Installation and service instructionsfor contractors

VIESMANN

Vitogate 300Type BN/MB

Communication with heating systems via BACnet and Modbus

For applicability, see the last page

VITOGATE 300

5672 142 GB 10/2014 Please keep safe.

Page 2: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

2

Please follow these safety instructions closely toprevent accidents and material losses.

Safety instructions explained

DangerThis symbol warns against the risk of injury.

! Please noteThis symbol warns against the risk of materiallosses and environmental pollution.

NoteDetails identified by the word "Note" contain additionalinformation.

Target group

These instructions are exclusively intended for quali-fied contractors.■ Work on electrical equipment must only be carried

out by a qualified electrician.■ The system must be commissioned by the system

installer or a qualified person authorised by theinstaller.

Regulations

Observe the following when working on this system: ■ National installation regulations■ Statutory regulations regarding the prevention of

accidents■ Statutory regulations regarding environmental pro-

tection■ The Code of Practice of relevant trade associations■ All current safety regulations as defined by DIN, EN,

DVGW, VDE and all locally applicable standardsa ÖNORM, EN and ÖVEc SEV, SUVA, SVTI and SWKI

If you smell flue gas

DangerFlue gas can lead to life threatening poisoning.■ Shut down the heating system.■ Ventilate the installation site.■ Close all doors in the living space.

Flue systems and combustion air

Ensure that flue systems are clear and cannot besealed, for instance due to accumulation of conden-sate or other causes. Ensure a sufficient supply ofcombustion air.Instruct system users that subsequent modifications tothe building characteristics are not permissible (e.g.cable/pipework routing, cladding or partitions).

DangerLeaking or blocked flue systems, or an insuffi-cient supply of combustion air can cause lifethreatening poisoning from carbon monoxide inthe flue gas.Ensure the flue system is in proper workingorder. Apertures for supplying combustion airmust be non-closable.

Extractors

Operating appliances that extract air to the outside(cooker hoods, extractors, air conditioning units, etc.)can create negative pressure. If the boiler is operatedat the same time, this can lead to reverse flow of theflue gas.

DangerThe simultaneous operation of the boiler andappliances that extract air to the outside canresult in life threatening poisoning due toreverse flow of the flue gas.Fit an interlock circuit or take suitable steps toensure a sufficient supply of combustion air.

Working on the system

■ Isolate the system from the power supply (e.g. byremoving the separate fuse or by means of a mainsisolator) and check that it is no longer 'live'.

■ Safeguard the system against reconnection.

DangerHot surfaces can cause burns.■ Before maintenance or service work, switch

OFF the appliance and let it cool down.■ Never touch hot surfaces on the boiler, burner,

flue system or pipework.

! Please noteElectronic assemblies can be damaged by elec-trostatic discharge.Before beginning work, touch earthed objects,such as heating or water pipes, to dischargestatic loads.

Repair work

! Please noteRepairing components that fulfil a safety func-tion can compromise the safe operation of thesystem.Faulty components must be replaced with origi-nal Viessmann spare parts.

Safety instructions

Safety instructions

5672

142

GB

Page 3: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

3

Auxiliary components, spare and wearing parts

! Please noteSpare and wearing parts that have not been tes-ted together with the system can compromise itsfunction. Installing non-authorised componentsand making non-approved modifications or con-versions can compromise safety and may inva-lidate the warranty.For replacements, use only original spare partssupplied or approved by Viessmann.

Safety instructions

Safety instructions (cont.)

5672

142

GB

Page 4: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

4

1. Preparing for installation ................................................................................................................ 5

2. Installation sequence Installing the Vitogate 300 ..................................................................... 6Making the LON connection .................................................................. 6Power supply ......................................................................................... 8■ Directives ............................................................................................ 8■ Power supply via the mains isolator ................................................... 8■ Power supply independent of the mains isolator ................................ 9

3. Commissioning andadjustment

Connection diagram ............................................................................... 10Integrating the Vitotronic control unit into LON ...................................... 10■ LON system number and subscriber number ..................................... 10■ Updating LON subscriber list .............................................................. 11■ Carrying out subscriber check ............................................................ 11

