AB-6438 © 2012-2017 Azbil Corporation All Rights Reserved. 1 Specifications/Instructions InfilexAC Air Handling Unit Controller for NC-bus Communication General Infilex AC Model WY5117C1XXX is a DDC controller for AHU. It is installed in a small space such as an AHU control panel. Infilex AC is equipped with inputs and outputs suitable for AHU control, and its software is freely editable in response to the applications. Operator interface and room user terminal are connectable to Infilex AC, supporting you in various situations to operate Infilex AC. Infilex AC also is networked with our BMS via our proprietary protocol NC-bus. Infilex AC sends operating status to the BMS and performs operating management in accordance with the commands sent from the BMS in order for you to integrally control and manage a whole building. The time scheduling function of Infilex AC, on the other hand, enables autonomous-distributed control. AHU: Air handling unit BMS: Building management system DDC: Direct digital control Features Compact design: Small sized body fits inside a control panel of a compact AHU. Wide range of input/output (I/O) combinations: Model with the I/O combination best-suitable for the air conditioning controls you desire, such as outdoor air cooling control, humidification, etc. is selectable. Increase in I/O points: An I/O module is added to Model WY5117C140X for increasing the I/O points. Operator interface (Operator Panel): Operator Panel (panel mount type/integral type) connected to Infilex AC allows you to change the settings of Infilex AC without accessing Infilex AC from the BMS. Room user terminals: User terminal (Neopanel or Neoplate) is connectable to Infilex AC, enabling the room occupants to turn on/off air conditioning unit and change temperature setting. Cooperation with BMS: Infilex AC is networked with our BMS to centrally monitor and control AHU. Autonomous distributed control: Even if a trouble occurs in the BMS, Infilex AC individually performs backup operation to distribute potential risks caused by malfunction of the BMS. Installation: Screwless push-in terminals for I/O reduce wiring workload. Additionally, either DIN rail mount or screw mount is selectable. CE Marking certified product: Infilex AC Model WY5117C conforms to all the applicable standards of CE Marking. DIN: Deutsches Institut fur Normung (German Institute for Standardization)

Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

Embed Size (px)

Citation preview

Page 1: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

© 2012-2017 Azbil Corporation All Rights Reserved. 1

Specifications/Instructions

Infilex™ AC

Air Handling Unit Controller for NC-bus Communication

General

Infilex AC Model WY5117C1XXX is a DDC controller for AHU. It is installed in a small space such as an AHU control panel.

Infilex AC is equipped with inputs and outputs suitable for AHU control, and its software is freely editable in response to the applications.

Operator interface and room user terminal are connectable to Infilex AC, supporting you in various situations to operate Infilex AC.

Infilex AC also is networked with our BMS via our proprietary protocol NC-bus. Infilex AC sends operating status to the BMS and performs operating management in accordance with the commands sent from the BMS in order for you to integrally control and manage a whole building.

The time scheduling function of Infilex AC, on the other hand, enables autonomous-distributed control.

AHU: Air handling unit BMS: Building management system DDC: Direct digital control

Features

Compact design: Small sized body fits inside a control panel of a compact AHU.

Wide range of input/output (I/O) combinations: Model with the I/O combination best-suitable for the air conditioning controls you desire, such as outdoor air cooling control, humidification, etc. is selectable.

Increase in I/O points: An I/O module is added to Model WY5117C140X for increasing the I/O points.

Operator interface (Operator Panel): Operator Panel (panel mount type/integral type) connected to Infilex AC allows you to change the settings of Infilex AC without accessing Infilex AC from the BMS.

Room user terminals: User terminal (Neopanel or Neoplate) is connectable to Infilex AC, enabling the room occupants to turn on/off air conditioning unit and change temperature setting.

Cooperation with BMS: Infilex AC is networked with our BMS to centrally monitor and control AHU.

Autonomous distributed control: Even if a trouble occurs in the BMS, Infilex AC individually performs backup operation to distribute potential risks caused by malfunction of the BMS.

Installation: Screwless push-in terminals for I/O reduce wiring workload. Additionally, either DIN rail mount or screw mount is selectable.

CE Marking certified product: Infilex AC Model WY5117C conforms to all the applicable standards of CE Marking.

DIN: Deutsches Institut fur Normung (German Institute for Standardization)

Page 2: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

2

Safety Instructions

Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for ready reference.

Usage Restrictions

This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact our sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators.

