INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Jamuna Apparels Address: 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh Assessor: Bureau Veritas Date: 11 Apr 2014 Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com. The Alliance for Bangladesh Worker Safety Page 1/18

INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

  • Upload
    lamtu

  • View
    224

  • Download
    3

Embed Size (px)

Citation preview

Page 1: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

INITIAL ELECTRICAL ASSESSMENT REPORT(EAR)

 

Factory Name: Jamuna Apparels

Address: 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK CTONGI INDUSTRIAL AREA,, TONGI, GAZIPUR,GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

 

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 1/18

Page 2: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

 Introduction to the Report

The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by theAlliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment wasconducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard,which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) forthe Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technicalrequirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairlyevaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used byRMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on actionsteps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements throughtechnical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wagesupport for workers if factories are closed for remediation.

The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute orcontinued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to providea non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF northe Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report.

For more information and report feedback please go to: www.bangladeshworkersafety.org. 

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 2/18

Page 3: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

GENERAL INFORMATION 

General Information

Factory Name: Jamuna Apparels

Address: 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR,0, BD GAZIPUR Dhaka Bangladesh

Country: Bangladesh

Province: Dhaka

City: GAZIPUR

Zip Code: 1710

Audit Duration: 2 Days

Re-Audit: Re-Audit After 0 Months

Draft Report Date : 05-25-2014

Final Report Date : 05-29-2014

Are all action items fromprevious assessmentcomplete? :

N/A

Buildings in Complex : There are 6 buildings on the premises. These are: 1. Main Building (RCC), 2. Utility Building, 3. Fire PumpRoom (RCC), 4. Child Care Shed, 5. Gas Meter Room, 6. Wastage Godown Shed.

Is the building(s) ownedor rented by theFactory?:

Rented

Number of BuildingLevels (Stories) :

1. Main Building: Building Height (Highest occupied floor level) 21.52m or 70.50 ft. Storied above grade: 8(including Mezzanine & lift room floor) Storied below Grade: 0, Occupied levels: 8. 2. Utility Building: BuildingHeight (Highest occupied floor level) 03.05m or 10.00 ft. Storied above grade: 2, Storied below Grade: 0,Occupied levels: 2. 3. Fire Pump Room: Building Height (Highest occupied floor level) 3.05m or 10.00 ft.Storied above grade: 2, Storied below Grade: 1, Occupied levels: 3. 4.Child Care Shed: Building Height(Highest occupied floor level) at Grade. Storied above grade: 1, Storied below Grade: 0, Occupied levels: 1. 5.Gas Meter Room: Building Height (Highest occupied floor level)at Grade. Storied above grade: 1, Storiedbelow Grade: 0, Occupied levels: 1. 6. Wasteage Godown Shed: Building Height (Highest occupied floor level)at Grade. Storied above grade: 1, Storied below Grade: 0, Occupied levels: 1.

Approximate BuildingArea (SF) :

Total Area: 98739.14 sft 1. Main Building: 94962.38 sft , 2. Utility Building: 360.46 sft, 3. Fire Pump Room:543.48 sft, 4. Child Care Shed: 1721.6 sft, 5. Gas meter Room: 75.72 sft, 6. Wastage Godown Shed: 1076 sft.

Date of BuildingConstruction :

1. Main Building: June-1983, 2. Utility Building: 2006, 3. Fire Pump Room: April-2014, 4. Child Care Shed:2006, 5. Gas meter Room: 2006, 6. Wastage Godown Shed: 2012.

Date of Last Building Fire Pump Room: April-2014.

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 3/18

Page 4: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Renovation/Addition :

Ancillary Structures inComplex :

There are 5 ancillary structures: 1. Utility Building, 2. Fire Pump Room (RCC), 3. Child Care Shed, 4. GasMeter Room, 5. Wastage Godown Shed.

Approximate AncillaryStructures Area (SF) :

Total Area: 3776.16 sft: 1. Utility Building: 360.46 sft, 2. Fire Pump Room: 543.48 sft, 3. Child Care Shed:1721.6 sft, 4. Gas meter Room: 75.72 sft, 5. Wastage Godown Shed: 1076 sft.

