Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 1 of 10 650483-000 INSTRUCTION SHEET Installation Instructions for N2LED Series Emergency Luminaire Product Safety FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS. Signal Words Defined DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE is used to address practices not related to physical injury. Safety Instructions ! WARNING: Before installation, ensure that the unit complies with the hazardous area classification. Failure to do so may result in bodily injury and/or property damage. Refer to the fixture nameplate for suitability in specific hazardous locations. To prevent ignition of hazardous atmospheres, the area must be free of hazardous vapors before opening the enclosure or servicing the fixture. To reduce the possibility of static sparking, do not attach metallic parts to the outside of the unit (e.g. metallic screws, tags, decals, etc). Do not mount the unit near gas or electric heaters. De-energize the unit before opening. To reduce the risk of electric shock, disconnect AC power before servicing. To prevent arcing, avoid shorting the battery terminals. ! CAUTION: Servicing of this equipment should be performed by qualified service personnel. Do not attempt to service the battery. The unit uses a sealed, NiCD battery which requires no maintenance. For replacement, contact the factory. ! NOTICE: Do not use this equipment for anything other than its intended use. The use of accessory equipment is not recommended and may cause an unsafe condition. Wiring and installation should be performed in accordance with the National Electrical Code® (NEC®) and other applicable local code requirements. Agency Ratings • Class I, Division 2, Groups A, B, C, D • Class I, Zone 2, Group IIC • Type 4X • IP66 Marine Outside Type (Salt Water)

Installation Instructions for N2LED Series Emergency ......EMERGENCY LAMP UNIT MOUNTED LIGHT HEAD SET SCREWS COVER SCREW INSERT (FOUR [4] PLACES) 5.18 in. [131 mm] 6.69 in. [170 mm]

  • Upload
    others

  • View
    4

  • Download
    1

Embed Size (px)

Citation preview

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 1 of 10

    650483-000 INSTRUCTION SHEET

    Installation Instructions for N2LED Series Emergency Luminaire

    Product Safety

    FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.

    Signal Words Defined

    DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE is used to address practices not related to physical injury.

    Safety Instructions! WARNING:

    • Before installation, ensure that the unit complies with the hazardous area classification. Failure to do so may result in bodily injury and/or property damage. Refer to the fixture nameplate for suitability in specific hazardous locations.

    • To prevent ignition of hazardous atmospheres, the area must be free of hazardous vapors before opening the enclosure or servicing the fixture. To reduce the possibility of static sparking, do not attach metallic parts to the outside of the unit (e.g. metallic screws, tags, decals, etc).

    • Do not mount the unit near gas or electric heaters.

    • De-energize the unit before opening.

    • To reduce the risk of electric shock, disconnect AC power before servicing. To prevent arcing, avoid shorting the battery terminals.

    ! CAUTION:

    • Servicing of this equipment should be performed by qualified service personnel.

    • Do not attempt to service the battery. The unit uses a sealed, NiCD battery which requires no maintenance. For replacement, contact the factory.

    ! NOTICE:

    • Do not use this equipment for anything other than its intended use.

    • The use of accessory equipment is not recommended and may cause an unsafe condition.

    • Wiring and installation should be performed in accordance with the National Electrical Code® (NEC®) and other applicable local code requirements.

    Agency Ratings

    • Class I, Division 2, Groups A, B, C, D

    • Class I, Zone 2, Group IIC

    • Type 4X

    • IP66

    • Marine Outside Type (Salt Water)

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 2 of 10

    Product Description

    N2LED2T1 Master Unit

    FRONT VIEW—COVER REMOVED

    EMERGENCY LAMPSUNIT MOUNTED

    CONDUITHUB

    LIGHT HEADSET SCREWS

    LIGHT HEADSET SCREWS

    BATTERY

    UNIT MOUNTING HOLES(FOUR [4] PLACES)

    COVER SCREW INSERT(FOUR [4] PLACES)

    LIGHT HEAD CONTACTEIGHT (8) AVAILABLE FOR MAXIMUM

    FOUR (4) LIGHT HEADSINSTALLER CONNECTSBATTERY TO PCA CONNECTOR

    PUSH TO TEST SWITCHINTEGRAL PILOT LIGHT

    5.75 in. [146 mm]