Caution for instrumentation design

Considering unexpected failures and contingencies, be sure to design and check safety of the system and equipments.

Warnings and Cautions

WARNING Alerts users that improper handling may cause death or serious injury.

CAUTION Alerts users that improper handling may cause minor injury or material loss.

Signs

Alerts users possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside indicates the specific type of danger. (For example, the sign on the left warns of the risk of electric shock.)

Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside graphically indicates the prohibited action. (For example, the sign on the left notifies that disassembly is prohibited.)

Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside graphically indicates the actual action to be carried out. (For example, the sign on the left indicates general instructions.)

WARNING

Be sure to ground the product with ground resistance of less than 100 Ω. Improper grounding might cause electric shock or malfunction.

Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover. Failure to do so might cause electric shock.

Before wiring and maintenance, be sure to turn off the power to the product. Failure to do so might cause electric shock.

Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel) Failure to do so might cause electric shock.

CAUTION (1/2)

Install the product in a location that satisfies the operating conditions (temperature, humidity, power, vibration, shock, mounting direction, atmospheric condition, etc.) as listed in the specifications and use the product within the operating ranges as listed in the specifications. Failure to do so might cause fire or device failure.

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

All wiring must comply with applicable codes and ordinances.

Connect the cables to the product power supply terminals with the terminal lugs or an equivalent method to assure permanent connection.

To connect the wires to the screw terminals, use crimp terminal lugs with insulation. Failure to do so might cause short circuit or electric shock.

Page 3: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

3

CAUTION (2/2)

Take anti-lightening measures based on regional and building characteristics. Lightening might cause fire or critical damage to the products without the anti-lightening measures.

Take anti-noise measures if the product is installed in a location near electric noise sources. Failure to do so might cause malfunction or device failure.

Be sure to provide a circuit breaker for the power to the product as the product does not have a power switch.

Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating.

For wiring, strip each wire insulation for the length specified in this manual. If the strip length is longer than the specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent terminals. If it is shorter, the stripped part will not contact the connector.

Do not use unused/spare terminals on the product as relay terminals. Doing so might cause malfunction.

Do not block the ventilation holes of this product. (Be sure to peel off the protective sheet after installation and wiring).Doing so might cause device failure.

If more than the rated power voltage is applied to the product, replace the product with new one for your safety. Failure to do so might cause fire.

Do not disassemble the product. Doing so might cause device failure.

When replacing batteries, read the instructions hereinafter and correctly replace the product batteries.

Failure to do so might cause overheating, burst, or leakage of the batteries.

Dispose of the used batteries in accordance with your local regulations. Do not throw them in fire or in general garbage. Doing so might cause burst or ignition.

Dispose of this product as industrial waste in accordance with your local regulations. Do not reuse all or a part of this product.

Page 4: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

4

System Configurations

For BMS and devices that are compatible to Infilex AC, ask our salesperson.

Figure 1. System configuration example

Other connectable devices to NC-bus: DIF-II/Energy meter

BACnet IP

BMS: Building management system DIF-II: DGP (Data Gathering Panel) line interface-II

Client PC

Infilex GC Model WY5111

Infilex GDModel WY5110

NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)

Infilex FC Model WY5205

SC-bus (Max. 50 units and 1000 m)

Neopanel Model QY7205

Infilex FC Model WY5205

Temperature sensor

Temperature sensor

NeoplateModel QY7290

Infilex ZMModel WY5122

Temperaturesensor

Neopanel Model QY7205

Temperaturesensor

Infilex VCModel WY5206

SC-bus (Max. 50 units and 1000 m)

Infilex ZM Model WY5122

Infilex VCModel WY5206

Neopanel Model QY7205

Neopanel Model QY7205

Infilex FC Model WY5205

NeopanelModel QY7205

Infilex FC Model WY5205

Infilex VC Model WY5206

Neoplate, Model QY7290

Operator Panel(Panel mount type)

Model QY5100

UT module Model RY5001Q

Infilex AC Model WY5117C

Neopanel Model QY7205

Operator Panel(Panel mount type)

Model QY5100

UT moduleModel RY5001Q

Infilex ACModel WY5117C

Neopanel Model QY7205

Operator Panel(Integral type)

Model RY5001Q

Infilex ACModel WY5117C

Neoplate Model QY7290

Operator Panel(Integral type)

