16
-1- INCREASING THE DUCTILITY OF REINFORCED CONCRETE PANELS TO IMPROVE BLAST RESPONSE Patrick Trasborg Ph.D. Student, Lehigh University 117 IMBT Labs, ATLSS Dr, Bethlehem PA 18015 610-758-6254, [email protected] Pierluigi Olmati Ph.D. Student, Sapienza Università di Roma Via Eudossiana 18 - 00184 Rome (ITALY) +39-06-44585224, [email protected] Clay Naito Associate Professor, Associate Department Chair, Lehigh University 117 IMBT Labs, ATLSS Dr, Bethlehem PA 18015 610-758-3081, [email protected] ABSTRACT Government facilities and military installations have always been prime targets for terrorists. To protect occupants within, these structures are required to meet minimum blast loads. With a dramatic shift towards considering life cycle and environmental footprint of buildings, these structures must also meet criteria for LEED certification. Sandwich wall panels are ideal systems to satisfy both requirements; however, due to their slender geometry, wall panels do not form the same resistance-functions as their more stout reinforced concrete counterparts. This paper reviews blast design methodology and the U.S. Army’s damage level criteria for reinforced concrete members controlled by flexural failure. To improve slender concrete component’s behavior under blast loading, locally unbonding longitudinal reinforcement is investigated both experimentally and numerically. Developed from numerical models, an analytical model is devised to aid in the design of locally unbonded panels. KEYWORDS Blast Design, Precast Wall Panels, Local Unbonding, Improving Ductility

INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

  • Upload
    others

  • View
    16

  • Download
    0

Embed Size (px)

Citation preview

Page 1: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-1-

INCREASING THE DUCTILITY OF REINFORCED CONCRETE PANELS TO

IMPROVE BLAST RESPONSE

Patrick Trasborg

Ph.D. Student, Lehigh University

117 IMBT Labs, ATLSS Dr, Bethlehem PA 18015

610-758-6254, [email protected]

Pierluigi Olmati

Ph.D. Student, Sapienza Università di Roma

Via Eudossiana 18 - 00184 Rome (ITALY)

+39-06-44585224, [email protected]

Clay Naito

Associate Professor, Associate Department Chair, Lehigh University

117 IMBT Labs, ATLSS Dr, Bethlehem PA 18015

610-758-3081, [email protected]

ABSTRACT

Government facilities and military installations have always been prime targets for terrorists. To

protect occupants within, these structures are required to meet minimum blast loads. With a

dramatic shift towards considering life cycle and environmental footprint of buildings, these

structures must also meet criteria for LEED certification. Sandwich wall panels are ideal

systems to satisfy both requirements; however, due to their slender geometry, wall panels do not

form the same resistance-functions as their more stout reinforced concrete counterparts. This

paper reviews blast design methodology and the U.S. Army’s damage level criteria for

reinforced concrete members controlled by flexural failure. To improve slender concrete

component’s behavior under blast loading, locally unbonding longitudinal reinforcement is

investigated both experimentally and numerically. Developed from numerical models, an

analytical model is devised to aid in the design of locally unbonded panels.

KEYWORDS

Blast Design, Precast Wall Panels, Local Unbonding, Improving Ductility

Page 2: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-2-

PROJECT MOTIVATION

Government facilities, military installations, and civilian buildings alike have been and will

continue to be targets in terrorist attacks. The vehicle borne improvised explosive device

(VBIED) has become a prominent delivery method for attacking both domestic and foreign US

structures due to their high power and relative ease of deployment. The 1995 Oklahoma City

Bombing serves as a testament as to how devastating a VBIED can be. In addition to intentional

explosions, many industrial facilities are at risk of accidental detonations due to various

manufacturing processes that deal with sensitive materials. All of these buildings have blast

design requirements that must be met in order to ensure the safety of the occupants within.

In recent times, there has been a dramatic shift towards considering the life cycle and

environmental footprint of buildings constructed in the United States. Today, many state and

government agencies either encourage or mandate that newly constructed buildings attain a

minimum Leadership in Energy and Environmental Design (LEED) certification. An effective

and popular method to decrease operating costs and reduce the environmental impact of a

structure is to install a thermally efficient building envelope. Thus, in addition to meeting

thermal requirements, envelopes for government and military structures must also meet rigorous

blast criteria.

BACKGROUND

Concrete components can either be fabricated on-site (cast-in-place) or off-site in a factory

(precast). Cast-in-place requires that formwork (often lumber) be constructed in the

component’s final resting position and then stripped once the concrete has cured. Precast

components allow the piece to be built with reusable formwork (often steel) and after the

concrete has cured, the component is shipped to the construction site.

