Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,qualified in hot water heater installation and maintenance. Improper installation and/or operation couldcreate carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.Improper installation and/or operation will void the warranty.
WARNINGIf the information in this manual is not followed exactly, a fire or explosion may resultcausing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this orany other appliance.
WHAT TO DO IF YOU SMELL GAS• Do not try to light any appliance.• Do not touch any electrical switch; do not use any phone in your building.• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's
instructions.• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gassupplier.
Installation and OperationInstructions for
Mighty Therm
Volume Water HeatersModels VW, PW and IWSizes 500-1825
These instructions are to be stored in the pocket provided on the boiler.
H01
0500
0D
Installation and Operation Instructions Document 2040D
LAARS HEATING SYSTEMSPage 2
SECTION 1.General Information1A. Introduction................................................... 31B. Heater Identification ..................................... 31C. Flow Requirements ...................................... 41D. Water Chemistry ........................................... 4
SECTION 2.Installation2A. Heater Placement ......................................... 42B. Installation of Indoor Heaters ....................... 42B-1. Combustion Air Supply ................................. 62B-2. Venting ......................................................... 62C. Installation of Outdoor Heaters ..................... 72D. Gas Supply and Piping ................................. 72E. Electrical Wiring ............................................ 82F. Water Piping of System ................................ 82G. Water Expansion .......................................... 92H. Pump Performance and Installation ........... 102I. Water Pressure .......................................... 162J. Tank Installation ......................................... 162K. Two-Temperature System .......................... 16
SECTION 3.Operation3A. Controls - General ...................................... 163B. Initial Start-Up ............................................. 17
TABLE OF CONTENTS
3C. To Start Up System .................................... 183D. To Turn Off Heater ....................................... 193E. To Shut Down System ................................ 19
SECTION 4.Maintenance
................................................................... 19
SECTION 5.Troubleshooting and Analysis ofService Problems
................................................................... 20
SECTION 6.Parts Descriptions and Order Numbers
................................................................... 22
SECTION 7.Outdoor Parts Descriptions andOrder Numbers
................................................................... 30
SECTION 8.Optional Parts Descriptions andOrder Numbers
................................................................... 32
Mighty Therm Volume Water Heater Page 3
SECTION 1.General Information
1A. IntroductionThis manual provides information for the
installation and operation of Laars volume waterheaters. It is strongly recommended that all applicationand installation procedures be reviewed completelybefore proceeding with the installation. Consult theLaars factory, or local factory representative, with anyproblems or questions regarding this equipment.Experience has shown that most problems are causedby improper installation.
Some accessory items are shipped in separatepackages. Verify receipt of all packages listed on thepackage slip. Inspect everything for possible damageupon delivery, and inform the carrier of any shortagesor impairments. Any such claims should be filed withthe carrier. The carrier, not the shipper, is responsiblefor shortages and damage to the shipment whethervisible or concealed.
WARNINGAll volume water heaters must be installed inaccordance with the procedures outlined in thismanual. The warranty does not apply toheaters not installed or operated in accordancewith these procedures. Consult local buildingand safety codes before proceeding with work.The installation must conform to therequirements of the authority having jurisdictionor, in the absence of such requirements, to thelatest edition of the National Fuel Gas Code;ANS1 Z223.1, National Electrical Code ANSI/NFPA 70 and/or in Canada CAN1-B149requirement.When required by the authority havingjurisdiction, the installation must conform toAmerican Society of Mechanical Engineerssafety codes for controls and safety devices forautomatically fired heaters No. CSD-1, and inCanada CGA 3.3. Any modification to the waterheater, its gas controls, gas orifices, wiring ordraft diverter may void the Laars warranty. Iffield conditions require such modifications,consult factory.
1B. Heater IdentificationConsult rating plate on the heater. The following
example simplifies the heater identification.
1 2 3 4 5 6
PW 1670 I N 09 C
1. Basic heater model.*2. Input rate X 1000 BTU/hr.3. Indoor (I) or Outdoor (E) installation.4. Gas type: Natural (N) or Propane (P).5. Ignition system: I.I.D. (09) or continuous pilot
(16).**6. Firing rate: On/Off (C), 2-stage (K), 4-stage (L).
*Model VW water heaters for use with separatestorage tank. There must be a field installed pump tocirculate water between the heater and the storagetank.
*Model PW water heaters are basically the sameas the VW series except that the PW heaters comewith integrally mount pumps.
*Model IW water heaters are tanklessinstantaneous heaters, complete with mount pump foruse in applications having a suitable diversity in heaterload.
**Special Options: I.I.D. (04) 115 volts.Laars commercial water heaters are available in
two models: an indoor version and an outdoor version.Both are available from the factory (see Figure 1).
Figure 1. Boiler Configuration.
Pump12¼(311)
GasConn.
A
Fro
nt
Top
V
10¼(260)
295/8(752)
58(1473)
C
17(432)
28¼(718)Side
17¾(197)
RearOut In
29(737)
B
Pump(PH Models)
19(483)
GasInlet
12(305)
A
Front
30¾(781)
61(1549)
Out In
14(356)7¾
(197)
41¾(1060)Side
4(102)
LAARS HEATING SYSTEMSPage 4
1C. Flow RequirementsFor proper operation, all low volume hot water
heaters must have continuous flow through the heatexchanger when firing. The system pump must becapable of developing sufficient pressure to overcomethe resistance of the heater plus the entire circulatingsystem at the designed flow rate.
1D. Water ChemistryLaars equipment is designed for use in a wide
variety of water conditions. The water velocitymaintained in the heat exchanger tubes is kept highenough to prevent scaling from hard water and lowenough to avoid corrosion from soft water. Ninety-five percent of the urban areas in the country havewater that is compatible with this equipment, but insome areas a water supply will contain a large quantityof scaling chemicals or the water may be extremelysoft and corrosive. In rare situations the water willcontain both scaling chemicals and corrosivechemicals such as calcium or sodium chloride. Theseconditions may be the result of a nearby well orpumping station and the particular condition may notbe characteristic of the entire city water system.
If an installer observes damage from theseconditions to any water handling equipment in thearea, a factory representative should be contactedimmediately for assistance in minimizing maintenancecosts. If erosion is present, the pump impeller can bereplaced to reduce water velocity. If scaling conditionsare bad, tube cleaning maintenance schedules can beestablished to prevent tube burn-out and cracking.Neglecting the problem could mean serious damage tothe heater and water system.
Scaling can be recognized as a layer depositedon the inner walls of the tube which reduces the innerdiameter of the tube. Scale can be any color or texture;smooth or rough, granular or amorphous. Signs oferosion are generally pitting, cavitation, ridges and“islands” on the inner walls of the tubes. Since thiscondition results from extremely soft water sources, oras a result of a water softening program, the internalcopper surfaces will be extremely shiny. Otherchemicals, such as chlorine or chlorides in the water,will cause dark surfaces of erosion.
In areas where the water supply is extremelycorrosive, it is advisable to order the heater withcupro-nickel tubes in the exchanger.
Damage From Scaling, Corrosion, or Erosionis Not Covered by the Warranty.
SECTION 2.Installation
2A. Heater PlacementThe heater must be placed to provide specific
clearances on all sides for maintenance and inspection.There must also be minimum distances maintainedfrom combustible surfaces. These clearances alsoapply to non-combustible materials because the heaterrequires air circulation for proper operation.
Heater should be mounted on a level surface. Anintegral combustible flooring base is provided asstandard equipment on outdoor models. Indoor modelscan be installed on a combustible floor with a specialbase assembly which is available from the factory, orwith a base that complies with local coderequirements. See rating plate for part number of thebase assembly.
Do not install a heater on carpeting.Under the National Fuel Gas Code, ANSI
Z223.1, it is permissible to place the heater on floorsother than non-combustible when the installationcomplies with the American Insurance Code. Figures2, 3, 4 and 5 show common installation oncombustible flooring.
2B. Installation of Indoor Heaters1. Locate the water heater to provide adequate
clearance for inspection and service on all sides(see Table I). We recommend minimums of 24"from front (for proper access to and service ofcontrols) and 18" at water connection end. Foralcove installation (see Figure 6).
2. Install the heater on a waterproof floor with anadequate floor drain and a 6" minimum curb onall four sides to protect the building if heaterrepairs are required. The manufacturer will notbe held liable for any water damage inconnection with this heater.
Table 1. Minimum Boiler ClearancesFrom Combustible Surfaces.
Clearance Indoor OutdoorFrom (inches) (inches)
Top 30 unobstructWater Conn. Side 12 24Opposite Side 6 24Front Alcove UnobstructRear 8 24Vent Pipe* 6 —Hot Water Pipes Per Code Per Code
*1" when using type B Vent (refer to Manufacturer'sInstructions
Mighty Therm Volume Water Heater Page 5
Figure 2. Typical Heater Installation with Base forCombustible Floors, Example A.
Figure 3. Typical Heater Installation with Base forCombustible Floors, Example B.
Figure 4. Typical Heater Installation with Base forCombustible Floors, Example C.
Figure 5. Installation on Concrete Blocks or Tile.
* When the ceiling height exceeds 8 feet, you are only allowed toconsider 8 feet when calculating the total volume of the enclosure.
123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890
WaterHeater
12345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890
CLOSET INSTALLATION(UNACCEPTABLE)
A closet is any 4 sided enclosurewhich is less than 16* times the totalvolume of all the gas fired applianceswithin the enclosure.
ROOM INSTALLATION(ACCEPTABLE)
A room is any enclosure which is atleast 16* times greater than the totalvolume of all the gas fired applianceswithin the enclosure.
123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890
WaterHeater
ALCOVE INSTALLATION(ACCEPTABLE)
An alcove suitable for the installationof a water heater is a restricted sectionof a room not separated from theroom by a door or partition and whichmeets the minimum clearances forthe specific model water heater listedbelow.
Figure 6. Alcove Installation.
LAARS HEATING SYSTEMSPage 6
2B-1. Combustion Air Supply1. The heater location must provide sufficient air
supply for proper combustion and ventilation ofthe surrounding area as outlined in the latestedition of ANSI standard Z223.1, and any localcodes that may be applicable. Inadequatecombustion air supply may result in incompletecombustion, sooting of the heat exchanger, andunsafe operation of the heater.
2. In general, these requirements specify that smallheater rooms should be provided with twopermanent air supply openings communicatingdirectly through the wall to outside air; onewithin 12 inches of the ceiling, and the otherwithin 12 inches of the floor. Each openingshould have a minimum free area of one squareinch per 4,000 BTUH input of the total inputrating of all appliances in the enclosed area. SeeTable 2 for recommended air supply for eachmodel. An improperly ventilated equipmentroom can get excessively hot and causeaccelerated deterioration of controls andelectrical components.