Number of Occupants : Total Occupant: 1046, 1. Main Building: 1034 (Ground Floor: 20, Mezzanine Floor: 5, 1st Floor: 100, 2ndFloor: 170, 3rd Floor: 250, 4th Floor: 268, 5th Floor: 220, Roof: 1), 2. Utility Building: 4 (Ground Floor: 3, 1stFloor: 1), 3. Fire Pump Room: 2 (Basement: 2, Ground Floor: 0, 1st Floor: 0), 4. Child Care Shed: 5, 5. Gasmeter Room: 0, 6. Wastage Godown Shed: 1.

Provide brief descriptionof the electrical systemfor each building.:

DPDC power is connected to LT panel via 400KVA transformer. 410KVA & 110KVA diesel standby generatoris connected to LT via changeover switch-1 & change over switch-2. 11KVA generator is used for to run theemergency load lift, fire pump etc. 400KVA transformer, HT panel, LT panel & 410KVA generator is placedinside substation room. 110KVA generator is placed in the shed out side. Power is fed to the floor via LT, oneMDB, ten numbers of DB.

Physical location ofSubstation? :

Substation is located in the Ground floor of the main building.

What equipment/loadsdoes the UPS serve? :

UPS serves Desktop computer, Server. IPS serves Fire alarm, emergency lighting and exit signage.

 

 

 

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 4/18

Page 5: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

ASSESSMENT FINDINGS 

Electrical System Maintenance

Question: Have workers that operate and maintain the electrical system receivedelectrical safety training? Is training documentation on site?

 

Priority Level: High

Non-Compliance Level: 3

Description: Workers that operate and maintain the electrical system have not receivedelectrical safety training.

Source of Findings: Worker Interviews: No electrical safety training has taken place.

Suggested Plan ofAction:

Develop and implement an electrical safety program and providedocumentation. Include key topics such as lock-out tag-out procedures,personal protective equipment requirements, etc. Reference NFPA 70e forexample program requirements.

Suggested DeadlineDate:

19 Jul 2014

Standard: Reference NFPA 70e for example

Question: Is the electrical switchgear and panel boards inspected on an annual basis toensure that the equipment is installed in accordance with the listed ratings?

 

Priority Level: Medium

Non-Compliance Level: 3

Description: The electrical switchgear and panel boards are not inspected on an annualbasis to ensure that the equipment is installed in accordance with the listedratings.

Source of Findings: Document Review: No annual inspection records for electrical switchgear andpanel boards.

Suggested Plan ofAction:

Inspect electrical switchgear and panel boards on an annual basis to ensurethat the equipment is in good working condition and provide documentation.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standards Part 10 Section 10.13.8 Electrical Inspections

Question: Are thermographic scans of electrical equipment completed at least everythree years?

 

Priority Level: Medium

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 5/18

Page 6: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Non-Compliance Level: 3

Description: Thermographic scans of electrical equipment are not completed at least onceevery three years.

Source of Findings: Document Review: No thermographic scans of electrical equipment have beencompleted.

Suggested Plan ofAction:

Complete thermographic scans at least once every three years and providedocumentation. Thermographic scans should be completed in accordance withthe Standard for Infrared Inspection of Electrical Systems & RotatingEquipment and NFPA70B or a comparable standard.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standards Part 10 Section 10.13.8 Electrical Inspections

Question: Transformers do not contain harmful substances such as PCBs.  

Priority Level: Medium

Non-Compliance Level: 3

Description: There was no document found that can prove that the transformer doesn'tcontain any harmful substances, such as PCBs.

Source of Findings: Document Review: No documentation was found.

Suggested Plan ofAction:

Perform a test to prove whether transformers contain harmful substance (likePCBs) or not, and provide documentation. If any harmful substance is foundtake necessary actions to ensure a healthy environment.

Suggested DeadlineDate:

19 Jul 2014

Standard: Not Applicable

Question: Are periodic safety inspections of the electrical system components completedand documented?

 

Priority Level: Medium

Non-Compliance Level: 3

Description: No periodic safety inspections of the electrical system components have beencompleted.

Source of Findings: Worker Interviews: No periodic safety inspections of the electrical system.

Suggested Plan ofAction:

Establish a periodic inspection program to ensure that the electrical systemsare free from damage, debris, dirt, lint, etc. Maintain records concerninginspections and follow up actions.

Suggested DeadlineDate:

19 Jul 2014

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 6/18

Page 7: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Standard: Alliance Standard Part 10 Section 10.13 Inspection and Testing and Part 13Section 13.6 Housekeeping

Question: A transformer oil analysis is routinely completed on main service transformers.  