Precast concrete has many advantages over the cast-in-place concrete counterpart. The final

condition of a concrete product is highly sensitive to environmental conditions during the curing

process. The more finely controlled the environment is (such as humidity, temperature,

hydration effects, etc), the better control of the final condition of the concrete. For this reason,

precast components are often more aesthetically pleasing than cast-in-place components.

Additionally, precast concrete can often be more economical than cast-in-place concrete.

Formwork is generally the controlling factor in the cost of a concrete component, often making

up more than 60% of the total cost for construction of the concrete piece. As precast components

can be made with the same formwork repeatedly, the cost for constructing the component drops.

Finally, precast components will often allow for a more efficient construction process and

decrease the total construction time. Precast components are fabricated in the factory, shipped to

the work site, and then are placed into position while formwork would have to be built and time

for curing of concrete for cast-in-place components.

A precast component utilized prominently to create an energy efficient building envelope is the

sandwich wall panel. Sandwich wall panels are composed of two concrete layers (wythes)

Page 3: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-3-

separated by a layer of insulation (1). Due to the separation of the concrete wythes by the layer

of insulation, the wythes may not act together (compositely) in resisting flexural demands when

an out of plane load is applied. In order to create a system that acts compositely, mechanical

connectors (shear ties) are placed throughout the length of the panel that connect the exterior

wythe to the interior wythe. The number and stiffness of the shear ties dictate the degree to

which the panel acts compositely.

BLAST DESIGN METHODOLOGY

This paper will focus on far-field detonations that tend to create a uniform pressure distribution

across the face of the component and cause a flexural failure mode as opposed to close-in

detonations that tend to cause localized effects such as spall and breach. Typical blast design

methodology utilizes time stepping methods to solve the differential equation of motion in order

to predict the response of the reinforced concrete component to the blast loading. In many cases,

structural components subjected to blast load can be modeled as an equivalent single degree of

freedom (SDOF) mass-spring system with a non-linear spring as shown in Figure 1 below (2).

Figure 1: Equivalent Spring-Mass SDOF System (2)

An equivalent SDOF system is created by developing appropriate transformation factors for the

system’s mass, damping, load and resistance. Furthermore, inherit with an SDOF analysis is the

assumption that the system behaves only in a single mode shape. As the system begins to deflect

under the blast load, it eventually yields and forms plastic hinges at various locations depending

on the applied boundary conditions. Thus in reality, the system’s mode shape changes with the

progression of plastic hinges. Therefore, the transformation factors are adjusted accordingly to

account for the change in mode shape. For a more detailed review on the development of

transformation factors, see the PCI Report on Blast-Resistant Design of Precast/Prestressed

Concrete Components.

For a simply supported, one way slab under uniform loading, it is assumed that a single plastic

hinge will form at center span of the panel. The resistance-deflection relationship for such a

panel is assumed to act in an elastic-perfectly plastic manner. Thus, at a certain deflection, the

component will continuously yield at near constant resistance until an ultimate deflection limit is

reached, at which point the component will fail (see Figure 2 below). This resistance-deflection

relationship (resistance function) serves as the property for the non-linear spring in the equation

Page 4: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-4-

of motion. Thus, in order for an accurate prediction to be made of a component subjected to a

dynamic load, it is imperative that the resistance function be accurate.

Figure 2: Resistance-Deflection Relationship for Simply Supported Beam (3)

Once the time-history behavior of the component is known, it is desirable to determine the

amount of damage the component has taken. The US Army Corps has developed levels of

protection (LOP) which correlates a component’s ductility and/or maximum support rotation to a

given amount of damage (4). Ductility, μ, is measured as the maximum deflection of a

component divided by the deflection of the component at yield. Support rotation, θ, of a

component can be determined by Equation 1 below:

Equation 1: Calculation of Support Rotation

where Δmax is the maximum deflection at midspan and L is the span length before the blast

loading. Table 1 below provides the levels of damage for a reinforced concrete slab subjected to

a blast loading (4). A support rotation greater than 10 º is considered to be a blowout of the

component.