IMPORTANT: In beauty shops, barber shops,cleaning establishments and self-service laundrieswith dry cleaning equipment, it is important that thewater heater be installed in a location where
combustion and ventilation air is received from asource outside the building. Please refer to the mostrecent edition of the National Fuel Gas Code, ANSIZ223.1, or in Canada, CGA requirements.
3. (a) In the United States: Exhaust Fans or Vents:Any equipment which exhausts air from theheater room can deplete the combustion airsupply or reverse the natural draft action of theventing system. This could cause flue products toaccumulate in the heater room. Additional airmust be supplied to compensate for such exhaust.The information in Table 2 is not applicable ininstallations where exhaust fans or blowers ofany type are used. Such installations must bedesigned by qualified engineers.(b) In Canada: Follow Canadian standard,CANI-B149or local codes.
4. If a blower or fan is used to supply air to theheater room, the installer should make sure itdoes not create drafts which could causenuisance shutdowns of the pilot. If a blower isnecessary to provide adequate combustion air tothe heater, a suitable switch or equivalent mustbe wired into the heater control circuit to preventthe heater from firing unless the blower isoperating.
5. The heater must be completely isolated andprotected from any source of corrosive chemicalfumes such as trichlorethylene, perchlorethylene,chlorine, etc.
2B-2. Venting1. Laars heaters have built-in draft diverters for
natural draft operation and must not beconnected to any portion of a mechanical draftsystem under positive pressure. The flue outletmust be connected to a clear, unobstructed ventof adequate capacity ending above the highestpoint of the building with an approved vent cap.The venting system should be installed accordingto the latest edition of ANSI Z223.1 and/or, inCanada, CAN1-B149 requirement and any localcodes having jurisdiction.
IMPORTANT NOTE: Do not use sheet metalscrews at the snap lock joints of Type B gas vents.
2. Do not weld or fasten the vent pipe to the heaterdraft hood. The weight of the stack must not reston the heater. The draft hood and heater top mustbe easily removable for normal heater serviceand inspection.
3. Avoid using long horizontal runs of the ventpipe, and too many 90° elbows, reductions orrestrictions. Horizontal runs should have at leasta 1/4" rise per foot in the direction of flow. Avent connector should be supported for thedesign and weight of the material used to
Table 2. Minimum RecommendedAir Supply to Boiler.
Heater Each Opening*Model (Square Inches)
500 125600 150715 179850 213
1010 2531200 3001430 3581670 4181825 457
*Net Free Area in Square Inches
Area indicated is for one of two openings; one atfloor level and one at the ceiling, so the total netfree area could be double the figures indicated.For special conditions refer to the latest edition ofANSI Z223.1.
Consult factory if not communicating directlythrough the walls with the outdoors.
Note: Check with louver manufacturers for netfree area of louvers. Correct for screenresistance to the net free area if a screen isinstalled. Check all local codes applicable tocombustion air.
Mighty Therm Volume Water Heater Page 7
maintain clearances and prevent physical damageand separation of joints.
4. Avoid ending heater vents near air conditioningor air supply fans. The fans can pick up exhaustflue products from the heater and return theminside the building, creating a possible healthhazard. A minimum of 4 feet horizontal distancemust be maintained from electrical meters, gasmeters, and relief equipment.
5. Always use double-wall or insulated vent pipe(Type B or equivalent). In cold weather,uninsulated outside vents can chill the rising flueproducts, blocking the natural draft action of theventing system. This can create a health hazardby spilling flue products into the heater room.
6. Avoid oversize vent piping or extremely longruns of the pipe which may cause excessivecooling and condensation. Rule of Thumb: Thetotal length of the vent, including the connectorand any offset, should not exceed 15 feet forevery inch of vent diameter. Longer total lengthsshown in venting tables are based on maximumcapacity, not condensation factors.
7. When the installation of a draft fan is necessaryin connecting a venting system to a Laars heater,the installation should be engineered bycompetent personnel following good engineeringpractices. The draft fan supplier should beconsulted for correct size. The installation shouldbe in accordance with the latest edition of ANSIZ223.1 and/or, in Canada, CAN1-B149requirement and any local codes havingjurisdiction. When a draft fan is installed, asuitable draft switch must be wired into theheater control circuit at terminal designated“Field Interlock” to prevent firing of the heaterunless a positive draft has been established.
2C. Installation of Outdoor Heaters1. Locate the heater to provide the minimum
clearances as listed in Table 1, “Placement ofHeater”.
2. Do not place the heater in an enclosure or wallrecess. Avoid locations where wind deflectionoff structures might cause down draft. Whensuch wind conditions are possible, place theheater at least three (3) feet from the structures.
3. Never install the heater under any kind of roofoverhang. Do not place the heater below oradjacent to any doors, windows, louvers, grills,etc. which connect in any way with an inhabitedarea of a building. This includes other structuressuch as garages or utility rooms (see Figure 7).
4. Although these models are AGA and CGAdesigned certified for outdoor installations, suchinstallations are not recommended in areas where
Figure 7. Incorrect Outdoor Installation.
the danger of freezing exists unless properprecautions are taken for freeze protection.
2D. Gas Supply and PipingReview the following instructions before
proceeding with the installation.
1. Verify that the heater is fitted for the proper typeof gas by checking the rating plate. Laars heatersare normally equipped to operate below a 2000foot altitude. Heaters equipped to operate athigher altitudes have appropriate stickers or tagsattached.
2. Use the figures in Table 3 to provide adequategas piping from the gas meter to the heater.
3. A trap (drip leg) must be provided ahead of thegas controls (see Figure 8 ). A manual gasshutoff valve must also be provided for serviceconvenience and safety. Check the local codes.
Table 3. Gas Piping Sizes.
Distance from Gas Meteror Last Stage Regulator
Size 0-100' 100-200' 200-300'
50060071585010101200143016701825
1-1/2"1-1/2"
2"2"2"
2-1/2"2-1/2"2-1/2"2-1/2"
2"2"2"
2-1/2"2-1/2"
3"3"3"3"
2"2-1/2"2-1/2"2-1/2"
3"3"3"3"
3-1/2"
Note: These figures are for Natural Gas (.65 Sp. Gr.), and arebased on 1/2" water column pressure drop. Check supplypressure with a manometer, and local code requirements forvariations. For LPG, reduce pipe diameter one size, but maintaina 1" minimum diameter. A normal number of Tees and elbowshave been taken into allowance.
LAARS HEATING SYSTEMSPage 8
4. The boiler and its individual shutoff valve must bedisconnected from the gas supply piping systemduring any pressure testing of that system at testpressures in excess of 1/2 psig. The boiler mustbe isolated from the gas supply piping system byclosing its individual manual gas shutoff valveduring any pressure testing of the gas supplypiping system at test pressures equal to or lessthan 1/2 psig.
5. Provide gas supply pressure to the heater asfollows:
Natural Gas LPG
Min. (inches water column)
Max. (inches water column)
Note: The heater and all other gas appliancessharing the heater gas supply line must be firing atmaximum capacity to properly measure the inletsupply pressure. Low gas pressure could be anindication of an undersized gas meter and/orobstructed gas supply line.
6. The correct burner manifold gas pressure isstamped on the rating plate. The regulator ispreset at the factory and normally requires nofurther adjustment.
7. The gas manifold and control assembly wastested and conform to the safe lighting and otherperformance criteria specified in the latesteditions of ANSI Z21.13 and CGA 3.3 LowPressure Boiler Standard.
8. Before operating the boiler, the complete gassupply system and all connections must be testedfor leaks using a soap solution. Do not use rawflame.
Figure 8. T-Fitting Sediment Trap Installation.
Per Rating Plate
9 14
CautionSince some leak test solutions (including soapand water) may cause corrosion or stresscracking, the piping must be rinsed with waterafter testing, unless it has been determinedthat the leak test solution is noncorrosive.
2E. Electrical Wiring
WARNINGThe heater must be electrically grounded inaccordance with the most recent edition of theNational Electrical Code, ANSI/NPA 70. InCanada, all electrical wiring to the heatershould be in accordance with the CanadianElectrical Code, CSA C22.1 Part 1. Do not relyon the gas or water piping to ground the metalparts of the heater. Oftentimes, plastic pipe ordielectric unions isolate the heater electrically.Service and maintenance personnel who workon or around the heater may be standing onwet floors and could be electrocuted by anunderground heater.
1. Check heater wiring and pump for correctvoltage, frequency and phase. If the pump circuitis other than 115V, check to see that the heater isprovided with an appropriate transformer.
2. Wire the heater and pump exactly as shown inthe wiring diagram supplied with the heater.
3. The pump and heater must be electricallyinterlocked so the heater cannot come on unlessthe pump is running.
4. All field installed electrical safety devices and allfield installed devices (draft switches, relays,timers, outdoor temperature reset devices, etc.)can be connected to the heater wiring at pointsshown in the wiring diagram designated “FieldInterlock”.
2F. Water Piping of System1. Be sure to provide valves at the inlet and outlet
of the boiler so it can be readily isolated forservice. A butterfly or similar type of valve isrecommended.
2. The pressure relief valve installed in the tappedopening provided in the outlet header (seeFigure 9), must be piped, but not fastened, to adrain or floor sink. The drain pipe must be thesame size as the valve outlet and must pitchdownward from the valve.
Mighty Therm Volume Water Heater Page 9
Special attention must be given to relief valvesettings in installations where the heater islocated on the ground floor of a tall building.The static pressure of the system is elevated andcould cause the relief valve to leak. Where nospecial setting of the relief valve is ordered, thefactory will furnish a 125 psi setting. Neverreduce the relief valve openings.
3. Pressure relief valve lever must be tripped atleast once a year to insure that waterways areclean. When manually operating lever, water willdischarge through drain line. Precautions must betaken to avoid contact with hot water and waterdamage.
4. The weight of all water and gas piping should besupported by suitable hangers or floor stands.
5. Check piping diagrams with local applicableplumbing, heating and building safety codes.
6. All two-temperature systems using temperaturevalves must have forced recirculation in the lowtemperature building loop.
7. A check valve installed at the hot water inlet tothe tempering valve will prevent cold water frombeing drawn in reverse through the temperingvalve into the hot water.
8. When installing a tempering valve, place atbottom of antithermosyphon loop at least 24"high to prevent excessive hot water fromentering mixed water supply. Bring the coldwater supply up from the floor to the valve (seeFigure 10).
2G. Water ExpansionWhen cold water is heated the water expands. If
no water is being used during the heat-up period theexpanded water will normally back up into the citymains.
A water pressure reducing valve installed in theincoming cold water line may act as a check valve andprevent the expanded water from moving backward.This will cause pressure to rise in the heater, whichwill be relieved by the pressure relief valve.
If the relief valve pops frequently a mineraldeposit may build up on the valve seat, causing it toleak.
The following suggestions may solve the problem:
1. Install a properly sized expansion tank.
2. Replace the installed water pressure reducing valvewith a suitable valve having a back flow port. Thesevalves have a back flow port which allows waterto flow backwards when the pressure in the systemexceeds the pressure in the mains.