Priority Level: Low

Non-Compliance Level: 3

Description: A transformer oil analysis is not routinely completed on main servicetransformers.

Source of Findings: Document Review: Transformer oil analysis is not routinely completed.

Suggested Plan ofAction:

Complete an oil analysis on applicable transformers at appropriate intervalsbased on voltage and power, and provide documentation.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standard Part 10 Section 10.13.8 Electrical Inspections

Electrical System Conditions

Question: The substation room has the required fire rating/protection and is physicallyseparated from the remainder of the building.

 

Priority Level: High

Non-Compliance Level: 3

Description: The substation room does not have the required fire rating/protection and isnot physically separated from the remainder of the building. Location:Substation Room

Source of Findings: Photograph: There is no fire rating/protection for the substation room, orphysical separation.

Suggested Plan ofAction:

Provide adequate fire rating/protection for the substation room and ensure thatit is separated from the rest of the building.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standard Part 3 Section 3.4.2.1.4

Question: All metal in the building is connected to the building earthing/grounding systemsuch as metal rebar in concrete, metal frame of building, or metal water pipe.

 

Priority Level: High

Non-Compliance Level: 3

Description: Not all of the metal in the building is connected to the building earthing systemsuch as metal rebar in concrete, metal frame of building, or metal water pipe.

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 7/18

Page 8: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Source of Findings: Worker Interviews: Not all metal in the building is connected to the buildingearthing system.

Suggested Plan ofAction:

Connect all metal in the building to the building earthing system such as metalrebar in concrete, metal frame of building, or metal water pipe.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standard Part 10 Section 10.10 Earthing

Question: Are all switchboards and/or distribution boards metal enclosed with a deadfront construction?

 

Priority Level: High

Non-Compliance Level: 1

Description: Distribution boards are metal enclosed but don't have a dead frontconstruction. Location: LT panel/ Substation.

Source of Findings: Photograph: No dead front construction on distribution boards.

Suggested Plan ofAction:

Provide all distribution boards in metal enclosure with a dead frontconstruction.

Suggested DeadlineDate:

21 Jun 2014

Standard: Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and MetalClad Switchgear

Question: Indications of overheating, overloading, or signs of burning were not observed.  

Priority Level: High

Non-Compliance Level: 1

Description: Signs of burning were observed. Location: Socket/Dining section.

Source of Findings: Photograph: Signs of burning.

Suggested Plan ofAction:

Find out the cause of the burning, correct the problem, and replace of theconductors or equipment.

Suggested DeadlineDate:

24 May 2014

Standard: Alliance Standard Part 10 Section 10.3.5

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 8/18

Page 9: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Question: Shielding or additional insulation is provided for wiring exposed to externalheat sources.

 

Priority Level: High

Non-Compliance Level: 1

Description: No additional insulation is provided for wiring exposed to external heatsources. Location:Boiler Room

Source of Findings: Photograph: Inadequate insulation.

Suggested Plan ofAction:

Provide Shielding for wiring exposed to external heat sources.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.3.4.2 External heat sources.

Question: Power and telecommunication or antenna cables are led in separately.  

Priority Level: Medium

Non-Compliance Level: 3

Description: Power and telecommunication or antenna cables are not led in separately.Location: IT Room(1st Floor)

Source of Findings: Photograph: Power and telecommunication or antenna cables are not led inseparately.

Suggested Plan ofAction:

Lay in telecommunication or antenna cables separately to the main point ofservice. Power and telecommunications cables must have separate entrances.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standards Part 10 Section 10.3.10 Service Entry

Question: Are all switchboards and/or distribution boards properly grounded (earthed)?  

Priority Level: Medium

Non-Compliance Level: 3

Description: Distribution boards are not properly grounded. The size of the earthing cablesare inadequate. Location: All distribution boards.

Source of Findings: Photograph: Inadequate grounding.

Suggested Plan ofAction:

Provide proper grounding (earthing) for distribution boards as per BNBCsection 2.8.1.

Suggested DeadlineDate:

19 Jul 2014

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 9/18

Page 10: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Standard: Alliance Standard Part 10 Section 10.10.2 Circuit and System Earthing

Question: Are switchboards and/or distribution boards provided with physical means toprevent the installation of more over current devices than that number forwhich the panel board was designed, rated, and listed.