Model RY5001Q

Infilex AC Model WY5117C

BMS

Page 5: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

5

Model Numbers

Base model number

Power — I/O Temperature

input Description

WY5117 Infilex AC for NC-bus communication

C 24 V AC

1 Fixed

1 Temperature input: 2 pts, voltage input: 2 pts, digital input: 4 pts, voltage output: 2 pts, relay output: 3 pts, 1 UT module or Operator Panel (integral type) connectable*1, *2

2 Temperature input: 2 pts, voltage input: 2 pts, digital input: 4 pts, voltage output: 3 pts, relay output: 4 pts, 1 UT module or Operator Panel (integral type) connectable*1, *2

3 Temperature input: 2 pts, voltage input: 2 pts, digital input: 6 pts, voltage output: 5 pts, relay output: 5 pts, 1 UT module or Operator Panel (integral type) connectable*1, *2

4 Temperature input: 2 pts, voltage input: 2 pts, digital input: 8 pts, voltage output: 6 pts, relay output: 6 pts, 1 UT module or Operator Panel (integral type) + 1 I/O module connectable*1, *2

00 RTD (Pt100) 0K RTD (Pt1000)

Notes: *1 UT module, Operator Panel (integral type), and I/O module are optional. Separately order if needed. *2 Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to

AB-6527 Specifications/Instructions of Model RY50XX.

Parts for Installation (Optional)

Part number Description

83165861-001 Screw tab 83104567-001 DIN rail mounting bracket

Page 6: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

6

Specifications (1/2)

Item Specification

Power supply Rated voltage 24 V AC ± 15 %, 50 Hz/60 Hz Power shutdown detection

Max. 19.2 V AC

Power consumption 15 VA Leakage current 1 mA or less

Environmental conditions

Rated operating conditions

Ambient temperature 0 C to 50 C Ambient humidity 10 %RH to 90 %RH (non-condensing) Altitude Max. 2,000 m Vibration Max. 5.9 m/s2 (10 Hz to 150 Hz)

Transport/ storage conditions

Ambient temperature -20 C to 60 C Ambient humidity 5 %RH to 95 %RH (non-condensing) Vibration for storage Max. 5.9 m/s2 (10 Hz to 150 Hz) Vibration for transport Max. 9.8 m/s2 (10 Hz to 150 Hz)

Installation Inside of control panel LED indication (Operating status LED)

After Infilex AC is turned on, the LED operates as follows in response to the Infilex AC operating status.

Power ON ON for several tens of seconds Power OFF OFF Major failure or initializing ON Minor failure Repetition of 1-second ON, 0.25-second OFF, 0.25-seccond ON, and

0.25-second OFF Engineering mode Repetition of 0.25-sec ON, 0.25-second OFF, 0.25-second ON, and

1.25-second OFF Data transmitting Repetition of 1-second ON and 1-second OFF NC-bus error Repetition of 0.25-second ON and 0.25-second OFF

Backup in the event of power failure RAM*1, RTC*2 Lithium battery backup Data file Non-volatile memory (flash memory) backup

Input Digital input Current 5 mA typ. Voltage 24 V DC typ. Connectable output Dry contact or open collector Allowable contact ON-resistance

Max. 100 Ω

Allowable contact OFF-resistance

Min. 100 kΩ

Allowable ON residual voltage

Max. 1 V DC

Temperature input

Input signal RTD (Pt100 (100 Ω/0 C), Pt1000 (1000 Ω/0 C)) Measuring range -20 C to 80 C

Voltage input Input voltage range 1 V DC to 5 V DC Input impedance 500 kΩ

Output Relay output (N.O. contact)

Output method Relay output N.O. contact (N.O. contacts share the same common line.) Contact rating Max. 24 V AC, 0.5 A (Inductive load: cosø = 0.4 or more)

Max. 24 V DC, 0.5 A Minimum applicable load 5 V DC, 10 mA DC

Relay output (N.O./N.C. contact)

Output method Relay output, N.O./N.C. contact (N.O./N.C. contact does not share the common line with N.O contact.)