3. Install a check valve around the pressure reducingvalve to permit reverse flow. This will allowthe expanded water to back flow into the mains.
4. Install an auxiliary small relief valve set at 25 psiless than the main relief valve. The valve must bepiped to a drain and may require occasionalcleaning. It will bleed off the expanded waterand protect the main pressure relief valve frombecoming fouled.
Figure 9. Pressure Relief Valve Location.
Figure 10. Tempering Valve Installation.
LAARS HEATING SYSTEMSPage 10
2H. Pump Performance and Installation1. The factory provided pump on PW heaters and
the recommended field provided pump formodel VW heaters are sized to provide propercirculation through the heater and heater-to-tank circulation loop (see Figures 11 and 12). Ifthe heater-to-tank circulating loop does notcontain more than 6 elbows or 30 feet ofpipe, use pipe fittings in the loop no smallerthan the following:
Model Pipe Size
500 through 850 2"1010 through 1825 2-1/2"
If the heater-to-tank circulating loop containsmore than 6 elbows or 30 feet of pipe, use pipeor fittings in the loop no smaller than thefollowing:
Model Pipe Size
500 through 850 2-1/2"1010 through 1825 3"
To assure free circulation, do not use globevalves, side outlet tee connections or otherrestrictive fittings in heater-to-tank loop.
2. The Model IW heater is designed for use in asystem without a hot water storage tank. The hotwater supply line to usage point must have areturn leg to the heater (see Figure 13, 14 and15). A built-in circulating pump and internal heatexchanger bypass maintains the heater in astandby condition. It also maintains thetemperature at the controller setting of the waterin the entire building circulating loop whether ornot there is any use of hot water.
A separate circulating pump is required forcirculation of water in the building loop. Thecontrol system provides variable heat inputs tomatch periods of higher or lower waterconsumption.
3. The Model IW heater requires a minimum ofcirculating hot water in the building circulationloop. To prevent excessive temperaturefluctuations in the delivered water, the wholebuilding system, including the return loop, musthave the equivalent volume of pipe shownbelow:
MinimumReservoir Equivalent Pipe
Model IW Gallons* Size and Length
500 through 850 ...............6.3 ................. 1 1/4" x 100 ft.1010 through 1220 .........10.2 ................. 1 1/2" x 100 ft.1430 through 1670 .........17.0 ....................... 2" x 100 ft.1825 ................................ 27.0 ................. 2 1/2" x 100 ft.
* The gallons shown are the calculated volumes of the pipes.
4. Model VW, PW and IW heaters are not suitablefor heating swimming pools or any otherapplication where temperature of the waterflowing through the heater remains below thedew point (110°F).
In applications requiring the rapid use ofmeasured volumes of water, the recovery of theheater between the time intervals of use mustequal the volume used. See the recovery table inthe current Document 2045 (Submittal Data).
5. Pump Sizing: A suitable pump must be field-provided for circulation of water between ModelVW heaters and the storage tank. This pumpmust be sized to avoid excessive temperature riseand to provide correct flow for water hardnessconditions. Specifications in Table 4 includeallowance for 30 feet of piping and normalfittings between heater and tank.
6. Install pump in a cool location. When pump isinstalled where it is subjected to excessive heat,the life of the pump will be shortened. Heat willembrittle motor insulation and dry out bearinglubricants. If the pump motor is equipped withthermal protection, excessive heat may trip thethermal switch and shut down the pumpintermittently. This could result in rapid scalingof the heater.
IMPORTANT: Check oil level in pump beforestarting. Oil pump every three (3) months. Fill bearingassembly to lower level of overflow vent. Add five (5)or six (6) drops of oil to front and rear of motor. Use20W non-detergent oil. Pumps located in excessivelyhot or dusty locations should be oiled once a month.Self lubricating pumps do not require oiling.
7. The pump should be accessible for lubrication,inspection and service.
8. If pump is designed for floor mounting, installsecurely on concrete block or pad at least six (6)inches above floor level. This will preventflooding of motor when floor is washed. Be surethat floor mounted pumps are not suspendedfrom piping and that piping is plumbed to avoidstrain on the pump casing.
Mighty Therm Volume Water Heater Page 11
Figure 11. Hot Water Supply System (Model VW & PW).
WithVertical
Tank
WithHorizontal
Tank
NOTES:Heavy line indicates Heater to Tank Circulating Loop.
LAARS HEATING SYSTEMSPage 12
CAUTION:1. This piping arrangement is required on split systems to provide constant hot water temperatures.2. Pipe size and length must conform to the recommendations for each heater model.3. A loop circulator is required to maintain forced circulation in the building hot water piping system.
Figure 13. Split System Piping Diagram, Model IW.
Figure 12. Hot Water Supply System Using Model PW with Dual Tanks, Building Loop Return and Circulating Pump.
Mighty Therm Volume Water Heater Page 13
Figure 15. Single Installation Piping Diagram, Model IW.
Figure 14. Dual Installation Piping Diagram, Model IW.
NOTES:1. All water connections 2" N.P.T. models.2. Drain valve per ASME requirements.3. A loop circulator is required to maintain forced circulation in the building hot water piping system.
NOTES:1. All water connections 2" N.P.T. models.2. Drain valve per ASME requirements.3. A loop circulator is required to maintain forced circulation in the building hot water piping system.
LAARS HEATING SYSTEMSPage 14
Figure 16. Two-Temperature Hot Water Supply System (Model VW or PW).
WithVertical
Tank
WithHorizontal
Tank
LegendB - Check Valve in Hot Water Supply
to Tempering ValveC - Check Valve in Return Line from
Building LoopD - Tempering ValveE - Venturi (Suction) TeeH - Throttling Valves in Building Loop
ReturnsI - Circulating Pump for 180° Building
LoopJ - Circulating Pump for 140° Building
LoopK - Service Valves to Isolate Heater
and Pump for Service
LegendB - Check Valve in Hot Water Supply
to Tempering ValveC - Check Valve in Return Line from
Building LoopD - Tempering ValveE - Venturi (Suction) TeeH - Throttling Valves in Building Loop
ReturnsI - Circulating Pump for 180° Building
LoopJ - Circulating Pump for 140° Building
LoopK - Service Valves to Isolate Heater
and Pump for Service
Mighty Therm Volume Water Heater Page 15
Figure 17. Two-Temperature Hot Water Supply System with Vertical Tank for Models VW and PW Water Heaters.
LegendB - Check ValveC - Check ValveD - Tempering ValveH - Throttling Valves in Building Loop ReturnsJ - Circulating Pump for Return LoopK - Service Valves to Isolate Heater and Pump
for Service
LAARS HEATING SYSTEMSPage 16
2I. Water PressureIt is very important that water pressure in the
system be maintained above 30 psi. If the systempressure should drop below this, the vapor pressure ofwater in the suction side of the pump can causehammer and cavitation in the pump and damage theheater through lack of water circulation. If for anyreason the water supply is turned off temporarily toservice a piece of equipment, the manual gas valveon the Model IW should be closed until the waterpressure has been restored and the lines bled ofaccumulated air. If the heater fails to fire when it isturned back on, it may be airlocked. To eliminate theairlock, open the pressure relief valve and allow air tobleed out until water flows. As soon as full circulationis resumed, the entrained air will be carried outthrough the hot water faucets.
2J. Tank Installation1. Be sure the floor is waterproof and structurally
capable of supporting the tank when it is filledwith water.
2. The tank should be placed so that manholes,inspection covers, nameplates and drain valvesare accessible.
3. Be sure the tank is suitable for the water in thesystem. Some water is corrosive and requires aprotected tank with a special lining.
4. If the tank is glass-lined, it should be equippedwith a suitable magnesium anode. It is goodpractice to replace the anode when it isapproximately 50% used. The factory warrantyon a glass-lined tank will be void if a satisfactoryanode is not in place at the time of a failure or ifit is consumed by cathodic action.
5. Make sure the tank connections in the heater-tank circulating loop are the proper size as listedin Section 2H. If tappings are smaller than therecommended pipe size, a larger pump may berequired. Consult the factory if in doubt.
6. Install a pipe in the tank drain fitting that goes toa floor sink, and install a drain valve. If a floorsink is not available, install a hose bib.
7. Hot water tanks in an existing installation arelikely to have a deposit of silt on the bottom.Therefore, it is important to extend the pumpsuction pipe in the tank to a position near the top.Pipe the return from the heater to the bottom ofthe tank.
2K. Two-Temperature SystemSee Figures 16 and 17 for piping schematics.
This system is designed to maintain the temperedwater circulating loop at the desired temperatureduring idle periods as well as when there is a demandfor hot water. It is recommended for general purposewater supply including shower and bathingapplications. Water at 180°F is available directly fromthe tank.
SECTION 3.Operation
3A. Controls - General1. Electronic Ignition Controls:
a. Intermittent Ignition:
Pilots are automatically lit when theoperating aquastat calls for heat (System #9and #4)
The unit performs its own safety check andopens the main valves only after the pilot is
Flow Head* Temp. Rise Water Rate Loss Across
Model Category (GPM) (ft.) Heater, (°F)
Soft 45 5.0 17500 Normal 68 9.9 11
Hard 90 15.7 8
Soft 45 5.1 20600 Normal 68 10.0 14
Hard 90 15.9 10
Soft 45 5.3 24715 Normal 68 11.0 16
Hard 90 17.8 12
Soft 45 5.4 30850 Normal 68 11.1 20
Hard 90 18.1 15
Soft 45 3.9 351010 Normal 68 7.5 23
Hard 90 11.7 18
Soft** 68 7.8 271200 Normal 68 7.8 27
Hard 90 12.2 21
Soft** 68 8.1 321430 Normal 68 8.1 32
Hard 90 12.6 24
Soft** 68 8.3 371670 Normal 68 8.3 37
Hard 90 13.0 28
Soft** 90 13.5 301825 Normal** 90 13.5 30
Hard 90 13.5 30
Water Category Grain Hardness per Gal. Soft 1 through 7.5 Normal 7.6 through 17 Hard Over 17
* Pressure drop includes loss through 30 feet of pipe and normal fittings whenheater is installed with storage tank. Pipe and fittings are assumed to be 2" onModels (500-850) and 2 1/2" on Models (1010-1825)
** To prevent erosion, these models must be ordered with cupro-nickel heatexchanger tubes.
Table 4. Pump Performance Requirements.
Mighty Therm Volume Water Heater Page 17
proven to be lit. Whenever the pilot flame isinterrupted, the main gas valve closes within0.8 seconds.
b. Electronically Supervised Standing PilotSystem (System #16):
When pilot flame fails, the ignition controlmodule responds in less than 0.8 secondsand provides 100% safety shutdown.
