Panels.

    3.1.2.3 Alarms

    Internal and external alarms of all racks are collected by ACT (Alarm Collection Termi-

    nal) modules and channeled to the COBA in the base rack.

    There are three types of ACT modules:

    ACTC is the standard alarm connection module, for every rack and it is a part of the

    DC Panel. ACTM (ACT Master) is an optional alarm connection module for the base racks/shel-

    ters.

    ACTP provides a connection to the COBA via the CAN BUS. ACTP is for extension

    and service rack/shelter.

    Internal and External Alarms

    All racks are equipped with one ACTC, which provides the rack alarms and the environ-

    mental alarms (ENVAs). The ACTC in the base rack is directly connected to the COBA,

    in every other rack it is connected to ACTP. ACTC provides 16 alarms. There are 7 Rack

    Alarms (RAL), created automatically during the creation of RACK and FAN, and 9

    Operator Alarms (OAL). The OAL are numbered ENVA 0 - ENVA 8. ENVAs alarms can

    be customized.

    For detailed information refer to IMN:BTSE BS-41, section Alarm Collection Terminal

    ACTC - internal Alarms/DC Supply.

    The Base Rack can be equipped with ACTM, which is used for connecting of additional

    environmental alarms (ENVAs). The ACTM supports 48 ENVAs, numbered ENVA 9

    ENVA 56, and 8 Operator Commands. The installation of ACTM is optional. If no ACTM

    is installed, there are 16 Alarms available in the Base Rack.

    For detailed information refer to IMN:BTSE BS-41, section Alarm Collection Terminal

    - external Alarm Sensors.

    Alarms can be checked by using the LMT after BTSE Power-On.

    http://hwmnbtseframes.pdf/http://hwmnbtseframes.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://hwmnbtseframes.pdf/http://hwmnbtseframes.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    28/69

    28 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3.1.2.4 DC Connector for Network Termination (NT)

    The power supply (-48 V DC, max. 1A) at the SubD9 connector is free for operator use.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    29/69

    A30808-X3247-M282-05-7630

    29

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.1.3 Visual Inspection of BTSE Modules

    3.1.3.1 Abis Configurations to the BTS

    The following figure shows four possible Abis configurations to connect the BTS to the

    BSC. These configurations are called Star (single), Loop (several in circle), Multidrop

    (several), and Cross Connect.

    Figure 11 Abis Connections to the BTS

    In case of a Star link, only PCM1 must be wired. For Loop and Multidrop links, PCM one

    and two are necessary.

    For pinning see IMN:BTSE Chapter Abis-InterfacePCM Link Terminal.

    For the settings of Abis Interface to match 120 , 100 or 75 line impedance, see

    Chapters , Switch Settings on COBA2P8 and , Switch Settings on COSA.

    3.1.3.2 Tower Mounted Amplifier (TMA) Connection

    If an antenna is present check for correct RF cabling connections of TMA. The (F)DUA-

    MCO/DIAMCO supply the DC power for TMA at their antenna ports via the RF coax

    cable.

    %6&

    %76( %76(%76(

    6WDU

    %6&

    %76( %76(%76(

    0XOWLGURS

    %76( %76(%76(

    /RRS

    %6&

    &URVV&RQQHFW

    %6&

    %76( %76(

    %76(

    %76(

    http://a200.pdf/http://imnbs41.pdf/http://imnbs41.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    30/69

    30 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    Figure 12 TMA, e.g.

    3.1.3.3 Adjustable Modules

    There are several modules containing adjustable devices. Check the default states or

    special project settings. The software image SWI is only adjustable via LMT.

    The following table gives an overview:

    Boot Software (FW)

    Some modules contain special on board boot software on EEPROMs.

    ANT

    BTS

    No MODULE see

    1 ACT HW:BTSE Modules, ACTP

    2 COBA Figure 14

    3 COSA Figure 15

    4 DCBCTRL Figure 16

    5 DIAMCO Table 8

    6 (F)DUAMCO Table 8

    Table 2 Adjustable Modules

    http://a200.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    31/69

    A30808-X3247-M282-05-7630

    31

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    The allocation of the EPROMs is listed in the Release Note. The new boot software can

    be downloaded via LMT.

    Software Images SWI

    Some modules receive the SWI via the LMT.

    Switch Settings on COBA2P8

    The COBA contains three transceiver submodules for 75 , 100 , or 120 impedance

    matching.

    Module Board FILE NAME

    COBA COBA2P8 btbbcx01.swi

    COBA4P12 btbbcx03.swi

    CU CUxxx btbbix01.swi

    ECU/FCU btbbix07.swi

    GCU btbbix10.swi

    Table 3 Boot Software

    OBJECT FILE NAME

    SWL HSxxxxxx.SWL

    depending on variant of ciphering

    VAM VSxxxxxx.VAM

    depending on variant of ciphering

    COBA2P8 BTSBCX01.SWI

    COBA4P12 BTSBCX03.SWI

    CU BTSBIX01.SWI

    GCU/ECU/FCU BTSBIX07.SWI

    Table 4 Software Images SWI

    http://a200.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    32/69

    32 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    Figure 13 COBA2P8

    Port 2 Port 1

    S2 S1

    External ClockSynchronization

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    33/69

    A30808-X3247-M282-05-7630

    33

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Switch Settings of Port 1 and Port 2

    External Clock Synchronization

    For more detailed information about Settings on COBA2P8 refer to HW:BTSE Modules,

    COBA.

