72 HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution of the traditional hydronic system. The cooling or thermal energy required for climate control is produced on a centralised level, then distributed – using chilled or hot water as a vector – in the serviced rooms via specific air treatment units and hydronic terminals, in partnership with the air renewal and purification units. HYDRONIC System

HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

72

HYDRONIC SystemThe complete range of chillers, heat pumps and air handling units in large installations

HYDRONIC System is the innovative evolution of the traditional hydronic system.

The cooling or thermal energy required for climate control is produced on a centralised level, then distributed – using chilled or hot water as a vector – in the serviced rooms via specific air treatment units and hydronic terminals, in partnership with the air renewal and purification units.

HYDRONIC System

Guida_2011_v26.indd 72Guida_2011_v26.indd 72 15/03/11 18:1215/03/11 18:12

Page 2: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

73

WSAT-XEE / WSAN-XEE 82 302 ELFOEnergy Medium 74

WSAT-XEE / WSAN-XEE 352 802 ELFOEnergy Large2 76

WSAT / WSAN 82 242 - 78

WSAT-XSC2 / WSAN-XSC2 80D 240F SPINchiller2 New 80

WSAT-XSC 270J 360L SPINchiller 82

WDATA 2.160 2.600 SCREWLine 84

WDATB 2.160 2.600 SCREWLine 86

WDAT-HT 2.180 2.600 SCREWLine 88

WSA-EE / WSN-EE 17 91 ELFOEnergy Small 90

WSA-XEE / WSN-XEE 122 402 ELFOEnergy Duct Medium New 92

WRA / WRN 404 604 - 94

WSA-SC 65D 100D SPINchiller 96

WSHF-XSC 65D 180F SPINsaver 98

WRH / WRHN 102 422 - 100

WSH-XSC 65D 180F SPINchiller 102

WDH-HE 2.220 2.600 SCREWLine New 104

WDH 2.160 2.600 SCREWLine 106

REM 75C 2.440 - 108

ME 17 422 - 110

CE 25 602 - 112

MSE-SC 65D 180F SPINchiller 114

MDE 2.160 2.600 SCREWLine 116

CEM 75C 2.440 - 118

GPA M0 M9 - 120

GP1 / GP2 00 12 - 122

GP7 60 63 - 124

GPM 60 99 - 126

ELFOSpace OUT-V / OUT-H 3 31 ELFOSpace 128

ELFOSpace IN-V / IN-H 3 31 ELFOSpace 130

ELFOSpace BOX2 7 41 ELFOSpace 132

ELFOSpace WALL 3 17 ELFOSpace 134

ELFODuct CFD 7 41 ELFODuct 136

ELFODuct CFI 25 71 ELFODuct 138

ELFODuct CF 25 242 ELFODuct 140

ELFODuct CF-V 31 242 ELFODuct 142

AQ 14 803 - 144

P-Matic for Hydronic - - - 146

series to name page

System components

size from

Water chillers and Heat pumps - air source - axial fans

Water chillers and Heat pumps - air source - centrifugal fans

Water chillers and Heat pumps - water source

Condenserless water chillers - air source

Pumping units

Water terminal units

Air handling units

Remote management systems

Guida_2011_v26.indd 73Guida_2011_v26.indd 73 22/03/11 14:3822/03/11 14:38

Page 3: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

7474

WSAT-XEE WSAN-XEE 82÷302

ELFOENERGY MEDIUM

WSAT-XEE 82S(1)

400TN(2)

1PUS(3)

-(4)

74

AIR

4

4

R-410A

OHP (5)

-(6)

-(7)

-(8)

-(9)

-(10)

FC

-(11)

-(12)

Eurovent EnergyEfficiency Class

HY

DRO

NIC

functions and features

available configurations

Water chillerWSAT-XEE: cooling onlyWSAN-XEE: reversible heat pump

Air cooledOutdoor installationCapacity from 24,3 to 72,2 kW

Liquid chillers and heat pumps of the ELFOEnergy WSAT-XEE and WSAN-XEE series are units designed for outdoor installation and best energy efficiency in relation to their reduced size.The ELFOEnergy series has been the turning point in the evolution of chillers.Every unit has been conceived and made by applying state-of-the-art technology, emphasising the qualities of EFFICIENCY, SELF-ADAPTATION and EASY INSTALLATION that distinguish this productThanks to its constructional and electronic peculiarities, ELFOEnergy permits:

4high energy efficiency, in particular during partial-load operation, thanks to the use of two compressors with different capacities that work on a single refrigerant circuit;

4Eurovent energy efficiency classification class "A" in heating operation, also in full load condition;

4adaptability of operating parameters to the load conditions of the connected system, thereby optimising consumption, efficiency and working life of the parts;

4easy, quick installation thanks to the standard hydronic group and the factory test carried out prior to dispatch;

4installation of hydronic group with non-standard working head pumps or with double pump.

