22
TECHNOLOGY SYMBOL LIST SYMBOL: DESCRIPTION: NOTE: EQUIPMENT LIST ABBREV.: W C# C# 1. INFORMATION OUTLET (CEILING) SC-IO-C 1. INFORMATION OUTLET (WALL) SC-IO-W 1. INFORMATION OUTLET WALL PHONE (WALL) SC-IO-W C#-WAP 1. WIRELESS ACCESS POINT DEVICE (CEILING) SC-WAP-C C# 1., 2. ELECTRICAL FLOOR BOX WITH TECHNOLOGY N/A WP1 . AUDIO/VISUAL FACEPLATE (WALL) - TYPE 1 AV-WP1-W RTE EDH DC 3. DOOR CONTACT AC-DC 3. ELECTRIFIED DOOR HARDWARE AC-EDH 3. REQUEST TO EXIT AC-RTE CSS CR2 CR1 3. CREDENTIAL READER - TYPE 1 AC-CR1-W 3. CREDENTIAL READER - TYPE 2 AC-CR2-W 3. CONTROLLED SECURITY SCHEME SCHEDULE IDENTIFIER AC-CSS CAM CAM CLOSED CIRCUIT TELEVISION (CCTV) WALL CAMERA . CLOSED CIRCUIT TELEVISION (CCTV) CEILING CAMERA . N/A N/A AA1 AMS . AREA OF RESCUE - ASSISTANCE MASTER STATION AR-AMS-W . AREA OF RESCUE - ASSISTANCE CALL STATION - TYPE 1 AR-AA1-W 1 2 2-Port Faceplate IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION 1 2 4 3 4-Port Faceplate PAIR 3 PAIR 1 PAIR 2 PAIR 4 WO WG O BL WBL G WBRBR 1 3 2 4 5 6 7 8 ANSI/TIA/EIA T568B PIN/PAIR ASSIGNMENT TECHNOLOGY ABBREVIATION KEY ENTRANCE FACILITY EF-# MAIN CROSS-CONNECT MC-# TELECOMMUNICATIONS ROOM TR-# ABOVE FINISHED FLOOR AFF BELOW FINISHED CEILING BFC CONDUIT C SIMILAR SIM TYPICAL TYP MOUNTING HEIGHT ABOVE FINISHED FLOOR +# JUNCTION BOX J-BOX ABBR: DESCRIPTION: UNLESS NOTED OTHERWISE UNO TECHNOLOGY GENERAL NOTES: 1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS "EQUIPMENT LIST ABBREVIATION" 2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES. TECHNOLOGY MOUNTING SUBSCRIPT KEY: A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH H MOUNT ORIENTED HORIZONTALLY L MOUNT IN CASEWORK M MOUNT IN MODULAR FURNITURE S MOUNT IN SURFACE RACEWAY A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H. 1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION. 2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE. 3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE FRA, LLC. 4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT. 5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER SUBCONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER SUBCONTRACTOR. 6. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED SUBCONTRACTOR AT THE EXPENSE OF THIS SUBCONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS. 7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 07 84 13 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING. 8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS SUBCONTRACTOR. 9. ALL LADDER RACK AND CABLE TRAY SIZES ARE AS DEFINED ON THE DRAWINGS. REFER TO SPECIFICATION SECTIONS 27 05 36 AND 27 11 00 FOR APPROVED MANUFACTURERS AND INSTALLATION REQUIREMENTS. 10. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED. TECHNOLOGY INSTALLATION NOTES: GENERAL NOTES: 1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION AND ITEMS. 2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION. 3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL INFORMATION. 4. REFER TO RISERS ON SHEET(S): T-16 AND T-17. TECHNOLOGY SYMBOL NOTES: 1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 FOR ADDITIONAL INFORMATION. 2. INFORMATION OUTLET INSTALLED IN E.C. PROVIDED FLOOR BOX. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 FOR ADDITIONAL INFORMATION. REFER TO THE ELECTRICAL FLOOR PLANS AND ELECTRICAL EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION. 3. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T-17 FOR ADDITIONAL INFORMATION. CABLE TRAY, CHANNEL TRAY, BASKET TRAY LADDER RACK WIDTH X HEIGHT WIDTH X HEIGHT DIAMETERø C CONDUIT CONDUIT DOWN CONDUIT UP OR UP/DOWN CONDUIT SLEEVE CONTINUATION TEMPERATURE CONTROLS SUBCONTRACTOR T.C.C. SECURITY SUBCONTRACTOR S.C. FIRE PROTECTION SUBCONTRACTOR F.P.C. PLUMBING SUBCONTRACTOR P.C. MECHANICAL SUBCONTRACTOR M.C. ELECTRICAL SUBCONTRACTOR E.C. SUBCONTRACTOR ABBREVIATION KEY ABBR: DESCRIPTION: TECHNOLOGY SUBCONTRACTOR T.C. AUDIO VISUAL SUBCONTRACTOR A.V.C. 48" MAX. 20" MAX. 44" MAX. 20"-25" MAX. 48" MAX. 15" MIN. 48" MAX. 46" MAX. 10" MAX. 10"-24" MAX. ADA GUIDELINES - FRONT ACCESS ADA STANDARDS FOR ACCESSIBLE DESIGN INSTALL ABOVE COUNTER DEVICE AT 44" ABOVE FINISHED FLOOR. INSTALL ABOVE COUNTER DEVICE AT 40" ABOVE FINISHED FLOOR. INSTALL DEVICE AT 18" ABOVE FINISHED FLOOR. ADA GUIDELINES - SIDE ACCESS INSTALL DEVICE AT 44" ABOVE FINISHED FLOOR. INSTALL DEVICE AT 42" ABOVE FINISHED FLOOR. REFER TO SPECIFICATIONS FOR IDENTIFICATION REQUIREMENTS (TYP.) NUMBER INDICATES FACEPLATE POSITION (TYP.) TECHNOLOGY SHEET INDEX T-1 TECHNOLOGY COVERSHEET T-2 OVERALL TECHNOLOGY PLANS - TUNNEL AND LEVEL 01 T-3 TECHNOLOGY PLAN - TUNNEL - N1 T-4 TECHNOLOGY PLAN - TUNNEL - N2 T-5 TECHNOLOGY PLAN - TUNNEL - S1 T-6 TECHNOLOGY PLAN - TUNNEL - S2 T-7 TECHNOLOGY PLAN - TUNNEL - S3 T-8 TECHNOLOGY PLAN - TUNNEL - BTL-E T-9 TECHNOLOGY PLAN - TUNNEL - BTL-W T-10 TECHNOLOGY PLAN - LEVEL 01 - N1 T-11 TECHNOLOGY PLAN - LEVEL 01 - N2 T-12 TECHNOLOGY PLAN - LEVEL 01 - S1 T-13 TECHNOLOGY PLAN - LEVEL 01 - S2 T-14 TECHNOLOGY PLAN - LEVEL 01 - S3 T-15 TECHNOLOGY PLAN - LEVEL 01 - BTL-W T-16 TECHNOLOGY ENLARGED PLANS T-17 TECHNOLOGY DETAILS T-18 TECHNOLOGY SECTIONS T-19 TECHNOLOGY SECTIONS T-20 TECHNOLOGY SECTIONS T-21 TECHNOLOGY SECTIONS T-22 TECHNOLOGY SECTIONS SUGGESTED MATRIX OF RESPONSIBILITY ITEM: SHOWN ON: FURNISHED BY: INSTALLED BY: NOTES: TECHNOLOGY ROUGH-IN, REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR DEFINITION T-SERIES E.C. E.C. 3. 4. INFORMATION OUTLET FACEPLATES, JACKS, AND TERMINATIONS T-SERIES T.C. T.C. CONDUIT SLEEVES (WHEN SHOWN ON DRAWINGS) T-SERIES E.C. E.C. CONDUIT SLEEVES (NOT SHOWN BUT REQUIRED FOR PROPER INSTALLATION OF SYSTEM) N/A T.C. T.C. 2. 4. TELECOMMUNICATION SYSTEMS ROUGH-IN T-SERIES E.C. E.C. 1. TELECOMMUNICATION EQUIPMENT, CABLING, AND TERMINATIONS T-SERIES T.C. T.C. CABLE TRAY (INCLUDING WIRE BASKET TRAY) REFER TO SPECIFICATION SECTION 27 05 28 FOR DEFINITION T-SERIES E.C. E.C. LADDER RACK T-SERIES T.C. T.C. 5. GROUNDING LUGS ON TECHNOLOGY EQUIPMENT T-SERIES T.C. E.C. 6. BONDING SYSTEM FOR TECHNOLOGY SYSTEM, REFER TO SPECIFICATION SECTION 27 05 26 FOR DEFINITION T-SERIES E.C. E.C. 7. 8. CONNECTION OF TECHNOLOGY BONDING SYSTEM TO THE ELECTRICAL GROUND SYSTEM T-SERIES E.C. E.C. LINE VOLTAGE POWER (+120V OR GREATER) E-SERIES E.C. E.C. LINE VOLTAGE POWER (NOT SHOWN BUT REQUIRED FOR PROPER INSTALLATION OF SYSTEM) N/A T.C. E.C. 2. 4. LINE VOLTAGE POWER FOR DOOR HARDWARE POWER SUPPLIES ARCH SPEC E.C. E.C. LOW VOLTAGE CABLING FOR TECHNOLOGY SYSTEMS T-SERIES T.C. T.C. CABLE HANGERS AND SUPPORTS OR OTHER CABLE ROUTING METHODS (OTHER THAN CONDUIT AND CABLE TRAY) T-SERIES T.C. T.C. 5. FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C. SUGGESTED MATRIX OF RESPONSIBILITY NOTES 1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR ADDITIONAL INFORMATION. 2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE MANUFACTURERS. 3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE CONTRACT DOCUMENTS. 4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE SUBCONTRACTOR SHALL BE INCLUDED IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN. 5. UNLESS TRADE RULES DICTATE OTHERWISE. 6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR INSTALLATION IN THE FIELD. 7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETE BONDING SYSTEM REQUIRED BY THE SPECIFICATIONS. 8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWN IN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM. TELECOM ROOM REFERENCES TELECOM ROOM DETAIL / SHEET REFERENCE FLOOR PLAN REFERENCE ARCH ROOM NUMBER TR-3 1/T-16 1/T-10 01H01 REV. DATE DESIGNED CHECKED APPROVED SUBMITTED DRAWN DRAWING NO. DESCRIPTIONS REVISIONS REV. UNITED STATES DEPARTMENT OF ENERGY NAME DATE SCALE: Consulting Engineers 550 North Commons Drive Suite 116 Aurora, IL 60504 Tel : 630.820.1022 Fax: 630.820.0350 Architects 11 East Madison Street Suite 300 Chicago IL 60602 Tel : 312.456.0123 Fax: 312.456.0124 Structural Engineers 600 West Van Buren Suite 900 Chicago, IL 60607 Tel : 312.341.0055 Fax: 312.341.9966 MEP Engineers 1100 Warrenville Rd. Suite 400W Naperville, IL 60563 Tel : 630.527.2320 Fax: 630.527.2321 Landscape Architects 1431 Opus Pl. Suite 400 Downers Grove, IL 60515 Tel : 630.724.3200 Fax: 630.724.3201 Pre-Construction Contractor 55 East Monroe Street Suite 1430 Chicago, IL 60603 Tel : 312.327.2770 Fax: 312.327.2800 4-3-5 NOT TO SCALE T-1 PIP-II Linac Complex Fermilab Research Alliance AA JE JK JO TECHNOLOGY COVERSHEET 2021-03-12 2021-03-12 2021-03-12 2021-03-12 2021-03-12 THE EQUIPMENT LIST ABBREVIATIONS AND THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE SUBCONTRACTOR. EACH SUBCONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING SYSTEM. CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE SUBCONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH SUBCONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE. GENERAL TECHNOLOGY EQUIPMENT SCHEDULE EQUIPMENT LIST ABBREVIATION EQUIPMENT LIST DESCRIPTION EQUIPMENT LIST MANUFACTURER AND MODEL AC-CR1-W ACCESS CONTROL CREDENTIAL READER, WALL MOUNTED. PROXIMITY COMMUNICATIONS, MULTICOLOR LED, INTERNAL OR HOST CONTROL OF THE LED. REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS. CARDKEY L73-G-2W NO SUBSTITUTION AC-CR2-W ACCESS CONTROL CREDENTIAL READER, MULLION MOUNTED. AC-CSS ACCESS CONTROL SECURITY SYSTEM. SYMBOL INDICATES THAT DOOR HAS SECURITY FUNCTIONALITY, REFER TO SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T-17 FOR ADDITIONAL INFORMATION. * AC-DC DOOR POSITION INDICATOR SWITCH, SPDT OR DPDT CONTACTS. 1" DIAMETER OF CONTACTS WITH STANDARD GAP. REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS. SENTROL 1076 OR PRE-APPROVED EQUAL AC-EDH ELECTRIC LOCKING HARDWARE, FURNISHED AND INSTALLED BY DOOR HARDWARE PROVIDER, CONTROLLED BY THE SECURITY SYSTEM. REFER TO ARCHITECTURAL DOOR SCHEDULE FOR ADDITIONAL INFORMATION. REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS. * AC-PSP-1 ACCESS CONTROL POWER SUPPLY AND DISTRIBUTION PANEL, NEMA 1 LOCKABLE ENCLOSURE. 120V INPUT, WITH LOCAL DISCONNECT IN ENCLOSURE TO SEPARATE 12VDC @ 6A AND 24VDC @ 6A POWER SUPPLIES. LOCKS SHALL BE INDEPENDENTLY FUSED, 12VDC DEVICES AT DOORS SHALL BE INDEPENDENTLY FUSED PER DOOR, FIRE ALARM DISCONNECT. ALTRONIX AL600ULXB OR PRE-APPROVED EQUAL AC-RTE PIR REQUEST TO EXIT MOTION DETECTOR, DOOR MONITOR WITH SOUNDER ALERT, ADJUSTABLE LATCH TIME, SELECTABLE FAIL SAFE/SECURE, ADJUSTABLE SOUNDER VOLUME, ACTIVATION LED, 12VDC OPERATION, SEQUENTIAL LOGIC INPUT, TWO FORM C CONTACTS. CEILING MOUNTED OR WALL MOUNTED AT 84" AFF. REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS. BOSCH DSI-160 OR PRE-APPROVED EQUAL AC-SCP-1 ACCESS CONTROL PANEL. PANEL WILL CONTROL UP TO 12 DOORS. PROVIDE COMPLETE NETWORK CONTROLLER AND MODULES FOR A COMPLETE SYSTEM. 30' X 42' PANEL NEMA 1 ENCLOSURE. REFER TO 2/T-17 ACCESS CONTROL RISER DIAGRAM FOR ADDITIONAL INFORMATION. JOHNSON CONTROLS SPA1B600-E310 NO SUBSTITUTION AR-AA1-W EMERGENCY COMMUNICATION SYSTEM CALL STATION, SURFACE MOUNT, FACEPLATE SIZE 7-1/4” H X 4-3/4” W, PUSH FOR HELP BUTTON, WALL RECEIVED INDICATOR LIGHT, MICROPHONE, SPEAKER. INSTALL IN A 7.25” H X 4.82” W X 1.86” D SURFACE MOUNT BACK BOX AT +48” AFF WITH A 3/4” EMT CONDUIT STUBBED TO ABOVE NEAREST ACCESSIBLE CEILING. REFER TO 04/T-17 RESCUE ASSISTANCE RISER DIAGRAM FOR ADDITIONAL INFORMATION. RATH 2100-956SRM CORNELL OR APPROVED EQUAL AR-AMS-W EMERGENCY COMMUNICATION SYSTEM MASTER STATION, WALL MOUNT, STEEL ENCLOSURE, ACCOMMODATES UP TO 5 COMMUNICATION SYSTEM DEVICES. INSTALL CABLE AND CONNECTORS IN A 15.62” H X 12” W X 3” D BACK BOX AT +60” AFF WITH A 1” EMT CONDUIT STUBBED TO ABOVE NEAREST ACCESSIBLE CEILING. REFER TO 04/T-17 RESCUE ASSISTANCE RISER DIAGRAM FOR ADDITIONAL INFORMATION. RATH 2500-205FM CORNELL OR APPROVED EQUAL AR-PS-1 EMERGENCY COMMUNICATION SYSTEM POWER SUPPLY, WALL MOUNT. 11.25" W X 15.75" H X 4.5" D STEEL ENCLOSURE,120 VAC 5 AMP, 24 VDC 8 AMP TOTAL OUTPUT VIA EIGHT CLASS 2 PTC-PROTECTED OUTPUTS, INTEGRAL BATTERY BACKUP VIA TWO 12 VDC BATTERIES. REFER TO 04/T-17 RESCUE ASSISTANCE RISER DIAGRAM FOR ADDITIONAL INFORMATION. RATH 2500 PWR 24 CORNELL OR APPROVED EQUAL AV-WP1-F AV INFORMATION OUTLET, FLOOR BOX MOUNT FACEPLATE WITH FEMALE TO FEMALE CONNECTOR. ROUTE HDMI CABLE DIRECTLY IN E.C. PROVIDED PATHWAY FROM AV INPUT PANEL AT FLOOR BOX TO AV-WP1-W INFORMATION OUTLET IN THE SAME ROOM. COORDINATE AV INFORMATION OUTLET INSTALLATION WITH FURNITURE PROVIDER. INSTALL HDMI CABLE IN A 1-1/4" EMT CONDUIT STUBBED TO NON-CONTINUOUS CABLE SUPPORT ROUTE ABOVE NEAREST ACCESSIBLE CEILING. FACEPLATE PANDUIT NK2FIWY HDMI CONNECTOR PANDUIT NKHDMIIW EXTRON CABLE 26-650-XX OR PRE-APPROVED EQUAL AV-WP1-W AV INFORMATION OUTLET, WALL MOUNT FACEPLATE WITH FEMALE TO FEMALE CONNECTOR. ROUTE HDMI CABLE DIRECTLY IN E.C. PROVIDED PATHWAY FROM AV-WP1-F AV INPUT PANEL AT FLOOR BOX TO AV-WP1-W INFORMATION OUTLET IN THE SAME ROOM. INSTALL INFORMATION OUTLET IN A 4-11/16" SQUARE 2-1/8" DEEP BACKBOX WITH A SINGLE GANG PLASTER RING AND A 1-1/4" EMT CONDUIT STUBBED TO NON-CONTINUOUS CABLE SUPPORT ROUTE ABOVE NEAREST ACCESSIBLE CEILING. FACEPLATE PANDUIT NK2FIWY HDMI CONNECTOR PANDUIT NKHDMIIW EXTRON CABLE 26-650-XX OR PRE-APPROVED EQUAL SC-EXT ETHERNET OVER 2-WIRE EXTENDER WITH POE+, MADE UP OF LOCAL AND REMOTE DEVICE. LOCAL AND REMOTE MUST BE USED AS A PAIR, PORTS: ETHERNET: 10/100/1000BASE-T RJ-45 OR 100/1000BASE-X SFP COMBO, 2-WIRE TERMINAL BOLCK, FULL POE+ PORT AT 335-1500FT OVER A SINGLE PAIR, STATUS LED, DIMENSION: 3.25"WX5.38"DX1.25"H, POWER: 48VDC, 45W. TRANSITION NETWORKS LOCAL: EO2PSE4052-111 REMOTE: EO2PD4052-111 NO SUBSTITUTION SC-IO-C INFORMATION OUTLET, CEILING MOUNT, 4-PORT COVERPLATE AS INDICATED ON DRAWINGS, SEE INFORMATION OUTLET SCHEDULE ON T-1 FOR PIN CONFIGURATION. "#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 FOR ADDITIONAL INFORMATION. INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT TO ABOVE ACCESSIBLE CORRIDOR CEILING. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (PANDUIT NKBM SERIES OR APPROVED EQUAL). COVERPLATE: PANDUIT NK4FIWY JACK: PANDUIT (CAT6A) NK6X88M SERIES FCONNECTOR: CMFWH-C OR PRE-APPROVED EQUAL SC-IO-W INFORMATION OUTLET, WALL MOUNT, 2 OR 4-PORT COVERPLATE AS INDICATED ON DRAWINGS, SEE INFORMATION OUTLET SCHEDULE ON T-1 FOR PIN CONFIGURATION. "#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 FOR ADDITIONAL INFORMATION. INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT TO ABOVE ACCESSIBLE CORRIDOR CEILING. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (PANDUIT NKBM SERIES OR APPROVED EQUAL). COVERPLATE: PANDUIT NK2FIWY NK4FIWY JACK: PANDUIT (CAT6A) NK6X88M SERIES FCONNECTOR: CMFWH-C OR PRE-APPROVED EQUAL SC-LR-1 ALUMINUM LADDER TYPE CABLE TRAY. 4" NOMINAL OUTSIDE DEPTH. 3" NEMA LOADING DEPTH. 12" RUNG SPACING, 24" OR 36” WIDTH, 12' LENGTH. ALUMINUM ALLOY 6063-T6 COPPER FREE MARINE GRADE CONSTRUCTED AND LOAD TESTED PER NEMA 20A. PROVIDE COMPLETE WITH ALUMINUM MID-SPAN SPLICE PLATES, ALUMINUM WEDGE LOCK SPLICE PLATES, ALUMIMUM VERTICAL ADJUSTABLE SPLICE PLATES, ALUMINUM HOLD DOWN CLAMP/GUIDES AS REQUIRED. PROVIDE BONDING JUMPERS AT EACH SPLICE. PROVIDE COMPLETE WITH CABLE TRAY SUPPORT BRACKETS AS REQUIRED. ALUMINUM 4" SIDERAIL, 24" WIDTH, 90 DEGREE HORIZONTAL BEND, 12” OR 24" RADIUS. ALUMINUM 4" SIDERAIL, 24" WIDTH, 45 DEGREE HORIZONTAL BEND, 24" RADIUS ALUMINUM 4" SIDERAIL, 24" WIDTH, HORIZONTAL TEE, 12" RADIUS. ALUMINUM 4" SIDERAIL 36" WIDTH TO 24" REDUCER. GROUND WIRE CLAMP. HANGER ROD CLAMP. CONDUIT TO CABLE TRAY ADAPTER - USE FOR 500KCM GROUND WIRE. CABLE TRAY COOPER B-LINE 24-A-12-24-144 24-A-12-36-144 WALL SUPPORT BRACKETS B-494-24 CANTILEVER BRACKETS B297-24 BONDING JUMPERS 99-N1 HORIZONTAL BENDS 4A-24-90HB24 4A-24-90HB12 4A-24-45HB24 HORIZONTAL TEE 4A-24-HT12 4A-36-HT12 4A-36-24-HT12 HORIZONTAL EXPANSION TEE 4A-24-42-HT REDUCER 4A-36-SR24 GROUND CLAMP 9ZN-2351 HANGER CLAMP 9ZN-5324 CONDUIT ADAPTER 9ZN-1155-1” OR PRE-APPROVED EQUAL SC-LR-2 CABLE TRAY, WIRE MESH TYPE, 4" LOADING DEPTH, 12", 18", 24” AND 36” WIDTH, COMPLETE WITH ALL FITTINGS AND MOUNTING HARDWARE. CUTTING OF MESH CABLE TRAY SHALL BE DONE WITH OFFSET CUTTERS ONLY. 10' MAXIMUM SUPPORT SPAN. EITHER SPLICE WASHERS OR TERMINAL GROUND SUPPORT AND JUMPER WIRE SHALL BE USED TO ATTAIN GROUNDING CONTINUITY THROUGHOUT. Z-BRACKETS SHALL BE USED FOR WALL MOUNTED APPLICATIONS. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS AND SPECIFICATION SECTION 27 05 28 FOR ADDITIONAL INFORMATION. COOPER FLEXTRAY FT 4 x 12 x 10 FT 4 x 18 x 10 FT 4 x 24 x 10 FT 4 x 36 x 10 L BRACKETS 12 LBRKTEG 20 LBRKTEG 24 LBRKTEG SHELF BRACKETS FTB12CSGLV FTB18CSGLV FTB20CSGLV FTB24CSGLV OR PRE-APPROVED EQUAL SC-WAP-C INFORMATION OUTLET, 2-PORT SURFACE MOUNT BOX AS INDICATED ON DRAWINGS. "#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-1 FOR INFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION. INSTALL A 3/4" EMT CONDUIT 6" BEYOND BOX AND TERMINATE WITH A NYLON BUSHING. COVERPLATE: PANDUIT NK2BXIW-A JACK: PANDUIT (CAT6A) NK6X88M SERIES OR PRE-APPROVED EQUAL SC-WP-W INFORMATION OUTLET, WALL PHONE. PROVIDE (1) RJ-45 JACK FOR VOICE AT +48" AFF FOR WALL HUNG PHONE. PROVIDE WITH STAINLESS STEEL FACEPLATE, MATING LUGS, (HUBBELL SFB10A OR APPROVED EQUAL). INSTALL INFORMATION OUTLET IN A 4" SQUARE 2-1/8" DEEP BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT STUBBED TO NEAREST CABLE TRAY OR NON-CONTINUOUS CABLE SUPPORT ABOVE NEAREST ACCESSIBLE CEILING AND TERMINATE WITH NYLON BUSHING UNLESS OTHERWISE NOTED. REFER TO SUGGESTED MATRIX OF SCOPE OF RESPONSIBILITY ON DRAWING T-1 FOR ADDITIONAL INFORMATION. HUBBELL P630S1GJ8 2. PROVIDE CABLE FROM COMMAND CENTER CONSOLES FOR FRA, LLC. PROVIDED HDMI/DISPLAY PORT EXTENDERS. SUPPORT FOR POSSIBLE RELOCATION AFTER WIRELESS SURVEY. 1. LOCATION OF FUTURE FRA, LLC. PROVIDED WIRELESS ACCESS POINT. PROVIDE A 20' SLACK COIL AT THE NEAREST CABLE SCHEDULE NOTES: VOICE CAT 6A RJ-45 2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. BLANK BLANK FILLER MODULE 1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6A RJ-45 NOTES: LEGEND SINGLE GANG WALLPLATES INFORMATION OUTLET SCHEDULE CONFIGURATION FACEPLATE PORTS FACEPLATE PORT IDENTIFICATION NOTES POSITION 1 JACK TYPE POSITION 2 JACK TYPE POSITION 3 JACK TYPE POSITION 4 JACK TYPE POSITION 5 JACK TYPE POSITION 6 JACK TYPE C1 2 DATA BLANK C2 2 DATA DATA C2-1 4 DATA DATA BLANK BLANK 2. C2-WAP 2 DATA DATA 1. C4 4 DATA DATA DATA DATA W 1 VOICE

