27
iGrow800 – Stand Alone Controller Installation Information

iGrow800 Stand Alone Controller Installation Information

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Stand Alone Controller Installation Information

Page 2: iGrow800 Stand Alone Controller Installation Information

LOADRelay

PilotRelay

LOADRelay

PilotRelay

OFF= Load Contactor Ice Cube Relay OFF &

De-Energized

ON = Load Contactor Ice Cube Relay ON &

Energized

iGrow Output OFF

iGrow Output

ON

The iGrow800 output relays are provided as dry contacts, switch closures. If an output is activated to ON, the switch is “closed” (shorted); if it is activated to OFF, the switch is “open” (no continuity between the positive and negative terminals).

Per – RELAY

Max Voltage – 24V

Max Current – 1 AMP

The board mounted relays are intended as “pilot” relays. (NO VOLTAGE)For most loads you will want the iGrow outputs to control a load relay or contactor that is connected to the motor.

However, irrigation valves that are 24 VAC, you can drive them directly assuming that you are wiring only one or two valves per relay. The maximum run current and voltage is 1 Amp / 24 volts

Pilot RelaysSignaling the High Current Load Relays /

Contactors

iGrow800 – Relay Output Design and Understanding

Page 3: iGrow800 Stand Alone Controller Installation Information

1-Wet Wiring Example1 – 24v Transformer source powering multiple Outputs

for controlling multiple control relays

2 - Dry Wiring Examples2 – 24v Transformer each Powering

its own dedicated output for controlling a single piece of

equipment. Common for heaters & Chill systems which have there own

24v thermostat control source

1 – Proportional Dry wirng for Motor Controller Example

1 Paired set of Outputs powered by 24v Transformer from motor controller. 1st output for Open

& 2nd output for Close signal

iGrow800 – Relay Output Design and Understanding

Note: for Proportional equipment using 2 outputs you would have to use an Odd/Even pair of adjacent outputs1-2, 3-4, 5-6 etc..

Page 4: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Wiring Diagram Examples

Page 5: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Wiring Diagram Examples

Wiring an Irrigation Solenoid

Wiring an iDrive Motor Controller

Page 6: iGrow800 Stand Alone Controller Installation Information

iGrow800 Stand AloneIntegrating with Link4

Standard Panel

Page 7: iGrow800 Stand Alone Controller Installation Information

Understanding how to wire your Link44 Output Expansion Boards

iGrow800 - 4 Output Expansion Board

Page 8: iGrow800 Stand Alone Controller Installation Information

Wiring a RS232 to RS485Converter Board

To Stand Alone Controller

The following describe instructions for an alternative connection of the converter board to the communication module that allows the

enclosure to be closed. The final result is shown in the following picture.

Page 9: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Sensor Installation – what sensors it supports

Digital Temp & Humidity Sensor

100 Series Weather Station

Analog Temperature Probe

AspiratedDigital Temp &

Humidity Sensor

Digital Integrated Sensor Module

AnemometerStand Alone

Solar Light SensorStand Alone

Optical Rain SensorStand Alone

Page 10: iGrow800 Stand Alone Controller Installation Information

Analog Sensor Use Combinations1) In Temp 2) Out Temp3) Analog Sensor Averaging4) Back Up In Temp5) In & Out Temp6) In & Out & Back Up In Temp7) In Temp Averaging & Out Temp8) In Temp Averaging & Out Temp & Back

Up In Temp

PolarityDoes not matter

Analog MappingIn Temp – only Analog 1Out Temp – Analog 1 thru 8Averaging – Analog 1 thru 8Back Up In Temp – Analog 1 thru 8

iGrow800 – Sensor Installation – Analog Probe Wire Installation

Page 11: iGrow800 Stand Alone Controller Installation Information

In Temperature Out Temperature Backup In Temperature

Single Probe

Averaging with

multiple probes

Sensor Mapping

With Analog Probe

Page 12: iGrow800 Stand Alone Controller Installation Information

PolarityDoes not matter

iGrow800 – Sensor Installation – Analog Probe In Temp Averaging

In Temp Averaging with

multiple probes

PolarityDoes not matter

Analog MappingIn Temp – only Analog 1Out Temp – Analog 1 thru 8Averaging – Analog 1 thru 8Back Up In Temp – Analog 1 thru 8

Page 13: iGrow800 Stand Alone Controller Installation Information

GND – Black Wire3V – Red Wire

CLK – White WireDAT1 – Green Wire

Sensor MappingIn Temp – Digital 1In Humidity – Digital 1

iGrow800 – Sensor Installation – Digital Temp & Humidity Sensor Wire Installation

Page 14: iGrow800 Stand Alone Controller Installation Information

GND – Black Wire3V – Red Wire

CLK – White WireDAT1 – Green WireGND – Blue Wire12V- Brown Wire

Sensor MappingIn Temp – Digital 1In Humidity – Digital 1

iGrow800 – Sensor Installation – Digital Temp & Humidity Sensor (Aspirated) Wire Installation

Page 15: iGrow800 Stand Alone Controller Installation Information

GND – Black Wire12V – Red Wire

CLK – White WireDAT2 – Green Wire

Sensor MappingIn Temp – Digital 2 In Humidity – Digital 2C02 – Digital 2Light – Digital 2

iGrow800 – Sensor Installation – Digital Integrated Multi-Sensor (DISM) Wire Installation