4. Connection diagram ................................................................................................................ 12

5. Commissioning ................................................................................................................ 13

6. Parts list ................................................................................................................ 14

7. Specification Vitogate 300, type BN/MB ..................................................................... 15Power supply unit .................................................................................. 15

8. Certificates Declaration of conformity ....................................................................... 16

9. Keyword index ................................................................................................................ 17

Index

Index

5672

142

GB

Page 5: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

5

Intended use

Install and operate Vitogate products as intended inconjunction with the electronic control units and con-trollers for the Viessmann heat and power generatorsdesigned for this system, giving due consideration tothe associated installation, service and operatinginstructions. In particular, observe the current and volt-age specifications for connections and hook-ups.

Use Vitogate products exclusively for monitoring, oper-ating and optimising systems with the user and com-munication interfaces specified for this purpose in therelevant printed documentation. In the case of commu-nication interfaces, ensure on site that the systemrequirements specified in the product documentationare met at all times for every transfer mediumemployed. Only use the specified components for themains power supply (e.g. mains power adaptors).

Product information

The Vitogate 300, type BN/MB gateway is designed tohook-up Vitotronic control units with integral LON com-munication module (accessory) to BACnet or Modbuscontrol systems. For supported appliances/devicesand further information, see www.vitogate.info.

The Vitogate 300, type BN/MB must be integrated intothe BACnet or Modbus control system by an author-ised contractor.

Functions

The Vitogate 300, type BN/MB enables system usersto utilise the following functions in conjunction with aBACnet or Modbus control system:■ Transferring heating system operating states■ Setting heating system parameters■ Relaying fault and error messages

Preparing for installation

Preparing for installation56

72 1

42 G

B

Inst

alla

tion

Page 6: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

6

+ + - -

Output DC

DC OK

L(+)N(-)

STEP

PO

WER

10065

A B

Fig. 1

A Power supply unit (standard delivery)B Vitogate 300

Vitogate 300, type BN/MB and its power supply unitare suitable for mounting on a support rail (TS 35 toEN 50 022: 35 x 15 and 35 x 7.5) inside control panels.

Making the LON connection

The Viessmann LON is designed for "Line" BUS topol-ogy with a terminator at both ends (accessories). Fur-ther information can be found in the "Viessmann LONmanual"; see www.viessmann.de/lon.The transfer distances for LON are subject to the elec-trical properties of the respective cable. For this rea-son, only use the specified cable types. Use only onecable type within each LON.Cable types (on site):■ 2-core cable, CAT5, screened■ JY(St)Y 2 x 2 x 0.8 mm (telephone cable)Observe the cabling requirements for the operation ofthe LON interface FTT 10-A (see www.echelon.com).All Viessmann appliances are connected with RJ45connectors. The Viessmann LON always requirescores "1" and "2" plus the screen. The cores are inter-changeable. The installation is therefore reverse polar-ity protected.

NoteWhen connecting devices and routing cables, observethe requirements of safety category II. That is 8.0 mmair and creep paths or 2.0 mm insulation thicknessagainst 'live' components.Ensure the safe electrical separation of all on-site com-ponents (incl. PC/laptops) conforms to EN 60 335 orIEC 65.

Installation sequence

Installing the Vitogate 300

5672

142

GB

Inst

alla

tion

Page 7: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

7

Connection with LON cable

C

A A B

DC

DFig. 2 Installation spacing ≤ 7 m

A Vitotronic control unitB Vitogate 300

C TerminatorD LON cable, 7 m long

Connection with LON cable and LON coupling

C

E

A A B

E DD D EE DD

C

D

Fig. 3 Installation spacing 7 to 21 m

A Vitotronic control unitB Vitogate 300C Terminator

D LON cable, 7 m long:Max. 3 cables between 2 devices

E LON coupling

Connection with on-site cable and LON plug

C

A A B

EC

E

F

≤ 900 m

D D D D

Fig. 4 Installation spacing ≤ 900 m (with LON con-nector)

A Vitotronic control unitB Vitogate 300C Terminator

D LON plugE On-site cableF Up to 99 subscribers

Connection with LON cable, on-site cable and LON socket

≤ 900 m

FC

DC

D D DE

F F F

E

A A G B

Fig. 5 Installation spacing ≤ 900 m (with LON sock-ets)

A Vitotronic control unitB Vitogate 300C TerminatorD LON cable, 7 m long

E On-site cableF LON socketsG Up to 99 subscribers

Installation sequence

Making the LON connection (cont.)