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6

    PCM30 120 off off off off off offPCM30 75 on on on off off off

    PCM24 100 off off off on on on

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6

    75 on off off on on on

    100 off on off off on on

    120 off off on off on on

    high (TTL)

    f=< 2 MHz

    off off off on off off

    high (TTL)

    f=> 2 MHz

    off off off on on on

    http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    34/69

    34 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    Switch Settings on COBA4P12

    Figure 14 COBA4P12

    g Settings for port 0 up to port 7 are made with the LMT. For example: CreateBPORT:NAME=BPORT:0,L1PT=pcm30crc4,L1RAT=ProtocolSignalling,

    LCONF=star, LIMP=Imp100 or 120 ;

    External Clock Synchronization

    External ClockSynchronization

    Impedance Switch

    1

    Switch

    2

    Switch

    3

    Switch

    4

    Switch

    5

    Switch

    6

    Switch

    7

    Switch

    8

    75 coaxial pair on off off on on on off off

    100 balanced twisted pair off on off off on on off off

    120 balanced twisted pair off off on off on on off off

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    35/69

    A30808-X3247-M282-05-7630

    35

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    For more detailed information about Settings on COBA4P12 refer to HW:BTSE Mod-

    ules,COBA.

    high (TTL) f< 100 kHz off off off on off off off off

    high (TTL) f> 100 kHz off off off on on on off off

    Impedance Switch

    1

    Switch

    2

    Switch

    3

    Switch

    4

    Switch

    5

    Switch

    6

    Switch

    7

    Switch

    8

    http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    36/69

    36 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    Switch Settings on COSA

    Figure 15 COSA

    Port 1Port 2Port 3Port 4Port 5Port 6

    S1S2S3S4S5S6

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    37/69

    A30808-X3247-M282-05-7630

    37

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Switch Settings of Port 1 to Port 6

    For more detailed information about Settings on COSA refer to HW:BTSE Modules,

    COSA.

    Switch Settings on DCBCTRL

    Battery Type

    Select a proper characteristic curve for battery charging.

    Impedance Switch

    1

    Switch

    2

    Switch

    3

    Switch

    4

    Switch

    5

    Switch

    6

    PCM30 120 off off off off off off

    PCM30 75 on on on off off off

    PCM24 100 off off off on on on

    Type Bit 0 Bit 1

    Oerlikon on not used

    Sonnenschein/Exite/Hawker off not used

    Table 5 Battery Type

    http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    38/69

    38 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    Figure 16 DIP Switches for Battery Type, Battery Capacities and Slot-ID

    Battery TypeBattery Capacity

    Selectable battery capacities: 0 Ah (no battery), 5 Ah, 10 Ah,...1275 Ah.The battery

    capacities can be set with two 8 bit DIP switches, one for each battery block;1 LSB =

    5Ah. The setting is calculated by adding all values where the contacts of theDIP switch

    are set to "ON".

    g The state of the object BATTERY does not depend on the existence of a real

    battery. It depends on the Battery Capacity DIP switch settings on the DCBCTRL

    640 Ah on

    320 Ah on

    160 Ah on

    80 Ah on

    40 Ah on

    20 Ah on

    10 Ah on

    5 Ah on

    Table 6 Battery Capacity DIP Switch

    6ZLWFK6ORW,'

    6ZLWFK%DWWHU\&DSDFLW\

    6ZLWFK%DWWHU\&DSDFLW\

    9

    6ZLWFK%DWWHU\7\SH

    %$7

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    39/69

    A30808-X3247-M282-05-7630

    39

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    module. If one of these two DIP switches is set to a value different from 0 Ah, the

    respective HMO BATTERY goes to enabled.

    Slot-ID

    Selec table Slot-ID: The CAN-Bus address can be set with a 2 bit DIP switch in order to

    distinguish between different AC/DC frames mounted to one rack.

    Both switches must be in different positions.

    Some DCBCTRL versions dont have DIP switches, but are programmable by means ofa special software application. For more information see HW:BTSE Modules, DCBCTRL

    3.1.3.4 Antenna Combining

    The (F)DUAMCO/FICOM must be installed in the ACOM slots. To achieve short cabling

    between CU and ACOM, the ACOM slots are assigned to definite CU slots.

    g All unused RX and RXCA connectors must be terminated with a 50 load when thecorresponding antenna port of the (F)DUAMCO is connected to an antenna or cas-

    cading output of (F)DUAMCO/DIAMCO/COAMCO.

    The open TX inputs of (F)DUAMCO/COAMCO do not need to be terminated in

    normal operation.

    DUAMCO

    The DUAMCO 2:2 and 4:2 occupy one ACOM slot each and are installed in the assigned

    slot for the CU that must be combined.

    The DUAMCO 8:2 occupies two ACOM slots and is installed either on the left or on the

    right two slots.

    FDUAMCO

    For each system GSM 850, GSM 900, GSM 1800 and GSM 1900 one type of

    FDUAMCO units is available, which can be configured by jumper cables for One-To-One mode (= FDUAMCO 2:2) or Two-To-One mode (= FDUAMCO 4:2).

    The FDUAMCO unit can be configured to different modes by application of two jumpers.

    FDUAMCO 2:2

    The FDUAMCO in 2:2 configurations is used for 2 antennas with 1 carrier each.