Table 1: US Army 2008 Response Limits for Flexural Controlled Non-Prestress Reinforced

Concrete (4)

Component Damage Level Superficial Moderate Heavy Hazards

Non-Prestress Panel μ≤1 2.0 º 5.0 º 10.0º

BEHAVIOR OF SLENDER REINFORCED CONCRETE COMPONENTS

A series of experiments were conducted at the Air Force Research Laboratory (AFRL) in

Tindall, Florida on prestress and non-prestress sandwich wall panels. Dynamic tests subjecting

panels to various charge detonations to examine panel behavior, shear tie tests to characterize

shear tie behavior and panel sensitivity, and static tests subjecting panels to uniform loading to

Page 5: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-5-

determine resistance functions for sandwich wall panels were conducted. Only static tests

conducted on non-prestress panels will be discussed in this paper.

To determine resistance functions, simply supported sandwich panels were tested to failure under

a uniform static load (5). Uniform loading was simulated by subjecting the wall system to 16

individual but equal in magnitude point loads, applied by a single actuator through a loading tree

(see Figure 3). The midspan deflection of each sandwich panel was recorded in order to back

calculate the end rotation of each panel through Equation 1.

Figure 3: Loading Tree Configuration (5)

Non-prestress panels were broken up into groups that varied by shear tie configuration, foam

type and thickness, or wythe thickness. Three non-prestress panels were tested from each group

of panels and a resistance-rotation curve was computed for each panel. An average resistance-

rotation curve and standard deviation was determined for each group of panels. Finally, a

simplified multi-linear response curve was formed based on the average resistance-rotation

curve. Levels of damage for each panel group were determined by taking a given percentage of

the maximum pressure value (see Figure 4). Blowout was considered to have occurred when the

panel’s resistance reached 50% of the maximum pressure. More detailed information on

development of the sandwich panels resistance function can be found in reference (5).

Figure 4: Development of Sandwich Panel Resistance-Function (5)

Table 2 summarizes current US Army LOP and recommended response limits for non-prestress

wall panels based on the static, uniform loading tests (5). The response of the non-prestress

Page 6: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-6-

sandwich panels creates two major differences when compared to blast design methodology.

First, blast design methodology assumes that a simply supported reinforced concrete component

will have an elastic-perfectly plastic response. In reality, the experiments revealed that the

panels behave in an elastic-hardening-softening behavior. The softening behavior is nearly

impossible to predict due to the highly non-linear behavior of concrete due to cracking and

heterogeneity of the material. Furthermore, modeling the softening behavior in current time-

stepping methods is extremely difficult and not practical for the practicing engineer whom will

be responsible for designing sandwich panels. Secondly, non-prestress panels did manage to

meet or outperform the criteria for superficial, moderate, and heavy levels of damage; however,

the panels failed to meet the criteria specified for hazardous or blowout levels of damage. This

implies that a panel design meeting current US Army standards may actually fail prematurely.

While US Army LOP criteria could be reduced for sandwich wall panels, this would also limit

wall panel’s application to certain government structures. An economical system would have to

be employed that meets both blast requirements and environmental requirements.

Table 2: US Army LOP versus Observed LOP (5)

Superficial Moderate Heavy Hazardous Blowout

Current Limits μ≤1 θ≤2.0º 2.0º<θ≤5.0º 5.0º<θ≤10.0º θ>10.0º

Observed Limits μ≤1 θ≤3.1º 3.1º<θ≤5.7º 5.7º<θ≤7.6º θ>7.6º

Tests were recently conducted by the authors on simply supported small scale, single wythe slabs

under a point loading. The panels were 3 in. thick, 12 in. wide, and had a clear span of 4ft. The

slabs were reinforced with 2 #3 bars at 2.5 in. deep in the longitudinal direction and #3 bars

spaced at 9 in. on center in the transverse direction. Conventionally reinforced slabs showed

excellent agreement with the results found in the tests conducted at the AFRL, with softening of

the slabs occurring at approximately 5º of support rotation (see Figure 5 below). From

observation during tests, it was noted that softening began to take place as the concrete

compression zone began to become unstable and crush (see Figure 6 below).

Figure 5: Conventionally Reinforced Small Scale Slab Response

0

2

4

6

8

10

12

14

16

0 5 10 15 20

Res

ista

nce

[psi

]

Support Rotation [deg]

Control Average

Page 7: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-7-

Figure 6: Instability of Concrete in Compression Zone

LOCALLY UNBONDING PANELS TO IMPROVE DUCTILITY

Experiments were conducted to examine the effect on the behavior of a slab by locally

unbonding longitudinal reinforcement. Unbonding reinforcement refers to removing any

mechanical (bar deformities, friction, etc.) or chemical (adhesion between mortar paste and bar

surface) bond between the reinforcement and surrounding concrete, thus preventing any shear

transfer at the bar-concrete interface as is common in a conventionally reinforced component

with deformed bars (6). Slabs tested were of the same dimensions and reinforcement

configuration as the conventionally reinforced small scale slabs discussed in the previous

section; however, longitudinal reinforcement was unbonded from the surrounding concrete at the

center of the panel in the region of highest moment.