INFORMATION OUTLET SCHEDULE TECHNOLOGY SYMBOL LIST

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

TECHNOLOGY SYMBOL LIST

SYMBOL: DESCRIPTION: NOTE:EQUIPMENT

LIST ABBREV.:

W

C#

C#1.INFORMATION OUTLET (CEILING)SC-IO-C

1.INFORMATION OUTLET (WALL)SC-IO-W

1.INFORMATION OUTLET WALL PHONE (WALL)SC-IO-W

C#-WAP1.WIRELESS ACCESS POINT DEVICE (CEILING)SC-WAP-C

C#1., 2.ELECTRICAL FLOOR BOX WITH TECHNOLOGYN/A

WP1 .AUDIO/VISUAL FACEPLATE (WALL) - TYPE 1AV-WP1-W

RTE

EDH

DC 3.DOOR CONTACTAC-DC

3.ELECTRIFIED DOOR HARDWAREAC-EDH

3.REQUEST TO EXITAC-RTE

CSS

CR2

CR1 3.CREDENTIAL READER - TYPE 1AC-CR1-W

3.CREDENTIAL READER - TYPE 2AC-CR2-W

3.CONTROLLED SECURITY SCHEME SCHEDULEIDENTIFIER

AC-CSS

CAM

CAM CLOSED CIRCUIT TELEVISION (CCTV) WALL CAMERA

.CLOSED CIRCUIT TELEVISION (CCTV) CEILING CAMERA

.N/A

N/A

AA1

AMS .AREA OF RESCUE - ASSISTANCE MASTER STATIONAR-AMS-W

.AREA OF RESCUE - ASSISTANCE CALL STATION -TYPE 1

AR-AA1-W

1

2

2-Port Faceplate

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

1 2

43

4-Port Faceplate

PAIR 3

PAIR 1PAIR 2 PAIR 4

WO WGO BL WBL G WBRBR

1 32 4 5 6 7 8

ANSI/TIA/EIA T568BPIN/PAIR ASSIGNMENT

TECHNOLOGY ABBREVIATION KEY

ENTRANCE FACILITYEF-#

MAIN CROSS-CONNECTMC-#

TELECOMMUNICATIONS ROOMTR-#

ABOVE FINISHED FLOORAFF

BELOW FINISHED CEILINGBFC

CONDUITC

SIMILARSIM

TYPICALTYP

MOUNTING HEIGHT ABOVE FINISHED FLOOR+#

JUNCTION BOXJ-BOX

ABBR: DESCRIPTION:

UNLESS NOTED OTHERWISEUNO

TECHNOLOGY GENERAL NOTES:

1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS "EQUIPMENT LIST ABBREVIATION"

2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.

TECHNOLOGY MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHH MOUNT ORIENTED HORIZONTALLYL MOUNT IN CASEWORKM MOUNT IN MODULAR FURNITURES MOUNT IN SURFACE RACEWAY

A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.

2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.

3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE FRA, LLC.

4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.

5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER SUBCONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER SUBCONTRACTOR.

6. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED SUBCONTRACTOR AT THE EXPENSE OF THIS SUBCONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.

7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 07 84 13 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS SUBCONTRACTOR.

9. ALL LADDER RACK AND CABLE TRAY SIZES ARE AS DEFINED ON THE DRAWINGS. REFER TO SPECIFICATION SECTIONS 27 05 36 AND 27 11 00 FOR APPROVED MANUFACTURERS AND INSTALLATION REQUIREMENTS.

10. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

TECHNOLOGY INSTALLATION NOTES:

GENERAL NOTES:

1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION AND ITEMS.

2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION.

3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL INFORMATION.

4. REFER TO RISERS ON SHEET(S): T-16 AND T-17.

TECHNOLOGY SYMBOL NOTES:

1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 FOR ADDITIONAL INFORMATION.

2. INFORMATION OUTLET INSTALLED IN E.C. PROVIDED FLOOR BOX. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 FOR ADDITIONAL INFORMATION. REFER TO THE ELECTRICAL FLOOR PLANS AND ELECTRICAL EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.

3. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T-17 FOR ADDITIONAL INFORMATION.

CABLE TRAY, CHANNEL TRAY, BASKET TRAY

LADDER RACK

WIDTH X HEIGHT

WIDTH X HEIGHT

DIAMETERø C CONDUIT

CONDUIT DOWN

CONDUIT UP OR UP/DOWN

CONDUIT SLEEVE

CONTINUATION

TEMPERATURE CONTROLS SUBCONTRACTORT.C.C.

SECURITY SUBCONTRACTORS.C.

FIRE PROTECTION SUBCONTRACTORF.P.C.