    For this configuration, the connectors 2 and 3 have to be jumpered.

    The second free jumper per module can be placed at connector 4.

    FDUAMCO 4:2

    The FDUAMCO in 4:2 configurations is used for 2 antennas with 2 carriers each.

    Address Bit 0 Bit 1

    ACDCP0 on off

    ACDCP1 off on

    Table 7 Slot-ID

    http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    40/69

    40 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    For this configuration, the connectors TX 0 and TX 1 are used as TX inputs. One jumper

    is applied for the connectors 1 and 2. The second jumper is placed between connectors

    3 and 4.

    FICOM

    Usage of FICOM modules of different variants

    There are several different FICOM modules: FIPLUB2RV3, FIPLUB2RV4,

    FIPLUX2RV3, FIPLUX2RV4.

    One Base Module can be expanded by 3 Expansion Modules, all modules in this com-

    bination must have the same variant (all ...V3 or all ...V4).

    Installation of FICOM Modules

    For each cell, install 1 FICOM plus base module (FIPLUB). To combine more than 2 car-

    riers, the base module can be expanded by the FICOM plus expansion module

    (FIPLUX). The expansion can be done to one side only per base module.

    Expansion of FICOM can only be done inside each rack. To combine more than 8 car-

    riers, a base module must be installed in the extension rack.

    g Open expansion connectors RF EXP of FICOM modules must be terminated withthe terminator delivered with the FICOM base module.

    It is suggested to fix the jumper cable very carefully, do not torque too strong. The cable

    should not move. Otherwise the cables inner conductor will tear.

    The mounting location of the FICOM modules depends on the Cell configuration and

    antenna combining.

    It is possible to have a mixed installation of (F)DUAMCO and FICOM modules, withinone rack.

    3.1.3.5 Antenna Multicoupling

    Multicoupling can be done by DIAMCO, (F)DUAMCO or COAMCO. Each

    DIAMCO/(F)DUAMCO/COAMCO can drive as many CUs as RX output connectors are

    available.

    DIAMCO

    All unused RX and RXCA connectors must be terminated with a 50 load when the cor-

    responding antenna port of the DIAMCO is connected to an antenna or cascading outputof DIAMCO / (F)DUAMCO/COAMCO.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    41/69

    A30808-X3247-M282-05-7630

    41

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Figure 17 DIAMCO Antenna Connection and DIP Switches

    The DIP switch is used for setting the TMA configuration of the DIAMCO/(F)DUAMCO.

    Switch 1 must be set to "on" if a TMA is installed. If no TMA is installed, switch 1 must

    be set to "off".

    g The setting of switches 2-4 determines the DIAMCO/(F)DUAMCO attenuation.The total attenuation of the feeder cable (between TMA and DIAMCO/(F)DUAMCO)

    and the DIP switch must be 6 dB.

    That means, the following formula applies:

    DIP switch value = 6 dB minus measured insertion loss of feeder cable.

    Function Switch 1 Switch 2 Switch 3 Switch 4

    TMA off / AMCO mode off X X X

    TMA on / MUCO mode on X X X

    attenuator LNA 0 dB off X X X

    Table 8 Switch Settings for DIAMCO / DUAMCO / FDUAMCO

    0RGXOH 0RGXOH

    $17 $17

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;&$ 5;&$

    6ZLWFKHV

    $QWHQQD&RQQHFWRU

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    42/69

    42 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    "X": any position allowed

    g Switch 1 does not work when a TMA Alarm is present.

    DUAMCO/FDUAMCO

    The switch settings for (F)DUAMCO is the same as for DIAMCO, described in Table 8.

    attenuator LNA 0 dB on off off off

    attenuator LNA 1 dB on on off off

    attenuator LNA 2 dB on off on off

    attenuator LNA 3 dB on on on off

    attenuator LNA 4 dB on off off on

    attenuator LNA 5 dB on on off on

    attenuator LNA 6 dB on off on on

    attenuator LNA 7 dB on on on on

    factory setting off off off off

    Function Switch 1 Switch 2 Switch 3 Switch 4

    Table 8 Switch Settings for DIAMCO / DUAMCO / FDUAMCO

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    43/69

    A30808-X3247-M282-05-7630

    43

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Figure 18 (F)DUAMCO DIP Switch abd Antenna Connection, e.g.

    Cascading Multicouplers

    For supplying more receiver inputs, the multicoupler can be cascaded to save antennas

    in the RX path. Cascading can be done twice, the possible configurations are shown in

    Table 9.

    The chain goes from the antenna to the BTSE, so the first device is the one nearest to

    the antenna. The Parameter LNAPRED must be set if there is a TMA installed to activate

    the TMA. If there is no TMA, LNAPRED must be set only for the 1. Cascade.

    $17 $17

    7HVWRXW 7HVWRXW

    7; 7;

    7; 7;

    5;&$

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;&$

    $QWHQQD&RQQHFWRU

    First Device 1. Cascade 2. Cascade

    (F)DUAMCO DIAMCO

    TMA(F)DUAMCO DIAMCO

    Table 9 Cascading of Multicouplers

    http://bsplcml.pdf/http://bsplcml.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    44/69

    44 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    g The first device in the chain must be switched into the high amplifying AMCO mode,the cascaded devices into MUCO mode.