Cooling only(WSAT-XEE)

Heating-Cooling(WSAN-XEE)

Air cooled Outdoor inst. Refrig. R-410A Herm. Scroll ELFOControl Ice protectionsystem (WSAN-XEE only)

(1) LOW TEMPERATURE:4S Standard4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -8°C inclusive.

4DSPB Double set-point for water low temperature (Brine)(2) SUPPLY VOLTAGE:

4400TN 400/3/50+N(3) HYDRONIC GROUP USER SIDE:

41PUS Standard pump 41PUR Single pump with reduced discharge head 41PUM Single pump with larger discharge head

42PUS Standard double pump 42PUR Double pump with reduced discharge head 42PUM Double pump with larger discharge head

4- Not required(4) ENERGY RECOVERY:

4- Not required (Standard)4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 25% of the total unit heat.

(5) OPERATION (WSAN-XEE only):4OHP Operation in heat pump

Cooling and heating unit (Standard)4OHO Operation in heating-only

Heating only unit

(6) CONDENSER COIL:4CCS Standard condenser coil4CCCA Condenser coil in copper/aluminium with acrylic coating4CCCA1 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment4CCCC Condenser coil in copper/copper

(7) SOFT STARTER:4- Not required (Standard)4SFSTR4N Device for inrush current reduction, for 400/3/50+N units

(8) FREE CONTACTS HEATING EXTERNAL SIGNAL:4- Not required (Standard)

4CLSE Free Contacts External Signal(9) SHUNT CAPACITORS (POWER FACTOR > 0,9):

4- Not required (Standard) 4PFCP Shunt capacitors (power factor > 0,9)(10) STORAGE TANK:

4- Not required (Standard) 4ACC1 Teflon steel storage tank(11) FREE-COOLING (WSAT-XEE only):

4- Not required (Standard) 4FCD Direct free-cooling

For technological air conditioning, and when the air temperature permits, the free-cooling option makes it possible to recover cold energy from the outdoor environment

(12) REDUCED OUT. SECT. FAN CONSUMPTION (WSAT-XEE only):4- Not required (Standard)

4CREFB Device for the reduction of ECOBREEZE type outdoor section fan consumption

Free-Cooling(WSAT-XEE only)

Guida_2011_v26.indd 74Guida_2011_v26.indd 74 22/03/11 14:3822/03/11 14:38

Page 4: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

757575

82 102 122 162 182 222 262 302

4 kW 24.3 28.2 33.7 40.0 45.9 54.4 64,1 72.2kW 8,90 10,4 12,5 14,2 16,7 20,1 23,4 26,6- 2,73 2,72 2,71 2,81 2,74 2,71 2,74 2,71- 4,32 4,48 4,18 4,20 4,34 4,47 4,19 4,06kPa 132 126 120 104 88 148 139 131

4 kW 23,6 27,5 32,7 39,4 45,6 52,9 63,0 71,9kW 9,36 10,9 13,0 15,3 17,8 21,0 25,0 28,4- 2,52 2,53 2,51 2,57 2,56 2,51 2,52 2,53- 4,07 4,11 3,85 3,82 4,00 4,11 3,90 3,86

4 kW 28,8 32,9 37,5 45,6 53,0 61,9 72,4 83,7kW 9,00 10,3 11,7 14,1 16,5 19,0 22,2 25,6- 3,20 3,18 3,21 3,23 3,21 3,26 3,27 3,27kPa 136 129 125 107 89 150 141 131

4 kW 31.5 36.7 43,8 52,6 60,2 72,3 83,1 97,2kW 9.95 11.9 14,4 16,8 18,9 22,7 26,6 30,5- 3,16 3,09 3,05 3,13 3,18 3,18 3,13 3,19

