Upload
others
View
8
Download
0
Embed Size (px)
Citation preview
PRICE BID
Indian Institute Of Technology, Bombay (Maharashtra)
TENDER DOCUMENT
For
Refurbishment of P.C. Saxena Auditorium inside the campus of
IIT Bombay, Powai, Mumbai – 400 076
BILL OF QUANTITIES
Tender Number : P.C.Sax/Reno/IITB/DC/02-2014
Date: 18th March, 2014
203-204 | Prabhadevi Industrial Estate |
Veer Savarkar Marg | Prabhadevi |
Mumbai 400 025 | India
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
SR. NO. ITEM DESCRIPTION AMOUNT
I SUB STRUCTURE WORKS
II FINISHING WORK
III PLUMBING WORK
IV FIRE ALARM SYSTEM & PUBLIC ADDRESS SYSTEM
V ELECTRICAL WORK
VI HVAC WORK
SUMMARY
TOTAL OF (I+II+III+IV+V+VI)
TENDER DOCUMENT BILL OF QUANTITIES SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
SR. NO. ITEM DESCRIPTION AMOUNT (RS.)
I SUB STRUCTURE WORKS
TOTAL OF EXCAVATION & EARTH WORKS
TOTAL OF PLAIN CEMENT CONCRETE
TOTAL OF REINFORCED CEMENT CONCRETE
TOTAL OF SUB STRUCTURE WORKS
II FINISHING WORK
TOTAL OF STEEL & ROOFING WORK
TOTAL OF DEMOLITION WORK
TOTAL OF BRICK WORK
TOTAL OF PLASTERING / PUNNING WORK
TOTAL OF FALSE CEILING WORK
TOTAL OF FLOORING, SKIRTING & DADO WORK
TOTAL OF PAINTING WORK
TOTAL OF DOOR WORKS
TOTAL OF WOOD WORKS (PARTITION & PANELLING)
TOTAL OF ALUMINUM WINDOW WORK
TOTAL OF MISCELLANEOUS WORKS
TOTAL OF FINISHING WORK
ITEMWISE SUMMARY
TENDER DOCUMENT BILL OF QUANTITIES SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
III PLUMBING WORK
TOTAL OF SANITARYWARES & CP APPURTENANCES
TOTAL OF WATER SUPPLY SYSTEM
TOTAL OF INTERNAL DRAINAGE SYSTEM
TOTAL OF PLUMBING WORK
IV FIRE ALARM SYSTEM & PUBLIC ADDRESS SYSTEM
TOTAL OF FIRE ALARM SYSTEM
TOTAL OF CABLES & ACCESSORIES
TOTAL OF FIRE ALARM SYSTEM & PUBLIC ADDRESS SYSTEM WORK
V ELECTRICAL WORK
TOTAL FOR POINT WIRING IN PVC CONDUIT, TELEPHONE WIRING,
T.V WIRING ETC.
TOTAL OF LIGHT FIXTURES AND FITTINGS, CEILING FANS, EXHAUST
FANS ETC
TOTAL FOR POWER POINT WIRING
TOTAL FOR UPS SYSTEM
TOTAL OF DISTRIBUTION BOARDS
TOTAL FOR L.T.CABLES, END JOINTS
TOTAL OF EARTHING SYSTEM
TOTAL OF ELECTRICAL WORK WORK
VI HVAC WORK
GRAND TOTAL OF (I+II+III+IV+V+VI)
TENDER DOCUMENT BILL OF QUANTITIES SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
GENERAL IMPORTANT NOTES APPLICABLE TO THIS CONTRACT
(APPLICABLE TO CIVIL, FINISHING, PHWORKS, FIRE FIGHTING, ELECTRICAL WORKS, IBMS & HVAC WORKS)
1
2
3
4
5
The approach road should be kept clean & free from obstructions for smooth functioning of existing traffic and damages caused any to be
made good without any extra cost to the IITB.
Tenderer's are advised to acquaint themselves with access to site, location of work, local labour problems and any other matter relating to
availability and carriage of construction materials.
Signature of tenderer with Date & seal:
e) Security Regulations & rules of I.I.T, and its constituent units shall be strictly followed while movement/ deployment of materials & work
forces and Cost arising due to security regulations.
g) Scaffolding to be provided for execution , shall be of Independent Scaffold Conforming to IS 2750 -latest revision.
h) Safety of Labours working at site shall be as per safety code enclosed in the specifications and to be strictly adhered by employing
safety engineer.
Cement for structural works shall be OPC/PPC ISI marked and duly approved by the Engineer-in-charge
PPC/blended cement of ISI marked shall only be used for finishing works on prior approval of Engineer-in-charge
Refurbishment of P.C. Saxena Auditorium inside the campus of IIT Bombay, Powai Mumbai 400 076
In addition to Clause 3.5.2 of Special Conditions of Contract Rate quoted for the items shall also be inclusive of
a) The tenderer shall provide barricade consisting of MS angle/pipe posts runners, bracing & corrugate GI sheet for a height up to 3m to
separate the working area, maintaining the barricade in good condition including removing the same after completion of the work without
any cost to IITB.
b) Statutory traffic regulations inforce shall be considered for transporting material, labour etc and nothing shall be paid extra on account
of the restrictions imposed by the local statuary authorities. Royalty charges for excavation and transporting earth , debris, and other
materials
c) Transporting of material ,labour , machinery etc to all heights & including locations of where direct access is non existing and
including arranging own arrangement
TENDER DOCUMENT BILL OF QUANTITIES - 1 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
I SUB STRUCTURE WORKS
A EXCAVATION & EARTH WORKS
1 Earth work excavation by mechanical means / labour means for foundation pits,
trenches etc. in all types of soils other than soft and hard rock up to depths
mentioned below including shoring, dressing the sides, trimming, ramming and
preparing the bed for foundation and disposing of the surplus earth within a
distance of 150 meters etc. complete as per specifications, drawings & as directed
by the EIC.
1.1 Depth not exceeding 1.50 m. from ground level. Cum 80.00
2 Disposing off the surplus excavated materials by mechanical transport lead up to
2 KM to the nearby dumping pits/ dumping areas with in IITB campus identified by
Engineer in charge , including all lifts, loading, unloading, stacking etc. complete
as per specifications & as directed by the EIC.
2.1 All type of Soil Cum 40.00
3 Refilling around basement, foundation and in plinth with available murrum /
excavated earth / Demolished structure debris / selected earth approved by
Engineer-in-charge excavated from nearby borrow areas including all leads up to 2
Km, lifts, loading, unloading, stacking, leveling, spreading, in layers not exceeding
150 mm thick, watering, compaction to give 95% proctor density etc. complete as
per specifications, drawings & as directed by the EIC.
Cum 25.00
4 Supplying and spreading pesticides CHLORPYRIPHOS or other chemical
approved by central insecticides Board as directed by the manufacturer and
spraying the mixture uniformly by sprayer as pre-construction anti- termite
treatment at the rate of 7.5 liters (or as directed by the manufacturer ) per sqm on
vertical and 5 liters. per sqm on horizontal surfaces of the sub-structure, within the
trenches, 50% of the emulsion to be filled in the holes made in trenches at 150
mm center to center etc. complete all as per IS 6313 Part-II(latest) specification
& as directed by the Engineer-in-charge. (The payment will be made on the basis
of plinth area measurement only aground floor/stilt area for all stages of operation
and vertical faces will not be measured for payment).
The contractor shall have to furnish ten years guarantee in the prescribed Performa
(Appendix 'E') to maintain the anti-termite treated area /structure free from termite.
Sqmt 15.00
5 Providing and laying dry rubble stone hard core soling of 230mm consolidated
thickness in sub base to floor and in plinth protection to required levels and lines
with first quality rubble, hand set, well packed including filling the interstices with
smaller stone chips, supplying & finishing/blinding the surfaces with approved
blinding quality murrum including watering, consolidation etc. complete as per
specifications, drawings & as directed by EIC.
5.1 230 mm thick with contractor supply of stone Sqm. 20.00
TOTAL OF EXCAVATION & EARTH WORKS
B PLAIN CEMENT CONCRETE
6 Providing and laying of plain cement concrete as leveling course for foundation,
basement, vertical surfaces of soil retention system and all locations depth with
Ready Mixed Concrete conforming to IS 4926 (latest revision) Plain cement
concrete grade M : 15 conforming to IS 456-2000 as per specifications
manufactured in fully automatic batching plant and transported to site of work,
having continuous agitated mixer, manufactured as per mix design of specified
grade for Plain cement concrete work , including lead from manufacturer site to site
of work, pumping of R.M.C from transit mixer to site of laying, cost of admixtures in
recommended proportions as per IS 9103 (latest) to accelerate / retard setting of
concrete, improve workability without impairing strength and durability, mechanical
conveying, placing in position mechanical compaction, finishing, curing, scaffolding
including necessary form work, consolidation, finishing, curing etc. complete as
per specifications ,drawings and as directed by the Engineer-in-charge.
TENDER DOCUMENT BILL OF QUANTITIES - 2 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
(Note :- 1) Prior approval of Engineer in charge for the supplier of RMC to be
taken.
2) On prior approval of Engineer-in-charge Fly ash conforming to Grade I of IS
3812 (Part I) may be used as part replacement of OPC provided uniform blending
with cement is ensured in accordance with Clauses 5.2 and 5.2.1 of IS 456 - 2000
in the items of BMC and RMC)
6.1Foundation Plain cement concrete of Grade M-15
Cum 12.00
TOTAL OF PLAIN CEMENT CONCRETE
C REINFORCED CEMENT CONCRETE
7 a) All RCC shall be as specified and shall be carried out strictly in accordance
with the drawings and specifications.
b) The rates for RCC works shall be inclusive of all depths below G.L slabs at
all heights as detailed in the drg but exclusive of cost of reinforcement unless
otherwise mentioned.
c) All coarse aggregate to be 20 mm maximum size and uniformly graded
unless otherwise mentioned.
d) For all RCC items, the rates quoted shall include the following without any extra
cost to the Dept.
i) Spacers to maintain clear cover for reinforcement.
ii) Fixing at correct level & in proper alignment the inserts, pipe sleeves, pipe
bends, fan hooks, other pipe specials etc. supplied by Department or Contractor
unless otherwise mentioned in a separate item
iii) Test for concrete shall be done as per IS 456-2000 and the cost of the testing
to be carried out shall be borne by the contractor.
d) Precaution to be taken to avoid uplifting forces on the raft of water tanks.
As per the soil report, water table is expected near the ground level and contractor
is advised to use following sequence during concreting of the water tank.
1) Dewatering to keep the area dry during construction.
2) Plum concrete to be completed as shown in the drawing.
3) Backfilling in layers and compaction for full height of the backfill as directed by
the EIC, over the raft projection.
4) Keeping the tank filled with water for at least half the depth.
Reinforced cement concrete of M-20 grade of design mix concrete conforming to IS
456-2000, at all depth & location and levels using graded stone aggregate of
20mm. and down graded including machine mixing, conveying, placing in position,
mechanical consolidation, finishing, curing, scaffolding, dewatering if necessary
complete all as per drawing & specifications, but excluding the cost of form work
and steel reinforcement (which shall be paid under relevant item)
7.1 For RCC work for all structural Members such as Raft , foundations , all types of
Walls, Columns, Beams , Waffle beams, Slabs, Staircases , Pardis, drop pardis ,
parapets, chajjas, niches etc of any shapes, sizes , thickness and depths etc.
Grade of concrete :- M20
(Note :- Rate inclusive of all shapes, sizes, curves, slopes, thickness and depths
at all heights etc and No extra payment for shall be payable.)
Cum 12.00
TENDER DOCUMENT BILL OF QUANTITIES - 3 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
8 Providing, erecting, fixing in position striking / removing and cleaning steel /
plywood or any other approved material shuttering and centering for formwork in
substructure at all depths for all geometrical shapes, as per details shown in
drawings and as required for specific design of formwork wherever specified,
including proper bracing, ties, anchors, bolts, nuts, washers, packing plates,
fasteners of adequately designed capacities, producing finished concrete surfaces.
at all locations including chamfers, splays, keys, wedges, props, rails, bracings,
brackets, cutting holes if specified for pipes etc. providing and applying approved
form oil on all surfaces of formwork coming in contact with concrete including close
hacking of all exposed concrete work wherever required to receive other type of
finishing after removal of form work, all materials, labour etc.complete as per
specifications, drawings and as directed by the Engineer-in-Charge. (Area of
formwork in contact with concrete shall only be measured for payment and stop
boards for construction joints will not be measured for payment). Note : - Prior
approval of Engineer - in - charge to be obtained for clearance of form work for
laying RCC.
For Foundation Area
8.1 Foundations, footings, bases of columns, etc. for mass
concrete and Raft.
Sqm. 5.00
8.2 Columns of any size and shape. Sqm. 15.00
8.3 Lintels, beams, girders, bressumers and cantilevers etc complete. Sqm. 15.00
8.4 Suspended floors, roofs, landings, balconies and access platform. Sqm. 35.00
9 Reinforcement for RCC work including supplying, delivering and storing of various
diameters as required at site of work transporting, decoiling, straightening, cutting,
bending, placing in position at all depths, levels and binding with 18-20 gauge,
soft drawn locations annealed steel binding wire complete as per specifications and
drawings. (Cost of binding wire shall be borne by the contractor & binding wire
shall not be measured for payment. Rate includes cost of tests of materials by
Contractor as specified in the Specifications and IS) and preparing and obtaining
prior approval of bar bending schedule .
9.1 Thermo Mechanically Treated bars of grade Fe-415 manufactured by
recommended list of manufacturers conforming to IS 1786 - latest revision as per
specifications of works and drgs.
MT 1.50
TOTAL OF REINFORCED CEMENT CONCRETE
TOTAL OF SUB STRUCTURE WORKS
II FINISHING WORK
General Notes
a) Unless otherwise specified all individual items are deemed to include the cost of
required single or double scaffolding, staging as required and contractor shall not
be entitled for any extra/ separate compensation on account of the same.
b) The contractor shall provide at their own cost temporary tarpaulin screens for the
entire duration of the contract to cover the works under execution to avoid
spreading / flying of dust to the adjoining buildings/ areas.
TENDER DOCUMENT BILL OF QUANTITIES - 4 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
c) 43/ 53 grade cement to be used in masonry / plaster / wet cladding / flooring
works shall be of approved make and in compliance with technical specifications.
Sand and stone aggregates shall be from approved source and in compliance with
the technical specifications.
d) The materials required for the following works shall be sorted out as per the
manufacturing dates & batches, approved samples & shades. Prestacking,
handling, rehandling, transporting within the site, stacking & protection of materials
approved and rejected materials (rejected materials shall be replaced), confirming
the net quantities selected for use. No extras shall be paid for all above and the
contractor shall allow for all such eventualities in the construction time period. No
material/ samples including their makes/ brands shall be procured/ appointed/
subcontracted for mock up or for execution as the schedule of quantities without
the prior approval of the client / Architect.
A STEEL & ROOFING WORK
Preparing shop drawings, obtaining consultant's approval, supplying, fabricating,
delivering at site, hoisting and fixing in position including all temorary staging and
supporting work and making all structural steel work in accordance with the design,
drawings prepared by the consultants. the rate of steel work shall include 1 coat of
red oxide primer and 2 coats of enamal paint assembly, welding, jointing, building
up new sections using plates / rolled section,/chs/rhs cost of fasteners , nuts, bolts
and washers), pre-heating the sections to temperatures up to 250ºC if thickness of
the section is equal to or more than 25mm.and fabrication out of the following types
of structural steel material for trusses, purlins, girders, brackets, etc. with
connections using plates, channels and angles, gusset plate, connection bolts,
cleats, fasteners etc. as per drawing, steel conforming to IS:226 and IS:2062-Gr.A
with minimum yield strength of 335 Mpa for plates. (Fasteners,welding electrodes,
consumables will not be paid seperately. Rates inclusive of necessary tests as per
technical specification)
10 For Deck slab, roof extension including cols trusses purlins, extension of existing
members , site welding etc
MT 6.75
11 Rebaring by using various diameter 12mm to 25mm. Dia, hilti make chemical (Re-
500) max.depth 300 mm.
each 40.00
12 Providing & Fixing in position Metal Decking Sheets ( Tata Bluscope/ inter arch
roofing/ raj mohan roofing 0.7mm thk smart deck 51 @ 6.56 kg/sqm ) for
supporting RC Slab including eadge trims cutting, trimming, fixing, leak proffing of
joints etc. complete.
Sqm. 30.00
13 Providing & fixing STUD type shear connector 12mm dia Thermomechanically
fixed,
each 50.00
14 Providing & fixing in position 12mm thk. of Shalitex board at various joints such as
isolation joints at wall edge, and column junctions and sealing with Winsil-20
neutral base sealent manufactured by GE Silicon , as per manufacturer's
requirements ,etc. complete,
Sqm. 5.00
15 Providing and fixing in position Bare Galvalume sheets for Roof & Colour Coated
Galvalume Sheet for Cladding, including providing necessary laps, Flashing
pieces, self tapping screws , EPDM washers, seam bolts, stitch rivets at overlap
and all other hardware, scaffolding Etc.Complete.
