Sonoco , Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018
Infrared Thermographic InspectionProvided for
Infrared Thermography
Electrical Inspections
Mechanical Inspections
Roof Moisture Analysis
Building Envelope / Heat Loss
Power Quality Consulting
Power Quality Surveys
Load Studies
Harmonic Content Analysis
Power Metering
Electrical Mapping/Documentation
1-Line Electrical Drawings
Panel Schedules
Panel Identification / Labeling
1-Critical 60-Above NA0 = 0% NA
Sonoco Protective Solutions - Putnam CT
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Current Inspection No: 457129 Park RoadSonoco Protective Solutions - Putnam
Putnam, CT 06260Report Date: 8/18/2018Inspected By : Fitzpatrick, Mike
Recently, a Dyna Scan Thermographer performed an Infrared Thermographic Inspection of the electrical distribution system at your facility. The objective of this inspection was to expose temperature extremes, which could be indicative of problems and defects in the electrical system.
An Infrared Imager detects radiated energy as heat emanating from the target. In utilizing this tool for examining electrical power circuitry, it must be recognized that temperatures indicative of defects will normally be observed only in circuits which are normally or heavily loaded. Scanning lightly loaded or de-energized circuits may produce inconclusive results.
This report is set up to list all distribution panels and current carrying devices in an organized manner. The electrical equipment and the results of the inspection are listed for each location. A defect report is provided for each problem area found during the inspection. This defect report includes a load analysis, a visual inspection comment, and recommendations for corrective action.
The report summary on the following page is an arbitrary guideline intended to provide perspective with respect to temperature differences between target areas and reference points. Take note that many variables may affect the temperature differences, most notably the ambient temperature, wind speed and circuit load.
Many electrical panels such as switchboards and motor control centers contain multiple circuits that may or may not be de-energized at the time of inspection. Dyna Scan technicians will identify in the equipment inventory in this report when it is obvious that equipment is not running at time of inspection. However, without taking load readings on every circuit in each individual panel, it is impossible to identify all equipment and circuits that are not under load.
If you should have any questions regarding the scan or this report, feel free to contact our office at any of the numbers below. We appreciate the opportunity to be of service to you and look forward to working with you in the future.
Sincerely,
Jim O'Brien - Director of Operations
Dyna Scan Technical Services
(513) 245-5951
NOTE-In the course of an Infrared Thermography Inspection on electrical distribution equipment, may times circuits are reported as being "overloaded." In general this statement is made on the basis of instantaneous amperage readings which have been found to be in excess of 80% of the overcurrent devices nameplate rating. In accordance to the National Electrical Code Articles 210-22(c) and 384-16(c) the total load on an overcurrent device shall not exceed 80% of its rating where in normal operation the load will continue for 3 hours or more (See NEC for exceptions).
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Overview:
The Infrared Electrical Inspection was performed by Dyna Scan Technical Services, by a certified Infrared Thermographer. All of the items inspected are listed in this InspecTrend report. Any anomalies are listed in order of priority based on the component's temperature rise, as measured from a reference component of equal type and load at the time of the inspection. Dyna Scan Technical Services assumes no liability directly or indirectly as a result of this inspection.
