44
Installation and Operation Instructions Document 1218B H2330500B WARNING If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency, or gas supplier. FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty. AVERTISSEMENT Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort. Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil. QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ: Ne pas tenter d’allumer d’appareils. Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez. Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur. Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies. L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz. Installation and Operation Instructions for NeoTherm ® Modulating Boiler Model NTH Sizes 080–500 MBTU/h

Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

Installation and Operation Instructions Document 1218B

H23

3050

0B

WARNINGIf the information in this manual is notfollowed exactly, a fire or explosion mayresult causing property damage, personalinjury or loss of life.

Do not store or use gasoline or otherflammable vapors and liquids in the vicinityof this or any other appliance.

WHAT TO DO IF YOU SMELL GAS• Do not try to light any appliance.• Do not touch any electrical switch; do not

use any phone in your building.• Immediately call your gas supplier from a

nearby phone. Follow the gas supplier'sinstructions.

• If you cannot reach your gas supplier, callthe fire department.

Installation and service must be performed bya qualified installer, service agency, or gassupplier.

FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operationcould create carbon monoxide gas in flue gases which could cause serious injury, property damage, ordeath. Improper installation and/or operation will void the warranty.

AVERTISSEMENTAssurez-vous de bien suivres les instructionsdonnées dans cette notice pour réduire auminimum le risque d’incendie ou d’explosion oupour éviter tout dommage matériel, touteblessure ou la mort.

Ne pas entreposer ni utiliser d’essence nid’autres vapeurs ou liquides inflammables dansle voisinage de cet appareil ou de tout autreappareil.

QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:• Ne pas tenter d’allumer d’appareils.• Ne touchez à aucun interrupteur. Ne pas vous

servir des téléphones dansle bâtiment où vousvous trouvez.

• Appelez immédiatement votre fournisseur degaz depuis un voisin. Suivez les instructionsdu fournisseur.

• Si vous ne pouvez rejoindre le fournisseur degaz, appelez le sservice des incendies.

L’installation et l’entretien doivent être assurés parun installateur ou un service d’entretien qualifié oupar le fournisseur de gaz.

Installation and OperationInstructions for

NeoTherm®

Modulating BoilerModel NTH

Sizes 080–500 MBTU/h

Page 2: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 2

TABLE OF CONTENTS

SECTION 1.General Information1.1 Introduction...................................................... 31.2 Model Identification ......................................... 31.3 Appliance Overview ......................................... 31.4 Warranty .......................................................... 31.5 Unpacking ....................................................... 41.6 Dimensions...................................................... 41.7 Locating the Appliance .................................... 41.8 Locating Appliance for Correct Vent Distance

from Outside Wall or Roof Termination ........... 8

SECTION 2.Venting and Combustion Air2.1 Combustion Air ................................................ 82.1.1 Combustion Air From Room ............................ 82.1.2 Intake Combustion Air ..................................... 92.2 Venting ............................................................ 92.3 Locating Vent & Combustion Air Terminals ... 102.3.1 Side Wall Vent Terminal ................................ 122.3.2 Side Wall Combustion Air Terminal ............... 122.3.3 Vertical Vent Terminal ................................... 122.3.4 Vertical Combustion Air Terminal .................. 122.3.5 Installations in the Commonwealth

of Massachusetts .......................................... 122.4 Common Vent Test ....................................... 13

SECTION 3.Gas Supply and Piping3.1 Gas Supply and Piping .................................. 13

SECTION 4.Water Connections4.1 Heating System Piping:

Hot Supply Connections ................................ 144.2 Cold Water Make-Up ..................................... 144.3 Freeze Protection .......................................... 154.4 Recognized Chemicals .................................. 17

SECTION 5.Electrical Connections5.1 Main Power ................................................... 225.2 Control Features ............................................ 225.2.1 User Mode ..................................................... 225.2.1.1 Temperature Control Point Adjustment ......... 225.2.1.2 Direct Hot Water Control Point Adjustment ... 225.2.2 Setup Mode ................................................... 225.2.2.1 Adjusting the Temperature Display

Units in °F or °C ............................................. 23

5.2.2.2 Adjusting the Outdoor Reset On or Off .......... 235.2.2.3 Adjusting Low Boiler Temperature Setpoint .. 235.2.2.4 Adjusting High Outdoor Temperature

Setpoint ......................................................... 235.2.2.5 Adjusting Low Outdoor Temperature

Setpoint ......................................................... 235.2.2.6 Anti Short Cycle Time .................................... 235.2.3 Diagnostic Mode............................................ 235.2.3.1 High Limit Setting .......................................... 235.2.3.2 DHW Limit Setting ......................................... 235.3 Pump Connections ........................................ 245.4 Temperature Control ..................................... 245.5 Temperature Control - Indirect Tank ............. 245.6 Outdoor Reset Operation .............................. 245.7 External Control Connections ........................ 255.8 Wiring Diagram.............................................. 27

SECTION 6.Operating Instructions6.1 Filling the Boiler System ................................ 276.2 Operating the Burner and Set Up .................. 276.2.1 Burner Operation ........................................... 286.2.2 Boiler Setpoint and Adjustment ..................... 296.3 Shutting Down the NeoTherm ....................... 296.4 To Restart the NeoTherm .............................. 29

SECTION 7.Maintenance7.1 System Maintenance ..................................... 307.2 Appliance Maintenance and

Component Description ................................. 317.2.1 Burner ............................................................ 317.2.2 Modulating Gas Valve / Venturi ..................... 317.2.3 Appliance Control .......................................... 317.2.4 Ignitor Assembly ............................................ 317.2.5 Flame Sensor ................................................ 317.2.6 Transformers ................................................. 327.2.7 Blower ........................................................... 327.2.8 Heat Exchanger Coils .................................... 327.2.9 Gas Pressure Switches (optional) ................... 33

SECTION 8.Trouble Shooting8.1 Sequence of Operation ................................. 338.2 Short Cycling ................................................. 338.3 Error Codes ................................................... 33

SECTION 9.Replacement Parts9.1 General Information ....................................... 359.2 Parts List ....................................................... 36

Page 3: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 3

SECTION 1.General Information

WARNINGThe NeoTherm hydronic boiler must be installed inaccordance with the procedures detailed in thismanual, or the LAARS Heating Systems warranty willbe voided. The installation must conform to therequirements of the local jurisdiction having authority,and, in the United States, to the latest edition of theNational Fuel Gas Code, ANSI Z223.1/NFPA54. InCanada, the installation must conform to the latestedition of CSA B149.1 Natural Gas and PropaneGas Installation Code, and/or local codes. Whererequired by the authority having jurisdiction, theinstallation of NeoTherm boilers must conform to theStandard for Controls and Safety Devices forAutomatically Fired Boilers, ANSI/ASME CSD-1. Anymodifications to the boiler, its gas controls, or wiringmay void the warranty. If field conditions requiremodifications, consult the factory representativebefore initiating such modifications.

1.1 IntroductionThis manual provides information necessary for

the installation, operation, and maintenance of LAARSHeating Systems NeoTherm appliances. Read itcarefully before installation.

All application and installation procedures shouldbe reviewed completely before proceeding with theinstallation. Consult the LAARS Heating Systemsfactory, or local factory representative, with anyproblems or questions regarding this equipment.Experience has shown that most operating problems arecaused by improper installation.

The NeoTherm appliance is protected against overpressurization. A pressure relief valve is fitted to allappliances. It is installed inside the jacket (see Section 4for instructions on how to pipe the relief valve outlet).IMPORTANT: The inlet gas pressure to the appliancemust not exceed 13" W.C. (3.2kPa).

All installations must be made in accordance with1) American National Standard Z223.1/NFPA54-LatestEdition “National Fuel Gas Code” or 2) CSA B149.1

“Natural Gas and Propane Installation Code” and withthe requirement of the local utility or other authoritieshaving jurisdiction. Such applicable requirements takeprecedence over the general instructions containedherein.

All electrical wiring is to be done in accordancewith the local codes, or in the absence of local codes,with: 1) The National Electrical Code ANSI/NFPA No.70-latest Edition, or 2) CSA STD. C22.1 “CanadianElectrical Code - Part 1”. This appliance must beelectrically grounded in accordance with these codes.

1.2 Model IdentificationConsult the rating plate on the unit. The following

information describes the model number structure.(1-2) Model Series Designation

N T = NeoTherm(3) Usage

H = Hydronic(4-6) Size

0 8 0 = 80,000 BTU/hr input1 0 5 = 105,000 BTU/hr input1 5 0 = 150,000 BTU/hr input2 1 0 = 210,000 BTU/hr input2 8 5 = 285,000 BTU/hr input3 9 9 = 399,000 BTU/hr input5 0 0 = 500,000 BTU/hr input

(7) FuelN = Natural GasP = LP Gas

(8) Options CodeX = Standard UnitJ = CSD-1, FM, GAP, IL Code (size 500 only)

(9) Pump OptionsN = Factory-mounted pump (standard)X = No pump

(10) Revision1 = First version

1.3 Appliance OverviewSee Figures 2 through 6.

1.4 WarrantyLAARS Heating Systems’ NeoTherm appliances

are covered by a limited warranty. The owner shouldcomplete the warranty registration at www.Laars.com.

All warranty claims must be made to an authorizedLAARS Heating Systems representative. Claims must

Model Nomenclature1 2 3 4 5 6 7 8 9 10

N T H 1

SERIES

N T

USAGE

H - HYDRONIC

SIZEMBTU/h

0 8 01 0 51 5 02 1 02 8 53 9 95 0 0

FUEL

N - NATURAL

P - PROPANE

OPTIONS CODE

X - STANDARD

J - CSD-1,FM, GAP,IL (500 only)

PUMP OPTIONS

N - PUMP-MTD(standard)

X - NO PUMP

REVISION

1 - FIRST

Page 4: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 4

include the serial number and model (this informationcan be found on the rating plate), installation date, andname of the installer. Shipping costs are not included inthe warranty coverage.

Some accessory items may be shipped in separatepackages. Verify receipt of all packages listed on thepacking slip. Inspect everything for damageimmediately upon delivery, and advise the carrier of anyshortages or damage. Any such claims should be filedwith the carrier. The carrier, not the shipper, isresponsible for shortages and damage to theshipment whether visible or concealed.

1.5 UnpackingThe NeoTherm is shipped in a single crate with the

following standard components packed on top of theappliance (see Figure 1):

A. exhaust terminal C. temperature/pressure gaugeB. intake terminal D. alternate terminal screens

1. Remove all packing and tie-down materials.2. Check contents of the carton against items shown.

1.6 DimensionsDimensions are shown in Figure 7.

1.7 Locating the ApplianceThe NeoTherm is for indoor installations only.

Figure 2. Location of Components, Sizes 80–105.

The appliance should be located to provideclearances on all sides for maintenance and inspection.It should not be located in an area where leakage of anyconnections will result in damage to the area adjacent tothe appliance or to lower floors of the structure.

When such a location is not available, it isrecommended that a suitable drain pan, adequatelydrained, be installed under the appliance.

The appliance is design certified by CSA-International for installation on combustible flooring; inbasements; in closets, utility rooms or alcoves.

Figure 1. Contents of Shipping Package.

Page 5: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 5

Figure 4. Location of Components, Size 285.

Figure 3. Location of Components, Sizes 150–210.

Page 6: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 6

Figure 6. Location of Components, Size 500.

Figure 5. Location of Components, Size 399.

Page 7: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 7

Figure 7. Dimensional Drawing.