Sqm. 300.00
16 Same as item 15 above above using j hooks Sqm. 25.00
17 Providing and fixing in position GI gutter made from 1.22mm thick a GI
sheet,moulded to shape as per detail drawing approximately 300mm wide and
average 300mm deep laid to slope all as per design. Including treating the joints
with rubber & watrerproofing compound etc. complete.
Rmt. 35.00
18 Providing & fixing in position flashing at the junction of roof sheet and existing wall Rmt. 32.00
19 Providing & fixing Hilti make anchor bolts (mechanical) Kg 20.00
TENDER DOCUMENT BILL OF QUANTITIES - 5 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
20 Providing, fabricating and fixing 1020 mm high Bright MS railing (Bright steel
conforming to IS : 226 and IS : 2062 with minimum yield strength of 250 Mpa
and upto 500 Mpa ) for balcony as per architectural drawing and instructions.
The system shall be consist with 100mm x100mm and 8mm thick base plate fixed
in RCC member with anchor bolt ( 3/8 size) c/c as per site condition and given the
drawing. The verticale meber shall be consist with 65 mm nominal bore medium
section and 1020 mm height Ms pipe welded to base plate properly as per
architectural drawing with 3nos. 65 mm nominal bore medium section ms
horizontal pipe including hand rail pipe @ 303 mm c/c properly, including
necessary hardware, anchor bolt, cutting, grinding, machining, assembly, welding,
jointing, drilling, grouting and cleaning etc. completed as per the instructions of
EIC/ Architect Rate also included providing and applying one coat epoxy primer
of MRF or equivalent and finish the railing with two coates of approved quality
enamel paint of MRF or equivalent etc. completed
Kg 1615.00
21 Non shrink grout of FOSROCK Make GP 2, under side of base plates etc Cum 1.00
TOTAL OF STEEL & ROOFING WORK
B DEMOLITION WORK
22 Dismantling, Demolishing, Cutting, Breaking, Removing & Cleaning Existing Items
Carefully and Stacking the Materials at site or as Instructed including necessary
tool, tackles, machineries, requisite scaffolding, carting away debris from site time
to time or disposing the material as directed and specified by the Architect / Client
for the following Items. (The rate shall include all leads, lift and height)
22.1 Removing of existing Flooring in Green rooms, and Prefunction area etc. including
bedding materials. (Refer Drw. No. I-200, I-201, I-202)
Sqm. 190.00
22.2 Removing of existing windows including window frames (Refer Drw. No. I-200, I-
201, I-202)
Sqm. 45.00
22.3 Removing of existing Doors including door frames (Refer Drw. No. I-200, I-201, I-
202)
Sqm. 45.00
22.4 Remove and salvage door for refurbishment & refixing (Refer Drw. No. I-200, I-
201, I-202)
Sqm. 10.00
22.5 Removing of existing partitions on stage (Refer Drw. No. I-200, I-201, I-202) Sqm. 50.00
22.6 Removing existing internal plaster with racking out the masonry joints. (Refer Drw.
No. I-200, I-201, I-202)
Sqm. 585.00
22.7 Removing of existing Ms Grill,ventilators,aluminium frame ,glass with fixtures etc
(Refer Drw. No. I-200, I-201, I-202)
Sqm. 15.00
22.8 Providing and doing core cutting in RCC slab at given location as per architectural
instructions inluding necessary tools and machinaries, scaffolding, watering, rate
also included carting away the debris from site time to time or disposing the
material as directed and specified by the Architect / Client (Refer Drw. No. A-200)
Sqm. 5.00
22.9 Removing of existing internal 100 mm thick brick work for green room partion.
(Refer Drw. No. I-200, I-201, I-202)
Sqm. 40.00
22.10 Removing of existing internal 150 mm thick brick work for green room partion.
(Refer Drw. No. I-200, I-201, I-202)
Sqm. 10.00
22.11 Removing of existing internal 230 mm thick brick work for green room partion.
(Refer Drw. No. I-200, I-201, I-202)
Sqm. 5.00
22.12 Removing of existing wooden box for Duct in post Function (Refer Drw. No. I-200,
I-201, I-202)
Sqm. 15.00
22.13 Removing of existing counter pre function area (Refer Drw. No. I-200, I-201, I-
202)
Rmt. 5.00
22.14 Removing of existing curtains with pelmet in Auditorium (Refer Drw. No. I-200, I-
201, I-202)
Sqm. 125.00
22.15 Removing of existing foundation stone and salvage with extreme care in pre
function and post function area (Refer Drw. No. I-200, I-201, I-202)
each 2.00
22.16 Removing existing IPS in Auditorium area. (Refer Drw. No. I-200, I-201, I-202) Sqm. 245.00
22.17 Removing of existing screen with accessories & fittings (Refer Drw. No. I-200, I-
201, I-202)
Sqm. 50.00
TENDER DOCUMENT BILL OF QUANTITIES - 6 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
22.18 Removing of existing grid false ceiling with supports, framings, light fittings etc.
(Refer Drw. No. I-200, I-201, I-202)
Sqm. 375.00
22.19 Removing of existing push back chairs (Refer Drw. No. I-200, I-201, I-202) each 399.00
22.20 Removing of existing roof with structural memebers in post function area. (Refer
Drw. No. I-200, I-201, I-202)
Sqm. 205.00
22.21 Removing of existing corrugated sheet in post function area (Refer Drw. No. I-200,
I-201, I-202)
Sqm 370.00
22.22 Removing of existing electical wirings, cables, fittings, boards, switches etc. (Refer
Drw. No. I-200, I-201, I-202)
Job 1.00
22.23 Making cut outs in RC wall, with supporting steel frame etc Edge prepation to
receive steel frame etc.. (str.steel frame qty, & anchor bolts, item will be paid
separetly in respective items (Refer Drw. No. A-200)
Cum 5.00
22.24 Removing of existing mosaic flooring in Auditorium (Refer Drw. No. I-200, I-201, I-
202)
Sqm. 155.00
22.25 Removing of Wash basin with tap,bottle trap with all fixtures & supports. (Refer
Drw. No. I-200, I-201, I-202)
each 2.00
22.26 Removing of existing Storage with all fixtures in Green room. (Refer Drw. No. I-
200, I-201, I-202)
Sqm. 10.00
22.27 Removing of panel in post function area (Refer Drw. No. I-200, I-201, I-202) Sqm. 20.00
22.28 Removing the existing stage flooring & sub base for flooring to place subwoofers of
approximate size 650mm x 650mm x 450mm and making good the same after
placing the subwoofers with capping using hard wood floor matching to the existing
stage flooring etc complete as per the drawings and instructions of Engineer - In -
Charge
Nos. 2.00
TOTAL OF DEMOLITION WORK
C BRICK WORK
23 Providing & doing well Burnt Brick masonary in all location with conventional type
bricks in cement mortar 1:4 in superstructure including striking joints, racking out
joints, watering, scaffolding and cleaning etc. complete Rate also included
providing & laying cast in situ rcc patali in M:150 at 1200mm c/c with 2nos 8mm dia
reinforcement including shuttering, deshuttering,curing, cleaning etc. completed at
all heights and satifaction to the EIC/ Architect.
23.1 150mm thick brick work in superstructure (Refer Drw. No. I-210, I-211, I-213, I-
600A, I-600B, I-601,I-602A, I-602, I-603A, I-603B, I-605A, I-605B,I-607A, I-607B, I-
701, I-703, I-706, I-830)
Sqm. 15.00
23.2 100mm thick brick work in superstructure (Refer Drw. No. I-210, I-211, I-213, I-
600A, I-600B, I-601,I-602A, I-602, I-603A, I-603B, I-605A, I-605B,I-607A, I-607B, I-
701, I-703, I-706, I-830)
Sqm. 100.00
23.3 230mm thick brick work in superstructure (Refer Drw. No. I-210, I-211, I-213, I-
600A, I-600B, I-601,I-602A, I-602, I-603A, I-603B, I-605A, I-605B,I-607A, I-607B, I-
701, I-703, I-706, I-830)
Sqm. 35.00
24 Providing & Constructing Uncoursed rubble masonry of trap stones in cement
mortar 1:6 in foundations and plinth ramp including through stones, corner
stones, pointing etc. including bailing out water, striking joints on exposed
faces and watering complete
Cum 75.00
TOTAL OF BRICK WORK
D PLASTERING / PUNNING WORK
TENDER DOCUMENT BILL OF QUANTITIES - 7 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
25 Providing and applying avg. 12mm thk. (avg.) single coat internal plaster in
cement sand mortar (1:4) for all plain / curved surfaces of brick / block / RCC
walls and finishing the same (smooth or broom) in correct line, level & plumb,
making of edges, corners, sill, jambs, soffits, grooves, pattas etc. as per drawings
& relevant specifications including all necessary surface preparation, scaffolding,
p/f of PVC chicken mesh of approved quality at all junctions of RCC & masonry
work, hacking of concrete surface to receive plaster, watering, curing, cleaning etc.
complete at all levels and heights. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-
600B, I-601,I-602A, I-602, I-603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-
605A, I-605B, I-606, I-607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-
830)
Sqm. 585.00
26 Providing and applying avg. 8mm thk. (avg.) single coat internal plaster in
cement sand mortar (1:4) for all plain / curved Ceiling surfaces and finishing the
same (smooth or broom) in correct line & level, making of edges, corners, sill,
jambs, soffits, grooves, pattas etc. as per drawings & relevant specifications
including all necessary surface preparation, scaffolding, hacking of concrete
surface to receive plaster, watering, curing, cleaning etc. complete at all levels and
heights. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-602A, I-602, I-
603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-605B, I-606, I-
607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-830)
Sqm. 10.00
27 Providing and applying avg. 13mm thk( avg.) POP plaster to walls using
approved quality POP as per IS 2547-1976, over all plain / curved surfaces of brick
/ block / RCC and to be finished smooth in correct line, level & plumb, making of
edges, corners, sill, jambs, soffits, pattas etc. as per drawings & relevant
specifications including all necessary surface preparation, making level pads
(Dada), scaffolding, hacking of surface to receive plaster, cleaning etc. complete at
all levels and heights. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-
602A, I-602, I-603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-
605B, I-606, I-607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-830)
Sqm. 125.00
28 Providing and applying avg. 6mm thk. (avg.) POP to ceiling using approved
quality pop as per IS 2547,1976 for all plain / curved surfaces, pattas finished
smooth in correct line & level including all necessary surface preparation, making
level pads (Dada), scaffolding, hacking of surface to receive plaster, cleaning etc.
complete as per relevant working drawings & specifications at all levels and
heights. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-602A, I-602, I-
603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-605B, I-606, I-
607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-830)
Sqm. 10.00
29 Providing & laying POP of sufficient thickness over plastic sheets as a protective
layer for flooring during the work including all maintenance, p/l plastic sheets,
removing & disposing POP after the use, cleaning, etc. complete at all floors & as
directed by the EIC. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-
602A, I-602, I-603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-
605B, I-606, I-607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-709, I-830)
Sqm. 45.00
30 Providing and making Grooves of approved shape and size in POP at various
locations viz.above skirting, around the door & window frame,above dado or
wherever required as per the
drawing including finishing of groove in correct line and level, making of moulds
(farmas), cleaning, scaffolding etc. complete at all heights & floors. (Refer Drw.
No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-602A, I-602, I-603A, I-603B, I-
604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-605B, I-606, I-607A, I-607B, I-701,I-
702, I-703, I-705A, I-705B, I-706, I-830)
30.1 Groove up to 6 mm (Depth – 6mm) Rmt. 130.00
30.2 12mm groove (Depth – 6mm) Rmt. 40.00
30.3 16mm groove (Depth – 6mm) Rmt. 5.00
30.4 25mm groove (Depth – 12mm) Rmt. 5.00
TOTAL OF PLASTERING / PUNNING WORK
E FALSE CEILING
General Note
TENDER DOCUMENT BILL OF QUANTITIES - 8 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
a) All types of false ceiling shall be inclusive of side profile, coves, grooves,
finishing etc.
Providing & fixing suspended false ceiling using 12.5mm thick Gypsum boards
confirming to IS 2095-1982 and GI framework of Gyp steel or approved equivalent
as per architectural drawing and instructions comprising of following.
1. GI perimeter channel of 0.55mm thick having one flange of 20mm, another of
30mm and web of 27mm fixed to brick wall partition along periphery of ceiling with
the help of nylon sleeves and screws at 610mm c/c
2. GI intermediate channel of size, 45mm web, two flanges each of 15mm &
thickness 0.9mm ) suspended from the soffit / ceiling at 600mm c/ c spacing.
3. GI ceiling sections of 0.55mm thick having knurled web of 51.5mm and two
flanges each of 26mm with leaves of 10.5mm fixed to intermediate channel with the
help of connecting clip at direction perpendicular to the intermediate channel at
spacing of 600 mm c/c,
4. GI suspender angle of 25mmx10mm and thk.0.55mm at spacing of 600mm c/c,
fixed to the ceiling / soffit using GI cleat angle 25mm x 25mm, 0.55mm thk. Cleat
angle to be fixed to the ceiling / soffit using 6mm dia anchor fastener.
Gyp boards with tapered edges to be screwed to the framework with 25mm long GI
screws at 230 mm c/c. Screw fixing shall be done mechanically. Gyp boards are to
be joined and finished so as to have a flush look which includes filling and finishing
the tapered and square edge of the boards with gypsum roller net tape & approved
quality joining compounds. The work also includes vertical drops, curvature,
providing & making farma cutting of gyp boards & frame work and providing cutouts
/ openings and additional supports wherever required for the fixing of ceiling
fixtures like, lights, A.C grills, sprinklers, smoke detectors etc.
Refer Drw. No. I-210, I-211, I-213 I-300A, I-602A, I-602B, I-603A, I-603B, I-703, A-
202, A-501, A-502, I-830
(Mode of measurements : Only plan are of ceiling shall be measured for
payment)
32 Do as per item No.31 but for Gypsum patta in various sizes for ceiling.
Refer Drw. No. I-210, I-211, I-213, I-300A, I-602A, I-602B, I-603A, I-603B, I-703,
I-830
Mode of measurements : Only running length of patta shall be measured for
payment)
32.1 Up to 50mm wide patta. Rmt. 5.00
32.2 Above 50mm and up to 100mm patta. Rmt. 5.00
32.3 Above 100mm and up to 150mm patta. Rmt. 5.00
32.4 Above 150mm and up to 200mm patta. Rmt. 5.00
32.5 Above 200mm and up to 250mm patta. Rmt. 5.00
32.6 Above 250mm and up to 300mm patta. Rmt. 25.00
32.7 Above 300mm patta. Sqm. 10.00
31 55.00 Sqm.
TENDER DOCUMENT BILL OF QUANTITIES - 9 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
33 Providing and fixing Decosonic CNBM MgO board false ceiling which includes G.I
perimeter channels of size 0.55mm thk. (having one flange of 20mm and another
flange of 30mm and a web of 27mm) along with perimeter of ceiling screw fixed to
brick wall/partition with the help of nylon sleeves and screws, at 610mm centers
Then suspending G.I intermediate channels of size 45mm (0.9mm thk. With two
flanges of 15mm each) from the sofit at 1220mm centers with ceiling range of
width 25mm x10mmx0.55mm thk fixed to sofit with G.i cleat and steel expansion
fasteners celling section of 0.55 mm thk having knurled web of 51.5mm and two
flanges of 26mm each with lips of 10.5 mm are then fixed to the intermediate
channel with the help of connecting clip and in direction perpendicular to the
intermediated channel at 457mm centers Decosonic CNBM board of thickness
12mm is then screw fixed to ceiling section with 25mm drywall screws at 230mm
centers screw fixing is to be done mechanically either with screw driver or drilling
machine with suitable attachment.The boards shall have Moisture Absorption 6.8%
after 2 hours and 11.3% after 24 hours soaking,Wet expansion < 0.02% from
ambient to saturation,Dry Contraction < 0.02% from ambient to
evaporation.STRENGTH-Compressive Strength - 27.3 N/mm2,Flexural Strength -
10.87 N/mm2,Tensile Strength - 3.38 N/mm2,FIRE-Fire Resistance < 180 minutes
under 1200°C,BS476 Part 4 - Non-combustible,Thermal Conductivity - 0.11792
W/m0K, with Green Building application. (Mode of measurements : Only plan
area of ceiling shall be measured for payment)
Sqm. 170.00
34 Do as per item No. 33 but for CNBM MgO board patta in various sizes for ceiling.
Refer Drw. No. I-210,I-211, I-213, I-300A, I-600B, I-700, I-830 (Mode of
measurements : Only running length of patta shall be measured for
payment)
34.1 Up to 50mm wide patta. Rmt. 10.00
34.2 Above 50mm and up to 100mm patta. Rmt. 40.00
34.3 Above 100mm and up to 150mm patta. Rmt. 10.00
34.4 Above 150mm and up to 200mm patta. Rmt. 10.00
34.5 Above 200mm and up to 250mm patta. Rmt. 30.00
34.6 Above 250mm and up to 300mm patta. Rmt. 15.00
34.7 Above 300mm patta. Sqm. 15.00
35 Providing & fixing Accoustical Fabric Ceiling for Auditorium false ceiling as per
architectural drawing and instructions. The system shall be comprise with following
Frame work - Providing and doing and fixing 16 guage 50 x 38 mm aluminum
frame for outer peripheri of false celing and P/f 16 guage 50 x 50mm aluminum
frame @ 600 mm c/c both direction, entire frame shall be fixed to main ceiling with
GI cleat angle 25mm x 25mm, 0.55mm thk. Cleat angle to be fixed to the ceiling /
soffit using 6mm dia anchor fastener @ 6000mm c/c. P/f ply frame made out of
12mm thick 75mm patta @ 600mm c/c both direction. the frame shall be fixed to
aluminum frame properly. The accoustical false ceiling is at different level and in
shall be 150mm overlapped to each other and 12mm thick 200mm wide
commercial ply vertical patta fixed between two celing as per architectural
drawings Accoustic/ Fabric - Providing and fixing 40mm thick (Density 12 kg/cum
and NRC Value 0.8) foam of Basotect or any other approved make fixed in
aluminum framework with 12 guage 38mm GI wire mash properly. Entire frame
work shall be finished with rapping approved color fabric (Bharat Furnishing -
Premium shade - 24293 - Sr. No. 6 Munar Silk / Decotex - VRN 817). Fabric
should be fixed properly, avoid bubbles/ looseness in fabric as per architectural
drawings and instructions including making the . Cut out for light fixtures &
providing necessary GI frames to hang the same independently all necessary
hardware, scaffolding, cutting, drilling, screwing and cleaning etc. Completed at all
levels and heights and as specified by EIC/ Architect. Both sides vertical pattas of
false ceiling at longitudinal direction and end support shall be included in the rate.
