i-3 Lighting ControlsSelection and Application Guide

www.usa.siemens.com/i-3

i-3 ControlTechnology™

Page 2: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

2

Page 3: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

P1 Series Lighting Panel with i-3 Control Technology™

3

The Siemens P1 Series Lighting Panelboard with i-3 Control Technology is the next step in engineering innovation for our lighting control

product portfolio. The i-3 is a lighting control solution that allows engineers and end users to integrate, install, and interface controllable

breakers into their electrical applications; hence the name i-3.

The i-3 is designed to provide a simple,flexible, compact solution for controlling branch lighting circuits remotely via a time schedule or

an external signal (i.e. a switch, Building Automation System, etc.). The i-3 reduces energy consumption by providing programmable

remote control of our patented SIPODs, which are connected to Siemens BQD frame breakers. This modular design produces a “smart”

breaker system that lowers installation costs, minimizes the impact and cost of future system modifications, makes retrofit applications less

tedious, and reduces component replacement costs. The i-3 offers a touch screen panel on its system controller that provides a user friendly

graphical interface for commissioning and scheduling. i-3 components mount inside a standard P1 lighting panelboard. The i-3 can

stand alone or be networked into a larger Building Automation System (BAS).

Page 4: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Contents

P1 Series Lighting Panel 5

i-3 System Overview 6

Branch Circuit Breakers 7

SIPOD™ 8-9

Emergency SIPOD™ 10-11

Controllers 12

I/O Controller 13

I/O Configuration Software 14

System Controller 15

USB Interface 16

Communication andNetworking Configurations

17

Dimensions 18

Ordering Information 19-21

Integrated PowerSystem Switchboards

22

4

Page 5: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

5

P1 Series Lighting Panel

integration J Small footprint — can stack up to two 42 circuit panels in one section of an IPS Switchboard J Reduced labor costs -- add to existing P1 installations by simply replacing interior, using the current enclosure. J Enhanced power management -- control up to eight panels from a single system controller.

interface J EIB, MODBUS, BACnet and dry contact capable J USB interface for uploading and downloading panel configurations (Only with System Controller) J Integrated touch panel w/intuitive commissioning setup wizards (no PC required). PC interface also available.

installation J Modular design with use of standard BQD breakers, add SIPODs only where control is needed J Reduced wiring complexity over traditional systems J Reduced labor and installation costs

Qualified PersonThis device/system may only be set up and used in conjunction with these instructions. Installation, maintenance and operation of this device/system may only be performed by qualified personnel. Within the context of these instructions, qualified persons are defined as persons who have the skills and knowledge related to the construction and operation of the electrical equipment and installations and have received safety training to recognize and avoid the hazards involved.

Panel Amp Ratings: Up to 250A

System Ratings:3 phase, 4-wire, 480Y/277V AC3 phase, 4-wire, 208Y/120V AC1 phase, 3-wire, 120/240V AC

Panel Size: 18, 30, 42 circuits

Mains: Breaker or Lug

Enclosures: NEMA 1, 3R, 3R/12, 4 & 4X

Dimensions:(NEMA 1)

20” wide x 5.75” deep (End walls with knockouts supplied at no charge, if requested at the time of order)

Mounting: Flush or Surface

Front:Hinged, piano hinged, door-in-door, screw to the box

Approvals:

UL 916 Energy Management EquipmentUL 67 PanelsUL 50 EnclosuresUL 489 BreakersCA Title 24

Operating Conditions:

Ambient temperature operating: 238F...1048F (-58C...408C)Ambient temperature non-operating: -138F...1588F (-258C...708C)

Specifications:

Page 6: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Meter Breaker CombinationsApproved for Keyspan

System ControllerSystem ControllerSystem Controller

System Controller

MLO/MainBreaker Space

Ground Bar

i-3 Controller

Data Rail(Cover removed for picture)

SIPOD

BQD Breaker

NeutralExtension

ConvenientFront PanelCommunicationPorts (throughdeadfront)

System ControllerI/O Controller

J 250A max. busJ No column mounted panelsJ No feed thru or sub feed lugsJ No split busJ No internal TVSS

(deadfront/door removed for picture)

6

i-3 System Overview

Page 7: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

7

Branch Circuit Breakers

Load Lug Terminal

BQD Line Connection

BQD breakers are required for all control points. BL breakers may be used for 240V applications involving non-controlled points.BQD breakers without a SIPOD can be usedfor 277V applications involving non-controlled points.

