41
Technical University of Denmark Professor Bjarne W. Olesen, Ph.D. Department of Civil Engineering Technical University of Denmark Indoor Air Quality and Thermal Comfort in Zero Energy Buildings

IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

  • Upload
    lamtu

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Technical University of Denmark

Professor Bjarne W. Olesen, Ph.D.

Department of Civil Engineering

Technical University of Denmark

Indoor Air Quality and Thermal Comfort in

Zero Energy Buildings

Page 2: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

COMFORT-PRODUCTIVITYBuilding costs

People 100

Maintenance 10

Financing 10

Energy 1

Page 3: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Achieving Excellence in Indoor Environmental Quality

• Physical factors– Thermal Comfort

– Air quality (ventilation)

– Noise-Acoustic

– Illumination

• Personal factors– Activity

– Clothing

– Adaptation

– Expectation

– Exposure time

Page 4: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Energy Efficient Technologies

• Indoor air quality

– Reduce loads (pollution sources)

– Natural ventilation

– Air distribution (contaminant removal) effectiveness

» Personal ventilation

– Air cleaning

• Thermal comfort– Reduce loads (building shell, solar screen, internal loads)

– Low Temperatur Heating- and High Temperature Cooling Systems

– Use of building mass (Thermo-Active-Building-Systems (TABS))

– Drifting temperatures

Page 5: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

MINIMIZE

Primary Energy UseIndoor Environmental Quality

WILL NOT WORK WITH ZERO

ENERGY BUILDINGS

Page 6: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Required energy for heating in residential buildings kWh / (m² . a)

220 130 54 30 00

50

100

150

200

250

300

Older

houses

1982 1995 2000 future

270

180

10070

22

kW

h/(

m².

a)

Low energy buildings will be standard !

Ventilation

TRANSMISSION

19%

28%

46%

85%

Page 7: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

STANDARDS

• ISO EN 7730-2005 – Ergonomics of the thermal environment – Analytical determination and

interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort effects.

• ASHRAE 55-2004– Thermal environment conditions for human occupancy

• ASHRAE 62.1 and 62.2 -2004– Ventilation and indoor air quality

• CR 1752– Ventilation of buildings-Design criteria for the indoor environment

• EN 13779– Ventilation for non-residential buildings - performance requirements for

ventilation and room-conditioning systems

Page 8: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

EN15251 (CEN TC156 WG12)Indoor environmental input parameters for design and assessment of energy performance of buildings- addressing

indoor air quality, thermal environment, lighting and acoustics

Page 9: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

CRITERIA FOR LIGHTING

Daylight factor, 2-5%, Ra colour rendering index

Page 10: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Indoor System Noise Criteria

Noise from

outside by

natural

ventilation?

Page 11: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Categories

Category Explanation

I High level of expectation and is recommended for spaces occupied

by very sensitive and fragile persons with special requirements

like handicapped, sick, very young children and elderly persons

II Normal level of expectation and should be used for new buildings

and renovations

III An acceptable, moderate level of expectation and may be used for

existing buildings

IV Values outside the criteria for the above categories. This category

should only be accepted for a limited part of the year

Page 12: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Cate

gory

Thermal state of the body as a

whole

Local thermal discomfort

PPD

%

Predicted

Mean Vote

Draught

Rate,

DR

%

Vertical air

tempe-

rature

difference

%

Warm

or

cool

floor

%

Radiant

Tempe-

rature

Asymmetry

%

I < 6 -0.2 < PMV < + 0.2 <10 < 3 < 10 < 5

II < 10 -0.5 < PMV < + 0.5 <20 < 5 < 10 < 5

III < 15 -0.7 < PMV < + 0.7 <30 < 10 < 15 < 10

IV > 15 PMV<-0.7; or 0,7<PMV >30

Recommended categories for design of mechanical heated and cooled buildings

Page 13: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Temperature ranges for hourly calculation of cooling and heating energy in three

categories of indoor environment

Type of building/ space

Category Operative Temperature for

Energy Calculations oC

Heating (winter

season), ~ 1,0 clo

Cooling (summer

season), ~ 0,5 clo

I 21,0 – 23,0 23,5 - 25,5

II 20,0 – 24,0 23,0 - 26,0

Offices and spaces with

similar activity (single offices, open plan offices,

conference rooms,

auditorium, cafeteria, restaurants, class rooms,

Sedentary activity ~1,2 met III 19,0 – 25,0 22,0 - 27,0

Page 14: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

LOCAL THERMAL DISCOMFORT

• FLOOR SURFACE TEMPERATURE

• VERTICAL AIR TEMPERATURE DIFFERENCE

• DRAUGHT

• RADIANT TEMPERATUR ASYMMETRI

Page 15: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

DRAUGHT

• MEAN AIR VELOCITY

• TURBULENCE

• AIR TEMPERATURE

DRAUGHT RATING, DR= (34-ta)(v-0.05)0.62(0.37 v Tu + 3.14)