(Mode of measurements : Only plan area of curve ceiling shall be measured
for payment)
Sqm. 200.00
TENDER DOCUMENT BILL OF QUANTITIES - 10 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
36 Providing and fixing 20mm thick Black Straw board of Anutone or any other
approved make. ( Strand square edge magnesite bonded wood fiber panels of size
600x600x20mm having density 400kg/m3, weight 8kg.) for auditorium celing. The
panels shall be fixed directly to existing rcc ceiling with screw properly as per
architectural drawing and instruction. including necessary hardware, scaffolding,
drilling, cuting, filling the screw holes with putty or any other filler material and
finish the holes with paint matching to straw board andcleaning etc. completed at at
all levels and heights and as specified by EIC/ Architect Refer Drw. No. I-210,I-
211, I-213, 1-300A, I-300B, I-604A, I-604B, I-604C, I-604D,I-604E, I-704, I-830
(Mode of measurements : Only plan are of ceiling shall be measured for
payment)
Sqm. 210.00
37 Providing and making Grooves of approved shape and size in Gypsum/ MGO
Ceiling at various locations viz. above skirting, around the door & window frame,
above dado or wherever required as per the drawing including finishing of groove in
correct line and level, making of moulds (farmas), cleaning, scaffolding etc.
complete at all heights & floors. (Refer Drw. No.I-210, I-211, I-213 1-300A, I-
300B, I-604A, I-604B, I-604C, I-604D,I-604E, I-704, I-830)
37.1 groove up to 6 mm Rmt. 10.00
37.2 12mm groove Rmt. 10.00
37.3 19mm groove Rmt. 10.00
37.4 25mm groove Rmt. 65.00
TOTAL OF FALSE CEILING WORK
F FLOORING, SKIRTING & DADO WORK
Note:
1) White marble and Italian should be fixed in white cement.
2) All polishing shall be mirror polished unless otherwise specified.
38 Providing & Laying in position 32 mm avg. thick machine cut machine polished
Kota Stone of approved size, quality, type & colour as per the approved sample for
Post function Flooring in approved shape and pattern in true line and level / to
required slope over average 50mm thick bedding of cement mortar (1:4) floated
with neat cement slurry / paste (cement @ 4.5 kg/sqm) including cutting to the
required sizes (up to 570mm x 570mm), surface preparation, providing & laying ,
filling & finishing the joints with neat cement slurry & approved colour pigments,
mirror polishing, watering curing, cleaning etc complete at all floors & levels as per
the instructions of the EIC. (Refer Drw No.I-210, I-211, I-213, I-605A, I-605B, I-
606,I-706, I-830, A-201, A-501, A-502, A-503, A-800) (Mode of measurements :
Only plan are of flooring shall be measured for payment)
Sqm. 80.00
39 Providing & Laying in position 32 mm thick machine cut Rough finished Kota
Stone of approved size, quality, type & colour as per the approved sample for Fire
exit Ramp Flooring in approved shape and pattern in true line and level / to
required slope over average 50mm thick bedding of cement mortar (1:4) floated
with neat cement slurry / paste (cement @ 4.5 kg/sqm) including cutting to the
required sizes (up to 570mm x 570mm), surface preparation, providing & laying ,
filling & finishing the joints with neat cement slurry & approved colour pigments,
watering curing, cleaning etc complete at all floors & levels as per the instructions
of the EIC. Refer Drw No.-I-210, I-213, I-605A, I-605B, I-606,I-706, I-830, A-201,
A-501, A-502, A-503, A-800 (Mode of measurements : Only plan are of
flooring shall be measured for payment)
Sqm. 20.00
40 Doing mirror polishing to existing Kota Stone flooring Post function/Ramp/ pantry
Flooring including all machinaries, kits, cleaning etc complete at all floors & levels
as per the instructions of the EIC. Refer Drw No.--I-210, I-211, I-213, I-605A, I-
605B, I-606,I-706, I-830, A-201, A-501, A-502, A-503, A-800 (Mode of
measurements : Only plan are of flooring shall be measured for payment)
Sqm. 245.00
TENDER DOCUMENT BILL OF QUANTITIES - 11 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
41 Providing & Laying in position 19 mm thick machine cut Telephone Black Flamed
finish Granite slab of approved size, quality, type & colour as per the approved
sample for Pre- Function Flooring/ Mid landing in approved shape and pattern in
true line and level / to required slope over average 50mm thick bedding of cement
mortar (1:4) floated with neat cement slurry / paste (cement @ 4.5 kg/sqm)
including cutting to the required sizes, surface preparation, providing & laying ,
filling & finishing the joints with neat cement slurry & approved colour pigments,
watering curing, cleaning etc complete at all floors & levels as per the instructions
of the EIC. Refer Drw No.I-210, I-213, I-600A, I-601, I-701, I-702, I-606, I-707, I-
830 (Mode of measurements : Only plan are of flooring shall be measured for
payment)
Sqm. 80.00
42 Providing & Laying in position 19 mm thick machine cut Telephone Black Sand
Blasted Granite slab of approved size, quality, type & colour as per the approved
sample for Pre- Function Flooring/ Mid landing in approved shape and pattern in
true line and level / to required slope over average 50mm thick bedding of cement
mortar (1:4) floated with neat cement slurry / paste (cement @ 4.5 kg/sqm)
including cutting to the required sizes, surface preparation, providing & laying ,
filling & finishing the joints with neat cement slurry & approved colour pigments,
watering curing, cleaning etc complete at all floors & levels as per the instructions
of the EIC. Refer Drw No.I-210, I-211 I-213, I-600A, I-601, I-701, I-702, I-606, I-
707, I-830 (Mode of measurements : Only plan are of flooring shall be
measured for payment)
Sqm. 20.00
43 Providing & Laying in position full body Vitrified tiles of different sizes
(thickness to be specified by the manufacturers) of approved size, quality, type
& colour as per the approved sample for Flooring (conforming to IS 15622) in
approved shape and pattern in true line and level to required slope over average
20mm thick bedding of cement mortar 1:4 (1 cement : 4 coarse sand) floated with
neat cement slurry / paste (cement @ 4.5 kg/sqm) including chamfering of tiles
wherever required, cutting to the required sizes, surface preparation, providing &
laying, grouting the joints with white cement & matching pigments, watering, curing,
cleaning etc complete at all floors & levels as per the instructions of the EIC.
Refer Drw No.I-210, I-211 I-213, I-602A, I-602B, I-603A, I-603B, I-703, I-830
(Mode of measurements : Only plan area of flooring shall be measured for
payment)
43.1 600mm x 600mm in size Vitrified tile for Green room VT 01) (Code No. SCPL-
5286 Make - Sameer Ceramics/ Mirage- Vision Charcoal /).
Sqm. 55.00
44 Providing & Fixing in position skirting of following types using material as per
approved sample at all floor & levels fixed flush to the wall surface with cement
paste of desired consistency as per the pattern given to correct line, level & plumb
including chasing of wall / plaster wherever required, surface preparation, filling &
finishing the tile joints with cement & approved quality colour pigments, cutting of
tiles, mitering at edges, curing, cleaning, etc complete as per the instructions of the
EIC. 100mm high skirting with length of tile as per the architectural drawings.
(Mode of measurements : Only Running length of skirting shall be measured
for payment)
Refer Drw. No. I-210, I-211 I-213, I-602A, I-602B, I-603A, I-603B, I-703, I-600A, I-
601, I-701, I-702, I-606, I-707,I-830, I-605A, I-605B, I-606,I-706, I-830, A-201, A-
501, A-502, A-503, A-800
44.1 10mm thick Vitrified tile skirting (Code No. SCPL-5286 Make - Sameer
Ceramics/ Mirage- Vision Charcoal /).
Rmt. 60.00
44.2 19 mm thk. Telephone Black flamed Granite skirting with top edge polish Rmt. 125.00
44.319 mm thk. Telephone Black sandblasted Granite skirting with top edge polish
Rmt. 35.00
44.4 19mm thk. Kota stone skirting with top edge polish. Rmt. 55.00
TENDER DOCUMENT BILL OF QUANTITIES - 12 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
45 Providing and laying 1st quality Ceramic tiles for Dado at all heights and location
(CR 01) (thickness to be specified by the manufacturer) conforming to IS : 15622
of approved make and colour and pattern, in dado laid over 12mm thick backing
coat of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey
cement slurry @ 3.3kg per sqm including cost of backing coat pointing in white
cement and matching pigment, staging if required etc. complete all as per
specifications and drawings and as directed by Engineer In Charge.
Ref Drg no. I-210, I-211, I-213, I-606, I-707, I-830
45.1 600mm x 600mm in size Ceramic tile for Pantry/Green room Dado in (CR 01)
(Crema Dun Make - Nitco/ RAK/ Kajaria)
Sqm. 45.00
46 Providing & Fixing in position up to 150mm wide and 19mm thick machine cut
Telephone Black Flamed Granite as per the approved sample for ledges/
Threshold etc. as per the drawing laid to the required level & line including
cutting of stone to the required size & shape, edge polishing / chamferred edges,
surface preparation including cement backing with 1:1 cement grout, filling &
finishing the joints with cement & approved colour pigments, cutting, mirror
polishing to moulding & exposed edges, curing, cleaning etc complete as per the
instructions of the EIC. (Mode of measurements : Running length of ledge/
treshhold shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-820, I-830
Rmt. 35.00
47 Providing & Fixing in position 150mm wide 19mm thick machine cut, Second
quality marble as per the approved sample for Door/ window sils, jambs etc. as
per the drawing laid to the required level & line including cutting of stone to the
required size & shape, edge polishing / chamferred edges, surface preparation
including cement backing with 1:1 cement grout, filling & finishing the joints with
cement & approved colour pigments, cutting, mirror polishing to moulding &
exposed edges, curing, cleaning etc complete as per the instructions of the EIC.
(Mode of measurements : Running length of individual marble patti shall be
measured for payment)
Refer Drw. No I-210, I-211, I-213, I-800, I-801, I-820, I-830
Rmt. 65.00
48 Providing & Fixing in position 19mm thick machine cut,Telephone Black Flamed
Granite as per the approved sample for Door/ window cills, jambs or any other
specified in the drawing etc. as per the drawing laid to the required level & line
including cutting of stone to the required size & shape, edge polishing / chamfered
edges, surface preparation including cement backing with 1:1 cement grout, filling
& finishing the joints with cement & approved colour pigments, cutting, mirror
polishing, curing, cleaning etc complete as per the instructions of the EIC. (Mode
of measurements : Running length of individual marble patti shall be
measured for payment).
Refer Drw. No.I-210, I-211, I-213, I-800, I-801, I-820, I-830
48.1 Up to 75mm wide patti. Rmt. 130.00
48.2 Above 75mm and up to 150mm wide patti Rmt. 10.00
48.3 Above 150mm and up to 300mm wide patti Rmt. 40.00
48.4 Above 300mm and up to 400mm wide patti Rmt. 10.00
49 Providing & Fixing in position 19mm thick machine cut, Telephone Black
prepolished granite as per the approved sample for door thresholds, window
cills, jambs or any other specified in the drawing etc. as per the drawing laid to
the required level & line including cutting of stone to the required size & shape,
edge polishing / chamfered edges, surface preparation including cement backing
with 1:1 cement grout, filling & finishing the joints with cement & approved colour
pigments, cutting, mirror polishing to moulding & exposed edges, curing, cleaning
etc complete as per the instructions of the EIC. (Mode of measurements :
Running length of individual Granite patti shall be measured for payment)
Refer Drw. No I-210, I-211, I-213, I-800, I-801, I-820, I-830
49.1 Up to 75mm wide patti. Rmt. 5.00
49.2 Above 75mm and up to 150mm wide patti Rmt. 15.00
49.3 Above 150mm and up to 300mm wide patti Rmt. 10.00
TENDER DOCUMENT BILL OF QUANTITIES - 13 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
50 Providing & constructing 600mm wide wash basin counters with 100mm deep
facia as per the architectural drawing using min. 19mm thk pre polished
Telephone Black granite slab as per approved sample including, bed mortar in
CM 1:4, providing & fixing 19mm thk second quality marble base, including filling &
finishing the joints with cement & colour pigments, cutting opening in granite &
marble to accommodate wash basin, fixing of wash basin, half / full round
moulding, moulding polishing, edge polishing, curing, cleaning, etc complete at all
levels and as per the instructions of the EIC. Rate to include entire design as per
the detail in addition to the vertical and horizontal support to be polished on the
exposed side. (Mode of measurements : Running length of counter shall be
measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-602A, I-602B, I-603A, I-603B, I-703, I-830
Rmt. 3.00
51 Providing & constructing Prepolished Telephone Black Granite Pantry Platform /
Registration Counter comprising of 600mm wide counter top made out of 16-
18mm thk machine cut prepolished granite slab as per approved sample with
75mm high granite fascia & end vertical granite piece (both side polished) etc. as
per the architectural drawing including, chasing in wall, providing & fixing 30mm
thk. polished cuddapah slab base supported on vertical cadappa supports, p/l bed
mortar in CM 1:4, cutting of stone to the required size & shape, filling & finishing
the joints with cement & colour pigments, making opening in granite & cudappa to
accommodate the 600mm sink, Providing & fixing of sink, half / full round moulding,
Granite moulding/ edge mirror polishing, curing, cleaning, etc complete as per the
instructions of the EIC (Mode of measurements : Running length of -platform
shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-606, I-830
Rmt. 10.00
52 Providing & laying IPS flooring (as base for Vinyle flooring) or any other location
as specified by EIC of various thickness with cement concrete nominal mix of
proportion 1:2:4 (cement : Sand : Aggregate) in correct level / slope at all levels as
per architectural drawings including mixing of concrete in mixer, lifting, shifting to
the work location, compacting / vibrating, finishing smooth to the satisfaction of the
EIC, curing, and cleaning the surface etc. complete. (Mode of measurements
:Plan area of Flooring shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-709, I-830
52.1 Average up to 25mm thick IPS. Sqm. 5.00
52.2 Average above 25mm and up to 50mm thick IPS. Sqm. 5.00
52.3 Average above 50mm and up to 100mm thick IPS. Sqm. 395.00
53 Providing & fixing 3mm thick Vinyl sheet (Armstrong-VARIT PUR 531-052 /
Responsive - SP-10) for flooring confirming to IS 3462-1986 of Armstrong/ Atco
make & colour/pattern for Auditorium flooring and any other specified area in
correct level / slope at all levels as per architectural drawings and manufacturer's
specifications & instructions. Vinyl shall be fixed with approved adhesive properly,
avoid bubbles in flooring including cleaning the surface, pressing the vinyl by
appropriate roller properly, cutting and filling/ welding the joints by approved and
matching colour welding rod properly etc. completed as per the instructions of the
EIC. Joints shall be finished properly so that area shall look Continuously and joint
less. (Mode of measurements : Area of Vinyl flooring shall be measured for
payment) Refr Drw. No. I-210, I-211, I-213, I-709, I-830
Sqm. 395.00
54 Providing & Fixing in position 19mm thick machine cut, machine polished
Anglomerated marble as per the approved sample for Door/ window cills,
jambs or any other specified in the drawing etc. as per the drawing laid to the
required level & line including cutting of stone to the required size & shape, edge
polishing / chamfered edges, surface preparation including cement backing with 1:1
cement grout, filling & finishing the joints with cement & approved colour pigments,
cutting, mirror polishing, curing, cleaning etc complete as per the instructions of the
EIC. (Mode of measurements : Running length of individual marble patti
shall be measured for payment).