Interrupting Rate (RMS kA)

PolesVolts (AC)

120 240 277 480

1 65 - 14 -

2 - 65 - 14

Poles Amperage(@ 40 C)

CatalogNumber

1

15A BQD115

20A BQD120

30A BQD130

2

15A BQD215

20A BQD220

30A BQD230

Breaker Selection for controlled circuits

BQD 15A Breaker Side View

Note: For non-controlled circuits, the full range of BQD and BL breakers can be used.

Page 8: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

8

SIPOD™

The SIPOD is a remotely operated electro-mechanical contactor that is attached to a Siemens BQD molded case circuit breaker allowing loadsto be switched ON and OFF. The SIPOD has the following features:

J UL Listed 489 CB AccessoryJ Same kA rating as the BQD breakerJ Rated for 500,000 + operations at full load

The SIPOD connects to the load side of the breaker by inserting the conductor tab into the breaker load lug. The SIPOD load lug is the same size as the circuit breaker load lug, so load wire connections can easily be attached to the SIPOD load lug.

Manual Override To simplify testing during installation and commissioning, the SIPOD includes a manual override that forces the main contacts to close. Once the override lever is rotated to the closed position, the contacts remain closed until the SIPOD receives a remote signal from the controller. This feature allows electrical loads to be tested prior to configuring the lighting control system. The manual override of remote commands is temporary until the controller is commissioned and operational. The manual override is purely mechanical, so no electrical feedback is provided. The manual override is not designed to be used to open the SIPOD contacts. This may damage the mechanism.

Maglatch MechanismThe SIPODs switch ON/OFF via a maglatch mechanism, designed to hold and actuate between the ON and OFF state. This bi-stable operation is achieved with the use of a solenoid, a permanent magnet and a spring to ensure the SIPOD contacts remain in their current state if power is lost. When power is restored, normal operation resumes. Unlike motor driven mechanisms that are prone to high inrush currents, slippage, failureand loud noise due to the operation

of the DC motor, the maglatch mechanism requires less power (approximately 1.7A @ 24VDC for 2-25 milliseconds), is faster (breaks continu-ity in less than 4.5 milliseconds), has a

longer mechanical life (more than half a million operations at full load) and is quieter (the only noise is the sound of the contacts striking). SIPOD statistics can be retrieved using the System Controller or the Modbus map. Thisenables the user to determine when the SIPOD has reached 500,000 operations.

Components Description

1 Conductor tab The conductive element that connects the circuit breaker to the SIPOD

2 Mechanical Status Indicator Provides the open/close status of the SIPOD contacts

3* Manual Override Allows the user to close the SIPOD contacts if system is offline.

4 SIPOD Load Lug The terminal that connects SIPOD to the lighting loads

5 SIPOD Connector 4-pin connector that links SIPOD to the data rail

Components

1 Manual Override

2 Maglatch Mechanism

3 Blow-Closed Mechanism

4 Integrated Electronics

A

DC

B

A

B

C

D

E

* If the manual override is engaged while the controller is functioning, the controller will re-open the contacts. Signals from the controller take priority when functioning. This minimizes tampering when the system is functioning.