Contact rating Max. 24 V AC, 0.5 A (Inductive load: cosø = 0.4 or more) Max. 24 V DC, 0.5 A

Minimum applicable load 5 V DC, 10 mA DC Voltage output Output voltage range 2 V DC to 10 V DC / 0 V DC to 10 V DC

Min. load resistance Min. 10 kΩ Communications NC-bus Transmission system Current transmission

Transmission speed 4800 bps Transmission distance 500 m

Weight 500 g Material (housing), color Modified PPE, light gray Terminal connection Power supply, ground M3 screw terminals (7.62 mm pitch between terminals)

NC-bus communication, I/O Screwless push-in terminals

PPE: Polyphenylene ether RAM: Random-access memory RTC: Real-time clock Notes: *1 RAM: A form of data storage that can be accessed directly in any random order. Stored data is erased when the power is turned off. RAM

of Infilex AC is backed up by a lithium battery. *2 RTC: A computer clock that keeps track of the current time. RTC of Infilex AC is backed up by a lithium battery.

Page 7: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

7

Wire Specifications

Item Wiring Wiring length*1 Condition

Power supply*2 JIS IV2.0 mm2 or JIS CVV 2.0 mm2 or greater Ground*2 JIS IV 2.0 mm2 or JIS CVV 2.0 mm2 or greater Ground resistance: Max. 100 Ω Digital input*3 JIS IV, JIS CVV, or KPEV 0.9 mm2, 1.25 mm2 50 m Relay output*3 JIS IV, JIS CVV, or KPEV 1.25 mm2 50 m Max. 30 V AC/DC Temperature input*3, 4 JIS IV, JIS CVV, or KPEV 1.25 mm2 50 m Voltage input*3 JIS IV, JIS CVV, or KPEV 0.9 mm2, 1.25 mm2 50 m Voltage output*3 JCS CVV-S 1.25 mm2 20 m Inverter output

JIS IV, JIS CVV, or KPEV 1.25 mm2 10 m Valve/damper (for the system common wiring*5)

JIS IV, JIS CVV, or KPEV 2.0 mm2

(from the relay terminal block) 20 m

JIS IV, JIS CVV, or KPEV 1.25 mm2 20 m Valve/damper Communication (NC-bus)*3

JCS IPEV-S 0.9 mm2 500 m

JCS: Japanese Electric Wire & Cable Makers' Association Standard JIS: Japanese Industrial Standards KPEV: Cable standard provided by Furukawa Electric Co., Ltd. Notes: *1 Wiring length shown above is the total wiring length from Infilex AC to a device in connection, including the wiring to and from an external

terminal block. *2 Power supply and ground wires are connected to the M3 screw terminals. Crimp the terminal lugs on the wire ends. *3 Communication and input/output wires are connected to the screwless push-in terminals. Strip the wire sheath and connect the wires.

Sheath strip length: 8 mm (Pin terminal cannot be used.) *4 RTD (Pt1000) temperature input is two-wire. Take the measuring error into account because the wire resistance causes measuring error.

For instance, 1.25 mm2 size wire causes approx. 0.1 °C measuring error every 10 m. Correct the measuring error by setting Infilex AC. *5 When the valve/damper is connected for the system common wiring, the valve/damper operating current flows through the common line.

Hence, the specification is as shown above. For a 20 m long IV 1.25 mm2 cable, 4-wire connection is necessary to prevent the operating current from flowing through the common line.

Page 8: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

8

Terminals Layout

Notes: *1 Other items that satisfy input/output specifications of Infilex AC are connectable as well. For available inputs and outputs of each Infilex AC

model, refer to Table 1. *2 RTD (Pt100) temperature input is three-wire. Connect Pt100 temperature sensor to the terminals 13 –15 or 16 –18.

RTD (Pt1000) temperature input is two-wire. Connect Pt1000 temperature sensor to the terminals 13 and 14 or 16 and 17.

Figure 2. Terminals layout with I/O connection example

Table 1. Applicable inputs/outputs for each model number

Model number AI1 to AI4

AO1, AO2

AO3 AO4 AO5 AO6DI1 to DI4

DI5,DI6

DI7,DI8

DO1,DO2

DO3 DO4 DO5 DO6

WY5117C110X WY5117C120X WY5117C130X WY5117C140X*

Note: * For an I/O module that can be added to Model WY5117C1400, refer to AB-6527 Specifications/Instructions of Model RY50XX.

