State of Washincfton PRINTED: 08/05/2019 FORM APPROVED STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION (X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: 60429197 (X2) MULTIPLE CONSTRUCTION A. BUILDING: B. WING NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY. (X3) DATE SURVEY COMPLETED 07/26/2019 TATE, ZIP CODE CASCADE BEHAVIORAL HOSPITAL 1284,4,,MILI1:ARYROAD SOUTH (X4) ID PREFIX TAG L 0001 L 070] SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) INITIAL COMMENTS STATE LICENSING SURVEY The Washington State Department of Health (DOH) in accordance with Washington Administrative Code (WAC), Chapter 246-322 Private Psychiatric and Alcoholism Hospitals, conducted this health and safety survey. Onsite dates: 07/23/19 - 07/26/19. Examination number: 2019-691 The survey was conducted by: Surveyor #6 Surveyor #10 The Washington Fire Protection Bureau conducted the fire life safety inspection, During the course of the survey, surveyors assessed issues related to complaint 2019-2838 HPSY. 322-025.1A RESP & RIGHTS-COMPLIANCE WAC 246-322-025 Responsibilities and Rights - Licensee and Department. (1) The licensee shall: (a) Comply with the provisions of chapter 71.12 ROW and this chapter; This Washington Administrative Code is not met ID PREFIX TAG LOGO L 070 PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) 1. A written PLAN OF CORRECTION is required for each deficiency listed on the Statement of Deficiencies. 2, EACH plan of correction statement must include the following: The regulation number and/or the tag number; HOW the deficiency will be corrected; WHO is responsible for making the correction; WHAT will be done to prevent reoccurrence and how you will monitor for continued compliance; and WHEN the correction will be completed. 3. Your PLANS OF CORRECTION must be returned within 10 calendar days from the date you receive the Statement of Deficiencies. Your Plans of Correction must be postmarked by August 16, 2019. 4. Return the ORIGINAL REPORT with the required signatures. (X5) COMPLETE DATE State Form 2567 LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE U^JUc^A—UG TITLE Udo T_N (X6) DATE /L-0\(;t' STATE FORM NGVJ11 If continuation sheet 1 of 20

IDENTIFICATION NUMBER: Administrative Code (WAC), …L410 Continued From page 4 consistent with this chapter and services provided; (v) Food service consistent with chapter 246-215

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • State of Washincfton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTIONA. BUILDING:

    B. WING

    NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY.

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    TATE, ZIP CODE

    CASCADE BEHAVIORAL HOSPITAL 1284,4,,MILI1:ARYROAD SOUTH

    (X4) IDPREFIX

    TAG

    L 0001

    L 070]

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    INITIAL COMMENTS

    STATE LICENSING SURVEY

    The Washington State Department of Health(DOH) in accordance with WashingtonAdministrative Code (WAC), Chapter 246-322Private Psychiatric and Alcoholism Hospitals,conducted this health and safety survey.

    Onsite dates: 07/23/19 - 07/26/19.

    Examination number: 2019-691

    The survey was conducted by:

    Surveyor #6Surveyor #10

    The Washington Fire Protection Bureauconducted the fire life safety inspection,

    During the course of the survey, surveyorsassessed issues related to complaint 2019-2838HPSY.

    322-025.1A RESP & RIGHTS-COMPLIANCE

    WAC 246-322-025 Responsibilities andRights - Licensee and Department. (1)The licensee shall: (a) Comply withthe provisions of chapter 71.12 ROWand this chapter;This Washington Administrative Code is not met

    IDPREFIX

    TAG

    LOGO

    L 070

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    1. A written PLAN OF CORRECTION isrequired for each deficiency listed on theStatement of Deficiencies.

    2, EACH plan of correction statementmust include the following:

    The regulation number and/or the tagnumber;

    HOW the deficiency will be corrected;

    WHO is responsible for making thecorrection;

    WHAT will be done to preventreoccurrence and how you will monitor forcontinued compliance; and

    WHEN the correction will be completed.

    3. Your PLANS OF CORRECTION mustbe returned within 10 calendar days fromthe date you receive the Statement ofDeficiencies. Your Plans of Correctionmust be postmarked by August 16, 2019.

    4. Return the ORIGINAL REPORT withthe required signatures.

    (X5)COMPLETE

    DATE

    State Form 2567LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE

    U^JUc^A—UGTITLE

    Udo T_N(X6) DATE

    /L-0\(;t'

    STATE FORM NGVJ11 If continuation sheet 1 of 20

  • State of WashincjtQji

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE

    CASCADE B^OKAL HOSPITAL ^"^3^ SOUTH

    (X4) IDPREFIX

    TAG

    L 070 I

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    Continued From page 1

    as evidenced by:

    Based on observation and record review, thehospital failed to submit its policy for charity carewithin 30 days of adoption to the WashingtonDepartment of Health (Item #1); and failed tomake the policy available on the hospital's publicwebsite (Item #2).

    Failure to provide patient rights policies to thepublic risks patients' ability to make informeddecisions regarding access to care.

    Reference: RCW 70.170.060 - Current versionsof the hospital's charity care policy, a plainlanguage summary of the hospital's charity carepolicy, and the hospital's charity care applicationfor must be available on the hospital's web site.

    WAC 246-453-070 (1) Each hospital shalldevelop, and submit to the department, charitycare policies, procedures, and sliding feeschedules consistent with the requirementsincluded in WAC 246-453-020, 246-453-030,246-452-040, and 246-453-050. Any subsequentmodifications to those policies, procedures, andsliding fee schedules must be submitted to thedepartment no later than thirty days prior to theiradoption by the hospital,

    Findings included:

    Item #1 Policy update

    1. Review of the hospital policies posted on theWashington State Department of Health (DOH)internet website showed that the hospital'sun-dated, un-numbered policy titled "FinancialAssistance and Charity Care," was most recentlyupdated with DOH in January 2014.

    IDPREFIX

    TAG

    L 070

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 2 of 20

  • SState of Washington

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPL1ER/CLIAIDENTIFICATION NUMBER-.

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L 070

    L 335

    Continued From page 2

    2. On 07/25/19 at 3:15 PM, the Director of Risk &Quality (Staff #601) provided Surveyor #6 with thehospital's policy number ADM.C.300, titled"Charity Care," approved 02/19. Staff #601 statedit was the current policy for charity care.

    Item #2 Charity care access

    1. Review of the hospital's internet websiteshowed that neither a policy for charity care, noran application for charity care was available orreferenced.

    2. On 05/26/19 at 2:00 PM, during the surveyors'exit conference, the Director of Risk & Quality(Staff #601) confirmed the hospital's internetwebsite had not been updated to include thecurrent policy for charity care.