A B C D E F G H J K ConnectionsSIZE in in in in in in in in in in NPT Size (in)

water gas

80 19-3/8 18-3/8 8 11-1/4 12 21-1/8 14 13-5/8 9-3/8 8-7/8 1 1/2

105 19-3/8 18-1/8 5-7/8 10-5/8 11-5/8 20-7/8 14-1/8 13-3/8 7-7/8 8-7/8 1 1/2

150 19-3/8 18-1/8 3 10-3/4 7-1/2 19-3/8 14-1/8 13-1/4 5-1/8 8-7/8 1 1/2

210 26-5/8 18-1/8 3-1/8 17-3/4 7-5/8 19-3/8 14-1/8 17-3/4 5-1/8 8-7/8 1 1/2

285 26-5/8 18-1/2 5-3/4 14 17-3/4 19 14 20-1/8 5-1/8 8-3/4 1-1/4 3/4

399 31-1/2 18-5/8 4-1/8 14-5/8 21-3/8 19 19-1/4 25 5-1/8 8-3/4 1-1/4 3/4

500 37-3/4 18-3/4 4-1/8 14-7/8 27-5/8 19 2-3/4 29-3/4 5-1/8 8-3/4 1-1/2 1

A B C D E F G H J K ConnectionsSIZE cm cm cm cm cm cm cm cm cm cm NPT Size (in)

water gas

80 49 47 20 29 30 54 36 35 24 23 1 1/2

105 49 46 15 27 30 53 36 34 20 23 1 1/2

150 49 46 8 27 19 49 36 34 13 23 1 1/2

210 68 46 8 45 19 49 36 45 13 23 1 1/2

285 68 47 15 36 45 48 36 51 13 22 1-1/4 3/4

399 80 47 10 37 54 48 49 64 13 22 1-1/4 3/4

500 96 48 10 38 70 48 7 76 13 22 1-1/2 1

Page 8: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 8

SECTION 2.Venting and Combustion Air

2.1 Combustion AirNeoTherm boilers and water heaters must have

provisions for combustion and ventilation air inaccordance with the applicable requirements forCombustion Air Supply and Ventilation in the NationalFuel Gas Code, ANSI Z223 1; or in Canada, the NaturalGas and Propane Installation Code, CSA B149.1. Allapplicable provisions of local building codes must alsobe adhered to.

A NeoTherm unit can take combustion air fromthe space in which it is installed, or the combustionair can be ducted directly to the unit. Ventilation airmust be provided in either case.

2.1.1 Combustion Air From RoomIn the United States, the most common

requirements specify that the space shall communicatewith the outdoors in accordance with method 1 or 2,which follow. Where ducts are used, they shall be of thesame cross-sectional area as the free area of theopenings to which they connect.

Method 1: Two permanent openings, onecommencing within 12" (300mm) of the top and onecommencing within 12" (300mm) of the bottom, of theenclosure shall be provided. The openings shallcommunicate directly, or by ducts, with the outdoors orspaces that freely communicate with the outdoors.When directly communicating with the outdoors, orwhen communicating to the outdoors through verticalducts, each opening shall have a minimum free area of 1square inch per 4000 Btu/hr (550 square mm/kW) oftotal input rating of all equipment in the enclosure.When communicating to the outdoors throughhorizontal ducts, each opening shall have a minimumfree area of not less than 1 square inch per 2000 Btu/hr(1100 square mm/kW) of total input rating of allequipment in the enclosure.

Method 2: One permanent opening, commencingwithin 12" (300mm) of the top of the enclosure, shall bepermitted. The opening shall directly communicate withthe outdoors or shall communicate through a vertical orhorizontal duct to the outdoors or spaces that directlycommunicate with the outdoors and shall have aminimum free area of 1 square inch per 3000 Btu/hr(734 square mm/kW) of the total input rating of allequipment located in the enclosure. This opening mustnot be less than the sum of the areas of all ventconnectors in the confined space.

Other methods of introducing combustion andventilation air are acceptable, providing they conform tothe requirements in the applicable codes listed above.

In Canada, consult local building and safety codes or,in absence of such requirements, follow CAN/CGA B149.

NeoTherm Boilers must never be installed oncarpeting. The location for the appliance should bechosen with regard to the vent pipe lengths and externalplumbing and on a level surface. The unit shall beinstalled such that the gas ignition system componentsare protected from water (dripping, spraying, rain, etc.)during operation and service (circulator replacement,control replacement, etc.). When vented vertically, theNeoTherm must be located as close as practical to thevertical section of the vent. If the vent terminal and/orcombustion air terminal terminate through a wall, andthere is potential for snow accumulation in the localarea, both terminals should be installed at an appropriatelevel above grade or the maximum expected snow line.

The dimensions and requirements that are shownin Table 1 should be met when choosing the locationsfor the appliance.

1.8 Locating Appliance for Correct VentDistance from Outside Wall orRoof TerminationThe forced draft combustion air blower in the

appliance has sufficient power to vent properly whenthe guidelines in Table 2 are followed.NOTE: When located on the same wall, the NeoThermcombustion air intake terminal must be installed aminimum of 12" (30cm) below the exhaust vent terminal.

For concentric vent terminal kit (optional), followinstallation instructions included with the kit.

REQUIRED CLEARANCE FROM SUGGESTED SERVICE

APPLIANCECOMBUSTIBLE MATERIAL ACCESS CLEARANCE

SURFACE IN. CM IN. CM

Left Side 1 2.5 1 2.5

Right Side 1 2.5 12 31

Top 1 2.5 24 61

Back 1 2.5 6 15

Closet, Front 1 2.5 6 15

Alcove, Front 1 2.5 24 61

Vent 0 0 – –

Table 1. Clearances.

SIZE MAX EQUIVALENT* VENT LENGTH PVC/CPVC(EACH INTAKE AND EACH EXHAUST)

2" DIA / 5.1CM 3" DIA / 7/6CM 4" DIA / 10.2CM

80 40 ft 6.1M 100 ft 30.5M n/a

105 40 ft 6.1M 100 ft 30.5M n/a

150 n/a 100 ft 30.5M n/a

210 n/a 100 ft 30.5M n/a

285 n/a 20 ft 6.1M 100 ft 30.5M

399 n/a n/a 100 ft 30.5M

500N n/a n/a 100 ft 30.5M

500P n/a n/a 80 ft 24.4M

* Each 90° fitting = 5 equivalent feet 1.5M

Table 2. Vent / Air Pipe Sizes.

Page 9: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 9

2.1.2 Intake Combustion AirThe combustion air can be taken through the wall, or

through the roof. When taken from the wall, it must betaken from out-of-doors by means of the LAARShorizontal wall terminal, shown in Table 3. See Table 2 toselect the appropriate diameter air pipe. When taken fromthe roof, a field-supplied rain cap or an elbow arrangementmust be used to prevent entry of rain water (see Figure 8).

Use ABS, PVC, CPVC or galvanized pipe for thecombustion air intake (see Table 4), sized per Section 1.8.Route the intake to the heater as directly as possible. Sealall joints. Provide adequate hangers. The unit must notsupport the weight of the combustion air intake pipe. Max-imum linear pipe length allowed is shown in Table 2.Subtract 5 allowable linear ft. (1.5m) for every elbow used.

The connection for the intake air pipe is at the top ofthe unit. To aid in boiler service, a removable adapter isrecommended when making the connection to the boiler.

In addition to air needed for combustion, air shallalso be supplied for ventilation, including air required forcomfort and proper working conditions for personnel.

2.2 Venting

WARNINGFailure to use CPVC or stainless steel venting for thefirst 20" (285-500) / 30" (80-210) of vent material orfor any part of the venting that is installed inside acloset may lead to property damage, personal injuryor death. The proper length of this material issupplied with boiler.

WARNINGFailure to use the appropriate vent material,installation techniques, glues/sealants could lead tovent failure causing property damage, personal injuryor death.

WARNINGAll venting must be installed according to this manualand any other applicable local codes, including butnot limited to, ANSI Z223.1/NFPA 54, CSA B149.1,CSAB149.2 and ULC-S636. Failure to follow thismanual and applicable codes may lead to propertydamage, severe injury, or death.

The flue temperature of the NeoTherm changesdramatically with changes in operating watertemperature. Therefore, it is necessary to assess theapplication of the boiler to determine the requiredcertified vent class. If the NeoTherm is installed inan application where the ambient temperature iselevated, and/or installed in a closet, CPVC or stain-less steel material is required. If the system temp-eratures are unknown at the time of installation,class IIB or higher venting material is recommended.

The NeoTherm is a Category IV appliance andmay be installed with PVC and CPVC that complieswith ANSI/ASTM D1785 F441, or a stainless steel

venting system that complies with UL 1738 Standard(see Table 5).

Installations in Canada require the use ofventing material certified to ULCS636. All Gas ventsconnected to the NeoTherm, plastic, stainless steel orotherwise must be certified to this ULC standard.Appropriate selection of vent material is veryimportant for proper performance and safeoperation of the NeoTherm. Vent material MUST beselected based upon operating conditions such asoutlet water temperature and installed location.

The flue temperature of the NeoTherm changesdramatically with changes in operating watertemperature. Therefore, it is necessary to assess theapplication of the boiler to determine the requiredcertified vent class. If the NeoTherm is installed inan application where the outlet water temperatureexceeds 145°F, and/or installed in a closet, class IIBor higher vent material is required. If the systemtemperatures are unknown at the time ofinstallation, class IIB or higher venting material isrecommended.

In Canada all venting used must meet thefollowing requirements:1. ULC-S636 certified and marked2. The first 3 feet of venting must be accessible for

visual inspection.3. All components used in the vent system must be

from a certified manufacturer.4 . Vent system components must not be mixed

with alternate manufacturers certifiedcomponents and/or unlisted components.

5 . The venting must be installed according to thevent manufacturers installation instructions.

Figure 8. Combustion Air and Vent Through Roof.

Page 10: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 10

The unit’s vent can terminate through the roof, orthrough an outside wall.

Venting should be connected to the CPVC sectionincluded with the boiler. The included section of CPVCmust be used to make the connection to the boiler. It maybe broken by CPVC fittings if necessary, but never reducedin total length. See Table 2 to select the appropriate ventpipe diameter. Vent pipe must pitch upward, toward thevent terminal, so that condensate will run back to theNeoTherm to drain. Route vent pipe to the heater asdirectly as possible. Seal all joints and provide adequatehangers as required in the venting system manufacturer’sInstallation Instructions. Horizontal portions of the ventingsystem must be supported to prevent sagging and may not haveany low sections that could trap condensate. The unit must notsupport the weight of the vent pipe. Horizontal runs must slopeupwards not less than ¼ inch per foot from the unit to the ventterminal. Up to 100 equivalent feet (30m) of pipe can be used.Subtract 5 feet (1.5m) for each elbow used.

IMPORTANT NOTE ABOUT COMMON VENTING: Asingle vent that is shared by multiple NeoTherm unitsMUST be engineered by a competent ventingspecialist, and involves the selection of draft inducingequipment, hardware and controls to properly balanceflue gas pressures. Do not common vent NeoThermunits unless the vent system meets thisrequirement. NeoTherm units are never permittedto share a vent with Category I appliances.

A condensate drain is built into the NeoTherm. Afloat switch monitors the condensate trap, and will openif the condensate level gets too high. This will preventthe NeoTherm from firing if there is a blockage oroverflow.

Connect a 3/4" PVC pipe between the drainconnection and a floor drain (or condensate pump if afloor drain is not accessible).

The condensate drain must be installed so as toprevent accumulation of condensate. When acondensate pump is not used, the tubing mustcontinuously slope downward toward the drain with nospiraling.

Consult local codes for disposal method.

CautionCondensate is mildly acidic (pH.....5), and may harmsome floor drains and/or pipes, particularly those thatare metal. Ensure that the drain, drainpipe, andanything that will come in contact with thecondensate can withstand the acidity, or neutralizethe condensate before disposal. Damage caused byfailure to install a neutralizer kit or to adequatelytreat condensate will not be the manufacturer’sresponsibility.

2.3 Locating Vent & Combustion AirTerminals2.3.1 Side Wall Vent TerminalThe appropriate Laars side wall vent terminal must

be used, and is listed in this installation and operationmanual. The terminal must be located in accordancewith ANSI Z223.1/NFPA 54 and applicable local codes.In Canada, the installation must be in accordance withCSA B149.1 or .2 and local applicable codes. Considerthe following when installing the terminal:1. Figure 9 shows the requirements for mechanical

vent terminal clearances for the U.S. and Canada.2. Vent terminals for condensing appliances or

appliances with condensing vents are notpermitted to terminate above a public walkway, orover an area where condensate or vapor could

HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS

2" PVC 3" PVC 4" PVCSIZE Standard Concentric Standard Concentric Standard

CA006000 CA005900 239-44069-01

80 included optional optional optional n/a

105 included optional optional optional n/a

150 n/a n/a included optional n/a

210 n/a n/a included optional n/a

285 n/a n/a optional optional included

399 n/a n/a n/a n/a included

500 n/a n/a n/a n/a included

Concentric vent terminal = 10 ft. pipe length.

Table 3. PVC Vent Terminal Kits.

INSTALLATION STANDARDS

MATERIAL UNITED STATES CANADA

Stainless Steel UL 1738 All venting must be ULC-S636 certified for use asPVC, sch 40 ANSI/ASTM D178 venting material. The venting material must be chosen

CPVC, sch 40 ANSI/ASTM F441 based upon the intended application of the boiler.