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-820, I-830
TENDER DOCUMENT BILL OF QUANTITIES - 14 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
54.1 Up to 75mm wide patti. Rmt. 5.00
54.2 Above 75mm and up to 150mm wide patti Rmt. 5.00
54.3 Above 150mm and up to 300mm wide patti Rmt. 10.00
55 Providing & constructing Prepolished 19mm thick Telephone Black Granite
Sitting (350 x 450 mm high in size) in Prefunction area comprising of following.
Providing and constructing 230mm thick brick work in 450mm height finish the brick
work with 12mm thick single sandfaced plaster in 1:4. P/f 350 mm wide granite top
fixed with backing cement paste properly. Also fixing 30mm wide nosing with
araldite all round with 6mm patta moulding at top and bottam as per architectural
drawing and instructions including necessary excavation, 230mm thk soling, 100
mm thick pcc in M100, cutting of stone to the required size & shape, filling &
finishing the joints with cement & colour pigments, Granite moulding/ edge mirror
polishing, curing, cleaning, etc complete as per the instructions of the EIC (Mode
of measurements : Running length of counter shall be measured for
payment)
Refer Drw. No. I-210, I-211, I-213, I-600, I-601, I-702, I-830
Rmt. 15.00
TOTAL OF FLOORING, SKIRTING & DADO WORK
G PAINTING WORK
56 Providing & applying following types of acrylic based emulsion paint / Luxury
emulsion paint ( Conforming IS 5411-1974) of make JOTUN for internal gypsum /
POP surface to be applied as per manufacturer's instructions & methodology as
directed by Architect including preparing the surface, p/a one coat of water base
PVA primer (copolymer based alkali resistant primer with fungicide) of Jotun make
and two coat of water base acrylic putty of Jotun make, sanding, light sanding,
scaffolding, work platform, painting equipment / apparatus etc. required to
complete interior grade finish with 3 coats of approved shade colour etc. complete
as directed by the EIC at all heights & levels. (Mode of measurement- Only
painting area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-300A, I-300B, I-602A, I-602B, I-603A, I-603B,
I-606, I-607A, I-607B, A-501, A-502, A-800 I-830)
56.1 Fenomastic gold 007 to wall in green room and projector room Sqm. 150.00
56.2 Fenomastic matt 003 to ceiling green room and projector room Sqm. 70.00
56.3 Do as per item no.56.2 but spray painting (217-4000 B-G) for ceiling straw
boards/ AC ducts and any other location as directed by EIC/ Architects.
Sqm. 210.00
57 Providing & applying 1st quality synthetic enamel paint ( Conforming IS 2932-
1994) (for service areas) of approved make & shade in 3 coats over a coat of
approved quality primer to the wooden surface / MS railings & grills including
providing, erecting & dismantling scaffolding, preparation of surface, appying hard
putty, sanding, etc. complete as diected by the EIC at all lheights & levels. (Mode
of measurement- Only painting area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-605A, A-201, A-501, A-502, A-503, A-800, I-
830
Sqm. 200.00
58 Providing & applying 1st quality Water cut enamal paint ( Conforming IS 2932-
1994) of approved make & shade for wooden surface / MS railings & grills to be
applied as per manufacturer's instructions & methodology as directed by Architect
including preparing the surface, p/a one coat of water base metalic primer of Estee
or equivalent make and two coat of water base acrylic putty, sanding with water,
light sanding with water, scaffolding, work platform, painting equipment /
apparatus, dismantling scaffolding and cleaning etc. required to complete interior
grade finish with 3 coats of approved shade colour etc. complete as directed by the
EIC at all heights & levels. (Mode of measurement- Only painting area shall be
measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-605A, A-201, A-501, A-502, A-503, A-800, I-
830
Sqm. 5.00
TENDER DOCUMENT BILL OF QUANTITIES - 15 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
59 Providing & applying following types of Decorative paint / Texture paint of make
OIKOS/Jotun or equivalent make for internal gypsum / POP surface to be applied
as per manufacturer's instructions & methodology as directed by Architect including
preparing the surface, p/a one coat of water base PVA primer (copolymer based
alkali resistant primer with fungicide) of OIKOS / Jotun and two coat of water base
acrylic putty of OIKOS / Jotun , sanding, light sanding, scaffolding, work platform,
painting equipment / apparatus etc. required to complete interior grade finish with 3
coats of approved shade colour etc. complete as directed by the EIC at all heights
& levels (Mode of measurement- Only painting area shall be measured for
payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-600A, I-600B, I-601, I-602A, I-602B, I-
603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E, I-605A, I-605B, I-606, I-
607A, I-607B, I-701, I-703, I-705A, I-705B, I-706
59.1 For Auditorium wall paneling (Make - OIKOS- Antique effect-811/ Asian paints-
Royale play Dune Silver Streak M609) Range - Special Products)
Sqm. 165.00
59.2 For Green room wall paneling (Make - OIKOS-Antique effect-812 / Asian paints-
Royale play Dune Silver Streak M609 Dark ) Range - Special Products
Sqm. 10.00
59.3 For Prefunction and Post Function area.External texture paint (Make - Jotun-
Texotile- B-G-213-4502B / Asian Paints - Pebble Tex Head cut- steel 6142) Range
- Special Products
Sqm. 75.00
59.4 For Prefunction and Post Function area.External texture paint (Make - Jotun-
Texotile- B-G-213- 7502B / Asian Paints - Pebble Tex Head cut- Charcoal Shadow
8286) Range - Special Products
Sqm. 135.00
59.5 For Prefunction area (Make- Asian Silver metalic paint-Shade code 135- 30 %
dark) Range - Special Products .
Sqm. 15.00
59.6 For Prefunction and Post Function area External paint (Make - Sherwin Williams-
Beige Assorted Paino / Aisan Paints - Swirl Tex with top coat of Apex)
Sqm. 40.00
60 Providing and applying Two coats of acrylic based paint Jotashield matt- Jotamatt
white of Jotun or equivalent make, color & shade to the external surface over a
coat of primer of Jotun make in Pre-function area including scaffolding, labour, and
material and preparing surface. The surface shall be thoroughly cleaned off all
mortar dropping, dirt dust, algae, fungus or moth grease and other foreign matter of
brushing and washing ,pitting in plaster shall make good surface imperfections
such as cracks , holes etc. should be repaired using white cement. Approval of the
prepraed surface to be obtained before commencement of painting work. Paint
shall be applied with a brush on the cleaned and smooth surface .Horizontal
strokes shall be given , first and vertical strokes shall be immediately afterwards.
This entire operation will constitute one coat .The surface shall be finished smooth
uniformly etc. complete. as directed by the Project In charge at all heights & levels.
Refer Drw. No. I-210, I-211, I-213, I-830, I-300A, I-600B, I-601, I-700
Sqm. 115.00
61 Providing & applying Natural / French polish ( Conforming IS 348-1968) in 3 or
more coats of approved shade to the wooden / Plywood / veneer surface,
mouldings pattas, grooves etc. including surface preparation, applying filler /
hardener / putty, sanding, cleaning of furniture after completion of job etc. complete
as directed by the EIC. (Mode of measurement- Only polishing area shall be
measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A , I-602B, I-603A, I-603B, I-606, I-
703, I-707
Sqm. 10.00
62 Providing and applying Melamine polish for exposed wooden surfaces wherever
directed by the architects. including surface preparation, applying filler / hardener /
putty, sanding, cleaning of furniture, required smooth finishing after completion of
job etc. complete as directed by the EIC. (Mode of measurement- Only
polishing area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A , I-602B, I-603A, I-603B, I-606, I-
703, I-707
Sqm. 65.00
TOTAL OF PAINTING WORK
H DOOR WORKS
TENDER DOCUMENT BILL OF QUANTITIES - 16 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
All the hardware fitings and Fixtures shall be Ozone or any other equivalent
approved make
Providing & fixing 45mm thick(excluding finishes) single leaf commercial Flush
door shutter (D1) (900 X 2075mm in size) for Green room Gents Main door of
approved make & type comprising of phenol bonded solid core made up of kiln
seasoned battens, crossbands & face veneers all from selected strong & durable
hardwoods bonded together under heat & pressure using a BWP type Phenol
Formaldehyde synthetic resin adhesive. The flush door shall conform to IS2202,
1991. Door shall be fire rated for 30 minutes. The flush door shall be finished
with 1 mm thk laminate on both sides (Laminate to be approved by architect before
commencement of work) including providing & fixing 12 mm thk TW lipping all
around ffinish with approved melemine poilish matching to the laminate . Rate also
included providing and fixing teak wood door frame of size 150mm x 75mm finish
with approved water cut enamel paint , p/f teak wood architrave 42 x 10mm in size
finish with approved watercut enamel paint, including providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping,fastenings, 8 Nos MS hold fast, p/f fittings and fixtures of Ozone make &
cleaning etc. completed at all floors & heights as per architectural drawings and
instructions.
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
SS finished leaver handle with Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
Key hole-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 45mm thick(excluding finishes) single leaf commercial Flush
door shutter (D2) (900 X 2075mm in size) for Green room Ladies Main door of
approved make & type comprising of phenol bonded solid core made up of kiln
seasoned battens, crossbands & face veneers all from selected strong & durable
hardwoods bonded together under heat & pressure using a BWP type Phenol
Formaldehyde synthetic resin adhesive. The flush door shall conform to IS2202,
1991.Door shall be fire rated for 30 minutes. The flush door shall be finished
with 1 mm thk laminate on both sides (Laminate to be approved by architect before
commencement of work) including providing & fixing 12 mm thk TW lipping all
around finish with approved melemine poilish matching to the laminate . Rate also
included providing and fixing teak wood door frame of size 150mm x 75mm finish
with approved water cut enamel paint, p/f teak wood architrave 42 x 10mm in size
finish with approved watercut enamel paint, including providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping,fastenings, 8 Nos MS hold fast, p/f fittings and fixtures of Ozone make &
cleaning etc. completed at all floors & heights as per architectural drawings and
instructions.
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
SS finished leaver handle with Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
Key hole-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
65 Providing & exchanging 1mm thick laminate (Laminate to be approved by
architect before commencement of work) of existing door (D3) for Green room
Gents internal door. including removing old laminate providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping,fastenings, cleaning etc. completed at all floors & heights as per
architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
each 1.00
1.00 each 64
1.00 each 63
TENDER DOCUMENT BILL OF QUANTITIES - 17 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
66 Providing & exchanging 1mm thick laminate (Laminate to be approved by
architect before commencement of work) of existing door (D4) for Green room
Ladies internal door. including removing old laminate providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping,fastenings, cleaning etc. completed at all floors & heights as per
architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
each 1.00
Providing & fixing in positions double shutter Glass door inclusive of side fixed
glazing (D5) (2100 x 2100mm in size) for main enterance Door in prefunction
area with using 12 mm thick fixed Toughened Plain glass of Modi make or any
other approved equivalent make and quality,having top & bottom frame in tw of
approx size 200mm x 50mm thk finished in dark melamine polish, hung with heavy
duty floor spring of Ozone as per architectural drawings and instructions including
cutting, edge polishing, buffing necessary hardware, etc. completed.at all floors &
heights as per architectural drawings and instructions.
each 1.00
Fittings & Fixtures (per leaf)
heavy duty floor spring - 1no.
26mm dia & 600mm long handle 'D' type in ss finish as approved.
SS Patch fittings lock
150mm Concealed SS tower bolt
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing in positions double shutter Glass door inclusive of side fixed
glazing (D6) (2100 x 2100mm in size) for main enterance Door in prefunction
area with using 12 mm thick fixed Toughened Plain glass of Modi make or any
other approved equivalent make and quality,having top & bottom frame in tw of
approx size 200mm x 50mm thk finished in dark melamine polish, hung with heavy
duty floor spring of Ozone as per architectural drawings and instructions including
cutting, edge polishing, buffing necessary hardware, etc. completed.at all floors &
heights as per architectural drawings and instructions.
each 1.00
Fittings & Fixtures (per leaf)
heavy duty floor spring - 1no.
26mm dia & 600mm long handle 'D' type in ss finish as approved.
SS Patch fittings lock
150mm Concealed SS tower bolt
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 45mm thick(excluding finishes) Double leaf commercial Flush
door shutter (D7) (2100 X 2400mm in size) for Main house entry door of approved
make & type comprising of phenol bonded solid core made up of kiln seasoned
battens, crossbands & face veneers all from selected strong & durable hardwoods
bonded together under heat & pressure using a BWP type Phenol Formaldehyde
synthetic resin adhesive. The flush door shall conform to IS2202, 1991. The flush
door shall be finished with 1 mm thk laminate on both sides (Laminate to be
approved by architect before commencement of work) including providing & fixing
12 mm thk TW lipping all around finish with approved melemine poilish matching to
the laminate . Rate also included providing and fixing teak wood door frame of size
475mm x 95mm finish with approved water cut enamel paint, including providing
all necessary consumables viz. adhesive, necessary hardware, necessary beads
moulding, lipping,fastenings, 8 Nos MS hold fast, p/f fittings and fixtures of Ozone
make & cleaning etc. completed at all floors & heights as per architectural drawings
and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
Double cylindrical lock- 1 no.
Concealed door closer- 1 No.
26mm dia & 600mm long handle 'D' type in ss finish as approved.
Door drop seal
Concealed door stopper
67
69
68
TENDER DOCUMENT BILL OF QUANTITIES - 18 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
Door seal-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 45mm thick(excluding finishes) Double leaf commercial Flush
door shutter (D8) (2100 X 2400mm in size) for Main house entry door of approved
make & type comprising of phenol bonded solid core made up of kiln seasoned
battens, crossbands & face veneers all from selected strong & durable hardwoods
bonded together under heat & pressure using a BWP type Phenol Formaldehyde
synthetic resin adhesive. The flush door shall conform to IS2202, 1991. The flush
door shall be finished with 1 mm thk laminate on both sides (Laminate to be
approved by architect before commencement of work) including providing & fixing
12 mm thk TW lipping all around finish with approved melemine poilish matching to
the laminate . Rate also included providing and fixing teak wood door frame of size
475mm x 95mm finish with approved water cut enamel paint, including providing
all necessary consumables viz. adhesive, necessary hardware, necessary beads
moulding, lipping,fastenings, 8 Nos MS hold fast, p/f fittings and fixtures of Ozone
make & cleaning etc. completed at all floors & heights as per architectural drawings
and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
26mm dia & 600mm long handle 'D' type in ss finish as approved.