    322-035.1GPOLICIES-EMERGENCYCARE

    WAC 246-322-035 Policies andProcedures. (1) The licensee shalldevelop and implement the followingwritten policies and proceduresconsistent with this chapter andservices provided: (g) Emergencymedical care, including: (I) Physicianorders; (ii) Staff actions in theabsence of a physician; (iii) Storingand accessing emergency supplies andequipment;This Washington Administrative Code is not metas evidenced by:

    Based on observation, interview, and review ofhospital policies and procedures, the hospitalfailed to ensure staff checked and verified the

    L 070

    L 335

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 3 of 20

  • State of Washington

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING;

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE

    CASCADE BEHA.OKAL HOSPITAL ^^^D SOUTH

    (X4) IDPREFIX

    TAG

    L 335 I

    L 410|

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    Continued From page 3

    correct serial-numbered lock when performing adaily Emergency Crash Cart EquipmentChecklist.

    Failure to verify the correct serial-numbered lockon the emergency cart could result in a cartwithout the supplies listed within that could riskpotential delays In providing emergency care.

    Findings included:

    1. Review of the hospital's policy and proceduretitled, "Emergency Cart" policy number PC.C.110,reviewed 01/19, showed that there are seven (7)emergency carts in the hospital and checkednightly by the Charge Nurse. A log fordocumenting daily checks is located on the cartincludes: date, lock serial number, locked Y/N,suction checked Y/N, back board, and signatureof the staff member checking the cart.

    2. On 07/24/19 at 2:00 PM, Surveyor #10inspected the emergency cart located on the 3rdfloor North Unit. A review of the emergency cartchecklist for July 2019 showed a lock serialnumber #154254 entered for the last 24 days, onthe list. A closer look at the actual red serial lockshowed a lock number #326884.

    3. During an interview on 07/24/19 at 3:50 PM,the North Unit Nurse Manager (Staff #1001)confirmed the incorrect checklist entry.

    322-035.1V POLICIES-FOOD SERVICE

    WAC 246-322-035 Policies andProcedures. (1) The licensee shalldevelop and implement the followingwritten policies and procedures

    IDPREFIX

    TAG

    L 335

    L410

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    State Form 2567

    STATE FORM NGVJ11 Ifcontinuation sheet 4 of 20

  • PRINTED: 08/05/2019FORM APPROVED

    State of WashinptonSTATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA.WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATiON)

    IDPREFIX

    TAG

    PROVIDER'S PU^N OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L410 Continued From page 4

    consistent with this chapter andservices provided; (v) Food serviceconsistent with chapter 246-215WAC and WAC 246-322-230.This Washington Administrative Code is not metas evidenced by:

    Based on document review and interview, thehospital failed to develop and implement policiesand procedure to ensure compliance with theWashington State Retail Food Code (Chapter246-215 WAC).

    Failure to develop food service policies that directfood preparation and service in compliance withfood safety standards places patients and staff atrisk from food borne illness.

    Findings included:

    1. On 07/24/19 between 9:00 AM and 10:15 AM,Surveyor #6 toured the kitchen and dining roomwith the Dietary Services Director (Staff #602).During the tour, the surveyor requested a copy ofthe hospital's policy for cooling potentiallyhazardous foods (PHF). Staff #602 provided aninformation sheet copied from the New York StateDepartment of Health's public website.

    2. On 07/24/19 at 2:00 PM, during an interviewwith the Director of Risk & Quality (Staff #601),Surveyor #6 requested copies of all food servicepolicies. At 3:15 PM Staff #601 provided copies oftemperature logs, food storage logs, sanitizerlogs, and food safety information handouts. Staff#601 stated that she was not able to locate anyapproved policies related to food sen/ice.

    L410

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 5 of 20

  • State of Washington

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2» MULTIPLE CONSTRUCT!ON

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PU\N OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L 420

    L 420

    Continued From page 5

    322-040,1 ADMIN-ADOPT POLICIES

    WAC 246-322-040 Governing Body andAdministration. The governing bodyshall: (1) Adopt written policiesconcerning the purposes, operation andmaintenance of the hospital, and thesafety, care and treatment ofpatients;This Washington Administrative Code is not metas evidenced by:

    Based on interview, medical record review, andreview of the hospital's policies and procedures,the hospital failed to assure that policies andprocedures were reviewed and revised to reflectcurrent clinical practice.

    Failure to review and revise policies to reflectcurrent practice prevents the hospital staff fromcarrying out all of the functions of the organizationand risks unsafe, inconsistent patient care.

    Findings included:

    1. Record review of the hospital's policy andprocedure titled, "Policies and Procedures," policy#ADIV1.P.500 reviewed 05/19, showed that thehospital will have policies and procedures in placethat will reflect evidence-based practice andguide staff to carry out all of the functions of thehospital to promote safe, consistent, high-qualitycare.

    a. Record review of the hospital's policy andprocedure titled, "Diabetes: Patient Care," policy#PC.D.200 reviewed 02/19, showed that staff willtreat a blood sugar level below 70 by following thehypoglycemia protocol and staff will not withholdscheduled insulin doses. For treatment of high or

    L 420

    L 420

    State Form 2567STATE FORM NGVJ11 If continuation sheet 6 of 20

  • State of Washinqton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTIONA. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA.WA 98168

    (X4» IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L 420 Continued From page 6

    low blood sugar levels, staff will foilow physicianorders and/or Cascade Behavioral Hospitalnursing procedure.

    b. Record review of the hospital's pharmacypolicy and procedure titled, "IntravenousTherapy," policy #MM.05.01.07 reviewed 05/18,showed that the hospital offers no intravenoustherapy services (no IV solutions or supplies) anda home health agency will administer allintravenous medication on site.

    2. Review of Patient #1 001 's medical record on07/24/19 at 1:25 PM, showed a pre-printed ordersheet to guide staff on the treatment of thepatient's blood glucose levels. Review of theorder form showed it was labeled with thepatient's ID stamp and a hand written noteshowing orders were faxed to pharmacy. The topof the form showed orders for monitoring thepatient's blood glucose (before meals & atbedtime), showed Regimen #1 and #2 guidelinesfor supplemental insulin according to the currentpatient's blood glucose level, and the bottom ofthe form showed the hypoglycemia protocol.

    The hypoglycemia protocol provides steps thatstaff will follow to treat a diabetic patient with ablood glucose level

  • State ofWashinfiton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTIONA. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVfDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS. CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKW1LA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L 420

    L715

    Continued From page 7

    3. During an interview on 07/24/19 at 2:00 PM,the Chief Nursing Officer [CNO] (Staff #1002)confirmed that the hospital does not provide staffsupplies or medications to administer medicationintravenously. The CNO was asked how staffcould follow the hypoglycemia protocol for Patient#1001 if the hospital does not provide intravenousservices. The CNO stated that if the patient'sblood glucose level reaches a critical point andbecomes unconscious, then staff are to call 911.

    4. During an interview on 07/25/19 at 1:00 PM,the hospital's Pharmacist (Staff #1003) reviewedPatient #1001's blood glucose order form andrevealed that the form's approval date (showed inthe footer) was 05/18. The Pharmacist alsostated that the hospital does not stock D50Wintravenous solutions and it is not available. Hestated that the pre-printed blood glucose orderform will need to be reviewed and revised by theP & T committee.