Page 16: iGrow800 Stand Alone Controller Installation Information

TerminationPoints

------------V+ – Red Wire

LGHT - Black Wire

iGrow800 – Sensor Installation – Solar Light Sensor (Stand Alone)

Sensor MappingOut Light – Enable

Page 17: iGrow800 Stand Alone Controller Installation Information

TerminationPoints

------------GND – Black Wire

3V – Red WireGND – White Wire

RAIN – Green Wire

iGrow800 – Sensor Installation – Optical Rain Sensor (Stand Alone)

Sensor MappingRain – Enable

Page 18: iGrow800 Stand Alone Controller Installation Information

TerminationPoints

------------GND – Green WireDIR – Yellow WireGND – Red WireSPD – Black Wire

iGrow800 – Sensor Installation – Anemometer Sensor (Stand Alone)

Sensor MappingWind – Enable

Page 19: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Sensor Calibration

Next / Previous allows you to toggle thru the different sensors you have installed

Editallows you to calibrate and change the sensor

value

RAW: Is what the sensor actually reads

CAL: is the increase/decrease amt you want the sensor to change

ADJ: is the sensor value that will be displayed on home screen, as well as the value the controllers programming will respond to.

Page 20: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Setpoint Understanding

Cool Setpoint - if the temp goes above this threshold it will enter cooling stages to bring the temp back in line within the Normal temp range (you can have up to 6 cool stages)

Heat Setpoint - if the temp goes below this threshold it will enter Heating stages to bring the temp back in line within the Normal temp range (you can have up to 2 heat stages)

Humidify Setpoint - if the RH reading is below this parameter, the condition is considered too dry, and the system will go into the humidification stage.Dehumidify Setpoint - if the RH reading is above this parameter, the condition is considered too damp, and the system will go into the dehumidification stage.

C02 Setpoint - if the C02ppm level is blow this parameter, the condition will be Low C02, and the system will start injecting C02 until it reaches the Setpoint plus Deadband.Note:* Temperature, Relative Humidity, and C02 can have up to 3 setpoints in a 24-hour time period.* Start Times set for setpoints are the same for Temperature, Relative Humidity, and C02

You can program setpoints for

Temperature ~ Relative Humidity ~ C02

You can program Setpoint Times for

Day ~ Night ~ DIF (or the difference between day & night)

Page 21: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Setting Stages – Temperature & Relative Humidity

Temp & Relative Humidity Stages can be set from the Main Menu

Temp & Relative Humidity Stages can be set from the Equipment Settings Screen

Page 22: iGrow800 Stand Alone Controller Installation Information

1

2

3

1 2 3

4 5 6

All Equipment Stages All Equipment StagesSingle output view of Equipment Stages

iGrow800 – Setting Stages – Temperature

From Stages on main menu

From the equipment settings screen

Page 23: iGrow800 Stand Alone Controller Installation Information

On/Off Equip Type Checked = device ON

for that stageUnchecked = OFF for

that stage

Vent Equip Type Input % increments on each cool

stage

Curtain & C02 Equip Type temp stages are not applicable

Vents at 100% = fully Open | 0% = fully Closed

To Navigate in Screen use buttons 5.6.7.8

5 up | 6 down | 7 left |8 right OK & SetupUse to change the state of the

highlighted stage.

Menu WheelUse to

increase &decrease

Percentage values for

Vent & Shade Equipment

Types

iGrow800 – Setting Stages – Temperature

Page 24: iGrow800 Stand Alone Controller Installation Information

1

2

3

1 2 3

4 5 6

All Equipment Stages All Equipment StagesSingle output view of Equipment Stages

From Stages on main menu

From the equipment settings screen

iGrow800 – Setting Stages – Relative Humidity

Page 25: iGrow800 Stand Alone Controller Installation Information

C02 Equip Type on Relative Humidity stages are not applicable

On/Off Equip Type

Override OFF device is OFF in that stage

Override ONdevice is ON in that stage

No Changedevice doesn't have an

effect in that stage

Vent & Curtain Equip Type Input % increments on each

Relative Hum Stage

Vents at 100% = fully Open | 0% = fully Closed

Curtains at 100% = fully covered | 0% = uncovered

To Navigate in Screen use buttons 5.6.7.8

5 up | 6 down | 7 left |8 rightOK & Setup

Use to change the state of the

highlighted stage.

Menu WheelUse to

increase &decrease

Percentage values for

Vent & Shade Equipment

Types

iGrow800 – Setting Stages – Relative Humidity

Page 26: iGrow800 Stand Alone Controller Installation Information

iGrow800 – Setting Stages – ADVANCE Relative Humidity settings

From Home Screen

press OK -> 3. System Setup -> 10. Advance

In advance settings

press button #1 Humidity Settings

Page 27: iGrow800 Stand Alone Controller Installation Information

Relative Humidity by default Cycles

2 minutes ON1 minute OFF

You can change these ON/OFF values min/sec with

buttons 1 thru 4 Menu Wheel

increases/decreases values

to make RH run without a cycle and run constantly

non-stopSet off time to 0

Set Low Out Temp If Out Temp falls below this value the

Cold De-Hu will work and override the De-Hum

Set Low Out Temp De-Hum = regular Dehumidification control

Cold De-Hu = is Cold Dehumidification control which occurs when Out Temp is below the Low Out Temp Threshold

To enable this feature you must have Out Temp Analog probe installed