Page 9: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

SIPOD™

Blow-Closed MechanismThe blow-closed mechanism is designed to keep the SIPOD contacts closed during short circuit and overload conditions. This is achieved by using a compression spring, a steel yoke and armature that function as a magnet, and two parallel conductors. During normal operation, the spring provides the force required to maintain the contacts in either the open or closed position. During extremely high current levels, the parallel conductors produce a non-saturating force that is proportional to the square of the current and length over which the parallel conductors are acting. This force combines with the forces produced by the spring and magnet, to keep the contacts closed. For more information, please refer to the Blow-Closed Mechanism White Paper. Available on www.usa.siemens.com/i-3

Integrated ElectronicsThe SIPOD contains a printed circuit board (PCB) that controls the SIPOD contacts and communicates with the controller through a data rail connection. Commands from the controller can open or close the SIPOD contacts, request contact status, or other operational parameters. The PCB also has a microprocessor that minimizes the power supplied from the source and ensures proper operation of the solenoid.

Fast and Easy MaintenanceAn exclusive i-3 system feature is the ability to keep operating even if the SIPOD fails. Just remove the SIPOD and use the breaker like a normal uncon-trolled breaker. This keeps the lights on while waiting for a replacement SIPOD. If the BQD breaker fails you can quickly get a replacement from your local Siemens distributor.

Dangerous voltages are present in the equipment which may cause death, serious injury or property damage. Always disconnect and lock-off the equipment before maintenance. Maintenance should be performed only by qualified personnel.

Qualified PersonThis device/system may only be set up and used in conjunction with the instructions supplied with the equipment. Installation, maintenance and operation of this device/system may only be performed by qualified personnel. Within the context of these instructions, qualified persons are defined as persons who have the skills and knowledge related to the construction and operation of the electrical equipment and installations and have received safety training to recognize and avoid the hazards involved.

The modularity of the SIPOD/breaker combination reduces system down-time by allowing parts to be mixed and matched. This is not possible with a single unit remotely operated breaker.

How to minimize downtime if a SIPOD fails:J Remove the SIPOD from the panelJ Connect the load to the load side of the breakerJ The circuit is now restored and controlled by the manual breaker switch J Order a replacement SIPOD from your Siemens distributor

If a breaker fails:J Remove the breaker from the panelJ Obtain an off-the shelf replacement BQD breaker J BQD breakers are stock items with minimal lead time

Danger

9

Page 10: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

10

Emergency SIPOD™

Emergency Lighting Circuits ApplicationThe i-3 Technology System offers an option to control emergency lighting circuits. This option meets the require-ments of the National Electrical Code, 700.12(F).

For this application, i-3 utilizes a standard two-pole BQD breaker coupled with a standard one-pole SIPOD. The assembly is installed in a factory modified P1 Panel-board.

Note: This is not a field modification option. The i-3 system with this option must be ordered with this modification. An i-3 system with emergency lighting circuits can have 2, 4, 6, 8, 10 or 12 circuits factory modified for this application.

The functional circuit is shown below.

Page 11: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

11

Emergency SIPOD™

The graphic above depicts the 12 possible panel configurations.Spaces not configured for emergency lighting control may be used for controlled or non controlled circuits.

Page 12: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Controllers

The i-3 P1 Series Lighting Control Panel has four available controllers:J Front Panel Touch ScreenJ EIB (only to network with system controller on stand-alone system)J Modbus – for Modbus BASJ BACnet – for direct connection with Siemens APOGEEThe controllers enable users to implement time schedules, create zones, manage inputs, and display SIPOD and system status. The I/O

Board shown in Figure 1 provides the logic for the operation of the entire system.

Battery Backup (System Controller Only)In the event that power is lost, a factory installed battery will maintain the system clock and panelboard configurations for at least one year.The lithium coin cell battery is rated

EIB SelectAddress

CommunicationInterface Section

Three-way “All Pods” Switch

Ribbon CableConnectors

Input WiringSection

Power SupplyConnector

EIB ResetReset

BatteryBackup(up to1 year)

RS–485terminal

Figure 1. I/O Board

The I/O Board input terminals are designed for 3-pin connections where the common terminal can be shared by two 2-wire inputs. These input terminals accept dry contact inputs from external control devices. Input connectors (shown in Figure 2) areprovided for the 16 input terminal sets.