5672

142

GB

Inst

alla

tion

Page 8: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

8

Directives

Regulations

Connect the power supply and implement all safetymeasures (e.g. RCD circuit) in accordance withIEC 60364, the connection requirements of your localpower supply utility, and VDE or national regulations.Protect the Vitogate 300 power cable with an appropri-ate fuse.

For oil and gas combustion equipment over 100 kW,according to the Sample Combustion Ordinance"FeuVO", an "emergency stop switch" must be instal-led on site outside the installation room. Observe thenational combustion equipment regulations for yourlocal region. For combustion equipment to EN50156-1, the "emergency stop" installed on site mustcomply with the requirements of EN 50156-1. Fit the"emergency stop switch" outside the installation room.

Install an isolator in the power cable to provide omnip-olar separation from the mains for all active conduc-tors, corresponding to overvoltage category III (3 mm)for full isolation. This isolator must be fitted in the per-manent electrical installation in line with installationrequirements.We also recommend installing an AC/DC-sensitiveRCD (RCD class B ) for DC (fault) currents thatcan occur with energy efficient equipment.

Recommended power cable

3-core cable:■ H05VV-F3G 1.5 mm2

■ H05RN-F3G 1.5 mm2

Power supply via the mains isolator

When the heating system is switched off via the mainsisolator, the Vitogate 300 and the Vitotronic control unitare also switched off.No data is transferred to the BACnet or Modbus con-trol system.

DangerIncorrect core allocation can result in seriousinjury and damage to the appliance.Take care not to interchange wires "L1" and "N":L1 BrownN BluePE Green/yellow

B

C

DE

G

F

A

L1PEN

40

L N

+24 V GND

N

LBN

BUGNYE

+ -

24 V DC

100-240 V AC

Fig. 6

A Vitogate 300B Power supply 100 to 240 V~, 45 to 65 HzC Fuse (max. 16 A)D Mains isolator, 2-pole, on site (if installed)

E Junction box (on-site)F Vitotronic control unit power supply (plug fÖ)G Power supply unit

Installation sequence

Power supply

5672

142

GB

Inst

alla

tion

Page 9: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

9

1. Check whether the power cable to the Vitotroniccontrol unit has appropriate fuse protection.

2. Terminate the power cable on site in terminal boxE and at plug fÖ.

3. Insert plug fÖ into the Vitotronic control unit.

Colour coding in accordance with DIN IEC 60757BN/MB BrownBU BlueGNYE Green/yellow

Power supply independent of the mains isolator

When the heating system is switched off via the mainsisolator, the Vitogate 300 remains on, whilst theVitotronic control unit is switched off.

No data is transferred to the BACnet or Modbus con-trol system.

B

C

ED

G

F

A

L1PEN

40

L N

+24 V GND

BN

BUGNYE

+ -

24 V DC

100-240 V AC

N

L

Fig. 7

A Vitogate 300B Power supply 100 to 230 V~, 45 to 65 HzC Fuse (max. 16 A)D Junction box (on-site)

E Mains isolator, 2-pole, on site (if installed)F Vitotronic control unit power supply (plug fÖ)G Power supply unit

1. Check whether the power cable to the Vitotroniccontrol unit has appropriate fuse protection.

2. Terminate the power cable on site in terminal boxD and at plug fÖ.

DangerIncorrect core allocation can result in seriousinjury and damage to the appliance.Take care not to interchange wires "L1" and"N":L1 BrownN BluePE Green/yellow

3. Insert plug fÖ into the Vitotronic control unit.

Installation sequence

Power supply (cont.)