Table 5. Required Exhaust Vent Material.

INSTALLATION STANDARDS

MATERIAL UNITED STATES CANADA

ABS ANSI/ASTM D1527 All venting must be ULC-S636 certified for use asPVC, sch 40 ANSI/ASTM D1785 or D2665 venting material. The venting material must be chosen

CPVC, sch 40 ANSI/ASTM F441 based upon the intended application of the boiler.

Table 4. Required Combustion Air Vent Material.

Page 11: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 11

*When vent terminal is less than 10 feet (3m) horizontallyfrom a forced air inlet, the terminal must be at least 3 feet(0.9m) above the air inlet.

Figure 9. Combustion Air and Vent Through Side Wall.

U.S. Installations (see note 1) Canadian Installations (see note 2)

A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)deck, or balcony See note 6 See note 6

B= Clearance to window or door that may be Direct vent only: 12 inches (30cm); 36 inches (91 cm)opened Other than Direct vent: 4 ft (1.2m) below or to

side of opening; 1 ft (30cm) above opening

C= Clearance to permanently closed window See note 4 See note 5

D= Vertical clearance to ventilated soffit locatedabove the terminal within a horizontal See note 4 See note 5distance of 2 feet (61cm) from the centerline of the terminal

E= Clearance to unventilated soffit See note 4 See note 5

F= Clearance to outside corner See note 4 See note 5

G= Clearance to inside corner See note 4 See note 5

H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet aboveextended above meter/regulator assembly See note 4 the meter/regulator assembly

I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)

J= Clearance to nonmechanical air supply Direct vent only: 12 inches (30cm);inlet to building or the combustion air inlet Other than Direct vent: 4 ft (1.2m) below or to 36 inches (91 cm)to any other appliance side of opening; 1 ft (30cm) above opening

K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)horizontally

L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in this locationdriveway located on public property for category IV appliances. for category IV appliances.

M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)or balcony

Notes:1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.

2. In accordance with the current CAN/CGA-B149 Installation Codes.

3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of thegas supplier.

5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gassupplier.

6. IMPORTANT: terminal must be placed such that it remains a minimum 12" above expected snow line. Local codes may have morespecific requirements, and must be consulted.

Page 12: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 12

create a nuisance or hazard.3. Locate the vent terminal so that vent gases can-not

be drawn into air conditioning system inlets.4. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows, gravityinlets or other openings. Whenever possible, avoidlocations under windows or near doors.

5. Locate the vent terminal so that it cannot beblocked by snow. The installer may determinethat a vent terminal must be higher than theminimum shown in codes, depending upon localconditions.

6. Locate the terminal so the vent exhaust does notsettle on building surfaces or other nearby objects.Vent products may damage surfaces or objects.

7. If the boiler or water heater uses ductedcombustion air from an intake terminal located onthe same wall, locate the vent terminal at least 1foot (0.3m) above the combustion air terminal.

2.3.2 Side Wall Combustion Air TerminalThe LAARS side wall combustion air terminal, or

concentric terminal (see Table 3), must be used whenthe heater takes air from a side wall. Consider thefollowing when installing the terminal:1. Do not locate the air inlet terminal near a source of

corrosive chemical fumes (e.g., cleaning fluid,chlorine compounds, etc.)

2. Locate the terminal so that it will not be subject todamage by accident or vandalism. It must be atleast 7 feet (2.1m) above a public walkway.

3. Locate the combustion air terminal so that itcannot be blocked by snow. The National Fuel GasCode requires that it be at least 12 inches (30cm)above grade, but the installer may determine itshould be higher, depending upon local conditions.

4. If the NeoTherm is side-wall vented to the samewall, locate the vent terminal at least 1 foot (0.3m)above the combustion air terminal.

5. For concentric vent, follow instructionsincluded with vent kit.

6. Multiple vent kits should be installed where thehorizontal distance between outlet group and inletgroup is 18" minimum.

7. Vent outlet should be 12" above and/or 12"horizontal to inlet pipe, but outlet should never bemounted below the inlet centerline at anyhorizontal distance.

2.3.3 Vertical Vent TerminalWhen the unit is vented through the roof, the vent

must extend at least 3 feet (0.9m) above the point atwhich it penetrates the roof. It must extend at least 2feet (0.6m) higher than any portion of a building withina horizontal distance of 10 feet (3.0m), and high enoughabove the roof line to prevent blockage from snow.When the combustion air is taken from the roof, thecombustion air must terminate at least 12" (30cm)below the vent terminal (see Figure 8).

2.3.4 Vertical Combustion Air TerminalWhen combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must beused to prevent entry of rain water (see Figure 8). Theopening on the end of the terminal must be at least 12"(30cm) above the point at which it penetrates the roof,and high enough above the roof line to prevent blockagefrom snow. When the vent terminates on the roof, thecombustion air must terminate at least 12" (30cm)below the vent terminal.

2.3.5 Installations in the Commonwealth ofMassachusetts

In Massachusetts the following items are required ifthe side-wall exhaust vent termination is less than seven (7)feet above finished grade in the area of the venting,including but not limited to decks and porches. FromMassachusetts Rules and regulations 248 CMR 5.081. Installation of Carbon Monoxide Detectors

At the time of installation of the side wall ventedgas fueled appliance, the installing plumber orgasfitter shall observe that a hard-wired carbonmonoxide detector with an alarm battery back-up isinstalled on the floor level where the gas applianceis to be installed. In addition, the installingplumber or gasfitter shall observe that a batteryoperated or hard-wired carbon monoxide detectorwith an alarm is installed on each additional levelof the dwelling, building or structure served by theside-wall horizontally vented gas fueled equip-ment. It shall be the responsibility of the propertyowner to secure the services of qualified licensedprofessionals for installation of hard-wired carbonmonoxide detectors.a. In the event that the side-wall horizontallyvented gas fueled equipment is installed in a crawlspace or an attic, the hard-wired carbon monoxidewith alarm and battery back-up may be installed onthe next adjacent floor level.b. In the event that the requirements of the subdivi-sion cannot be met at the time of completion ofinstallation, the owner shall have a period of thirty(30) days to comply with the above requirements,provided, however, that during said thirty (30) dayperiod, a battery operated carbon monoxidedetector with an alarm be installed.

2. Approved Carbon Monoxide DetectorsEach carbon monoxide detector shall comply withNFPA 720 and be ANSI/UL 2034 listed and IAScertified.

3. SignageA metal or plastic identification plate shall be per-manently mounted to the exterior of the building ata minimum height of eight (8) feet above gradedirectly in line with the exhaust vent terminal forhorizontally vented gas fueled heating appliance or

Page 13: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 13

above, return doors, windows, exhaust fans,fireplace dampers and any other gas burningappliance to their previous conditions of use.

7. Any improper operation of the common ventingsystem should be corrected so that the installationconforms to the National Fuel Gas Code, ANSIZ223.1/NFPA 54 and/or CSA B149.1, InstallationCodes. When resizing any portion of the commonventing system, the common venting system shouldbe resized to approach the minimum size as deter-mined using the appropriate tables and guidelines inthe National Fuel Gas Code, ANSI Z223.1 NFPA 54and/or CSA B149.1, Installation Codes.

SECTION 3.Gas Supply and Piping

3.1 Gas Supply and PipingGas piping should be supported by suitable

hangers or floor stands, not the appliance.Review the following instructions before

proceeding with the installation.1. Verify that the appliance is fitted for the proper type of

equipment. The sign shall read, in print no lessthan one-half (1/2) inch in size: "GAS VENTDIRECTLY BELOW, KEEP CLEAR OF ALLOBSTRUCTIONS".

4. InspectionThe state or local gas inspector of the side-wallhorizontally vented gas fueled appliance shall notapprove the installation unless, upon inspection,the inspector observes carbon monoxide detectorsand signage installed in accordance with theprovisions of 248 CMR 5.08(2)(a) 1-4.

2.4 Common Vent TestNOTE: This section does not describe a method forcommon venting NeoTherm units. It describes what mustbe done when a unit is removed from a common ventsystem. NeoTherm units require special vent systems andfans for common vent. Contact the factory if you havequestions about common venting NeoTherm units.

When an existing boiler is removed from acommon venting system, the common venting system islikely to be too large for proper venting of theappliances remaining connected to it.

At the time of removal of an existing boiler, thefollowing steps shall be followed with each applianceremaining connected to the common venting systemplaced in operation, while the other appliancesremaining connected to the common venting system arenot in operation.1. Seal any unused openings in the common venting

system.2. Visually inspect the venting system for proper size

and horizontal pitch and determine there is noblockage or restriction, leakage, corrosion andother deficiencies which could cause an unsafecondition.

3. Insofar as it is practical, close all building doorsand windows and all doors between the space inwhich the appliances remaining connected to thecommon venting system are located and otherspaces of the building. Turn on clothes dryers andany appliance not connected to the commonventing system. Turn on any exhaust fans, such asrange hoods and bathroom exhausts, so they willoperate at maximum speed. Do not operate asummer exhaust fan. Close fireplace dampers.

4. Place in operation the appliance being inspected.Follow the lighting instructions. Adjust thermostatso the appliance will operate continuously.

5. Test for spillage at the draft hood relief openingafter 5 minutes of main burner operation. Use theflame of a match or candle, or smoke from acigarette, cigar or pipe.

6. After it has been determined that each applianceremaining connected to the common ventingsystem properly vents when tested as outlined

EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS

NOMINAL PIPE SIZE

FITTING 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"LINEAR FEET

90° ELBOW 3.6 4.4 5.2 6.6 7.4 8.5

TEE 4.2 5.3 6.6 8.7 9.9 12

Table 6B.

SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS

NOMINAL PIPE SIZE @ 0.30" W.C. PRESSURE DROP

LENGTH 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"FT CUBIC FEET OF GAS PER HOUR

20 92 190 350 730 1100 2100

40 130 245 500 760 1450

60 105 195 400 610 1150

80 90 170 350 530 990

100 150 305 460 870

Table 6C.

NEOTHERMNATURAL GAS

REQUIRED

CU FTSIZE / HR.

80 80

105 105

150 150

210 210

285 285

399 399

500 500

Table 6A.

TO SIZE PIPING:Measure linear distance from meter outlet to lastboiler. Add total input of all boilers and divide by1000 to obtain cu ft / hr required. Add totalequivalent length of fittings used according toTable 6B. Align total length (pipe and fittings) onleft side column of Table 6C with highest cubicfeet of gas required.

Notes:Consult and confirm with Applicable Fuel GasCode before beginning work. Verify gas inletpressure is between 13 and 4 in W.C. beforestarting boiler.

Page 14: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 14

gas by checking the rating plate. NeoTherm willfunction properly without the use of high altitudemodification at elevations up to 10,000 feet (3050 m).

2. The maximum inlet gas pressure must not exceed13" W.C. (3.2kPa). The minimum inlet gaspressure is 4" W.C. (1.0kPa).

3. Refer to Tables 6A, 6B, 6C and 6D to size piping.4. Run gas supply line in accordance with all

applicable codes.5. Locate and install manual shutoff valves in

accordance with state and local requirements.6. A sediment trap must be provided upstream of the

gas controls.7. All threaded joints should be coated with piping

compound resistant to action of liquefiedpetroleum gas.

8. The appliance and its individual shutoff valvemust be disconnected from the gas supply pipingduring any pressure testing of that system at testpressures in excess of 1/2 PSIG (3.45kPa).

9. The unit must be isolated from the gas supplysystem by closing its individual manual shutoffvalve during any pressure testing of the gas supplypiping system at test pressures equal to or less than1/2 PSIG (3.45kPa).

10. The appliance and its gas connection must be leaktested before placing it in operation.

11. Purge all air from gas lines.

WARNING:Open flame can cause gas to ignite and result inproperty damage, severe injury, or loss of life.

NOTE: The NeoTherm appliance and all other gasappliances sharing the gas supply line must be firing atmaximum capacity to properly measure the inlet supplypressure. The pressure can be measured at the supplypressure port on the gas valve. Low gas pressure couldbe an indication of an undersized gas meter, undersizedgas supply lines and/or an obstructed gas supply line.Some NeoTherm units are equipped with low and highgas pressure switches that are integrally vent limited.These types of devices do not require venting toatmosphere.