    322-100.1E INFECT CONTROL-PROVISIONS

    WAC 246-322-100 Infection Control.The licensee shall: (1) Establish andimplement an effective hospital-wideinfection control program, whichincludes at a minimum: (f) Provisionsfor: (i) Providing consultationregarding patient care practices,equipment and supplies which mayinfluence the risk of infection;(ii) Providing consultation regardingappropriate procedures and productsfor cleaning, disinfecting andsterilizing; (iii) Providing infection

    L 420

    L715

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 8 of 20

  • State of Washinaton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTfON

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A, BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L715 Continued From page 8

    control information for orientationancf in-service education for staffproviding direct patient care; (iv)Making recommendations, consistentwith federal, state, and locallaws and rules, for methods of safeand sanitary disposal of: (A)Sewage; (B) Solid and liquid wastes;and (C) Infectious wastes includingsafe management of sharps;This Washington Administrative Code is not metas evidenced by:

    Based on observation, interview, and documentreview, the hospital failed to implement aneffective procedure to monitor the physicalenvironment for situations that support the growthof microorganisms that could spread infectiousdisease.

    Failure to prevent the growth and spread ofwaterborne pathogens places patients, staff, andvisitors at risk for infections.

    Reference: CDC Legionelia Toolkit, Developing aWater Management Program to ReduceLegionella Growth & Spread in Buildings; APractical Guide to Implementing IndustryStandards, updated 05/15/17. Elements of aneffective water management program includeidentification of areas where water could pool andstagnate, apply and monitor control measures,establish corrective actions to intervene whencontrols are not met, evaluate the program'seffectiveness, and document the activities.

    Findings included:

    1. Document review of the hospital's policy titled,"Water Management Plan," Policy #F.WMP. 100

    L715

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 9 of 20

  • PRINTED; 08/05/2019FORM APPROVED

    State of WashinatonSTATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING;

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L715 Continued From page 9

    approved 11/18, showed that ice/water dispenserdrain lines are not identified as areas where watercould pool and stagnate; control measures/limits,including elimination of stagnant water andmonitoring disinfectant levels are not identified;corrective actions do not address equipmentdrain lines; and the verification process(evaluation) refers to semiannual testing withoutidentifying testing protocols.

    Document review of Follett Symphony series Iceand Water Dispensers Installation, Operation andService Manual showed that drains must maintainat least 1/4-inch per foot of slope on horizontalruns.

    2. During the survey, Surveyor #6 made thefollowing observations of 6 ice/water dispensers:

    a. On 07/23/19 at 2:00 PM, Surveyor #6 touredUnit 2-W with the Chief Nursing Officer (CNO)(Staff #603). Surveyor #6 observed a Follettbrand Symphony series ice/water dispenser in thedining room. The lce/water dispenser's drain lineran horizontally with a dip that allowed water topool. The drain line did not maintain the requiredslope.

    b. On 07/24/19 at 10:10 AM, Surveyor #6 touredthe hospital's kitchen and cafeteria with theDietary Director (Staff #609). Surveyor #6observed a Hoshizaki brand ice/water dispenserwith a clear PVC (polyvinyi chloride) drain hosethat rested horizontally across the flat surface of acabinet for a length of approximately 2-feet. Thedrain hose showed significant black slimeaccumulation indicating bacterial growth.

    c. On 07/24/19 at 10:55 AM, Surveyor #6 touredUnit 2-N with the Nurse Manager (Staff #609).

    L715

    State Form 2567

    STATE FORM NGVJ11 if continuation sheet 10 of 20

  • State of'Washinqton

    PRINTED; 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTtFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L715 Continued From page 10

    Surveyor #6 observed a Follett brand Symphonyseries ice/water dispenser in the Day Room. Theice/water dispenser's drain line ran horizontallywith a dip that allowed water to pool. The drainline did not maintain the required slope.

    d. On 07/25/19 at 10:50 AM, Surveyor #6 touredUnit 3-N with the Nurse Manager (Staff #610) andthe Director of Facilities (Staff #606). Surveyor #6observed a Follett brand Symphony seriesice/water dispenser in the Clean Utility room. Theice/water dispenser's drain line ran through anopening in the countertop and was not visible.Staff #606 stated that special tools were requiredto access the space below the countertop andthat the drain line installation was the same asother countertop ice/water dispensers. Staff #606stated he did not know whether the drain linemaintained the required slope.

    e. On 07/25/19 at 11:30 AM, Surveyor #6 touredUnit 3-W with the Nurse Manager (Staff #611)and the Director of Facilities (Staff #606).Surveyor #6 observed a Follett brand Symphonyseries ice/water dispenser in the pantry for thedining room. The ice/water dispenser's drain lineran through an opening in the countertop and wasnot visible. Staff #606 stated that special toolswere required to access the space below thecountertop and that the drain line installation wasthe same as other countertop ice/waterdispensers. Staff #606 stated he did not knowwhether the drain line maintained the requiredslope.

    f. On 07/25/19 at 11:45 AM, Surveyor #6 touredUnit 4-W with the Nurse Manager (Staff #611)and the Director of Facilities (Staff #606).Surveyor #6 observed a Follett brand Symphonyseries ice/water dispenser in the Clean Utility

    L715

    State Form 2567STATE FORM NGVJ11 If continuation sheet 11 of 20

  • State ofWashinflton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER STREET ADDRESS. CITY, STATE, ZIP CODE

    CASCAOH B.HAVIOR^ HOSPITAL :S^S:D SOUTH

    (X4) IDPREFIX

    TAG

    L715|

    L 815|

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    Continued From page 11

    room. The ice/water dispenser's drip tray was fullof water (not draining). The drain line ran throughan opening in the countertop and was not visible.Staff #606 stated that special tools were requiredto access the space below the countertop andthat the drain line installation was the same asother ice/water dispensers. Staff #606 stated hedid not know whether the drain line maintainedthe required slope.

    322-120.7 MAINTENANCE P&P

    WAC 246-322-120 Physical EnvironmentThe licensee shall: (7) Implementcurrent, written policies, procedures,and schedules for maintenance andhousekeeping functions;This Washington Administrative Code is not metas evidenced by:

    Based on observation, document review, andinterview, the hospital failed to ensure that staffmembers properly performed housekeepingfunctions, including failure to maintain a cleanenvironment (1), failure to maintain environmentalsurfaces in smooth, non-absorbent, and easilycleanable condition (2), and failure to adequatelyand effectively disinfect environmental surfaces inpatient rooms (3).

    Failure to properly perform housekeepingfunctions places patients, staff, and visitors at riskof increased exposure to allergens and harmfulmlcroorganisms.

    Findings included:

    Item #1 - Clean environment

    IDPREFIX

    TAG

    L715

    L815

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 12 of 20

  • State ofWashinqton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L 815 Continued From page 12

    Reference: Guidelines for EnvironmentalInfection Control in Health-Care Facilities.Recommendations from CDC and the HealthcareInfection Control Practices Advisory Committee(HICPAC), 2003; updated July 2019. Pg. 147. ERecommendations - Environmental Services;subsection E. Keep housekeeping surfaces (e.g.,floors, walls, and tabletops) visibly clean on aregular basis and clean up spills promptly.

    1. Document review of the hospital's policy titled,"Belongings (Patient)," policy #PC.B.100reviewed 02/19, showed that the hospital shouldprovide for safe and appropriate management ofpatients' personal belongings.