Figure 2. Input Connector

Modbus AddressingSwitches

12

Page 13: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

I/O Controller

The I/O Controller provides the intelligence required to switch the remote operated breakers ON and OFF.The I/O Controller also enables the P1 lighting panel to accept dry contact inputs and commands over communication networks.

Inputs and OutputsJ 32 Digital, 2-wire InputsJ 16 Digital, 3-wire InputsJ 2 Analog Inputs J 2 Analog Outputs*

Communication InterfaceJ Modbus RTUJ EIB – BACnet MSTP (for Siemens Building Technologies APOGEE applications only)

Features:J Configurable zones dependent on number of breakers per zoneJ Off Warning Blink

Communication Cables(Modbus and BACnet applications)An RS–232/RS–485 or USB/RS–485 converter kit is required to allow communi-cation between the i-3 I/O Controller and a personal computer. This kit can be owner furnished or ordered through the factory using the following part numbers:J RS–232–RS485 Kit: 5WG1 715-8XY01 J USB to RS–485 Kit: 5WG1 715-8XY02

In addition to the converter, the kit includes:J DB9 or USB CableJ Phoenix Connector

Note: Contact Technical Support for Instructions ([email protected])

*Analog functionality is not yet available. Please contact Siemens for information on availability.

13

Page 14: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

I/O Configuration Software (Modbus Only)

Initial Startup Screen

The i-3 Configurator Software is a Windows based application that enables the user to easily configure a P1 Series Lighting Control Panel with i-3 Control Technology. Please visit www.usa.siemens.com/i-3 to obtain a free copy of the software after your system is delivered/installed.

The i-3 Control Technology Panel Configurator allows the user to:J See an accurate graphical panel layout J Check the status of breakers, inputs, and zonesJ Configure zones and I/O mappingsJ Import/ Export system configurations System RequirementsJ Net Framework 2.0J Windows XP, 2003, or newer versions

Status Screen: The graphical panel representation on the left indicates which PODs are open (green) or closed (red). The table on the right provides the status of up to 32 digital inputs.

Operations Screen: Allows the user to override the current POD status, create zones, and set I/O mappings.14

Page 15: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

System Controller

This 24V low voltagesection is accessiblethrough the paneldeadfront.

The System Controller provides an intuitive touch screen panel application with set-up wizards to configure the system. Off-line configuration software is also available from the factory. Please visit www.usa.siemens.com/i-3 to download a free copy.

The System Controller also includes the Modbus TCP/IP communication protocol.

Features:J Touch Screen PanelJ 6 Setup Wizards (Panels, Breakers, Inputs, Zones, I/O Mapping, and Schedules)J Password ProtectionJ User Access LevelsJ Event LogsJ Flexible Automatic Daylight Saving Time and Leap Year compensationJ USB interface (details on page 16)J 20 independent schedules (10 events per schedule)J Unlimited holiday overridesJ Modbus TCP/IP

System Controller Screenshots

Setup Wizards SchedulesPassword Protection

Tools and Overrides Zones I/O Mapping 15

Page 16: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

USB Interface

The USB interface enables users to upload or download panel configuration files and software updates. This feature simplifies the installation, commissioning, and support of i-3 equipped panelboards. Upgrades will no longer require lighting control “experts”. On occassions when technical assistance is needed, the user simply e-mails the configuration files to technical support. After the issue is remotely diagnosed, the updated file is e-mailed back to the user and uploaded. This reduces downtime and costs.