PLUMBING SUBCONTRACTORP.C.

MECHANICAL SUBCONTRACTORM.C.

ELECTRICAL SUBCONTRACTORE.C.

SUBCONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY SUBCONTRACTORT.C.

AUDIO VISUAL SUBCONTRACTORA.V.C.

48

" M

AX

.20" MAX.

44

" M

AX

.

20"-25" MAX.

48

" M

AX

.

15

" M

IN. 48

" M

AX

.

46

" M

AX

.

10" MAX. 10"-24" MAX.

ADA GUIDELINES - FRONT ACCESS

ADA STANDARDS FOR ACCESSIBLE DESIGN

INSTALL ABOVE COUNTER DEVICE AT 44" ABOVE FINISHED FLOOR.

INSTALL ABOVE COUNTER DEVICE AT 40" ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 18" ABOVE FINISHED FLOOR.

ADA GUIDELINES - SIDE ACCESS

INSTALL DEVICE AT 44" ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 42" ABOVE FINISHED FLOOR.

REFER TO SPECIFICATIONS FOR IDENTIFICATION REQUIREMENTS (TYP.)

NUMBER INDICATES FACEPLATE POSITION (TYP.)

TECHNOLOGY SHEET INDEXT-1 TECHNOLOGY COVERSHEET

T-2 OVERALL TECHNOLOGY PLANS - TUNNEL AND LEVEL 01

T-3 TECHNOLOGY PLAN - TUNNEL - N1

T-4 TECHNOLOGY PLAN - TUNNEL - N2

T-5 TECHNOLOGY PLAN - TUNNEL - S1

T-6 TECHNOLOGY PLAN - TUNNEL - S2

T-7 TECHNOLOGY PLAN - TUNNEL - S3

T-8 TECHNOLOGY PLAN - TUNNEL - BTL-E

T-9 TECHNOLOGY PLAN - TUNNEL - BTL-W

T-10 TECHNOLOGY PLAN - LEVEL 01 - N1

T-11 TECHNOLOGY PLAN - LEVEL 01 - N2

T-12 TECHNOLOGY PLAN - LEVEL 01 - S1

T-13 TECHNOLOGY PLAN - LEVEL 01 - S2

T-14 TECHNOLOGY PLAN - LEVEL 01 - S3

T-15 TECHNOLOGY PLAN - LEVEL 01 - BTL-W

T-16 TECHNOLOGY ENLARGED PLANS

T-17 TECHNOLOGY DETAILS

T-18 TECHNOLOGY SECTIONS

T-19 TECHNOLOGY SECTIONS

T-20 TECHNOLOGY SECTIONS

T-21 TECHNOLOGY SECTIONS

T-22 TECHNOLOGY SECTIONS

SUGGESTED MATRIX OF RESPONSIBILITY

ITEM: SHOWN ON:

FURNISHED

BY:

INSTALLED

BY: NOTES:

TECHNOLOGY ROUGH-IN, REFER TOGENERAL TECHNOLOGY EQUIPMENTSCHEDULE AND SPECIFICATIONS FORDEFINITION

T-SERIES E.C. E.C. 3. 4.

INFORMATION OUTLET FACEPLATES,JACKS, AND TERMINATIONS

T-SERIES T.C. T.C.

CONDUIT SLEEVES (WHEN SHOWN ONDRAWINGS)

T-SERIES E.C. E.C.

CONDUIT SLEEVES (NOT SHOWN BUTREQUIRED FOR PROPER INSTALLATIONOF SYSTEM)

N/A T.C. T.C. 2. 4.

TELECOMMUNICATION SYSTEMSROUGH-IN

T-SERIES E.C. E.C. 1.

TELECOMMUNICATION EQUIPMENT,CABLING, AND TERMINATIONS

T-SERIES T.C. T.C.

CABLE TRAY (INCLUDING WIRE BASKETTRAY) REFER TO SPECIFICATIONSECTION 27 05 28 FOR DEFINITION

T-SERIES E.C. E.C.

LADDER RACK T-SERIES T.C. T.C. 5.

GROUNDING LUGS ON TECHNOLOGYEQUIPMENT

T-SERIES T.C. E.C. 6.

BONDING SYSTEM FOR TECHNOLOGYSYSTEM, REFER TO SPECIFICATIONSECTION 27 05 26 FOR DEFINITION

T-SERIES E.C. E.C. 7. 8.

CONNECTION OF TECHNOLOGYBONDING SYSTEM TO THE ELECTRICALGROUND SYSTEM

T-SERIES E.C. E.C.

LINE VOLTAGE POWER (+120V ORGREATER)

E-SERIES E.C. E.C.

LINE VOLTAGE POWER (NOT SHOWNBUT REQUIRED FOR PROPERINSTALLATION OF SYSTEM)

N/A T.C. E.C. 2. 4.

LINE VOLTAGE POWER FOR DOORHARDWARE POWER SUPPLIES

ARCH SPEC E.C. E.C.

LOW VOLTAGE CABLING FORTECHNOLOGY SYSTEMS

T-SERIES T.C. T.C.

CABLE HANGERS AND SUPPORTS OROTHER CABLE ROUTING METHODS(OTHER THAN CONDUIT AND CABLETRAY)

T-SERIES T.C. T.C. 5.

FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.

SUGGESTED MATRIX OF RESPONSIBILITY NOTES

1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATIONOUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FORADDITIONAL INFORMATION.

2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALLREQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLEMANUFACTURERS.

3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMSINSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THECONTRACT DOCUMENTS.

4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OFTHE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEMCONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE SUBCONTRACTOR SHALL BEINCLUDED IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSEDELECTRICIAN.

5. UNLESS TRADE RULES DICTATE OTHERWISE.

6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FORINSTALLATION IN THE FIELD.

7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETEBONDING SYSTEM REQUIRED BY THE SPECIFICATIONS.

8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWNIN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOWDIAGRAM.

TELECOM ROOM REFERENCES

TELECOM ROOM

DETAIL / SHEET

REFERENCE

FLOOR PLAN

REFERENCE ARCH ROOM NUMBER

TR-3 1/T-16 1/T-10 01H01

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

NOT TO SCALE

T-1

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY COVERSHEET

2021-03-12

2021-03-12

2021-03-12

2021-03-12

2021-0

3-1

2

THE EQUIPMENT LIST ABBREVIATIONS AND THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE SUBCONTRACTOR. EACH SUBCONTRACTOR SHALL BERESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING SYSTEM.

CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE SUBCONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BYMANUFACTURER AND CATALOG NUMBER ONLY. EACH SUBCONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. THEFIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.

GENERAL TECHNOLOGY EQUIPMENT SCHEDULE

EQUIPMENT LIST

ABBREVIATION EQUIPMENT LIST DESCRIPTION

EQUIPMENT LIST MANUFACTURER

AND MODEL

AC-CR1-W ACCESS CONTROL CREDENTIAL READER, WALL MOUNTED. PROXIMITY COMMUNICATIONS, MULTICOLOR LED,INTERNAL OR HOST CONTROL OF THE LED.

REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS.

CARDKEY L73-G-2W

NO SUBSTITUTION

AC-CR2-W ACCESS CONTROL CREDENTIAL READER, MULLION MOUNTED.

AC-CSS ACCESS CONTROL SECURITY SYSTEM. SYMBOL INDICATES THAT DOOR HAS SECURITY FUNCTIONALITY, REFER TO SPECIFICATIONSECTION 28 13 00 FOR COMPLETE INFORMATION.

REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T-17 FOR ADDITIONAL INFORMATION.

*

AC-DC DOOR POSITION INDICATOR SWITCH, SPDT OR DPDT CONTACTS. 1" DIAMETER OF CONTACTS WITH STANDARD GAP.

REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS.

SENTROL 1076

OR PRE-APPROVED EQUAL

AC-EDH ELECTRIC LOCKING HARDWARE, FURNISHED AND INSTALLED BY DOOR HARDWARE PROVIDER, CONTROLLED BY THE SECURITY SYSTEM.REFER TO ARCHITECTURAL DOOR SCHEDULE FOR ADDITIONAL INFORMATION.

REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS.

*

AC-PSP-1 ACCESS CONTROL POWER SUPPLY AND DISTRIBUTION PANEL, NEMA 1 LOCKABLE ENCLOSURE. 120V INPUT, WITH LOCAL DISCONNECTIN ENCLOSURE TO SEPARATE 12VDC @ 6A AND 24VDC @ 6A POWER SUPPLIES. LOCKS SHALL BE INDEPENDENTLY FUSED, 12VDCDEVICES AT DOORS SHALL BE INDEPENDENTLY FUSED PER DOOR, FIRE ALARM DISCONNECT.

ALTRONIX AL600ULXB

OR PRE-APPROVED EQUAL

AC-RTE PIR REQUEST TO EXIT MOTION DETECTOR, DOOR MONITOR WITH SOUNDER ALERT, ADJUSTABLE LATCH TIME, SELECTABLE FAILSAFE/SECURE, ADJUSTABLE SOUNDER VOLUME, ACTIVATION LED, 12VDC OPERATION, SEQUENTIAL LOGIC INPUT, TWO FORM CCONTACTS. CEILING MOUNTED OR WALL MOUNTED AT 84" AFF.

REFER TO 01/T-17 FOR CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL. REFER TO 02/T-17 FOR CABLING REQUIREMENTS.

BOSCH DSI-160

OR PRE-APPROVED EQUAL

AC-SCP-1 ACCESS CONTROL PANEL. PANEL WILL CONTROL UP TO 12 DOORS. PROVIDE COMPLETE NETWORK CONTROLLER AND MODULES FOR ACOMPLETE SYSTEM. 30' X 42' PANEL NEMA 1 ENCLOSURE.

REFER TO 2/T-17 ACCESS CONTROL RISER DIAGRAM FOR ADDITIONAL INFORMATION.

JOHNSON CONTROLS SPA1B600-E310

NO SUBSTITUTION

AR-AA1-W EMERGENCY COMMUNICATION SYSTEM CALL STATION, SURFACE MOUNT, FACEPLATE SIZE 7-1/4” H X 4-3/4” W, PUSH FOR HELP BUTTON,WALL RECEIVED INDICATOR LIGHT, MICROPHONE, SPEAKER. INSTALL IN A7.25” H X 4.82” W X 1.86” D SURFACE MOUNT BACK BOX AT +48” AFF WITH A 3/4” EMT CONDUIT STUBBED TO ABOVE NEAREST ACCESSIBLECEILING.

REFER TO 04/T-17 RESCUE ASSISTANCE RISER DIAGRAM FOR ADDITIONAL INFORMATION.

RATH 2100-956SRM

CORNELLOR APPROVED EQUAL

AR-AMS-W EMERGENCY COMMUNICATION SYSTEM MASTER STATION, WALL MOUNT, STEEL ENCLOSURE, ACCOMMODATES UPTO 5 COMMUNICATION SYSTEM DEVICES. INSTALL CABLE AND CONNECTORS IN A 15.62” H X 12” W X 3” D BACK BOX AT +60” AFF WITH A 1”EMT CONDUIT STUBBED TO ABOVE NEAREST ACCESSIBLE CEILING.

REFER TO 04/T-17 RESCUE ASSISTANCE RISER DIAGRAM FOR ADDITIONAL INFORMATION.

RATH 2500-205FM

CORNELLOR APPROVED EQUAL

AR-PS-1 EMERGENCY COMMUNICATION SYSTEM POWER SUPPLY, WALL MOUNT. 11.25" W X 15.75" H X 4.5" D STEEL ENCLOSURE,120 VAC 5 AMP, 24VDC 8 AMP TOTAL OUTPUT VIA EIGHT CLASS 2 PTC-PROTECTED OUTPUTS, INTEGRAL BATTERY BACKUP VIA TWO 12 VDC BATTERIES.

REFER TO 04/T-17 RESCUE ASSISTANCE RISER DIAGRAM FOR ADDITIONAL INFORMATION.

RATH 2500 PWR 24

CORNELLOR APPROVED EQUAL

AV-WP1-F AV INFORMATION OUTLET, FLOOR BOX MOUNT FACEPLATE WITH FEMALE TO FEMALE CONNECTOR.

ROUTE HDMI CABLE DIRECTLY IN E.C. PROVIDED PATHWAY FROM AV INPUT PANEL AT FLOOR BOX TO AV-WP1-W INFORMATION OUTLETIN THE SAME ROOM.

COORDINATE AV INFORMATION OUTLET INSTALLATION WITH FURNITURE PROVIDER. INSTALL HDMI CABLE IN A 1-1/4" EMT CONDUITSTUBBED TO NON-CONTINUOUS CABLE SUPPORT ROUTE ABOVE NEAREST ACCESSIBLE CEILING.

FACEPLATEPANDUIT NK2FIWY

HDMI CONNECTORPANDUIT NKHDMIIW

EXTRON CABLE 26-650-XX

OR PRE-APPROVED EQUAL

AV-WP1-W AV INFORMATION OUTLET, WALL MOUNT FACEPLATE WITH FEMALE TO FEMALE CONNECTOR.

ROUTE HDMI CABLE DIRECTLY IN E.C. PROVIDED PATHWAY FROM AV-WP1-F AV INPUT PANEL AT FLOOR BOX TOAV-WP1-W INFORMATION OUTLET IN THE SAME ROOM.

INSTALL INFORMATION OUTLET IN A 4-11/16" SQUARE 2-1/8" DEEP BACKBOX WITH A SINGLE GANG PLASTER RINGAND A 1-1/4" EMT CONDUIT STUBBED TO NON-CONTINUOUS CABLE SUPPORT ROUTE ABOVE NEAREST ACCESSIBLE CEILING.

FACEPLATEPANDUIT NK2FIWY

HDMI CONNECTORPANDUIT NKHDMIIW

EXTRON CABLE 26-650-XX

OR PRE-APPROVED EQUAL

SC-EXT ETHERNET OVER 2-WIRE EXTENDER WITH POE+, MADE UP OF LOCAL AND REMOTE DEVICE. LOCAL AND REMOTE MUST BE USED AS APAIR, PORTS: ETHERNET: 10/100/1000BASE-T RJ-45 OR 100/1000BASE-X SFP COMBO, 2-WIRE TERMINAL BOLCK, FULL POE+ PORT AT335-1500FT OVER A SINGLE PAIR, STATUS LED, DIMENSION: 3.25"WX5.38"DX1.25"H, POWER: 48VDC, 45W.

TRANSITION NETWORKS LOCAL: EO2PSE4052-111

REMOTE: EO2PD4052-111

NO SUBSTITUTION

SC-IO-C INFORMATION OUTLET, CEILING MOUNT, 4-PORT COVERPLATE AS INDICATED ON DRAWINGS, SEE INFORMATION OUTLET SCHEDULE ONT-1 FOR PIN CONFIGURATION.

"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION OUTLETSCHEDULE ON T-1 FOR ADDITIONAL INFORMATION.

INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT TO ABOVEACCESSIBLE CORRIDOR CEILING. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (PANDUIT NKBM SERIES OR APPROVEDEQUAL).

COVERPLATE:PANDUIT NK4FIWY

JACK:PANDUIT(CAT6A) NK6X88M SERIES

FCONNECTOR: CMFWH-C

OR PRE-APPROVED EQUAL

SC-IO-W INFORMATION OUTLET, WALL MOUNT, 2 OR 4-PORT COVERPLATE AS INDICATED ON DRAWINGS, SEE INFORMATION OUTLET SCHEDULEON T-1 FOR PIN CONFIGURATION.

"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION OUTLETSCHEDULE ON T-1 FOR ADDITIONAL INFORMATION.

INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT TO ABOVEACCESSIBLE CORRIDOR CEILING. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (PANDUIT NKBM SERIES OR APPROVEDEQUAL).