Three groups of panels were fabricated, one group of panels unbonded for a length of 7.5 in., one

group unbonded for a length of 15 in., and the final group unbonded for a length of 22.5 in.

Unbonded lengths were chosen based on the panel’s plastic hinge length, which was determined

by examining the panel’s curvature over the length as developed by a moment-curvature analysis

(see Analytical and Numerical Models on page 9). Unbonding of the bar-concrete interface was

achieved by sliding Teflon tubing over the reinforcing bars for the prescribed distance (see

Figure 7 below). Tubing with sufficiently thin wall section (1/32 in. thick) and an outer diameter

similar to the diameter of the reinforcement (7/16 in. diameter) was selected to minimize any

effect of enhancing the reinforcement. The ends of the Teflon tubing were taped shut in order to

prevent any grout from entering between the tubing and the reinforcement to ensure the rebar

remain unbonded.

Page 8: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-8-

Figure 7: Unbonding of Longitudinal Reinforcement

Figure 8 below plots the resistance functions of the 7.5 in. unbonded length reinforced panels

versus the predicted resistance function formulated by conventional blast design methodology.

The panels behave in a near elastic-perfectly plastic manner, with the controlling failure

mechanism switching from instability of the compression zone to fracture of the longitudinal

reinforcement. Unlike the conventionally reinforced slabs, the unbonded panels did not exhibit a

softening behavior.

Figure 8: Performance of 7.5in Unbonded Length Reinforced Panels

Three panels from each unbonded group were tested to failure and average curves were formed

for each group. Figure 9 below plots the average curve for each unbonded group versus the

average curve for the conventionally reinforced panel. The response of the slab showed

sensitivity to unbonded length, with an increase in maximum measured support rotation and a

decrease in maximum achievable resistance. Moreover, the greater the unbonded length of the

panel, the greater the reduction in the panel’s post-cracking stiffness. Both 7.5 in. and 15 in.

unbonded groups failed in fracture of the reinforcement, while the 22.5 in. unbonded group could

not be failed due to lack of stroke on the testing apparatus.

0

2

4

6

8

10

12

14

16

0 5 10 15 20

Res

ista

nce

[psi

]

Support Rotation [deg]

UFCUnbond Average

Page 9: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-9-

Figure 9: Average Unbonded Length Curves versus the Control Panel

ANALYTICAL AND NUMERICAL MODELS

Conventional Panel Model

To predict the response of the conventionally reinforced panel, a fiber analysis was performed.

A fiber analysis approximates cross sectional geometry, reinforcement size and location, and

material properties by dividing the cross section up into discrete “fibers”. Each fiber is assigned

an area and a specific force-deformation relationship. Reinforcement layers are superimposed to

the cross section and are assumed to be located in a single fiber layer for simplicity despite the

reinforcement diameter. Figure 10 below provides the concrete and reinforcement material

properties incorporated into the fiber analysis. Stress-strain curves were obtained for concrete by

multiple cylinder tests. Popovics’ unconfined concrete model showed good correlation with the

experimental data (7).

0

2

4

6

8

10

12

14

0 5 10 15 20 25

Res

ista

nce

[psi

]

Support Rotation [deg]

Control7.5" Unbond15" Unbond22.5" Unbond

Page 10: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-10-

Figure 10: Concrete and Reinforcement Material Properties

In the fiber model, strains at the top of the concrete section were stepped until equilibrium could

no longer be satisfied. At this point, the section was considered failed and the fiber analysis was

terminated. From the fiber analysis, a moment-curvature relationship is developed for the

section. By knowing the boundary conditions and loading scenario, curvature over the length of

the section can be formulated. Finally, by integrating the curvature over the length with a virtual

moment, the load-deflection of the cross section can be formed. Figure 11 below shows the

results of the fiber analysis compared to bounded experimental results for the conventionally

reinforced control panel.