Door drop seal
Concealed door stopper-
Door seal-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 40mm thick(excluding finishes) single leaf commercial Flush
door shutter (D9) (800 X 2100mm in size) for Stage door of approved make &
type comprising of phenol bonded solid core made up of kiln seasoned battens,
crossbands & face veneers all from selected strong & durable hardwoods bonded
together under heat & pressure using a BWP type Phenol Formaldehyde synthetic
resin adhesive. The flush door shall conform to IS2202, 1991.Door shall be fire
rated for 30 minutes. The flush door shall be finished with approved water cut
enamel paint (Asian paints- Gloos Enamel Paint or Satin Enamel Paint Matching
the Laminate) from outside and finished with 1 mm thk laminate (Laminate to be
approved by architect before commencement of work) from inside, including
providing & fixing 12 mm thk TW lipping all around ffinish with approved water cut
enamel paint. Rate also included providing and fixing teak wood door frame of size
110mm x 50mm finish with approved water cut enamel paint, p/f teak wood
architrave 42 x 10mm in size finish with approved watercut enamel paint, including
providing all necessary consumables viz. adhesive, necessary hardware,
necessary beads moulding, lipping,fastenings, 8 Nos MS hold fast, p/f fittings and
fixtures of Ozone make & cleaning etc. completed at all floors & heights as per
architectural drawings and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
SS finished leaver handle with Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
Door drop seal-
Key hole-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
70
71
69
TENDER DOCUMENT BILL OF QUANTITIES - 19 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
Providing & fixing 40mm thick(excluding finishes) single leaf commercial Flush
door shutter (D10) (800 X 2100mm in size) for Stage door of approved make &
type comprising of phenol bonded solid core made up of kiln seasoned battens,
crossbands & face veneers all from selected strong & durable hardwoods bonded
together under heat & pressure using a BWP type Phenol Formaldehyde synthetic
resin adhesive. The flush door shall conform to IS2202, 1991.Door shall be fire
rated for 30 minutes. The flush door shall be finished with approved water cut
enamel paint (Asian paints- Gloos Enamel Paint or Satin Enamel Paint Matching
the Laminate) from outside and (Laminate to be approved by architect before
commencement of work), including providing & fixing 12 mm thk TW lipping all
around ffinish with approved water cut enamel paint . Rate also included providing
and fixing teak wood door frame of size 110mm x 50mm finish with approved
water cut enamel paint, p/f teak wood architrave 42 x 10mm in size finish with
approved watercut enamel paint, including providing all necessary consumables
viz. adhesive, necessary hardware, necessary beads moulding, lipping,fastenings,
8 Nos MS hold fast, p/f fittings and fixtures of Ozone make & cleaning etc.
completed at all floors & heights as per architectural drawings and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
SS finished leaver handle with Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
Door drop seal-
Key hole-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 45mm thick (excluding finishes) single leaf marine Flush door
shutter (D11) (1000 X 2100mm in size) for Fire exit door of approved make &
type comprising of phenol bonded solid core made up of kiln seasoned battens,
crossbands & face veneers all from selected strong & durable hardwoods bonded
together under heat & pressure using a BWP type Phenol Formaldehyde synthetic
resin adhesive. The flush door shall conform to IS2202, 1991. Door shall be fire
rated for 30 minutes. The flush door shall be finished with 1 mm thk laminate on
both sides (Laminate to be approved by architect before commencement of work)
including providing & fixing 12 mm thk TW lipping all around finish with approved
melemine poilish matching to the laminate . Rate also included providing and fixing
teak wood door frame of size 150mm x 75mm finish with approved water cut
enamel paint, p/f teak wood architrave 42 x 10mm in size finish with approved
watercut enamel paint, including providing all necessary consumables viz.
adhesive, necessary hardware, necessary beads moulding, lipping,fastenings, 8
Nos MS hold fast, p/f fittings and fixtures of Ozone make & cleaning etc. completed
at all floors & heights as per architectural drawings and instructions.
each 1.00
Fittings & Fixtures (per leaf)
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
Panic bar -.
Door drop seal
Concealed door closer.
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
72
73
TENDER DOCUMENT BILL OF QUANTITIES - 20 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
Providing & fixing 45mm thick (excluding finishes) single leaf marine Flush door
shutter (D12) (1000 X 2100 mm in size) for Fire exit door of approved make &
type comprising of phenol bonded solid core made up of kiln seasoned battens,
crossbands & face veneers all from selected strong & durable hardwoods bonded
together under heat & pressure using a BWP type Phenol Formaldehyde synthetic
resin adhesive. The flush door shall conform to IS2202, 1991. Door shall be fire
rated for 30 minutes. The flush door shall be finished with 1 mm thk laminate on
both sides (Laminate to be approved by architect before commencement of work)
including providing & fixing 12 mm thk TW lipping all around finish with approved
melemine poilish matching to the laminate . Rate also included providing and fixing
teak wood door frame of size 150mm x 75mm finish with approved water cut
enamel paint, p/f teak wood architrave 42 x 10mm in size finish with approved
watercut enamel paint, including providing all necessary consumables viz.
adhesive, necessary hardware, necessary beads moulding, lipping,fastenings, 8
Nos MS hold fast, p/f fittings and fixtures of Ozone make & cleaning etc. completed
at all floors & heights as per architectural drawings and instructions.
each 1.00
Fittings & Fixtures (per leaf)
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
Panic bar -.
Door drop seal
Concealed door closer.
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 45mm thick(excluding finishes) Double leaf commercial Flush
door shutter (D13) (1520 X 2100mm in size) for Post function area door of
approved make & type comprising of phenol bonded solid core made up of kiln
seasoned battens, crossbands & face veneers all from selected strong & durable
hardwoods bonded together under heat & pressure using a BWP type Phenol
Formaldehyde synthetic resin adhesive. The flush door shall conform to IS2202,
1991. The flush door shall be finished with 1 mm thk laminate on both sides
(Laminate to be approved by architect before commencement of work), including
providing & fixing 12 mm thk TW lipping all around finish with approved melemine
poilish matching to the laminate . Rate also included providing and fixing teak wood
door frame of size 475mm x 75mm finish with approved water cut enamel paint,
including providing all necessary consumables viz. adhesive, necessary hardware,
necessary beads moulding, lipping,fastenings, 8 Nos MS hold fast, p/f fittings and
fixtures of Ozone make & cleaning etc. completed at all floors & heights as per
architectural drawings and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
26mm dia & 600mm long handle 'D' type in ss finish as approved.
Door drop seal
Concealed stopper
Door seal-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
74
75
TENDER DOCUMENT BILL OF QUANTITIES - 21 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
Providing & fixing 45mm thick(excluding finishes) Double leaf marine Flush
door shutter (D14) (1520 X 2100mm in size) for Post function area door of
approved make & type comprising of phenol bonded solid core made up of kiln
seasoned battens, crossbands & face veneers all from selected strong & durable
hardwoods bonded together under heat & pressure using a BWP type Phenol
Formaldehyde synthetic resin adhesive. The flush door shall conform to IS2202,
1991. The flush door shall be finished with 1 mm thk laminate on both sides
(Laminate to be approved by architect before commencement of work) including
providing & fixing 12 mm thk TW lipping all around finish with approved melemine
poilish matching to the laminate . Rate also included providing and fixing teak wood
door frame of size 475mm x 75mm finish with approved water cut enamel paint,
including providing all necessary consumables viz. adhesive, necessary hardware,
necessary beads moulding, lipping,fastenings, 8 Nos MS hold fast, p/f fittings and
fixtures of Ozone make & cleaning etc. completed at all floors & heights as per
architectural drawings and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
per shutter
Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
26mm dia & 600mm long handle 'D' type in ss finish as approved.
Door drop seal
Concealed stopper
Door seal-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
Providing & fixing 45mm thick(excluding finishes) single leaf marine Flush door
shutter (D15) (900 X 2100mm in size) for Projector room door of approved make
& type comprising of phenol bonded solid core made up of kiln seasoned battens,
crossbands & face veneers all from selected strong & durable hardwoods bonded
together under heat & pressure using a BWP type Phenol Formaldehyde synthetic
resin adhesive. The flush door shall conform to IS2202, 1991.Door shall be fire
rated for 30 minutes. The flush door shall be finished with 1 mm thk laminate on
both sides (Laminate to be approved by architect before commencement of work)
including providing & fixing 12 mm thk TW lipping all around ffinish with approved
melemine poilish matching to the laminate. Rate also included providing and fixing
teak wood door frame of size 150mm x 75mm finish with approved water cut
enamel paint, p/f teak wood architrave 42 x 10mm in size finish with approved
watercut enamel paint, including providing all necessary consumables viz.
adhesive, necessary hardware, necessary beads moulding, lipping,fastenings, 8
Nos MS hold fast, p/f fittings and fixtures of Ozone make & cleaning etc. completed
at all floors & heights as per architectural drawings and instructions.
each 1.00
Fittings & Fixtures per leaf
Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos.
SS finished leaver handle with Doble cylindrical lock- 1 no.
Concealed door closer- 1 No.
Key hole-
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
78 Providing & exchanging 1mm thick (Laminate to be approved by architect
before commencement of work) of existing door (D16) for pantry door.
including removing old laminate providing all necessary consumables viz.
adhesive, necessary hardware, necessary beads moulding, lipping,fastenings,
cleaning etc. completed at all floors & heights as per architectural drawings and
instructions.
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
each 1.00
TOTAL OF DOOR WORKS
77
76
TENDER DOCUMENT BILL OF QUANTITIES - 22 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
I WOOD WORKS (PARTITION & PANELLING)
79 Providing & fixing 6mm thick Plain Mirror of modi or equivalent for Green Room
as per approved shape, size and as per architectral rawing and instruction fixed
with 25mm dia SS Studs properly. Rate also included providing all necessary
consumables viz., necessary hardware etc. complete at all heights as per
architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-703
Sqm. 10.00
80 Providing & fixing 6mm thick frosted glass of modi or equivalent for Green Room
as per approved shape, size and as per architectral rawing and instruction fixed
with 25mm dia SS Studs properly. Rate also included providing all necessary
consumables viz., necessary hardware etc. complete at all heights as per
architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-703
Sqm. 2.00
81 Providing & fixing in positions 12 mm thick commercial ply and 12 mm thick
calicium silicate board paneling as per architectural drawing and instructions.
The system shall be comprising following. Ply frame work -Providing, making and
fixing 18mm thick marine ply frame work as architectural drawing and instruction at
all shapes and sides.
Panelling- providing and fixing 12mm thick commercial ply fix on the frame and
finish the ply with 12mm thick calcium silicate board as per architectural drawing,
including cutting, necessary hardware, drilling, The work also includes vertical
drops, sides, curvature, cutting of ply/veneer & frame work and providing cutouts /
openings for switch boards, fd and cleaning etc. completed at all floors and heights
as specified and directed by Architects/ EIC.
Ref Drw. No. I-210, I-211, I-213, I-830, I-600A, I-600B, I-601, I-700, I-701
(Front elevational area shall be measured for Billing)
81.1 Up to 50mm thick paneling- Sqm. 35.00
81.2 Above 50mm and up to 100mm thick paneling Sqm. 5.00
81.3 Above 100mm and up to 150mm thick paneling Sqm. 15.00
81.4 Above 150mm and up to 200mm thick paneling Sqm. 10.00
82 Providing & fixing in positions 12 mm thick commercial ply and fabric paneling
as architectural drawing and instructions. The system shall be comprising following.
Aluminum frame work -Providing, making and fixing aluminum frame work made
out of 38x 50mm aluminum heavy box section @ 600mm c/c both ways (spacing
should no be exceed than 600mm depending on length and height). Frame shall be
supported with aluminum box section of 38x 50mm @ 600mm c/c fix on wall with
40x40x3mm aluminum angle as per thickness of paneling.
Panelling- providing and fixing 12mm thick commercial ply frame made out of
150mm x 12mm @ 600mm c/c both ways.p/f 20mm thick basotect foam in the
frame as per drawing. And finish the paneling with approved fabric (Bharat
Furnishing -premium shade 24293- SR. No.- 6- Munnar silk / Decotex - VRN 817).
including cutting, necessary hardware, drilling, Vinyl pvc gripper,. The work also
includes vertical drops, curvature, coves, cutting & frame work and providing cut
out and necessary support for switch boxes and lightfittings and cleaning etc.
completed at all floors. Fabric should be streched properly to avoid bubbles and
loosness.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
82.1 Up to 100mm thick paneling Sqm. 2.00
82.2 Above 100mm and up to 150mm thick paneling Sqm. 75.00
82.3 Above 150mm and up to 200mm thick paneling Sqm. 2.00
TENDER DOCUMENT BILL OF QUANTITIES - 23 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
83 Providing & fixing in positions 20 mm thick Basotect Foam and fabric paneling
as per architectural drawing and instructions. The system shall be comprising
following.
Panelling- providing and fixing 20mm thick basotect foam including wire mesh on
the wall at given location as per drawing. And finish the paneling with approved
fabric (Surprise house warming- premium shade HW/FLTEX / Surprise house
warming- premium shade Shiro 32 N Blue) including cutting, necessary hardware,
drilling, Vinyl pvc gripper,. The work also includes vertical drops, curvature, coves,
cutting & frame work and providing cut out and necessary support for switch boxes
and lightfittings and cleaning etc. completed at all floors. Fabric should be streched
properly to avoid bubbles and loosness.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
Sqm. 25.00
84 Providing & fixing in positions 20 mm thick Straw board and fabric paneling as
per architectural drawing and instructions. The system shall be comprising
following.
Aluminum frame work -Providing, making and fixing aluminum frame work made
out of 50 x 50mm aluminum heavy box section @ 600mm c/c both ways ( spacing
should no be exceed than 600mm depending on length and height). Frame shall be
supported with aluminum box section of 50x 50mm @ 600mm c/c fix on wall with
50x500x3mm aluminum angle as per thickness of paneling.
Panelling- providing and fixing 20mm thick Straw board as per drawing. And
finish the straw board with approved fabric (Bharat Furnishing - Premium shade -
24293 - Sr. No. 6 Munar Silk / Decotex - VRN 817). including cutting, necessary
hardware, drilling,The work also includes vertical drops, curvature, coves, cutting &
frame work and providing cut out and necessary support for switch boxes and
lightfittings and cleaning etc. completed at all floors. Fabric should be streched
properly to avoid bubbles and loosness.
84.1 Up to 100mm thick paneling Sqm. 2.00
84.2 Above 100mm and up to 150mm thick paneling Sqm. 2.00
84.3 Above 150mm and up to 300mm thick paneling Sqm. 2.00
84.4 Above 300mm and up to 400mm thick paneling Sqm. 45.00
85 Providing & fixing in positions 20 mm thick Straw board and fabric paneling as
per architectural drawing and instructions. The system shall be comprising
following.
Aluminum frame work -Providing, making and fixing aluminum frame work made
out of 50 x 50mm aluminum heavy box section @ 600mm c/c both ways ( spacing
should no be exceed than 600mm depending on length and height). Frame shall be
supported with aluminum box section of 50x 50mm @ 600mm c/c fix on wall with
50x500x3mm aluminum angle as per thickness of paneling.
Panelling- providing and fixing 20mm thick Straw board as per drawing. And
finish the straw board with approved fabric (Bharat Furnishing -premium shade
24293- SR. No.- 6- Munnar silk / Decotex - VRN 817). including cutting,
necessary hardware, drilling,The work also includes vertical drops, curvature,
coves, cutting & frame work and providing cut out and necessary support for
switch boxes and lightfittings and cleaning etc. completed at all floors. Fabric
should be streched properly to avoid bubbles and loosness.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
85.1 Up to 100mm thick paneling Sqm. 70.00
TENDER DOCUMENT BILL OF QUANTITIES - 24 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
86 Providing & fixing in positions MDF board paneling as per architectural drawing
and instructions. The system shall be comprising following.
Aluminum frame work -Providing, making and fixing aluminum frame work made
out of 50 x 50mm aluminum heavy box section @ 600mm c/c both ways ( spacing
should no be exceed than 600mm depending on length and height). fixed directly
on wall as per drawing and thickness of paneling.
Panelling- providing and fixing two nos. 6mm thick sandwitched exterior grade
MDF board fixed on frame as per drawing including cutting, necessary hardware,
drilling,The work also includes vertical drops, curvature, coves, cutting & frame
work and providing cut out and necessary support for switch boxes and lightfittings
and cleaning etc. completed at all floors.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
86.1 Up to 100mm thick paneling Sqm. 165.00
87 Providing and fixing 20mm thick Commercial ply storage shutters of approved
make as per architectural drawing and instructions Frame out of 40MM X 25MM
,fixed to the kadappa or wall surface with as per detailed drawing. Shutter panels
finished with 1mm thick laminate (Laminate to be approved by architect before
commencement of work) on out side and french polish at inside and hinged to
framework with 2nos 100mm s.s hinges including providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping, fastenings, fittings and finish the wooden frame french polish etc. complete
at all floors & heights as per architectural drawings and instructions. (Mode of
measurement- Only one side shutter area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-606, I-
703, I-707
Sqm. 10.00
88 Providing, making and fixing 75mm thick full height Stage back Ply partition as
per architectural drawing and instructions . The system shall be comprising of
following.Frame work- Providing. making and fixing aluminum frame work made
out of 38mm x 50mm aluminum box section @ 600 mm c/c in both ways fix
properly as per drawing.Ply - Providing and fixing 12 mm thick commercial ply
fixed on peripheri of the frame as per architectural drawings and instructions
including cutting, necessary hardware, drilling, cut out and necessary support for
switch boxes and lightfittings and finish. All connections in framework shall be with
GI screws of approved quality.Ply with tapered edges to be screwed to the
framework with 25mm long GI screws at 230 mm c/c. Screw fixing shall be done
mechanically. 20 mm thick Basotect foam shall be sandwithched in ply and frame
properly. and finish the panelling with aproved colour fabric (Bharat Furnishing -
Premium shade - 24293 - Sr. No. 6 Munar Silk / Decotex - VRN 817), fabric shall
be stiched properly to avoid bubbles and looseness and cleaning etc. completed
at all floors and heights as specified and directed by Architects/ EIC.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
Sqm. 65.00
89 Providing and fixing 300mm wide and 25mm thick commercial ply shelves for
Changing Room fixed in partitions at given loction properly as per architectural
drawing and instructions and finish the shelves with 1mm thick approved make and
colour laminate(Laminate to be approved by architect before commencement of
work) including providing all necessary consumables viz. adhesive, necessary
hardware, necessary beads moulding, lipping, fastenings etc. complete at all floors
& heights as specified and as directed by EIC. (Mode of measurement- Only
running length of shelves shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-703
Rmt. 5.00
TENDER DOCUMENT BILL OF QUANTITIES - 25 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
90 Providing & fixing 12mm thick & 75mm high approved quality Wooden skirting
finished with approved melamine polish as per the pattern given to correct line,
level & plumb including chasing of wall wherever required, surface preparation,
joints should be proper, cutting, mitring at edges, screwing, necessary hardware,
lipping, commercial ply backing as per site condition, adhesives, cleaning . etc
complete as per the Architectural drawings & instructions. (Mode of measurement-
running length of skirting shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
Rmt. 15.00
91 Providing & fixing 2000mm x 795mm x 750mm height Unit for music
instruments (Audio Mixer) in commercial ply as per architectural Drawing and
instructions comprise with following.- P/f two nos 19mm thick sandwitched ply for
legdge/top with drawers made out of 12mm thick commercial ply as per architeural
drawings and finish the unit with approved laminate (Laminate to be approved by
architect before commencement of work) at visible side.Back/ hidden portion of ply
& drawer inside shall be finish with french polish. providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping, fastenings, fittings, SS Chanels and cleaning etc. complete at all floors &
heights etc. completed as directed and as specified by EIC.