    To install TMA, all other devices have to be set in MUCO mode.

    3.1.3.6 HPDU

    The High Power Duplexer is an RF module with the requirement to save antennas in the

    TX path. For FICOM use is one antenna for TX necessary. Also are two antennas per

    cell for RX diversity necessary.

    The main functions of HPDU is combining RX and TX signal. In the TX path, the HPDU

    is filtering the TX signals coming from the shelter and feeding them to the TX/RX

    antenna. In the RX path, the function is filtering the incoming signal.

    The HPDU is placed between antenna and FICOM/DIAMCO.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    45/69

    A30808-X3247-M282-05-7630

    45

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.2 Preparation for Offline Tests

    The purpose of this module is to execute all commissioning activities for checking the

    delivery quality and quantity of the BTSE on site. The following steps must be executed

    to start the system:

    1. Obtain the recommended tests and test equipment

    2. Preparation of tests and test equipment

    3. Check Polarity of DC Input and Tolerance

    4. BTSE power on

    5. Start of LMT

    6. Offline tests

    Finally all documents must be filled in and all activities must be confirmed by the cus-

    tomer.

    3.2.1 Recommended Test Equipment and ToolsSeveral devices, instruments, accessories, and utensils must be provided and prepared

    for commissioning on site.

    3.2.1.1 Test Equipment

    The equipment, especially the available options change quickly. Therefore, the listed

    equipment may not be currently available. It is suggested that the equipment listed

    below or equivalent must be present for call simulation and verification of correct oper-

    ation.

    Multimeter

    HW

    SIEMENS Multimeter

    Local Maintenance Terminal LMT

    For detailed requirements, refer to manual OGL:LMT Evolution.

    RF Termination

    Depending on the BTSE and the equipped modules, some RF terminations must be

    present.

    TX

    50 SMA ((F)DUAMCO,FICOM)

    RX

    50 SMC (DIAMCO,(F)DUAMCO)

    RXCA

    50 SMA (DIAMCO cascading output)

    Mobile Station MS

    HW

    GSM 900/1800 mobile phone, e.g. S45

    GSM 1900 mobile phone, e.g. S55

    Test Plug-In SIM

    http://ogllmtev.pdf/http://ogllmtev.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    46/69

    46 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    Tools

    Special tools for commissioning activities on site are listed below.

    Antistatic Set

    for ESD Module Handling SMA Tool

    with torque wrench for semi-rigid/flexi Cable Connectors

    SMC Tool

    with torque wrench for semi-rigid/flexi Cable Connectors

    Semi-Rigid Bending Tool

    for semi-rigid cable connection

    TDMA Measuring Tools (Tests with HP 8594A/E) and Trigger Adapter- HW

    GSM 1900: HP 8594 Personality Card

    2 Measuring cables with BNC-Plugs male (sufficient length)

    Adapter SMA maleBNC female

    Trigger Adapter TAD-L S30861-U2003-X-*(100-pins AMP-Plug with 4 x BNC-Plug female

    1 Adapter N-Connector maleBNC female

    HP 8590 series spectrum analyzer operating manual

    Users Guide HP85715B GSM 850 - 900 Transmitter Measurement Personality

    Users Guide HP 85722B GSM 1800 Transmitter Measurement Personality

    3.2.1.2 Preparation and Presetting of Test Equipment

    Test Equipment

    For minimum test time and correct test results, the devices must be prepared on site.

    RF Termination

    HW: Before RF measurements are executed, the following connectors must be ter-

    minated with 50 SMA/SMC resistors:

    TX: open FICOM/(F)/DUAMCO inputs (SMA)

    RX: open (F)DUAMCO/DIAMCO outputs (SMC)

    RXCA: open (F)DUAMCO/DIAMCO outputs (SMA)

    TESTOUT: open (F)DUAMCO/FICOM outputs (SMA)

    Software (SW)

    For all tests, only released SW (corresponding to the BTSE HW/SW release) is allowedto be running on the test equipment (TE).

    Boot Software/Firmware (SW/FW)

    For all tests, only the released SW is allowed to be running on the BTSE corresponding

    to the BTSE HW/SW/FW release/revision.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    47/69

    A30808-X3247-M282-05-7630

    47

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.2.2 BTSE Power-On

    3.2.2.1 Check Polarity of DC Input and Tolerance

    The BTSE requires -48 V DC with a tolerance of -15% to +20% (-40,8V/-57,6V) for

    correct operation (positive pole is grounded). Use the SIEMENS Multimeter to check the

    voltage.

    3.2.2.2 Breakers before BTSE Power-On

    Depending on the configuration of equipped modules, only the corresponding breakers

    must be switched on. All other breakers are switched off.

    For more detailed information about DC Breakers for BS-41 refer to HW:BTSE

    Frames/Panels.

    g In case of supervising all breakers with one common alarm sensor, all breakersmust be switched on, independent of the configuration.

    Power-On

    1 Turn on the power switch for power supply to the BTSE.

    2 The BTSE requires -48 V DC with a tolerance of -15% to +20% (-40,8V/-57,6V) for

    correct operation (positive pole is grounded). Check this voltage.

    END

    !CAUTION Electrostatically Sensitive Components

    Modules are susceptible to damage by electrostatic discharge.

