    6

    Lead the motor and mains cables through the

    bottom plate.

    ENSURE MAINS SUPPLY TO INSTALLATION IS OFF.

    LOCK THE DISCONNECTOR TO OPEN POSITION.ACx 600 MUST BE INSTALLED BY A COMPETENT PERSON.IF IN DOUBT DO NOT INSTALL.

    1

    1. Measure the places for four screw holes.

    Mark the hole positions. 2. Drill the holes.

    3. Screw in the screws.

    2

    Position ACx 600 onto screws and securelytighten in all four corners. Note: Lift ACx 600

    by its chassis, not by its cover.

    1. Remove the Control Panel. 2. Remove thetelephone connector of the Panel. 3. Remove

    the cover.

    STOP

    FOR

    INSTALLATION

    OF OPTIONAL

    EQUIPMENT, SEE

    SEPARATE

    INSTRUCTIONS

    INCLUDED IN

    THE DELIVERY.

    4 5

    1. Strip off the insulation from the motor cable

    and mains cable. Twist the screen wires to

    bundles. 2. Make suitable holes to motor and

    mains cable grommets.

    Before Starting Installation

    CHECK BOX CONTENTS: ACx 601, Manual(s), Testing report, Ordered options, Quick Guide(s)

    CHECK INSTALLATION SITE AMBIENT CONDITIONS: See Manual.

    CHECK INSTALLATION SPACE: ACx 600 free space requirements are 300 mm above and below, 50 mm on the left and on the right.

    CHECK INSTALLATION SURFACE: Vertical, smooth and solid, free from heat, damp and condensation.

    CHECK ACCESSORIES NEEDED: See Manual for fuse, supply disconnecting device and cable specifications.

    3

    Mains cable

    OUTPUT

    STOP

    CHECK THE

    INSULATIONS

    OF MOTOR,

    AND MAINS

    AND MOTOR

    CABLE.

    See Manual.

    7

    2.

    1.

    3.

    2.1.

    3.

    1.

    2.

    INPUT

    Motorcable

    300 mmfree space

    ACS 600 Installation GuideACF 601-0016-3/5, ACx 601-0020-3 ... -0070-3,

    -0025-5 ... -0100-5 and -0025-6 ... -0070-6

    10

    7

    7

    15

  • 8/12/2019 Ins_r4r6

    2/2

    1. Connect the motor cable.

    2. Connect the mains cable.

    Ensure proper earthings.

    For minimal radio frequency

    interference (RFI) at the motor

    end:

    1. Twisted screen:

    Diameter () >1/5 Length (L),

    or

    2. Screen 360 earthing at cable

    lead-through.

    L

    8

    9

    Control cable installation:

    1. Make hole to a control cable

    grommet and lead the cable into

    the unit.

    2.Connect the earthing wires and

    the cable shield to the earthing

    terminal next to the NIOC board.

    3. Connect the control cables to

    the input/output terminals.

    1. Replace the cover.

    2. Replace the telephone

    connector of the Control Panel.

    3. Replace the Control Panel.

    10

    1.

    2.

    2.3.

    1.

    Earthing Wires

    and the cable shield 3.

    300 mmfree space

    ABB IndustryOy Drives P.O. Box 184 FIN-00381 Helsinki tel: +358-10 22 2000 fax: +358-10 22 22681

    Code:

    3AFY5

    8972665R0225REV

    A

    Effective:3.3.1

    998/EN

    Standard

    Input/Output

    Connections: See

    theStart-up

    Guide or Manual.