SECTION 4.Water Connections4.1 Heating System Piping: Hot Supply

ConnectionsNOTE: This appliance must be installed in a closedpressure system with a minimum of 12 psi (82.7kPa)static pressure at the boiler.

Hot water piping should be supported by suitablehangers or floor stands. Do not support piping with thisappliance. Due to expansion and contraction of copperpipe, consideration should be given to the type ofhangers used. Rigid hangers may transmit noise throughthe system resulting from the piping sliding in thehangers. It is recommended that padding be used whenrigid hangers are installed. Maintain 1" (2.5cm)clearance to combustibles for hot water pipes.

Pipe the discharge of the relief valve (full size) toa drain or in a manner to prevent injury in the event ofpressure relief. Install an air purger, an air vent, adiaphragm-type expansion tank, and a hydronic flowcheck in the system supply loop. Minimum fill pressuremust be 12psig (82.7kPa). Install shutoff valves whererequired by code.

Suggested piping diagrams are shown in Figures10 through 16. These diagrams are meant only as aguide. Components required by local codes must beproperly installed. The NeoTherm boiler’s efficiencyis higher with lower return water temperatures.Therefore, to get the most of low return temperaturewith multiple boilers, pipe as shown in Figure 13.

All NeoTherm models are built standard with apump mounted inside the jacket. Sizes 399 and 500 canbe ordered without the pump, as an option. If the boileris a size 399 or 500, it is important to know whetherthere is an internal pump in the unit or not.

NeoTherm boilers that are pump-mounted MUSTbe piped in a primary-secondary fashion (using eitherpiping or a hydraulic separator) such that the pump thatis mounted on the boiler ONLY serves the boiler.

For best results, the NeoTherm boiler should belocated within 15 feet (4.6m) of the supply and returnheader (or the hydraulic separator). The pump is sizedfor a maximum of 30 feet (9.1m) of piping and theheadloss of the boiler only (see Table 7).

If a pump-mounted boiler must be installed withlonger piping runs, then larger diameter tubing may beused. Consult the Applications Engineering Departmentat the factory for assistance.

Models 399 and 500 can be ordered without amounted pump. If ordered without the pump, a field-supplied pump should be chosen to supply the boileronly. Primary/secondary piping methods should still beused, to ensure proper water flow through the unit.

4.2 Cold Water Make-Up

1. Connect the cold water supply to the inlet

SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITYUNDILUTED PROPANE

NOMINAL PIPE SIZE @ 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP

SIZE 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR

20 200 418 787 1616 2422 4664

40 137 287 541 1111 1664 3205

60 110 231 434 892 1337 2574

80 94 197 372 763 1144 2203

100 84 175 330 677 1014 1952NOTES: 1. Follow all local and national LP gas codes for line sizing andequipment requirements. 2. Verify that inlet gas pressure remains between4 and 13 inches of water column before and during operation.Source: ANSI Z223.1-80 National Fuel Gas Code.

Table 6D.

Page 15: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 15

connection of an automatic fill valve.2. Install a suitable back flow preventer between the

automatic fill valve and the cold water supply.3. Install shut off valves where required.NOTE: The boiler, when used in connection with arefrigeration system, must be installed so the chilledmedium is piped in parallel with the boiler withappropriate valves to prevent the chilled medium fromentering the boiler.

The boiler piping system of a hot water heatingboiler connected to heating coils located in air handling

appliances where they may be exposed to refrigeratedair circulation must be equipped with flow controlvalves or other automatic means to prevent gravitycirculation of the boiler water during the cooling cycle.

A boiler installed above radiation level, or asrequired by the authority having jurisdiction, must beprovided with a low water cutoff device either as a partof the boiler or at the time of boiler installation.

4.3 Freeze ProtectionNeoTherm units are certified for indoor use only,

and are not design-certified for placement outdoors.

Figure 10. Hydronic Piping — Single Boiler (zoning with circulators).

Page 16: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 16

Proper precautions for freeze protection arerecommended for boiler installations in areas where thedanger of freezing exists.

Power outage, interruption of gas supply, failureof system components, activation of safety devices, etc.,may prevent a boiler from firing. Any time a boiler issubjected to freezing conditions, and the boiler is notable to fire, and/or the water is not able to circulate,there is a risk of freezing in the boiler or in the pipesin the system. When water freezes, it expands whichmay result in bursting of pipes, or damage to the boiler,

which could result in leaking or flooding conditions.Do not use automotive anti-freeze. Laars

recommends a mixture of minimum 20% and maximum35% of inhibited HVAC glycol solution, which containsan anti-foaming agent, as the preferred method of freezeprotection for NeoTherm boilers. Percentage of glycolused in the NeoTherm boiler must not exceed 35%.Typically, this mixture will serve as burst protection fortemperatures down to approximately –5°F (-15°C).IMPORTANT NOTES: Different glycol products mayprovide varying degrees of protection. Glycol products

Figure 11. Hydronic Piping — Single Boiler with Indirect DWH Tank (zoning with circulators)..

Page 17: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 17

Figure 12. Hydronic Piping — Single Boiler, Low Temp Radiant Space Heating using Low Loss Header and Zone Valves.

must be maintained properly in a heating system, or theymay become ineffective. Consult the glycol specifications,or the glycol manufacturer, for information about specificproducts, maintenance of solutions, and set up accordingto your particular conditions.

4.4 Recognized Chemicals The following manufacturers offer glycols,

inhibitors, and anti foamants that are suitable for use inthe NeoTherm. Please refer to the manufacturersinstructions for proper selection and application.

1. Sentinel Performance Solutions Group2. Hercules Chemical Company3. Dow Chemical Company

Page 18: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 18

Figure 13. Hydronic Piping — Multiple Boilers (zoning with circulators).

Temperature Rise in °F20°F 25°F 30°F

Flow H/L Flow H/L Flow H/LSize gpm feet gpm feet gpm feet 80 7.6 14.9 6.1 10.1 5.1 7.1 105 10.0 23.1 8.0 17.0 6.7 12.4 150 14.3 28.5 11.4 19.0 9.5 13.6 210 20.0 24.1 16.0 16.7 13.4 11.6

Temperature Rise in °C11°C 14°C 17°C

Flow H/L Flow H/L Flow H/LSize lpm m lpm m lpm m 80 7.6 14.9 6.1 10.1 5.1 7.1 105 10.0 23.1 8.0 17.0 6.7 12.4 150 14.3 28.5 11.4 19.0 9.5 13.6 210 20.0 24.1 16.0 16.7 13.4 11.6

Table 8. Water Flow Requirements, Sizes 80-210.

BOILER HEAD (FT) AT TEMP RISE PUMPSIZE 20°F 25°F 30°F MODEL INCL.

80 14.9 10.1 7.1 008

105 23.1 17 12.4 0011

150 28.5 19 13.6 0011

210 24.1 16.7 11.6 0013

285 25.5 17.5 14 0013

399 28 20 14.5 1400-45

500 24 18 12 1400-45Pre-mounted pumps are sized for:

a) 25-30°F Temp Rise with;b) 30 feet external boiler loop piping, and;c) 6 elbows (90°).

Table 7. NeoTherm Pump Data.

Page 19: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 19

Figure 14. Hydronic Piping — Multiple Boilers with Indirect DWH Tank (zoning with circulators).

Temperature Rise in °F20°F 25°F 30°F 35°F 40°F

Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L

Size gpm feet gpm feet gpm feet gpm feet gpm feet

285 27 25.5 22 17.5 18 14 15 10.5 13 8

399 38 28 31 20 25 14.5 22 11 19 9

500 47 24 38 16 32 12 27 9 24 8

Temperature Rise in °C11°C 14°C 17°C 19°C 22°C

Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L

Size lpm m lpm m lpm m lpm m lpm m

285 102 7.8 81 5.3 68 4.3 58 3.2 51 2.4

399 145 8.5 116 6.1 96 4.4 83 3.4 72 2.7

500 179 7.3 143 4.9 119 3.7 102 2.7 89 2.4

Table 9. Water Flow Requirements, Sizes 285-500.

Page 20: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 20

Figure 15. Hydronic Piping — Multiple Boilers, Reverse Return, Multi-Temp Zones (zoning with circulators).

Page 21: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 21

Figure 16. Hydronic Piping — Heating zones with indirect DWH tank piped with zone pumps (indirect directly off boiler).Boiler pump must shut down during DHW.

Page 22: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 22

SECTION 5.Electrical Connections

WARNINGThe appliance must be electrically grounded inaccordance with the requirements of the authorityhaving jurisdiction or, in the absence of suchrequirements, with the latest edition of the NationalElectrical Code, ANSI/NFPA 70, in the U.S. and withlatest edition of CSA C22.1 Canadian Electrical Code,Part 1, in Canada. Do not rely on the gas or water pipingto ground the metal parts of the boiler. Plastic pipe ordielectric unions may isolate the boiler electrically.Service and maintenance personnel, who work on oraround the boiler, may be standing on wet floors andcould be electrocuted by an ungrounded boiler.Electrocution can result in severe injury or death.

Single pole switches, including those of safetycontrols and protective devices must not be wired in agrounded line.

All electrical connections are made on the terminalblocks that are located inside the control panel.NOTE: All internal electrical components have beenprewired. No attempt should be made to connectelectrical wires to any other location except the terminalblocks.

Wiring connections are shown in Figure 21.

5.1 Main PowerConnect a minimum 15A fused, 120-volt supply to

the main power switch (hot leg is connected directly toswitch). Neutral leg is connected directly to the whitewire. Ground wire can be connected to the groundinglug in the box.

5.2 Control FeaturesThe NeoTherm boiler control is a versatile control

that interfaces with a user display. The user displayallows access to many features of the control for setup,diagnostics and operation. There are three menustructures to choose from, USERUSERUSERUSERUSER mode, SETUPSETUPSETUPSETUPSETUP mode, and

MENU ITEM

Outlet water temperature Displays the current outlet watertemperature and allows the setpointto be adjusted.

Inlet water temperature Displays the current inlet watertemperature

Delta T Displays the current Temperaturerise across the heat exchanger

DHW water temperature Displays the current DHWtemperature and allows the setpointto be adjusted

Stack Temperature Displays the current stacktemperature

Outdoor Temperature Displays the current Outdoor airtemperature

Firing Rate Displays an indicator of the currentfiring rate based upon fan RPM. Theactual firing rate may vary.

Table 10. User Mode Menu Structure.

DIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTIC mode. Each mode will give the user access todifferent types of information. The menus are accessedby using the buttons located on the display.

5.2.1 User ModeUSERUSERUSERUSERUSER mode is the home screen shown on the

control. To navigate from item to item within USERUSERUSERUSERUSERmode press the NEXT button. If a menu that is useradjustable is selected, such as outlet or DHW the UP orDOWN arrows can be used to adjust the temperaturesetpoint. Once the correct value is selected the DONEbutton can be pressed to select the adjusted values. TheUSERUSERUSERUSERUSER mode menu structure and information that isavailable is shown in Table 10.

5.2.1.1 Temperature Control PointAdjustment

To adjust the temperature control point, confirmthe display is in USERUSERUSERUSERUSER mode and the outlet temperature isbeing displayed. Press the UP or DOWN arrow to adjustthe control point temperature. The control pointtemperature is measured at the outlet of the heatexchanger. When making adjustments make sure thecontrol point is set far enough away from the high limitto keep the temperature rise of the heat exchanger fromcausing nuisance high limit tripping problems.

5.2.1.2 Domestic Hot Water Control PointAdjustment

To adjust the DHW temperature control point,confirm the display is in USERUSERUSERUSERUSER mode. Scroll through themenu structure using the NEXT button until the currentDHW temperature is being displayed. Use the UP orDOWN arrow to adjust the setpoint to the desired value.Press the DONE button when complete.

5.2.2 Setup ModeSETUPSETUPSETUPSETUPSETUP mode is accessed by holding the UP and

DOWN arrow keys simultaneously for 3 seconds. SETUPSETUPSETUPSETUPSETUPmode allows the parameters listed in Table11 to beadjusted by using the NEXT button to select theparameter to be adjusted and then the UP or DOWN

Figure 17. Control Buttons on User Interface.

Page 23: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 23

arrow keys to make the adjustment. When theadjustment is complete press the DONE (or NEXT) buttonto move to next menu item.