System Controller Screenshots

USB import file feature

For technical support call:1-877-757-5002

Users can now sendconfiguration files totechnical supportfor remote diagnosisand solutions

16

Page 17: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Communication and Networking Configurations

RS-485

I/O Controllers

Modbus RS–232 toRS–485orUSB to RS–485

The i-3 System Controller and I/O Controller are capable of communicating via EIB, Modbus RS–485, or dry contacts (Bacnet applications only), the i-3 System Controller communicates via Modbus TCP/IP. This enables communication with other building systems over the building LAN. Each panel in the system acts as a stand-alone unit

or a “slave” to a building automation system. One system controller in a panel can network up to 7 additional panels (for a total of 8 panels). The I/O Controller can also be networked with Modbus RS–485 or on a LAN. To network panels, 18–gauge twisted pair wires are used to communicate through EIB. The total maximum cable length allowed for networking panels

is 3,300 ft (1,000 meters).Note: Future versions of the system controller will be Internet capable for remote access and configuration.Contact Siemens sales for more information.

...Up to 7 additional panels can be networked from a single system controller

EIB

SystemController

I/O Controllers

1st Floor...up to 7 I/O Controllers

2nd Floor...up to 7 I/O Controllers

SystemController 1

SystemController 2

ModbusLAN/RS485

Note: System controllers cannot communicate with each other even if they are on the same LAN.

*Depending on maximum distance and network bandwidth.Note: Up to a maximum of 32 devices may be connected in one loop.

...Up to 247 I/0 Controller Modbus Slaves*

...central building automation system can control several local system controllers. (i.e. Highrise application)

Modbus RTU orModbus TCP/IP or BACnet MSTP

I/O Controllers

SystemController

...System Controller can be connected on a LAN

EIB

Note: BACnet is designed for Siemens Building automationAPOGEE applications only.

17

Page 18: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Dimensions

Type 1 Box

Type 3R and 3R/12 Box

AmpRating

EndGutter

NeutralLocation

125 10.500 11.500

250 10.500 11.500

Main Lug End Gutter Dimensions

BranchBreakers

WiringSpace

BQD + SIPOD Combo 3.25

BQD 5.5

BL 6.375

Branch Breaker Side Gutter Wiring Space (inches) Main

BreakerSideGutter

NeutralLocation

BL, BLH, HBL, BQD 8.500 11.500

ED4, ED6, HED4 6.125 11.500

QJ2,QJH2, QJ2-H 6.500 11.500

FD6, FXD6, HFD6 5.250 11.500

Main Breaker Gutter Dimensions (inches)

18

Page 19: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Ordering Information

The i-3 is derived from a standard Siemens P1 panel. Please refer to the P1 Panelboard Selection and Application Guide to select the interior, enclosure modifications, and front options. They can be found at: http://www.usa.siemens.com/panelboards

Keep the following parameters in mind when ordering a P1 Series Panel with i-3 Control Technology: J 250A Maximum BusJ No column mounted panelsJ No feed through or sub feed lugsJ No Fast-Latch TrimJ No Split BusJ No 200 % NeutralJ No Internal TVSS**

Summary of Ordering Steps:1. Select Interior and Main Device 2. Select Branch Breakers and SIPODs3. Select the Controller4. Select Enclosure Modifications and Front Options (from P1 S&A Guide)5. Contact your local Siemens Sales Representative for pricing and order entry.

**Can be mounted externally using a branch mounted circuit breaker.

How to Order1. Select Interior and MainSelect the interior by bus type, panel rating, and the number of branch circuits.

Main Lugs Only*

MaxPanelAmps

Max1-Pole

Circuits

BoxHeight

(inches)

Catalog Numbers

120/240V1-ph, 3-wire

208Y/120V3-ph, 4-wire

480Y/277V3-ph, 4-wire

125

18 32 P1A18ML125ATS P1C18ML125ATS P1E18ML125ATS

30 38 P1A30ML125ATS P1C30ML125ATS P1E30ML125ATS

42 44 P1A42ML125ATS P1C42ML125ATS P1E42ML125ATS

250

18 32 P1A18ML250ATS P1C18ML250ATS P1E18ML250ATS

30 38 P1A30ML250ATS P1C30ML250ATS P1E30ML250ATS

42 44 P1A42ML250ATS P1C42ML250ATS P1E42ML250ATS

* Catalog Numbers are for aluminum main bus. For optional copper main bus change “A” in position 11 to “C”. For example, a 125A panel with 120/240V 1-phase, 4-wire would have the following catalog number: P1A18ML125CTS. Specify bottom feed by changing the character in position 12 from “T” (top) to “B”. Specify flush mount by changing the character in position 13 from “S” (surface) to “F”.