COVERPLATE:PANDUIT NK2FIWY NK4FIWY

JACK:PANDUIT(CAT6A) NK6X88M SERIES

FCONNECTOR: CMFWH-C

OR PRE-APPROVED EQUAL

SC-LR-1 ALUMINUM LADDER TYPE CABLE TRAY. 4" NOMINAL OUTSIDE DEPTH. 3" NEMA LOADING DEPTH. 12" RUNG SPACING, 24" OR 36” WIDTH, 12'LENGTH. ALUMINUM ALLOY 6063-T6 COPPER FREE MARINE GRADE CONSTRUCTED AND LOAD TESTED PER NEMA 20A.

PROVIDE COMPLETE WITH ALUMINUM MID-SPAN SPLICE PLATES, ALUMINUM WEDGE LOCK SPLICE PLATES, ALUMIMUM VERTICALADJUSTABLE SPLICE PLATES, ALUMINUM HOLD DOWN CLAMP/GUIDES AS REQUIRED. PROVIDE BONDING JUMPERS AT EACH SPLICE.

PROVIDE COMPLETE WITH CABLE TRAY SUPPORT BRACKETS AS REQUIRED.

ALUMINUM 4" SIDERAIL, 24" WIDTH, 90 DEGREE HORIZONTAL BEND, 12” OR 24" RADIUS.

ALUMINUM 4" SIDERAIL, 24" WIDTH, 45 DEGREE HORIZONTAL BEND, 24" RADIUS

ALUMINUM 4" SIDERAIL, 24" WIDTH, HORIZONTAL TEE, 12" RADIUS.

ALUMINUM 4" SIDERAIL 36" WIDTH TO 24" REDUCER.

GROUND WIRE CLAMP.

HANGER ROD CLAMP.

CONDUIT TO CABLE TRAY ADAPTER - USE FOR 500KCM GROUND WIRE.

CABLE TRAYCOOPER B-LINE 24-A-12-24-144 24-A-12-36-144

WALL SUPPORT BRACKETS B-494-24

CANTILEVER BRACKETSB297-24

BONDING JUMPERS 99-N1

HORIZONTAL BENDS 4A-24-90HB24 4A-24-90HB12 4A-24-45HB24

HORIZONTAL TEE 4A-24-HT12 4A-36-HT12 4A-36-24-HT12

HORIZONTAL EXPANSION TEE 4A-24-42-HT

REDUCER 4A-36-SR24

GROUND CLAMP 9ZN-2351

HANGER CLAMP 9ZN-5324

CONDUIT ADAPTER 9ZN-1155-1”

OR PRE-APPROVED EQUAL

SC-LR-2 CABLE TRAY, WIRE MESH TYPE, 4" LOADING DEPTH, 12", 18", 24” AND 36” WIDTH, COMPLETE WITH ALL FITTINGS AND MOUNTINGHARDWARE. CUTTING OF MESH CABLE TRAY SHALL BE DONE WITH OFFSET CUTTERS ONLY. 10' MAXIMUM SUPPORT SPAN. EITHERSPLICE WASHERS OR TERMINAL GROUND SUPPORT AND JUMPER WIRE SHALL BE USED TO ATTAIN GROUNDING CONTINUITYTHROUGHOUT. Z-BRACKETS SHALL BE USED FOR WALL MOUNTED APPLICATIONS. REFER TO MANUFACTURERS INSTALLATIONINSTRUCTIONS AND SPECIFICATION SECTION 27 05 28 FOR ADDITIONAL INFORMATION.

COOPER FLEXTRAY FT 4 x 12 x 10 FT 4 x 18 x 10 FT 4 x 24 x 10 FT 4 x 36 x 10

L BRACKETS 12 LBRKTEG 20 LBRKTEG 24 LBRKTEG

SHELF BRACKETS FTB12CSGLV FTB18CSGLV FTB20CSGLV FTB24CSGLV

OR PRE-APPROVED EQUAL

SC-WAP-C INFORMATION OUTLET, 2-PORT SURFACE MOUNT BOX AS INDICATED ON DRAWINGS.

"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-1 FOR INFORMATIONOUTLET SCHEDULE FOR PIN CONFIGURATION.

INSTALL A 3/4" EMT CONDUIT 6" BEYOND BOX AND TERMINATE WITH A NYLON BUSHING.

COVERPLATE:PANDUIT NK2BXIW-A

JACK:PANDUIT(CAT6A) NK6X88M SERIES

OR PRE-APPROVED EQUAL

SC-WP-W INFORMATION OUTLET, WALL PHONE. PROVIDE (1) RJ-45 JACK FOR VOICE AT +48" AFF FOR WALL HUNG PHONE. PROVIDE WITHSTAINLESS STEEL FACEPLATE, MATING LUGS, (HUBBELL SFB10A OR APPROVED EQUAL).

INSTALL INFORMATION OUTLET IN A 4" SQUARE 2-1/8" DEEP BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A1" EMT CONDUIT STUBBED TO NEAREST CABLE TRAY OR NON-CONTINUOUS CABLE SUPPORT ABOVE NEAREST ACCESSIBLE CEILING ANDTERMINATE WITH NYLON BUSHING UNLESS OTHERWISE NOTED. REFER TO SUGGESTED MATRIX OF SCOPE OF RESPONSIBILITY ONDRAWING T-1 FOR ADDITIONAL INFORMATION.

HUBBELL P630S1GJ8

2. PROVIDE CABLE FROM COMMAND CENTER CONSOLES FOR FRA, LLC. PROVIDED HDMI/DISPLAY PORT EXTENDERS.

SUPPORT FOR POSSIBLE RELOCATION AFTER WIRELESS SURVEY.

1. LOCATION OF FUTURE FRA, LLC. PROVIDED WIRELESS ACCESS POINT. PROVIDE A 20' SLACK COIL AT THE NEAREST CABLE

SCHEDULE NOTES:VOICE CAT 6A RJ-45

2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. BLANK BLANK FILLER MODULE

1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6A RJ-45

NOTES: LEGEND

SINGLE GANG WALLPLATES

INFORMATION OUTLET SCHEDULE

CONFIGURATION FA

CE

PL

AT

E P

OR

TS

FACEPLATE PORT IDENTIFICATION

NOTESPO

SIT

ION

1 J

AC

K T

YP

E

PO

SIT

ION

2 J

AC

K T

YP

E

PO

SIT

ION

3 J

AC

K T

YP

E

PO

SIT

ION

4 J

AC

K T

YP

E

PO

SIT

ION

5 J

AC

K T

YP

E

PO

SIT

ION

6 J

AC

K T

YP

E

C1 2 DATA BLANK

C2 2 DATA DATA

C2-1 4 DATA DATA BLANK BLANK 2.

C2-WAP 2 DATA DATA 1.

C4 4 DATA DATA DATA DATA

W 1 VOICE

CSSCSSCSS

L1

L1

L2

L2

L3

L3

L4

L4

L5

L5

L6

L6

L7

L7

L8

L8

L9

L9

L10

L10

L11

L11

L12

L12

L13

L13

L14

L14

L15

L15

L16

L16

L17

L17

L18

L18

L19

L19

L20

L20

L21

L21

L22

L22

L23

L23

L24

L24

L25

L25

L26

L26

L27

L27

L28

L28

L29

L29

L30

L30

L31

L31

L32

L32

L33

L33

L34

L34

L35

L35

L36

L36

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

LBLB

LALA

L37

L37

L38

L38

L39

L39

L40

L40

L41

L41L42L43L44L45

L45

L46

L46

L47

L47

L48

L48

L49

L49

L50

L50

L52

L52

L53

L53

ADDITIVE ALTERNATE BUILDING EXTENSION

ADDITIVE ALTERNATE BUILDING EXTENSION

FC

FC

FA

FAFB

FB

F1

F1

F2

F2

1

CAM

/M

AT

CH

LIN

E:

SE

E 0

1T

-13

/M

AT

CH

LIN

E:

SE

E 0

1T

-13

/M

AT

CH

LIN

E:

SE

E 0

1T

-12

/M

AT

CH

LIN

E:

SE

E 0

1T

-12

/M

AT

CH

LIN

E:

SE

E 0

1T

-11

/M

AT

CH

LIN

E:

SE

E 0

1T

-11

/M

AT

CH

LIN

E:

SE

E 0

1T

-10

NO TECHNOLOGY ENLARGEMENT

NO TECHNOLOGY ENLARGEMENT

/MATCHLINE: SEE 01 T-15

/M

AT

CH

LIN

E:

SE

E 0

1T

-14

/MATCHLINE: SEE 01 T-14

CAM1

1

CAM

CAM1

CAM1

L1

L1

L2

L2

L3

L3

L4

L4

L5

L5

L6

L6

L7

L7

L8

L8

L9

L9

L10

L10

L11

L11

L12

L12

L13

L13

L14

L14

L15

L15

L16

L16

L17

L17

L18

L18

L19

L19

L20

L20

L21

L21

L22

L22

L23

L23

L24

L24

L25

L25

L26

L26

L27

L27

L28

L28

L29

L29

L30

L30

L31

L31

L32

L32

L33

L33

L34

L34

L35

L35

L36

L36

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

LBLB

LALA

L37

L37

L38

L38

L39

L39

L40

L40

L41

L41L42

L42

L43

L43

L44

L44

L45

L45

L46

L46

L47

L47

L48

L48

L49

L49

L50

L50

L52

L52

L53

L53

ADDITIVE ALTERNATE BUILDING EXTENSION

/M

AT

CH

LIN

E:

SE

E 0

1T

-7

/M

AT

CH

LIN

E:

SE

E 0

1T

-6

/MATCHLINE: SEE 01 T-8

/MATCHLINE: SEE 01 T-7

/MATCHLINE: SEE 01 T-9

/MATCHLINE: SEE 01 T-8

/M

AT

CH

LIN

E:

SE

E 0

1T

-6

/M

AT

CH

LIN

E:

SE

E 0

1T

-5

/M

AT

CH

LIN

E:

SE

E 0

1T

-5

/M

AT

CH

LIN

E:

SE

E 0

1T

-4

/M

AT

CH

LIN

E:

SE

E 0

1T

-4

/M

AT

CH

LIN

E:

SE

E 0

1T

-3

SHEET NOTES

KEY PLAN

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1" = 40'-0"

T-2

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOOVERALL TECHNOLOGY PLANS - TUNNEL AND

LEVEL 01

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1" = 40'-0"

OVERALL TECHNOLOGY PLAN - LEVEL 01 02

SCALE: 1" = 40'-0"

OVERALL TECHNOLOGY PLAN - TUNNEL 01

1. PROVIDE (1) 1” CONDUIT FROM CABLE TRAY TO ROOF PENETRATION WITH (1) CAT 6A CABLE FOR ROOF MOUNTED VIDEO SURVEILLANCE CAMERA. COORDINATE FINAL LOCATION OF ROOF PENETRATION AND CAMERA MOUNT WITH FRA, LLC. PRIOR TO INSTALLATION. VIDEO SURVEILLANCE CAMERA AND PARAPET MOUNT ARE FRA, LLC. PROVIDED AND INSTALLED BY THIS SUBCONTRACTOR. REFER TO ENLARGED FLOOR PLANS FOR ADDITIONAL INFORMATION. CAT 6A CABLE SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET. REFER TO 03/T-17 FOR ADDITIONAL INFORMATION.

UP

UP

UP

GB

GB

GB

W

W

GB

AA

1

GB

C2-WAP

C2-WAP

L2

L2

L3

L3

L4

L4

L5

L5

L6

L6

L7

L7

L8

L8

L9

L9

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

STAIR E1

01M09

VEST

00A02

STAIR VEST

00B01

SUPPORT -SOUTH

00E01

SUPPORT -NORTH

00C01

WARM FRONTEND

00B03

CORRIDOR

00D03

CORRIDOR

00F00

CORRIDOR

00D01

RF TRENCHACCESS STAIR

N

00F04

PPE

00D00

UPSTREAMLASER ROOM

00B02

(2) LEVELS (LOWER AND UPPER) OF SC-LR-1. REFER TO 01/T-19 FOR ADDITIONAL INFORMATION.

(44) 6" L-BEND CONDUITS UP TO MECHANICAL SPACE WITH 2" SNAP-LOC SPACERS

01

T-19

[HWR][SSR1-1][SSR1-2]

SC-LR-1UPPER LEVEL

1

2

E.C. PROVIDED GROUND BAR (TYP.)

3

/M

AT

CH

LIN

E:

SE

E 0

1T

-406

T-19(16) 6" CONDUITS FROM TUNNEL TO TRENCH. REFER TO 06/T-19.

12"x

4"

(40) 6" L-BEND CONDUITS UP TO MECHANICAL SPACE WITH 1-1/2" SNAP-LOC SPACERS

2

SC-LR-1+10 AFF

24"x4"

03

T-18

44

4

4

4

55

6

(2) LEVELS OF SC-LR-1 MOUNTED AT +10' AND +11' AFF (TYP.) REFER TO 08/T-21 FOR ADDITIONAL INFORMATION.

SC-LR-1 FROM HIGHBAY DOWN TO +10' AFF OF TUNNEL SLAB REFER TO T-10 AND 07/T-21 FOR ADDITIONAL INFORMATION.

(2) LEVELS OF SC-LR-1 TRANSITION FROM +10' AND +11' AFF DOWN TO +1' AND +2' AFF WITH 90 DEGREE BENDS. REFER TO 08/T-21 FOR ADDITIONAL INFORMATION.

UPPER LEVEL OF SC-LR-1MOUNTED AT +11' AFF.

LOWER LEVEL OF SC-LR-1MOUNTED AT +10' AFF.

6

24"x

4"

24"x

4"

24"x

4"

36"x4"

24"x4"

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-3

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - N1

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - N1 01

1. PROVIDE CANTILEVER BRACKETS AND ALL ADDITIONAL HARDWARE REQUIRED TO PROPERLY SUPPORT CABLE TRAY. SUPPORTS FOR CABLE TRAY SHOULD BE PER MANUFACTURER RECOMMENDATIONS AND NOT TO EXCEED 10'-0' WITH WITH NO SUPPORT HARDWARE AT A CABLE TRAY SPLICE. REFER TO 01/T-19 AND 08/T-21 FOR REQUIRED ELEVATIONS.

2. REFER TO 01/T-19 FOR MORE INFORMATION.3. REFER TO 03/T-18 FOR TECHNOLOGY TUNNEL GROUNDING DETAIL.4. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH

SIDES OF THE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

5. WIRELESS ACCESS POINT SHALL BE MOUNTED ON SC-LR-1.6. SUBCONTRACTOR TO INSTALL CAT 6A FROM DEVICE TO NEAREST FRA, LLC.

PROVIDED CABINET AND PROVIDE ETHERNET EXTENDERS, SC-EXT AT EACH END. COORINATE FINAL LOCATIONS WITH FRA, LLC. REFER TO T-1 GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

1. INFORMATION OUTLETS SHALL BE SERVED FROM NETWORK ROOM 01H01. REFER TO T-10 FOR ROOM LOCATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

UP

GBGB

W AA1

L9

L9

L10

L10

L11

L11

L12

L12

L13

L13

L14

L14

L15

L15

L16

L16

L17

L17

L18

L18

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

(2) LEVELS (LOWER AND UPPER) OF SC-LR-1 AT 10'-4" AND 11'-6" AFF. REFER TO 01/T-20 FOR ADDITIONAL INFORMATION.

(15) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

(15) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

[SSR2-1][SSR2-2][SSR2-3][SSR2-4][SSR2-5][SSR2-6][SSR2-7][LB650-1][LB650-2]

SC-LR-1 AT +11'-6" AFF. REFER TO 01/T-20. (TYP.)