5.2.2.1 Adjusting the TemperatureDisplay Units in °F or °C

Confirm the display is in SETUPSETUPSETUPSETUPSETUP mode. Scroll to theF/CF/CF/CF/CF/C menu. Press the UP or DOWN arrow to adjustbetween Fahrenheit and Celsius. Press the DONE keywhen complete.

5.2.2.2 Adjusting the Outdoor ResetOn or Off

Confirm the display is in SETUPSETUPSETUPSETUPSETUP mode. Scroll to theLBTHODLODLBTHODLODLBTHODLODLBTHODLODLBTHODLOD menu using the NEXT button. Use the UP orDOWN arrows to select on or off. When outdoor reset isturned on, three new menus will be added to setup mode.

5.2.2.3 Adjusting Low BoilerTemperature Setpoint

Confirm the display is in SETUPSETUPSETUPSETUPSETUP mode. Scroll to theLBTLBTLBTLBTLBT menu. Use the UP or DOWN arrows to scroll to theminimum water temperature desired during outdoor reset.

5.2.2.4 Adjusting High OutdoorTemperature Setpoint

Confirm the display is in SETUPSETUPSETUPSETUPSETUP mode. Scroll to theHODHODHODHODHOD menu. Use the UP or DOWN arrows to scroll to themaximum outdoor temperature the reset curve will useto equate to the minimum water temperature.

5.2.2.5 Adjusting Low OutdoorTemperature Setpoint

Confirm the display is in SETUPSETUPSETUPSETUPSETUP mode. Scroll to theLODLODLODLODLOD menu. Use the UP or DOWN arrows to scroll to theminimum outdoor temperature the reset curve will useto equate to the maximum water temperature.

5.2.2.6 Anti Short Cycle TimeConfirm the display is in SETUPSETUPSETUPSETUPSETUP mode. Scroll to the

ASCASCASCASCASC menu. Use the UP or DOWN arrows to adjust thetime for the anti short cycle period. The numbersdisplayed are in minutes of delay. The anti short cycletime creates a delay for the specified period of timebetween the completion of a call for heat and when thenext call for heat may occur.

5.2.3 Diagnostic ModeDIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTIC mode is accessed by holding the NEXT

button for 3 seconds. DIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTIC mode allows the user tomonitor and control the items shown in Table 12. Toscroll through the menu structure use the NEXT button.When a value that is adjustable has been selected the UPor DOWN arrow keys may be used to adjust the setpoint.When adjustments are complete press the DONE button.

5.2.3.1 High LimitThe appliance high limit sensor is located on the

outlet of the boiler. The sensor is a dual element sensorthat is limit rated. This sensor must be replaced withLaars original equipment parts only. The high limit isnot adjustable.

5.2.3.2 DHW LimitThe DHW maximum temperature setting has been

adjusted at the factory, and can be viewed by enteringthe DIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTICDIAGNOSTIC mode and scrolling to the DHWDHWDHWDHWDHW menu.Once in the DHWDHWDHWDHWDHW menu, the maximum temperature willbe displayed. DHW limit is not adjustable.

WARNINGThe DHW sensor is NOT a limit rated device. An anti-scald device MUST be installed to prevent exces-sively hot water from reaching the end user. Failure

MENU ITEM DEFINITION

Fahrenheit / Selects the temperature units beingCelsius displayedLBTHODLOD Turn outdoor reset on or offLBT Low boiler temperature setpoint.

Display and set the lowest boiler watertemperature desired during outdoor reset

HOD High outdoor temperature setpoint.Display the current setpoint and allow foradjustment of the high outdoor temperaturesetpoint for the reset curve. Cannot be setabove boiler setpoint.

LOD Low outdoor temperature setpoint.Display the current setpoint andallow for adjustment of the Low outdoortemperature setpoint for the reset curve

RMT Remote firing control.(future use) Set the Remote Firing Control ON or OFF.

This allows the use of a external analogsignal to control boiler modulation

RMT ADR RMT Address. Display the current(future use) Modbus address and allows for adjustment

of the address.ASC Anti short cycle. Display the current Anti

Short cycle time and allows for adjustmentusing the up and down arrows.

BAC Backup feature. Not used at this time.Press DONE to exit menu.

RES Restore feature. Not used at this time.Press DONE to exit menu.

PAS Pass Code entry screen. Not used at thistime. Press DONE to exit menu.

Table 11. Setup Mode Parameters.

MENU ITEM DESCRIPTION

mA Display the flame sense signal

Alert codes Displays the current alert code

Lockout code Displays the current lockout code

Outlet Limit Displays outlet temperature limit

DHW limit Displays Domestic Hot Water limit setting

Stack Limit Displays Stack limit setting

Min. firing rate Displays the minimum firing rate allowed

Min. forced Allows the user to force the boiler to fire atfiring rate the minimum firing rate

Max forced Allows the user to force the boiler to fire atfiring rate the maximum firing rate

Rate indicator Displays a indicator of the firing rate basedoff of the fan RPM. Actual firing rate mayvary depending upon setup.

Table 12. Diagnostic Mode Menu Structure.

Page 24: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 24

to install an anti-scald device may lead to propertydamage, personal injury or death.

5.3 Pump ConnectionsThe boiler pump is wired at the factory (pump

mounted models only). The NeoTherm Controlenergizes the pump upon a call for heat. Once the callfor heat is satisfied the pump will remain on for thedefined pump overrun time.NOTE: System and DHW contacts are dry contacts.The appropriate voltage must be supplied to thecontacts for proper operation.

The system pump connections are located onTerminal Block 5 in the control panel (see Figure 18).The system pump contacts are rated for 120Vac, 7.4amps. To use the contacts power must be supplied onone terminal. The other terminal wired to the pump or acontact controlling the pump.

The DHW pump connections are located onTerminal Block 5 in the control panel. The DHW pumpcontacts are rated for 120Vac, 7.4 amps. To use thecontacts power must be supplied on one terminal. Theother terminal wired to the pump or a contactcontrolling the pump.

5.4 Temperature ControlThe NeoTherm temperature control measures the

temperature on the outlet sensor, measuring the supplywater temperature. Set the control setpoint for thedesired supply temperature.

5.5 Temperature Control - Indirect TankFor indirect domestic hot water applications a

DHW sensor or mechanical aquastat may be used todetermine the domestic load call. The sensor or aquastatshould be connected to Terminal block 6 connectionslabeled "DHW temp sensor". The sensor is a dualelement sensor. The Laars sensor is the only sensor thatcan be used with this controller. To connect an aquastatuse the middle and far right terminals on TB6, labeled"DHW temp sensor". Once a sensor or switch isinstalled, the call should be "Autodetected" by thecontrol (see wiring diagrams, page 26).

When the DHW sensor is used the boiler modulatesoff of the DHW sensor using the DHW setpoint. The boilerloop temperature is allowed to operate to the limit setting.To assure correct operation, proper temperature settingsand system plumbing is required to eliminate short-cyclingand nuisance lockouts.

When an aquastat is used for the DHW demand,the boiler modulates off of the outlet water temperature,using the DHW setpoint as the target temperature.

5.6 Outdoor Reset OperationOutdoor reset varies the control point setpoint

based on the outdoor temperature. The reset functionworks as shown in Figure 19. When the Outdoor airtemperature reaches the High Outdoor temperaturesetpoint (HOD), the control point is adjusted to the LowBoiler temperature setpoint (LBT). When the outdoorair temperature reaches the Low Outdoor temperature(LOD) setpoint, the control setpoint is adjusted to theCH setpoint temperature. To access the LOD, HOD andLBT variables, refer to Sections 5.2.2.3 through 5.2.2.5.To access CH setpoint, refer to Section 5.2.1.1.

An outdoor air temperature sensor must beconnected to TB7 in the control panel. The connection

Figure 18. Control Panel Layout.

Page 25: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 25

points are labeled “outdoor temp sen.” The sensor is notpolarity sensitive.

5.7 External Control ConnectionsNeoTherm units are built with a terminal strip to

allow the NeoTherm to receive a 4-20mA modulatingsignal from an external controller (such as a buildingautomation system or multiple boiler control).

When a 4-20mA signal is supplied to NeoTherm,it will modulate according to the signal supplied.

The Brown/White wire is for signal (+) and theBrown wire is for signal (–).

A call for heat signal MUST also be connected tothe field interlock terminal strip on the NeoTherm(shown in Figures 18 and 21).

The NeoTherm unit will modulate between 4mAand 20mA (for 20% and 100%, respectively).Important Note: DO NOT MAKE/BREAK NEOTHERMLINE VOLTAGE TO SIGNAL CALL FOR HEAT. A “callfor heat / end call for heat” MUST be connected to thefield interlock terminals. The NeoTherm does notrecognize 4mA as a signal to shut off. If the call for heatis not connected between the field interlock terminals,the NeoTherm will remain in low fire when it sees 4mAas a modulating signal.

CautionNeoTherm supply voltage must not be disengaged,except for service or isolation, or unless otherwiseinstructed by procedures outlined in this manual. Tosignal a call for heat, use the 24V field-interlock, asshown in the wiring diagram(s).

Some NeoTherm components are designed to haveconstant voltage during normal operation. If theNeoTherm's supply voltage is toggled as a call forheat signal, premature failure of these componentsmay result.

Figure 20. Ladder Diagram.Figure 19. Outdoor Reset Setpoint Temperatures.

Page 26: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 26

Figure 21. Wiring Diagram (all sizes).

Page 27: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 27

10. Recheck the water level in the expansion tank. Ifthe water level exceeds ¼ of the volume of theexpansion tank, open the tank drain, and drain tothat level.

11. Shut down the entire system and vent all radiationunits and high points in the system piping, asdescribed in Step 4.

12. Close make-up water valve and check strainer inpressure reducing valve for sediment or debrisfrom the make-up water line. Reopen make-upwater valve.

13. Check gauge for correct water pressure and alsocheck water level in the system. If the heightindicated above the boiler insures that water is atthe highest point in the circulating loop, then thesystem is ready for operation.

14. Prime condensate trap with water.15. Refer to local codes and the make-up water valve

manufacturer’s instructions as to whether themake-up water valve should be left open or closed.

16. After placing the unit in operation, the ignitionsystem safety shutoff device must be tested. First,shut off the manual gas valve, and call the unit forheat. Main gas terminals will be energized,attempting to light, for four (4) seconds, and thenwill de-energize. The unit will go into lockoutafter the required number of trial for ignitionperiods. Second, turn the power off, press themanual reset button on the boiler control, or theuser display, open the manual gas valve and allowthe unit to light. While the unit is operating, closethe manual gas valve and ensure that power to themain gas valve has been cut.

17. Within three (3) days of start-up, recheck all airbleeders and the expansion tank as described inSteps 4 and 8 above.

Important Note: The installer is responsible foridentifying to the owner/operator the location of allemergency shutoff devices.

WARNINGDo not use this appliance if any part has been underwater. Immediately call a qualified service technicianto inspect the applianceand to replace any part of the control system and anygas control that may have beenunder water.

6.2 Operating the Burner and Set UpThe NeoTherm modulating appliance utilizes an

advanced, state-of-the-art design. The setup must bechecked before the unit is put in operation. Problemssuch as failure to start, rough ignition, strong exhaustodors, etc. can be due to improper setup. Damage to the

5.8 Wiring Diagram (see Figures 20 and 21)

CautionLabel all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper anddangerous operation. Verify proper operation afterservicing

SECTION 6.Operating Instructions

6.1 Filling the Boiler System1. Ensure the system is fully connected. Close all

bleeding devices and open make-up water valve.Allow system to fill slowly.

2. If make-up water pump is employed, adjustpressure switch on pumping system to provide aminimum of 12 psi (81.8 kPa) at the highest pointin the heating loop.

3. If a water pressure regulator is provided on themake-up water line, adjust the pressure regulatorto provide at least 12 psi (81.8 kPa) at the highestpoint in the heating loop.

4. Open bleeding devices on all radiation units at thehigh points in the piping throughout the system,unless automatic air bleeders are provided at suchpoints.Note that there is an air bleed located on the leftside of the unit, on top of the water manifold.

5. Cycle the boiler pump on and off 10 times, 10seconds on and 10 seconds off to remove all airfrom the heat exchanger. Then run system andappliance pump for a minimum of 30 minutes withthe gas shut off.

WARNING

Failure to remove all air from the heat exchangercould lead to property damage, severe injury or death.

6. Open all strainers in the circulating system, checkflow switch operation (if equipped), and check fordebris. If debris is present, clean out to ensureproper circulation.

