PUBLICPUBLIC Copyright © 2018 Rockwell Automation, Inc. All Rights Reserved. 2018 Rockwell Automation TechED™ Event #ROKTechED
IN22 SyTech, TheReportCompany.comOptimize Data From FactoryTalk Alarms and Events To Improve Performance
Presenter Name, Peter V. KaprielianPresenter Title, CTO2pm 11th June 2018, 9am 13th June 2018
✓ SyTech: The Company
✓ XLReporter: The Product
✓ Evolution of Alarm Management
✓ Alarm Management Standards
✓ XLReporter Alarm Module
IN22 - Session Content
Copyright © SyTech, Inc. 2018, All rights reserved.
XLReporter Is Industrial ReportingSoftware for Process Automation
✓ About SyTech▪ Founded in 1994
▪ Headquartered in Massachusetts USA
▪ Encompass partner since 2001
▪ Develop and Support XLReporter▪ Reporting Software for Industry
✓ XLReporter Used By … for▪ Water and Wastewater … Compliance
▪ Energy Management … Performance
▪ Automotive … Operational
▪ Oil and Gas … Production
▪ and more …
SyTech
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ “Out of Box” Software▪ No Scripting/SQL/Programming▪ No Limits, Tags, Reports or Templates
✓ Designed for Industrial Automation▪ Award winning
o Two-time winner of Control Engineering Award
▪ Small footprint o Use on existing hardware and OS
✓ Utilize Existing Skills▪ Design Workbook Templates
o No Limitso Need a tip? Over 1B users of Excel or 1 in 7 people!
✓ Report, Reliably, 24x7▪ Produce Workbook, PDF and Web Pages▪ No additional software to produce or view reports
o XLReporter uses the Microsoft Open XML standard
✓ Scalable▪ Start small and grow
XLReporter Is Industrial Reporting
Connect Design Produce DistributeCopyright © SyTech, Inc. 2018, All rights reserved.
✓ Connectivity▪ Over 70 connectors.
o No Limits
o Real time, historical and relational databaseso OPC, ODBC, OLE DB
✓ Industry Analytics▪ Standard Calculations
o Minimum, Maximum and Average (for each day of month)
▪ Industry Specific Calculationso How many times did the pumps cycle
o How efficiently is equipment utilized
o What are the top 5 occurring alarms
▪ Scaling, Filtering
✓ Report Automatically or On-Demand▪ Schedule tasks on Time or Event
o End of each shift, batch end
▪ Schedule tasks on Evento Cycle End
Industry analytics From Raw Data
Industrial Components
Copyright © SyTech, Inc. 2018, All rights reserved.
Industrial Features
Bitmaps and Icons
Tabular/Free Format Content
Conditional Formatting
Charts
Copyright © SyTech, Inc. 2018, All rights reserved.
Custom Report Names
Industrial Calculations
“Report As You Run” Technology
Excel/XLR Functions
Connectors for Rockwell AutomationP
lant F
loor
To B
ack O
ffic
e
PLCs
For Any BudgetFrom $995
FT View SE
Panel View Plus
FT View ME
Data Logger (eWon)
FT Historian SE
XLReporter Analytics
Manual Data Entry
FT View SE
Data Logs
FT Historian ClassicFT Alarm/Event
No LimitsTags, Templates,
Reports
Relational Database
Data SourcesReal time Historical Relational
Copyright © SyTech, Inc. 2018, All rights reserved.
Session FocusP
lant F
loor
To B
ack O
ffic
e
FT Alarm/Event
Data SourcesReal time Historical Relational
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ Mimic Panels▪ Hard Wired▪ Expensive▪ Required Space
✓ Alarm Management▪ Very Effective▪ Careful Alarm Selection▪ Plenty Of Discussion▪ Documentation
Copyright © SyTech, Inc. 2018, All rights reserved.
Alarms In the 70’s
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ The Digital Era▪ Mimic Panels Became Obsolete▪ Adding Alarms Became Cheap▪ Information on Computers
▪ Visibility Restrictions
✓ Alarm Management▪ Setup Was Easy, Far Too Easy▪ Documentation Took A Backseat
Alarms In the 80’s
Copyright © SyTech, Inc. 2018, All rights reserved.
Alarm Flood!✓ Waste Water Treatment Plant
▪ 2:12 am - several critical alarms flooded the main control room and indicated the plant’s process has broken down and pumps had stopped. The following quote is directly from the operator “Alarms within …. A matter of minutes, a ton of them”
▪ 2:21 am - two alarms triggered by a bubbler, hit high-high on the operator's display, showing the two primary tanks were dangerously close to overflowing, however, the operator didn’t see them. Four minutes later two more alarms showed the tanks were past capacity.
▪ 2:25 am - wastewater began flooding the plant
235 million gallons of untreated wastewater and 30 million gallons of raw sewage released into Puget Sound.
Damage > $25 million
Copyright © SyTech, Inc. 2018, All rights reserved.