    Follow ESD precautions when removing and inserting modules. Refer to Chapter 2.1,

    Electrostatically Sensitive Components.

    http://hwmnbtseframes.pdf/http://hwmnbtseframes.pdf/http://hwmnbtseframes.pdf/http://hwmnbtseframes.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    48/69

    48 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3.3 Checking the State of all Modules

    1 Check the State of all Modules

    The State of Modules checked via LMT:

    All images have been loaded. This is confirmed by a state event report: Administrative

    State = UNLOCKED, Operational State = ENABLED for all successfully created objects.

    This can be verified via logfile in browser mode or via LMT commands with:

    b BSS

    NE Btseep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    :

    GET

    NAME=RACK:/:

    The State of Modules checked via LEDs

    All red LEDs (except the PA LED on the CU) are switched off. If no Abis is connected,

    the coresponding LED on the COBA/COSA (if installed) is red. The files can be viewed

    in the Message Browser window.

    The following LED description is only valid for the software installation.

    The modules have the normal LED indication set as shown below for normal operation.

    1. DIAMCO

    2. FICOM

    OK off off AL

    OK green off RS

    FICOM (base module) FIBLUB2*V4

    TNF ALM off off TNF ALM

    green DC ON

    VSWR off off RESET

    FICOM (expansion module) FIBLUX2*V4

    TNF ALM off off TNF ALM

    green DC ON

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    49/69

    A30808-X3247-M282-05-7630

    49

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3. DUAMCO/FDUAMCO

    4. CU

    4. FlexCU

    5. COBA2P8

    5. COBA4P12

    off RESET

    FICOM (base module) FIBLUX2*V3

    VSWR ALM off off TNF ALM 0

    DC ON green off TNF ALM 1

    RESET off

    FICOM (expansion module) FIBLUX2*V3

    off TNF ALM 0

    DC ON green off TNF ALM 1

    TMA0 off off TMA 1

    RESET o off off RESET 1

    VSWR 0 off off VSWR 1

    POWER 0 green green POWER 1

    OK flashing green off SW

    RES off red PA

    OK flashing green off RES

    SW 0 off off SW 1

    PA 0 red red PA 1

    ACT flashing green flashing red RCOBA

    FLOC off off HMO

    ABIS 1 off off ABIS 2

    ACT flashing green flashing red RCOBA

    FLOC off off HMO

    ABIS 1 off off ABIS 2

    ABIS 3 off off ABIS 4

    FICOM (expansion module) FIBLUX2*V4

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    50/69

    50 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    6. COSA6P16

    6. COSA4P12

    7. ACT

    For more information about LED position see HW:BTSE Modules.

    END

    ACT flashing green flashing red RCOSA

    ABIS 7 off off ABIS 8ABIS 5 off off ABIS 6

    ABIS 3 off off ABIS 4

    ACT flashing green flashing red RCOSA

    ABIS 5 off off ABIS 6

    ABIS 7 off off ABIS 8

    To be activated by SW off off Reset of C

    http://hwmnbtsemodules.pdf/http://hwmnbtsemodules.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    51/69

    A30808-X3247-M282-05-7630

    51

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.4 Checking the Environmental Alarms

    Check the Operator Alarm Interface. The environmental alarms must have been config-

    ured previously.

    1 For every couple of alarm terminals on the alarm collecting point, alternatively

    close/open the contact and check the corresponding alarm message on the LMT. If the

    alarm is configured as high, an alarm start message will be displayed first. If it is con-

    figured as low, an alarm cease message will be displayed first (provided that the alarm

    was active before).

    gImportant: The test should not be done before the completion of ACT config-uration.

    For more information about alarms for:

    BS-240/240 II/240XL/240XL II refer to IMN BS-241/241 II refer to IMN

    BS-40/40 II refer to IMN

    BS-41 refer to IMN

    BS-288 refer to IMN

    BS-240XS refer to IMN

    BS-82 eMicro refer to IMN

    BS-82 II eMicro refer to IMN

    END

    http://imnbs240.pdf/http://imnbs241.pdf/http://imnbs40.pdf/http://imnbs41.pdf/http://imnbs288.pdf/http://imnbs240xs.pdf/http://imnbs82.pdf/http://imnbs82ii.pdf/http://imnbs82ii.pdf/http://imnbs82.pdf/http://imnbs240xs.pdf/http://imnbs288.pdf/http://imnbs41.pdf/http://imnbs40.pdf/http://imnbs241.pdf/http://imnbs240.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    52/69

    52 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3.5 Replacing Failed HW

    1 Test Replaced Modules

    After replacing a failed HW unit, it is necessary to enable this new HW unit via TEST

    or DELETE/CREATE command before starting any other activities (e. g. downloading

    or activating SW). The reason for this is that the PID of a new module is only updated

    after the command TEST or DELETE/CREATE was performed and it is necessary

    during download to have the actual PID of all modules stored on the COBA.

    Test any replaced module.

    If the BTSM is unlocked, a full BTS alignment is caused. If any BTSE configuration

    commands are performed during an alignment, a new alignment will be started.

    For more information refer to Maintenance Manual.

    END

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    53/69

    A30808-X3247-M282-05-7630

    53

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.6 Generating BTS Backup Files

    Via the backup files (script files) a quick reconfiguration of the BTSE is possible (for

    example necessary after a COBA replacement).

    For generating BTS backup files with the LMT Evolution, refer to the operator guidelines

    OGL:LMT Evolution.