7. Recheck all air bleeders as described in Step 4.8. Check liquid level in expansion tank. With the

system full of water and under normal operatingpressure, the level of water in the expansion tankshould not exceed ¼ of the total, with the balancefilled with air.

9. Start up boiler according to the procedure in thismanual. Operate the entire system, including thepump, boiler, and radiation units for one (1) hour.

Page 28: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 28

boiler resulting from improper setup is not covered bythe limited warranty.

6.2.1 Burner OperationREQUIRED TOOLS: differential pressure gauge

capable of reading negative 0.01 inches W.C.(0.002kPa), screw drivers, torx bits, combustionanalyzer.1. Using this manual, make sure the installation is

complete and in full compliance with theinstructions and all local codes.

2. Determine that the appliance and system are filledwith water and all air has been bled from both.Open all valves.

3. Observe all warnings on the Operating Instructionslabel and turn on gas and electrical power toappliance.

4. The NeoTherm will enter the start sequence. Theblower and pump will energize for pre-purge, thenthe ignition sequence starts. After all safetydevices are verified, the gas valve opens. Ifignition doesn’t occur, turn off the NeoTherm,check that there is proper gas supply. Wait 5minutes and start the unit again.

5. Turn the NeoTherm on.

6. After placing the appliance in operation, theBurner Safety Shutoff Device must be tested.To test:(a) Close gas shutoff valve with burner

operating.(b) The flame will go out and blower will

continue to run for the post purge cycle. Oneor three additional attempts to light willfollow including pre-purge, ignitor on, valve/flame on and post purge. Ignition will notoccur as the gas is off. The ignition controlwill lockout.

(c) Open gas shutoff valve. Reset the boilercontrol by pressing the RESET button on thecontrol or on the display. Restart theappliance. The ignition sequence will startagain and the burner will start. The appliancewill return to its previous mode of operation.

CautionShould any odor of gas be detected, or if the gasburner does not appear to be functioning in a normalmanner, CLOSE MAIN SHUTOFF VALVE. Do notshut off switch. Contact your heating contractor, gascompany, or factory representative.

CO2 HIGH FIRE CO2 LOW FIRE

Natural Gas 8.8 – 9.5% 8.0 – 8.8%

Propane Gas 9.7 – 10.2% 9.0 – 9.7%

Differential Pressure -.005 to -.015 -.001 to -.015

Table 13. CO2 Range and Pressure Differential. Figure 22. NeoTherm Gas Valves (285, 399 and 500).

399

80–285

500

Page 29: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 29

6.2.2 Boiler Setup and Adjustment1. Connect a manometer capable of reading -.005"wc

to the gas valve locations shown in Figure 22. Thepositive side of the manometer should beconnected to the location labeled “air pressuretap.” The negative side of the manometer shouldbe connected to the location labeled "gas pressuretap." This differential pressure should be slightlynegative (see Table 13).

2. Measure the CO2/O2 in the flue products at highfire. The NeoTherm can be forced to high fire toallow for easier setup. Refer to Section 5.2.3 forinstructions on how to access the forced rate menu.The CO2 readings should be between the valuesshown in Table 13. If the CO2 is not within therange shown, adjustments may be made. To adjustthe high fire CO2, locate the high fire adjusterscrew according to the appropriate figure. Slowlymake adjustments in 1/16 of a revolutionincrements until the CO2 is within the rangeidentified.NOTE: NeoTherm 399 does not have a high fireadjustment.

3. Measure the CO2/O2 in the flue products at lowfire. The NeoTherm can be forced to low fire toallow for easier setup. Refer to Section 5.2.3 forinstructions on how to access the forced rate menu.The CO2 readings should be between the valuesshown in Table 13. If the CO2 is not within therange shown, adjustments may be made. To adjustthe low fire CO2, locate the low fire adjuster screwaccording to the appropriate figure. Slowly makeadjustments in 1/16 of a revolution incrementsuntil the CO2 is within the range identified.

4. Repeat steps 2 and 3 to confirm that the CO2

ranges are within the required ranges. Adjust ifnecessary.

5. Confirm that the differential pressure is still withinthe appropriate range.

6. If any of the measurements cannot be adjusted tothe specified ranges or the CO levels are above150ppm when adjusted please consult the factoryfor further information.

7. Remove the differential pressure gauge from theair and gas pressure taps making sure to close allports after the gauge has been removed.

WARNINGImproper adjustment may lead to poor combustionquality, increasing the amount of carbon monoxideproduced. Excessive carbon monoxide levels maylead to personal injury or death.

6.3 Shutting Down the NeoTherm1. Turn off the main electrical disconnect switch.2. Close all manual gas valves.3. If freezing is anticipated, drain the NeoTherm and

be sure to also protect building piping fromfreezing. All water must be removed from heatexchanger or damage from freezing may occur.

This step to be performed by a qualified service person.

6.4 To Restart the NeoThermIf drained, follow Section 6.1 in this manual for

proper filling and purging.1. Turn off the main electrical disconnect switch.2. Close all manual gas valves.3. WAIT FIVE (5) MINUTES.4. Set the aquastat or thermostat to its lowest setting.5. Open all manual gas valves.6. Reset all safety switches (pressure switch, manual

reset high limit, etc.).7. Set the temperature controller to the desired

temperature setting and switch on electrical power.8. Burner will go through a prepurge period and

ignitor warm-up period, followed by ignition.

Page 30: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 30

SECTION 7.Maintenance

WARNINGDisconnect all power to the appliance beforeattempting any service to the appliance. Contact withelectricity can result in severe injury or death.

7.1 System Maintenance (Yearly)1. Lubricate the system water-circulating pump, if

required, per the instructions on the pump.2. If a strainer is employed in a pressure reducing

valve or the piping, clean it every six months.3. Inspect the venting system for obstruction or

leakage at least once a year. Periodically clean thescreens in the vent terminal and combustion airterminal (when used).

4. Keep the appliance area clear and free fromcombustible materials, gasoline, and otherflammable vapors and liquids.

5. If the appliance is not going to be used forextended periods in locations where freezingnormally occurs, it should be isolated from thesystem and completely drained of all water.

6. Low water cutoffs, if installed, should be checkedevery 6 months. Float type low water cutoffsshould be flushed periodically.

7. Inspect and clean the condensate collection, floatswitch and disposal system yearly.

8. When a means is provided to neutralizecondensate, ensure that the condensate is beingneutralized properly.

9. Inspect flue passages, and clean with brushes/vacuums, if necessary. Sooting in flue passagesindicates improper combustion. Determine thecause and correct.

Figure 23. Burner Service.

Page 31: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 31

10. Inspect the vent system and air intake system, andensure that all joints are sealed properly. If jointsneed to be resealed, completely remove existingsealing material, and clean with alcohol. Applynew sealing material, and re-assemble.

7.2 Appliance Maintenance andComponent DescriptionUse only genuine LAARS replacement parts.

CautionLabel all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper anddangerous operation. Verify proper operation afterservicing.

The gas and electric controls on the appliance areengineered for long life and dependable operation, butthe safety of the equipment depends on their properfunctioning. Only a qualified service technician shouldinspect the basic items listed below every year:

a. Appliance control f. Flow switchb. Automatic gas valve g. Low water cutoffc. Pressure switches h. Burnerd. Blower i. Heat exchangere. Pump

7.2.1 BurnerCheck the burner for debris. Remove the blower

arm assembly to access the burner. Remove the 4 boltsconnecting the blower to the arm (see Figure 23).Remove the 5 bolts, which hold the burner arm in place.Pull burner up and out. Clean burner, if necessary, byblowing compressed air from the outside of the burnerinto the center of the burner, and wipe the inside of theburner clean with glass cleaner. A dirty burner may bean indication of improper combustion or dirtycombustion air. Determine the cause, and correct. Ifdamaged, replace the burner gasket when replacing theburner.NOTE: When installing the burner, make sure theflange is aligned with the mating surface, as each iskeyed to control fit.

7.2.2 Modulating Gas Valve / VenturiThe modulating gas valve consists of a valve body

that incorporates the ON/OFF gas flow control and anegative pressure regulator. It provides the air/gas ratiocontrol in combination with the venturi to the unit. It isdesigned to operate with gas supply pressure between 4and 13 inches w.c.. To remove the gas valve and orventuri. Shut off the 120 Volt power supply to theboiler. Turn off all manual gas valves connecting theboiler to the main gas supply line. Remove the frontdoor of the boiler to gain access to the gas valve andventuri. Disconnect the four (4) flange bolts connectingthe gas manifold pipe to the gas valve. Remove theelectrical connections to the gas valve. Remove the bolts

connecting the venturi flange to the blower. This allowsthe entire gas valve/venturi assembly to be removed asan assembly to facilitate inspection and cleaning.

After the valve has been removed, reassemble inreverse order making sure to include all gaskets and O-rings. Turn on the manual gas valves and check for gasleaks. Turn on the 120 Volt power. Place the unit inoperation following the instructions in Section 6.2.Once the boiler is operating check for leaks again andconfirm all fasteners are tight.

Check appliance setup according to Section 6.2.

7.2.3 Appliance ControlThe NeoTherm appliance control is an integrated

control that incorporates the manual reset high limitcontrol, the operating temperature control, modulatingcontrol, ignition control, outdoor reset control, pumpcontrol and many other features. If any of these featuresare thought to be defective, please consult the factoryfor proper trouble shooting practices prior to replacingthe control. If control replacement is required, turn offall power to the appliance. Shut all manual gas valves tothe appliance. Remove the front door to the applianceand the control panel plastic bezel. Remove all wireconnections from the control board. The control boardconnections are keyed to only allow connection in theproper location, but proper handling techniques shouldbe used to avoid damage to the wiring or connectors. Toremove the control push in on the two tabs on the leftside of the board to unlatch the clips from the controlpanel. Rotate the control around the fastening points onthe right side of the control to remove the hooks fromthe control panel. To replace the control repeat the stepsabove in the reverse order making sure to connect allwires in the proper location. Place the appliance inoperation following the steps outlined in Section 6.2.

7.2.4 Ignitor AssemblyThe ignitor assembly is a two rod system that

consists of a ground rod and a sense rod. To remove theignitor assembly, shut off the 120 Volt power supply tothe appliance. Turn off all manual gas valves connectingthe appliance to the main gas supply line. Remove thefront door of the boiler to gain access to the ignitorassembly. Remove the two wires connected to theassembly. Then remove the two bolts connecting theignitor assembly to the burner door. Remove andreplace the old ignitor assembly gasket. Reinstall a newignitor assembly in the reverse order if the old assemblyis determined defective. Replace gasket if necessary.

7.2.5 Flame SensorThe flame sensor is a single rod system. To replace

the flame sensor electrode, shut off the 120 Volt powersupply to the boiler. Turn off all manual gas valvesconnecting the boiler to the main gas supply line.Remove the front door of the boiler to gain access to theflame sensor electrode. Remove the flame sensor wire

Page 32: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 32

from the electrode. Remove the two bolts fastening theelectrode to the burner doors. Remove and replace theold flame sensor gasket. Reinstall a new flame sensorelectrode in the reverse order if the old electrode isdetermined defective.

CautionIgniters and sensors get hot and

can cause burns or injury.

7.2.6 TransformersThere are various transformers used on the

NeoTherm units. Be sure to replace the transformerswith factory parts. These transformers are not capable ofsupplying control voltage for external devices such aszone valves, which must have their own separate powersupply. Should a transformer need replacing, shut offthe 120 Volt power. Unplug the transformer wires,remove the mounting screws and remove thetransformer. Replace transformer in the reverse order.

7.2.7 BlowerThe combustion air blower is a high-pressure

centrifugal blower with a variable speed motor. Thespeed of the motor is determined by the control logic.The 120 Volt current remains on to the blower at alltimes. If a blower change is required, turn off the 120Volt power and gas supply to the unit. Take the frontpanel off. Disconnect the 120 Volt and control signalconnections from the blower. Disconnect the boltsconnecting the venturi to the blower housing.Disconnect the fan outlet bolts from the burner doorblower arm. If the fan is determined to be defectivereplace the existing fan with a new one reversing thesteps above. Make sure to install all of the required O-rings and gaskets between the blower arm and theblower and blower face and venturi flange.

7.2.8 Heat Exchanger CoilsBlack carbon soot buildup on the external surfaces

of the heat exchanger is caused by one or more of thefollowing; incomplete combustion, combustion airproblems, venting problems and heater short cycling.Soot buildup or other debris on the heat exchanger mayrestrict the flue passages.

