INSTALLATION INSTRUCTIONS EMERGENCY FLUORESCENT BATTERY PACK MODEL PSQ500 CAUTION: For safety and proper operation, read and follow instructions carefully before installation. IMPORTANT NOTES: The PSQ500 can be used with a switched or unswitched (night) circuit. When used with a switched fixture it is important to note that the power to the PSQ500 Battery Pack must be provided by an unswitched circuit. Make sure that the switched and unswitched sources are derived from a common circuit. U.S. PATENT # 5,814,971 & 6,522,147 NOTE: Field installable battery pack for one lamp emergency operation of 2'-4' (including U-lamps), T8-T-12 and long compact (4-pin) lamps (17W -40W lamps). Compatible with electronic T8 and magnetic T12 ballasts. INSTALLATION PROCEDURE: 1. Inspect PSQ500 and make sure the Test Switch/Pilot Light connector is not connected. If so, disconnect it before installation. 2. Position unit in fixture wireway and fasten securely through inverter housing mounting slots . If necessary, drill holes and mount with screws (not provided). 3. Refer to appropriate wiring diagram. Connect unit to ballast, lamp(s) and AC power leads as indicated in appropriate wiring diagram. TEST SWITCH PILOT LIGHT (TSPL) INSTALLATION: CAUTION: Do not locate Test Switch/Pilot Light or route cable within 1” of fixture lamps. NOTE: If pilot light is not visible through fixture lens when energized and de-energized, the charge indicator sticker located in the pre-pack should be placed on the smooth side of the lens directly below the TSPL to identify it as an emergency fixture. 4. Drill or punch a 1/2” diameter hole in fixture wall or wireway cover. 5. Insert one side of the TSPL into the hole from the back and snap in the other side. Slide mounting clip firmly onto mounting post with the TSPL assembly secured in place. 6. Connect the polarized Test Switch/Pilot Light connector . CAUTION: Connecting the Test Switch/Pilot Light connector also connects the battery to the inverter circuit which can result in high voltage being present between the RED & BLUE output leads. 7. Apply continuous power to PSQ500. CAUTION: A potential electrical hazard exists even when AC power supply has been turned off. Disconnect polarized Test Switch/Pilot Light connector before servicing fixture. IMPORTANT SAFEGUARDS 1.READ AND FOLLOW ALL SAFETY INSTRUCTIONS 2. Before wiring to power supply, turn off electricity at fuse or circuit breaker. 3. To reduce the risk of electrical shock, disconnect Test Switch/Pilot Light connector before servicing. 4. All servicing should be performed by qualified personnel. 5. Consult your local building code for approved wiring and installation. 6. Do not use standard product outdoors. This product is for use with indoor fixtures sealed or unsealed, except air handling heated outlets or hazardous location applica- tions. Battery packs with the DW option are UL listed for installation (0 o - 50 o C ambient) in: Dry or damp locations, sealed or unsealed luminaries Wet locations, only if installed in a sealed and/or gasketed wet location listed luminaire. Note: DW option does not make the product suitable for mounting outside the fixture in wet location applications. 7. The emergency battery pack must be connected to an unswitched AC power source (120 or 277). 8. Do not mount near gas or electric heater. 9. Do not attempt to service the battery. A sealed mainte- nance-free battery is used that is not field replaceable. Contact manufacturer for service information. 10. Equipment should be mounted in location and at heights where it will not readily be subjected to tampering by unauthorized personnel. 11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 12. Do not use this equipment for other than intended use. SAVE THESE INSTRUCTIONS Part no. EMCSA00662 Rev D

IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

INSTALLATION INSTRUCTIONS EMERGENCY FLUORESCENT BATTERY PACK MODEL PSQ500

CAUTION: For safety and proper operation, read and follow instructions carefully before installation.

IMPORTANT NOTES:

The PSQ500 can be used with a switched or unswitched(night) circuit. When used with a switched fixture it isimportant to note that the power to the PSQ500 BatteryPack must be provided by an unswitched circuit.Make sure that the switched and unswitched sources arederived from a common circuit.