2. Operating Controls:
a. Electrically Operating Controls:
Single, two-stage, four-stage or modulatingaquastats are provided in models VW, PWand IW heaters to control the desiredservice water temperature. The temperaturesensing bulb is located in the heater inlet.
b. Modu-snap Valves:
These valves are furnished in addition tothe main electric gas valve when heater isordered with mechanical modulation. Eachvalve has a remote capillary bulb immersedin a well at the outlet header to maintain aconstant outlet temperature. Consult Table5 for desired temperature setting.
3. High Limit Controls:
The manual reset high limit switches areprovided as standard equipment on all heaters.Automatic reset switches are optionally
provided. The temperature sensing bulb of theswitch is always located in the heater outlet.Burners will automatically shut down wheneveroverheating of water occurs.
4. Flow Switch:Standard on all models: Models VW and PW, theswitch is mounted in the outlet “tee” connection.Model IW, the switch is mounted directly in theheader outlet. The flow switch shuts down allburners in case of low water condition or pumpfailure.
5. Low Water Cut Off:The low water cut off automatically shuts offheater whenever water level drops below probe.Located at heater inlet (model IW and PW) andat return header (model VW).
3B. Initial Start-UpBefore placing the heater in operation, be certain
that the heater is filled with water and all air is purgedfrom the system. Once the heater is connected to the
Figure 18. Single Installation Piping Diagram, Model IW.
Dial No. 1 2 3 4 5 6 7 8 9+
Temp °F 120 128 135 143 150 158 165 173 180+
Table 5. Modu-Snap Temperature Settings.
LAARS HEATING SYSTEMSPage 18
gas supply, the automatic safety shutoff devices mustbe checked.1. Before beginning the tests, make sure the main
manual gas valve, and any other heater firingvalves are in the “OFF” position.
2. Make sure the heater’s power switch is in the“ON” position. After placing the manual pilotgas valve in the open position and resetting allsafety devices, (high limit, pressure switch, low-water cutoff, etc.) pilot(s) can be lit following theprocedure located on the heater rating plate.
3. Once the pilot(s) is lit and has been establishedfor five minutes, the flame failure response timeshould be checked as follows:Systems 9 and 4 - (Intermittent ignition): With
this system pilots are automatically lit when theoperating controls call for heat. If the pilot flame failsfor any reason, the main valve is shut off within onesecond and the pilot spark ignition is initiated until thepilot flame has been reestablished. On propanesystems, unit locks out for safety. This sequenceshould be checked by turning off the manual pilot gasvalve, and, at the same time, monitoring the audiblesparking at the pilot burner and signal interruption tothe main valve.
CautionPropane gas is heavier than air and sinks tothe ground. Exercise extreme care in lightingthe heater when so equipped.
System 16 - (Electronically supervised standingpilot system): Extinguish the pilot flame by placingthe manual pilot valve in the closed position, and atthe same time, begin recording the time it takes for theoutput signal from the electronic ignition control to beinterrupted. The signal interruption can be detectedeither with a test light or a voltmeter. The responsetime should never exceed one second.
4. With the pilots lit, initial activation of the mainburners can be achieved by slowly opening themain manual valve. The result should be asmooth lighting of the main burners.
Hi-Limit Checkout:After running the heater for a long enough
period, bring the water temperature within the range ofthe hi-limit and slowly back off the high limit settinguntil the heater shuts off. The main burners shouldreignite when the hi-limit is reset and turned back upto its original setting. The heater should now run untilit shuts off automatically on operating aquastat.
3C. To Start Up System:1. Start Up BoilerBe certain system pump is running, then proceed
as follows:
a. Turn off main electrical switch.b. Turn off all manual gas valves and wait five
minutes (see Figure 19).c. Set operating control to lowest setting.d. Slowly turn manual gas valve to “ON”.e. Reset all safety valve switches (manual reset
high limit and low water cut off).f. Open manual pilot valve. Turn on main electrical
switch.g. Set temperature controller to desired
temperature. Pilot will light automatically toignite main burners whenever the aquastat callsfor heat.For standing pilot system, press on pilot relay
knob, see Figure 20, light pilot and keep relay knob
Figure 19. Gas Manual Valves.
Figure 20. Pilot Safety Relay.
Mighty Therm Volume Water Heater Page 19
depressed for one minute then release. Once the pilotis lit, the power is supplied through the aquastat to themain gas valve.
2. To set the temperature and high-limit controls:When using a tank aquastat:Set the tank aquastat to the desired tank
temperature. Set the heater temperature control 20°Fhigher than tank aquastat. Set the manual reset highlimit 50°F higher than tank aquastat. Example: Ifdesired temperature is 140°F, set the tank aquastat at140°F, set the heater temperature control at 160°F, andset the manual reset high limit at 190°F. If the heateris equipped with a pump time delay, the three-positionswitch on the side of the heater can be put into the“Auto Pump” pposition, so that the pump will onlyrun when the tank aquastat calls for heat. then, whenthe call for heat is satisfied, the heater will turn off,but the pump will run for the set amount of delay time(adjustable between 0.1 and 10 minutes).
When a tank aquastat is not used:The pump on the heater must run continuously,
so the heater's temperature control will sense the tank'swater temperature. Set the heater temperature controlto the desired tank temperature. Set the manual resethigh limit 50°F higher than the heater temperaturecontrol. Example: If desired temperature is 140°F, setthe heater temperature control at 140°F, and set themanual reset high limit at 190°F.
3D. To Turn Off Heater:1. Turn off main electric switch.2. Close all manual gas valves.
3E. To Shut Down System:To shut down heater, turn off all manual gas
valves and electrical disconnect switches. Wheneverdanger of freezing exists, shut off water supply andremove drain plug in the bottom of front header cover.Drain every part of system subject to freezingtemperature.
SECTION 4.Maintenance1. Lubricate the water circulating pump (see
instructions found on the pump).
2. If a strainer is employed in a pressure reducingvalve or in piping, clean it every six (6) months.
3. At start-up and every six (6) months thereafter,the pilot and main burner flame should beobserved for proper performance (see Figure 21).See attached lighting and shut-down instructionsfor proper pilot flame pattern). If flame has the
appearance of “sooting” tips, check for debrisnear orifices. Call serviceman.
4. Inspect the venting system for obstruction,leakage and corrosion at least once each year.
5. Keep heater area clear and free from combustiblematerial, gasoline and other flammable vaporsand liquids (see Table 1 for minimumclearances).
6. Be certain all combustion air and ventilationopenings are unobstructed.
7. Check for fouling on the external surfaces of theheat exchanger every six months. (NOTE: Afterinstallation and first start-up, check the heatexchanger for fouling after the following periodsof operation: 24 hours, 7 days, 30 days, 90 days,and once every six months thereafter).
Fouling on the external surfaces of the heatexchanger is caused by incomplete combustionand is a sign of combustion air and/or ventingproblems. As soon as any fouling is observed,the cause of the fouling should be corrected (seeSection 5, Troubleshooting Guide). The heatexchanger can be checked by locating a mirrorunder the burners with a flashlight. An alternatemethod is to remove the venting and top panel asnecessary to inspect from above. Also check thevent system for defects at this time.a. If cleaning is required, shut off all electrical
and gas supply to the heater.b. To expose the heat exchanger:Indoor Models:Remove flue pipe, top of unit, rear upper jacket,flue collector rear panel and heat exchangerbaffles.Outdoor Models:Remove vent top assembly, rear upper jacket,flue collector rear panel and heat exchangerbaffles.c. Remove all burners:It is usually more convenient to remove theburner tray assembly. Disconnect sensor wire,ignition cable (or thermocouple generator) andpilot gas line. Disconnect manifold inletunion(s). Remove the four (4) retaining screws.Grasp burner/pilot assembly firmly at the front.Push it back, disengaging it from the gas orifice.
Figure 21. Main Burner Flame Pattern.
LAARS HEATING SYSTEMSPage 20
Lower the front of the burner (to avoid damagingpilot shield) then remove the burner tray.
CautionBlack carbon or green soot on a dirty heatexchanger can, under certain conditions, beignited by a random spark or open flame. Toprevent this unlikely occurrence, dampen thesoot deposits with wet brush or fine waterspray before servicing or cleaning the heatexchanger.
With a wire brush, remove soot and loose scalefrom heat exchanger. Clean fallen debris frombottom of heater. Make sure burner ports areclear and pilot assembly is free of debris.d. Reassemble in reverse order:Be sure the heat exchanger baffles are replaced.
8. The gas and electric controls installed on heatersare engineered for both dependable operationand long life, but the safety of this equipmentcompletely depends on their proper functioning.It is strongly recommended that the basic itemsbe checked by a competent serviceman everyyear and replaced when necessary. The basiccontrols are:a. Water temperature controls.b. Pilot safety system.c. Automatic electric gas valve(s).d. Flow sensing safety device.
9. Low water cutoffs should be inspected every six(6) months, including flushing of float types.
NOTE: Warranty does not cover any damagecaused by lack of required maintenance or improperoperating practices.10. Both modulating and stage valve are adjusted at
the factory for minimum permissible rates andshould not be readjusted.
SECTION 5.Troubleshooting and Analysis ofService Problems1. For proper service and problem diagnosis of the
heater and heater system, the following tools arerequired:a. Gas pressure test kit with range from zero
to 14 W.C. Either a slack tub manometer oran accurate gas pressure gauge isacceptable with proper adapters which willconnect to the available fittings in the lineand on the gas valve.
b. Multi-meter with the following ranges:0 to 500 volts A.C.0 to 1000 ohms continuity.
c. Tube cleaning kit consisting of reamer,stainless steel brush, speed handle andhandle extensions.
d. Heater thermometer (with 1/2" NPT well)100-240°F.
2. In addition, the heater should be equipped with asystem pressure gauge with proper ranges forheater operation.
I. HEATER WILL NOT FIRE.
Possible Cause What To Do
A. Electric power is off A. Check to see that main powerswitch is “ON.” Use testingdevice to trace power toheater junction box.
B. Operating or safety control B. Turn off power. Use continuityhas opened circuit to electric across terminals of eachgas valve. operating and safety control
switch up to the electric gasvalve. Replace effectivecontrol.
C. Pilot flame is out. C.Relight pilot per instruction.
D. Manual reset device has D.Follow instructions for start-tripped. up. Reset Pilot safety and all
manual reset safety switchesand reset manual safety gasvalve.
E. No gas pressure to burners. E. Trace gas line to serviceshutoff cock. If service cock isopen, trace gas line to meter.If no pressure is present atmeter, call for public utilityservice. If gas is present inheater inlet, check pressuresin following sequence:(1) downstream from pressureregulator. (2) downstreamfrom electric gas valve.Replace or adjust asnecessary.
F. Electric gas valve operator is F. Disconnect wiring harness atburned out or shortened. gas valve terminals. Check
continuity to actuator coil. Ifopen circuit or short isindicated, replace coil oroperator.