Page 1Current Inspection No:
Previous Inspection No:
Priority Temp Rise Prior InspectionCurrent Inspection Percent Change
Sonoco , Sonoco Protective Solutions - Putnam CT
4571 August 16, 2018
Report Date: 8/18/2018
Sonoco Protective Solutions - Putnam CT
1-Critical 60-Above NA 3 = 33% NA
2-Serious 40 - 59 NA 0 = 0% NA
3-Important 11 - 39 NA 5 = 56% NA
4-Minor 1 - 10 NA 1 = 11% NA
5-Normal 0 NA 0 = 0% NA
Total Tested Problems:
Number of New Documented Problems:
Number of Tested re-occuring Problems:
Number of prior problems which were Not Tested this inspection :
Number of Total Open Problems :
Number of prior problems which tested Normal this inspection : NA
9
NA
0 = 0% NA
NA 9 =100%
9 NA
NA
NA
NA
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Important - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Infrared Inspection Inventory
Test Status Problem #Location / Name
Page: 1
TBT = To Be TestedNT/NL = Not Tested/No Load
NT/TC = Not Tested/Time ConstraintNT/UR = Not Tested/Under Repair
Equipment Test Status KeyCurrent Inspection No: 4571
29 Park RoadSonoco Protective Solutions - Putnam
Putnam, CT 06260Report Date: 8/18/2018Inspected By
NT/NA = Not Tested/Not Accessible
Fitzpatrick, Mike
Equipment Type
Location: Main Floor Perimeter TESTED
LSPP2 TESTEDBranch Panel
CTR-5 TESTEDBranch Panel
#3 TESTED E1Branch Panel
DRYER TESTEDControl Panel
DRYER TESTEDStarter-Disconnect
SP1 TESTEDBranch Panel
KILN ROOM TESTEDBranch Panel
CORRUGATOR BAILER TESTEDDisconnect
GARBAGE COMPACTOR TESTEDControl Panel
GARBAGE COMPACTOR TESTEDDisconnect
UNNAMED TESTEDDisconnect
#4 TESTEDBranch Panel
PPPFF TESTEDBranch Panel
F1 TESTEDStarter
F2 TESTEDStarter
F3 TESTEDStarter
F4 TESTED E2Starter
F5 TESTEDStarter
F6 TESTEDStarter
F7 TESTEDStarter
F8 TESTEDStarter
LPPF TESTEDBranch Panel
UNNAMED TESTEDBreaker
#9 TESTEDBranch Panel
#10 TESTEDBranch Panel
LP-2B TESTEDBranch Panel
LP-2A TESTEDBranch Panel
1A TESTEDStarter
1B TESTEDStarter
1C TESTEDStarter
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Infrared Inspection Inventory
Test Status Problem #Location / Name
Page: 2
TBT = To Be TestedNT/NL = Not Tested/No Load
NT/TC = Not Tested/Time ConstraintNT/UR = Not Tested/Under Repair
Equipment Test Status KeyCurrent Inspection No: 4571
29 Park RoadSonoco Protective Solutions - Putnam
Putnam, CT 06260Report Date: 8/18/2018Inspected By
NT/NA = Not Tested/Not Accessible
Fitzpatrick, Mike
Equipment Type
1D TESTEDStarter
M1 (Machine Shop) TESTEDBranch Panel
Location: Main Center Machine Line TESTED
E13 NTNLControl Panel
SP1 TESTEDBranch Panel
PP1 TESTEDBranch Panel
E9 TESTEDControl Panel
E32 NTNLDisconnect
UNNAMED NTNLDisconnect
PRESS 13 NTNLControl Panel
PRESS 9 NTNLControl Panel
E31 NTNADisconnect
E4 TESTEDDisconnect
E4 TESTEDStarter
PRESS 4 TESTEDControl Panel
E1 TESTEDDisconnect
E1 TESTEDStarter
UNNAMED TESTEDDisconnect
UNNAMED TESTEDStarter
PRESS 2 TESTEDControl Panel
E2 TESTEDDisconnect
PRESS 2 TESTED E3Disconnect
PRESS 2 TESTEDStarter
BLUE VALVE TESTEDControl Panel
SP1 TESTEDStarter
PRESS 10 TESTEDControl Panel
E10 TESTEDDisconnect
E10 TESTEDStarter
PRESS 3 TESTED E4Control Panel
E3 TESTEDDisconnect
PRESS 3 TESTEDDisconnect
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Infrared Inspection Inventory
Test Status Problem #Location / Name
Page: 3
TBT = To Be TestedNT/NL = Not Tested/No Load
NT/TC = Not Tested/Time ConstraintNT/UR = Not Tested/Under Repair
Equipment Test Status KeyCurrent Inspection No: 4571
29 Park RoadSonoco Protective Solutions - Putnam
Putnam, CT 06260Report Date: 8/18/2018Inspected By
NT/NA = Not Tested/Not Accessible
Fitzpatrick, Mike
Equipment Type
PRESS 3 TESTEDStarter
PRESS 8 TESTEDControl Panel
E8 TESTEDDisconnect
E8 TESTED E5Starter
REGRIND 1 TESTEDStarter
REGRIND 1.1 TESTEDStarter
PRESS 5 TESTEDContol Panel
E5 TESTEDDisconnect