5672

142

GB

Inst

alla

tion

Page 10: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

10

LON

PWR

RS485

+-

24 V AC/D

CD

CB+

A-AG

ND

Shld

ON

OFF

12

3

BIASBIAS

Term

LON

LAN

USB

Reset

Power

Status

RX

TX

LON status

Fig. 8

LON status Illuminates greenRX Flashes yellow: Device receives data.TX Flashes yellow: Device sends data.Power Illuminates green: Power ON, operating

voltage 'live'Status Multicolour status LED: red, green, orange

Meaning of the status indication:Illuminatesgreen.

Reset is being held down.

Flashes green. Standard operationFlashes green/red.

DHCP server enabled

Illuminates or-ange.

Indication during re-start

Flashes or-ange.

Indication following the start phasewhen there is no gateway configura-tion

Flashes red. Indication in the case of BUS errorsin the MS/TP network (e.g. framingerrors)

Illuminates red. Indication prior to a reset whilst filesare being connected.

Integrating the Vitotronic control unit into LON

The LON communication module (accessory) must beplugged into the Vitotronic control unit.

NoteThe data transfer via LON can take several minutes.

LON system number and subscriber number

Set LON system number, LON subscriber number andfurther functions via code 2.

Vitotronic control unit service instructions andthe following table

NoteIn the same LON system, each number an only beallocated once.Only one Vitotronic control unit per system may beprogrammed as the fault manager.

Commissioning and adjustment

Connection diagram

5672

142

GB

Serv

ice

Page 11: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

11

Example: Single boiler system with Vitotronic 300, Vitotronic 200-H heating circuit control unit down-stream and Vitogate 300, type BN/MBVitotronic 300 Vitotronic 200-H Vitogate 300

LON LON

Subscriber no. 1Code "77:1"

Subscriber no. 10Code "77:10"

Delivered condition Vitogate 300:Subscriber no. 97

Control unit is fault managerCode "79:1"

Control unit is not fault manager.Code "79:0"

Device is fault manager.

Viessmann system numberCode "98:1"

Viessmann system numberCode "98:1"

LON subscriber fault monitoringCode "9C:20"

LON subscriber fault monitoringCode "9C:20"

Updating LON subscriber list

Vitotronic control unit installation and serviceinstructions

Carrying out subscriber check

Vitotronic control unit installation and serviceinstructions

Commissioning and adjustment

Integrating the Vitotronic control unit into LON (cont.)

5672

142

GB

Serv

ice

Page 12: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

12

D

LON

PWR

RS485

+-

24 V AC/D

CD

CB+

A-AG

ND

Shld

ON

OFF

12

3

BIASBIAS

Term

F

LON

LAN

USB

E

Reset

Power

Status

RX

TX

LON status

A

B

C

Fig. 9

A DIP switch:1 Bias voltage for RS 485 interface2 Bias voltage for RS 485 interface3 120 Ω terminator

B RS 485 connection: Interface for BACnet MS/TP orModbus RS 485

C Supply voltage 24 V–: Power supply unit, secon-dary side

D LAN connection with PC/Laptop or BACnet IP orModbus TCP/IP

E LON connection, 2 pce RJ 45 sockets, screenedF USB connection for software updates

Connection diagram

Connection diagram

5672

142

GB

Serv

ice

Page 13: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

13

Devices required for commissioning:■ PC/laptop with the following equipment:

– Minimum monitor resolution 1024 x 768– Integral or external Ethernet network module– PDF Reader

■ Supported web browsers:– MS Internet Explorer V 7 or higher– Mozilla Firefox V 2 or higher– Mobile Safari V 3.1 or higher– Google Chrome V 18.0 or higher

■ Twisted pair network cable

Enabling the DHCP server

Dynamic Host Configuration Protocol (DHCP) makesIP addresses available to clients on request. If the computer has been set up as DHCP client(standard setting), the DHCP server of theVitogate 300 can be used to provide an IP address.

Hold down the reset button on the Vitogate 300 for atleast 5 s, but no longer than 10 s.The DHCP server has been enabled once the LEDLON status flashes green/red alternately.

NoteThe DHCP server does not need to be enabled if amanual IP address is to be used.