    Document review of the hospital's documenttitled, "Quick Reference: EnvironmentalCleaning," revised 10/17, showed that equipmentwith visibly soiled surfaces should be scrubbedwith a cleaner/detergent or disinfectant.

    2. On 07/23/19 from 10:50 AM to 3:10 PM,Surveyor #6 toured patient care areas with theChief Nursing Officer (CNO) (Staff #603). Theobservations showed unclean areas, excessiveamounts of dirt, dust, and debris, and items/areaswhose readiness for use could not bedetermined;

    a. Room #103 (used for video court) - patientcare equipment that could not be identified asclean or disinfected, or whether it had been used:a wheelchair, a disposable, cone-style face maskhanging from a push handle of the wheelchair, 2sets of cloth restraints lying on the seat of thewheelchair, 2 Ambu® disposable face masksloose in a drawer.

    b. Assessment Room #4 (used for medicalA/ital

    L815

    State Form 2567STATE FORM NGVJ11 If continuation sheet 13 of 20

  • PRINTED: 08/05/2019FORM APPROVED

    State of WashinfltonSTATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTIONA. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L815 Continued From page 13

    signs assessment) - no sanitizer/disinfectantwasavailable for sanitizing patient care items afteruse. There was no indicator that informed staffwhether the room was ready for use.

    c. Assessment Room #2 " contained soiledclothing and discarded paper products. Therewas no indicator that informed staff whether theroom was ready for use.

    d. Patient Belongings Storage (Room 4 in the "oldsurgical suite") - over-flowing garbage bin, trashon the floor throughout the room, disorganizedstorage of patient belongings on the floor andshelves intermingled with debris.

    e. Soiled Utility on Unit 2-W - stained surfaceunder the sink, dirt & debris along floor coving.

    f. An OfficeA/isitation Room on Unit 2-W - dirt &debris on the floor.

    3. On 07/23/19 at 11:15 AM. Surveyor #6interviewed Staff #603 and a Milieu Specialist(Staff #605) about the patient care items listed inRoom #103. Staff #605 stated that the wheelchairshould have been disinfected after patient use,but that she did not know whether that had beendone. Staff #605 stated she did not know of apolicy or procedure to launder cloth restraints,and that they might have been used up to 5 timesin the past year without being cleaned or sanitizedafter patient use. Staff #603 stated that theAmbu® bags were probably left over from aprevious hospital facility.

    4. On 07/24/19 from 10:40 AM to 1:45 PM,Surveyor #6 toured patient care areas with theDirector of Risk & Quality (Staff #601). Theobservation showed unclean areas and

    L815

    State Form 2567STATE FORM NGVJ11 If continuation sheet 14 of 20

  • State of Washinqton

    PRINTED: 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTIONA. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDERCIENCY)

    (X5)COMPLETE

    DATE

    L815 Continued From page 14

    accumulation of dirt, dust, and debris:

    a. Clean Utility on Unit 2-N " an electric razorblade guard was covered with whisker debris, theemergency cart had a layer of dust on the topsurface, 2 bladder scanners and a patient vitalsigns monitor had dried debris on the housingsurfaces; 3 rolling stands for patient careequipment had dust and debris on their surfaces.

    b. Seclusion room on Unit 2"N - accumulation ofdust in the corners & along the bed pedestal.

    c. Shower/toilet Room #386 on Unit 3-S-significant dust accumulation on exhaust fancover.

    Item #2 - Cleanable surfaces

    1. On 07/23/19 at 12:00 PM, during a tour ofpatient intake areas with the CNO (Staff #603),Surveyor #6 observed a couch in AssessmentRoom 2 with a tear in the vinyl upholstery suchthat the cloth padding was exposed. Cloth isabsorbent and not a cleanabte surface.

    2. At the time of the observation, the surveyorasked Staff #603 about the torn vinyl. Staff #603stated that a repair request would be madeimmediately.

    3. On 07/24/19 at 10:55 AM, during a tour ofpatient care areas with the Director of Risk &Quality (Staff #601), Surveyor #6 observeduncleanable surfaces in the Unit 2-N Dayroom:

    a. Five chairs with worn vinyl upholstery such thatthe structural mesh fabric was exposed. Themesh fabric is absorbent and not a cleanablesurface.

    L815

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 15 of 20

  • PRINTED: 08/05/2019FORM APPROVED

    State of WashinqtonSTATEMENT OF DERCIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKW1LA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFfCIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L815 Continued From page 15

    b. Wall surfaces along the window and on asupport column had deep gouges such thatsheetrock was exposed. Sheetrock is absorbentand not a cleanable surface.

    4. At the time of the observations, the surveyorasked Staff #601 about the worn vinyl andgouges in the wall. Staff #601 stated that thosesurfaces should be repaired.

    5. On 07/25/19 at 11:45 AM, during a tour ofpatient care areas with the Director of Facilities(Staff #606), Surveyor #6 observed uncleanablesurfaces in the Unit 4-W Clean Utility:

    a. Counter edges and cabinet doors had areas ofbroken and missing laminate such that particleboard was exposed. Particle board is absorbentand not a cleanable surface.

    b. Drawers and cabinet surfaces had areas ofswollen particle board.

    6. At the time of the observations, the surveyorasked the Unit 4-W Nurse Manager (Staff #611)about the exposed and swollen particle board.Staff #611 stated that the surfaces were notcleanable,

    Item #3 - Disinfection of environmental surfaces

    1. Reference Sheet Virex II 256 - EPAReg. No.70627-24 states that all surfaces must remainwet for 10 minutes.

    Document review of the hospital's policy titled,"Daily Cleaning of Toilet - Tub," Policy #ES.D.300dated 06/19, showed that facility staff are to useVirex 256 disinfectant solution to clean toilet seat,

    L815

    State Form 2567

    STATE FORM NGVJ11 If continuation sheet 16of20

  • PRINTED: 08/05/2019FORM APPROVED

    _ State of'lA/ashinqton.STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER STREET ADDRESS. CITY, STATE, ZIP CODE

    CASC.OB BEHAVIOP.L HOSPITAL :S^3Rr SOUTH

    (X4) IDPREFIX

    TAG

    L815|

    L1485I

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    Continued From page 16

    top, and underneath and around hinge.

    2. On 07/25/19 at 10:30 PM, Surveyor #6observed a housekeeper (Staff #607) perform aterminal cleaning of Patient Room #392 on Unit3-N, During the process, the surveyor observedineffective disinfectant use:

    a. Staff #607 used a wiping cloth that had beensoaked in Virex II 256 (a quaternary disinfectantsolution) to wipe surfaces around the room.When disinfecting the door handles and mirror,Staff #607 wiped the surfaces with thedisinfectant cloth and then immediately wiped thesurfaces with a dry cloth.

    b. Staff #607 used a disinfectant soaked cloth towipe the toilet bowl but used a dry cloth to wipethe toilet seat, top, and underneath.

    3. At the time of the observations, Surveyor #6asked Staff #607 about the disinfectant solution.Staff #607 stated that the solution was Virex andthat surfaces must remain wet 10 minute for thedisinfectant to be effective.