International Centre for Indoor Environment And Energy

Page 16: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Parameter

Distance from cold

surface

Formular

Unit

Min. Air temperature at the

floor

x tmin = tRaum – (0,30 – 0,034*X)(tRaum –

tFläche )

°C

x<0.4 m 5,0

max 055,0 httv FlächeRaum m/s

0,4<x< 2,0 5.0

max32,1

095,0htt

Xv FlächeRaum

m/s

Max. air velocity at the floor

2,0<x 5.0

max 028,0 httv FlächeRaum m/s

Calculated values for the air movement at the floor (Heiselberg 1994) for

two-dimensional (Window- = Room width)

Page 17: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

DOWN DRAUGHT

0

0,05

0,1

0,15

0,2

0,25

0,3

0,35

0,4

0,45

0 1 2 3 4 5 6 7

Height m

Air

velo

cit

y

m/s

U-Value

4.0

3.0

2.0

1.5 W/m2K

1.2

1.0

0.6

0.4

0.2

Outside Temperatur -12 0C

Page 18: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

RADIANT TEMPERATURE ASYMMETRY

• HEATED CEILING: < 5 oC

• COOLED CEILING: < 14 oC

• WARM WALL: < 23 oC

• COOL WALL: <10 oC

Page 19: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

UNIFORMITY OF OPERATIVE TEMPERATURE DISTRIBUTION

• to,warm - to,cold < 4 K

• to,warm - to,cold ~ 1,0 x Uw

• Uw < 4 W/m2K

Page 20: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

RADIANT TEMPERATURE ASYMMETRY

tpr,warm - tpr,cold < 10 K

• tpr,warm - tpr,cold ~ 4,0 x Uw

•Uw < 2,5 W/m2K

Page 21: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

THERMAL COMFORT

• VERTICAL AIR TEMPERATURE DIFFERENCE ta BETWEEN HEAD AND FEET:

< 3 oC (ISO EN 7730)

• SEATED PERSON:1.1 m and 0.1 m above floor level

Page 22: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,
Page 23: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

FLOOR TEMPERATURE

• SEATED/STANDING PERSONS: 19 °C < ts < 29 °C

• BY HIGHER ACTIVITY LEVELS A LOWER FLOOR TEMPERATURE IS ACCEPTABLE

International Centre for Indoor Environment And Energy

Page 24: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

SELF CONTROL

80

W/m?40

W/m?20

W/m?10

W/m?Heat load

Floortemperature

Heat. level temp. tiles

Heat. level temp. carpet

38,4

29,4

24,9

22,5

31,9

26,2

23,3

21,7

27,3

23,9

22,121,120

22242628303234363840

Floortemperature at 20 °C Roomtemperature

Page 25: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

FLOOR TEMPERATURE

Floor construction on concrete Optimum floortemperature

Recommended floortemperature range °C

1 min.°C

10 min.°C

1 min.10%

dissatisfied

10 min.15%

dissatisfied

Wilton-carpetNeedled felt sheet

5 mm corkWooden floor

PVC-sheet with felt underlay

Painted concrete floorConcrete floor

Marble

2123

2426.5

28

3028.5

30

24.525

2625.5

27

28.527

29

12-30.515.5-31

17-3122-31.5

24.5-32

27.5-32.524.6-32.0

27.5-32.5

21-2822.5-28

23-2823-28

25.5-28

27.5-2926-28.5

28-29.5

Page 26: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

CONTROL OF ROOM TEMPERATURE

• Drifting temperature– OK within the comfort range

• Air temperature – Operative temperature– Less difference in zero energy buildings

• Individual room control– May be less important for energy use

– Still important for thermal comfort (bed room, living room)

Page 27: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Concept for calculation of design ventilation rate

People Component Building Component

Breathing Zone

Outdoor Airflow

Minimum

l/s/Person

Number of

People

Ventilation

per Smoker

Minimum

l/s/m²

Building Area

Vbz = RpPz + RsSd + RaAz

Number of

Smokers

Page 28: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Breathing zone outdoor airflow (Vbz),

• Vbz = RpPPz + RaAAz

• where:– Az = Zone floor area: the net occupiable floor area of the zone m2

– Pz = Zone population: the largest number of people expected to occupy the zone during typical usage.