Alarm Suppression!✓ Deepwater Horizon Oil Rig
▪ On April 20, 2010, a surge of natural gas went undetected causing an explosion on the Deepwater Horizon offshore oil rig
▪ From the Washington Post on July 23, 2010, Michael Williams, a chief engineer on the Deepwater Horizon Rig told a federal panel that he understood the rig had been operating with the gas alarm system in “inhibited” mode for a year to prevent false alarms from disturbing the crew.
The explosion, fire and sinking of the rig were responsible for 11 workers killed and 17 injured, The rig left more than 60,000 barrels of oil spilling into the Gulf of Mexico for a total of approximately 5 Million barrels in total.
Damage > $60 billion and manslaughter charges
Copyright © SyTech, Inc. 2018, All rights reserved.
EEMUA-191
ISA-18.2
IEC-62682
Industry Standards
1999 2009 2014Copyright © SyTech, Inc. 2018, All rights reserved.
ISA 18.2 provides requirements and recommendations for the activities of
the alarm management life cycle. It was reaffirmed globally with the
release of IEC-62682
What is an Alarm
✓ ISA 18.2 Definition
▪ “an alarm is an audible and/or visible means of
indicating to the operator an equipment malfunction,
process deviation, or abnormal condition requires a
response”
Copyright © SyTech, Inc. 2018, All rights reserved.
Action Required Information
Abnormal Alarm Alert
Expected Prompt Message
Key Design Principles
✓ Every alarm should have a defined response
✓ Adequate time should be allowed for the operator to carry out the defined response
✓ Every alarm presented to the operator should be useful, relevant and unique
✓ Operators should not get overwhelmed with alarms
✓ Alarms should be prioritized and understandable
Copyright © SyTech, Inc. 2018, All rights reserved.
If the Operator
Response (Action)
Cannot Be Defined
then it is Not an Alarm
- EEMUA 191 (2013)
ISA-18.2, IEC-62682
✓ Alarm Philosophy
▪ Objectives, guidelines and work processes
✓ Alarm Rationalization
▪ Identify alarms and their priorities
▪ Consequences of no action
✓ Implementation
▪ Configuration of the rationalization results
✓ Monitoring and Assessment
▪ Measure performance regularly
Copyright © SyTech, Inc. 2018, All rights reserved.
Alarm Management Life Cycle
✓ Encompass Partnership▪ Collaborative Effort
✓ exida▪ Consulting Services
▪ PR016 Alarm Management
✓ SyTech▪ Reporting Services and Software
▪ Benchmark Assessment Report
▪ Monitor and Report
Copyright © SyTech, Inc. 2018, All rights reserved.
Performance Indicators
Copyright © SyTech, Inc. 2018, All rights reserved.
Average Alarm Rate per day
Average Alarm Rate per hour
Average Alarm Rate per 10 min
Alarm Priority Distribution
% of Time with >10 Alarms per 10 min
Maximum Alarms in a 10 min Period
% of Time with >30 Alarms per hour
% of Time in Alarm Flood Condition
Number of Stale Alarms
% of the Top 10 Active Alarms
Number of Chattering Alarms
Average Alarm Rateper hour in Flood
Average Alarm Rateper hour excl. Flood
Alarm Priority Timeline
Performance Targets
Copyright © SyTech, Inc. 2018, All rights reserved.
Performance Indicator Target
Average Alarm Rate per day 150 - 300
Average Alarm Rate per hour 6 - 12
Average Alarm Rate per 10 minutes 1 - 2
Percentage of 10 mins periods > 10 alarms < 1%
Maximum Alarms in a 10 minute Period <= 10
Percentage of Time in Alarm Flood Condition < 1%
Percentage of the Top 10 Alarms < 1% to 5%
Number of Chattering/Fleeting Alarms 0
Number of State Alarms < 5
Priority Distribution (Low) ~ 80%
Priority Distribution (Medium) ~ 15%
Priority Distribution (High) ~ 5%
Top 10 Alarm Contribution
Copyright © SyTech, Inc. 2018, All rights reserved.
The percentage of alarms coming from the top-ten most frequent alarm sources relative to the total alarm count.
✓ Contributors▪ Nuisance Alarms (which tend to get ignored over time)
▪ Misuse of the Alarm System
Top Ten Alarms create 32% of
notifications!
Average Alarm Rate
Copyright © SyTech, Inc. 2018, All rights reserved.
Average alarm rate is the measure of the frequency with which new alarms are presented to the operator, expressed as an average count.
✓ Contributors▪ Events that are not Alarms
▪ Chattering/Fleeting Alarms
▪ Cascading Alarms
Alarm Timeline
Distribution over each day
of the reporting period
Distribution over each
hour of the day of
maximum activity
Copyright © SyTech, Inc. 2018, All rights reserved.
Identifying “Bad Actors”
Top Ten Alarms create 32% of
notifications!
Copyright © SyTech, Inc. 2018, All rights reserved.
Alarm Floods
Copyright © SyTech, Inc. 2018, All rights reserved.