Refer Drw. No. I-210, I-211, I-213, I-830, I-607A, I-607B
each 1.00
92 Providing, making and errecting 500 mm wide and 750mm high Green room
Dressing counter with wash basin made out of 19mm commercial ply as per
architectural drawing and instructions. Including 12mm thick marine ply facia,
drawers, p/f approved washbasin, providing all necessary consumables viz.
adhesive, necessary hardware, necessary beads moulding, lipping, fastenings,
fittings and finish the ply with approve laminate (Laminate to be approved by
architect before commencement of work) at visible side and french polish at drawer
inner side and whereever is required and cleaning etc. complete as directed and
as specified by EIC.
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-703
Rmt. 10.00
93 Providing & fixing 38 mm thick Glass Shutter (1350 X 950) for TV in Postfunction
area comprising with 12mm thick Toghened clear glass fixed in 50 x 38mm teak
wood frame finished with approved water cut enamel paint as per architectural
drawings and instructions including providing & fixing 12 mm thk TW lipping all
around finished with approved water cut enamel paint. Rate also included providing
and fixing teak wood shutter of size 50 x 38mme of size finish with approved water
cut enamel paint including providing all necessary consumables viz. adhesive,
necessary hardware, necessary beads moulding, lipping,fastenings, L & Key
locking system & cleaning etc. completed at all floors & heights as per architectural
drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-830, I-605A, I-605B, I-607A, I-607B, I-706
each 1.00
94 Providing, making and errecting 325mm high (height from finish top of existing
stage) Proscenium as per architectural drawing and instructions . The system
shall be comprising of following .Frame work- Providing. making and fixing teak
wood frame work made out of 38mm x 38mm @ 600 mm c/c in both ways fix
properly to the existing stage from bottam of the stage as per drawing. Top portion
of vertical members shall be curve/ bend as per drawing. Ply - Providing and fixing
8 mm thick flexi commercial ply fixed on peripheri of the frame including boxing for
conduting as per architectural drawings and instructions including cutting,
necessary hardware, drilling, cut out and necessary support for switch boxes and
lightfittings and finish the Ply with 1mm thick approved laminate (Laminate to be
approved by architect before commencement of work) at visible side. All
connections in framework shall be with GI screws of approved quality and cleaning
etc. completed at all floors and heights as specified and directed by Architects/
EIC.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B, I-708
Rmt. 12.00
TENDER DOCUMENT BILL OF QUANTITIES - 26 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
95 Providing & fixing aluminium louvered grill for return air duct with approved colour
power coated matching to the wall texture paint and 50 mm X 65 mm aluminium
box frame as per architectural detailed drawing including louvers, brass fixtures,
fastenings & fittings, necessary back packing, cutting, griding, drilling and cleaning
etc. complete. as specified and as directed by EIC / Architect.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
Sqm. 20.00
96 Providing and doing laminated wooden flooring of approved make and pattern and
as per architectural drawing and instructions. The system shall be comprise with
following.
Wooden Flooring- Providing and fixing 150mm to 200mm and 19mm thick
interlocking wooden planks matching to the existing wooden flooring for stage
fixed on existing base properly as per architectural drwaing and instructions.
including necessary hardware, lipping, moulding, approved quality foam below the
wooden strips, cutting, drilling, finish the strips with approved melamine polish
matching to the existing wooden flooring and cleaning etc. completed as directed
and specified by EIC.
Sqm. 10.00
TOTAL OF WOOD WORKS (PARTITION & PANELLING)
TENDER DOCUMENT BILL OF QUANTITIES - 27 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
J ALUMINUM WINDOW WORK
Note: -
i) The contractor shall submit 6 copies of shop drawings for each windows,
ventilators showing dimension details of construction etc. for approval of the
Engineer - in - charge. And according to the approved shop drawing a sample of
each of windows with all fittings and fixtures with locking arrangement including
glass panes etc. complete as per schedule of quantities, specifications and
drawings, shop drawing should be submitted for preliminary inspection for
approval. After preliminary inspection , the sample should be fixed at site to
ascertain its performance. Large scale manufacturing should be taken up only
after rectification of defects in samples as directed to the full satisfaction of the
department and after obtaining formal approval.
ii) All doors, windows, ventilators section shall be anodized extruded section of
M/s Jindal / M/s Indal or or any other makes specified in the list of approved
makes.
iii) All fittings / fixtures shall be of approved make / quality and as approved
by Architect.
iv) All dimensions mentioned in the drawing are approximate. Necessary
allowance for fixing over rough ground, and also necessary allowances for fixing
tolerances to be considered while manufacturing. While manufacturing, actual
site measurement shall be considered. Necessary planning for fixing the unit has
to be carried out by the contractor without any extra cost to the department.
However, rate quoted by the contractor shall hold good.
v) Payment shall be made per Kg basis.Aluminium sections such as shutter
frames, track window / door frame/beading channel for glass adjustable louvers
etc., shall only be measured linearly as per actual / finished cutting size nearest to
centimeter and multiplied with sectional weight of the individual section and the
total quantity of aluminum section will be arrived at for payment without any
allowance for wastage.
vi) All glass panes shall be of M/s Modi guard or or any other makes specified in
the list of approved makes. The glasses will be measured for payment separately
under relevant item.
vii) Glass panes shall be fixed with approved EPDM gasket ting, beading, to be
free from settling. Necessary polysulphide sealant to be provided against
seepage of rain water.
viii) All top hung/side hung shutters to be provided with approved quality of
stainless steel friction hinges.
ix) In case of damage of any existing work, the same has to be made
good/restored to original condition by the contractor at his own cost.
x) No separate payment shall be made for fittings such as locking arrangement,
hinges,frictionhinges, fittings and fixtures, gasket etc., Tenderer are required to
consider the cost of all fittings, fixtures, locking arrangement , handles, pegstays,
gaskets, screws, hinges etc., while quoting the rate for unit weight of aluminum
sections for window / door except for floor spring, hydraulic door closer and floor
lock will be paid separately under relevant item.
xi) Shall furnish guarantee of one year on a stamp paper for performance of
smooth operation and leakage.
97Supply & fixing in position at all floors integrated Champagne color anodized matt
finished alluminium work work for door, window, ventilator, louver with extruded
builtup standard sections of Jindal / Aluminax or other approved make conforming
IS: 733 & IS: 1285 fixing with dash fastners of required size, including filling up the
gaps at junctions i.e. top, bottom & sides with required EPDM rubber / neoprene /
polysulphide sealant etc. Alluminium section shall be smooth, rust free, straight and
jointed mechanically wherever required, including cleat angle, alluminium snap
beading for glazing / paneling, stainless steel screws all complete.
The Aluminum consisting of followings described as 'under: - All fixing shall be
concealed pvt and/ 'anodized finished as per aluminum.
- EPDM / Neoprene purpose made beading shall be provided.
- Fixing shall be with GI screws.
- All sections shall be extruded.
- All beading shall be snap on type.
- Glazing beading shall be from inside only.
TENDER DOCUMENT BILL OF QUANTITIES - 28 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
- Minimum thickness of glass shall be 6mm when not specified.
Refer Drw. No. I-210, I-211, I-213, I-820, I-830
Sliding Windows.
- Anti-lifting device.
- Bottom rail shall be with self cleaning gutter section unless noted otherwise.
- Stainless steel ball bearings rollers.
- Concealed locking arrangement.
- In louvered windows, extruded sections only shall be used.
- All fitting and fixtures such as lever locks, handles, hinges, concealed tower
bolts, door closer etc. shall be suited to sections and be of approved make. They
shall be finished in matching coating or as approved.
- Supply and fixing of aluminum work shall be carried out from 'approved agency.
- Prior to start of work supplier shall submit detailed full scale
Shop drawings including plan, elevation and detail of fixing with structure for
approval of the EIC. Samples of each item on full
scale or smaller scale as directed by the EIC shall be submitted for approval.
- Work shall proceed only on approval of shop drawing, samples of each extruded
section, neoprene beading, gaskets, wool pile,
fittings and fixtures by the EIC in writing.
- Glazing shall be as noted for each unit in drawing.
97.1 For Fixed portion Kg 180.00
97.2 For shutters of doors, windows and ventilators including providing and fixing hinges
/ pivots and making provision for fixing of fittings wherever required including the
cost of PVC / neoprene gasket required (fittings shall be paid under relevant item)
Kg 190.00
98 Providing and fixing glass panes in windows, doors, at all location and heights of
following thickness etc. all complete as per the directions of the EIC. (Mode of
measurement :-Dimension in length and width of exposed finished surface of glass
panel shall be measured sq.m nearest to 0.01 )
98.1 With 5.0 mm thick clear glass of approved make (fixed panel of windows) Sqm. 5.00
99 Vision Glass - 6mm Solar Low E Refl HS +12mm air Gap +6mm clear float HS.
The glass spectrophotometric properties shall be as follows : Glass appearance -
_______ , VLT- ______ , Solar factor - _____max , shading coefficient - ____max ,
U value - _______ W/m2K
Refer Drw. No. I-210, I-211, I-213, I-820, I-830
Sqm. 20.00
TOTAL OF ALUMINUM WINDOW WORK
K MISCELLANEOUS WORKS
100 Providing and fixing 75mm high Aluminum anodized skirting of Ensemble or any
other equivalent approved make fixed to the wall with 5x25mm counter sunk
screws properly as per manufacturer’s specifications and instructions at given
location with architectural drawing including matching color inner/ outer connector,
end cap, rubber beading, commercila ply backing as per site condition, drilling,
cutting and cleaning etc. completed at floors & levels and as per the instructions of
the EIC. Joints shall be finished properly so that skirting shall look Continuously
and joint less. (Mode of measurement- Running length of the skiring shall be
measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
Rmt. 80.00
101 Providing & fixing Trap door (hinged) of sizes given below with Red Meranti
frame & suspenders (section 50mm x 50mm). Single shutter made out of 19mm
marine plywood & teak wood leaping hinged to the frame as shown in drawing
including P/f allen key lock, hinges, safety chain, necessary hardware, finished with
1.0mm thick approved laminate on one side and synthetic enamel paint ( primer +
3 coats ) of approved make & shade on other side etc. complete as instructed by
the EIC. (Mode of measurements : Area of trap door opening shall be
measured for payment)
Sqm. 5.00
TENDER DOCUMENT BILL OF QUANTITIES - 29 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
102 Providing and doing conbond chemical treatment to damaged RCC portion with
rich concrete and using sunanda or equivalent bonding chemical as per
manufacturar's specifications & instructions.including removing damaged RCC
portion,form-work, compacting, finishing the exposed faces, curing & rate also
included P/d chemical treatment to Reainforcement etc. completed as specified
and as directed by EIC. (Mode of measurements : Only damaged area shall be
measured for payment)
Refer Drw. No. A-200, A-201, A-202, A-502, A-503, A-800
Sqm. 10.00
103 Providing, making and fixing Roller Blinds as per architectural drawing and
instructions made out of approved make and quality fabrics shall be made from
high quality texturised and spun yarn. It should has excellent textile appearance of
translucency, 100% polyster fabric, acrylic coating on both side of fabric, fabric
fixed to the proper location.including necessary hardware, drilling, cutting, powder
coate aluminum clips, rods and pulling rope. two blinds should be over lap to each
other by 150mm. etc. cpmpleted as required as specified by EIC. (Area of the
fabric shall be measured for billing)
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D, I-604E, I-
705A, I-705B
103.1 2) Providing and fixing Blackout Blinds ( Make- Galeecha -CB-04/ NL- 1511 W -
2.4 MT)
Sqm. 25.00
104 Providing and fixing of Wall 25 mm dia SS Curtain Rod with approved Curtains
(- Make -Gujarat furnishing -Mooshy collection design No. 22/ Pride- PR - DS
1004) for Green room of approved colour fixed to the wall properly and SS pipe
shall be fixed to the wall by 50 mm ss flange including necessary hardware,
runners and accessiories, drilling, scaffolding, distance between two folds of curtain
shall not be more than 25mm, and cleaning etc..complete as required as specified
by EIC. (Elevational area of the opening shall be measured for billing)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-703
Sqm. 10.00
105 Providing & fixing in position 40 mm wide 16 guage SS Transition clipping 'T'
patti of approved shape and pattern for flooring joint as per architectural drawing
and instructions including necessary hardware, drilling, cutting as specified and as
directed by Architect. (Running length of patti shall be measured for billing)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B, I-703, I-
709
Rmt. 10.00
Providing, making & errecting False Floor system as per architectural drawings
& instruction. System consisting of concore steel panels, bare steel panels of size
60cm x 60cm with following details. The floor panels made out of hard cold rolled
steel top sheet welded to a formed draw quality steel bottom pan at assembly of
each dome and multiple points along perimeter. The panels shall be internally filled
with lightweight cementitious product (Concore). The floor panels shall be
protected from corrosion by powder coat epoxy paint finish. The understructure
shall be with stringer system with finish floor height (FFH) of 200mm. The system
shall be stringer system provide a range of adjustment upto 35mm total. The
understructure supporting the panel shall be as follows
Refer Drw. No. I-210, I-211, I-213, I-830, I-607A, I-607B, I-706
Pedestal Assembly : Pedestal assembly to provide a means of leveling and
locking the assembly at a selected height which requires deliberate action to
change height setting and which prevents vibrating displacement.
Pedestal Heads : Consist of solid steel stud roll formed and press fitted into head.
Pedestal heads shall incorporate tabs, which accurately align the head with the
panel. The stud shall provide an anti rotation feature and vibration proof locking
device when engaged with the pedestal base assembly.
Pedestal Bases :Fabricated of a square base with not less than 100 cm sq.
assembled to a stud or tube, which is designed to engage the pedestal assembly,
secured to sub floor with adhesive or with screws. The tube shall be 2.22 Sq. Cm.
15.00106 Sqm.
TENDER DOCUMENT BILL OF QUANTITIES - 30 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
System performance: The panels shall be capable of supporting a minimum
concentrated load of 363 kgs. placed on one square inch area at any location with
maximum top surface permanent deflection not to exceed 2.4mm after load is
removed. The panels shall be capable of supporting a minimum uniform load of
1496 kgs. Per sqm. with maximum bottom surface permanent deflection not to
exceed 2.4mm after load is removed. The safety load of the floor system shall
provide a loading capacity of 953 kgs. On a one square inch area at any location
without failure. Failure is defined as the point at which the system will no longer
accept the load. The pedestal a
107 Antitermite Treament - providing & doing Antitermite treatment to wooden surface
such as doorframes, wooden partitions should be spreyed all sides of the wooden
surface with termisile chemical. Chemical mixing and application should be as per
manufacturar's specifications and instructions through approved agency with 15
yrs.Guarantee. solution should spreyed properly on required area. etc. completed
as required as specified by EIC
107.1 Anti-termite treatment to door frames. each 16.00
107.2 Anti-termite treatment to shutters & plan area. Sqm. 935.00
108 Providing, making and fixing in position custom made SS Signages as per
arcthitectural drawings and instructions with approved SS fixtures, approved base
including necessary hardware, farmas etc. complete as per detail drawing, as
specified and as directed by Architect.
108.1 Embossed sign with black paint (230mm x 230mm high in size)
109.1.1 Ladies - (230mm x 230mmc height in size) each 1.00
109.1.2 Gents - (230mm x 230mm height in size) each 1.00
109.1.3 Green Room Ladies- (600mm x 150mm height in size) each 1.00
109.1.4 Green Room Gents- (600mm x 150mm height in size) each 1.00
109.1.5 Fire Room- (600mm x 150mm heigh in size) each 1.00
TOTAL OF MISCELLANEOUS WORKS
TOTAL OF FINISHING WORK
III PLUMBING WORK
A SANITARYWARES & CP APPURTENANCES
Detail of Sanitary fixture are for the information of the Contractor, however model /
makes of all sanitary fixture shall be selected by Architect / Interior designer / client
and the same shall be binding for execution
No additional all fixing cost shall be paid for change in type of sanitary fixture or
fitting.