 

Priority Level: Medium

Non-Compliance Level: 3

Description: Distribution boards are not provided with physical means to prevent theinstallation of more over current devices than that number for which the panelboard was designed, rated, and listed. Locations: All DBs

Source of Findings: Photograph: No means to prevent the installation of more over current devicesthan that number for which the panel board was designed, rated, and listed.

Suggested Plan ofAction:

Ensure switchboards and/or distribution boards are provided with physicalmeans to prevent the installation of more over current devices than thatnumber for which the panel board was designed, rated, and listed, followingNFPA 70 section 408.54.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and MetalClad Switchgear

Question: Each circuit is provided with a dedicated neutral.  

Priority Level: Medium

Non-Compliance Level: 3

Description: Each circuit is not provided with a dedicated neutral. Locations: All DBs.

Source of Findings: Photograph: No dedicated neutral.

Suggested Plan ofAction:

Provide a dedicated neutral for each circuit.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standards Part 10 Section 10.3 Electrical Wiring and Cabling

Question: Stranded conductors having a nominal cross-sectional area 6mm2 or greaterare provided with cable sockets. Conductors below 6 mm2 without cablesockets, all strands at the exposed ends are soldered together or are crimpedusing suitable sleeve or ferrules.

 

Priority Level: Medium

Non-Compliance Level: 3

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 10/18

Page 11: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Description: Cable sockets are not provided for stranded conductors. Locations: All DBs.

Source of Findings: Photograph: No cable socket provided.

Suggested Plan ofAction:

Provide cable sockets for stranded conductors having a nominal cross-sectional area of 6mm2 or greater.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.3.8.3 Cable Ends

Question: Lighting fixtures are supported from the structure and seismic bracing isinstalled as required.

 

Priority Level: Medium

Non-Compliance Level: 3

Description: Lighting fixtures are not supported properly. Location : Most of the floor area.

Source of Findings: Photograph: Lighting fixtures are not supported properly.

Suggested Plan ofAction:

Ensure lighting fixtures are supported from the structure and seismic bracing isinstalled as required.

Suggested DeadlineDate:

21 Jun 2014

Standard: Alliance Standards Part 10 Section 10.3.6 Lighting Fittings

Question: Electrical wiring and conduit is properly supported.  

Priority Level: Medium

Non-Compliance Level: 2

Description: Electrical wiring and conduit is not properly supported in substation room.Locations:Substation Room

Source of Findings: Photograph: Inadequate cable support.

Suggested Plan ofAction:

Provide adequate supports for electrical wiring and conduit.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standard Part 10 Section 10.3.2, 10.3.4.3, and 10.3.5

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 11/18

Page 12: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Question: Are there additional areas of non-compliance to report?  

Priority Level: Medium

Non-Compliance Level: 2

Description: Transformer breather’s oil cup was empty, and the breather's silica gel wasfound to be pink.

Source of Findings: Photograph: Transformer breather’s oil cup was empty, and the breather'ssilica gel was found to be pink.

Suggested Plan ofAction:

Ensure that the breather is filled up with fresh silica gel and that the oil cup isnot empty.

Suggested DeadlineDate:

18 Apr 2014

Standard: Not Applicable

Question: The substation room has adequate illumination levels.  

Priority Level: Medium

Non-Compliance Level: 1

Description: The substation room is not illuminated properly. There are only two sets of36W tube lights installed, which are inadequate for the substation room.

Source of Findings: Photograph: Improper illumination in the substation room.

Suggested Plan ofAction:

Provide additional light fixtures to increase illumination levels, as provided inthe BNBC.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standard Part 10 Section 10.13.7.1 Inspection of SubstationInstallations.

Question: Do switchboards and/or distribution boards have capacity information labels?  

Priority Level: Medium

Non-Compliance Level: 1

Description: Distribution boards have capacity information labels but not labels that arepermanent in nature. Locations: All DBs.

Source of Findings: Photograph: Capacity information labels are not permanent in nature.

Suggested Plan ofAction:

Provide permanent capacity information labels (indicating maximum currentrating, number of circuit breakers, etc.) for distribution boards.

Suggested DeadlineDate:

05 Jul 2014

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 12/18

Page 13: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Standard: Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And MetalClad Switchgear and 10.13.7 Inspection of the Installation

Question: Cable joints are through porcelain/PVC connectors with PIB tape woundaround joint.