    7.87 in. [200 mm]

    9.80 in. [248.9 mm]

    7.44 in. [189 mm]

    8.46 in. [215 mm]

    9.00 in. [228.6 mm]

    5.20 in. [132.1 mm]

    TERMINALBLOCK

    LIGHT HEADGROUND WIRE

    LIGHT HEADGROUND WIRE

    GROUND PLATE

    GROUND PLATEGROUND WIRE

    Figure 1: Description & Dimensions for N2LED2T1 Master Unit

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 3 of 10

    N2LED0T1 Master Unit

    FRONT VIEW—COVER REMOVED

    CONDUITHUB

    COVER SCREW INSERT(FOUR [4] PLACES)

    LIGHT HEAD CONTACTEIGHT (8) AVAILABLE FOR MAXIMUM

    FOUR (4) LIGHT HEADS

    BATTERY

    7.87 in. [200 mm]

    8.70 in. [221.0 mm]

    8.46 in. [215 mm]

    9.00 in. [228.6 mm]

    5.20 in. [132.1 mm]

    INSTALLER CONNECTSBATTERY TO PCA CONNECTOR

    UNIT MOUNTING HOLES(FOUR [4] PLACES)

    PUSH TO TEST SWITCHINTEGRAL PILOT LIGHT

    TERMINALBLOCK

    GROUND PLATEGROUND WIRE

    GROUND PLATE

    5.75 in. [146 mm]

    7.44 in. [189 mm]

    Figure 2: Description & Dimensions for N2LED0T1 Master Unit

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 4 of 10

    N2LEDR2R1 Remote Unit

    FRONT VIEW—COVER REMOVED

    EMERGENCY LAMPSUNIT MOUNTED

    LIGHT HEADSET SCREWS

    COVER SCREW INSERT(FOUR [4] PLACES)

    6.69 in. [170 mm]

    5.18 in. [131 mm]

    8.60 in. [218.4 mm]

    6.69 in. [170 mm]

    7.59 in. [192.8 mm]

    6.02 in. [153 mm]

    CONDUITHUB

    UNIT MOUNTING HOLES(FOUR [4] PLACES)

    3.35 in. [85.1 mm]

    LIGHT HEADGROUND WIRE

    GROUND PLATE

    Figure 3: Description & Dimensions for N2LEDR2R1 Remote Unit

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 5 of 10

    N2LEDR1R1 Remote Unit

    FRONT VIEW—COVER REMOVED

    CONDUITHUB

    UNIT MOUNTING HOLES(FOUR [4] PLACES)

    EMERGENCY LAMPUNIT MOUNTED

    LIGHT HEADSET SCREWS

    COVER SCREW INSERT(FOUR [4] PLACES)

    5.18 in. [131 mm]

    6.69 in. [170 mm]

    8.60 in. [218.4 mm]

    6.02 in. [153 mm]

    6.69 in. [170 mm]

    7.59 in. [192.8 mm]

    3.35 in. [85.1 mm]

    LIGHT HEADGROUND WIRE

    GROUND PLATE

    Figure 4: Description & Dimensions for N2LEDR1R1 Remote Unit

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 6 of 10

    Installation

    ! WARNING: Ensure the intended AC power supply to the enclosure is OFF before proceeding with installation.

    Installing the Unit:

    1. Select a mounting location. The unit should be mounted in locations and at heights where tampering by unauthorized personnel is not achievable.

    2. Loosen (do not remove) the four (4) captive screws from the enclosure cover. Set the cover aside for reassembly.

    3. Mount the unit with the back of the enclosure fastened to a vertical supporting surface using 1/4-20 UNC or M6 fasteners and anchors appropriate for the mounting surface. Fasteners are not supplied.

    4. Feed the AC power conductors through the conduit hub on top of the master unit. An Appleton nickel-plated enclosed hub with ground lug is provided for entrance to the AC power supply. AC input should be routed directly to the “AC IN” wiring terminal. There should not be any additional slack in the housing compartment. After the final conductor routing, use a thread sealant in the conduit-to-hub joint to maintain maximum environmental protection.