Main Circuit Breaker*

MaxPanelAmps

Max1-Pole

Circuits

BoxHeight

(inches)

Catalog Numbers

120/240V1-ph, 3-wire

208Y/120V3-ph, 4-wire

480Y/277V3-ph, 4-wire

100

18 32 P1A18BL100ATS P1C18BL100ATS P1E18BL100ATS

30 38 P1A30BL100ATS P1C30BL100ATS P1E30BL100ATS

42 44 P1A42BL100ATS P1C42BL100ATS P1E42BL100ATS

125

18 32 P1A18E4125ATS P1C18E4125ATS P1E18E4125ATS

30 38 P1A30E4125ATS P1C30E4125ATS P1E30E4125ATS

42 44 P1A42E4125ATS P1C42E4125ATS P1E42E4125ATS

225

18 32 P1A18QJ225ATS P1C18QJ225ATS P1E18QJ225ATS

30 38 P1A30QJ225ATS P1C30QJ225ATS P1E30QJ225ATS

42 44 P1A42QJ225ATS P1C42QJ225ATS P1E42QJ225ATS

250

18 32 P1A18FX250ATS P1C18FX250ATS P1E18FX250ATS

30 38 P1A30FX250ATS P1C30FX250ATS P1E30FX250ATS

42 44 P1A42FX250ATS P1C42FX250ATS P1E42FX250ATS

2. Select Branch Breakers and SIPODs. BQD breakers are required for all control points.

BranchBreakers

BreakerType

PolesAvailable

Amp Rating

Max Interrupting Rate (kA)

120/240V 240V 277V

Controllable BQD 1,2 15, 20 65 - 14

Non-Controllable

BL, BQD 1, 2, 3

15, 20, 25, 30,35,40, 45, 50, 60

10 - -

70 10 - -

80, 90, 100

10 - -

19

Page 20: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Ordering Information

* Use the Catalog Number provided in the table to specify circuit breakers.NOTE: Contact sales for availabiliy of the 30A rating.

3. Select Controller

Description Catalog number

I/O Controller 5WG1 718-8XY01

I/O Controller (Modbus) 5WG1 718-8X12

I/O Controller (BACnet) 5WG1 718-8X13

System Controller 5WG1 718-8XY11

RS485/R232 Converter* 5WG1 715-8XY01

RS485/USB Converter* 5WG1 715-8XY02

*Communication cable factory available or owner constructed.

4. Enclosure Modifications and Front OptionsThere are several enclosure modifications and front options for the P1 Series Panel with i-3 Control Technology. Please review the P1 Selection and Application Guide for details. Ordering Example:3-phase, 4-wire 480Y/277V AC250 Amp Main circuit breaker 42 Branch CircuitsBottom FeedSurface MountedHinged Trim30 – 20 Amp one-pole Controllable Breaker SIPOD Combos3 – 20 Amp two-pole Controllable Breaker SIPOD Combos6 – 30 Amp one-pole Non-ControllableBreakersSystem Controller

5. Contact your local Siemens Sales Representative for order entry. For your nearest sales office call us at 1.800.964.4114.