Alarm Flood can be defined as beginning when the alarm rate exceeds more than 10 alarms in 10 mins and ending when the rate drops below 5 alarms in 10 mins
✓ Contributors▪ Alarms for the Same Abnormal Condition
▪ Cascading Alarms
▪ Poor Control Design
Identifying Alarm Floods
Multiple Flood scenarios
Floods last a long
period of time
Copyright © SyTech, Inc. 2018, All rights reserved.
Chattering Alarms
Copyright © SyTech, Inc. 2018, All rights reserved.
Chattering alarms are alarms that repeatedly transition between alarm state and normal state in a short period of time. Most common measure is 3 alarms in 1 minute.
✓ Contributors▪ Insufficient hysteresis (deadband)
▪ No on/off delays
Two alarms contribute to
over 50% of chattering
Stale Alarms
Copyright © SyTech, Inc. 2018, All rights reserved.
A stale alarm is one that remains annunciated for an extended period of time, most often specified as 24 hours. Challenging to measure and difficult to remove.
✓ Contributors▪ Standby or idle equipment
▪ Alarms no longer relevant
▪ Alarms latched due to excessive hysteresis
▪ Alarms outside the operators control, waiting for maintenance
Identifying Stale Alarms
Alarm Active Time
D:H:M:S
Copyright © SyTech, Inc. 2018, All rights reserved.
Benchmark Assessment Report✓ Free to Eligible Users
▪ Users Provides Data (15-30 days)
▪ Report Returned at No Cost
✓ Purpose▪ Provide a Benchmark
▪ Help Justify Investment
✓ Subscription or Installation▪ Subscribe to Periodic Reports
▪ User Provides Data
▪ XLReporter with Alarm Module▪ Install on premises
Copyright © SyTech, Inc. 2018, All rights reserved.
Monitoring and Assessment
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ Plant View of Alarm Performance
✓ Alarm KPI Metrics
✓ Alarm Report Includes▪ “bad actors”
▪ nuisance alarms
▪ alarm floods
▪ frequency
✓ Alarm Priority Distribution▪ Calculated using ISA recommendations
Monitoring and Assessment✓ Based on ISA 18.2
✓ KPI Dashboards
✓ Drill Down to Details
✓ Scheduled and On-Demand
✓ Customize to Needs
✓ Combine with Process Data
✓ Automated Report Distribution
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ Add Process Metrics and KPIs▪ Uptime/Downtime starts/stops e.g., OEE
✓ Export to Back Office▪ Produce XML, CSV from worksheet
▪ Quality Control.
Report Automatically
Copyright © SyTech, Inc. 2018, All rights reserved.
Report On Demand
Template Selection.
Alarm/Process/History
Filter Selection.
Date/Position/Area
Distribute.
Workbook/PDF
Email/Printer
Report Tabs.
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ Web Portal▪ Open from any browser.
▪ No Access Limits
✓ Auto Update
✓ Email, FTP, Printer▪ Mobile, Email, Text Message
o Dynamic/Compressed attachments
o Live values in content
Publish to Web Portal
Copyright © SyTech, Inc. 2018, All rights reserved.
✓ Publishing Methods▪ Automatically
▪ Manual “Dropbox”
✓ Hyperlinks▪ Trends
Publish to VantagePoint
Links to VP
Trends
Copyright © SyTech, Inc. 2018, All rights reserved.
Automatically Add
Content
Benefits of Alarm Management✓ Increased Uptime and Production
▪ Studies show 3-8% losses due to abnormal situations
✓ Regulatory Compliance▪ GAAP
✓ Insight Into Emerging Problems▪ Tuning
✓ Incident Prevention▪ Reduce chance to miss critical alarms.
✓ Improved Productivity▪ Reduce Alarm Load on Operator
▪ Remove nuisance alarms
Copyright © SyTech, Inc. 2000-2018
Awards and Testimonials
“The automation interface provided by SyTech enables Excel to be used in more niche markets that require automated and unattended operation. This is an example of how Microsoft Office applications can solve critical business problems for our customers and deliver great benefits from creative partners like SyTech.”
Microsoft Corp.
XLReporter is a two-time winner of Control Engineering Choice Award
Copyright © SyTech, Inc. 2000-2018
Information and Download
✓ Show
▪ Evaluation CDs at Booth
▪ Daily Amazon Gift Card Giveaway
✓ Web
▪ www.SyTech.com
▪ www.TheReportCompany.com
✓ Phone
▪ 508 520 9957 (9XLR)
41Copyright © 2018 Rockwell Automation, Inc. All Rights Reserved. 2018 Rockwell Automation TechED™ Event #ROKTechEDPUBLIC
Share your FeedbackPlease complete a session survey on the mobile app
▪ Download the Rockwell Automation Events App
▪ Select Rockwell Automation TechED and login
▪ Click on Session Surveys or Schedule in the main menu
▪ Select the session you are attending
▪ Click on the survey tab
▪ Complete the survey and submit
www.rockwellautomation.com
PUBLICPUBLIC Copyright © 2018 Rockwell Automation, Inc. All Rights Reserved. 2018 Rockwell Automation TechED™ Event #ROKTechED
#ROKTechED
Thank You!