    5. Connect the AC power supply as shown in Figures 5 & 6. NOTE: The conduit ground plate must be grounded.

    CONDUITGROUND PLATE

    G

    GN L

    INDICATOR LIGHT

    RED

    BATTERY12 V, 1A MAX

    N

    N

    L _

    MOUNTING PAN

    L

    + + + +_ _ _ _

    +

    RED RED REDBLACK BLACK BLACKBLACK

    LAMP 1 LAMP 2 LAMP 3 LAMP 4

    RED BLACK

    BATTERY PACK

    LIGHT HEAD 1 LIGHT HEAD 2 LIGHT HEAD 3 LIGHT HEAD 4

    + +

    ++

    TWO (2) LIGHT HEADS ARE FACTORY INSTALLED

    TWO (2) ADDITIONAL LIGHT HEADS CAN BE CONNECTED USING SEPARATE REMOTE LIGHT BOX(ES)

    AC INPUT100-277

    BONDING WIREBONDING WIRE BONDING WIRE

    AC/DCADAPTOR

    PUSH-TO-TESTSWITCH (NC)

    Figure 5: Wiring Diagram for N2LED2T1 Master Unit

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 7 of 10

    INDICATOR LIGHT

    RED

    BATTERY12V, 1A MAX

    N

    L _

    MOUNTING PANG

    GN

    L

    + + + +_ _ _ _

    +

    RED RED REDBLACK BLACK BLACKBLACK

    LAMP 1 LAMP 2 LAMP 3 LAMP 4

    RED BLACK

    BATTERY PACK

    LIGHT HEAD 1 LIGHT HEAD 2 LIGHT HEAD 3 LIGHT HEAD 4

    + +

    ++

    N

    L

    BONDING WIRE

    AC/DCADAPTOR

    CONDUITGROUND PLATE

    AC INPUT100-277

    PUSH-TO-TEST SWITCH(NC)

    UP TO FOUR (4) LIGHT HEADS CAN BECONNECTED USING SEPARATEREMOTE LIGHT BOX(ES)

    Figure 6: Wiring Diagram for N2LED0T1 Master Unit

    6. Feed the remote unit wires through the conduit hub to the main unit.

    7. Connect the additional remote light head wires to the open lamp terminals by following the polarity on the wiring diagram.

    8. If applicable, install and connect the remote unit(s) as shown in Figures 7 & 8. Wire sizes are provided in Table 1. NOTE: The hub must be grounded. After the final conductor routing, use a thread sealant in the conduit-to-hub joint to maintain maximum environmental protection.

    Table 1: Wire Size for Remote Units*

    Maximum Wire Length Wire Gage78 ft. 18 AWG

    125 ft. 16 AWG198 ft. 14 AWG315 ft. 12 AWG500 ft. 10 AWG

    *Use copper wire between the power supply and the remote lighting system to limit the voltage drop to 5%

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 8 of 10

    _

    LIGHT HEAD 2

    +

    BLACKRED

    _

    RED BLACK

    WIRE CONNECTIONUSING WIRE NUT (FOUR [4] PLACES)

    +

    LIGHT HEAD 1

    CONDUIT ENTRY

    LIGHT HEAD WIRINGFROM MAIN FIXTURE

    + +

    BONDING WIRE

    BONDING WIRE

    CONDUITGROUND PLATE

    G

    Figure 7: Wiring Diagram for N2LEDR2R1 Remote Unit

    LIGHT HEAD WIRINGFROM MAIN FIXTURE

    LIGHT HEAD 1

    +

    WIRE CONNECTIONUSING WIRE NUT (TWO [2] PLACES)

    BLACKRED

    _

    CONDUIT ENTRY

    +

    BONDING WIRE

    G

    CONDUITGROUND PLATE

    Figure 8: Wiring Diagram for N2LEDR1R1 Remote Unit

  • Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 9 of 10

    9. Connect the battery leads. Follow the placement and connections exactly as shown in Figures 5 & 6. NOTE: The battery will be fully charged within 48 hours (maximum). Emergency lamps may or may not light at this time, depending on the battery charge.

    10. Loosen (do not remove) the set screws at the swivel base of the light head assembly. Adjust the lighting fixtures to the desired position/angle and tighten the set screws.