Mighty Therm Volume Water Heater Page 21
II. HEATER IS POUNDING, KNOCKING OREMITTING STEAM FROM RELIEF VALVES.
Possible Cause What To Do
A. Low or no water flow. A. This condition is usuallycaused by lack of adequatewater flow through heater.Check the following:1. Is the heater wired into thepump circuit so that the heatercannot fire unless the pump isrunning?2. Check to see that all valvesin system are open to be surethat water can circulatethrough the heater and thesystem.3. If the system has automaticwater valves (2-way or 3-way)that can cut off the water flowthrough the heater check tosee that they are equipped withend-switches which shut theheater down when the waterflow through the heater isreduced by 70% from full flow.4. Examine pump for cloggedimpeller.
B. Low or no system pressure. B. Clean strainer in pressurereducing valve. Look for closedvalve water line or a leak in thesystem.
C. Clogged “Y” strainer. C. Remove strainer element andclean screen.
D. Debris from system piping D. Remove header covers.is blocking tubes. Examine all tubes and
waterways. Use new gasketswhen reassembling. Cleanout tubes.
E. Scale has formed in tubes. E. This is always caused by theinflow of raw water into thesystem. Clean tubes with tubecleaning kit. Determinehardness. Check water flow,replace pump for modifiedflow if necessary.
IV. PRESSURE RELIEF VALVES LEAKINGINTERMITTENTLY OR STEADILY.
Possible Cause What To Do
A.Static pressure in system A. Calculate height of water inexceeds setting of relief valve. system above heater. Install
new valve with psi setting 25%above required static systemworking pressure. Do notexceed 160 psi.
B. Expansion tank is water- B. Drain expansion tank, thenlogged (if installed). reopen it to the system. Look
for leaks in expansion tank orfittings. Calculate requiredvolume of expansion tank inrelation to system to determineif tank is adequate.
V. SOOT IN FLUEWAYS OR IN TUBES, ORNOXIOUS FUMES INDICATIVE OF BADCOMBUSTION.
Possible Cause What To Do
A. Combustion air supply to A. Check air supply opening.heater room is inadequate. Look for debris in screen or
louvre which coverscombustion air opening, or formaterial blocking the opening.
B. Stack or vent is blocked or B. Look for blocked stack andrestrictive. excessive number of elbows in
stack or excessive length ofhorizontal runs.
C.Severe down draft is causing C.Check for (1) proper vent capspillage of flue products into on stack; (2) adequate heightroom. of stack above roof;
(3) equipment exhausting airfrom inside of building; and(4) proper installation of draftdiverter.
D.Gas pressure to burners is D.Check gas pressure withexcessive. nanometer, and adjust with
heater firing at full rate.
E. Heater not fitted for the fuel E. See nameplate for correct fuel.supplied.
F. Heater installed at high F. Installations at altitudes inaltitude without proper excess of 2000 ft. above seaderating. level are subject to jurisdiction
of the local inspectionauthorities.
III. WATER DRIPPINGIN FIREBOX.
Possible Cause What To Do
Tube in heat exchanger has A tube failure is almost alwaysoverheated and ruptured. caused by (a) scale formation
in the tube or (b) inadequatewater flow through the boiler.
LAARS HEATING SYSTEMSPage 22
Key
Des
crip
tion
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
No
50
06
00
71
58
50
1010
1200
1430
1670
1825
1To
p P
anel
Ass
embl
y1
05
35
70
11
05
35
70
21
05
35
70
31
05
35
70
41
05
35
70
51
05
35
70
61
05
35
70
71
05
35
70
81
05
35
70
9
2S
pace
r, F
lue
Col
lect
or—
—1
05
40
80
01
05
40
80
01
05
40
80
01
05
40
80
01
05
40
80
01
05
40
80
0
3E
nd P
anel
, F
lue
Col
lect
or (
left)
10
53
37
00
10
53
37
00
10
53
37
00
10
53
37
00
10
53
37
00
10
53
37
00
10
53
37
00
10
53
37
00
10
53
37
00
4E
nd P
anel
, F
lue
Col
lect
or (
right
)1
05
33
80
01
05
33
80
01
05
33
80
01
05
33
80
01
05
33
80
01
05
33
80
01
05
33
80
01
05
33
80
01
05
33
80
0
5R
ear
Pan
el,
Flu
e C
olle
ctor
10
53
55
01
10
53
55
02
10
53
55
03
10
53
55
04
10
53
55
05
10
53
55
06
10
53
55
07
10
53
55
08
10
53
55
09
6R
ear
Pan
el, E
xt.,
Flu
e C
olle
ctor
——
——
——
——
——
——
——
——
——
——
——
——
—N
ot R
equi
red—
——
——
——
——
——
——
——
——
——
—
7F
ront
Sup
port
, F
lue
Col
lect
or1
05
34
40
11
05
34
40
21
05
34
40
31
05
34
40
41
05
34
40
51
05
34
40
61
05
34
40
71
05
34
40
81
05
34
40
9
8Ti
le C
over
, Fro
nt &
Rea
r1
05
34
20
11
05
34
20
21
05
34
20
31
05
34
20
41
05
34
20
51
05
34
20
61
05
34
20
71
05
34
20
81
05
34
20
9(2
)(2
)(2
)(4
)(4
)(4
)(4
)(4
)(4
)
9B
affle
, Hea
t Exc
h. (
Frt
& R
ear)
10
53
43
01
10
53
43
02
10
53
43
03
10
53
43
04
10
53
43
05
10
53
43
06
10
53
43
07
10
53
43
08
10
53
43
09
(2)
(2)
(2)
(4)
(4)
(4)
(4)
(4)
(4)
10,1
1 B
affle
, H
eat
Exc
hang
er1
05
34
60
11
05
34
60
21
05
34
60
31
05
34
60
41
05
34
60
51
05
34
60
61
05
34
60
71
05
34
60
81
05
34
60
1(7
)(1
4)(1
4)(1
4)(1
4)(2
8)(2
8)(2
8)(1
4)—
——
——
——
——
——
——
——
—1
05
34
60
2(1
4)
12
Ret
urn
Hea
der
(S-0
0981
)1
03
64
30
01
03
64
30
01
03
64
30
01
03
64
30
01
03
64
30
01
03
64
30
01
03
64
30
01
03
64
30
01
03
64
30
0R
etur
n H
eade
r (S
0064
2)
B
ronz
e10
3643
0110
3643
0110
3643
0110
3643
0110
3643
0110
3643
0110
3643
0110
3643
0110
3643
01
13In
let/O
utle
t Hea
der
(S-0
0943
)10
3645
0010
3645
0010
3645
0010
3645
0010
3645
0010
3645
0010
3645
0010
3645
0010
3645
00In
let/O
utle
t Hea
der
(S00
640)
1036
4501
1036
4501
1036
4501
1036
4501
1036
4501
1036
4501
1036
4501
1036
4501
1036
4501
Bro
nze
14F
lang
e, 2
" (S
0063
6)10
3913
0210
3913
0210
3913
0210
3913
02—
——
——
——
——
—F
lang
e, 2
1/2
“ (
S00
635)
——
——
——
——
1039
1303
1039
1303
1039
1303
1039
1303
1039
1303
Fla
nge,
2 1
/2"
(S00
644)
, Bro
nze
1039
1304
1039
1304
1039
1304
1039
1304
1039
1304
1039
1304
1039
1304
1039
1304
1039
1304
15F
lang
e G
aske
tS
0063
700
S00
6370
0S
0063
700
S00
6370
0S
0063
700
S00
6370
0S
0063
700
S00
6370
0S
0063
700
16H
eade
r G
aske
t w/B
arrie
rS
0095
100
S00
9510
0S
0095
100
S00
9510
0S
0095
100
S00
9510
0S
0095
100
S00
9510
0S
0095
100
17H
eade
r G
aske
tU
se S
0095
1 00
-Cut
Out
Bar
rier
18B
affle
, Wat
er In
let
1033
8300
1033
8300
1033
8300
1033
8300
1033
8300
1033
8300
1033
8300
1033
8300
1033
8300
19B
arrie
r, W
ater
1039
7500
1039
7500
1039
7500
1039
7500
1039
7500
1039
7500
1039
7500
1039
7500
1039
7500
20W
ell,
Aqu
asta
tE
0025
900
E00
2590
0E
0025
900
E00
2590
0E
0025
900
E00
2590
0E
0025
900
E00
2590
0E
0025
900
Wel
l, A
quas
tat
F/4
Sta
geE
0085
700
E00
8570
0E
0085
700
E00
8570
0E
0085
700
E00
8570
0E
0085
700
E00
8570
0E
0085
700
NO
TE
: Num
bers
in (
) re
pres
ent q
uant
ity r
equi
red
for
each
siz
e. Q
uant
ity is
one
oth
erw
ise.
SECTION 6. Parts Descriptions and Order Numbers
Mighty Therm Volume Water Heater Page 23
Figure 22. Parts Identification.
NOTE:Temperature Control Wells -Inlet/Outlet Header1. Firing Mode L, K, & C -
2 Dry Wells2. Firing Mode H
A. Natural Gas Boilers & Heaters500 thru 850 - 2 Dry Wells1010 thru 1430 - 3 Dry Wells1670 thru 1825 - 4 Dry Wells
B. Propane Gas Boilers & Heaters500 thru 850 - 2 Dry Wells1010 thru 1852 - 3 Dry Wells
LAARS HEATING SYSTEMSPage 24
Key
Des
crip
tion
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
No
50
06
00
71
58
50
1010
1200
1430
1670
1825
21
Tile
, Hea
t Shi
eld/
Spc
r, F
rt. &
Rr.