 

Priority Level: Medium

Non-Compliance Level: 1

Description: An improper cable joint was found. Location: DB Sewing section/5th floor.

Source of Findings: Photograph: Improper cable joint.

Suggested Plan ofAction:

Ensure that cable joints are through porcelain/PVC connectors with PIB tapewound around joint.

Suggested DeadlineDate:

19 Jul 2014

Standard: Alliance Standards Part 10 Section 10.3.8.4 Cable Joints

Question: Electrical connections at equipment, fixtures, etc are properly secured.  

Priority Level: Medium

Non-Compliance Level: 1

Description: Electrical connections at equipment, fixtures etc. are not properly secured inthe boiler room.

Source of Findings: Photograph: Electrical connections are not secured.

Suggested Plan ofAction:

Ensure that electrical connections at equipment, fixtures, etc. are properlysecured.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.3.1 Electrical Connections

Question: Are junction boxes and other electrical devices provided with covers?  

Priority Level: Medium

Non-Compliance Level: 1

Description: Electrical devices are not provided with covers.

Source of Findings: Photograph: Electrical cover missing.

Suggested Plan ofAction:

Provide adequate covers for all junction boxes and electrical devices.

Suggested Deadline 21 Jun 2014

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 13/18

Page 14: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Date:

Standard: Alliance Standard Part 10 Section 10.3.5 and 13.6.2

Question: Signage indicating the prohibition of light fixtures without protective covers isinstalled at required locations.

 

Priority Level: Low

Non-Compliance Level: 3

Description: No signage indicating the prohibition of light fixtures without protective coversis installed at required locations. Location: Fabric warehouse

Source of Findings: Photograph: No signage indicating the prohibition of installation of naked lightfixtures.

Suggested Plan ofAction:

Ensure Signage indicating the prohibition of light fixtures without protectivecovers is installed at required locations.

Suggested DeadlineDate:

21 Jun 2014

Standard: Alliance Standards Part 10 Section 10.15 Naked Lights

Question: Required equipment and safety signage is posted within the room.  

Priority Level: Low

Non-Compliance Level: 2

Description: Sufficient equipment and safety signage is not posted within the room.

Source of Findings: Photograph: Insufficient equipment and safety signage

Suggested Plan ofAction:

Indoor electrical installations that are accessible to unqualified persons shallbe made with metal-enclosed equipment. Switchgear, unit substations,transformers, pull boxes, connection boxes, and other similar associatedequipment shall be marked with appropriate caution signs. Entrances to roomsand other guarded locations that contain exposed live parts shall be markedwith conspicuous warning signs forbidding unqualified persons to enter.Caution, warning, danger signs, or labels should meet the followingrequirements: (1) The marking shall adequately warn of the hazard usingeffective words and/or colors and/or symbols. American National StandardsInstitute ANSI Z535.4-2011, Product Safety Signs and Labels, providesguidelines for suitable font sizes, words, colors, symbols, and locationrequirements for labels. (2) The marking shall be permanently affixed to theequipment or wiring method and shall not be hand written. The exception isthat portions of labels or markings that are variable, or that could be subject tochanges, shall be permitted to be hand written and shall be legible. (3) Thelabel shall be of sufficient durability to withstand the environment involved.ANSI Z535.4-2011, Product Safety Signs and Labels, provides guidelines forthe design and durability of safety signs and labels for application to electricalequipment

Suggested DeadlineDate:

21 Jun 2014

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 14/18

Page 15: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Standard: Alliance Standard Part 10 Section 10.3.7, Section 10.7.3, and 10.13.7, NFPA70 Chapter 1 Article 110.21, and Bangladesh Electricity Rules of 1937 Rule 46

Emergency Power System

Question: Is the generator room properly rated and physically separated from theremainder of the building?

 

Priority Level: High

Non-Compliance Level: 3

Description: The generator room is not properly rated or physically separated from theremainder of the building.

Source of Findings: Photograph: Generator room is not properly rated or physically seperated fromthe remainder of the building.

Suggested Plan ofAction:

Ensure that the generator room is properly rated and physically separatedfrom the remainder of the building.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.8.4 Generator Room

Question: Are cable trenches properly covered?  

Priority Level: High

Non-Compliance Level: 3

Description: Cable trenches are not properly covered in the substation room. Location:Substation Room

Source of Findings: Photograph: No cable trench cover.

Suggested Plan ofAction:

Provide adequate cover for cable trenches.