SIPODS*

Amp Rating Poles Catalog Number

20 1 BQD20CPOD1

20 2 BQD20CPOD2

30 1 BQD30CPOD1

30 2 BQD30CPOD2

Emergency Lighting Circuit Control (panel modification)

Description Catalog number

Emergency Lights control 18 ckts panel mod (1 set of 2 E ckts) I3ESIPODMOD1801

Emergency Lights control 18 ckts panel mod (2 sets of 2 E ckts) I3ESIPODMOD1802

Emergency Lights control 30 ckts panel mod (1 set of 2 E ckts) I3ESIPODMOD3001

Emergency Lights control 30 ckts panel mod (2 sets of 2 E ckts) I3ESIPODMOD3002

Emergency Lights control 30 ckts panel mod (3 sets of 2 E ckts) I3ESIPODMOD3003

Emergency Lights control 30 ckts panel mod (4 sets of 2 E ckts) I3ESIPODMOD3004

Emergency Lights control 42 ckts panel mod (1 set of 2 E ckts) I3ESIPODMOD4201

Emergency Lights control 42 ckts panel mod (2 sets of 2 E ckts) I3ESIPODMOD4202

Emergency Lights control 42 ckts panel mod (3 sets of 2 E ckts) I3ESIPODMOD4203

Emergency Lights control 42 ckts panel mod (4 sets of 2 E ckts) I3ESIPODMOD4204

Emergency Lights control 42 ckts panel mod (5 sets of 2 E ckts) I3ESIPODMOD4205

Emergency Lights control 42 ckts panel mod (6 sets of 2 E ckts) I3ESIPODMOD4206

Notes: 1- Emergency Lighting Circuit Control is sold in even numbers only.2- Configurations are available as described on pages 10 and 11.

Panel

Step 1 (from P1 Guide)

Step 2 Step 3Step 4

(from P1 Guide)

Interior and Main Device

Breakers and SIPODS:

Qty: Controller:

Enclosure Modifications

and Front Options

1 P1E42FX250ABS BQD20CPOD1BQD20CPOD2BQD120BQD220BQD130

3033036

5WG1 718-8XY11 HingedTrim

20

Page 21: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Ordering Information

Panel

Step 1 (from P1 Guide)

Step 2 Step 3 Step 4

Interior and Main Device:

Breakers and SIPODS:

Qty.: Controller:Enclosure Modifications

and Front Options

1

2

3

4

5

6

7

8

Panel Configuration Form

21

Page 22: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Integrated Power System Switchboards

Your Single Source For Simpler, Smaller and Faster Installations

By selecting the P1 Series Lighting Control Panel with i-3 Control Technology for your next Integrated Power System, you gain the ability to stack up to two panels with 42 branch controlled circuits each in one section!

The modular design of the Siemens Integrated Power System (IPS)switchboard allows the user to integrate electrical distribution equipment, power monitoring and environmental controls, that typically mount in multiple enclosures, into one switchboard line-up. Users have the freedom to configure asystem that best fits theirindividual needs.

How IPS can help reduce the cost of your next project: IPS reduces the number of components required which decreases the amount of time you spend on the job site. It also simplifies field setup and programming. Finally, the small footprint reduces space requirements so you have more room for revenue-generating resources.

Integrated Power System switchboards are built to UL 891 and NEMA PB-2 standards. The standard height of each Integrated Power System sections is 90 inches (Optional 70 inch height available). The minimum depth of the IPS is 13.75 inches. Optional depths of 20, 28, and 38 inches are available.

For more information on IPS and what it can do for you, please contact your nearest Siemens Sales Office at 1.800.964.4114.

22

Page 23: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

A

Page 24: i-3 Lighting Controls - Siemensw3.usa.siemens.com/us/internet-dms/btlv/PowerDistributionComm... · 5 P1 Series Lighting Panel integration J Small footprint — can stack up to two

Siemens Industry, Inc.Building Technologies Division 5400 Triangle ParkwayNorcross, GA 30092

1-877-757-5002 [email protected]

©2010 Siemens Industry, Inc.Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice.All rights reserved.

PBSA-i3TEC-0310 Printed in USA

www.usa.siemens.com/i-3