    11. Check all connections for continuity and grounding integrity.

    12. Reinstall the enclosure cover and securely tighten the four (4) captive screws. To maintain a proper seal, the screws require 1.83 ft.-lb. torque.

    13. Apply AC to the unit. The pilot light should begin to flash.

    14. Activate the diagnostic test by pushing and releasing the push-to-test switch. See “Self-Diagnostic Testing” for further information.

    Self-Diagnostic Testing

    Features

    There are three types of diagnostic monitoring/testing: on-going (constant), periodic (every 30 days), and user-initiated (push-to-test switch).

    • The on-going diagnostic monitors the battery voltage constantly to see if it is in the proper range. Battery failure status will be displayed when not in the proper range. See “Table 2—Status Indicator Codes” for more information.

    • The frequency of the self-diagnostic test is every 30 days (periodic) or approximately 1 second after the push-to-test switch is pushed and released (user-initiated). The 30-day counter resets to 0 when a power outage is detected or when the push-to-test switch is activated.

    • When the self-test is triggered (by pushing the push-to-test switch), the diagnostic test will not check for light head currents. The user can visually verify that the lights are working by pressing and holding the push-to-test switch. Any installed light heads connected to the unit will light to assure the user that the lamps are working.

    • During the self-diagnostic test, the LED light head(s) will be turned on for 30 seconds while the push-to-test switch LED flashes ON and OFF.

    • The self-diagnostic test stimulates the load transfer circuit by resetting the AC present detection circuit.

    • The push-to-test switch LED will show the status of the emergency light when AC is present. See “Table 2—Status Indicator Codes” for more information.

    • Learn Mode: When the push-to-test switch is activated and the battery has enough capacity to power the light heads, the unit will detect which light head and how many are installed. This information will be used during the periodic (30-day) diagnostic test.

    If the learn mode is successfully performed, the pilot light will flash a number of times equal to the number of light heads detected. If it is not successfully performed, then the pilot light will just flash indicating charging. You can either wait until the battery is charged before activating the push-to-test switch or just use the built-in default of one (1) light head minimum.

    Parameters

    In the AC present state, the following parameters are monitored:

    • Battery charge current.

    • Battery terminal voltage during charge.

    During the periodic (30-day) diagnostic test, the following parameters are tested:

    • Battery terminal voltage under load.

    • Transfer circuit states.

    • Lamp head current. NOTE: The installed light heads will be tested if a “Learn Mode” has occurred; otherwise, a minimum of one (1) working light head is checked.

  • 650483-000 Rev. B 07/15 • Page 10 of 10

    Status Indicator Codes

    Table 2: Status Indicator Codes for Push-to-Test Switch (when AC is present)

    Status Indication Status Description Status Definition

    No light AC power removed from circuit

    * Continuous steady light Battery fully charged

    *_*_ Light blinks 1 time Battery charging

    **_**_ Light blinks 2 times Battery failure

    ***_***_ Light blinks 3 times LED lamp head failure

    ****_****_ Light blinks 4 times Emergency circuit charger board failure

    * = Status LED ON; _ = Status LED OFF

    Maintenance

    Battery

    • The unit uses a sealed, NiCD battery which requires no maintenance. For replacement, contact the factory.

    Tests

    • Monthly: The unit will automatically test the operation of the emergency circuit (for 30 seconds minimum) once a month. The emergency lamps will illuminate during the test. See “Self-Diagnostic Testing” for further information.

    • Once a Year: Conduct a 90-minute discharge test once a year. The lamps should operate for at least 90 minutes.

    Replacement Parts

    Emergency Lighting Unit

    • Driver Board Kit: N2LEDCB.

    • Battery Pack Kit: N2LEDBP.

    • Nickel-Plated Brass M25 Male, 3/4 in. NPT Female Hub: 737DM7T25.

    Lighting Fixture Head Assembly

    • Light Head Kit: N2LEDLH. NOTE: If the LED fails, the entire assembly must be replaced.

    Except as expressly provided by Appleton Grp, LLC (Appleton), Appleton products are intended for ultimate purchase by industrial users and for operation by persons trained and experienced in the use and maintenance of this equipment