S

S

Fan ON/OFF

Fan ON/OFF

Humidifier

Outdoor air damper

Return air temperature

Supply air temperature

Return air humidity General-purpose

voltage input

I/O connection example*1

Supply air fan status Supply air fan alarm Return air fan status Return air fan alarm

Filter alarm Water-leak alarm

General-purpose input General-purpose input

Hot water valve or

Chilled/hot water valve Chilled water valve

Outdoor air damper or

Exhaust air damper Return air damper

Fan inverter

Fan inverter or Proportional humidifying

Temperatureinput*2

(-20 to 80 °C)

Voltage input(1 to 5 V)

Voltage output (2 to 10 V/ 0 to 10 V)

NC-bus

24 V AC

Relay output(for momentary only)

(24 V AC/DC)

Relay output(for momentary/maintained)

(24 V AC/DC)

Digital input Current: 5 mA Voltage: 24 V DC applied from Infilex AC

I/O connection example*1

Page 9: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

9

Dimensions

Figure 3. Dimensions (mm)

Parts Identifications

Table 2. Indication and operation of the operating status LED

LED indication LED operation

Data transmitting Repetition of 1-second ON and 1-second OFF

NC-bus error Repetition of 0.25-second ON and 0.25-second OFF

Major failure / initializing

ON

Minor failure Repetition of 1-second ON, 0.25-second OFF, 0.25-second ON, and 0.25-second OFF

Engineering mode Repetition of 0.25-second ON, 0.25-second OFF, 0.25-second ON, and 1.25 -second OFF

Power OFF OFF

Figure 4. Parts identifications

60 90

140

DIN rail mounting hook

Operating status LED

Battery holder

Data Setter connector (female)

S1 switch Do not press the S1 switch.

Page 10: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

10

Installation

CAUTION

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

Installation locations

Install Infilex AC in a control panel.

Do not mount Infilex AC under the conditions of high temperature and humidity.

Leave at least 35 mm clearance between the top/bottom surface of Infilex AC and other devices.

Mounting position

Do not mount Infilex AC with the body tilted. Always mount it in the positions as shown in the figure below. No other mounting positions are allowed.

Upright

Sideway (allowed only when I/O module, UT module, or integral type Operator Panel is NOT assembled with the basic unit)

Note: * Do not mount the Infilex AC basic unit sideway with the power supply terminals located upper corner, lying on its back, or lying face down.

Figure 5 Mounting positions

Do not tilt. Do not tilt.

Vertical (upright) direction

Power supply terminalslocated on the lower corner

of the front face Vertical (upright) direction

Page 11: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

11

DIN rail mount

The following figure shows the mounting dimensions of Infilex AC on DIN rail. The width may vary depending on how many modules (I/O module, UT module, and integral type Operator Panel)*1 are assembled with the Infilex AC basic unit.

Width of Infilex AC = 60 mm*2 + 30 mm*3 x n (quantity)

Notes: *1 Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to

AB-6527 Specifications/Instructions of Model RY50XX. *2 Width of Infilex AC basic unit *3 Width of I/O module, UT module, or integral type Operator Panel

Hatched area in the figure below shows the maintenance clearance.

Notes: *1 Pitch between upper/lower cable duct and the DIN rail. *2 Up to two modules (I/O module and/or UT module/integral type Operator Panel) can be assembled with the basic unit. *3 DIN rail position is shifted 5 mm downward from the center of Infilex AC.

Figure 6. Mounting dimensions (mm): DIN rail mount

Mount and fix Infilex AC on DIN rail so that it does not fall from the DIN rail. Check that the DIN rail holders of each module are pushed up and fixed on the DIN rail. Fasten the bilateral sides of Infilex AC with two DIN rail mounting brackets (Part No. 83104567-001, separate order is required).

DIN rail mounting brackets for bilateral sidesPart No. 83104567-001

Cable duct

Cable duct

Infilex AC

(45)

3

5

140

(45)

(122

.5)*

1

(

132.

5)*1

Cable duct

202092

(60)

(60)

Cable duct

65

75

35

DIN rail holder

Infilex AC basic unit

DIN rail

Infilex AC

60 + 30 n

Hook

5*3

106

*2

Page 12: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

12

Direct screw mount

The following figure shows the mounting dimensions of Infilex AC mounted directly on a mounting surface with screws. The width may vary depending on how many modules (I/O module, UT module, and integral type Operator Panel)*1 are assembled with the Infilex AC basic unit.

Width of Infilex AC = 60 mm*2 + 30 mm*3 x n (quantity)

Notes: *1 Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to

AB-6527 Specifications/Instructions of Model RY50XX. *2 Width of Infilex AC basic unit *3 Width of I/O module, UT module, or integral type Operator Panel

Hatched area in the figure below shows the maintenance clearance.

Note: * Up to two modules (I/O module and/or UT module/integral type Operator Panel) can be assembled with the basic unit.