    322-230.1 FOOD SERVICE REGS

    WAC 246-322-230 Food and DietaryServices. The licensee shall: (1)Comply with chapters 246-215 and246-217 WAC, food service;This Washington Administrative Code is not metas evidenced by:

    Based on observation, interview, and documentreview, the hospital failed to implement policiesand procedures consistent with the WashingtonState Retail Food Code (Chapter 246-215 WAC).

    IDPREFIX

    TAG

    L815

    L1485

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFfCIENCY)

    (X5)COMPLETE

    DATE

    State Form 2567

    STATE FORM NGVJ11 !f continuation sheet 17 of 20

  • 6tate of Washington

    PRINTED; 08/05/2019FORM APPROVED

    STATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVfDER/SUPPLIER/CLIAIDENTIFICATION NUMBER;

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L1485 Continued From page 17

    Failure to follow food safety standards placespatients at risk from food borne illness.

    Findings included:

    Item #1 Potentially Hazardous Foods (PHF)temperature control

    1. On 07/24/19 between 9:10 AM and 10:30 AM,Surveyor #6 toured the hospital's kitchen andcafeteria with the Dietary Director (Staff #609).Surveyor #6 requested a copy of the hospital'spolicy for cooling potentially hazardous foods(PHF). Staff #609 provided an information sheettitled, "Cooling and Reheating of PotentiallyHazardous Foods." Review of the informationsheet showed that it is a page from the New YorkState Department of Health's public website. Thedocument directs that PHFs must be cooled to 45degrees Fahrenheit. Washington State RetailFood Code requires PHFs to be cooled to 41degrees Fahrenheit.

    Reference: Washington State Retail Food Code(WAG) 246-215-03515; WAC 246-215-03520

    2. During the survey, Surveyor #6 made thefollowing observations of phf cold holdingtemperatures that exceeded the requiredmaximum of41 degrees Fahrenheit:

    a. Unit 2-W pantry: Yi pint milk - 45.4 degreesFahrenheit; 6-oz container of yogurt - 49.1degrees Fahrenheit;

    b. Unit 3-W pantry: Vi pint milk" 45 degreesFahrenheit; cheese stick - 51 degreesFahrenheit.

    L1485

    State Form 2567

    STATE FORM NO VJ 11 If continuation sheet 18 of 20

  • PRINTED: 08/05/2019FORM APPROVED

    State of WashinqtonSTATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROV1DER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B, WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY. STATE, ZIP CODE

    CASCAOB B.HAVIO^ HOSPITAL :S^3Rr SOUTH

    (X4) IDPREFIX

    TAG

    L1485I

    L1565|

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    Continued From page 18

    Reference: Washington State Retail Food Code246-215-03525

    Item #2 Handwashing sink

    3. On 07/24/19 at 10:10 AM, Surveyor #6inspected the cafeteria. The surveyor observedthere was no handwashing sink near the cafeteriatray line, where staff plate and serve ready-to-eatfood.

    4. At the time of the observation, Surveyor #6interviewed a food service worker (Staff #612)about handwashing during food service at the trayline. Staff #612 stated that staff could use ahandwashing sink in the kitchen.

    The nearest handwashing sink to the cafeteria isthrough a latching door, across a hallway, andthrough another doorway. The nearesthandwashing sink does not allow convenient useby food employees, as required.

    Reference: Washington State Retail Food Code246-215-05255

    322-240.4A LAUNDRY-WATER TEMPERATURE

    WAG 246-322-240 Laundry. The licenseeshall provide: (4) When laundry iswashed on the premises: (a) Anadequate water supply and a minimumwater temperature of 140 F in washingmachines;This Washington Administrative Code is not metas evidenced by:

    Based on obsen/ation and interview, the hospitalfailed to ensure the water supply used for on-site

    IDPREFIX

    TAG

    L1485

    L1565

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    State Form 2567STATE FORM NGVJ11 If continuation sheet 19 of 20

  • PRINTED: 08/05/2019FORM APPROVED

    State of WashinfltonSTATEMENT OF DEFICIENCIESAND PLAN OF CORRECTION

    (X1) PROVIDER/SUPPLIER/CLIAIDENTIFICATION NUMBER:

    60429197

    (X2) MULTIPLE CONSTRUCTION

    A. BUILDING:

    B. WING

    (X3) DATE SURVEYCOMPLETED

    07/26/2019

    NAME OF PROVIDER OR SUPPLIER

    CASCADE BEHAVIORAL HOSPITAL

    STREET ADDRESS, CITY, STATE, ZIP CODE

    12844 MILITARY ROAD SOUTHTUKWILA,WA 98168

    (X4) IDPREFIX

    TAG

    SUMMARY STATEMENT OF DEFICIENCIES(EACH DEFICIENCY MUST BE PRECEDED BY FULL

    REGULATORY OR LSC IDENTIFYING INFORMATION)

    IDPREFIX

    TAG

    PROVIDER'S PLAN OF CORRECTION(EACH CORRECTIVE ACTION SHOULD BE

    CROSS-REFERENCED TO THE APPROPRIATEDEFICIENCY)

    (X5)COMPLETE

    DATE

    L1565 Continued From page 19

    patient laundry services reaches a minimumtemperature of 140 degrees Fahrenheit.

    Failure to use sufficiently hot wash water placespatients at risk of illness due to insufficientreduction of microbial contamination in patientlaundry.

    Findings included:

    1. On 07/24/19 at 9:10 AM, Surveyor #6 used aninstant read thermometer to assess thetemperature of hot water at a handwashing sinkin the hospital kitchen. The temperature wasassessed at 116.8 degrees Fahrenheit after 90seconds.

    At 11:05 AM, Surveyor #6 used an instant readthermometer to assess the temperature of hotwater at the service sink in the Soiled Utility roomon Unit 2-N. The temperature was assessed at104.1 degrees Fahrenheit after 3 minutes.

    2. On 07/25/19 at 10:00 AM, Surveyor #6interviewed the Facilities Director (Staff #606)and the CNO (Staff #603) about hot watertemperature available to the on-site washingmachines for patient laundry. Staff #606 statedthat each patient unit had a domestic washingmachine and that the hot water source for eachmachine was the same system that serves therest of the hospital. Staff #606 stated that none ofthe washing machines had heat boosters to raisethe water temperature to the required minimumtemperature of 140 degrees Fahrenheit.

    L1565

    State Form 2567STATE FORM NGVJ11 If continuation sheet 20 of 20

  • CASCADE BEHAVIORAL HEALTHPlan of Correction for

    State Licensing Survey

    July 23-26, 2019

    TagNumber

    L 070

    L 335

    L 410

    How the Deficiency Wilt Be Corrected

    Charity Care policy: The Chief FinancialOfficer revised the current Charity Care

    policy ADM.C.300 and submitted it to theDepartment of Health. It will be

    upioaded to Cascades website by8/30/19.