Provision of extension piece for final connection of CP fitting shall be supplied and
installed by the contractor accordingly (as required)
109 Providing & fixing first quality white vitreous china wall mounting wash basin (size
as per architectural drawing) specially fabricated CI / MS brackets, painted with two
or three coats of enamel paint of approved shade over a coat of primer, 32 mm CP
brass waste and CP brass cast bottle trap and pipe to wall with CP brass flange
and rubber adopter for waste connection complete including and wash basin with
approved type poly sulphide sealant, cutting and making good the walls wherever
required.
each 2.00
110 Providing & fixing following size, approved quality CP brass Waste coupling with
brass check nuts conforming to IS 2963, including jointing with white zinc and spun
yarn and testing the joints for leak proofness all complete.
each 3.00
15.00106 Sqm.
TENDER DOCUMENT BILL OF QUANTITIES - 31 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
111 Providing & fixing following size approved quality CP brass Bottle trap with 32 mm
size & connection pipe upto the wall and wall flanges including jointing with white
zinc and spun yarn & testing the joints for leak proofness etc. complete.
each 3.00
112 Providing & fixing 15 mm dia. CP brass Basin Tap, fixing the cock in position with
inlet connection using white zinc and spun yarn testing the joints to a hydraulic
pressure of 10 kg / Sq.cm for leak proof joints etc. all complete as per
specifications.
each 2.00
113 Providing, fixing, testing and commissioning of C.P. brass angle valve with C.P.
wall flange, Nut and Washer etc. complete as required.
each 3.00
114 Fixing, testing and commissioning of sink including providing & fixing C.I./M.S.
Brackets (duly painted with 2 coats of paint over a coat of primer) C.P. cast brass
bottle trap with extension piece, rubber adaptor, wall flange, union, C.P. brass
chainrubber plug & making good. (wiithout drain board)For pantry area
each 1.00
115 Fixing, testing & commissioning of C.P. brass eurometic self closing pillar tap. each 1.00
116 Fixing push type liquid soap dispenser with PVC rawl plug & C.P. brass screw
complete as required.
each 3.00
TOTAL OF SANITARYWARES & CP APPURTENANCES
WATER SUPPLY SYSTEM
117 Providing, Fixing , Testing & Commissioning of exposed ' C' class GI pipes
conforming to IS: 1239 with specials, fittings, clamps, brackets & internal working,
painted with two coats of enamel paint of approved shade and make, including
holes in walls, floors, R.C.C. slab/ beam and restoration of the same complete in all
respects.
117.1 15 mm dia. Rmt. 25.00
117.2 20 mm dia. Rmt. 25.00
118 Providing high pressure "HP" following size Lever Ball Valve assembly of
approved make (horizontal plunger screw type) conforming to IS 1703 with
brass or gun metal piston, back nut and PVC float, carbon steel handle PVC
coated conforming to IS 9762 and described in technical specifications.
118.1 15mm dia. each 1.00
118.2 20 mm dia. each 1.00
TOTAL OF WATER SUPPLY SYSTEM
B INTERNAL DRAINAGE SYSTEM
119 Spigot and socket centri cast iron drainage pipes & fittings of approved make and
with ISI mark conforming to IS 3989/ 84 for soil, waste pipes including all fittings
(plain or access door) e.g. bends, junctions, cowls, offsets, access pieces etc.,
jointed with lead joints, fixed with M.S. clamps & brackets including holes in
wall/floors and restoration wherever required as mentioned in technical
specification. (For Waste drainage)
119.1 80 mm dia Rmt. 50.00
119.2 50 mm dia Rmt. 5.00
120 Providing and fixing in position G.I. pipe and fittings of heavy class (c)
conforming to IS:1239 (for waste pipe from individual fixtures to floor trap / floor
drain & vent pipe) Including fixing at wall / ceiling level supported by galvanized
clamps and hangers providing two coats of synthetic enamel paint of approved
shade as per pipe colour code over a coat of primer or cutting & chasing in wall &
floors, providing protection to embedded GI pipes & fittings by wrapping of 400
microne polythene sheet over two coats of bitumen including proper overlaps in
joints complete as required and making good the chase by using 1:1 cement
mortar.
120.1 32 mm dia. Rmt. 12.00
120.2 40 mm dia. Rmt. 10.00
121 Providing and fixing in position 75 mm N.B. CI. Nahni traps of self cleaning design
including 125 mm dia CP grating, joining, embedding in concrete etc. complete.
Rate to include making of opening in floor, marble / tiles, for fixing grating.
each 3.00
TENDER DOCUMENT BILL OF QUANTITIES - 32 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
122 Providing and fixing Heavy class SS grating with Cockroach proof SS strainer of
approved design including setting in floor with cement motor to match with floor
finish as per architect requirement & suitable for waste and FD.
122.1 100 mm dia. each 3.00
TOTAL OF INTERNAL DRAINAGE SYSTEM
TOTAL OF PLUMBING WORK
IV FIRE ALARM SYSTEM & PUBLIC ADDRESS SYSTEM
A FIRE ALARM SYSTEM
Note:
The rate of each item of work for Fire Detection and Alarm System shall also
include the following :
1. Permission & NOC from statutory authorities, Inspection and Fees for Chief Fire
Officer, Any kind of Liasioning work with Authorities will be Re-embussed on
provision of Original Receipt
2. All Detector & Devices Mounted on TRUE Celling/Concealed in WALL will be on
metal Powder coated Junction Box 2mm thick with Glanding
3. All materials, fixing materials, accessories, appliances, tools and equipment.
4. Approved cover plates for inspection, junction and outlet boxes.
5. 2 mm thick outlet boxes and junction boxes.
6. All fixing accessories such as clips, nails, screws etc.
7. Providing and fixing approved saddles, hooks and grouting the same as
required, in the case of all exposed cable work.
8. Testing and commissioning of each device, circuit as per the requirements of
NFPA 72, TAC, local authorities and to be witnessed by the PMC / Consultant /
Client.
123SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF OF THE
FOLLOWING EQUIPMENT/ Devices FOR FIRE ALARM SYSTEM
123.2 Adressable Control modules For Fans, AHU Tripping & Fire Exhaust /smoke
Extractas activation per specification
each 3.00
123.3 Adressable Monitor modules.as per specification each 2.00
123.4 Intelligent Analogue addressable photoelectric type smoke detector with mounting
base, LED, Address switch, complete as per specifications
each 8.00
123.5 Intelligent addressable rate of rise cum fixed temperature heat detector with
mounting base, LED, address switch complete as per specifications
each 1.00
123.6 Intelligent Analogue addressable photoelectric type beam detector with mounting
base & reflector, LED, Address switch, complete as per specifications
each 2.00
123.7 Addressable type manual Break glass (Pull station) unit as per specifications each 2.00
123.8 Surface mounted addressable type fully solid state circuitory dual tone Electronic
loud speaker type hooters with strobe lights of 110 Cd intensity as per
specifications
each 2.00
123.9 Addressable Fault Isolation Module as per specifications each 1.00
124.10 Response Indicator as per Specification each 1.00
123.1 Multi Loop Microprocessor based 1 loops (each loop shall be able to connect
minimum 124 detectors and 124 modules) intelligent, analogue addressable type
fire alarm control panel which can acomodate max 10 loops in each panel with 80
character LCD display, four access levels, 400 event historical logging, flash
EPROM sufficient numbers of programmable relay controls, 240 volts AC power
supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for
24 hours normal working and then be capable of operating the system for 2
hours during an emergency condition including all necessary software for
remote programming of fire alarm system through central control station.The
materials, appliances, equipment and devices shall be listed by a nationally
recognized approvals agency like UL864/FM/EN54 for use as part of a protected
premises protective signaling (fire alarm) system and smoke control system FACP
panle should be with standalone UPS (Location -COMMON AREA AT GROUND
FLOOR LEVEL)
Lot 1.00
TENDER DOCUMENT BILL OF QUANTITIES - 33 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
TOTAL OF FIRE ALARM SYSTEM
B CABLES & ACCESSORIES
CABLES & ACCESSORIES FOR FAS
Note : All the items from Fire alarm control panel, Repeater Panel, Monitor
module, Control module, Smoke detector, Heat detector, Multicrieria type smoke
detector, Manual break glass unit, Hooter, Fault isolation module,Telephone Jack,
Responce indicator and Magnetic door condact mentioned above shall be termed
as Devices for the cable measurement purpose. Outgoing cables from Control
module & monitor module will not be measured seperately.
124 Per Device 25.00
TOTAL OF CABLES & ACCESSORIES
TOTAL OF FIRE ALARM SYSTEM & PUBLIC ADDRESS SYSTEM
V ELECTRICAL WORK
GENERAL NOTES
Required clearances from the concerned statutory authorities are in the scope of
this work.Statutory fees paid will be reimbursed on production of original receipts in
the name of IITB.
A POINT WIRING IN PVC CONDUIT, TELEPHONE WIRING, T.V WIRING ETC.
125 Point wiring in PVC conduit (HMS variety)
Point wiring for light/ceiing fan/6A/ 16A/ socket outlet /6A outlet for exhaust fan,
bell point etc. with 1.1 KV grade FRLS PVC insulated multistranded copper
conductor wire(ISI marked), in 25 to 40 mm dia High mechanical stress (HMS) rigid
PVC conduit having ISI marked IS 9537 Part - 3, including fixing accessories &
hardware concealed /exposed in slab/wall or on 5mm. thick G.I. spacers fixed with
no. 10 nettle within the box piece fold wood screws with nylon plug complete with
all conduit accessories 20 SWG G.I. Saddles, ready made MS modular
switchboxes, socket outlet boxes of approved makes including termination inside
sw/sockets with using copper lugs ,zinc chromate passivated, brass earthing stud
1/2 nos, controlling modular switches, sockets with moulded front plate and inner
plate etc. including appropriate size of FRLS PVC insulated copper earth wire,
brass/bakelite (straight / angular) lamp holders, 3 plate ceiling rose,16 A,
connectors, painting etc. as per specifications and drawings and as directed by
E.I.C.and as detailed below : (sample switch Box etc. to be got approved before
fabrication)
NOTE:
1. Connections shall be done with crimped type tinned copper lugs & washers.
2. All switches & socket outlets shall be as per preferred makes.
3. All 16 A socket outlets should be with 6 pin & shuttered type
4. MS boxes other than switch boxes & socket outlet boxes shall be fabricated out
of 16 SWG thickness MS sheet duly painted with red oxide primer & 2 coats of
synthetic enamel paint.
Supplying, terminating, testing and commissioning of cabling for fire detection and
alarm system with 2C x 1.5 sq mm annealed tinned copper conductor Red
coloured PVC sheathed FRLS armoured cables as per specifications. FR grade
and ISI marked as per relavent IS standards and specifications. Cables shall be
estimated as per the drawings. Cabling for response indicator/ power
/communication cable shall not be considered seperatelyas device. The cost of the
same shall be included in the unit rate estimated for per device. Laying supervision
is under IBMS contractor scope. Cabling for response indicator/ power
/communication cable shall not be considered seperatelyas device. The cost of the
same shall be included in the unit rate estimated for per device(i.e.Cable from
FACP panel to First Detector/device ,Last Detector/device & return to Panel
,Detector to detector/device,Power from Hooter to Hooter and FACP panel l)
TENDER DOCUMENT BILL OF QUANTITIES - 34 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
5. Minimum size of the FRLS insulated copper earth wire continuity shall be 2.5
sq.mm.
6. The colour shade of switches & cover plates shall be white /off white & to be
approved by architect.
7. The scope also includes supply of modular blanking plates where ever required.
8. The maximum permissible number of PVC insulated wires through PVC conduits
shall be as per Tech Specs.
9.Test certificates shall be provided along with delivery of wires.
10. In case of Primary point controlled by switch,cost shall include wiring from DB
to switch board, Switch board to Occupancy sensor (Toilet blocks) & any looping
from Switch board to Switch board shall be part of point wiring .
11. Light point wiring cost shall include connection of fixture from ceiling rose with 3
core 1.5sqmm copper flexible cable.
125.1 Ceiling Mounted Lights In Sitting Area
126.1.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 18.00
126.1.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 56.00
125.2 Step Lights On Chair
126.2.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 6.00
126.2.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 70.00
125.3 Color Lights On Stage
126.3.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 2.00
125.4 Auditorium Foot Lighting
126.4.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 2.00
126.4.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 10.00
125.5 Post Function Area Lighting
126.5.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 1.00
126.5.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 8.00
125.6 Room Lighting
126.6.1 Wiring with 25mm dia HMS FR PVC conduit embedded or surface mounted as
including cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab,
cutting chasis and making good wherever called for or surface mounted including
all fixing hardware along with 3 nos - 2.5 sq.mm PVC insulated multi stranded
flexible FRLS copper wires from DB to Switch board near the entrance of room
and necessary accesories required to complete the job in an approved manner as
per instruction of Engineer In Charge as per specification. (As per scheme &
layout)
Pt 5.00
126.6.2 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires operated from 6A switch including cost of ceiling rose &
flex.wire as per specification.Only point wiring cost to be considered.
Pt. 7.00
126.6.3 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 12.00
125.7 Pre Function Area
126.7.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 5.00
126.7.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 25.00
125.8 Cove Lighting
TENDER DOCUMENT BILL OF QUANTITIES - 35 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
126.8.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
Pt. 2.00
126.8.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm
insulated earth wire looped to item above as per specification.
Pt 6.00
TOTAL FOR POINT WIRING IN PVC CONDUIT, TELEPHONE WIRING, T.V
WIRING ETC.
B LIGHT FIXTURES AND FITTINGS, CEILING FANS, EXHAUST FANS ETC
126 Light Fixtures & Fittings:
Supply, installation, testing & commissioning of fixtures & fittings, ceiling fans,
exhaust fans, etc. complete with accessories, tube/lamp etc in on surface of
slab/beam by 2 nos (minimum) of 6 mm anchor fasteners or on wall with 2 nos of
wood screws, nylon plug etc., suitable supporting frame fixed with rag bolts grouted
on the wall/anchor fastener on the beam/on the column & other fixing accessories
etc provision & connection with 1.5 sq.mm multistranded copper conductor FRLS
PVC wires etc., all as per drawing, specifications & as per the instruction of E.I.C.
Note:
1) Sample fixture/fittings shall be got approved from Department and Architects
with complete technical data.
2) The Cat No. indicated below is only indicative.
3) Cost of lamps to be included in installation rate.
4) All fixtures shall be with low loss electronic ballast
5) T5 High Efficiency Lamps control Gear with 10% Total harmonic distortion
(THD)
126.1 Philips Make 1X 70 W CDMT MSB 150 HF downlighter each 33.00
126.2 Philips Make 2X26 W PL-C/2P FBH225 downlighter (with dimmable ballast) each 37.00
126.3 Philips Make 1X28 W T5 V2 VECTOR TCH207 strip fitting each 30.00
126.4 Philips Make 1X70 W BCG 530 Stage track light with tracks as per drawings. each 8.00
126.5 Philips Make 1X11 W FOOT LIGHT BWG 150 each 12.00
126.6 Prolite Make 1 X 11 W PLE 111 E/NM emergency EXIT signage light with
Maintainance free batteries for 3hrs Backup
each 4.00
126.7 Philips Make 1X3 W STEP LIGHT(Only lamp with ballast) each 72.00
126.8 Philips Make 1X18W PL Circular down lighting FBS 085 each 14.00
126.9 Philips Make Colorblast Powercore RGB Stage Light (Procenium Mounting) each 2.00
127.10 Philips Make white LED strip light with driver for cove lighting Rmt. 75.00
127.11 DIN Rail mount, 12-Channel Ballst Controller, suitable for 0- of Make-
Philips.programmable. Input Power: 1-Phase, 220VAC, 50Hz. To be connected
dimming along with suitable type of dimmable ballst. All the 10VDC/DSI/DALI
Broadcast type (DDBC1200)
each 1.00
127.12 DIN Rail mount, 12-Channel Relay, suitable for 20 A (inductive) On/Off control per
channel.Total 12 Chanel Relay capable of 180 A load. All the Channels are
independentlyprogrammable. Input Power: 1-Phase, 220VAC, 50Hz. To be
connected on Dynet network.Make-Philips.(DDRC1220FR-GL)
each 1.00
127.13 Smart switch location to be sujested by Architect / Client .Low-voltage, User
interface keypad with 7 Buttons, Standard steel Finish.(DUS 804C)
each 3.00
127.14 Multi Sensor for IR Receiver, motion control.The operation of sensor is Subject to
Height of False Celing. Ideally it is suitable for 2.5 Meter height.
each 2.00
127.15 IR Handheld remote. (DTK 508) each 1.00
127 Supply, installation, testing & comissioning of following ceiling fans with double ball
bearing with standard downrod, canopies, shackles, blades with safety cable
suspension (Secondary support safety cable) white colour with all accessories
including continous earthing and final connection with 24/0.2 mm dia copper
conductor 2/3 core twisted PVC flexible wire etc but without speed regulator,
suitable for operation on any type of 100 W noise free capacitor type fan regulator
on 230 V 50 Hz single phase AC supply conforming to IS 374/79 with latest
amendments all as per specifications & instructions of E-I-C.