Figure 7. Mounting dimensions (mm): Direct screw mount

To mount Infilex AC with screws, the screw tabs (Part No. 83165861-001, with separate order required) are required. Mount and fix Infilex AC on the mounting surface with M4 8 screws. (One screw tab and two screws for one basic unit/module are required.)

DIN rail holder Pull down the DIN rail

Screw tab Part No.

Rear side

Screw

20 20

30 45 30

35

140

157

To attach the screw tab, insert the screw tab intothe slit provided on therear side of Infilex AC.

Infilex AC

60 + 30 n

Insert.

* See Note.

Page 13: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

13

Wiring

WARNING

Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover. Failure to do so might cause electric shock.

Before wiring and maintenance, be sure to turn off the power to the product. Failure to do so might cause electric shock.

CAUTION

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

All wiring must comply with applicable codes and ordinances.

Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating.

For wiring, strip each wire insulation for the length specified in this manual. If the strip length is longer than the specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent terminals. If it is shorter, the stripped part will not contact the connector.

Do not use unused/spare terminals on the product as relay terminals. Doing so might cause malfunction.

Do not block the ventilation holes of this product. (Be sure to peel off the protective sheet after installation and wiring).Doing so might cause device failure.

Precautions for wiring

Tube marker:

Since Infilex AC adopts the screwless push-in terminals, wires are connected without crimping terminal lugs. Therefore, if normal tube markers are used, they may come off when you disconnect the wires. To prevent this, use the following Flat Tube Marker. It is held on a wire by friction and thus does not come off easily.

Flat Tube Marker Manufacturer Phoenix Contact Item number 5880029 Model TMC-3 Applicable wire size 0.4 mm2 to 2 mm2 Package unit 200 m/roll

2 mm2 cable running outside the control panel: Use an external terminal block to switch to 1.25 mm2 cable inside the control panel.

Two wires for one terminal: Use an external terminal block to aggregate the wires.

Fan ON/OFF: Use a small-power circuit (max. 60 V operating voltage and 1.5 A operating current) to turn on and off fan.

Signal wire for output to inverter: Use a shielded cable.

Power supply wiring

Crimp M3 terminal lugs with insulation on the wire ends, and connect the wires to the power supply terminals.

Figure 8. Power supply wiring

Power supply wiresPower supply

terminals

1

2

3

Connect.

Page 14: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

14

Wiring to I/O and NC-bus terminals

The I/O and NC-bus wires are connected to the screwless push-in terminals of Infilex AC. Follow the procedure below for the I/O and NC-bus wiring.

1) Strip the wire sheath 8 mm. Note: * Scale for the strip length is indicated on the front surface of Infilex AC basic unit. If the insulation stripped part is longer than 8 mm, it

may get exposed, causing electrical shock or short circuit between adjacent terminals. If it is shorter, it may not contact the terminal connector.

2) Make sure that no wire fiber goes out of the wire end.

3) Press the button on the terminal block deeply enough using a slotted screwdriver and insert the wire. (Maximum button-pressing force is 23 N.) Then, release the button.

4) Gently pull out the wire horizontally to make sure that it is completely held by the clamp and check no wire fiber being disconnected from the terminal.

Note: * If you pull out the wire diagonally, it may be disconnected.

Arrangement of the wires connected to Infilex AC

Notes: * Neatly place the wires using cable ties or the like so as not to hide LED, Data Setter connector, mark of Data Setter connector, S1 switch,

battery holder, and indication tag. * Do not leave slack in the wires that run between the cable duct and Infilex AC. * Sideway mounting shown in the figure above is allowed only when I/O module, UT module, or integral type Operator Panel is NOT

assembled with the basic unit. Do not mount the Infilex AC basic unit sideway with the power supply terminals located upper corner, lying on its back, or lying face down. Always install the basic unit assembled with an I/O module, and/or UT module/integral type Operator Panel in upright position.

Figure 9. Arrangement of the wires connected to Infilex AC

LED

Data Setter connector

S1 switch

Battery holder

Indication tag

(Infilex AC mounted sideway with the power supply terminals located on the lower corner.

Page 15: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

15

Precautions for Wiring of Infilex AC and Devices

System common wiring

Ground line () is used as a common line for signal transmission to/from the field devices. For the system common, the common-mode power must be supplied to Infilex AC and each device (such as ACTIVAL™) via the wires connected to "~" and "" terminals of Infilex AC and each device. For the signal transmission between Infilex AC and each device, use "" wiring.