    Crash Cart: A new log will beimplemented by 8/23/19 on all crashcarts. All crash carts will be opened,

    expiration dates noted on all supplies inthe carts and carts will be re-locked on8/23/19. All nursing staff will be

    educated on the new logs and how to

    complete them properly on 8/29/19.Follow up education will be provided tothose who do not attend the 8/29/19nursing staff meeting.

    Foodborne Illness policy: The hospital's

    policies on foodborne illness were not

    located at the time of survey. Policies

    were subsequently located and placed inthe proper location on our public drive.

    Cooling foods policy: A policy for coolingpotentially hazardous foods will bedeveloped. Ail dietary staff will beeducated on this policy. This policy willbe submitted for approval by QualityCouncil and the Medicai Executive

    Responsible Individual(s)

    Chief Financial Officer

    Chief Nursing Officer

    Dietary Manager

    Dietary Manager

    Estimated Date ofCorrection

    8/14/19 submitted toDepartment ofHealth

    8/30/19 upload toCascade's website.

    New logs and audits

    will begin on 8/23/19and continue for a

    minimum of 3months to ensure

    sustained

    compliance.

    8/16/19

    9/13/19

    Monitoring procedure; Target for Compliance

    The Chief Financial Officer will be responsible

    for ensuring the Department of Health has themost current copy of the hospital's CharityCare policy annually. Cascade's website will

    reflect the same policy as well as an

    applicationfor charity care. Target forcompliance is 8/30/19

    Nursing Supervisors will audit the crash carts

    and the logs on a daily basis to ensuresustained compliance. Any deficiencies will be

    corrected immediately and staff will be re-

    educated if necessary. Target for compliance is

    8/23/19

    Dietary Manager re-educated regarding policy

    location and content.

    Kitchen staff will be educated on the CoolingFoods policy. New staff will receive education

    upon hire. Dietary Manager will continue tomonitor the temperatures and timeframes

    while cooling foods.

  • L 420

    L 715

    Committee during their August monthlymeetings.

    Intravenous Fluids: Both the pharmacy

    and hospital policies will be revised toremove instructions on treatment with

    intravenous fluids. The policy changeswill go through The Pharmacy andTherapeutics Committee/ Quality Counciland Medical Executive Committee attheir regularly scheduled Augustmeetings. All clinical staff will beeducated regarding the changes in the

    policies after final approval by the abovecommittees.

    Water Management plan: The Water

    Management policy will be revised toinclude the identification of ice/waterdrain lines as a place where water could

    stagnate; control measures/limits

    including the elimination of stagnantwater and the monitoring of disinfectantieveis. Verification process during

    semiannual testing identifies testing

    protocols and parameters.

    Ice Machines: All ice machines drain

    lines were inspected and adjusted tomeet the standard slope requirement on

    8/5/19. 2W drain line was reinstalled/kitchen line was replaced and reinstalled,

    2N reinstalled/ 3N checked and was atthe appropriate slope/ 3W checked andwas at the appropriate slope, 4W

    checked and was at the appropriateslope. Additionally/ all the ice machines

    have a built in drain separation inside theunits themselves to prevent backfill of

    any kind.

    Chief Medical Officer, LeadPharmacist & Chief

    Nursing Officer

    Director of Facilities

    Director of Facilities

    8/30/19

    9/27/19

    8/5/19

    New polices will be approved and clinical staffwill be educated by August 30th, 2019.The Chief Nursing Officer, Chief MedicalOfficer and Lead Pharmacist reviewed all otherpolicies to ensure no others mentioned

    intravenous therapy.

    The Water Management monitoring

    procedure will be developed and implementedby 9/27/19. Director of Facilities will reportwater management activities monthly to CEO

    moving forward.

    Inspected/corrected 8/5/19. Monthlyinspections of ice machine drain lines for any

    buildup, biockage and for correct slope by theDirector of Facilities will begin 9/2/19.

  • L 815Clean Environment: Belongings room

    Housekeeping staff completed a deepclean of the belongings room on 8/5/19.Housekeeping staff will dean this areadaily moving forward.

    Clean Environment: CourtWheel chair for court was cleaned.

    Cleaning/disinfecting wipes were stockedin the court area. Ambu bags were

    disposed of. Cloth Restraints were

    laundered. Nursing and court staff were

    educated on the mandatory cleaning ofthese items after each patient use:

    wheelchair, restraints and any other

    items that are used on a patient. A

    clipboard with a log was implemented todemonstrate that these items are

    cleaned after every patient use.

    Clean environment: Assessment rooms

    Staff have been provided with wipes for

    cleaning equipment and other surfaces

    between patients. A clipboard is postedto demonstrate when each room was

    last cleaned. The Dynamap (vital signmachine) was relocated to the

    admissions area and staff were trained

    regarding the new location for its storageand cleaning.

    All staff who discharge or admit patientsin these rooms have been instructed to

    clean the room after the patient has

    discharged and document the cleaningon the clipboard.

    The Director of Facilities is researchingoptions for indicators to be placedoutside the doors of these rooms to

    indicate if the room is in use/dirty or

    Director of Facilities

    Director of Facilities

    Chief Nursing Officer,Director of intake. Director

    of Facilities & Infection

    Control Nurse

    8/5/19

    8/5/19

    8/30/19

    Deep cleaning occurred on 8/5/19. Dailycleaning began 8/6/19. Director of Facilitieswill monitor this area weekly for cleanliness.

    Director of Facilities will include the

    monitoring of the cleaning and completion ofthe log on his monthly rounds beginning

    9/2/19.

    Intake staff and Nurse Supervisors wii! assess

    all of the rooms daily at random intervals for

    maintained compliance starting 8/30/19. Anyrooms found out of compliance will beimmediately cleaned and staff responsible wiiireceive 1:1 on the spot re-education.

    Infection Controi nurse will add these rooms

    to their monthly rounding and report anyfindings to CNO, Director of Intake andDirector of Facilities starting 8/30/19.

  • available/dean to install by 9/30/19.Housekeeping staff thoroughly clean allassessment rooms in the Intake areas

    once daily.

    Clean environment: 2N Clean utilityroom. Electric trimmer was removed and

    discarded. Disposable trimmers were

    purchased last year, staff reminded touse only those trimmers with thedisposable heads and to clean the basebetween each patient use. No other

    reusable trimmers remain at Cascade.

    Housekeeping staff were re-educated on

    cleaning all surfaces to include the crashcart tops.

    Nursing staff educated to clean allpatient care equipment after each

    patients use and if the item needs a

    more thorough clean on the bases or

    stands, they are to inform the Director of

    Facilities.

    Clean Environment; Cleanable Surfaces

    A complete hospital inspection wascompleted on furniture in patient care

    areas. Chairs were removed from the

    units/ soiled or damaged coverings were

    replaced with replaced with new vinyl on8/2/19. The couch in assessment room 2was sent out for repair and replaced with

    additional chairs until its return.

    Wall surface damage has been repaired

    and repainted in 2N.