E5 TESTEDStarter
FANS TESTEDStarter
PRESS 6 TESTEDCrontrol Panel
E6 TESTED E6Disconnect
PRESS 6 TESTEDDisconnect
PRESS 6 TESTEDStarter
PRESS 7 TESTEDControl Panel
E7 TESTEDDisconnect
E7 TESTEDStarter
PRESS 11 NTNLControl Panel
E11 NTNLDisconnect
E11 NTNLStarter
PRESS 12 TESTEDControl Panel
E12 TESTEDDisconnect
E12 TESTEDStarter
REGRIND 2 TESTEDStarter
PRESS PANEL 2 TESTEDDisconnect
HECP GRANULATOR TESTEDControl Panel
E16 TESTEDDisconnect
Location: Expanding Mezzanine TESTED
BLOWER MOTOR 1 TESTEDStarter
BLOWER MOTOR 2 TESTEDStarter
Location: Mezzanine Over Office TESTED
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Infrared Inspection Inventory
Test Status Problem #Location / Name
Page: 4
TBT = To Be TestedNT/NL = Not Tested/No Load
NT/TC = Not Tested/Time ConstraintNT/UR = Not Tested/Under Repair
Equipment Test Status KeyCurrent Inspection No: 4571
29 Park RoadSonoco Protective Solutions - Putnam
Putnam, CT 06260Report Date: 8/18/2018Inspected By
NT/NA = Not Tested/Not Accessible
Fitzpatrick, Mike
Equipment Type
PP1 TESTEDBranch Panel
SP1 TESTED V1Branch Panel
Location: Old Basement TESTED
OLD SERVICE MAIN TESTEDSwitch Board
#4 TESTEDDistribution Panel
#3 TESTEDDistribution Panel
UNNAMED NTNLBreaker
#4 TESTEDBranch Panel
SPDS TESTEDBranch Panel
PPDS TESTEDBranch Panel
RO WATER PUMP TESTEDDisconnect
RO WATER PUMP TESTEDControl Panel
CITY SEWER T4 TESTEDControl Panel
T3 AIR PUMP TESTEDControl Panel
HEAT EXCHANGER PUMP TESTEDStarter
WATER SYSTEM MAIN TESTED E7Disconnect
WATER SYSTEM MAIN TESTED E8Control Panel
NEW SERVICE MAIN NTNA V2Switch board
AIR COMPRESOR PNL TESTEDDistribution Panel
SP1 TESTEDBranch Panel
FAN TESTEDStarter
COOLING TOWER (Outiside Left) TESTEDDisconnect
COOLING TOWER (Outside Right) TESTEDDisconnect
E29 TESTEDDisconnect
UNNAMED TESTEDDisconnect
Location: Basement Boiler Room TESTED
DA TANK TESTEDControl Panel
PP BR TESTEDBranch Panel
SP BP TESTEDBranch Panel
CONDESATION PUMP TESTEDControl Panel
LCBR2 TESTEDBranch Panel
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Infrared Inspection Inventory
Test Status Problem #Location / Name
Page: 5
TBT = To Be TestedNT/NL = Not Tested/No Load
NT/TC = Not Tested/Time ConstraintNT/UR = Not Tested/Under Repair
Equipment Test Status KeyCurrent Inspection No: 4571
29 Park RoadSonoco Protective Solutions - Putnam
Putnam, CT 06260Report Date: 8/18/2018Inspected By
NT/NA = Not Tested/Not Accessible
Fitzpatrick, Mike
Equipment Type
BOILER 2 FRONT TESTEDControl Panel
BOILER 2 SIDE TESTEDControl Panel
BOILER 2 TESTED E9Disconnect
DEARATOR TESTEDDisconnect
BOILER 1 FRONT TESTEDControl Panel
BOILER 1 SIDE TESTEDControl Panel
BOILER 1 TESTEDDisconnect
LCBR1 TESTEDBranch Panel
TRANSFORMER TESTEDDisconnect
BOILER 3 FRONT TESTEDControl Panel
BOILER 3 SIDE TESTEDControl Panel
BOILER 3 TESTEDDisconnect
TRANSFORMER TESTEDDisconnect
LCBR3 TESTEDBranch Panel
Location: New Basement TESTED
FAN 1 TESTEDStarter
FAN 2 TESTEDStarter
FAN 3 TESTEDStarter
FAN 4 TESTEDStarter
LP 1A TESTEDBranch Panel
LP 1B TESTEDBranch Panel
UNNAMED TESTEDTransformer
OFFICE TESTEDBranch Panel
UNNAMED TESTEDTransformer
UNNAMED (Left) TESTEDBranch Panel
UNNAMED (Right) TESTEDBranch Panel
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 1
Location: Main Floor Perimeter #3
Severity: 4-Minor
Recommendation:
Further investigation is required to determine the correct repair procedure.
Equipment Type:Branch Panel
Target is breaker #2. Overload on breaker. Amp draw between 13 and 18.
Infrared Inspection Report
Comment:
Target Point
Breaker #2: 95 F
Reference Point
Breaker #1: 92 F
Temperature Difference
3 F
Breaker #2: 18
Breaker #1: 0
Load Test Results:
20Rated Load:
90% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 2
Location: Main Floor Perimeter F4
Severity: 3-Important
Recommendation:
Due to age and condition of target, recommend replacing
Equipment Type:Starter
Target is the (A) phase contact on starter.