Figure 10. Wiring example: System common wiring

IMPORTANT:

Use an isolation transformer. Do not ground the secondary side of the transformer.

Provide a terminal block aright ahead of the transformer, and divide the line at the terminal block to connect to each device. (See Fig. 10.)

Inverter

Figure 11. Wiring example: Inverter

IMPORTANT:

Shielded cable must be single-point grounded on the inverter.

24 V AC

Inverter

From From

+

-

Infilex AC

Terminal block for branching

Infilex AC

ACTIVAL or damper actuator

ACTIVAL or damper actuator

+-

+-

Page 16: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

16

Humidity sensor

Figure 12. Wiring example: humidity sensor

IMPORTANT:

If Infilex AC and a humidity sensor are powered by a single transformer, the sensor might get damaged. Depending on the other connected devices and on the wiring condition, a short-circuit current may flow into the sensor and into the Infilex AC.

Precautions for Use

Before supplying the power

Check that the all the wires are correctly connected.

Remove the protective sheet from the top surface of Infilex AC. Note: * if some foreign objects possibly come inside Infilex AC from the ventilation holes on the side and bottom surfaces, cover the ventilation

holes with sheets.

Figure 13. Protective sheet

Several tens of seconds are required for the Infilex AC normal operation after the power is turned on. During this time, the red LED on the front stays ON temporarily, but this does not indicate an error.

Humidity sensor

+

-

24 V A

C

Infilex AC

2) Tear off.

1) Peel off the adhesive area.

Page 17: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

17

Connection of our engineering tool (Data Setter / PC-MMI)

Connection of Data Setter Model QY5111B No conversion cable is required. Directly insert the male connector of the Data Setter into the female connector provided on the Infilex AC basic unit. At this time, hold the male connector with the mark facing left and insert it so that the mark points to the mark on the Infilex AC basic unit.

Connection of Data Setter Model QY7211B Convert the D-SUB connector to the mini DIN connector with the conversion cable (Part No. 83104995-001). At this time, hold the male connector with the mark facing left and insert it so that the mark points to the mark on the Infilex AC basic unit.

Figure 14. Connection of our engineering tool

System indication label for the controller number

The indication tag has the system indication label on its back. Turn it over and fill in the controller number on the label.

Figure 15. System indication label

Insert the maleconnector as the twomarks point to each

other.

Turn over.

Indication tag

Page 18: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

18

Maintenance (Lithium Battery Replacement)

CAUTION

When replacing batteries, read the instructions hereinafter and correctly replace the product batteries.

Failure to do so might cause overheating, burst, or leakage of the batteries.

Dispose of the used batteries in accordance with your local regulations. Do not throw them in fire or in general garbage. Doing so might cause burst or ignition.

IMPORTANT:

Only authorized service personnel is allowed to replace the battery.

Do not touch the power supply unit when replaceing the battery.

Replace the lithium battery every 5 years if the product is always in use (in ON state).

Since the remaining battery level cannot be checked by measuring the terminal voltage, be sure to replace the battery every 5 years.

Replace the lithium battery with the power ON.

If the product has never or hardly been operated (in OFF state) for a year, replace the lithium battery before the product operation.

Battery replacement

1) Pull out the battery holder using a slotted screwdriver.

2) Disconnect the connector and detach the lithium battery from the battery holder.

3) Place a new lithium battery in the battery holder and connect the connector.

4) Insert the battery holder into the basic unit.

5) Fill in the date for next replacement (5 years after the replacement) on the indication tag using an oil-based pen.

Figure 16. Battery replacement

3)

2)

Infilex AC basic unit

Lithium battery for backup

Battery holder Battery Connector

1)

4)

5)

Page 19: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

19

Blank page added for page editing purpose.

Page 20: Infilex AC Air Handling Unit Controller for NC-bus ... · Air Handling Unit Controller for NC-bus Communication ... BMS: Building management system ... be sure to design and check

AB-6438

ACTIVAL and Infilex are trademarks of Azbil Corporation in Japan or in other countries. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

20

AB-6438Rev. 9.0 Jul. 2017

Install this product in a panel cabinet.

This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive (EMCD) and the Restriction of the use of certain Hazardous Substances in Electrical and Electronic Equipment Directive (RoHSD).

EMCD: EN 61326-1 Class A, Table 2 (for use in an industrial electromagnetic environment)

RoHSD: EN 50581