4 kW 29,2 33,6 38,0 46,9 54,1 63,3 74,0 85,4kW 7,07 8,00 9,10 11,2 13,3 15,6 18,2 21,1- 4,13 4,21 4,15 4,19 4,07 4,05 4,07 4,05kPa 91,8 80,4 72,7 42,9 17,2 111,2 102,3 82,9- 1- 2 SCROLLdB(A) 60 60 60 61 62 62 64 64V/Ph/Hz 400/3/50+N

82 102 122 162 182 222 262 3021703 1703 1703 1932 1932 1932 2332 2332675 675 675 1100 1100 1100 1100 1100

1209 1209 1209 1417 1417 1417 1417 14174 700 700 700 700 700 700 700 700

700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700

298 303 323 456 469 490 547 561

315 320 370 530 550 580 675 690

BB2

B1A

A2

C

A1

HY

DRO

NIC

technical data

(1) Internal exchanger water = 12/7°C; air entering external exchanger = 35°C(2) Total input is obtained from the compressor input + fan input + auxiliary circuit input.(3) Ambient temperature = 7°C (R.H. = 85%); internal exchanger water outlet temperature 45°C

(4) Internal exchanger water = 23/18°C; air entering external exchanger = 35°C(5) Fresh air temperature = 7°C D.B./ 6°C W.B.; internal exchanger water temperature 30/35°C(6) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

Data referred to the following conditions:

accessories

■ Accessories supplied separately.

■ 4 Rubber antivibration mounts ■ 4 Serial communication module with supervisor (MODBUS) ■ 4 Steel mesh filter on water side (when unit is in “without hydronic

group” configuration)■ 4 High and low pressure gauges ■ 4 Daily and weekly programming clock ■ 4 Finned coil protection grilles■ 4 Phase monitor to check the presence and correct sequence of the

power supply phases

■ 4 Control keypad for remote installation that repeats all the functions already present on the onboard microprocessor control

■ 4 Humidity probe for summer set point compensation according to the outside enthalpy and defrosting optimization in winter operation

WSAT-XEE only:■ 4 Setpoint compensation on the basis of outdoor enthalpy WSAN-XEE only:■ 4 Setpoint compensation with outdoor air probe

Key to symbols:

dimensions and clearances

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

WSAT-XEEWeight in oper. kgWSAN-XEEWeight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

leave free

SizesApplication with terminal unitsWSAT-XEE

Cooling capacity (1)Total input (1)(2)EER EUROVENT (1)ESEER

Pump working head (1)WSAN-XEE

Cooling capacity (1)Total input (1)(2)EER EUROVENT (1)ESEERHeating capacity (3)Total input (2)(3)COP EUROVENT (3)

Pump working head (1)Application with radiant panelsWSAN-XEE

Cooling capacity (4)Total input (2)(4)EER EUROVENT (4)Heating capacity (5)Total input (2)(5)COP EUROVENT (5)

Pump working head (4)Number of refrigerant circuitsNumber and type of compressorsSound pressure level (6)Power supply

Guida_2011_v26.indd 75Guida_2011_v26.indd 75 22/03/11 14:3822/03/11 14:38

Page 5: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

767676

WSAT-XEE WSAN-XEE 352÷802

ELFOENERGY LARGE²4

4

HYDROPACK

ECOBREEZEFCR-410AAIR

WSAT-XEE EXC - -(3)

-(4)

352 SC(5)

T(6)(2)(1)

EEV

CE(7)

WSAT-XEE(cooling)

WSAN-XEE(heating)

HY

DRO

NIC

functions and features

available configurations

Water chillerWSAT-XEE: cooling onlyWSAN-XEE: reversible heat pump

Air cooledOutdoor installationCapacity from 83,1 to 218 kW

Heating-Cooling Air cooled Outdoor inst. Refrig. R-410A Ice protectionsystem

Free-Cooling(WSAT-XEE only)

ECOBreeze HydroPack

(1) VERSION:4EXC EXCELLENCE (Standard)4PRM PREMIUM

(2) ENERGY RECOVERY:4- Not required (Standard)4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 25% of the total unit heat.In addition, exchangers are complete with antifreeze heater to protect against the risk of ice.

4R Total recoveryCarried out using braze-welded plate-type exchangers suited for 100% recovery of condensation heat for producing hot water. In addition, exchangers are complete with safety differential pressure switch on the water side, antifreeze heater to protect against the risk of ice.