Infrared Inspection Report
Comment:
Target Point
(A) Phase: 125 F
Reference Point
(C) Phase: 92 F
Temperature Difference
33 F
(A) Phase: 3
(C) Phase: 3
(B) Phase: 3
Load Test Results:
Rated Load:
% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 3
Location: Main Center Machine Line PRESS 2
Severity: 1-Critical
Recommendation:
Shut off power to assembly and inspect knife switch for proper blade tension and alignment. Clean blades thoroughly. Repair or replace parts as necessary.
Equipment Type:Disconnect
Target is the (C) phase knife switch on disconnect. Staff notified.
Infrared Inspection Report
Comment:
Target Point
(C) Phase: 186 F
Reference Point
(A) Phase: 111 F
Temperature Difference
75 F
(C) Phase: 30
(A) Phase: 30
(B) Phase: 31
Load Test Results:
60Rated Load:
50% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 4
Location: Main Center Machine Line PRESS 3
Severity: 3-Important
Recommendation:
Check lug connection.
Equipment Type:Control Panel
Target is the (B) phase wire connection on disconnect. Visual heat damage.
Infrared Inspection Report
Comment:
Target Point
(B) Phase: 126 F
Reference Point
(A) Phase: 108 F
Temperature Difference
18 F
(B) Phase:
(A) Phase:
Load Test Results:
Rated Load:
% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 5
Location: Main Center Machine Line E8
Severity: 3-Important
Recommendation:
Check lug connection.
Equipment Type:Starter
Target is the load side Lug connection on breaker.
Infrared Inspection Report
Comment:
Target Point
Load Side: 130 F
Reference Point
Line Side: 110 F
Temperature Difference
20 F
Load Side:
Line Side:
Load Test Results:
20Rated Load:
% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 6
Location: Main Center Machine Line E6
Severity: 3-Important
Recommendation:
Shut off power to disconnect and remove the a-phase fuse. Clean fuse and fuse clips. Inspect fuse clips for proper tension and repair or replace parts as necessary. Upon completion, rescan target area with heat gun.
Equipment Type:Disconnect
Target is the (A) phase fuse clip on disconnect.
Infrared Inspection Report
Comment:
Target Point
(A) Phase: 128 F
Reference Point
(C) Phase: 110 F
Temperature Difference
18 F
(A) Phase: 16
(C) Phase: 17
(B) Phase: 18
Load Test Results:
60Rated Load:
26.6667% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 7
Location: Old Basement WATER SYSTEM MAIN
Severity: 1-Critical
Recommendation:
Shut off power to disconnect and remove the a-phase fuse. Clean fuse and fuse clips. Inspect fuse clips for proper tension and repair or replace parts as necessary. Upon completion, rescan target area with heat gun.
Equipment Type:Disconnect
Target is the (A) phase fuse clip on disconnect. Staff notified.
Infrared Inspection Report
Comment:
Target Point
(A) Phase: 218 F
Reference Point
(C) Phase: 109 F
Temperature Difference
109 F
(A) Phase:
(C) Phase:
Load Test Results:
200Rated Load:
% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 8
Location: Old Basement WATER SYSTEM MAIN
Severity: 1-Critical
Recommendation:
Shut off power to disconnect and remove the a-phase fuse. Clean fuse and fuse clips. Inspect fuse clips for proper tension and repair or replace parts as necessary. Upon completion, rescan target area with heat gun.
Equipment Type:Control Panel
Target is the (A) phase fuse clip on fuse block. Check the (C) phase clip also. Staff notified.
Infrared Inspection Report
Comment:
Target Point
(A) Phase: 199 F
Reference Point
(B) Phase: 116 F
Temperature Difference
83 F
(A) Phase:
(B) Phase:
(C) Phase:
Load Test Results:
30Rated Load:
% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
Sonoco Protective Solutions - Putnam CT
Report Date: 8/18/2018Page: 9
Location: Basement Boiler Room BOILER 2
Severity: 3-Important
Recommendation:
Further investigation is required to determine the correct repair procedure.
Equipment Type:Disconnect
Target is the (C) phase fuse clip on disconnect.
Infrared Inspection Report
Comment:
Target Point
(C) Phase: 135 F
Reference Point
(A) Phase: 123 F
Temperature Difference
12 F
(C) Phase:
(A) Phase:
Load Test Results:
Rated Load:
% Rated Load:
Thermal Analysis:
Corrective Action LogDate: Person:
Repair Description:
Amps
Amps
Amps
Critical - Danger to life and limb, eminent danger to equipment.
Serious - Equipment failure is inevitable without immediate attention. Repair should be expedited ASAP
Intermediate - If this is not redundant equipment, repair should be scheduled ASAP.