Figure 11: Fiber Analysis versus Bounded Experimental Results

Unbonded Panel Models

In order to investigate the unbonded panel behavior, finite element models (FEA) and simple

analytical models were developed. The goal of the FEA was twofold. The first goal was to

0 0.005 0.01 0.015 0.02 0.025 0.03

0

1000

2000

3000

4000

5000

6000

0

20000

40000

60000

80000

100000

120000

0 0.05 0.1 0.15 0.2

Concrete Strain

Concr

ete

Str

ess

[psi

]

Ste

el S

tres

s [p

si]

Steel Strain

Popovic's

Model

Rebar

Rebar

Model

Page 11: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-11-

determine the stress/strain distribution in the concrete and in the unbonded reinforcement. The

second goal was to understand the controlling failure mechanism in order to develop a simple

model to predict the resistance function of the unbonded panel. The FEAs are organized in two

categories: the ai plane stress models (models a1 and a2), and the bi beam element models

(models b1 and b2). Straus7®

was utilized to develop the FEA simulations (8).

The ai FEAs model the panel as plane structures with plate elements. The reinforcement was

modeled with truss elements and the unbonded zone is tied to the concrete only by discrete

contact elements in an attempt to simulate actual experimental conditions. The concrete was

modeled with four and three node constant stress plates. Model a1 (see Figure 12) contains a

discrete crack at mid-span and the concrete material properties were taken to be purely elastic.

Model a2 (see Figure 13) models the concrete using smeared cracking properties with Mohr-

Coulomb failure criteria and perfectly plastic behavior. The absence of softening in the concrete

constitutive law is the main limitation of model a2.

Figure 12: Plane Stress Model a1

Figure 13: Plane Stress Model a2

The bi FEAs model the panel with beam elements in the bonded region and with a compression

strut and tension strut in the unbonded region (see Figure 14 and Figure 15). The cross sectional

area of the compression strut was developed from the results of the ai FEA models while the

contact elements

contact elements

unbonded region

concrete

bonded region

discrete crack

contact elements

unbonded region

concrete

bonded rebar

Page 12: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-12-

cross sectional area of the concrete tension strut was approximated to have a depth of twice the

reinforcement cover. The rebar tension strut cross sectional area was calculated from the amount

of reinforcement in the actual experimental panels. The compression strut is located at the top of

the beam and the tension strut is located at the center of the reinforcement. The distances from

the centerline are referred to as h and k, respectively. Model b1 (shown in Figure 14) only

accounts for axial deformation of the rebar strut while model b2 (Figure 15) connects the tension

strut to the beam element with pinned links in order to account for second order effects in the

reinforcements.

Figure 14: Beam Model b1

Figure 15: Beam Model b2

As expected, the stress in the rebar is constant over the unbonded region (Figure 16 from model

a2). This result indicates that second order effects contribution to the overall stress in the

reinforcement is minimal.

Figure 16: Model a2 Rebar Axial Force Distribution

Figure 17 provides the FEA predictions of the panels’ resistance function compared to the

experimental results. From the plot, it is clear that each FEA model correlates well with

compression truss

tension truss: rebar, concrete

rigid link

elastic beam

imposed displacements

unbonded region

k

h

compression truss

tension truss: rebar, concrete

rigid link

elastic beam

imposed displacements

unbonded region

k

h

pinned link

Lb

rebar axial force

distribution

Page 13: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-13-

experimental results until yielding of the longitudinal reinforcement. Models a1 and b2 depict an

elastic-hardening response that deviates significantly from the experimental results as the panel

displacement progresses past yield. The hardening response of each model was attributed to the

fact that the concrete was treated elastically for model a1 and applying rigid links as opposed to

elastic links lead to a magnification of the panel curvature, and consequently higher steel strains

for model b2. Models a2 and b1 provided the best agreement with the experimental results,

suggesting that a simplified analytical model could be developed based on the kinematics from

each model.

Figure 17: Experimental and FEA Model Resistance Functions

Considering the results of the FEAs, the following simple analytical model was developed. The

kinematics shown in Figure 18 is assumed, which accounts for section rotation and large

displacements. The change in length of the unbonded reinforcement from section rotations is

given by Equation 2 where B is the internal moment arm and α is the support rotation of the

panel. The change in length of the unbonded reinforcement from large deflections is given by

Equation 3, where L1 is half the panel span length minus half the length of the unbonded region,

Lb.

Equation 2: Change in Rebar Length from Section rotations

Equation 3: Change in Rebar Length from Large Displacements

0

1000

2000

3000

4000

5000

0 1 2 3 4 5 6 7

Forc

e [l

b]

Displ. [in]

Experimental - 1

Experimental - 2

Experimental - 3

a1

a2

b1

b2

Page 14: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-14-

Figure 18: Kinematics of the Analytical Model

The force in the reinforcement was thus computed by Equation 4 where Kr is the stiffness of the

reinforcement. Consequently, the resisting moment can be calculated from Equation 5. Finally,

the load capacity of the entire system can be determined by considering statics as given by

Equation 6 and as shown in Figure 19.