1

2

222

E.C. PROVIDED GROUND BAR (TYP.)

3

/M

AT

CH

LIN

E:

SE

E 0

1T

-3

/M

AT

CH

LIN

E:

SE

E 0

1T

-5

07

T-19

10" CONDUIT FROM TUNNEL TO TRENCH. (TYP. OF 35)

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

2

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

2

4

5

36"x4"

12"x

4"

12"x

4"

36"x4"

24"x

4"

24"x

4"

24"x

4"

24"x4"

36"x4"

12"x

4"

12"x

4"

24"x

4"

24"x

4"

24"x4"

1

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-4

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - N2

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - N2 01

1. PROVIDE CANTILEVER BRACKETS AND ALL ADDITIONAL HARDWARE REQUIRED TO PROPERLY SUPPORT CABLE TRAY. SUPPORTS FOR CABLE TRAY SHOULD BE PER MANUFACTURER RECOMMENDATIONS AND NOT TO EXCEED 10'-0' WITH WITH NO SUPPORT HARDWARE AT A CABLE TRAY SPLICE. REFER TO 01/T-20 FOR REQUIRED ELEVATIONS.

2. REFER TO 01/T-20 FOR MORE INFORMATION.3. REFER TO 03/T-18 FOR TECHNOLOGY TUNNEL GROUNDING DETAIL.4. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH

SIDES OF THE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

5. SUBCONTRACTOR TO INSTALL CAT 6A FROM DEVICE TO NEAREST FRA, LLC. PROVIDED CABINET AND PROVIDE ETHERNET EXTENDERS, SC-EXT AT EACH END. COORINATE FINAL LOCATIONS WITH FRA, LLC. REFER TO T-1 GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET. REFER TO T-11 FOR CABINET LOCATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

GBGBGB

L18

L18

L19

L19

L20

L20

L21

L21

L22

L22

L23

L23

L24

L24

L25

L25

L26

L26

L27

L27

L28

L28

L29

L29

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

01

T-20

(2) LEVELS (LOWER AND UPPER) OF SC-LR-1 AT 10'-4" AND 11'-6" AFF. REFER TO 01/T-20 FOR ADDITIONAL INFORMATION.

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

[LB650-3][LB650-4][LB650-5][LB650-6][LB650-7][LB650-8][LB650-9][HB650-1][HB650-2][HB650-3][HB650-4]

12

E.C. PROVIDED GROUND BAR (TYP.)

3

/M

AT

CH

LIN

E:

SE

E 0

1T

-4

/M

AT

CH

LIN

E:

SE

E 0

1T

-6

36"x4"

24"x4"

24"x

4"

24"x

4"

36"x4"

24"x4"

24"x

4"

36"x4"

24"x4"

(15) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

2

(15) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

2

(15) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

2

04

T-20

05

T-20

4

02

T-18

24"x

4"

24"x

4"

SC-LR-1 AT +11'-6" AFF. REFER TO 01/T-20. (TYP.)

1

SHEET NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-5

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - S1

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - S1 01

1. PROVIDE CANTILEVER BRACKETS AND ALL ADDITIONAL HARDWARE REQUIRED TO PROPERLY SUPPORT CABLE TRAY. SUPPORTS FOR CABLE TRAY SHOULD BE PER MANUFACTURER RECOMMENDATIONS AND NOT TO EXCEED 10'-0' WITH WITH NO SUPPORT HARDWARE AT A CABLE TRAY SPLICE. REFER TO 01/T-20 FOR REQUIRED ELEVATIONS.

2. REFER TO 01/T-20 FOR MORE INFORMATION.3. REFER TO 03/T-18 FOR TECHNOLOGY TUNNEL GROUNDING DETAIL.4. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH

SIDES OF THE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

UP

GBGBGB

W

GB

AA1

L30

L30

L31

L31

L32

L32

L33

L33

L34

L34

L35

L35

L36

L36

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

L37

L37

L38

L38

L39

L39

L40

L40

L41

L41

(2) LEVELS (LOWER AND UPPER) OF SC-LR-1 AT 10'-4" AND 11'-6" AFF. REFER TO 01/T-20 FOR ADDITIONAL INFORMATION.

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

24"x4"

[FUTURE HB650-5][FUTURE HB650-6]

12

E.C. PROVIDED GROUND BAR (TYP.)

3

/M

AT

CH

LIN

E:

SE

E 0

1T

-5

/M

AT

CH

LIN

E:

SE

E 0

1T

-7

(2) LEVELS OF SC-LR-2BASKET TRAY MOUNTED AT +7' AND +6' AFF. (TYP.)

5

36"x4"

24"x

4"

24"x

4"

36"x4"

24"x4"

24"x

4"

(27) 6" S-BEND CONDUITS UP TO GALLERY WITH 6x3 SNAP-LOC SPACERS

218"x4"

18"x4"

36"x

4"

18"x4"

18"x4"

36"x4"

4

6

6

01

T-22

(12) 4" CONDUITS

03

T-22

/MATCHLINE: SEE 01 T-8

7

7

24"x

4"

24"x4"

(27) S-BEND CONDUITS - BASE BID CAP CONDUITS 3' BELOW GRADE. ADDITIVE ALTERNATE EXTEND CONDUITS TO GALLERY

8

36"x4"

24"x

4"

SC-LR-1 AT +11'-6" AFF. REFER TO 01/T-20. (TYP.)

1

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-6

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - S2

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - S2 01

1. PROVIDE CANTILEVER BRACKETS AND ALL ADDITIONAL HARDWARE REQUIRED TO PROPERLY SUPPORT CABLE TRAY. SUPPORTS FOR CABLE TRAY SHOULD BE PER MANUFACTURER RECOMMENDATIONS AND NOT TO EXCEED 10'-0' WITH WITH NO SUPPORT HARDWARE AT A CABLE TRAY SPLICE. REFER TO 01/T-20 FOR REQUIRED ELEVATIONS.

2. REFER TO 01/T-20 FOR MORE INFORMATION.3. REFER TO 03/T-18 FOR TECHNOLOGY TUNNEL GROUNDING DETAIL.4. INSTALL (12) 4" CONDUITS TIGHT TO CEILING. REFER TO 1/T-22 FOR ADDITIONAL

INFORMATION. PROVIDE 24” LADDER DROP-OUT ON SC-LR-1 TO ROUTE CABLES FROM SC-LR-1 TO 4" CONDUITS.

5. REFER TO 04/T-18 FOR TECHNOLOGY TUNNEL - BTL - GROUNDING DETAIL.6. SINGLE LEVEL OF SC-LR-2 AT +7' AFF. REFER TO 05/T-22 FOR ADDITIONAL

INFORMATION.7. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH

SIDES OF THE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

8. SUBCONTRACTOR TO INSTALL CAT 6A FROM DEVICE TO NEAREST FRA, LLC. PROVIDED CABINET AND PROVIDE ETHERNET EXTENDERS, SC-EXT AT EACH END. COORINATE FINAL LOCATIONS WITH FRA, LLC. REFER TO T-1 GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET. REFER TO T-13 FOR CABINET LOCATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

GBGBGB

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

L42

L42

L43

L43

L44

L44

L45

L45

L46

L46

L47

L47

L48

L48

L49

L49

L50

L50

L52

L52

L53

L53

ADDITIVE ALTERNATE BUILDING EXTENSION

/M

AT

CH

LIN

E:

SE

E 0

1T

-6

(2) LEVELS OF SC-LR-2BASKET TRAY MOUNTED AT +7' AND +6' AFF. (TYP.)

1

/MATCHLINE: SEE 01 T-8

18"x4"

18"x4"

36"x4"

2

(2) LEVELS OF SC-LR-2BASKET TRAY MOUNTED AT +7' AND +6' AFF. (TYP.)

1

(27) S-BEND CONDUITS WITH 6X3 SNAP-LOC SPACERS. - BASE BID CAP CONDUITS 3' BELOW GRADE, ADDITIVE ALTERNATE EXTEND CONDUITS TO GALLERY

(27) S-BEND CONDUITS - CAP CONDUITS 3' BELOW GRADE WITH 6x3 SNAP-LOC SPACERS

(27) S-BEND CONDUITS - CAP CONDUITS 3' BELOW GRADE WITH 6x3 SNAP-LOC SPACERS

(27) S-BEND CONDUITS - CAP CONDUITS 3' BELOW GRADE WITH 6x3 SNAP-LOC SPACERS

SHEET NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-7

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - S3

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - S3 01

1. REFER TO 04/T-18 FOR TECHNOLOGY TUNNEL - BTL - GROUNDING DETAIL.2. SINGLE LEVEL OF SC-LR-2 AT +7' AFF. REFER TO 05/T-22 FOR ADDITIONAL

INFORMATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

GB

GB

E.C. PROVIDED GROUND BAR (TYP.)

(2) LEVELS OF SC-LR-2BASKET TRAY MOUNTED AT +7' AND +6' AFF. (TYP.)

1

/MATCHLINE: SEE 01 T-7

/M

AT

CH

LIN

E:

SE

E 0

1T

-6

/MATCHLINE: SEE 01 T-9

/M

AT

CH

LIN

E:

SE

E 0

1T

-7

36"x4"

18"x4"

18"x4"

36"x4"

18"x4"

18"x4"

36"x4"

2

2

2

04

T-18

(2) LEVELS OF SC-LR-2BASKET TRAY MOUNTED AT +7' AND +6' AFF. (TYP.)

05

T-22

SHEET NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-8

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - BTL-E

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - BTL-E 01

1. REFER TO 04/T-18 FOR TECHNOLOGY TUNNEL - BTL - GROUNDING DETAIL.2. SINGLE LEVEL OF SC-LR-2 AT +7' AFF. REFER TO 05/T-22 FOR ADDITIONAL

INFORMATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

GB

GB

GB

GB

GB

CSS

CSSCSS

E.C. PROVIDED GROUND BAR (TYP.)

1

/MATCHLINE: SEE 01 T-8

(8) 4" CONDUITS

01

T-21

(32) 6" L-BEND CONDUITS UP TO BUILDING F37

2

1

2

1

2

1

3

24"x

4"

24"x

4"

18"x4"

36"x4"

18"x

4"

24" x

4"

24" x

4"

1

2

1

4

1

3

4

(TYP. OF 4)

SHEET NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-9

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - TUNNEL - BTL-W

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - TUNNEL - BTL-W 01

1. REFER TO 04/T-18 FOR TECHNOLOGY TUNNEL - BTL - GROUNDING DETAIL.2. (2) LEVELS OF SC-LR-2 MOUNTED AT +7' AND +6' AFF.3. (3) LEVELS OF SC-LR-2 MOUNTED AT +7' AND +6' AND +5' AFF.4. SINGLE LEVEL OF SC-LR-2 MOUNTED AT +7' AFF. REFER TO 01/T-21 FOR

ADDITIONAL INFORMATION.

E.C. SHALL CONFIRM CABLE TRAY ROUTING WITH FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION

GB

C4

C2-1

C2-1

WP

1

WP1

C2-WAP

C2-WAP

C2-WAP

C4

C4

C4

CR

1

CSS

CSS

CR2

C2-WAP

C2-1

C2-1

WP1

C2-1

C2-1

C2-1

C2-1

C4

C4

C4C4

CR1 CR1

CSSCSS

GB

C2 /A

GB GB

GB

AM

S

C2-WAP

C2-WAP C2-WAP

C2-WAP

C4

C4

C2-1 C2-1

C2-1

C2-1

C2-1C2-1

CR

1

CSS

CA

M

C2 /A

GB

GB

C1

L1

L1

L2

L2

L3

L3

L4

L4

L5

L5

L6

L6

L7

L7

L8

L8

L9

L9

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

LBLB

LALA

MECHANICAL

01G02

VEST

01E01

NW ENTRY

01E04

VEST

01D11

HIGH BAY

01G06

DOCK

01A09

ELEV. N

01B10STAIR E1

01B11

NETWORKROOM

01H01

W/C

01F05

COATS

01H14

W/C

01F02

CORRIDOR

01F03

COMMANDCENTER

01F12

TECH BAY

01F16

HUDDLE

01H17

CONFERENCE

01G16

HUDDLE

01G17

AV-WP1-F

(2) 1-1/4" CONDUIT

+48"

+48"

C2

1

24"x4"

01F16

+42"

+42"01E01

24"x4"

24"x4"

24"x4"

T-16

01

SC-LR-1UPPER LEVEL

SC-LR-2

SC-LR-1

24"x

4"

24"x

4"

24"x

4"

24"x

4"

24"x

4"

24"x

4"

24"x

4"

POWER POLE (TYP.) REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION

24"x4"

12"x

4"

T-16

02

(84) 6" L-BEND CONDUITS UP FROM TRENCH. CONDUITS EXTEND 7' AFF

+90"

+54"

01D1101A09

+42" +42"

2

TYP. OF 6

SC-LR-1UPPER LEVEL

(3) LEVELS (LOWER, MID AND UPPER) OF SC-LR-1.

33 3 3 3 3 3

3

E.C. PROVIDED GROUND BAR

3

4

5

/M

AT

CH

LIN

E:

SE

E 0

1T

-11

6

+48"+48"

(2) 1-1/4" CONDUIT

1

AV-WP1-F

C2

(2) 1-1/4" CONDUIT

1

AV-WP1-F

C2

(16) 6" CONDUITS DOWN TO TRENCHREFER TO 06/T-19.

7

77

7

+90"+54"

5

SC-LR-1 DOWN TO +10' AFF OF TUNNEL SLAB WITH 90 DEGREE BEND. REFER TO T-3 AND 07/T-21 FOR ADDITIONAL INFORMATION.

88

05

T-21

+42"

01H01

SC-LR-1 TRANSITION FROM UPPER LEVEL OF TRAY HEIGHT DOWN TO LOWER LEVEL.

24"x

4"

3

INF

OR

MA

TIO

N O

UT

LE

TS

SH

ALL B

E S

ER

VE

D

FR

OM

EX

IST

ING

MA

IN N

ET

WO

RK

ING

RO

OM

401 IN

CR

YO

PLA

NT

BU

ILD

ING

. R

EF

ER

TO

4/T

-16 F

OR

RO

OM

LO

CA

TIO

N.

INF

OR

MA

TIO

N O

UT

LE

TS

SH

ALL B

E

SE

RV

ED

FR

OM

NE

TW

OR

K R

OO

M 0

1H

01.

(3) 4" SLEEVES

+10'

CAM 9

REFER TO 04/T-16

01

T-19

06

T-19

10

11

TR-3 12

SHEET NOTES

GENERAL NOTES

KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-10

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - LEVEL 01 - N1

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - LEVEL 01 - N1 01

1. ROUTE WITH HDMI CABLE (1) FRA, LLC. PROVIDED ZOOM CAMERA CABLE FROM AV-WP1-F TO ABOVE ACCESSIBLE CEILING ABOVE FLAT PANEL DISPLAY. COORDINATE ZOOM CAMERA CABLE FINAL LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

2. ROUTE INFORMATION OUTLET CABLES TO MILLWORK IN E.C. PROVIDED POWER POLE.

3. LOWER LEVEL OF SC-LR-1. 4. REFER TO 01/T-18 AND 02/T-18 FOR

TECHNOLOGY GALLERY GROUNDING DETAILS.

5. PROVIDE TRAPEZE SUPPORT KIT WITH 1/2" THREADED RODS AND ALL REQUIRED HARDWARE EVERY 10'. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

6. INFORMATION OUTLET PROVIDED FOR 3 X 3 VIDEO WALL. COORDINATE WITH FRA, LLC. AND FRA, LLC. CONSTRUCTION COORDINATOR PRIOR TO INSTALLATION.