10
56
01
00
——
——
——
——
——
——
——
——
(2)
22Ti
le,
Hea
t S
hiel
d/S
pace
r, F
ront
——
1054
7901
1054
7902
——
——
1054
7903
1054
7901
1054
7904
1054
7903
23Ti
le,
Hea
t S
hiel
d/S
pace
r, F
ront
——
——
——
1054
8002
1054
8003
——
——
——
1054
8001
24Ti
le,
Hea
t S
hiel
d/S
pace
r, F
ront
——
——
——
——
——
1054
8101
1054
8102
1054
8103
1054
8104
25Ti
le,
Hea
t S
hiel
d/S
pace
r, R
ear
——
1054
8201
1054
8202
——
——
1054
8203
1054
8201
1054
8204
1054
8203
26Ti
le,
Hea
t S
hiel
d/S
pace
r, R
ear
——
——
——
1054
8302
1054
8303
——
——
——
1054
8301
27Ti
le,
Hea
t S
hiel
d/S
pace
r, R
ear
——
——
——
——
——
1054
8401
1054
8402
1054
8403
1054
8404
28S
addl
e A
ssem
bly,
End
Tile
1053
3600
1053
3600
1053
3600
1053
3600
1053
3600
1053
3600
1053
3600
1053
3600
1053
3600
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
29Lo
wer
End
Pan
el/H
eat S
hiel
dW
eldm
ent,
Rig
ht10
5407
0110
5407
0110
5407
0110
5407
0110
5407
0110
5407
0110
5407
0110
5407
0110
5407
01
30Lo
wer
End
Pan
el/H
eat
Shi
eld
Wel
dmen
t, Le
ft10
5407
0210
5407
0210
5407
0210
5407
0210
5407
0210
5407
0210
5407
0210
5407
0210
5407
02
31Lo
wer
Rea
r P
anel
& B
affle
Rea
r W
eldm
ent
1053
2901
1053
2902
1053
2903
1053
2904
1053
2905
1053
2906
1053
2907
1053
2908
1053
2909
32M
iddl
e R
ear
Pan
el/H
eat
Shi
eld
Wel
dmen
t10
5404
0110
5404
0210
5404
0310
5404
0410
5404
0510
5404
0610
5404
0710
5404
0810
5404
09
33E
nd P
anel
, Upp
er R
ight
1053
1600
1053
1600
1053
1600
1053
1600
1053
1600
1053
1600
1053
1600
1053
1600
1053
1600
34E
nd P
anel
, Upp
er L
eft
1053
4000
1053
4000
1053
4000
1053
4000
1053
4000
1053
4000
1053
4000
1053
4000
1053
4000
35U
pper
Rea
r P
anel
/Hea
tS
hiel
d W
eldm
ent
1054
0501
1054
0502
1054
0503
1054
0504
1054
0505
1054
0506
1054
0507
1054
0508
1054
0509
36F
ront
Pan
el, U
pper
1053
1501
1053
1502
1053
1503
1053
1504
1053
1505
1053
1506
1053
1507
1053
1508
1053
1809
37B
rack
ets,
Sup
port
, End
Tile
1055
1000
1055
1000
1055
1000
1055
1000
1055
1000
1055
1000
1055
1000
1055
1000
1055
1000
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
38D
rafth
ood,
Rel
ief B
affle
, Rig
ht10
5409
0110
5409
0210
5409
0310
5409
0410
5409
0510
5409
0610
5409
0710
5409
0810
5409
09
39D
rafth
ood,
Rel
ief B
affle
, Lef
t10
5410
0110
5410
0210
5410
0310
5410
0410
5410
0510
5410
0610
5410
0710
5410
0810
5410
09
40Lo
wer
Rig
ht P
anel
/Hea
tS
hiel
d W
eldm
ent
1055
4601
1055
4602
1055
4603
1055
4604
1055
4605
1055
4606
1055
4607
1055
4608
1055
4609
41M
iddl
e F
ront
Pan
el10
5544
0110
5544
0210
5544
0310
5544
0410
5544
0510
5544
0610
5544
0710
5544
0810
5544
09
42S
wee
p S
heet
, Flu
e C
olle
ctor
1053
3901
1053
3902
1053
3903
1053
3904
1053
3905
1053
3906
1053
3907
1053
3908
1053
3909
NO
TE
: Num
bers
in (
) re
pres
ent q
uant
ity r
equi
red
for
each
siz
e. Q
uant
ity is
one
oth
erw
ise.
Mighty Therm Volume Water Heater Page 25
Figure 23. Tile Assemblies.
LAARS HEATING SYSTEMSPage 26K
eyD
escr
iptio
nM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elN
o5
00
60
07
15
85
010
1012
0014
3016
7018
25
43
Igni
tion
Con
trol
, E
lect
roni
cE
01
00
90
0E
01
00
90
0E
01
00
90
0E
01
00
90
0E
01
00
90
0E
01
00
90
0E
01
00
90
0E
01
00
90
0E
01
00
90
0
44
Tran
sfor
mer
, 11
5V
/24V
E0
08
61
00
E0
08
61
00
E0
08
61
00
E0
08
61
00
E0
08
61
00
E0
08
61
00
E0
08
61
00
E0
08
61
00
E0
08
61
00
45
Con
trol
Box
Wel
dmen
t1
05
45
80
01
05
45
80
01
05
45
80
01
05
45
80
01
05
45
80
01
05
45
80
01
05
45
80
01
05
45
80
01
05
45
80
0
46
Con
trol
Box
Cov
er1
05
47
20
01
05
47
20
01
05
47
20
01
05
47
20
01
05
47
20
01
05
47
20
01
05
47
20
01
05
47
20
01
05
47
20
0
47
Win
g N
ut,
#8-3
2F
00
32
10
0F
00
32
10
0F
00
32
10
0F
00
32
10
0F
00
32
10
0F
00
32
10
0F
00
32
10
0F
00
32
10
0F
00
32
10
0(2
)(2
)(2
)(2
)(2
)(2
)(2
)(2
)(2
)
48
Bas
e Ti
le S
uppo
rt A
ssy.
10
53
69
01
10
53
69
02
10
53
69
03
10
53
69
04
10
53
69
05
10
53
69
06
10
53
69
07
10
53
69
08
10
53
69
09
49
Bur
ner,
Mai
nL
00
52
30
0L
00
52
30
0L
00
52
30
0L
00
52
30
0L
00
52
30
0L
00
52
30
0L
00
52
30
0L
00
52
30
0L
00
52
30
0
50
Pilo
t B
rkt/B
urne
r W
eldm
ent
(Joh
nson
Pilo
t)10
5295
0110
5295
0110
5295
0110
5295
0110
5295
0110
5295
0110
5295
0110
5295
0110
5295
01(H
oney
wel
l Pilo
t)10
5295
0210
5295
0210
5295
0210
5295
0210
5295
0210
5295
0210
5295
0210
5295
0210
5295
02
51P
ilot B
urne
r (J
ohns
on)
Sta
ndin
g P
ilot,
Nat
W00
3470
0W
0034
700
W00
3470
0W
0034
700
W00
3470
0W
0034
700
W00
3470
0W
0034
700
W00
3470
0P
ilot B
urne
r (H
oney
wel
l)S
tand
ing
Pilo
t, N
atW
0035
800
W00
3580
0W
0035
800
W00
3580
0W
0035
800
W00
3580
0W
0035
800
W00
3580
0W
0035
800
52P
ilot B
urne
r (J
ohns
on)
Sta
ndin
g P
ilot,
Pro
pane
W00
3460
0W
0034
600
W00
3460
0W
0034
600
W00
3460
0W
0034
600
W00
3460
0W
0034
600
W00
3460
0P
ilot B
urne
r (H
oney
wel
l)S
tand
ing
Pilo
t, P
ropa
neW
0034
400
W00
3440
0W
0034
400
W00
3440
0W
0034
400
W00
3440
0W
0034
400
W00
3440
0W
0034
400
53P
ilot B
urne
r (J
ohns
on)
IID P
ilot,
Nat
W00
3450
0W
0034
500
W00
3450
0W
0034
500
W00
3450
0W
0034
500
W00
3450
0W
0034
500
W00
3450
0P
ilot B
urne
r (H
oney
wel
l)IID
Pilo
t, N
atW
0034
300
W00
3430
0W
0034
300
W00
3430
0W
0034
300
W00
3430
0W
0034
300
W00
3430
0W
0034
300
54G
as M
anifo
ld W
eldm
ent (
sing
le)
1052
5901
1052
5902
1052
5903
1052
5904
1052
5905
1052
5906
1052
5907
1052
5908
1052
5909
55O
rific
e, N
at, G
asL0
0507
00L0
0507
00L0
0507
00L0
0507
00L0
0507
00L0
0507
00L0
0507
00L0
0507
00L0
0507
00(2
2)(2
6)(3
0)(3
6)(4
2)(5
0)(6
0)(7
0)(7
6)
56O
rific
e, P
ropa
ne -
9"
W.C
.L0
0329
00L0
0329
00L0
0329
00L0
0329
00L0
0329
00L0
0329
00L0
0329
00L0
0329
00L0
0329
00(2
2)(2
6)(3
0)(3
6)(4
2)(5
0)(6
0)(7
0)(7
6)
57M
anifo
ld C
over
Pla
t Ass
y.10
5529
0110
5529
0210
5529
0310
5529
0410
5529
0510
5529
0610
5529
0710
5529
0810
5529
09
58B
urne
r, A
nti R
otat
ion
Brk
t (le
ft)10
5253
0110
5253
0210
5253
0310
5253
0410
5253
0510
5253
0610
5253
0710
5253
0810
5253
09
59B
urne
r, A
nti R
otat
ion
Brk
t (rig
ht)
1054
2701
1054
2702
1054
2703
1054
2704
1054
2705
1054
2706
1054
2707
1054
2708
1054
2709
60B
urne
r Ti
e D
own
Bra
cket
(le
ft)10
5257
0110
5257
0210
5257
0310
5257
0410
5257
0510
5257
0210
5257
0310
5257
0410
5257
04(2
)(2
)(2
)10
5257
05
61B
urne
r T
ie D
own
Bra
cket
(rig
ht)
1054
2001
1054
2002
1054
2003
1054
2004
1054
2005
1054
2002
1054
2003
1052
5704
1052
5704
62V
alve
, Man
ual,
Gas
, Nat
ural
V00
0420
0V
0004
200
V00
0420
0V
0004
200
V00
0430
0V
0004
300
V00
0430
0V
0004
300
V00
0430
0
63V
alve
, Man
ual,
Gas
, Pro
pane
V00
0480
0V
0004
800
V00
0480
0V
0004
800
V00
0420
0V
0004
200
V00
0430
0V
0004
300
V00
0430
0
NO
TE
: Num
bers
in (
) re
pres
ent q
uant
ity r
equi
red
for
each
siz
e. Q
uant
ity is
one
oth
erw
ise.
Mighty Therm Volume Water Heater Page 27
Key
Des
crip
tion
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
No
50
06
00
71
58
50
1010
1200
1430
1670
1825
64
Saf
ety
Gas
Val
ve, O
n-O
ff,Tw
o S
tage
(N
at)
V00
4660
0V
0046
600
V00
4600
V00
4600
V00
4670
0V
0046
700
V00
4670
0V
0046
700
V00
4680
0
65S
afet
y G
as V
alve
, On-
Off,
Two
Sta
ge (
Pro
)V
0046
600
V00
4660
0V
0046
600
V00
4660
0V
0046
600
V00
4660
0V
0046
700
V00
4670
0V
0046
700
66V
alve
, Gas
, Ope
ratin
g / R
eg.