    4 west utility room broken and missinglaminate on counter edges, cabinet

    doors and drawers are scheduled to be

    Director of NursingDirector of Facilitiesinfection Control Nurse

    Director of FacilitiesInfection Control Nurse

    8/6/19

    9/25/19

    Infection Control has added patient care

    equipment to their monthly rounds and willnotify Director of Nursing and the Director of

    Facilities if any items are in need of cleaning.Monthly Founding begins in August 2019.

    infection Control has added the inspection of

    all furniture to their monthly rounds and wiflreport any findings or soiled or damagedfurniture to the Director of Facilities monthlyfor immediate removal or repair. Monthly

    rounding begins in August 2019.Infection control will also monitor all cleanablesurfaces to include cabinets/ countertops/

    walls and floors on their monthly rounds forany damage and inform the Director of

    Facilities immediately/ if discovered/ to initiatea work order for repair.

  • L 1485

    repaired/replaced by an external vendoron 9/25/19

    Clean Environment: 2W soiled utilityroom, 21M seclusion room &

    office/visitation room have been deepcleaned. Housekeeping was re-educated

    about getting floor corners cleaned in ailareas of the hospital. The area below thesink on 2W has been cleaned andsecured closed with screws.

    Clean Environment Shower/toiletexhaust fans: All exhaust fans have been

    cleaned. They will be externally cleanedby housekeeping daily moving forward.Preventative maintenance is performed

    every 3 months where the exhaust fans

    are opened, assessed for proper

    functionality, oiled & deep cleaned.

    Clean Environment: Ineffectivedisinfectant use. All Housekeeping staffattended mandatory training on CleaningProcedures and proper disinfectant use

    on 8/9/19. They will also receiveadditional training from the cleaningvendor on 8/22/19 on disinfectant dwelltimes and cleaning procedures.

    Potentially Hazardous Foods: A policyfor cooling potentially hazardous foodswil! be developed and implemented by9/13/19. All dietary staff will be

    educated on this policy. This policy willbe formally approved in Quality Counciland the Medical Executive Committeeduring their August monthly meetings.

    Director of Facilities

    Infection Control Nurse

    Director of FacilitiesInfection Control Nurse

    Director of FacilitiesInfection Control Nurse

    Dietary ManagerDirector of FacilitiesInfection Control Nurse

    8/16/19

    8/16/19

    8/22/19

    9/13/19

    Director of Facilities and Infection Control willround monthly to assess the cleanliness of

    these areas. Any accumulation of dust, dirt or

    debris will be reported to Housekeeping toaddress immediately. Specialized training withcleaning vendor is scheduled on 8/22/19 for

    all housekeeping staff. Director of Facilitieswill follow up with individual staff regarding

    job performance.

    The Director of Facilities and Infection Control

    have added the inspection ofshower/toiletexhaust fans to their monthly rounds forinspection. Any findings will be reported forimmediate attention.

    The Director of Facilities will observehousekeeping staff during his monthly roundsand provide immediate 1:1 correction ifneeded. The infection Contro! will observe a

    minimum of one housekeeper monthly duringtheir surveillance rounds and report any

    deviation from proper process to the Directorof Facilities.

    Dietary Manager will ensure all new staff are

    trained on this policy upon hire. Random spot

    checks of appropriate temperatures will occur

    monthly by the Dietary Manager and theinfection Control Nurse. Ali findings will bereported to the Director of Nursing as well as

    the Director of Risk & Quality with anexpected compliance of 100%. This will be

  • L1565

    Patient refrigerators: All patientrefrigerators were inspected by theDirector of Facilities by 8/16/19 andwere found to be in good working order.

    It was determined that dietary staff wereallowing nursing to stock therefrigerators and staff have been

    stocking the patient refrigeratorsexcessively. Nursing staff have been

    instructed to call the kitchen if they runout of a particular item prior to the next

    delivery.

    Handwashing sink in Cafeteria: Anew

    handwashing sink will be installed in thecafeteria. This will require coordination

    with the Department of HealthConstruction Review Service and

    installation of new plumbing.

    Laundry water temperature: New hot

    water boosters will be ordered to bring

    the temperature of the water in allpatient washing machines to 140 F. This

    will require major work pertaining to theinstillation of dedicated electrical and

    plumbing to all patient units ascoordination with the Department ofHealth Construction Review Service..

    Dietary Manager

    Director of Facilities

    Director of Facilities

    Director of Facilities

    8/16/19

    1/26/20

    5/26/20

    followed for 3 months to ensure sustained

    compliance. Target date 9/13/19 to developand implement policy as well as train staff.

    Moving forward only dietary staff will stock asmaller par level of supplies in ail of thepatient refrigerators on the units. This willprevent overstocking and maintain

    temperature control inside the refrigerators.

    Refrigerator temperatures are monitored

    monthly by infection Control/ daily by Directorof Dietary and monthly by the Director ofFacilities. Any deviation outside the acceptable

    temperature range will immediately bereported to the Director of Facilities.

    Working with Department of HealthConstruction Review. Mitigation plan until

    construction is complete: a portable

    handwashing station will be purchased andplaced in the cafeteria.

    Working with Department of HealthConstruction Review Service. Mitigation plan

    until construction is complete: Patient iaundry

    will contain a chemical additive to decreasethe risk of illness due to insufficient reductionof microbial contamination until hot waterboosters are installed.

  • .- ^yA:-rt^/J^/

    c^.f^n^/1/ ^7 A

    CASCADE BEHAVIORAL HEALTHPlan of Correction for

    State Licensing Survey

    July 23-26,2019

    .€ i'^e-L

    ^ i!,-

    AUG 2 7 2019 ^-t'^^^-i!^^/"'

    ^ySETOS"*IVIonitoring procedure^ Tai^el

    ^ ?u< ^- /Y

    TagNumber

    How the Deficiency Will Be Corrected Responsible Individuals) Estimated Date ofCorrection

    ipliance

    L 410 Food Service Policies: The hospital'sfood semce policies were not located at

    the time of survey. Policies will be

    developed to address food preparation/

    cooiing, cold & hot food holding, and

    'storage to meet Washington State Retail

    Food Code standards. These policies will

    be submitted for approval by QualityCouncil and the Medical Executive

    Committee during their Septembermonthly meetings.

    Dietary Manager 9/30/19 Dietary Manager to re-educate staff regardingnew policies and how to reference them.

    Kitchen staff will be educated on all policies.

    New staff will receive education upon hire.

    Dietary Managerwill continue to monitor

    compliance. 100% compliance goal to beachieved by 10/1/2019. Monthly audit resultsreported to Quality Council

    L 815 Clean EnvironmentRoom #103 Video Court.

    Wheel chairfor court was cleaned.CieanEng/dismfecting wipes were stocked

    in the court area. Ambu bags were

    disposed of. Cloth Restraints were

    laundered. Nursing and court staff were

    educated on the mandatory cleaning of

    these items after each patient use:

    wheetchair/ restraints and any other

    items that are used on a patient. A

    clipboard with a log was implemented todemonstrste that these items are

    cleaned after ever/ patient use.

    Assessment rooms #2 and #4.