    1 Generate BTS Backup Files

    To generate BTS Backup Files:

    1. Select File Backup Bts from the LMT Evolution menu or click on the correspond-

    ing icon in the tool bar.

    2. Click on the Get button in the appearing window.

    3. Enter a name for the saved configuration (e.g. Backup1) and confirm by clicking on

    the OK buttoon.

    The scripts will produce the following files on the [LMT_ROOT]\BKBTS\subdirectory:

    For BTS PLUS: BS240, BS240XL, BS241, BS40, BS41, BS40II, BS82II

    For BTS XS: BS240XS, BS288

    System Response:

    For BTS PLUS (BS240, BS240XL, BS241, BS40, BS41, BS40II, BS82II):The con-

    figuration data of the BTSE are loaded to the LMT PC and are then converted to

    script files: SCRIPT1P.LMT, SCRIPT2P.LMT, SCRIPT3P.LMT, SCRIPT4P.LMT,

    SCRIPT5P.LMT, SCRIPT6P.LMT. These files are written into the

    [LMT_ROOT]\BKBTS\subdirectory. After this process, the following message is

    displayed: Get HW operation is completed.

    For BTS XS (BS240XS, BS288):The configuration data of the BTSE are loaded to

    the LMT PC and are then converted to script files: SCRIPT1XS.LMT,

    SCRIPTX2.LMT, SCRIPT3XS.LMT, SCRIPT4XS.LMT, SCRIPT5XS.LMT,

    SCRIPT6XS.LMT. These files are written into the [LMT_ROOT]\BKBTS\subdirec-

    tory. After this process, the following message is displayed: Get HW operation is

    completed.

    2 Copy the Script Files to Disk

    Copy the script files from [Drive]:\[LMT_ROOT]\BKBTS\subdirectory to some storage

    media and keep it at the site, in case of need.

    END

    http://ogllmtev.pdf/http://ogllmtev.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    54/69

    54 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    3.7 Remote Inventory

    The function Remote Inventory of the Siemens Basestation System performs elec-

    tronic, non-volatile storing of the complete, individual product identification data (PID) of

    each inventory object.

    Modules that have their inventory data on board are called on-board Remote Inventory

    Units (ob_RIUs). The PID of these ob_RIUs are automatically loaded to an Inventory

    Data Table (IDT) file if you upload the inventory data from the BTSE.

    In order to include inventory data of objects without a non-volatile storage (e.g. frames,

    racks, OEM components), the data of these not on-board Remote Inventory Units

    (nob_RIUs) must be entered via the offline tool IDF Evolution, and downloaded to the

    BTSE where they are stored on the COBA.

    The complete Remote Inventory Data of each rack are provided on a disk as an Inven-

    tory Data File (IDF) by the Regional Logistic Center (RLC). The file name is composed

    of the serial number of the rack ( / replaced by _) and the extension IDF, for

    example: CN+_JD100001.IDF. However, since the RLC does not know the site

    specific values (such as the Sales Unique Name, the SBS equipment position or the

    rack position), these values are set to default numbers. Therefore, the provided IDF file

    must be modified. Afterwards, it is necessary to create an up-to-date IDF file for backup

    and to download the modified data to the BTSE.

    1 Start IDF Evolution

    To start the IDF Evolution select Tools IDF EVOLUTION from the LMT Evolution

    menu.

    2 Open IDF File

    The IDF file is stored on a disk that is delivered with each rack of the BTSE.

    To open the IDF file:

    1. Copy the IDF file from the storage media to the harddisk of the LMT, e.g.

    C:\LMT\ldf\*.idf.

    2. Select File Open from the menu of the IDF Evolution.

    3. Select the file from the list in the appearing window.

    4. Double-click on the file name or click on the Open button.

    3 Set SBS Equipment Position

    To set the SBS Equipment Position:

    1. Select File Set SBS_Eq_Pos from the menu.

    2. Enter the SBS equipment position in the appearing window and click on the Replace

    All " button.

    http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/http://a200.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    55/69

    A30808-X3247-M282-05-7630

    55

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Figure 19 Setting the SBS Equipment Position

    3. A message window opens that tells you that the search was completed and howmany replacements were made. Confirm this message window by clicking on the

    OK button.

    4 Set Rack Position

    To set the rack position:

    1. Select File Set F. A. Rack Pos from the menu.

    2. Enter the rack position RACK_Pos in the appearing window and click on the

    Replace All button.

    3. A message window opens that tells you that the search was completed and how

    many replacements were made. Confirm this message window by clicking on theOK button.

    5 Check nob_RIU Data

    Are the data of the nob_RIU units O.K.?

    Y h ......... 7

    N h ......... 6

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    56/69

    56 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    For a complete list of all nob_RIUs refer to...

    See ........... MMN:BTSE BS-240/240 II/240XL/240XL II

    ........... MMN:BTSE BS-241/241 II

    ........... MMN:BTSE BS-240XS

    ........... MMN:BTSE BS-288

    ........... MMN:BTSE BS-40/40 II

    ........... MMN:BTSE BS-41

    ........... MMN:BTSE BS-82

    ........... MMN:BTSE BS-82 II

    6 Edit Remote Inventory Data of nob_RIU Units

    The records of the nob-RIUs are shown in bold letters. Only these records are editable.

    The data can be edited manually or automatically via the 2D-Code Reader.