127.1 1400 mm sweep ( High Breeze Cropton make ) each 1.00
TENDER DOCUMENT BILL OF QUANTITIES - 36 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
127.2 Wall Mouting Fan each 2.00
127.3 Fan Hook Boxes
128 Supply, installation, testing of concealed fan hook boxes of size 125 x 125 x 75mm
deep fabricated out of 2mm thick M.S CRCA sheet with 12.5 mm dia M.S tested
rod hook with brass earthing stud & welded nut from inside and 2mm thick round
M.S cover plate overlapping by 10 mm, including red oxide and two coats of white
synthetic enamel paints and brass chromium plated screws and cup washers for
fixing and instruction of Engineer-in-charge (Sample box with cover to be got
approved before fabrication including the fabricator)
each 1.00
TOTAL OF LIGHT FIXTURES AND FITTINGS, CEILING FANS, EXHAUST
FANS ETC
C POWER POINT WIRING
129 Power Point Wiring FRLSom DB MCB to 16A socket outlet with 2 x 4.0mm2 + 1 x
2.5mm2 stranded/flexible copper wires with FRLS type PVC insulation as per IS
694 latest for primary point and 2 x 2.5mm2 + 1 x 1.5mm2 stranded/flexible
copper wires with FRLS type PVC insulation as per IS 694 latest for secondary
point; 25 mm Dia. MS conduit and accessories such as couplers, bends, junction
boxes, inspection elbows. Conduits shall be installed or cleated surface to ceiling
or wall with saddles or spacers; installed concealed in walls or floor as required and
as directed by the project incharge and as indicated in the approved shop
drawings. Rate shall include supply and installation of the following items:
1) 1.6/2.00mm, 25 mm Dia. PVC MMS conduit
2) Copper/PVC FRLS wires.
3) Associated civil works such as chasing the wall or floor and making good to
rough finish with plaster so that the conduit is properly concealed.
129.1 S/I/T/C of Primary point 6A modular type switched socket outlet complete with
flush mounting GI back box with earth terminal, civil works and making good to
rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.
each 10.00
129.2 S/I/T/C of Secondary Point 6A modular type switched socket outlet looped
FRLSom above point complete with flush mounting GI back box with earth
terminal, civil works and making good to rough finish plaster so that the box is lined
and levelled.
each 10.00
129.3 S/I/T/C of Primary point of 6/16A modular type switched socket outlet complete
with flush mounting GI back box with earth terminal, civil works and making good to
rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.
each 15.00
129.4 S/I/T/C of Secondary Point 6/16A modular type switched socket outlet looped
FRLSom above point complete with flush mounting GI back box with earth
terminal, civil works and making good to rough finish plaster so that the box is lined
and levelled.
each 26.00
129.5 AC Points
130.5.1 S/I/T/C of Primary point of 20A modular type switched socket outlet complete with
flush mounting GI back box with earth terminal, civil works and making good to
rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.(for AC)
each 4.00
129.6 UPS Points
130.6.1 S/I/T/C of Primary point of 6/16A modular type switched socket outlet complete
with flush mounting GI back box with earth terminal, civil works and making good to
rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.(ups primary point)
each 16.00
130.6.2 S/I/T/C of the 6/16A modular type switched socket outlet looped FRLSom above
point complete with flush mounting GI back box with earth terminal, civil works and
making good to rough finish plaster so that the box is lined and levelled. (ups
secondery point )
each 29.00
129.7 Telephone Point Wiring:
TENDER DOCUMENT BILL OF QUANTITIES - 37 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
130.7.1 Point wiring with 4 pair 0.50 sq.mm. Telephone copper conductor PVC insulated, in
25-40mm dia rigid FR-PVC conduit modular box (HMS variety - ISI
marked,conforming to IS 9537 Part-III) concealed in slab /wall or surface with 5mm
thick G.I.spacer & 20 SWG GI Saddle fixed with nylon plug, wood screws etc.
complete with all conduit accessories suitable MS pull boxes of suitable sizes as
per site condition wherever required M.S. telephone point accessories boxes
fabricated out of min 18 SWG thick CRCA sheet zinc chromate passivated, brass
earthing studs 1/ 2 nos., RJ-11 telephone socket outlets with shutter ferrule
numbers on both side of the circuits all terminations with ferrule /lugs if required,
labelling all as per drawing specifications & as per instructions of E-I-C. as per
specification.
NOTE:
1. Point wiring means 4 pair 0.50 sq.mm wires from Telephone Tag Block in
Tel/LAN shaft to the assigned point including end termination of one pair at both
sides and other pairs should be kept spare.
2. G.A drawings & fabrications drawing are to be got approved from E-I.C.
3. Approved makes for Telephone wire : FINOLEX / ITL/ POLYCAB
130.7.2 Point wiring for telephone point with 4 pair 0.50 sqmm wire with RJ 11 jack type
socket with shutter in a box with connector as per specification.
Pt. 4.00
129.8 Supply, installation, testing & commissioning of following Krone connector
telephone tag block box, readymade 18 SWG MS CRCA sheet, concealed/surface
mounted on MS frame of size 40 x 40 x 5mm and grouted on the wall/fixed on the
column free standing type with anchor fasterners, cable end/wire way box with
adequate space facility to be provided in the TTB, with front operable hinged door,
cam type locking arrangement, neoprene rubber/cork gasket for joints, ring type
wire bunching clamps at 4 corners, name plate etc. all as per standards,
specification, drawing & instructions of E.I.C as per specification.
Note:
1) Point distribution diagram shall put in side the DB with polythene protective
cover.
2) All fabrication drawings shall be got approved.
3) Final coat of painting shall be done at site after installation if required.
4) Disconnection module shall be Krone Part No. 69011006-02 or as specified in
the list of approved makes.
10 pair telephone tag box : Set 1.00
A set consisting of :
1) Disconnection module 2 /10 --> 1 nos.
2) Back mounting frame 2/10, 1 way suitable for mounting 1 no's of 2/10
modules. -->1nos (C.T. box with mounting bracket)
3) Transparent dust cover --> 1 no. complete with all accessories
4) Label Holder - 1 no
TOTAL FOR POWER POINT WIRING
D UPS
130 Supply, installation,testing and commissioning of 10 KVA online UPS System
(Three Phase In & Single Phase Out) with Inbuilt SMF batteries and 15 minutes of
battery backup.
each 1.00
131 Supply, installation,testing and commissioning of following MCB's in powder coated
enclosures.
131.1 32A 4P MCB 'C' curve each 1.00
131.2 63 A DP MCB 'C' each 1.00
132 Supply, installation,testing and commissioning of following sizes of stranded FRLS
copper wire inside flex.PVC conduits including termination at both the ends. (
MCB's mentioned in item no.2 & UPS terminal box.)
132.1 4 sq.mm. x 4 nos in 32 mm Flex. PVC conduit ( for incoming) Rmt. 2.00
132.2 10 sq.mm x 2 no's in 25 mm Flex.PVC conduit for Outgoing. Rmt. 2.00
TOTAL FOR UPS SYSTEM
E DISTRIBUTION BOARDS
READYMADE DISTRIBUTION BOARDS
TENDER DOCUMENT BILL OF QUANTITIES - 38 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
133 Fabrication, inspection at works Supply, installation, testing & commissioning of
following readymade distribution boards, double door, IP 42 degree protection
complete with necessary, MCB isolators, MCBs, earth leakage circuit breaker
(ELCB) etc including interconnections with appropriate capacity size of PVC
insulated copper conductor wires (ISI marked),suitable for concealed mounting
/wall mounting with MS frame work of 40 x 40 x 5 mm MS angle iron, with M.S.
enclosure fabricated out of min 16 SWG thick M.S. CRCA sheet with concealed
hinged door, locking arrangement etc. including earthing clamps for both incoming
& outgoing circuits, interconnections, per phase isolation kit as required,cable end
box & wire way box if required, continuous copper earth wire in the wire way box
with single/duplicate brass earthing terminals, danger board, name plate, flexible
earthing for the door, metal treatment & powder coated painting, Phase Distribution
drawing etc. all as per drawings (G.A. & fabrication drawing to be got approved),
etc. relevant IS & instruction of Engineer-in-charge.
Note:
1.MCBs shall be minimum 10 KA breaking capacity (Type –C)
2. Blanking Plates shall be included in scope of work.
3. DB shall be of standard readymade type as per catalouge No. from approved
manufacturers as indicated in preferred makes of material.
4. Wire way & cable end box also end & locking plates shall be provided.
5. Routine tests will be conducted at factory in presense of user as per relevant IS.
All Electrical component should have IS mark
Note:
133.1 DB :(12way TPN DB) Set 2.00
a) 63 A 4P MCB as incomer -- 1 No.
b) 63 A, 2 pole RCCB with 30mA sensitivity - 3Nos.
c) 6 - 32 A SP MCB -- 36 nos
d) 12 way brass neutral links -- 4 Sets.
e) Brass earth links - 1 Sets
e) Brass earth links - 1 Sets
133.2 UPSDB (AV System) Set 1.00
16Way SPN Emergancy Lighting Distribution Boards comprising of:
Incomer:63A DP MCB
16 nos. of 10/16/32A SP MCB C curve, 10kA
Enclosure IP 43 double door PPI Kit
TOTAL OF DISTRIBUTION BOARDS
F L.T.CABLES, END JOINTS & CABLE MARKER
134 LT. Cables
Supply, handling, laying effecting proper connections testing and commissioning of
following sizes of 1.1 KV grade PVC / XLPE core insulated, extruded PVC inner
sheath, armoured / unarmoured extruded outer sheath FRLS PVC, Copper /
Aluminium conductor cables as per IS 7098 Part I laid over MS supports, cable
racks, trenches, or fixing on walls including clamping the cable to supports in an
approved manner along with cable . (Earthing will be measured separately and
need not be quoted under this item). All complete as required and as per final
instruction as given by E.I.C / Consultants.
134.1 4 C x 10 sq.mm., XLPE Al. Armoured cable Rmt. 40.00
134.2 3 C x 10 sq.mm., XLPE Al. Armoured cable Rmt. 80.00
135 CABLE TERMINATION
Supply and making terminal joints for the following sizes of 1.1KV grade PVC /
XLPE Insulated armoured / unarmoured Copper / Aluminium conductor cables
including providing heavy duty bimetallic, crimping type terminal lugs wherever
Aluminium conductor cables are used Copper Gland Earthing as directed by E.I.C.,
insulation tape, heavy duty double compression type brass glands effecting
terminal connection to the equipment/Panel complete as required as per final
direction and approval of the Owner/Consultant.
135.1 4 C x 10 sq.mm., XLPE Al. Armoured cable each 4.00
135.2 3 C x 10 sq.mm., XLPE Al. Armoured cable each 2.00
TOTAL FOR L.T.CABLES, END JOINTS
TENDER DOCUMENT BILL OF QUANTITIES - 39 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
G EARTHING SYSTEM
136 Supply, installation, testing & commissioning of earthing system & associated
accessories, etc. complete all as per the instructions of E.I.C.
Note :
1) Measurements of resistance of each earth station & resistance of complete
scheme of earthing layout must be measured recorded & got approved by E.I.C.
2) Jointing of the earth strip shall be with brass nuts bolts and also with solder
joints.
3) Jointing of the earth wire shall be with solder joints with tinned cable sockets
136.1 Supply & making Tinned Cu. earth plate electrode 600 X 600 X 3.15 mm earth
station 2.5 m below ground level conforming to IS 3043 including 2 nos of 50 x 6
mm Copper earth strips from earthing plate upto the ground level inside the
chamber with all required materials like coke /charcoal, salt, brass nut-bolt &
washers, watering arrangement, G.I. Pipe (B class) concrete chamber of 450mm x
450mm x 450mm deep, thick chequered plate hinged cover with locking
arrengement mounted on 40x40x5 mm thick angle iron frame & excavation in all
types of soil in ground refilling & removal of excess earth within radius of 2 km.
within IITB campus etc.
each 2.00
NOTE
1) The chamber cover & frame shall be hinged type & it shall be got approved by
department.
136.2 Supply & Laying Tinned copper earth wire/earth strip fixed on wall/side of
trench/slab /column /beam/ shaft connection to panel/DBs/SFU's etc. with 5mm.
Thick G.I. Spacers & 2mm thick G.I. Saddle
137.2.1 32 x 6 mm thick tinned copper tape. Rmt. 30.00
137.2.2 25 x 3 mm thick tinned copper tape. Rmt. 20.00
137.2.3 8 SWG Copper wire Rmt. 50.00
136.3 Supply & Laying of following earthing tapes in already laid hume pipes with
interconnection of earth strip/wire with brass bolt, nuts & washers & solder jointing.
137.3.1 32 x 6 mm thick tinned copper tape. Rmt. 20.00
137.3.2 25 x 3 mm thick tinned copper tape. Rmt. 30.00
TOTAL OF EARTHING SYSTEM
TOTAL OF ELECTRICAL WORKS
VI HVAC WORK
137 Supply, Installation, Testing & Commissioning of Double Skin Air Handling Unit
25mm thick panel as per Tech.specifications.
each 1.00
Outer Skin : GSS 0.63mm Preplasticised
Inner Skin : GSS 0.63mm Plain
6RD Dx. Cooling Coil with 3 independent circuits / 48TR Capacity
MERV 13 Filters
Plug type / Backward Curved Fan of 11200 CFM
TEFC Induction Motor EFF1
Insulated SS Drain Tray
138 Supply, Installation, Testing & Commissioning Prefabricated Rectangular 120GSM
GSS Ducting + Rolamate Flanges + Proper Supportiong arrangement
138.1 22G Sqm. 220.00
138.2 18G Sqm. 50.00
139 Supply, Installation, Testing & Commissioning Prefabricated Round 120GSM GSS
Ducting + Flange less joints + Single Hanger Supporting arrangement
139.1 22G Sqm. 90.00
140 Supply, Installation, Testing & Commissioning Duct Thermal Insulation 25mm
Closed Cell Nitrile Rubber for Exposed Ducts covered with 24G Al.Cladding
Sqm. 195.00
141 Supply, Installation, Testing & Commissioning Duct Acoustic Insulation using
25mm thick Open Cell Nitrile Rubber
141.1 ARMASOUND covered with 28G Al.Perforated Sheet Sqm. 360.00
TENDER DOCUMENT BILL OF QUANTITIES - 40 SIGNATURE AND SEAL OF TENDERER
INDIAN INSTITUTE OF TECHNOLOGY BOMBAY REFURBISHMENT OF P.C. SAXENA AUDITORIUM
INSIDE I.I.T.B CAMPUS
Sr. No. Description Unit Qty Rate Amount
142 Supply, Installation, Testing & Commissioning Sound Attenuator to maintain sound
pressure at 45 dB A
142.1 W1100 x H1100 x L 1200 each 1.00
142.2 W1400 x H1400 x L 1200 each 1.00
143 Supply, Installation, Testing & Commissioning Motorised Smoke & Fire Damper
with Sleeve & Comprising of following,
Sqm. 4.00
143.1 ON/Off Spring Return Actuator of 10NM each 2.00
143.2 Fire Damper Electrical Panel each 2.00
143.3 CO2 Sensor each 1.00
144 Supply, Installation, Testing & Commissioning Motorised Modulating VCD for Fresh
Air & Comprising of following,
Sqm. 3.00
144.1 Modulating Actuator 10NM each 1.00
144.2 CO2 Sensor each 1.00
144.3 Electrical Panel each 1.00
145 Supply, Installation, Testing & Commissioning GSS VCD for Round Duct Sqm. 2.00
146 Supply, Installation, Testing & Commissioning Propeller Exhaust Air Fan of 1000
CFM / 10mm st. with Gravity Louver
each 4.00
147 Supply, Installation, Testing & Commissioning Extruded Aluminum Powder Coated
Flush Type four side flange Grille with VCD for Round Ducting
each 30.00
500mm x 150mm Ht
148 Supply, Installation, Testing & Commissioning Linear Continuous Grill for Return
Air 300mm wide
148.1 300mm wide Rmt. 54.00
148.2 600mm wide Rmt. 7.00
149 Modification of Existing MS Refrigerent Piping with Recharging of R22 as per the
drawings.
Lot 1.00
150 Dismantling of Existing GSS Ducting & lifting / shifting to a location as mandated
by IITB within the campus of IITB.
Lot 1.00
151 Dismantling of Existing AHU & shifting it to a location as mandated by IITB within
the campus of IITB.
Lot 1.00
152 Supply, Installation, Testing & Commissioning Cassette Type Split Unit of 2 TR
with Copper Piping upto 10mtr Distance with Scroll Compressor
each 2.00
153 Supply, Installation, Testing & Commissioning Hi Wall Type Split Unit of 1.5 TR
with Copper Piping upto 10mtr Distance with Scroll Compressor
each 1.00
TOTAL OF HVAC WORK