If black carbon soot buildup on the heat exchangeris suspected, disconnect electrical supply to the unit,and turn off the gas supply by closing the manual gasvalve on the unit. Access the heat exchanger through theburner door at the front of the boiler, and inspect thetubing using a flashlight. If there is a buildup of blackcarbon soot or other debris on the heat exchanger, cleanper the following:

CautionBlack carbon soot buildup on a dirty heat exchangercan be ignited by a random spark or flame. Toprevent this from happening, dampen the sootdeposits with a wet brush or fine water spray beforeservicing the heat exchanger.

1. Shut off the 120 Volt power supply to the boiler2. Turn off all manual gas valves connecting the

boiler to the main gas supply line.3. For NT 500 models only (all other sizes please

skip to step four). NT 500 models will require thegas valve to be removed in order to remove theburner door. To do this, remove the wireconnections from the gas valve. Remove the flangebolts from the gas supply pipe connected to the gasvalve (1B). Remove the flange bolts connectingthe gas train to the venturi (1A). Remove the gastrain assembly keeping gaskets and o-rings.

4. Remove the four bolts connecting the blowerflange to the burner door arm.

5. Remove the nuts located on the outside diameterof the burner door to the heat exchanger.

6. Remove the burner door/burner assembly from theheat exchanger.

7. Disconnect the condensate drain line.8. Attach a longer hose to drain and run to a bucket.9. Clean the heat exchanger by brushing light

accumulations of soot and debris. Use a brush withsoft bristle (non metal) to avoid damaging thesurface of the heat exchanger tubes.

10. Once the tubes have been brushed clean rinse thetubes and combustion chamber with a smallamount of water to rinse all of the debris out of thebottom of the flue collector and into the longercondensate trap line, which is being diverted into aseparate container.

NOTE: The Warranty does not cover damage causedby lack of required maintenance, lack of water flow,or improper operating practices.

WARNINGFailure to rinse the debris from the heat exchangerand temporary drain line may lead to cloggedcondensate lines, traps and neutralizers. Condensatepumps (if used) may also be damaged from thedebris left behind, possibly causing property damage.

11. Install all components removed in the reverseorder to place the appliance back in operation.Make sure all gaskets are in place as componentsare installed. Replace any damaged gaskets. DoNOT reuse damaged gaskets.

Page 33: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 33

12. Place the appliance in operation according toSection 6.2 checking all gas connections for leaks.Confirm all fasteners are tight.

7.2.9 Gas Pressure Switches (optional)The high and low gas pressure switches are 24V

manual reset switches that act to cut power to the gasvalves if the gas pressure is too low or too high forproper operation. The gas pressure switches used areintegrally vent limited, and do not require venting toatmosphere. To remove a switch, remove the screw onthe plastic housing and pull the clear cover off.Disconnect the two wires from the screw terminals.Twist the switch off the pipe nipple. Reassemble inreverse order. For natural gas, set the low gas pressureswitch to 3" w.c. For propane, set the low gas pressureswitch to 5" w.c. For natural and propane, set the highgas pressure switch to 14".

SECTION 8.Trouble Shooting

8.1 Sequence of OperationThe NeoTherm appliance is a cold start appliance

that should start only on a call for heat from a tankaquastat, room thermostat, zone valve end switch orother space temperature control device.1. Upon a call for heat: (a) the internal pump and

system pump will start; (b) the blower will begin a30 second pre-purge.

2. Following the prepurge cycle the direct sparkignition will spark and will begin a 4 second trialfor ignition. The unit is allowed one or threeignition retries.

3. The gas valve will then be energized and a reducedrate ignition will occur. The unit will remain in areduced rate start-up period for several seconds.

4. After the reduced rate start time is over, the unitwill be in normal operation. Firing rate willmodulate based on the heating load via thetemperature controller settings and readings.

5. When the call for heat is complete, or the unit reachesits setpoint temperature, the gas valve will close, andthe fan will continue to run for its 20 second post-purge. If a pump delay time is used, the pump willcontinue to run for the specified amount of time(adjustable from 0.1 to 10 minutes).

8.2 Short CyclingBecause the NeoTherm is a modulating boiler, and

its input will decrease when there is a reduction inheating load, short cycling is greatly reduced. If theheating load drops below the minimum input of theboiler for an extended period, the boiler will have atendency to short cycle. This can be a symptom ofimproper control strategy or setpoints, or a loaddistribution problem. The NeoTherm control has a built-in anti-short cycle (ASC) feature. The ASC is a timedsetting that will delay the boiler start for a specifiedtime after one call for heat is completed. The ASC timemay be adjusted as desired (see Sections 5.2.2 and5.2.2.6 for more information).

8.3 Error Codes - See Table 14.

Page 34: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 34

CODE# PROBLEM PROBABLE CAUSE SOLUTION

COMMON LOCKOUT CODES

27 Internal error Flame rod to ground Check wiring / probe grounded, dirty probe

47 Flame rod to ground leakage Faulty flame detector Clean or replace flame detector

49 24VAC voltage low/high Faulty transformer Check/correct supply line voltage; replace faultytransformer

52 Motor tachometer fault Faulty fan / fan wiring Check fan harness wiring for continuity; replace faultyfan circuit

53 AC inputs phase reversed Reverse 24V hot/neutral - use common ground

61 Anti short cycle Call for heat will be held Change ASC timer settinguntil timer resets

62 Fan speed not proved Dirty / defective fan Clean or replace fan; check wiring

63 LCI off Safety chain interrupt Check flow switch, aux high limit, LWCO, gaspressure switches, condensate level and correctproblem

69 Outlet high limit High limit tripped Determine cause: low/no flow, valves closed, settingsand correct

79 Outlet high limit

80 DHW high limit High limit reached Check pump, time delay, valves closed, etc. and

81 Delta T inlet/outlet limitcorrect overtemp

82 Stack limit High limit reached Could be caused by high ambient temperature, orhigh return water temperature

88 Outlet T-rise limit

90 Heat exchanger high limitHigh limit reached Diagnose / repair cause of high temperature

91 Inlet sensor fault

92 Outlet sensor fault

93 DHW sensor faultFaulty sensor or wiring Check wiring / replace sensor; condition can be

95 Stack sensor faultcaused by short

96 OAT temperature sensor fault Faulty outdoor air Check wiring and sensor for short; replace sensortemperature sensor is open or shorted

105 Flame detected Flame exists at burner Clean burner of soot or other debris that couldout of sequence when it should not be maintain flame

106 Flame lost in MFEP Unstable flame during107 Flame lost early in Run lighting / flame proving Check venting, gas supply pressure, burner, fan, etc.

108 Flame lost in Run sequence

109 Ignition failed Problem with ignitor, orCheck / replace ignitor, wiringother ignition-related device

113 Flame circuit timeout Flame not established Check all combustion components; purge gas;within expected time limit check ignition source

122 Lightoff rate proving failed

123 Purge rate proving failed

128 Fan speed failed / prepurge Fan did not reach Check fan wiring; replace fan;

129 Fan speed failed / preignition expected RPM

130 Fan speed failed / ignition

131 Fan movement detected Fan should not be moving Check for common venting problems or otherwiseduring standby when not powered forced air

132 Fan speed failed during run Fan lost or gained speed Fan overheating or otherwise failing; check cable;during run sequence away replace fanfrom control spec

137 ILK failed to close No power at interlock ILK Check J5 pin 1 for power - if no power, confirmsafeties are closed

continued next page >

Page 35: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 35

49 Maximum cycle count Control operates correctly,was reached however the cycle count will

not increment any higherthan 999,999 cycles

Replace controller or adjust the count using blue display50 Maximum hours count Control operates correctly,

was reached however the hours count willnot increment any higherthan 999,999 hours

248 CH outdoor temperaturewas invalid

251 CH ODR max outdoor temp- Confirm outdoor reseterature setpoint was invalid settings. An invalid

252 CH ODR min outdoor temp-adjustment has been

erature setpoint was invalid made

253 CH ODR min water temp-erature setpoint was invalid

254 CH ODR temperature range Increase Outdoor air temp-Adjust setting to within appropriate range

was too small erature min and max values(min. 12°C / 22°F) to a difference greater than

22°F (12°C)

255 CH setpoint minus ODR Increase Outdoor watermin water temperature was temperature min and maxtoo small (min. 12°C / 22°F) values to a difference greaterIncrease setpoint or than 22°F (12°C)decrease min water temp.

565 Heat exchanger T-rise limit Heat exchanger temperature Check for correct water flowwas exceeded rise exceed

MISCELLANEOUS

Boiler will not stay lit Indicates lack of flame signal, Check flame detector wiring; clean / replace flamecheck fault code on display detector

Boiler bangs, knocks, hisses Insufficient water flow / Check for proper flow, follow piping guidelines inpump failure; improper piping manual; replace pump; improper glycol percentage

(see Section 4.3)

Flame pulsates, venting Insufficient / improper Ensure venting complies with Section 2noise or has difficulty lighting venting; dirty burner; air in

gas line; dirty heat exchanger

Table 14. Error Codes.

CODE# PROBLEM PROBABLE CAUSE SOLUTION

ALERT CODES

SECTION 9.Replacement PartsUse only genuine LAARS replacement parts.

9.1 General InformationTo order or purchase parts for the LAARS

NeoTherm, contact your nearest LAARS dealer ordistributor. If they cannot supply you with what youneed, contact Customer Service (see back cover foraddress, telephone and fax numbers).

Page 36: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 369.

2P

arts

Lis

tIT

EM

DE

SC

RIP

TIO

NS

IZE

80

SIZ

E 1

05S

IZE

150

SIZ

E 2

10S

IZE

285

SIZ

E 3

99S

IZE

500

Jack

et C

om

po

nen

ts, S

ee F

igu

re 2

4

1F

ront

Pan

el A

ssem

bly

R50

D32

00R

50D

3200

R50

D32

00R

50D

3200

R50

D32

00R

50D

3200

R50

D32

00

2F

ront

Pan

el H

andl

eR

50D

3204

R50

D32

04R

50D

3204

R50

D32

04R

50D

3204

R50

D32

04R

50D

3204

3R

ear

Pan

elR

50D

3101

R50

D31

01R

50D

3101

R50

D31

01R

50D

3101

R50

D31

01R

50D

3101

4Le

ft S

ide

Pan

elR

8D30

02R

10D

3002

R15

D30

02R

20D

3002

R30

D30

02R

40D

3002

R50

D30

02

5R

ight

Sid

e P

anel

R15

D30

01R

15D

3001

R15

D30

01R

30D

3001

R30

D30

01R

40D

3001

R50

D30

01

6Le

ft T

op P

anel

R8D

3303

R10

D33

03R

15D

3303

R21

D33

03R

30D

3303

R40

D33

03R

50D

3303

7M

iddl

e T

op P

anel

R8D

3302

R10

D33

02R

15D

3302

R21

D33

02R

30D

3302

R40

D33

02R

50D

3302

8R

ight

Top

Pan

elR

8D33

01R

10D

3301

R15

D33

01R

21D

3301

R30

D33

01R

40D

3301

R50

D33

01

9Ja

cket

Ang

le S

uppo

rtR

8D31

02 (

RH

)R

15D

3102

R15

D31

02R

30D

3102

R30

D31

02R

40D

3102

R50

D31

02R

15D

3102

(LH

)(2

)(2

)(2

)(2

)(2

)(2

)

10Ja

cket

Sup

port

Lef

t Sta

nchi

onR

50D

3003

R50

D30

03R

50D

3003

R50

D30

03R

50D

3003

R50

D30

03R

50D

3003

11Ja

cket

Sup

port

Rig

ht S

tanc

hion

R50

D30

04R

50D

3004

R50

D30

04R

50D

3004

R50

D30

04R

50D

3004

R50

D30

04

12F

ront

Bez

elR

50D

7101

R50

D71

01R

50D

7101

R50

D71

01R

50D

7101

R50

D71

01R

50D

7101

Inte

rnal

Co

mp

on

ents

– S

ee F

igu

re 2

5

20B

ase

Ass

embl

yR

15D

1100

R15

D11

00R

15D

1100

R30

D11

00R

30D

1100

R40

D11

00R

50D

1100

21Le

ft R

ear

Sup

port

Sta

nchi

onR

50D

1001

R50

D10

01R

50D

1001

R50

D10

01R

50D

1001

R50

D10

01R

50D

1001

22Le

ft F

ront

/Rig

ht R

ear

Sup

port

Sta

nchi

onR

50D

1002

R50

D10

02R

50D

1002

R50

D10

02R

50D

1002

R50

D10

02R

50D

1002

(2)