    To edit the Remote Inventory Data of the nob_RIU units:

    1. Select the I-Record of the unit you need to edit and click the right mouse button.

    2. Click on the appearing Edit button.

    http://mmnbs240.pdf/http://mmnbs241.pdf/http://mmnbs240xs.pdf/http://mmnbs288.pdf/http://mmnbs40.pdf/http://mmnbs41.pdf/http://mmnbs82.pdf/http://mmnbs82ii.pdf/http://mmnbs82ii.pdf/http://mmnbs82.pdf/http://mmnbs41.pdf/http://mmnbs40.pdf/http://mmnbs288.pdf/http://mmnbs240xs.pdf/http://mmnbs241.pdf/http://mmnbs240.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    57/69

    A30808-X3247-M282-05-7630

    57

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    Figure 20 Editing Nob-RIU Units

    3. Edit the data manually, or click on the Scan button to use the 2D-Code Reader.

    4. If the 2D-Code Reader is used for the first time, select the serial port in the appearing

    window.

    5. To start the scanning process, press the button on the 2D-Code Reader.

    6. The data will be inserted into the corresponding fields. Confirm the data by clicking

    on the OK button.

    7. Select File Save.

    7 Export Nob_RIU Data

    The nob_RIU data of the IDF file must be attached to the Remote Inventory Data stored

    in the BTSE (IDT file). In order to attach the nob_RIU data to the IDT file of the BTSE,

    you must export them into a NOB file.

    To export the nob_RIU data:

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    58/69

    58 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    1. Select Export NOB from the menu.

    2. A window opens in which you can edit the file name and select the directory in which

    the file is saved. By default, the file name is composed of the SalesUniqueName

    with the extension .nob. Edit the file name and select the source directory or

    confirm the default name and directory by clicking on the Save button.

    3. The nob_RIU data are exported to the NOB file. The selected destination path of this

    file is displayed in an attention window. Confirm by clicking on the OK button.

    4. A question window is displayed: Create BTSE_NRIU for download? At present, it

    is not required to create this file. Click on the No button.

    8 Upload IDT File from BTSE

    Now you must upload the Remote Inventory Data that are stored in the BTSE (IDT file)

    to the LMT PC.

    Change to the LMT Evolution main window.

    b UPLLIDF REMINV

    1. A Select the Parameter Value window pops up:

    1.1 Enter the path (DESTDIR).

    1.2 Enter the file name

    1.3 Enter the parameter (OVERWRITE, e.g.yes/no)

    2. Click on the Submit button

    Additional Information: The attributes DESTDIR and FILE are optional. If no special

    path or file name is entered, the file is uploaded to the default directory of the IDF Editor.

    If the attribute OVERWRITE= is selected, a former version of an uploaded IDT file

    will be overwritten.

    System Response: In the Message Viewer window, the command result is displayed:Operation successful.

    9 Open IDT File

    To open the IDT file:

    1. Change to the IDF Evolution window.

    2. Select File Open from the menu.

    3. Select the uploaded file from the list in the appearing window; e.g.: .

    4. Click on the Open button.

    10 Attach nob_RIU data to Actually Loaded IDT

    To attach the nob_RIU data:

    1. Select File Attach from the menu.

    2. Select the exported nob_RIU file from the list in the appearing window (the file and

    destination path was selected in step 7); e.g.: .

    3. Click on the Open button.

    4. A window opens that tells you how many attachments were made. Confirm by

    clicking on the OK button.

    http://bsplcml.pdf/http://bsplcml.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    59/69

    A30808-X3247-M282-05-7630

    59

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    11 Remove Redundant Nob_RIU Files

    In the IDF file that is delivered with the rack, all units are considered as nob_RIUs even

    if they are in fact ob_RIUs. All nob_RIUs that are in fact ob_RIUs and are thereforeredundant can be removed automatically after they were attached to the IDT file of the

    BTSE.

    To remove the redundant nob_RIU files:

    1. Select File Remove nob_RIUs from the menu.

    2. Click on the Yes button in the appearing window to confirm the deletion of all redun-

    dant nob_RIUs.

    3. A window opens that tells you how many records were deleted. Confirm by clicking

    on the OK button.

    4. Select File Save from the menu. An attention window is displayed that informs

    you on the destination path and file name to which the changes are saved. Confirm

    by clicking on the OK button.

    12 Export Remote Inventory Data for Backup

    Now you must create an IDF file for backup. This new IDF file replaces the IDF file deliv-

    ered with the rack. It contains the modifications you have just made.

    To export the Remote Inventory Data for backup:

    1. Select Export IDF from the menu.

    2. Select the destination path in the appearing window, preferably A:\. The file name

    is automatically composed of the SalesUniqueName with the extension .idf.

    3. Click on the Save button.

    4. An attention window opens that tells you the destination path of the saved file.Confirm by clicking on the OK button.

    5. Put the disk with the backup file of the inventory data to the site specific documen-

    tation.

    13 Export Nob_RIU Data for Download to the BTSE

    The nob_RIU data must be downloaded to the BTSE. In order to download them, you

    must export the nob_RIU data again into a NOB file. This new NOB file now contains all

    modified data without the redundant nob_RIUs.

    1. Select Export NOB from the menu.

    2. A window opens in which you can edit the file name and select the directory in which

    the file is saved. By default, the file name is composed of the SalesUniqueName

    with the extension .nob. Edit the file name and select the source directory or

    confirm the default name and directory by clicking on the Save button.