(3) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.Two versions are available:

- Unit for low temperatures only- Unit with double operating set-point

(4) FREE-COOLING (WSAT-XEE only):4- Not required (Standard)4FCD Direct Free-Cooling

Version that allows cold to be recovered at no cost from the ambient when the external air temperature is lower than the system return water temperature.To avoid problems with the unit, the water system must be protected by a mixture of water and glycol based on the minimum temperatures which may occur at the place of installation.

(5) ACOUSTIC CONFIGURATION:4SC Compressor soundproofing

This set-up is obtained by inserting the compressors in a soundproofed compartment.

4EN Super SilencedThis configuration is reached by inserting the compressor in an soundproofed enclosure and reducing the fan speed.

(6) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(7) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Electronic Expansion Valve

Herm. Scroll

The Eurovent A Class ELFOEnergy Large² water chillers and heat pumps provide the highest seasonal efficiency. They're designed to be installed outdoor and feature uneven scroll compressors mounted in the same circuit, electronic expansion valves and high efficiency plate type evaporators.

ELFOEnergy Large² shows an unmatched seasonal efficiency ESEER and is available in two versions: EXCELLENCE and PREMIUM. The standard version EXCELLENCE offers the highest efficiency both at full and at part load. Also the PREMIUM version offers high efficiency at part load but favour also the compact dimensions being therefore extremely competitive.

Thanks to its features, ELFOEnergy Large² offers:

4self-adaptability in different load conditions, thanks to the availability of several capacity steps and the adjustment logic developed for maximum efficiency and minimum wear

4very high overall reliability, thanks to the consolidated construction choices and the use of industrially-made products

4lower sound emissions, achieved thanks to the optimal sizing of the exchange surfaces and the use of high efficiency fans with “winglets”

4quick and easy installation thanks to the quick connections with the main circuit, electrical wiring enablement and complete functional testing before delivery. The units can also be supplied with pump assemblies, partial heat recovery and inertial storage tank already installed on board, bringing together all the system's main components in a single solution.

Eurovent EnergyEfficiency Class

(Config. SC EXC)

Eurovent EnergyEfficiency Class

(552÷802)

Guida_2011_v26.indd 76Guida_2011_v26.indd 76 22/03/11 14:3922/03/11 14:39

Page 6: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

777777

BB2

B1 A

A2

C

A1

352 402 432 452 502 552 602 702 802

3075 3075 3075 4025 4025 4025 4025 5025 50251097 1097 1097 1097 1097 1097 1097 1097 10971805 1805 1805 1805 1805 1805 1805 1805 1805896 933 1024 1207 1234 1256 1302 1497 15442710 2710 2710 2710 2710 2710 3075 4025 40251097 1097 1097 1097 1097 1097 1097 1097 10971805 1805 1805 1805 1805 1805 1805 1805 1805778 802 892 924 963 984 1087 1295 1324

3075 3075 3075 3075 3075 4025 4025 5025 50251097 1097 1097 1097 1097 1097 1097 1097 10971805 1805 1805 1805 1805 1805 1805 1805 1805915 975 1059 1101 1126 1326 1341 1549 1566

4 1000 1000 1000 1000 1000 1000 1000 1000 1000700 700 700 700 700 700 700 700 7001350 1350 1350 1350 1350 1350 1350 1350 13501350 1350 1350 1350 1350 1350 1350 1350 1350

352 402 432 452 502 552 602 702 802

4 kW 97,4 110 121 131 143 155 174 197 218kW 31,2 35,3 39,0 41,7 45,8 49,5 56,1 63,2 70,3- 3,12 3,12 3,10 3,14 3,12 3,13 3,10 3,12 3,10- 4,42 4,48 4,40 4,39 4,44 4,44 4,36 4,50 4,29dB(A) 67 67 68 68 68 69 69 70 70

4 91,5 102 113 122 131 143 162 183 204kW 32,6 37,5 41,7 43,9 47,5 52,6 60,1 66,4 75,5kW 2,81 2,72 2,71 2,78 2,76 2,72 2,70 2,76 2,70- 4,07 4,11 4,06 4,22 4,21 4,18 4,09 4,18 3,98

67 67 67 67 68 68 68 69 69

4 kW 83,1 94,9 105 111 121 137 154 179 198kW 32,9 36,6 41,2 43,8 48,3 52,1 61,5 68,0 77,3- 2,53 2,59 2,55 2,53 2,51 2,63 2,50 2,63 2,56- 3,59 3,71 3,69 3,69 3,71 3,65 3,56 3,51 3,47