7. WIRELESS ACCESS POINT SHALL BE MOUNTED ON SC-LR-1.

8. FUTURE LOCATION. PROVIDE BACKBOX, CONDUIT AND BLANK COVER PLATE. REFER TO EQUIPMENT LIST SC-IO-C FOR ROUGH-IN INFORMATION.

9. PROVIDE (1) 1” CONDUIT FROM CABLE TRAY TO CANOPY WITH (1) CAT 6A CABLE FOR CEILING MOUNTED VIDEO SURVEILLANCE CAMERA. COORDINATE FINAL LOCATION OF CAMERA WITH FRA, LLC. PRIOR TO INSTALLATION. VIDEO SURVEILLANCE CAMERA IS FRA, LLC. PROVIDED AND INSTALLED BY THIS SUBCONTRACTOR. CAT 6A CABLE SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET. REFER TO 05/T-17 FOR ADDITIONAL INFORMATION.

10. SUBCONTRACTOR TO PROVIDE TEMPORARY PLUGS FOR ALL L-BEND CONDUITS.

11. SUBCONTRACTOR TO PROVIDE TEMPORARY PLUGS FOR CONDUITS.

12. PROVIDE ONE CAT 6 CABLE TO AREA OF RESCUE CALL MASTER FOR ANALOG PHONE SERVICE.

1. ACCESS CONTROL DEVICES TO BE FED FROM ACCESS CONTROL PANEL IN NETWORK ROOM 01H01. REFER TO T-16 FOR MORE INFORMATION

GBGB

CR1

CSS

GB GB

CSS

CR1

GB

C2-WAP

C2-WAP

C2-WAP

C2-WAP

C2-WAP

C2-WAP

C2-WAP

C2-WAP

C2-WAP

L9L10L11L12L13L14L15L16L17L18

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

STAIR W1

01V00

24"x4"

24"x4"

24"x4" 24"x4"

24"x4"

24"x4"

+42"

01AD02B

FRA, LLC. PROVIDED CABINET FOR DATA CABLE

(15) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(15) 6" S-BEND CONDUITS

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

(3) LEVELS (LOWER, MID AND UPPER) OF SC-LR-1. REFER TO 02/T-20 FOR ADDITIONAL INFORMATION.

1

1

111

1

1

1111111111

+42"

01AD02C

4 4 4 4 4 4 4 4 4

2

2

E.C. PROVIDED GROUND BAR (TYP.)

/M

AT

CH

LIN

E:

SE

E 0

1T

-10

/M

AT

CH

LIN

E:

SE

E 0

1T

-12

10" CONDUIT DOWN TO TRENCH. REFER TO 07/T-19 FOR ADDITIONAL INFORMATION. (TYP. OF 35)

5

5

5

5

5

5

5

5

5

SC-LR-1UPPER LEVEL

3

SC-LR-1UPPER LEVEL

3

07

T-19

6

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-11

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - LEVEL 01 - N2

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - LEVEL 01 - N2 01

#

1. (2) LEVELS (LOWER AND MID) OF SC-LR-1. REFER TO 02/T-20 FOR ADDITIONAL INFORMATION.

2. REFER TO 01/T-18 AND 02/T-18 FOR TECHNOLOGY GALLERY GROUNDING DETAILS.

3. PROVIDE TRAPEZE SUPPORT KIT WITH 1/2" THREADED RODS AND ALL REQUIRED HARDWARE EVERY 10'. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

4. SUBCONTRACTOR TO PROVIDE TEMPORARY PLUGS FOR ALL S-BEND CONDUITS. REFER TO 01/T-20 FOR MORE INFORMATION.

5. WIRELESS ACCESS POINT SHALL BE MOUNTED ON SC-LR-1.6. SUBCONTRACTOR TO PROVIDE TEMPORARY PLUGS FOR CONDUITS.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET.

GBGB

CR1

CSS

W

GB

GB GB GB

GB

C2-WAPC2-WAPC2-WAPC2-WAPC2-WAPC2-WAP

C2-WAPC2-WAPC2-WAP

C2-WAPC2-WAPC2-WAP

CSS

CR

1

W

L18L19L20L21L22L23L24L25L26L27L28L29

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

LINAC GALLERY

01AD02

STAIR E2

01X13

E2 PPE

01X12

24"x4"

24"x4"

24"x4"

24"x4"

24"x4"

24"x4"

(3) LEVELS (LOWER, MID AND UPPER) OF SC-LR-1. REFER TO 02/T-20 FOR ADDITIONAL INFORMATION.

SC-LR-1UPPER LEVEL

FRA, LLC. PROVIDED CABINET FOR DATA CABLE

01AD02D

+42"

24"x4"

24"x4"

24"x4"

(15) 6" S-BEND CONDUITS

(15) 6" S-BEND CONDUITS

(15) 6" S-BEND CONDUITS

(15) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4" 1111111111

SC-LR-1UPPER LEVEL

E.C. PROVIDED GROUND BAR (TYP.)

2

4

3

22

4444

/M

AT

CH

LIN

E:

SE

E 0

1T

-11

/M

AT

CH

LIN

E:

SE

E 0

1T

-13

5

5

5

5

5

5

5

5

5

5

5

53

01X13 6

+42"

7

02

T-18

01

T-18

SPACE FOR FUTURE ACCESS CONTROL PANEL

01

T-20

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-12

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - LEVEL 01 - S1

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - LEVEL 01 - S1 01

1. (2) LEVELS (LOWER AND MID) OF SC-LR-1. REFER TO 02/T-20 FOR ADDITIONAL INFORMATION.

2. REFER TO 01/T-18 AND 02/T-18 FOR TECHNOLOGY GALLERY GROUNDING DETAILS.

3. PROVIDE TRAPEZE SUPPORT KIT WITH 1/2" THREADED RODS AND ALL REQUIRED HARDWARE EVERY 10'. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

4. SUBCONTRACTOR TO PROVIDE TEMPORARY PLUGS FOR ALL S-BEND CONDUITS. REFER TO 01/T-20 FOR MORE INFORMATION.

5. WIRELESS ACCESS POINT SHALL BE MOUNTED ON SC-LR-1.6. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH

SIDES WITHIN 3' OF THE GATE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET.7. SUBCONTRACTOR TO INSTALL CAT 6A FROM DEVICE TO NEAREST FRA, LLC. PROVIDED CABINET AND PROVIDE ETHERNET EXTENDERS, SC-EXT AT EACH END. COORINATE FINAL LOCATIONS WITH FRA, LLC. REFER TO T-1 GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

GB

GB

CR1

CSS

W

GB

GB

C2-WAPC2-WAPC2-WAP

C2-WAPC2-WAP

C2-W

AP

GB

CR

1

CSS

GB

L30L31L32L33L34L35L36

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

L37

L37

L38

L38

L39

L39

L40

L40

L41

L41L42

L42

DOWNSTREAMLASER ROOM

01AS02

ADDITIVE ALTERNATE BUILDING EXTENSION

STAIR W2

01AV00

ELEV. S

01AT00

E3 PPE

01AZ12

STAIR E3

01AZ13

VESTIBULE

01AT01

24"x4"

24"x4"

24"x4"24"x4"

(3) LEVELS (LOWER, MID AND UPPER) OF SC-LR-1. REFER TO 02/T-20 FOR ADDITIONAL INFORMATION.

01AD02E

+42"

FRA, LLC. PROVIDED CABINET FOR DATA CABLE

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

(27) 6" S-BEND CONDUITS

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

36"x

4"

111111

SC-LR-1UPPER LEVEL

E.C. PROVIDED GROUND BAR (TYP.)

3

2

444

2

/M

AT

CH

LIN

E:

SE

E 0

1T

-12

5

5

5

55

+42"

01AZ13

+10'

/M

AT

CH

LIN

E:

SE

E 0

1T

-14

6

7

(27) S-BEND CONDUITS - BASE BID CAP CONDUITS 3' BELOW GRADE. ADDITIVE ALTERNATE EXTEND CONDUITS TO GALLERY

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-13

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - LEVEL 01 - S2

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - LEVEL 01 - S2 01

#

1. (2) LEVELS (LOWER AND MID) OF SC-LR-1. REFER TO 02/T-20 FOR ADDITIONAL INFORMATION.

2. REFER TO 01/T-18 AND 02/T-18 FOR TECHNOLOGY GALLERY GROUNDING DETAILS.

3. PROVIDE TRAPEZE SUPPORT KIT WITH 1/2" THREADED RODS AND ALL REQUIRED HARDWARE EVERY 10'. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

4. SCHEDULE FOR MORE INFORMATION.5. SUBCONTRACTOR TO PROVIDE TEMPORARY PLUGS FOR ALL S-BEND CONDUITS.

REFER TO 01/T-20 FOR MORE INFORMATION.6. WIRELESS ACCESS POINT SHALL BE MOUNTED ON SC-LR-1. 7. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH

SIDES WITHIN 3' OF THE GATE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET.8. SUBCONTRACTOR TO INSTALL CAT 6A FROM DEVICE TO NEAREST FRA, LLC. PROVIDED CABINET AND PROVIDE ETHERNET EXTENDERS, SC-EXT AT EACH END. COORINATE FINAL LOCATIONS WITH FRA, LLC. REFER TO T-1 GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

GB

CR1

CSS

WCR

1

CSS

GB

LDLD

LELE

LFLF

LGLG

LHLH

LCLC

L42

L42

L43

L43

L44

L44

L45

L45

L46

L46

L47

L47

L48

L48

L49

L49

L50

L50

L52

L52

L53

L53

ADDITIVE ALTERNATE BUILDING EXTENSION

E4 PPE

01F07

STAIR E4

01F08

01F08

+42"

01BF02

+42"

/M

AT

CH

LIN

E:

SE

E 0

1T

-13

1

FRA, LLC. PROVIDED CABINET FOR DATA CABLE

2

(27) S-BEND CONDUITS - BASE BID CAP CONDUITS 3' BELOW GRADE. ADDITIVE ALTERNATE EXTEND CONDUITS TO GALLERY AND PROVIDE TEMPORARY PLUGS ON CONDUITS

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - LEVEL 01 - S3 01

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-14

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - LEVEL 01 - S3

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

1. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH SIDES WITHIN 3' OF THE GATE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

2. SUBCONTRACTOR TO INSTALL CAT 6A FROM DEVICE TO NEAREST FRA, LLC. PROVIDED CABINET AND PROVIDE ETHERNET EXTENDERS, SC-EXT AT EACH END. COORINATE FINAL LOCATIONS WITH FRA, LLC. REFER TO T-1 GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET.

GB

CR

1

CR

1

CSS

CSS

GB

GB

C2-WAP

C2-WAP

PUMP ROOM

01F3700

F-37

01F3701

F-37 STAIR

01F3703

F-37 PPE

01F3702

FC

FC

FA

FA

FB

FB

F1

F1

F2

F2

F37-11

F37-13

01

T-21

(32) 6" L-BEND CONDUITS TO TUNNEL, SPACE WITH 3" SNAP-LOC SPACERS AND PROVIDE TEMPORARY PLUGS ON ALL CONDUITS

SC-LR-1(TYP.)

1

AC-SCP-1AC-PSP-1

FRA, LLC. PROVIDED WALL MOUNTED CABINET FOR DATA CABLING. CABINET MOUNTED BELOW SC-LR-1

1

1

+42"

+42"

SHEET NOTES GENERAL NOTES KEY PLAN

8

1/8"=1'-0"

0 8 16

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

N1N2S1S2S3

F-37

1/8" = 1'-0"

T-15

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY PLAN - LEVEL 01 - BTL-W

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: 1/8" = 1'-0"

TECHNOLOGY PLAN - LEVEL 01 - BTL-W 01

1. INTERLOCK LOCATION. PROVIDE 1900 BOXES FLUSHED MOUNTED ON BOTH SIDES OF THE DOOR WITH 1" CONDUIT CONNECTING THE BOXES. COORDINATE LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

2. WIRELESS ACCESS POINT SHALL BE MOUNTED ON SC-LR-1.

1. INFORMATION OUTLETS SERVED FROM NEAREST FRA, LLC. PROVIDED CABINET.2. INSTALL LADDER RACK AT 8'-10" AFF.

GB

GB

FRA, LLC.

PROVIDED

PATCH PANEL

FRA, LLC.

PROVIDED

NETWORK

EQUIPMENT

FRA, LLC.

PROVIDED

FIBER PANEL

L7

L7

LHLH

L7

L7

LHLH

LG.8LG.8

LG.9LG.9

L7.2

L7.2

LH

L7

L7.2

LG.9

AC-SCP-1

AC-PSP-1

+4'

+6'

FIRUS (BY FRA, LLC.) SEE ARCHITECTURAL DRAWINGS.

AR-PS-1

SPACE FOR FUTURE ACCESS CONTROL PANEL

L5

L5

L6

L6

L7

L7

12"x

4"

SC-LR-2

(4) 4" SLEEVES

REFER TO 01/T-10

L7

L7

LHLH

L7

L7

LHLH

LG.8LG.8

LG.9LG.9

L7.2

L7.2

LH

L7

L7.2

LG.9

(4) 4" SLEEVES

SC-LR-1(TYP.)

(6) 4" INCOMING CONDUITS. REFER TO ELECTRICAL DRAWINGS E-4 AND E-30 FOR ADDITIONAL INFORMATION

1

2

2

1

FRA, LLC. PROVIDED FIBER OPTIC BACKBONE

3

NEAREST FRA, LLC. PROVIDED CABINET

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO T-1 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

KEYNOTES:

1. 23 GAUGE, 4-PAIR, CATEGORY 6A, UNSHIELDED TWISTED PAIR CABLE, SEE SPECIFICATIONS.2. REFER TO INFORMATION OUTLET SCHEDULE ON T-1 AND THE FLOOR PLANS FOR QUANTITY OF

CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION OUTLET.3. RJ-45 TO RJ-45 CATEGORY CAT 6A UTP PATCH CORD PROVIDED BY SUBCONTRACTOR INSTALLED BY

FRA, LLC. SEE SPECIFICATIONS.4. FIBER PATCH CORD PROVIDED BY SUBCONTRACTOR INSTALLED BY FRA, LLC. SEE SPECIFICATIONS.

#

CAM

4

W

C#

2C#

CAM

4

1/4"=1'-0"

0 4 8

SCALE FEET

PR

OJE

CT

N

OR

TH

E

S

W

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

As indicated

T-16

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY ENLARGED PLANS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

EQUIPMENT PLAN LAYOUT - TR-3 01

SCALE: N.T.S.

TECHNOLOGY PLAN - EXISTING CRYO PLANT 04

SCALE: N.T.S.

EQUIPMENT PLAN PATHWAY - TR-3 02

SCALE: N.T.S.

CONNECTIVITY RISER DIAGRAM - TR-3 03

GENERAL NOTES:

1. INSTALL LADDER RACK AT 8'-6" AFF.

KEYNOTES:

1. PROVIDE 7' OF VERTICALLY MOUNTED SC-LR-1 TO INCOMING 4" CONDUITS. TOP OF VERTICAL LADDER RACK TO BE INSTALLED AT +96" AFF WITH THE BOTTOM AT +12" AFF.

AC-PSP-1

AR-PS-1

NOTES:

1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO DESCRIBE THE CONTROLLED SECURITY SCHEME ROUGH-IN REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAY NOT ACCURATELY REPRESENT DOOR SIZE, DOOR SWING, DOOR HARDWARE, OR DOOR FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPECIFICATIONS FOR COMPLETE INFORMATION. MIRROR THE DETAIL AS REQUIRED.

2. ROUGH IN SHOWN IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITY SYSTEM DEVICES AND CABLING UNLESS OTHERWISE NOTED. COORDINATE EXACT REQUIREMENTS WITH SELECTED DOOR MATERIALS, DOOR HARDWARE, AND CONTROLLED SECURITY DEVICES AND CABLING PRIOR TO INSTALLATION.