U.S. PATENT # 5,814,971 & 6,522,147NOTE: Field installable battery pack forone lamp emergency operation of 2'-4'(including U-lamps), T8-T-12 and longcompact (4-pin) lamps (17W -40W lamps).Compatible with electronic T8 and magneticT12 ballasts.

INSTALLATION PROCEDURE:1. Inspect PSQ500 and make sure the Test Switch/Pilot

Light connector is not connected. If so, disconnect itbefore installation.

2. Position unit in fixture wireway and fasten securelythrough inverter housing mounting slots . If necessary,drill holes and mount with screws (not provided).

3. Refer to appropriate wiring diagram. Connect unit toballast, lamp(s) and AC power leads as indicated inappropriate wiring diagram.

TEST SWITCH PILOT LIGHT (TSPL) INSTALLATION:CAUTION: Do not locate Test Switch/Pilot Light or route cablewithin 1” of fixture lamps.NOTE: If pilot light is not visible through fixture lens whenenergized and de-energized, the charge indicator stickerlocated in the pre-pack should be placed on the smooth side ofthe lens directly below the TSPL to identify it as an emergencyfixture.4. Drill or punch a 1/2” diameter hole in fixture wall or

wireway cover.5. Insert one side of the TSPL into the hole from the back

and snap in the other side. Slide mounting clip firmlyonto mounting post with the TSPL assembly secured inplace.

6. Connect the polarized Test Switch/Pilot Light connector .CAUTION: Connecting the Test Switch/Pilot Light connectoralso connects the battery to the inverter circuit which canresult in high voltage being present between the RED &BLUE output leads.7. Apply continuous power to PSQ500.CAUTION: A potential electrical hazard exists even when ACpower supply has been turned off. Disconnect polarized TestSwitch/Pilot Light connector before servicing fixture.

IMPORTANT SAFEGUARDS1.READ AND FOLLOW ALL

SAFETY INSTRUCTIONS 2. Before wiring to power supply, turn off electricity at fuse

or circuit breaker.

3. To reduce the risk of electrical shock, disconnect TestSwitch/Pilot Light connector before servicing.

4. All servicing should be performed by qualified personnel.

5. Consult your local building code for approved wiring andinstallation.

6. Do not use standard product outdoors. This product isfor use with indoor fixtures sealed or unsealed, except airhandling heated outlets or hazardous location applica-tions. Battery packs with the DW option are UL listed forinstallation (0o - 50oC ambient) in:

Dry or damp locations, sealed or unsealed luminaries

Wet locations, only if installed in a sealed and/orgasketed wet location listed luminaire.

Note: DW option does not make the product suitable formounting outside the fixture in wet location applications.

7. The emergency battery pack must be connected to anunswitched AC power source (120 or 277).

8. Do not mount near gas or electric heater.

9. Do not attempt to service the battery. A sealed mainte-nance-free battery is used that is not field replaceable.Contact manufacturer for service information.

10.Equipment should be mounted in location and at heightswhere it will not readily be subjected to tampering byunauthorized personnel.

11.The use of accessory equipment not recommended bythe manufacturer may cause an unsafe condition.

12.Do not use this equipment for other than intended use.

SAVE THESE INSTRUCTIONS

Part no. EMCSA00662Rev D

Page 2: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

Page 2

NOTE: Emergency lighting systems should be tested as oftenas local codes require, or at least monthly to insure that allcomponents are operational. Perform all tests (momentary/monthly) required by local codes.

1. Check equipment rating to be sure that fixture will receive properline voltage.

2. Engage test switch. The pilot light should turn off. One fluorescentlamp should operate at a reduced light output.

3. Be sure pilot light is on. If pilot light does not operate, check to seethat:

a. Test Switch / Pilot Light connector is properly connected.

b. AC power is on.

c. Voltage on unswitched circuit to battery pack should be rated linevoltage (120V or 277V). If no line voltage can be measured, locateproblem in branch circuit and correct.