    Staff have been provided with wipes for

    cleaning equipment and other surfaces

    between patients. A clipboard is posted

    to demonstrate when each room was

    last cieaned. The Dynamap (vital sign

    Director of Facilities 9/3/19

    Chief Nursing Officer,Director of Intake/ Directorof Facilities & [infectionControl Nurse

    8/30/19

    Director of Facilities will incEude themonitoring of the deaning and completion of

    the log on his monthly rounds beginning

    9/3/19,

    Intake staff and Nursing supervisors will assess

    ail of the rooms daily at random intervals for

    maintained compliance starting 8/30/19. Anyrooms found out of compliance will be

    immediately cleaned and staff responsible will

    receive 1:1 on the spot re-educatio.n.

  • between each patient use. No otherreusable trimmers remain at Cascade.

    Housekeeping staff were re-educated oncleaning all surfaces to include the crash

    cart tops (see cieanabie surfaces beiow).

    Mursing staff educated to clean al!

    patient care equipment after each

    patients use and if the item needs a

    more thorough dean on the bases or

    stands/ they are to Inform the Director of

    Faciiities.

    Cleanable Surfaces

    Afuil hospital inspection was completed

    to ensure that furniture is in good repair

    with intact/ cleanable surfaces. Damaged

    or soiled fu miture was removed from

    the units/ and soiled or damaged

    coverings were replaced with replacedwith new vinyi on 8/2/19. The couch inassessment room 2 was sent out for

    repair and replaced with additional

    chairs until its return. Wall surface

    damage has been repaired and repainted

    m 2N.4 west utiitty room broken and

    missing laminate on counter edges/cabinet doors and drawers are scheduled

    to be repaired/replaced by an externalvendor on 9/25/19

    Shower/toilet exhaust fans. A!l exhaust

    fans have been cleaned. They will be

    externally cleaned by housekeeping daily

    moving forward. Preventative

    maintenance is performed every 3

    months where the exhaust fans are

    opened, assessed for proper

    functionality/ oiled & deep cleaned.

    Director of Facilities

    Infection Control Nurse

    /•

    Director of Facilities

    Infection Control Nurse

    8/16/1&

    8/22/19

    Infection Control has added the inspection ofall furniture to their monthiy rounds and willreport any findings or soiled or damagedfurniture to the Director of Facilities monthly

    for immediate removal or repair. Monthiy

    Founding begins in August 2019.

    infection control will also monitor alE cleanable.

    surfaces to include cabinets/ countertops/

    walls and floors on their monthly rounds for

    any damage and inform the Director of

    Facilities immediately, if discovered, to initiate

    a work order for repair.

    The Director of Facilities and Infection Control

    have added the inspection ofshower/toilet

    exhaust fans to their monthly rounds for

    inspection. Any findings will be reported forimmediate attention.

  • L 1485

    Disinfection of Environmental Surfaces

    Ineffective disinfectant use. AilHousekeeping staff attended mandaton/

    training on Cleaning Procedures andproper disinfectant use on 8/9/19. They

    will also receive additional training fromthedeaningvendoron 8/22/19 on

    disinfectant dweil times and cleaning

    procedures.

    Policies wil! be developed to meet

    Washington State Retail Food Codestandards. These policies will be

    submitted for approval by Quality

    Council and the Medicai Executive

    Committee during their September

    monthfy meetings.

    Potentiaify Hazardous Foods: A policy

    for cooling potentially hazardous foodsand implemented by 9/30/19. All dietary

    staff will be educated on this policy. This

    poiicywill be formally approved in

    Q.uality Council and the Medical

    Executive Committee during their August

    monthty meetings.

    Patient refrigerators: All patient

    refrigerators were inspected by the

    Director of FaciEities by S/16/19 andwere fou nd to be in good working order.

    It was determined that cfietary staff were

    aliowlng nursing to stock the

    refrigerators and staff have beenstocking the patient refrigerators

    excessively. Nursing staff have been

    instructed local! the kitchen if they run

    out of a particular item prior to the nextdeliver/.

    Director of Facilities

    Infection Control Nurse

    Dietary ManagerDirector of Facilitiesinfection Control Nurse

    Dietary ManagerDirector of Facilities

    Director of Facilities/

    Dietary Manager

    8/22/19

    9/30/19

    9/30/19

    9/16/19

    The Director of Facilities will observe

    housekeeping staff during his monthiy rounds

    and provide immediate 1:1 correction if

    needed. The Infection Control wiii observe a

    minimum of one housekeeper monthly during

    their surveillance rounds and report anydeviation from proper process to the Directorof Facflities.

    Dietary Manager will ensure all new staff are

    trained on this policy upon hire. Random spotchecks of appropriate temperatures will occur

    monthly by the Dietan/Manager and the

    Infection Control Nurse. All findings will be

    reported to the Director of Nursing as well as

    the Director of Risk & Quality with anexpected compliance of 100%. This will be

    followed for 3 months to ensure sustained

    compfiance. After 3 months/monthiymonitoring will continue ard be report&d to

    Quality Counc!]. Target date 9/30/19 todevelop and impiement policies as wel! as

    train staff.

    Movmg forward only dietary staff will stock a

    smaller par level of supplies in all of thepatient refrigerators on the units. This will

    prevent overstocking and maintain

    temperature control inside the refrigerators.

    Refrigeratortemperatures are monitored

    monthly by infection Control/ daiiy by Directorof Dietary and monthly by. the Director of

    Facilities. Any deviation outside the acceptabletemperature range will immediately be

    reported to the Director of Facilities.

  • Handwashing sink in Cafeteria: Anew

    handwashing sink will be instailed in the

    cafeteria. This wi!i require coordination

    with the Department of HealthConstruction Review Service and

    installation of new plumbing and a

    temporary hand-wash station thatcomplies with WAC 246-215-09225 will

    be utilized as an interim solution.

    Director of Facilities 1/2G/20 Working w'rth Department of HealthConstruction Review. Mitigation plan until

    construction is complete: a handwashingstation in compliance with WAC 246-215-

    09225 wili be purchased and placed in thecafeteria.

  • STATH 01'' WASHINGTON

    DEPARTMENT OP HEALTH

    October 1,2019

    Janet Huff, Director of Risk & QualityCascade Behavioral Health

    12844 Military Road STukwiIa,WA 98168

    Dear Ms. Huff:

    Surveyors from the Washington State Department of Health and the Washington State Patrol FireProtection Bureau conducted a state hospital licensing survey at Cascade Behavioral Health on

    July 23 - 26, 2019. Hospital staff members developed a plan of correction to correct deficienciescited during this survey. This plan of correction, including extension requests, was approved on

    September 27,2019.

    A Progress Report is due on or before October 24, 2019 when all deficiencies have been

    corrected and monitoring for correction effectiveness has been completed. The Progress Reportmust address all items listed in the plan of correction, including the WAC reference numbers and

    letters, the actual correction completion dates, and the results of the monitoring processesidentified in the Plan of Correction to verify the corrections have been effective. A sample

    progress report has been enclosed for reference.

    Please mail this progress report to me at the following address:

    Robin Munroe, RS

    Department of Health, Office of Health Systems OversightPO Box 47874Olympic Washington 98504-7874

    Please contact me if you have any questions. I may be reached at 360-236-2914. I am also

    available by email at robm.munroc^cloh.wa.Kov.

    Sincerely, '^?

    Robin Munroe, RS

    Survey Team Leader