(2)

(2)

23C

antil

ever

ed B

ase

Sta

nchi

onR

15D

1002

R15

D10

02R

15D

1002

R40

D10

01R

40D

1001

R40

D10

01—

24F

ront

/Rea

r S

tanc

hion

Bra

ceR

50D

1005

R50

D10

05R

20D

1006

R20

D10

06R

50D

1005

R50

D10

05R

50D

1005

(2)

25M

ount

ing

Rai

lR

15D

1004

R15

D10

04R

15D

1004

R30

D10

04R

30D

1004

R30

D10

04R

50D

1004

(2)

(2)

(2)

(2)

26R

ight

Fro

nt S

uppo

rt S

tanc

hion

——

——

——

R50

D10

03

27C

onde

nsat

e T

rap

Ass

embl

yR

20D

4020

R20

D40

20R

20D

4020

R20

D40

20R

50D

4020

R50

D40

20R

50D

4020

28H

eat E

xcha

nger

Rai

l Clip

R50

D10

06R

50D

1006

R50

D10

06R

50D

1006

R50

D10

06R

50D

1006

R50

D10

06(4

)(4

)(4

)(4

)(4

)(4

)(4

)

30P

VC

Red

ucer

——

RP

2053

000

RP

2053

000

RP

2052

900

RP

2052

800

RP

2052

800

30a

CP

VC

Red

ucer

or

Cou

plin

gR

D20

1050

1R

D20

1050

1R

P20

6560

0R

P20

6560

0—

——

30b

2" P

ipe

CP

VC

RD

2010

212

RD

2010

212

RD

2010

213

RD

2010

213

——

31H

ose

Bar

b A

dapt

erR

P20

6710

0R

P20

6710

0R

P20

5610

0R

P20

5610

0R

P20

5610

0R

P20

6700

32S

tanc

hion

Bra

ceR

40D

1005

R40

D10

05R

40D

1005

R40

D10

05R

40D

1005

R40

D10

05—

33A

ir In

let/E

xhau

st B

rack

etR

8D30

05R

10D

3005

R20

D31

20R

20D

3120

R30

D30

05R

50D

3005

R50

D30

05

Page 37: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 37

ITE

MD

ES

CR

IPT

ION

SIZ

E 8

0S

IZE

105

SIZ

E 1

50S

IZE

210

SIZ

E 2

85S

IZE

399

SIZ

E 5

00

Gas

Tra

in C

om

po

nen

ts –

See

Fig

ure

26

40C

ombu

stio

n A

ir B

low

erR

A21

1370

0R

A21

1370

0R

A21

0750

0R

A21

1420

0R

A21

1420

0R

A21

1310

0R

A21

1310

0

41G

as V

alve

/Ven

turi

RV

2017

900

RV

2017

901

RV

2017

902

RV

2017

903

RV

2017

904

——

42G

as V

alve

——

——

—R

V20

1920

0R

V20

1780

0

43G

as/A

ir V

entu

ri—

——

——

—R

A21

1320

0

44M

anua

l Gas

Val

ve—

——

——

RV

2000

200

RV

2003

000

45G

as V

alve

Fla

nge

Kit

——

——

——

RP

2050

100

46G

as V

alve

/Ven

turi

Cor

k G

aske

t—

——

——

—R

S21

0490

0

47G

as V

alve

O-R

ing

R30

-227

R30

-227

R30

-227

R30

-227

R30

-227

——

48V

entu

ri O

-Rin

g—

——

——

RS

2105

200

RS

2105

200

(2)

49H

igh

Gas

Pre

ssur

e S

witc

h—

——

——

—R

2004

000

50Lo

w G

as P

ress

ure

Sw

itch

——

——

——

R20

0410

0

51V

entu

ri to

Duc

t T

rans

ition

R10

D50

13R

10D

5013

R10

D50

13R

10D

5013

R30

D50

13—

R10

5010

01

52G

as S

uppl

y P

ipe

RP

2051

700

RP

2051

400

RP

2051

400

RP

2051

400

RP

2051

500

——

53G

as P

ipe

3/4"

NP

T F

orm

ed N

ippl

e—

——

——

RP

2056

500

54A

ir C

onne

ctor

Pla

te—

——

——

—R

50D

5021

55A

ir In

let F

lex

Hos

eR

D00

9110

1R

D00

9110

1R

D00

9110

1R

D00

9110

1R

D00

9110

1R

D00

9120

1R

D00

9090

1

56A

ir In

let C

olle

ctor

——

——

—R

V20

1940

0—

57E

lecr

tric

al C

onne

ctor

with

Cab

le—

——

——

RE

2331

700

58E

lbow

Ada

pter

——

——

—R

V20

1930

0—

59B

low

er A

dapt

er P

late

with

Gas

ket &

Fas

tene

rs—

——

——

RA

2115

400

Hea

t E

xch

ang

er C

om

po

nen

ts –

See

Fig

ure

27

60H

eat E

xcha

nger

RS

2106

900

RS

2105

500

RS

2105

800

RS

2105

700

RS

2105

600

RS

2105

900

RS

2105

300

61P

ump

Ass

embl

yR

A21

1223

2R

A21

1222

7R

A21

1222

7R

A21

1222

8R

A21

1223

0R

A21

1223

1R

A21

1222

9

62Lo

w W

ater

Cut

off S

witc

h—

——

——

—R

E20

7650

0

63W

ater

Tem

pera

ture

Sen

sor

RE

2320

600

RE

2320

600

RE

2320

600

RE

2320

600

RE

2320

600

RE

2320

600

RE

2320

600

64D

uple

x W

ater

Tem

pera

ture

Sen

sor

RE

2319

900

RE

2319

900

RE

2319

900

RE

2319

900

RE

2319

900

RE

2319

900

RE

2319

900

65D

uple

x S

tack

Tem

pera

ture

Sen

sor

RE

2319

700

RE

2319

700

RE

2319

700

RE

2319

700

RE

2319

800

RE

2319

800

RE

2319

800

66P

ress

ure

Rel

ief

Val

veR

51-1

82R

51-1

82R

51-1

82R

51-1

82R

A21

1360

2R

A21

1360

2R

A21

1360

2(3

0 P

SI)

(30

PS

I)(3

0 P

SI)

(30

PS

I)(7

5 P

SI)

(75

PS

I)(7

5 P

SI)

67A

ir V

ent

R70

-216

R70

-216

R70

-216

R70

-216

R70

-216

R70

-216

R70

-216

68B

urne

r D

oor

with

Gas

kets

RS

2108

300

RS

2108

300

RS

2108

300

RS

2108

300

RS

2108

300

RS

2108

300

RS

2108

300

68A

Gas

kets

-onl

y (B

urne

r D

oor)

R20

6940

0R

2069

400

R20

6940

0R

2069

400

R20

6940

0R

2069

400

R20

6940

0

69B

urne

r G

aske

tR

S21

0850

0R

S21

0850

0R

S21

0850

0R

S21

0850

0R

S21

0850

0R

S21

0850

0R

S21

0850

0

Page 38: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 38

69A

Gas

ket S

et (

burn

er, i

gnito

r, s

enso

r &

doo

r ga

sket

s)R

S21

0910

0R

S21

0910

0R

S21

0910

0R

S21

0910

0R

S21

0910

0R

S21

0910

0R

S21

0910

0

70F

ront

Ref

ract

ory

Tile

RT

2109

000

RT

2109

000

RT

2109

000

RT

2109

000

RT

2109

000

RT

2109

000

RT

2109

000

71R

ear

Ref

ract

ory

Tile

R50

D20

21R

50D

2021

R50

D20

21R

50D

2021

R50

D20

21R

50D

2021

R50

D20

21

72M

ain

Bur

ner

w/g

aske

tR

2069

101

R20

6910

2R

2069

103

R20

6910

4R

2069

105

R20

6910

6R

2069

106

73F

lam

e S

enso

r w

/gas

ket

R20

6920

0R

2069

200

R20

6920

0R

2069

200

R20

6920

0R

2069

200

R20

6920

0

74Ig

nito

r w

/gas

ket

R20

6930

0R

2069

300

R20

6930

0R

2069

300

R20

6930

0R

2069

300

R20

6930

0

74A

Igni

tor

Gas

ket

RW

2013

300

RW

2013

300

RW

2013

300

RW

2013

300

RW

2013

300

RW

2013

300

RW

2013

300

74B

Scr

ew, I

gnito

r/F

lam

e S

enso

rm

4-.7

X8m

mm

4-.7

X8m

mm

4-.7

X8m

mm

4-.7

X8m

mm

4-.7

X8m

mm

4-.7

X8m

mm

4-.7

X8m

m

74C

Fla

me/

Sen

sor

Gas

ket

RW

2013

400

RW

2013

400

RW

2013

400

RW

2013

400

RW

2013

400

RW

2013

400

RW

2013

400

75A

ir/G

as C

hann

elR

S21

0840

0R

S21

0860

0R

S21

0860

0R

S21

0870

0R

S21

0870

0R

S21

0870

0R

S21

0880

0

75A

Scr

ew, A

ir/G

as C

hann

elR

S21

0940

0R

S21

0940

0R

S21

0940

0R

S21

0940

0R

S21

0940

0R

S21

0940

0R

S21

0940

0(5

)(5

)(5

)(5

)(5

)(5

)(5

)

76D

rain

R10

-143

R10

-143

R10

-143

R10

-143

R10

-143

R10

-143

R10

-143

77S

ight

Gla

ssR

50D

2020

R50

D20

20R

50D

2020

R50

D20

20R

50D

2020

R50

D20

20R

50D

2020

Ele

ctri

cal C

om

po

nen

ts –

See

Fig

ure

28

80C

ontr

ol P

anel

Enc

losu

reR

50D

7001

R50

D70

01R

50D

7001

R50

D70

01R

50D

7001

R50

D70

01R

50D

7001

81T

rans

form

erR

E21

0870

0R

E21

0870

0R

E21

0870

0R

E21

0870

0R

E21

0870

0R

E21

0870

0R

E21

0870

0

82H

igh

Vol

tage

Shi

eld

R50

D70

02R

50D

7002

R50

D70

02R

50D

7002

R50

D70

02R

50D

7002

R50

D70

02

83T

op P

anel

Bra

cket

R50

D70

03R

50D

7003

R50

D70

03R

50D

7003

R50

D70

03R

50D

7003

R50

D70

03

84E

lect

roni

c C

ontr

ol M

odul

e, s

tand

ard

R50

D70

18R

50D

7016

R50

D70

14R

50D

7012

R50

D70

06R

50D

7010

R50

D70

06

Ele

ctro

nic

Con

trol

Mod

ule,

CS

D-1

——

——

——

R50

D70

08

85R

ocke

r S

witc

hR

E23

2270

0R

E23

2270

0R

E23

2270

0R

E23

2270

0R

E23

2270

0R

E23

2270

0R

E23

2270

0

86C

ontr

ol D

ispl

ayR

E23

2660

0R

E23

2660

0R

E23

2660

0R

E23

2660

0R

E23

2660

0R

E23

2660

0R

E23

2660

0

87W

ire H

arne

ssR

50D

7407

R50

D74

07R

50D

7407

R50

D74

07R

50D

7407

R50

D74

05R

50D

7401

88C

SD

-1 W

ire H

arne

ss—

——

——

—R

50D

7403

ITE

MD

ES

CR

IPT

ION

SIZ

E 8

0S

IZE

105

SIZ

E 1

50S

IZE

210

SIZ

E 2

85S

IZE

399

SIZ

E 5

00

Page 39: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 39

Figure 24. Jacket Components.

Page 40: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 40

Figure 25A. Internal Components, sizes 80–210. Figure 25B. Internal Components, sizes 285–500.

Page 41: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 41

Figure 26. Gas Train Components.

Page 42: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

LAARS Heating SystemsPage 42

Figure 27. Heat Exchanger Components.

Page 43: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

NeoTherm Boiler Page 43

Figure 28 Electrical Components.

Page 44: Installation and Operation Instructions for NeoTherm · qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create

H23

3050

0B

800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)

20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)

1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130

www.Laars.com Litho in U.S.A. © Laars Heating Systems 0904 Document 1218B

®