NOTE: PSQ500 inverters are not field serviceable units.

NOTE: Allow battery to charge 24 hours before initial testingand 168 hours to fully charge battery.

CAUTION: Damage to battery will occur if the Test Switch/PilotLight is connected for a prolonged period of time without AC powerprovided.

APPROXIMATE WORKING VOLTAGEBattery Pack input: 120 OR 277V AC

INSPECTION AND MAINTENANCE

PARTS DESCRIPTION

WARRANTYTHREE-YEAR TOTAL CUSTOMER SATISFACTIONComplete Customer Satisfaction.This fixture is guaranteed toperform to our customers’ complete satisfaction for a period ofthree years from date of invoice. Our guarantee covers anydefect in manufacturing, provided the defect develops undernormal and proper use. This liability does not include lamps,and extends only to replacement of the defective part. Laborcharges will be honored by the factory only with prior writtenapproval from our Post Sales Service Department.

a HOUSINGb MOUNTING HOLES or SLOTSc TEST SWITCH/PILOT LIGHT (TS/PL)d MOUNTING CLIPe TS/PL CONNECTORf CHARGE INDICATOR STICKER

Part no. EMCSA00662Rev D

Page 3: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

WIRING DIAGRAMSIMPORTANT NOTES: Before connecting Test Switch / Pilot Light or wiring unit to fixture, refer to PSQ500 INSTALLATIONINSTRUCTIONS and IMPORTANT SAFEGUARDS for safety information and mounting procedures.

FIGURE C

FIGURE B

Page 3

ONE LAMP RAPID START BALLAST

TWO LAMP RAPID START BALLAST

THREE LAMP RAPID START BALLAST

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

FIGURE A

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot PowerLead to Black (120) or Orange (277).

/PILOT LIGHT

/PILOT LIGHT

Part no. EMCSA00662Rev D

Page 4: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

Page 4

FIGURE F

FIGURE D

ONE LAMP INSTANT START BALLAST

TWO LAMP INSTANT START BALLAST

FIGURE E

FOUR LAMP RAPID START BALLAST

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

/PILOT LIGHT

/PILOT LIGHT

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

Part no. EMCSA00662Rev D

Page 5: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

FIGURE I

FIGURE G

FIGURE H

ONE LAMP INSTANT START SLIMLINE BALLAST

THREE LAMP INSTANT START BALLAST

Page 5

FOUR LAMP INSTANT START BALLAST

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

/PILOT LIGHT

/PILOT LIGHT

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

Part no. EMCSA00662Rev D

Page 6: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

FIGURE J

FIGURE K

TWO LAMP SERIES LEAD SLIMLINE BALLAST

TWO LAMP SERIES SEQUENCE SLIMLINE BALLAST

Page 6

FIGURE L

TWO LAMP LEAD/LAG INSTANT START SLIMLINE BALLAST

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot Power LeadAnd Connect Unswitched Hot Power Lead to Black(120) or Orange (277).

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

/PILOT LIGHT

/PILOT LIGHT

/PILOT LIGHT

Part no. EMCSA00662Rev D

Page 7: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

INSTALLING TEST SWITCH/PILOT LIGHTFIGURE M

ONE LAMP NORMALLY OFF EMERGENCY FIXTURE

Page 7

UNSWITCHED FIXTUREConnect Black (120) or Orange (277) AndYellow Lead To Unswitched Hot PowerLead.

SWITCHED FIXTUREConnect Yellow Lead To Switched Hot PowerLead And Connect Unswitched Hot Power Leadto Black (120) or Orange (277).

/PILOT LIGHT

Part no. EMCSA00662REV D

Page 8: IMPORTANT SAFEGUARDS - Power Sentry...3. Be sure pilot light is on. If pilot light does not operate, check to see that: a. Test Switch / Pilot Light connector is properly connected

Part no. EMCSA00662REV DPage 8