3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAY. CABLING ROUTED HORIZONTALLY ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLY RATED FOR THE CEILING ENVIRONMENT.

4. THE ELECTRICAL OR SECURITY SUBCONTRACTOR SHALL NOT MODIFY ANY FIRE RATED DOOR AND/OR DOOR FRAME. REFER TO THE ARCHITECTURAL DOOR SCHEDULE, DOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANY FIRE RATED DOOR AND/OR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME WITH THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).

5. INSTALLING SUBCONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECURITY SCHEME ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

6. REFER TO THE ACCESS CONTROL RISER DIAGRAM 2/T-17 FOR CABLING REQUIREMENTS AND THE CONTROLLED SECURITY SCHEME SCHEDULE ON T-17 FOR ADDITIONAL INFORMATION.

7. INSTALLATION SHALL INCLUDE ALL POWER REQUIRED FOR SYSTEM OPERATION INCLUDING +120VAC. REFER TO THE SUGGESTED MATRIX OF SCOPE RESPONSIBILITY FOR ADDITIONAL INFORMATION.

KEYNOTES:

1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION SUBCONTRACTOR.

2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.

3. DOUBLE GANG BACKBOX WITH SINGLE GANG PLASTER RING. REFER TO FLOOR PLAN(S) FOR ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.

4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURE SIDE OF THE DOOR. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY PANEL.

5. MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURE SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING SUBCONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES. MAINTAIN ACCESS TO THE JUNCTION BOX.

6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. REFER TO THE CONTROLLED SECURITY SCHEME SCHEDULE ON T-17 FOR DOORS THAT REQUIRE THIS ROUGH-IN.

7. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY PANEL.8. CONDUIT INSTALLED IN PERMANENT MULLIONS ONLY. REFER TO THE ARCHITECTURAL DOOR SCHEDULE AND DOOR HARDWARE GROUPS FOR

LOCATIONS THAT REQUIRE THIS ROUGH-IN. PROVIDE A NYLON BUSHING ON THE CONDUIT END.

DOOR FRAME ROUGH-IN DIAGRAM (ALL SINGLE DOORS)

DOOR FRAME ROUGH-IN DIAGRAM (ALL DOUBLE DOORS WITH OR WITHOUT MULLION)

FINISHED ACCESSIBLE CEILING

MINIMUM 3/4" EMT CONDUIT TO ABOVE THE ACCESSIBLE CEILING

FINISHED FLOOR

CREDENTIAL READER ROUGH-IN 3

DOOR CONTACT ROUGH-IN

MINIMUM 1" EMT CONDUIT

11

REQUEST TO EXIT DEVICE ROUGH-IN

FOR DOOR HARDWARE POWER SUPPLIES

1/2" EMT CONDUIT MINIMUM (TYP.)

3'-6

"

1

MINIMUM 1" EMT CONDUITFOR DOOR

HARDWARE POWER SUPPLIES

MINIMUM 3/4" EMT CONDUIT TO ABOVE THE ACCESSIBLE CEILING

CREDENTIAL READER ROUGH-IN 3

REQUEST TO EXIT DEVICE ROUGH-IN

DOOR CONTACT ROUGH-IN

1

3'-6

"

2

2

4

4

5

5

5

5

66

4" 4" 4"

7 7

8

6"

6"

TYPICAL OF SINGLEDOORS WITH CARD READER

CONNECTION TO LAN

WIRING KEY:

18 AWG (2) TWO CONDUCTOR STRANDED

18 AWG (4) FOUR CONDUCTOR STRANDED

14 AWG (2) TWO CONDUCTOR STRANDED

22 AWG (6) SIX CONDUCTOR STRANDED

A

B

C

D

PERSONALCOMPUTER

TR-3

D

C

C

E

AC-SCP-1

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND NOT INTENDED TO SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE.

2. ALL CABLING SHALL BE PLENUM RATED.3. REFER TO 1/T-17 FOR DOOR ROUGH-IN AND WIRING DIAGRAM.4. REFER TO T-1 FOR TECHNOLOGY EQUIPMENT SCHEDULE.

CR#DCRTE EDH

CSS

A

B

CATEGORY 6 PATCHCORDE

A DB

D

C

CR# DC RTEEDH

A

B

DC

A

TYPICAL OF DOUBLEDOORS WITH CARD READER

CSS

DC

A

TYPICAL OF DOOR CONTACT ONLY LOCATION

CSS

PARAPET WALL

2'-1 1/2"

2'-11

"

FLEXIBLE CONDUIT

NOTES:

1. SECURE WALL MOUNT BASE PLATE TO PARAPET WALL WITH MINIMUM 1/4" MASONRY FASTENERS. COORDINATE WITH FRA, LLC. FOR APPROVED MOUNTING LOCATION (I.E. BRICK, BLOCK, ETC.)

2. SEAL WALL MOUNT BASE PLATE TO PREVENT WATER INFILTRATION.3. SUBCONTRACTOR SHALL ENSURE SUPPORT OF ALL OPEN CABLE WITH APPROPRIATE

MEANS.4. THE DETAIL IS DIAGRAMMATIC, AND IS NOT INTENDED TO CONVEY ALL EQUIPMENT,

CONDUCTORS, CONNECTIONS, AND QUANTITIES REQUIRED. SUBCONTRACTOR SHALL PROVIDE EQUIPMENT AS NECESSARY TO SUPPORT ALL CAMERAS AS SHOWN ON PLANS.

5. SUBCONTRACTOR SHALL PROVIDE ROOF PENETRATION REAR CAMERA LOCATION. PROVIDED WEATHER HEAD PENETRATION OR APPROPRIATE PENETRATION TO SUPPORT CCTV CABLING. COORDINATE FINAL LOCATION WITH FRA, LLC. PRIOR TO INSTALLATION.

6. SUBCONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL TO PROPERLY SEAL ROOF PENETRATIONS AND ANCHOR POINTS TO PREVENT WATER INFILTRATION.

KEYNOTES:

1. ROUTE CAT 6A PATCH CORD FROM OWNER PROVIDED CAMERA TO LIGHTNING PROTECTION MODULE LOCATED NEAR CAMERA IN BUILDING. ROUTE CAT 6A CABLE TO LIGHTING PROTECTION MODULE AND TERMINATE CABLE WITH RJ-45 PLUG.

#

1

TUNNEL LEVEL

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO T-1 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

FIRST FLOOR

TR-3

AMS

AA1 AA1 AA1

18/2 PLENUM RATED CABLE 22/2 PAIR SHIELDED PLENUM RATED CABLE

NOTES:

1. COORDINATE EXACT LOCATION ON SITE WITH WORK BY OTHER TRADES TO ENSURE DESIRED VIEWING AREA AND SERVICE ACCESS AFTER COMPLETION OF PROJECT AND TO MINIMIZE ANY POSSIBLE DAMAGE TO INSTALLED CAMERA OR ASSOCIATED CABLING.

2. INSTALLING SUBCONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR CAMERA ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.

3. CAMERA MOUNTING ACCESSORY SHALL BE FROM THE SAME MANUFACTURER OF THE CAMERA AND APPROVED BY THE MANUFACTURER FOR USE WITH THE SPECIFIC MODEL NUMBER OF CAMERA INSTALLED. SUBCONTRACTOR SHALL INSTALL CAMERA MOUNTING ACCESSORY AND CAMERA PER MANUFACTURER'S INSTRUCTIONS.

KEYNOTES:

1. ROUTE CAT 6A CABLE TO OWNER PROVIDED CAMERA. TERMINATE CABLE WITH RJ-45 PLUG.

SCHEDULED CEILING

1" FLEXIBLE METALLIC CONDUIT FROM JUNCTION BOX TO ENCLOSURE. FLEX CONDUIT SHALL ONLY BE USED FOR MAXIMUM OF 10'

4-SQUARE OR OCTAGON JUNCTION BOX AS REQUIRED FOR CAMERA

CAMERA AS SPECIFIED

1" EMT CONDUIT ROUTE TO NEAREST CABLE TRAY

IF REQUIRED, PROVIDE TRIM RING TO ENSURE BACK BOX IS COMPLETELY COVERED

#

1

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

NOT TO SCALE

T-17

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY DETAILS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL 01

SCALE: N.T.S.

ACCESS CONTROL RISER DIAGRAM 02

SCALE: N.T.S.

EXTERIOR PARAPET MOUNTING 03

CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULEELECTRONIC DOOR HARDWARE SUCH AS ELECTRIC STRIKES, ELECTRIC LATCH RETRACTION, ETC. SHALL BE PROVIDED AND INSTALLED BY OTHERS. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ON

T-1 FOR CREDENTIAL READER TYPE INFORMATION.

DOOR # RO

UG

H-I

N O

NL

Y

CREDENTIALREADER INTEGRATION

REQUEST TOEXIT DOOR HARDWARE

OTHER (REFER TONOTES)

NOTESCR

ED

EN

TIA

L R

EA

DE

R T

YP

E

MU

LT

IPL

E C

RE

DE

NT

IAL

RE

AD

ER

S O

PE

RA

TE

S S

ING

LE

DO

OR

OP

ER

AT

ES

MU

LT

IPL

E D

OO

RS

WIR

EL

ES

S

AU

TO

MA

TIC

DO

OR

OP

ER

AT

OR

EL

EV

AT

OR

LO

CK

ED

BY

EM

ER

GE

NC

Y D

UR

ES

S S

EQ

UE

NC

E

INF

AN

T P

RO

TE

CT

ION

RE

MO

TE

UN

LO

CK

VIA

IN

TE

RC

OM

MA

ST

ER

RE

MO

TE

UN

LO

CK

VIA

PU

SH

BU

TT

ON

INT

RU

SIO

N D

ET

EC

TIO

N

RE

MO

TE

UN

LO

CK

VIA

FIR

E C

OM

MA

ND

CE

NT

ER

VID

EO

SU

RV

EIL

LA

NC

E

WA

ND

ER

PR

EV

EN

TIO

N S

YS

TE

M

INT

ER

NA

L E

LE

CT

RIF

IED

HA

RD

WA

RE

CO

NN

EC

TIO

N

LO

CA

L P

US

HB

UT

TO

N D

OO

R H

AR

DW

AR

E O

VE

RR

IDE

MO

TIO

N D

ET

EC

TO

R

EL

EC

TR

ON

IC L

OC

KIN

G H

AR

DW

AR

E (

BY

OT

HE

RS

)

MA

G L

OC

K

LA

TC

H S

TA

TU

S D

ET

EC

TIO

N

LO

CA

L A

LA

RM

HO

RN

MO

NIT

OR

LA

TC

H B

OL

T

MO

NIT

OR

DO

OR

PO

SIT

ION

SW

ITC

H S

PD

T

MO

NIT

OR

DO

OR

PO

SIT

ION

SW

ITC

H D

PD

T

MO

NIT

OR

DO

OR

PO

SIT

ION

SW

ITC

H F

OR

OV

ER

HE

AD

DO

OR

DE

LA

YE

D E

GR

ES

S

LO

CA

L 1

20V

AC

PO

WE

R S

UP

PL

Y

SC

HE

DU

LE

BA

SE

D L

OC

KIN

G

VIS

UA

L S

TR

OB

E

CR1 ● ● ●

CR1 ● ● ●

CR1 ● ● ●

01A09 CR1 ● ● ●

01AD02B CR1 ● ● ●

01AD02C CR1 ● ● ●

01AD02D CR1 ● ● ●

01AD02E CR1 ● ● ●

01AZ13 CR1 ● ● ●

01BF02 CR1 ● ● ●

01D11 CR1 ● ● ●

01E01 CR2 ● ● ●

01F08 CR1 ● ● ●

01F16 CR1 ● ● ●

01H01 CR1 ● ● ●

01X13 CR1 ● ● ●

F37-11 CR1 ● ● ●

F37-13 CR1 ● ● ●

SCALE: N.T.S.

RESCUE ASSISTANCE RISER DIAGRAM04

#

SCALE: N.T.S.

INACCESIBLE CEILING MOUNTED CAMERA ROUGH-IN DETAIL 05

REAR OF EQUIP. RACK

REAR OF EQUIP. RACK

E.C. PROVIDED GROUND BAR

GROUND CABLE(TYP.)

GROUND TRUNK CABLE

GROUND CABLE(TYP.)

SC-LR-1UPPER LEVEL

SC-LR-1MID LEVEL

SC-LR-1LOWER LEVEL

GROUND WIRE CLAMP (TYP.)

1

3

3

2

2

2

3

4

E.C. PROVIDED GROUND BAR

GROUND CABLE

GROUND CABLE

GROUND TRUNK CABLE RUNS THE LENGTH OF THE TUNNEL

GROUND CABLE

SC-LR-1UPPER LEVEL

SC-LR-1UPPER LEVEL

SC-LR-1LOWER LEVEL

2

2

3

32

1

3

4

SC-LR-2+7' AFF

GROUND CABLE

E.C. PROVIDED GROUND BAR

3

4

2

GROUND TRUNK CABLE RUNS THE LENGTH OF THE TUNNEL

12

SC-LR-2+6' AFF

E.C. PROVIDED GROUND BAR

GROUND CABLE

GROUND TRUNK CABLE RUNS THE LENGTH OF THE GALLERY

SC-LR-1LOWER LEVEL

2

1

3

4

SC-LR-1MID LEVEL

2

SC-LR-1UPPER LEVEL

2

SC-LR-1UPPER LEVEL

2

SC-LR-1UPPER LEVEL

2

GROUND CABLE

3

GROUND CABLE

3

GROUND TRUNK CABLE RUNS THE LENGTH OF THE GALLERY

1

GROUND TRUNK CABLE RUNS THE LENGTH OF THE GALLERY

1

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

NOT TO SCALE

T-18

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY SECTIONS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

TECHNOLOGY GALLERY GROUNDING DETAIL A 01

NOTES:

1. CONFIGURATION SHOWN IN THE DETAIL ABOVE IS DIAGRAMMATIC AND INTENDED TO DESCRIBE THE CABLE TRAY GROUNDING. REFER TO SPECIFICATIONS FOR COMPLETE INFORMATION.

2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.3. REFER TO 1/T-3 FOR SECTION LOCATION.

KEYNOTES:

1. EXTEND #500KCM COPPER BONDING CONDUCTOR TO NEXT SC-LR-1 FOR LENGTH OF TUNNEL.2. REFER TO FLOOR PLANS FOR CABLE TRAY LOCATIONS AND ELEVATIONS.3. #500KCM COPPER BONDING CONDUCTOR FOR GROUND WIRE.4. REFER TO ELECTRICAL DRAWINGS FOR E.C. PROVIDED GROUND BAR LOCATIONS AND QUANTITY.

NOTES:

1. CONFIGURATION SHOWN IN THE DETAIL ABOVE IS DIAGRAMMATIC AND INTENDED TO DESCRIBE THE CABLE TRAY GROUNDING. REFER TO SPECIFICATIONS FOR COMPLETE INFORMATION.

2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.3. REFER TO 1/T-12 FOR SECTION LOCATION.

KEYNOTES:

1. EXTEND #500KCM COPPER BONDING CONDUCTOR TO NEXT SC-LR-1 FOR LENGTH OF GALLERY.2. REFER TO FLOOR PLANS FOR CABLE TRAY LOCATIONS AND ELEVATIONS.3. #500KCM COPPER BONDING CONDUCTOR FOR GROUND WIRE.4. REFER TO ELECTRICAL DRAWINGS FOR E.C. PROVIDED GROUND BAR LOCATIONS AND QUANTITY.