Creating an Ethernet network

Connect the computer network module by means of atwisted pair network cable with the RJ45 connection ofthe Vitogate 300.

Creating a connection with the Vitogate 300 configuration webserver

An IP address is automatically assigned to the com-puter if the DHCP server has been enabled.

If a manual IP address is to be used, make the follow-ing settings on the computer:■ IP address: 169.254.0.2 (or higher)■ Subnet mask: 255.255.0.0■ Standard gateway: Leave blank.

Calling up the Vitogate 300 configuration webserver

Open the Vitogate 300 configuration screens:

Start web browser:■ Enter IP address 169.254.0.1 into the address line.■ User name: vitogate■ Password: viessmann

You can change the password later.

The gateway default screen is called up.

NoteThe configuration screens are described in the integralVitogate 300 online help.

Commissioning

Commissioning56

72 1

42 G

B

Serv

ice

Page 14: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

14

Pos. Part0001 Standard unit Vitogate 300, type BN/MB0002 LON cable, 7 m long0003 Power supply unit0005 LAN cable0006 Vitogate 300, type BN/MB installation and service instructions

0005 00060002

00010003

Fig. 10

Parts list

Parts list

5672

142

GB

Serv

ice

Page 15: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

15

Mains voltage 12 to 24 V AC/DCPower consumption Max. 320 mARated output Max. 3.85 WFrequency range 47 to 63 HzPermiss. ambient temperature ■ During operation 0 to 45 °C■ During transport and storage −10 to +65 °CPermiss. humidity ■ During operation 20 to 80 % relative humidity, non-condensing■ During storage and transport 10 to 85 % relative humidity, non-condensingDimensions (height x width x depth) 100 x 48 x 70 mmInstallation Top-hat rail TS35 to EN 50022Power supply unit STEP-PS 1AC/24DC 0.75/FL.

Power supply unit

Rated voltage 100 to 240 V~Rated frequency 45 to 65 HzOutput voltage 24 V– ±1 %Output current max. 1.4 AIP rating IP20Safety category IIPermiss. ambient temperature ■ Operation –25 to +70 °C

> 55 °C line loss■ Storage and transport −40 to +85 °CMax. humidity 95 % relative humidity at 25 °C, non-condensingDimensions (height x width x depth) 150 x 36 x 43 mm

Specification

Vitogate 300, type BN/MB56

72 1

42 G

B

Serv

ice

Page 16: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

16

We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole responsible body that the productVitogate 300, type BN/MB complies with the following standards:

EN 60335-1 EN 60950-1EN 55024 EN 55022

This product is _ designated in accordance with the terms of the following Directives:

1999/5/EC 2004/108/EC2006/95/EC 2011/65/EU

Allendorf, 01 August 2014 Viessmann Werke GmbH & Co KG

Authorised signatory Manfred Sommer

Certificates

Declaration of conformity

5672

142

GB

Serv

ice

Page 17: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

17

BBACnet...................................................................5, 12

CControl panel................................................................6

EElectrical connections– Overview................................................................. 10– Power supply.............................................................8

FFault manager............................................................ 11

IInstallation.................................................................... 6Intended use................................................................ 5

LLON............................................................................10– cable..........................................................................7– Control unit integration............................................10– Coupling....................................................................7– Fault monitoring.......................................................11– Making a connection................................................. 6– on-site cable..............................................................7– Socket....................................................................... 7– Subscriber check.....................................................11– Subscriber list..........................................................11– Subscriber number..................................................10– System number.......................................................10LON communication module......................................10

MModbus.................................................................. 5, 12

PPower cable................................................................. 8Power supply– Directives.................................................................. 8– Independent of mains isolator...................................9– Via mains isolator......................................................8Power supply unit– Specification............................................................15Product information...................................................... 5

SSpecification...............................................................15

Keyword index

Keyword index56

72 1

42 G

B

Page 18: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

18

5672

142

GB

Page 19: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet

19

5672

142

GB

Page 20: Installation and service instructions Vitogate 300...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN/MB Communication with heating systems via BACnet