On-
Off,
Tw
o S
tage
(N
at)
V00
5120
0V
0051
200
V00
5120
0V
0051
200
V00
5130
0V
0051
300
V00
5130
0V
0051
400
V00
5140
0
67V
alve
, Gas
, Ope
ratin
g / O
n-O
ffTw
o S
tage
(P
ro)
V00
5480
0V
0054
800
V00
5480
0V
0054
800
V00
5480
0V
0054
800
V00
5490
0V
0054
900
V00
5490
0
68V
alve
, Pilo
t, G
as, M
anua
lW
0002
100
W00
0210
0W
0002
100
W00
0210
0W
0002
100
W00
0210
0W
0002
100
W00
0210
0W
0002
100
69Tu
be A
ssem
bly,
Cop
per
1053
4701
1053
4702
1053
4703
1053
4704
1053
4705
1053
4706
1053
4707
1053
4708
1053
4709
70Tu
be A
ssem
bly,
Cup
ro-n
icke
l10
5537
0110
5537
0210
5537
0310
5537
0410
5537
0510
5537
0610
5537
0710
5537
0810
5537
09
71S
crew
, Cap
, 1/2
" -
13 x
4 1
/2"
F00
2870
0F
0028
700
F00
2870
0F
0028
700
F00
2870
0F
0028
700
F00
2870
0F
0028
700
F00
2870
0
72S
crew
, Cap
, 1/2
" -
13 x
2 1
/4"
F00
2310
0F
0023
100
F00
2310
0F
0023
100
F00
2310
0F
0023
100
F00
2310
0F
0023
100
F00
2310
0
73S
crew
, Cap
, 1/2
" -
13 x
1 1
/2"
F00
1330
0F
0013
300
F00
1330
0F
0013
300
F00
1330
0F
0013
300
F00
1330
0F
0013
300
F00
1330
0
74W
ashe
rF
0011
400
F00
1140
0F
0011
400
F00
1140
0F
0011
400
F00
1140
0F
0011
400
F00
1140
0F
0011
400
75P
lug,
Sq.
Hd.
, 1 “
NP
TP
0033
000
P00
3300
0P
0033
000
P00
3300
0P
0033
000
P00
3300
0P
0033
000
P00
3300
0P
0033
000
76P
lug,
1/2
" N
PT
P00
2690
0P
0026
900
P00
2690
0P
0026
900
P00
2690
0P
0026
900
P00
2690
0P
0026
900
P00
2690
0
77N
ippl
e, B
rass
, 3/4
" x
2"P
0025
300
P00
2530
0P
0025
300
P00
2530
0P
0025
300
P00
2530
0P
0025
300
P00
2530
0P
0025
300
78Va
lve,
Pre
ss, R
elie
f 3/4
" -7
5 P
SI
A00
6360
0A
0063
600
A00
6360
0A
0063
600
A00
6360
0A
0063
600
A00
6360
0A
0063
600
A00
6360
0
79Te
mp/
Pre
ss G
auge
A00
7900
0A
0079
000
A00
7900
0A
0079
000
A00
7900
0A
0079
000
A00
7900
0A
0079
000
A00
7900
0
80F
low
Sw
itch
(indo
or)
E00
1310
0E
0013
100
E00
1310
0E
0013
100
E00
1310
0E
0013
100
E00
1310
0E
0013
100
E00
1310
0(o
utdo
or)
E00
1300
0E
0013
000
E00
1300
0E
0013
000
E00
1300
0E
0013
000
E00
1300
0E
0013
000
E00
1300
0
81N
ippl
e, 2
" x
cl. -
GaI
vP
0038
500
P00
3850
0P
0038
500
P00
3850
0—
——
——
——
——
——
——
——
——
——
—
82N
ippl
e, 2
1/2
" x
3" G
aIv
——
——
——
——
——
——
——
——
P00
2200
0P
0022
000
P00
2200
0P
0022
000
P00
2200
83R
ed. T
ee, 2
x 2
x 1
, GaI
vP
0028
500
P00
2850
0P
0028
500
P00
2850
0—
——
——
——
——
——
——
——
——
——
—R
ed. T
ee, 2
1/2
x 2
1/2
x 1
, GaI
v—
——
——
——
——
——
——
——
—P
0055
900
P00
5590
0P
0055
900
P00
5590
0P
0055
900
84P
ump
Rot
atin
g A
ssem
bly
See
Cur
rent
Doc
umen
t 204
0 F
or P
ump
Req
uire
men
ts
85P
ump
Hou
sing
1026
1501
1026
1501
1026
1501
1026
1501
1026
1501
1026
1501
1026
1501
1026
1501
1026
1501
86G
aske
t, P
ump
Hou
sing
S00
2460
0S
0024
600
S00
2460
0S
0024
600
S00
2460
0S
0024
600
S00
2460
0S
0024
600
S00
2460
0
87P
ump
Ada
pter
1036
4200
1036
4200
1036
4200
1036
4200
1036
4200
1036
4200
1036
4200
1036
4200
1036
4200
88S
crew
, Hex
Hd.
1/2
- 1
3 x
1 3/
4F
0009
200
F00
0920
0F
0009
200
F00
0920
0F
0009
200
F00
0920
0F
0009
200
F00
0920
0F
0009
20
NO
TE
: Num
bers
in (
) re
pres
ent q
uant
ity r
equi
red
for
each
siz
e. Q
uant
ity is
one
oth
erw
ise.
LAARS HEATING SYSTEMSPage 28K
eyD
escr
iptio
nM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elN
o5
00
60
07
15
85
010
1012
0014
3016
7018
25
89
Plu
g, 3
/4, S
q. H
d.P
00
27
00
0P
00
27
00
0P
00
27
00
0P
00
27
00
0P
00
27
00
0P
00
27
00
0P
00
27
00
0P
00
27
00
0P
00
27
00
0
90
Pip
e E
xten
sion
1/2
" F
emal
eP
ipe
Ext
ensi
on 1
/2"
Mal
eP
0072
300
P00
7230
0P
0072
300
P00
7230
0P
0072
300
P00
7230
0P
0072
300
P00
7230
0P
0072
300
91B
affle
, Diff
user
1033
8400
1033
8400
1033
8400
1033
8400
1033
8400
1033
8400
1033
8400
1033
8400
1033
8400
92B
urne
r Tra
y, II
D, 2
Sta
ge, S
GL
Sec
t. M
anifo
ld (
Nat
)10
5506
0110
5506
0210
5506
0310
5506
0410
5506
0510
5506
0610
5506
0710
5506
0810
5506
09
93B
urne
r Tr
ay,
St.
Pilo
t, 2
Sta
ge,
SG
L, S
ect.
Man
ifold
(P
ro)
1052
9601
1052
9602
1052
9603
1052
9604
1052
9605
1052
9606
1052
9607
1052
9608
1052
9609
94B
urne
r T
ray,
I I D
, 4 S
tage
,S
plit
Man
ifold
(N
at)
1055
0701
1055
0702
1055
0703
1055
0704
1055
0705
1055
0706
1055
0707
1055
0708
1055
0709
95B
urne
r Tr
ay,
St.
Pilo
t, 4
Sta
ge,
Spl
it M
anifo
ld (
Pro
)10
5503
0110
5503
0210
5503
0310
5503
0410
5503
0510
5503
0610
3303
0710
3305
0810
3305
09
96B
urne
r Tr
ay, I
ID, M
ech.
Mod
.S
plit
Man
ifold
(N
at)
1055
0701
1055
0702
1055
0703
1055
0704
——
——
——
——
——
97B
urne
r Tr
ay, I
I D
, Mec
h. M
od.,
3 &
4 S
ect.
Man
ifold
(N
at)
——
——
——
——
1055
1201
1055
1202
1055
1203
1055
1204
1055
1205
98B
urne
r Tra
y, S
t. P
l. M
ech.
Mod
. SpI
t. M
anifo
ld (
Pro
)10
5503
0110
5503
0210
5503
0310
5503
04—
——
——
——
——
—
99B
urne
r Tra
y, S
t. P
l., M
ech.
Mod
., 3
Sec
t. M
anifo
ld (
Pro
)—
——
——
——
—10
5505
0110
5505
0210
5505
0310
5505
0410
5505
05
100
Com
bina
tion
Gas
Val
ve,
V00
5960
0V
0059
600
V00
5960
0V
0070
400
V00
7040
0V
0070
400
——
——
——
4 S
tage
, (N
at)
(2)
(2)
(2)
(2)
(2)
(2)
101
Saf
ety
Gas
Val
ve, 4
Sta
ge (
Nat
)—
——
——
——
——
——
—V
0046
700
V00
4680
0V
0046
800
102
Ope
ratin
g/R
eg. G
as V
alve
,4
Sta
ge (
Nat
)—
——
——
——
——
——
—V
0051
300
V00
5130
0V
0051
300
(2)
(2)
(2)
103
Com
bina
tion
Gas
Val
ve,
V00
7080
0V
0070
800
V00
7080
0V
0070
900
V00
7090
0V
0070
900
V00
7090
0—
——
—4
Sta
ge, (
Pro
)(2
)(2
)(2
)(2
)(2
)(2
)(2
)
104
Saf
ety
Gas
Val
ve,
4 S
tage
, (P
ro)
——
——
——
——
——
——
——
V00
4670
0V
0046
700
105
Ope
ratin
g/R
eg. G
as V
alve
,4
Sta
ge (
Pro
——
——
——
——
——
——
——
V00
5490
0V
0054
900
(2)
(2)
106
Mod
usna
p G
as V
alve
, (H
H &
PH
V00
4510
0V
0045
100
V00
4510
0V
0045
100
——
——
——
——
——
Onl
y), M
ech.
Mod
. (N
at &
Pro
)V
0071
100
V00
7110
0V
0071
100
V00
7110
0V
0071
100
V00
7110
0V
0071
100
V00
7110
0V
0071
100
(3)
(3)
(3)
N(4
) &
P(3
)N
(4)
& P
(3)
107
Ope
ratin
g/R
eg. G
as V
alve
,M
ech.
Mod
. (N
at)
V00
4760
0V
0047
600
V00
4760
0V
0047
600
V00
4770
0V
0047
700
V00
4770
0V
0047
800
V00
4780
0
108
Ope
ratin
g/R
eg. G
as V
alve
,V
0054
800
V00
5480
0V
0054
800
V00
5480
0V
0054
800
V00
5480
0V
0054
900
V00
5490
0V
0054
900
Mec
h. M
od. (
Pro
)N
OT
E: N
umbe
rs in
()
repr
esen
t qua
ntity
req
uire
d fo
r ea
ch s
ize.
Qua
ntity
is o
ne o
ther
wis
e.
Mighty Therm Volume Water Heater Page 29
Figure 21. Outdoor Parts.