Suggested DeadlineDate:

21 Jun 2014

Standard: Alliance Standard Part 10 Section 10.13.7 Inspection of the Installation

Question: Are emergency power switchboards, distribution boards, and circuits properlyidentified?

 

Priority Level: High

Non-Compliance Level: 3

Description: Emergency power switchboards, distribution boards, and circuits are notproperly identified.

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 15/18

Page 16: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Source of Findings: Photograph: No identification of emergency distribution boards and circuits.

Suggested Plan ofAction:

Ensure proper identification of emergency power switchboards, distributionboards, and circuits.

Suggested DeadlineDate:

21 Jun 2014

Standard: NFPA 70 Chapter 7 Article 700.10 Wiring, Emergency System

Question: Is the generator frame earthing (grounding) provided at two separate points?  

Priority Level: Medium

Non-Compliance Level: 3

Description: Generator frame grounding is not provided at two separate points. Location:Generator Room

Source of Findings: Photograph: Inadequate generator frame earthing.

Suggested Plan ofAction:

Provide two separate points of earthing (grounding) for the generator frame.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standard 10.8.2.2

Question: Is the generator room appropriately sized in order to properly access thegenerator to perform routine maintenance activities?

 

Priority Level: Medium

Non-Compliance Level: 3

Description: The size of generator room is not appropriate. Location: Generator Room

Source of Findings: Photograph: Inadequate generator room size.

Suggested Plan ofAction:

Ensure appropriate size for generator room in order to properly access thegenerator to perform routine maintenance activities.

Suggested DeadlineDate:

13 Sep 2014

Standard: Alliance Standard Part 10 Section 10.8.4 Generator Room

Question: Is the generator room properly illuminated?  

Priority Level: Medium

Non-Compliance Level: 1

Description: The generator room is not properly illuminated. There are two 36W tube lights.Location: Generator Room

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 16/18

Page 17: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Source of Findings: Photograph: Inadequate illumination.

Suggested Plan ofAction:

Provide additional lighting to ensure that the generator room is properlyilluminated.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.8.4 Generator Room

Question: Is the appropriate type and number of firefighting equipment installed insidethe generator room?

 

Priority Level: Low

Non-Compliance Level: 1

Description: The appropriate type of firefighting equipment is installed, but the number isinadequate inside the generator room. In addition, the fire extinguisher isplaced outside the generator room in a location which is not readily accessible(12 feet from the generator room entrance) .

Source of Findings: Photograph: Inadequate firefighting equipment

Suggested Plan ofAction:

Install the appropriate type and number of firefighting equipment inside thegenerator room.

Suggested DeadlineDate:

21 Jun 2014

Standard: Is the appropriate type and number of firefighting equipment installed insidethe generator room?

Lightning Protection System

Question: The lightning protection ground terminals are bonded to the building orstructure grounding.

 

Priority Level: Medium

Non-Compliance Level: 3

Description: The lightning protection ground terminals are not bonded to the building orstructure grounding.

Source of Findings: Worker Interviews: The lightning protection ground terminals are not bondedwith the structure grounding.

Suggested Plan ofAction:

Bond the lighting protection ground terminals to the building or structuregrounding.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.11 Lightning Protection

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 17/18

Page 18: INITIAL ELECTRICAL ASSESSMENT REPORT - … · INITIAL ELECTRICAL ASSESSMENT REPORT ... Substation is located in the Ground floor of the main ... No electrical safety training has

Question: The appropriate number of down conductors are installed based on thebuilding size.

 

Priority Level: Medium

Non-Compliance Level: 2

Description: The appropriate numbers of down conductors are not installed based on thebuilding size.

Source of Findings: Photograph: Inadequate number of down conductors.

Suggested Plan ofAction:

Consult with an expert engineer to obtain a detailed design of the lightningprotection system. Verify that the appropriate number of down conductors areinstalled for this building size and/or provide the appropriate number of downconductors per the detailed design if not already installed.

Suggested DeadlineDate:

05 Jul 2014

Standard: Alliance Standards Part 10 Section 10.11 Lightning Protection

 

 

FactoryName:

Jamuna Apparels

Address:94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,,TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh

Assessor: Bureau Veritas

Date: 11 Apr 2014

Created with EO.Pdf for .NET trial version. http://www.essentialobjects.com.

The Alliance for Bangladesh Worker Safety Page 18/18