– RPp = Outdoor airflow rate required per person: these values are based on non-adapted (adapted) occupants.

– RAa = Outdoor airflow rate required per unit area.

Page 29: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Recommended ventilation rates for non-residential buildings for three categories

Type of

building or

space

Cate-

gory

Per person

l/s,person

Per floor

area

l/s,m2

Per person

l/s,person

Per floor

area

l/s,m2

Per person

l/s,person

Per floor

area

l/s,m2

Very low polluted

building, revision

Low polluted building,

revision

Non-low polluted

building, revision

Single office I 5,0 1,5 10,0 2,0 20,0 3,0

II 3,0 1,0 7,0 1,4 14,0 2,1

III 2,0 0,6 4,0 0,8 8,0 1,2

Landscaped

office

I 7,5 1,5 15,0 1,7 30,0 2,7

II 4,5 1,0 10,5 1,2 21,0 1,9

III 3,0 0,6 6,0 0,7 12,0 1,1

Conference

room

I 1,0 1,5 2,0 6,0 4,0 7,0

II 0,6 1,0 1,4 4,2 2,8 4,9

III 0,4 0,6 0,8 2,4 1,6 2,8

Page 30: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Residential buildings

Category Air change

rate 1)

Living room and

bedrooms, mainly

outdoor air flow

Exhaust air flow, l/s

l/s,m2

(1)

ach l/s, pers2)

(2)

l/s/m2

(3)

Kitchen

(4a)

Bathrooms

(4b)

Toilets

(4)

I 0,49 0,7 10 1,4 28 20 14

II 0,42 0,6 7 1,0 20 15 10

III 0,35 0,5 4 0,6 14 10 7

Page 31: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Required ventilation rate

• The total required system ventilation rate is calculated by taking into acount the ventilation effectiveness:

• Total system ventilation rate = V/εv

v

Page 32: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Ventilation effectiveness

Page 33: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Inhaled Air Quality

Veff 1 Veff 1.4 (6)

Page 34: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Ventilation effectiveness

Page 35: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Studies of heating systems

Page 36: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Studies of heating systems

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Page 37: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Vertical air temperature profile

0

0.5

1

1.5

2

2.5

20 21 22 23 24

he

igh

t [m

]

air temperature [ºC]

Temp. profile_syst1-case3-occupied zone

0

0.5

1

1.5

2

2.5

20 21 22 23 24

he

igh

t [m

]

air temperature [ºC]

Temp. profile_syst1-case5-occupied zone

System 1 (ach=0.5 h-1, internal gains=100 W) in the occupied zone

warm air heating, radiant floor heating

Page 38: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

WARM AIR HEATINGContaminat Removal Effectiveness

CRE as a function of air flow rate for a combination of mixing

ventilation and warm air heating, with internal gains of 90 W (cases 3,

4 and 7). The curves represent average in the occupied zone

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Supply air

Exhaust air

Window

heating floor

System 1 System 2 System 3

System 4 System 5 possible additional System with floor heating

Supply air

Exhaust air

window

heating floor

System 1 System 2 System 3

System 4 System 5

Page 39: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Indoor Air Quality and Thermal Comfortin

Zero Energy Buildings• Thermal Comfort

– More uniform conditions (radiant asymmetry, vertical air temperature differences)

– Less draught risk (reduced heat supply, no cold surfaces)

– Less difference between air and operative temperature

– Is individual room control important?

» Comfort

» Energy

• Indoor Air Quality– Tighter buildings

– Cannot rely on infiltration

– Can you heat with the ventilation system?

» Air distribution

» Ventilation effectiveness

» Individual room control

Page 40: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Indoor Air Quality and Thermal Comfortin

Zero Energy Buildings

If an energy efficient measure also improve the indoor environment

it will lower health risk and increase productivity

and always be cost efficient.

Page 41: IndoorAir Quality and Thermal Comfort in Zero Energy Buildings · for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment,

Occupant behaviourand

Energy Consumption• Simulation study:

– Occupant behaviour can affect energy consumption by more than 300 %

• Literature survey

– In identical dwellings, the highest energy consumption is typically 2-3 times as high as the lowest

– Differences as high as 600 % has been observed