LAARS HEATING SYSTEMSPage 30K
eyD
escr
iptio
nM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elM
od
elN
o5
00
60
07
15
85
010
1012
0014
3016
7018
25
1To
p P
anel
Ass
embl
y1
06
60
70
11
06
60
70
21
06
60
70
31
06
60
70
41
06
60
70
51
06
60
70
61
06
60
70
71
06
60
70
81
06
60
70
9
2R
ear
Win
dshi
eld
10
65
81
01
10
65
81
02
10
65
81
03
10
65
81
04
10
65
81
05
10
65
81
06
10
65
81
07
10
65
81
08
10
65
81
09
3U
pper
Rea
r Lo
uver
Shi
eld
10
65
71
01
10
65
71
02
10
65
71
03
10
65
71
04
10
65
71
05
10
65
71
06
10
65
71
07
10
65
71
08
10
65
71
09
4R
ear
Pan
el U
pper
10
65
87
01
10
65
87
02
10
65
87
03
10
65
87
04
10
65
87
05
10
65
87
06
10
65
87
07
10
65
87
08
10
65
87
09
5G
ap C
losu
re-S
ide
10
66
02
00
10
66
02
00
10
66
02
00
10
66
02
00
10
66
02
00
10
66
02
00
10
66
02
00
10
66
02
00
10
66
02
00
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
6G
ap C
losu
re-M
iddl
e1
06
60
10
01
06
60
10
01
06
60
10
01
06
60
10
01
06
60
10
01
06
60
10
01
06
60
10
01
06
60
10
01
06
60
10
0
7Lo
wer
Rea
r P
anel
Ass
embl
y1
06
60
50
11
06
60
50
21
06
60
50
31
06
60
50
41
06
60
50
51
06
60
50
61
06
60
50
71
06
60
50
81
06
60
50
9
8R
ear
End
Pan
el L
ft. &
Rt.
10
65
77
00
10
65
77
00
10
65
77
00
(2)
10
65
77
00
10
65
77
00
10
65
77
00
10
65
77
00
10
65
77
00
10
65
77
00
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
9Lo
wer
Rea
r S
hiel
d In
ner
10
65
99
01
10
65
99
02
10
65
99
03
10
65
99
04
10
65
99
05
10
65
99
06
10
65
99
07
10
65
99
08
10
65
99
09
10
Rea
r B
ase
Ext
ensi
on1
06
58
50
11
06
58
50
21
06
58
50
31
06
58
50
41
06
58
50
51
06
58
50
61
06
58
50
71
06
58
50
81
06
58
50
9
11G
as T
rain
Int
erfa
ce P
late
20
05
02
00
20
05
02
00
20
05
02
00
20
05
02
00
20
05
02
00
20
05
02
00
20
05
02
00
20
05
02
00
20
05
02
00
12
Fro
nt E
nd P
anel
10
65
75
00
10
65
75
00
10
65
75
00
10
65
75
00
10
65
75
00
10
65
75
00
10
65
75
00
10
65
75
00
10
65
75
00
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
13
Fro
nt B
ase
Ext
ensi
on1
06
59
70
11
06
59
70
21
06
59
70
31
06
59
70
41
06
59
70
51
06
59
70
61
06
59
70
71
06
59
70
81
06
59
70
9
14
Do
or
10
66
08
01
10
66
08
02
10
66
08
03
10
66
08
04
10
66
08
05
10
66
08
06
10
66
08
07
10
66
08
08
10
66
08
09
(2)
(2)
(2)
(2)
(2)
15
Fro
nt W
inds
hiel
d1
06
59
10
11
06
59
10
21
06
59
10
31
06
59
10
41
06
59
10
51
06
59
10
61
06
59
10
71
06
59
10
81
06
59
10
9
16
Fro
nt P
anel
Upp
er1
06
58
90
11
06
58
90
21
06
58
90
31
06
58
90
41
06
58
90
51
06
58
90
61
06
58
90
71
06
58
90
81
06
58
90
9
17
Flu
e P
anel
Fro
nt1
06
59
50
11
06
59
50
21
06
59
50
31
06
59
50
41
06
59
50
51
06
59
50
61
06
59
50
71
06
59
50
81
06
59
50
9
18
Flu
e P
anel
Rea
r1
06
59
30
11
06
59
30
21
06
59
30
31
06
59
30
41
06
59
30
51
06
59
30
61
06
59
30
71
06
59
30
81
06
59
30
9
19
Rai
n S
hiel
d-C
ontr
ol B
ox1
06
60
40
01
06
60
40
01
06
60
40
01
06
60
40
01
06
60
40
01
06
60
40
01
06
60
40
01
06
60
40
01
06
60
40
0(N
ot s
how
n)
See
Par
ts Il
lust
rati
on
On
Pag
e 21
5R
ear
Pan
el, F
lue
Col
lect
or10
6617
0110
6617
0210
6617
0310
6617
0410
6617
0510
6617
0610
6617
0710
6617
0810
6617
09
6R
ear
Pan
el, F
lue
Col
lect
or E
xt.
1066
1801
1066
1802
1066
1803
1066
1804
1066
1805
1066
1806
1066
1807
1066
1808
1066
1809
NO
TE
: Num
bers
in (
) re
pres
ent q
uant
ity r
equi
red
for
each
siz
e. Q
uant
ity is
one
oth
erw
ise.
SECTION 7. Outdoor Parts Descriptions and Order Numbers
Mighty Therm Volume Water Heater Page 31
Key
Des
crip
tion
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
Mo
del
No
50
06
00
71
58
50
1010
1200
1430
1670
1825
7F
ront
Sup
port
, F
lue
Col
lect
or1
06
62
10
11
06
62
10
21
06
62
10
31
06
62
10
41
06
62
10
51
06
62
10
61
06
62
10
71
06
62
10
81
06
62
10
9
8Ti
le C
over
, Fro
nt &
Rea
r1
06
61
50
11
06
61
50
21
06
61
50
31
06
61
50
41
06
61
50
51
06
61
50
61
06
61
50
71
06
61
50
81
06
61
50
9(2
)(2
)(2
)(4
)(4
)(4
)(4
)(4
)(4
)
10
Baf
fle,
Hea
t E
xcha
nger
10
66
77
01
10
66
77
02
10
66
77
03
10
66
77
04
10
66
77
05
10
66
77
06
10
66
77
07
10
66
77
08
10
66
77
09
(7)
(14)
(14)
(14)
(14)
(28)
(28)
(28)
(14)
41
Mid
dle
Fro
nt P
anel
10
66
20
01
10
66
20
02
10
66
20
03
10
66
20
04
10
66
20
05
10
66
20
06
10
66
20
07
10
66
20
08
10
66
20
09
42
Sw
eep
She
et F
lue
10
66
22
01
10
66
22
02
10
66
22
03
10
66
22
04
10
66
22
05
10
66
22
06
10
66
22
07
10
66
22
08
10
66
22
09
Col
lect
or
48
Bas
e T
ile S
uppo
rt1
06
02
30
11
06
02
30
21
06
02
30
31
06
02
30
41
06
02
30
51
06
02
30
61
06
02
30
71
06
02
30
81
06
02
30
9
69
Tub
e A
ssem
bly,
Cop
per
10
66
59
01
10
66
59
02
10
66
59
03
10
66
59
04
10
66
59
05
10
66
59
06
10
66
59
07
10
66
59
08
10
66
59
09
70
Tub
e A
ssem
bly,
Cup
ro-N
icke
l1
06
70
40
11
06
70
40
21
06
70
40
31
06
70
40
41
06
70
40
51
06
70
40
61
06
70
40
71
06
70
40
81
06
70
40
9
NO
TE
: Num
bers
in (
) re
pres
ent q
uant
ity r
equi
red
for
each
siz
e. Q
uant
ity is
one
oth
erw
ise.
Pump Rotating Sections and Repair PartsCheck pump assembly on heater for H.P. rating and find correct Laars part number from table below.
Description 1/4 HP 1/3 HP 3/4 HP
Pump Rotating Assembly, B&G, 1522 w/3 “ IMP, Bronze, 1P A0048700 —— ——Pump Rotating Assembly, B&G, Series 90 w/3 “ Impeller, 1P A0077100 —— ——Pump Rotating Assembly, TACO 1630 w/3 “ Impeller, 1P A0071000 —— ——Pump Rotating Assembly, TACO 1630 w/4" Impeller, 1P —— A0071200 ——Pump Rotating Assembly, B&G, 1522 w/4" Impeller, Bronze, 1P —— A0047500 ——Pump Rotating Assembly, B&G Series 90, w/4" Impeller, 1P —— A0077200 ——Pump Rotating Assembly, TACO 1630 w/5 “ Impeller, 1P —— —— A0071400Pump Rotating Assembly, B&G 1522 w/5 “ Impeller, Bronze, 1P —— —— A0047700Pump Rotating Assembly, B&G Series 90, w/5 “, Impeller, 1P —— —— A0077300Motor, Pump, B&G 1522 - I P A0054400 A0054800 A0055600Coupler, Pump, B&G - Universal A0020200 A0020200 A0020200Bearing Assembly, Pump, B&G 1522 - Universal A0021600 A0021600 A0021600Bearing Assembly, Pump, B&G 1522, Bronze A0022100 A0022100 A0022100Gasket, Pump, B&G 1522 - #PW1 -2151 A0021400 A0021400 A0021400Mounting Ring, B&G 1522 Motors A0065100 A0065100 A0065100Impeller, B&G 1522 - 3" A0058100 A0058100 A0058100Impeller, B&G 1522 - 4" A0058200 A0058200 A0058200Impeller, B&G 1522 - 5" A0058400 A0058400 A0058400
Automatic Reset Temp. Limit Switch .....................................................................................................................E0014400Manual Reset High Gas Pressure Switch ...............................................................................................................E0023300Manual Reset Low Gas Pressure Switch ................................................................................................................E0023500Alarm Bell, 110 Volts ...............................................................................................................................................A0014200Outdoor Reset, Single Stage 30' Bulb .....................................................................................................................E0067600Outdoor Reset, Two Stage, 30' Bulb .......................................................................................................................E0084200Low-water Cut-off, Electronic, Manual Reset ..........................................................................................................E0067900Low-water Cut-off, Electronic, Automatic Reset With Test Button ...........................................................................E2024200
Gas valve types and sizes vary with different boiler models, with different fuels and with different firing options. For service and replacement,copy exact number from nameplate giving manufacturer’s name and pipe size.
SECTION 8. Optional Parts Descriptions and Order Numbers
Energy Management Monitor (EM2)STANDARD COMPONENTS
Description Part No.
On/Off Auto Switch E0109200Time Delay Relay, 24 VAC E2077700Time Delay Relay, 120 VAC E2077800
OPTIONAL EQUIPMENT
Description Part No.Remote Aquastat, 110-240F E0014400Immersion Well E0025900Note: The Remote Aquastat and the Immersion Well, whenrequired, should be ordered separately.
Waterpik Technologies, Inc.6000 Condor Drive, Moorpark, CA 93021 • 805.529.2000 • FAX 805.529.593420 Industrial Way, Rochester, NH 03867 • 603.335.6300 • FAX 603.335.3355480 S. Service Road West, Oakville, Ontario, Canada L6K 2H4 • 905.844.8233 • FAX 905.844.2635www.laars.com Litho in U.S.A. © Laars Heating Systems 0011 Document 2040DH
0105
000D