NOTES:

1. CONFIGURATION SHOWN IN THE DETAIL ABOVE IS DIAGRAMMATIC AND INTENDED TO DESCRIBE THE CABLE TRAY GROUNDING. REFER TO SPECIFICATIONS FOR COMPLETE INFORMATION.

2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.3. REFER TO 1/T-8 FOR SECTION LOCATION.

KEYNOTES:

1. EXTEND #500KCM COPPER BONDING CONDUCTOR TO NEXT SC-LR-2 FOR LENGTH OF TUNNEL.2. REFER TO FLOOR PLANS FOR CABLE TRAY LOCATIONS.3. #500KCM COPPER BONDING CONDUCTOR FOR GROUND WIRE.4. REFER TO ELECTRICAL DRAWINGS FOR E.C. PROVIDED GROUND BAR LOCATIONS AND QUANTITY.

#

#

#

SCALE: N.T.S.

TECHNOLOGY TUNNEL GROUNDING DETAIL 03

SCALE: N.T.S.

TECHNOLOGY TUNNEL - BTL - GROUNDING DETAIL 04

SCALE: N.T.S.

TECHNOLOGY GALLERY GROUNDING DETAIL B 02

NOTES:

1. CONFIGURATION SHOWN IN THE DETAIL ABOVE IS DIAGRAMMATIC AND INTENDED TO DESCRIBE THE CABLE TRAY GROUNDING. REFER TO SPECIFICATIONS FOR COMPLETE INFORMATION.

2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE INFORMATION.3. REFER TO 1/T-12 FOR SECTION LOCATION.

KEYNOTES:

1. EXTEND #500KCM COPPER BONDING CONDUCTOR TO NEXT SC-LR-1 FOR LENGTH OF GALLERY.2. REFER TO FLOOR PLANS FOR CABLE TRAY LOCATIONS AND ELEVATIONS.3. #500KCM COPPER BONDING CONDUCTOR FOR GROUND WIRE.4. REFER TO ELECTRICAL DRAWINGS FOR E.C. PROVIDED GROUND BAR LOCATIONS AND QUANTITY.

#

6" SCHEDULE 40L-BEND CONDUITS

SC-LR-1LOWER LEVEL

SC-LR-1UPPER LEVEL

10

'-4

"

11

'-6

"

CLEAR ZONE, NO SUPPORTS ARE ALLOWED IN THIS ZONE.1

0'-0

"

1

2

TUNNEL LEVEL

MECHANICAL SPACE

6" CONDUIT FROM TUNNEL TO TRENCH

6" CONDUIT FROM GALLERY TO TRENCH

12

'-8

"

TUNNEL LEVEL

GALLERY LEVEL

10" CONDUIT FROM TUNNEL TO TRENCH

10" CONDUIT FROM GALLERY TO TRENCH

12

'-8

"

TUNNEL LEVEL

TRENCH LEVEL

GALLERY LEVEL

L-BEND CONDUIT BANK 2.REFER TO 05/T-19 FOR ADDITIONAL INFORMATION.

L-BEND CONDUIT BANK 1. REFER TO 04/T-19 FOR ADDITIONAL INFORMATION.

(4) #4 BARS CONTINUOUS ON TOP AND BOTTOM

6" SCHEDULE 40 PVC

4" MINIMUM COMPACTED AGGREGATE BASE.

#4 TIE BARS AT 3'-0" ON CENTER

INTERMEDIATE SPACER

CONDUIT NONMETALLIC SPACER, MAXIMUM 5' ON CENTER. SNAP LOC S288RHN AND S289RHN SERIES

3" MIN.

3"

MIN

.8.1

4"

6.3

8"

2500 PSI CONCRETE

1 1/4" 1 1/4"

8.38"

NOTES :

1. INSTALL 2000 lb TENSILE STRENGTH BRAIDED POLYPROPYLENE PULL CORD IN ALL CONDUITS.2. TRENCHING AND BACKFILL ACCORDING TO SPECIFICATIONS.3. DOWEL ENDS OF DUCTBANK TO FOUNDATION OR MANHOLE WITH A MINIMUM OF (4) #4 DOWELS.4. (40) 6" L-BEND CONDUITS UP TO MECHANICAL SPACE WITH 1-1/2" SNAP-LOC SPACERS.

8.38"8.38"

8.38"

8.38"

8.38"

8.38"

8.38"5/8"

19

/32

"

1"

8.1

4"

8.1

4"

8.38"

(4) #4 BARS CONTINUOUS ON TOP AND BOTTOM

6" SCHEDULE 40 PVC

4" MINIMUM COMPACTED AGGREGATE BASE.

#4 TIE BARS AT 3'-0" ON CENTER

INTERMEDIATE SPACER

CONDUIT NONMETALLIC SPACER, MAXIMUM 5' ON CENTER. SNAP LOC S288RJN AND S289RJN SERIES

3" MIN.

3"

MIN

.8.6

4"

6.3

8"

2500 PSI CONCRETE

1 1/4" 1 1/4"

8.88"

NOTES :

1. INSTALL 2000 lb TENSILE STRENGTH BRAIDED POLYPROPYLENE PULL CORD IN ALL CONDUITS.2. TRENCHING AND BACKFILL ACCORDING TO SPECIFICATIONS.3. DOWEL ENDS OF DUCTBANK TO FOUNDATION OR MANHOLE WITH A MINIMUM OF (4) #4 DOWELS.4. (44) 6" L-BEND CONDUITS UP TO MECHANICAL SPACE WITH 2" SNAP-LOC SPACERS.

8.88"8.88"

8.88"

8.88"

8.88"

8.88"

8.88"

8.88"

8.88"5/8"

19

/32

"

1"

8.6

4"

8.6

4"

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

NOT TO SCALE

T-19

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY SECTIONS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO MECHANICAL SPACE ISO-VIEW A 02

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO MECHANICAL SPACE SECTION 01

NOTES:

1. REFER TO 1/T-3 AND 1/T-10 FOR SECTION LOCATION.2. REFER TO 02/T-19 AND 03/T-19 FOR ISO-VIEWS.

KEYNOTES:

1. SUBCONTRACTOR TO PROVIDE BELLED END, FLUSH WITH OPENING. INSIDE EDGE OF BELLED END CONDUIT SHALL BE GROUND AND BEVELED.

2. SUBCONTRACTOR TO PROVIDE BELLED END. INSIDE EDGE OF BELLED END CONDUIT SHALL BE GROUND AND BEVELED.

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO TRENCH SECTION A 06

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO TRENCH SECTION B 07

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO MECHANICAL SPACE ISO-VIEW B 03

SCALE: N.T.S.

L-BEND CONDUIT BANK 1 - TUNNEL TO MECHANICAL SPACE 04

SCALE: N.T.S.

L-BEND CONDUIT BANK 2 - TUNNEL TO MECHANICAL SPACE 05

NOTES:

1. REFER TO 1/T-3 AND 1/T-10 FOR SECTION LOCATION.2. SUBCONTRACTOR TO PROVIDE BELLED END, FLUSH WITH OPENING. INSIDE EDGE OF BELLED END CONDUIT

SHALL BE GROUND AND BEVELED FOR ALL CONDUIT.

NOTES:

1. REFER TO 1/T-4 AND 1/T-11 FOR SECTION LOCATION.2. SUBCONTRACTOR TO PROVIDE BELLED END, FLUSH WITH OPENING. INSIDE EDGE OF BELLED END CONDUIT

SHALL BE GROUND AND BEVELED FOR ALL CONDUIT.

#

SC-LR-1LOWER LEVEL

SC-LR-1LOWER LEVEL

6" SCHEDULE 80S-BEND CONDUITS

11

'-6

"

10

'-4

"

11

'-3

1/2

"

SC-LR-1UPPER LEVEL

SC-LR-1UPPER LEVEL

SC-LR-1MID-LEVEL

10

'-4

"

SC-LR-1UPPER LEVEL

CLEAR ZONE, NO SUPPORTS ARE ALLOWED IN THIS ZONE.1

0'-0

"

10

'-0

"

CLEAR ZONE, NO SUPPORTS ARE ALLOWED IN THIS ZONE.

1

2

3

11

'-6

"

GALLERY LEVEL

TUNNEL LEVEL

TRENCH LEVEL

SC-LR-1 (TYP.)S-BEND CONDUIT BANK 1. REFER TO 04/T-20 FOR ADDITIONAL INFORMATION.

SC-LR-1 (TYP.)

S-BEND CONDUIT BANK 2. REFER TO 05/T-20 FOR ADDITIONAL INFORMATION.

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

As indicated

T-20

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY SECTIONS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO GALLERY SPACE SECTION 01

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO GALLERY SPACE - ISO VIEW A 02

NOTES:

1. REFER TO 1/T-5 AND 1/T-12 FOR SECTION LOCATION.2. REFER TO 02/T-20 AND 03/T-20 FOR ISO-VIEWS.

KEYNOTES:

1. SUBCONTRACTOR TO PROVIDE SUPPORT AND BRACING TO PREVENT CONDUITS FROM SHIFTING DURING AND AFTER INSTALLATION. SUBCONTRACTOR TO PROVIDE MOCK-UP OF BRACING FOR FRA APPROVAL PRIOR TO INSTALLATION

2. SUBCONTRACTOR TO LIMIT CONDUIT SHIFT WITH ADDITIONAL SEALANT AT PENETRATION3. SUBCONTRACTOR TO PROVIDE BELLED END, FLUSH WITH OPENING. INSIDE EDGE OF BELLED END CONDUIT SHALL BE

GROUND AND BEVELED.

SCALE: N.T.S.

S-BEND CONDUIT BANK 1 - TUNNEL TO GALLERY SPACE 04

SCALE: N.T.S.

S-BEND CONDUIT BANK 2 - TUNNEL TO GALLERY SPACE 05

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO GALLERY SPACE - ISO VIEW B 03

NOTES:

1. (27) 6" S-BEND CONDUITS UP TO GALLERY SPACE WITH 3" SNAP-LOC SPACERS.

NOTES:

1. (15) 6" S-BEND CONDUITS UP TO GALLERY SPACE WITH 3" SNAP-LOC SPACERS.

#

(32) 6" SCHEDULE 40CONDUITS

SC-LR-2(TYP.)5

'-0

"

6'-0

"

7'-0

"

8'-0

"

SC-LR-1

1

TUNNEL LEVEL

BUILDING F37

SC-LR-2(TYP.)

(32) 6" CONDUITS. REFER TO 03/T-21 FOR ADDITIONAL INFORMATION.

SC-LR-1(TYP.)

12

'-8

"

12

'-8

"

SC-LR-1(TYP.)

11

'-6

"

10

'-4

"

10

'-4

"

SC-LR-1

SC-LR-1(TYP.)

SC-LR-1(TYP.)

(4) #4 BARS CONTINUOUS ON TOP AND BOTTOM

6" SCHEDULE 40 PVC

4" MINIMUM COMPACTED AGGREGATE BASE.

#4 TIE BARS AT 3'-0" ON CENTER

INTERMEDIATE SPACER

CONDUIT NONMETALLIC SPACER, MAXIMUM 5' ON CENTER. SNAP LOC S288RJN AND S289RJN SERIES

3" MIN.

3"

MIN

.9.6

4"

6.3

8"

2500 PSI CONCRETE

9.88"

1 1/4" 1 1/4"

9.88" 9.88"

NOTES :

1. INSTALL 2000 lb TENSILE STRENGTH BRAIDED POLYPROPYLENE PULL CORD IN ALL CONDUITS.2. TRENCHING AND BACKFILL ACCORDING TO SPECIFICATIONS.3. DOWEL ENDS OF DUCTBANK TO FOUNDATION OR MANHOLE WITH A MINIMUM OF (4) #4 DOWELS.4. (8) 6" L-BEND CONDUITS UP TO MECHANICAL SPACE WITH 3" SNAP-LOC SPACERS.

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

As indicated

T-21

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY SECTIONS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO BUILDING F37 SECTION 01

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO BUILDING F37 SPACE- ISO VIEW A 02

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO BUILDING F37 SPACE- ISO VIEW B 04

SCALE: N.T.S.

TECHNOLOGY HIGHBAY TO GALLERY SECTION 05

SCALE: N.T.S.

TECHNOLOGY HIGHBAY TO GALLERY SECTION ISO-VIEW A 06

NOTES:

1. REFER TO 1/T-10 FOR ELEVATION LOCATION.2. REFER TO 06/T-21 FOR ISO-VIEW.

NOTES:

1. REFER TO 1/T-9 AND 1/T-15 FOR SECTION LOCATION.2. REFER TO 02/T-21 AND 04/T-21 FOR ISO-VIEWS.

KEYNOTES:

1. SUBCONTRACTOR TO PROVIDE BELLED END AT BOTH ENDS OF CONDUITS, FLUSH WITH OPENING. INSIDE EDGE OF BELLED END CONDUIT SHALL BE GROUND AND BEVELED.

SCALE: N.T.S.

TECHNOLOGY PIT TO HIGH-BAY SPACE ISO-VIEW 07

SCALE: N.T.S.

TECHNOLOGY PIT SPACE ISO-VIEW 08

SCALE: N.T.S.

L-BEND CONDUIT BANK - TUNNEL TO F37 03

11

'-6

"

10

'-4

"

7'-2

"

(12) 4" CONDUITS

SC-LR-1(TYP.)

SC-LR-1(TYP.)

(12) 4" CONDUITS

(12) 4" CONDUITS

7'-0

"

6'-0

"SC-LR-2(TYP.)

SC-LR-2(TYP.)

SC-LR-2(TYP.)

(12) 4" CONDUITS

7'-0

"

SC-LR-2(TYP.)

6'-0

"

8'-0

"

REV. DATE

DESIGNED

CHECKED

APPROVED

SUBMITTED

DRAWN

DRAWING NO.DESCRIPTIONS

REVISIONSREV.

UNITED STATES DEPARTMENT OF ENERGY

NAME DATE

SCALE:

Consulting Engineers550 North Commons Drive Suite 116Aurora, IL 60504

Tel : 630.820.1022Fax: 630.820.0350

Architects11 East Madison Street Suite 300Chicago IL 60602

Tel : 312.456.0123Fax: 312.456.0124

Structural Engineers600 West Van Buren Suite 900Chicago, IL 60607

Tel : 312.341.0055Fax: 312.341.9966

MEP Engineers1100 Warrenville Rd. Suite 400WNaperville, IL 60563

Tel : 630.527.2320Fax: 630.527.2321

Landscape Architects1431 Opus Pl. Suite 400Downers Grove, IL 60515

Tel : 630.724.3200Fax: 630.724.3201

Pre-Construction Contractor55 East Monroe Street Suite 1430Chicago, IL 60603

Tel : 312.327.2770Fax: 312.327.2800 4-3-5

1/2" = 1'-0"

T-22

PIP-II Linac Complex

Fermilab Research Alliance

AA

JE

JK

JOTECHNOLOGY SECTIONS

2021-03-12

2021-03-12

2021-03-12

2021-03-12

202

1-0

3-1

2

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO BTL SECTION01

SCALE: N.T.S.

TECHNOLOGY TUNNEL TO BTL ISO-VIEW A 02

SCALE: N.T.S.

TECHNOLOGY BTL TO TUNNEL SECTION03

SCALE: N.T.S.

TECHNOLOGY BTL TO TUNNEL ISO-VIEW A 04

NOTES:

1. REFER TO 1/T-6 FOR SECTION LOCATION.2. REFER TO 02/T-22 FOR ISO-VIEW.

NOTES:

1. REFER TO 1/T-6 FOR SECTION LOCATION.2. REFER TO 03/T-22 FOR ISO-VIEW.

SCALE: N.T.S.

TECHNOLOGY TUNNEL - BTL 05

As indicated

NOTES:

1. REFER TO 1/T-8 FOR SECTION LOCATION.