Minor - Problem is apparent and needs to be monitored on a regular basis.
Problem Severity Definitions:
P: (513) 245-5951 F: (513) 741-9503www.dynascantech.com
INFRARED THERMOGRAPHIC INSPECTIONOF
VISUAL PROBLEMS
Provided for
Overview:
The Infrared Electrical Inspection was performed by Dyna Scan Technical Services, by a certified infrared Thermographer. All of the items inspected are listed in this InspecTrend report. Any anomalies are listed in order of priority based on the component's temperature rise, as measured from a reference component of equal type and load at the time of the inspection. Dyna Scan Technical Services assumes no liability directly or indirectly as a result of this inspection.
Current Inspection No:Prior Inspection No:
Priority Temp RisePrior
InspectionCurrent
Inspection
Percentof
Change
Sonoco , Sonoco Protective Solutions - Putnam CT
4571 August 16, 2018
Page 1
8/18/2018Report Date:
1-Critical NA 0 = 0% NA2-Serious NA 0 = 0% NA3-Important NA 2 =100% NA4-Minor NA 0 = 0% NA
Total Tested Problems:
Number of New Documented Problems:
Number of Tested re-occuring Problems:
Number of prior problems which were Not Tested this inspection :
Number of Total Open Problems
I hereby certify the above project was inspected by myself or under my direction and that the enclosed data is the direct result of this inspection.
* Summary of reoccuring problems on following page(s)
Number of prior problems which tested Normal this inspection :
Certification Level/No.:Fitzpatrick, Mike
Certified Thermographer
Dyna Scan Technical Services
NA
2
NA
0 = 0% NA
NA 2 =100%
2 NA
NANA
NA
InspecTrend - Copyright © 2002-2003Logos Computer Solutions, Inc. All rights reserved. This document may not, in whole or in part, be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form without prior written consent.
This report was generated by InspecTrend and this inspection was performed by: Dyna Scan Technical Services
29 Park Road
Sonoco
Sonoco Protective Solutions - Putnam CT
Putnam, CT 06260
Report Date: 8/18/2018
Technician:Certification Level/No.:
Fitzpatrick, MikeCertified Thermographer
Is Chronic:
Operation Priority:
Current Prob No: Visual/1
1Page
Repair Priority:
Location/Equipment Information
File:File:
Date:Date:
FLIR13802.jpgFLIR13803.jpg
8/16/20188/16/2018
No
Critical to operation
3-Important
Time:Time:
01:01 PM01:01 PM
Location: Mezzanine Over Office SP1
Visual Problem Documentation
Hazard Type: NEC violation
Recommendations: Make repairs as per the National Electric Code.What is the Cause: Multiple Circuits to One Breaker
Consequences of Hazard: Code violation
Asset ID: Branch Panel
Hazard Group: NEC Code ViolationHazard Issue: Multiple Circuits To One Breaker
Observations: NEC violation. Multiple circuits to one breaker. Amp draw 16 amps. seperate circuits.
Hazard Classification: Multiple Circuits To One Breaker
Work Order#:
Barcode:
InspecTrend - Copyright © 2002-2003Logos Computer Solutions, Inc. All rights reserved. This document may not, in whole or in part, be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form without prior written consent.
This report was generated by InspecTrend and this inspection was performed by: Dyna Scan Technical Services
29 Park Road
Sonoco
Sonoco Protective Solutions - Putnam CT
Putnam, CT 06260
Report Date: 8/18/2018
Technician:Certification Level/No.:
Fitzpatrick, MikeCertified Thermographer
Is Chronic:
Operation Priority:
Current Prob No: Visual/2
2Page
Repair Priority:
Location/Equipment Information
File:File:
Date:Date:
FLIR13811.jpgFLIR13811.jpg
8/16/20188/16/2018
No
Critical to operation
3-Important
Time:Time:
01:38 PM01:38 PM
Location: Old Basement NEW SERVICE MAIN
Visual Problem Documentation
Hazard Type: NEC violation
Recommendations: Staff notified.What is the Cause: Blocked electrical equiipment
Consequences of Hazard: Code violation. Safety.
Asset ID: Switch board
Hazard Group: Blocked Electrical EquipmentHazard Issue: Equipment access obstructed
Observations: Equipment access obstructed. Water on floor.
Hazard Classification: Accessability
Work Order#:
Barcode:
InspecTrend - Copyright © 2002-2003Logos Computer Solutions, Inc. All rights reserved. This document may not, in whole or in part, be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form without prior written consent.
This report was generated by InspecTrend and this inspection was performed by: Dyna Scan Technical Services