Equation 4: Force in Rebar

Equation 5: Resisting Moment

Equation 6: System Load Capacity

Figure 19: Equilibrium of Analytical Model for Concentrated Load at Midspan

The results of the analytical model versus the 7.5 in. unbonded length are provided in Figure 20.

“Analytical without cut-off” refers to an analytical model that does not consider damage of the

Kconc

αKrebar

Δuu

L1

L

Ld

d

KINEMATICS

B

rigid beams

not to scale

MR

P/2

P/2 EQUILIBRIUM

L2

Page 15: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-15-

compression zone, while “analytical with cut-off” limits the achievable compressive force

developed by concrete in the compression zone. The depth of the compression zone for the

analytical model is determined through conventional reinforced concrete methods (9). This

simplified analytical model adequately captures the yield point of the unbonded section and

conservatively estimates the ultimate obtainable displacement before rebar fracture. The model

could be refined by developing a more accurate method to determine the compression block

depth; however, for practical design purposes this simple analytical model may be suitable.

Figure 20: Results of Analytical Model versus Experimental Results

CONCLUSION

High risk facilities have minimum blast requirements in order to protect occupants within. With

recent emphasis on “green” buildings, many of these facilities are now mandated to meet LEED

certification requirements. Precast sandwich wall panels are ideal systems to meet both

protection and environmental criteria; however, due to the slender geometry of these panels, they

fail to meet hazardous and blowout LOP as set by the U.S. Army. Additionally, panels behave in

an elastic-hardening-softening behavior which deviates from the assumed elastic-perfectly

plastic response in current blast design methodology. To improve the ductility and behavior of

slender concrete components, experiments were conducted by locally unbonding the longitudinal

reinforcement in the region of highest moment for a distance corresponding to the predicted

plastic hinge length. Local unbonding showed to increase the panel ductility at a decrease

ultimate resistance. Additionally, panels showed sensitivity to the length of local unbonding,

increasing in ductility and decreasing in ultimate resistance with longer unbonded lengths.

Analytical and numerical models were developed in order to predict the behavior of unbonded

wall panels. The resistance function of such panels was seen to be strongly influenced by the

stress-strain behavior of the longitudinal reinforcement.

0

1000

2000

3000

4000

5000

0 1 2 3 4 5 6 7

Forc

e [l

b]

Displ. [in]

Experimental - 1

Experimental - 2

Experimental - 3

Analitical, without cut-off

Analitical, with cut-off

Page 16: INCREASING THE DUCTILITY OF REINFORCED CONCRETE …

-16-

ACKNOWLEDGMENTS

This project has received support from an NSF grant, PD 08-1637, and from PCI’s Daniel P.

Jenny fellowship.

REFERENCES

(1) PCI Committee on Precast Sandwich Wall Panels, “State-of-the-Art of Precast/Prestressed

Sandwich Wall Panels”, PCI Journal: Vol 2, No 2, March 1997

(2) PCI Blast Resistance and Structural Integrity Committee, “Blast-Resistant Design of

Precast/Prestressed Concrete Components”, PCI Report, July 2010

(3) Department of Defense, “Structures to Resist the Effects of Accidental Explosions”, UFC 3-

340-02, 2008, p. 1106

(4) U.S. Army Corps of Engineers, “Single Degree of Freedom Structural Response Limits for

Antiterrorism Design”, Protective Design Center Technical Report PDC-TR 06-08 – Rev 1, 2008

(5) Air Force Research Laboratory, “Analytical Assessment of the Blast Resistance of Precast,

Prestressed Concrete Components”, AFRL-ML-TY-TP-2007-4529 Interim Report, April 2007

(6) R. Park, T. Paulay, Reinforced Concrete Structures, John Wiley & Sons, 1975, p. 392

(7) S. Popovics, “A Numerical Approach to the Complete Stress Strain Curve for Concrete”,

Cement and Concrete Research, Vol 3 Iss 5, 1973, p. 583-599

(8) G+D Computing, HSH srl, “Theoretical manual, theoretical background to the Straus7® finite

element analysis system” Sydney, Australia, 2004

(9) EN 1992-1-1, “Eurocode 2. Design of Concrete Structures – Part 1-1: General Rules and

Rules for Buildings”, 2004