    3. The nob_RIU data are exported to the NOB file. The selected destination path of this

    file is displayed in an attention window. Confirm by clicking on the OK button.

    4. A question window is displayed: Create BTSE_NRIU for download? Confirm by

    clicking on the YES button. An attention window is displayed that informs you on the

    destination path and file name to which the BTS_NRIU downloads saved. Confirm

    by clicking on the OK button.

    14 Download the Nob_RIU File to the BTSE

    Change to the LMT Evolution main window.

  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    60/69

    60 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    b DNLIDFD REMINV

    1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter (SRCDIR, e.g.source directory).

    1.2 Enter the parameter (SRCDIR, the source directory in which the exported NOBfile was saved).

    2. Click on the Submit button

    System Response: In the Message Viewer window, the command result is displayed:

    Operation successful.

    END

    http://bsplcml.pdf/http://bsplcml.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    61/69

    A30808-X3247-M282-05-7630

    61

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.8 Switch to Phase 3

    1 Manual Switch to Phase 3

    For forced switchover to Phase 3, a special command may be entered at the LMT.

    b CONNBSC BTSM

    2 Logon

    To log on LMT:

    1. Click on the LogOn button in the tool bar.

    2. Enter user ID and password in the appearing LogOn window.

    3. Click on the OK button.

    The BTSE is now in phase 3. In this phase, the BTSE is connected to the BSC.

    Only the specified LEDs are relevant for this step.

    The LED indication on the COB2P8/COBA4P12A changes to:

    ACT fl (G)

    FLOC fl (G)

    The LED indication on the COSA6P16/COSA4P12 changes to:

    ACT fl (G)

    The LED indication on the CU changes to:

    OK fl (G) fl (G) SW

    Checklist in Case of Problems Switching over to Phase 3

    Minimal BTSE configuration with preconditions for a successful switchover to

    Phase 3:

    COBA-0 = unlocked.enabled

    COBA-0 is always created and always enabled.

    Here the Administrative State (AST*) is relevant.

    Minimal parameters of

    RACK-0:

    available

    This means that TypeOfBTSE (TYPRACK) must

    be set first before any HMO can be created.

    LAPDLE-0 = created

    Minimal parameters of

    LAPDLE-0:

    available

    This means that the LAPD channel (LAPDCH) must

    be defined.

    Accuracy of CCLK >= medium (at least !)

    http://bsplcml.pdf/http://bsplcml.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    62/69

    62 A30808-X3247-M282-05-7630

    ITMN:BTSE BS-41

    Id:0900d805800c67fd

    Procedures

    END

    The current CCLK accuracy can be determined by

    performing the LMT command Get COBA --->

    REQATTL ---> CCLKACC.

    Minimal parameters of

    BTSM:

    available

    This means that the TEI must be defined.

    Minimal parameters of

    BPORT-0:

    available

    This means that the layer1ProtocolType (L1PT) and

    lineConfiguration (LCONF) must be defined

    *) For more information on the Administrative State (AST), refer to:

    MMN:BTSE BS-240/240 II/240XL/240XL II

    MMN:BTSE BS-241/241 II

    MMN:BTSE BS-40/40 II

    MMN:BTSE BS-41

    Checklist in Case of Problems Switching over to Phase 3

    http://mmnbs240.pdf/http://mmnbs241.pdf/http://mmnbs40.pdf/http://mmnbs41.pdf/http://mmnbs41.pdf/http://mmnbs40.pdf/http://mmnbs241.pdf/http://mmnbs240.pdf/
  • 7/27/2019 Installation Test-Base Transceiver Station Equipment

    63/69

    A30808-X3247-M282-05-7630

    63

    ITMN:BTSE BS-41 Procedures

    Id:0900d805800c67fd

    3.9 SW Download and Activation (optional)

    This procedure is optional.

    g Make sure that all files of the relevant software load are present in a directory on theharddisk of the LMT.

    The V.11/X.21 interface (HDLC-Adapter, DLHC) has been installed and tested in

    advance.

    1 Reset the COBA

    Reset the COBA by pressing the reset button on the module.

    After about 15 seconds the COBA reaches the start connection status.

    2 Connect LMT

    Connect the LMT cable to the LMT 15-pin SUB-D connector on the DC panel.

    3 Log on LMT

    To log on LMT:

    1. Start the LMT program in the corresponding directory of Start menu (Start:\Pro-

    grams\LMT Evolution (string of version)\LMT Evolution).

    2. Enter your user ID and password in the appearing "LogOn" window.

    3. Click on the OK button.

    System Response: Several changed state event reports follow. They can be examined

    in the Message Viewer window.

    The BTSE is now in phase 1. In this phase, you can download and activate the software.

    4 SW Download

    b DNLALLEXE SOFTWARE-MANAGEMENT

    1. A Select the Parameter Value window pops up:

    1.1 Enter the path where the SW Load is stored on the LMT (SRCPATH).

    1.2 Enter the parameter values (OVERWRITE = ).

    2. Click on the Submit button

    System Response: Several messages are displayed that provide information on

    the progress and the end of the download for each file.

    The LMT performs an automatic logoff after a few minutes. If the session is closed,

    please log on again.

    LED indication on COBA:ACT fl (G) (R) RCOBA

    FLOG o