4 kW 99,5 112 124 132 142 167 186 215 237kW 33,0 37,0 40,8 43,3 46,2 52,0 58,1 66,7 73,7- 3,02 3,03 3,04 3,05 3,07 3,21 3,20 3,22 3,22

4 dB(A) 115 133 143 150 165 186 205 239 266kW 37,7 41,0 46,9 48,5 54,6 55,6 66,2 71,6 82,6- 3,05 3,24 3,05 3,09 3,02 3,35 3,10 3,34 3,22

4 kW 107 121 135 139 151 173 189 221 245kW 28,1 31,6 35,0 36,2 39,3 44,5 49,7 57,7 64,0- 3,81 3,83 3,86 3,84 3,84 3,89 3,80 3,83 3,83dB(A) 67 67 67 67 67 68 68 71 71- 1- 2 SCROLLV/Ph/Hz 400/3/50

HY

DRO

NIC

accessories

technical data

■ Accessories supplied separately.

Sizes WSAT-XEEEXC Length (A) mmEXC Width (B) mmEXC Height (C) mmEXC Weight in oper. kgPRM Length (A) mmPRM Width (B) mmPRM Height (C) mmPRM Weight in oper. kgWSAN-XEE

Length (A) mmWidth (B) mmHeight (C) mmWeight in oper. kg

(A1) mm(A2) mm(B1) mm(B2) mm

The above data refer to standard units.CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water 12/7°C; ambient temperature 35°C(2) Internal exchanger water 40/45°C; air at external exchanger inlet 6,1°C W.B.(3) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.(4) Internal exchanger water 23/18°C; ambient temperature 35°C(5) Internal exchanger water 30/35°C; air at external exchanger inlet 6,1°C W.B.

leave free

Key to symbols:

Data referred to the following conditions:

dimensions and clearances

4 Free contacts for compressor status4 Free contact compressor state and local/remote management4 Switchboard ventilation4 Condenser coil in copper/aluminium with acrylic coating4 Copper/aluminium condensing coil with Energy Guard DCC

Aluminium shell4 Copper/copper condenser coil

■ 4 Spring antivibration mounts 4 Finned coil protection grilles4 Hail grilles4 Shut-off valve on compressor supply and return4 High and low pressure gauges4 Hydronic assembly with 1 x pump4 Hydronic assembly with 1 x pump + 1 x pump in stand-by4 Hydropack with 2 pumps

4 Storage tank 4 Storage tank with onboard primary circuit

■ 4 Steel mesh filter on water side 4 Set point compensation with 0-10 V signal4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Device for reducing consumption of the outdoor section fans of the ECOBreeze4 Phase monitor4 Multifunction phase monitor4 Soft Start4 Shunt capacitors (power factor > 0,9)4 MODBUS serial connection module4 BACNet serial connection module4 LonWorks serial connection module

■ 4 Unit microprocessor remote control interface kit

SizsWSAT-XEE

SC EXC Cooling capacity (1)SC EXC Total inputSC EXC Total EER at 100%SC EXC ESEERSC EXC Sound pressure level (3)SC PRM Cooling capacity (1)SC PRM Total inputSC PRM EER EUROVENTSC PRM ESEERSC PRM Sound pressure level (3)

WSAN-XEESC Cooling capacity (1)SC Total inputSC Total EER at 100%SC ESEERSC Heating capacity (2)SC Total inputSC COPSC Cooling capacity (4)SC Total inputSC Total EER at 100% SC Heating capacity (5)SC Total inputSC COPSC Sound pressure level (3)

Number of refrigerant circuitsNumber and type of compressorsPower supply

Guida_2011_v26.indd 77Guida_2011_v26.indd 77 22/03/11 14:3922/03/11 14:39

Page 7: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

7878

WSAT WSAN 82÷242

4

4

R-407CAIR

WSAT B82(1)

CE(2)

T(3)

HY

DRO

NIC

functions and features

available configurations

Water chillerWSAT: cooling onlyWSAN: reversible heat pump

Air cooledOutdoor installationCapacity from 20,7 to 62,9 kW

Cooling only(WSAT)

Heating-Cooling(WSAN)

Air cooled Outdoor inst. Refrig. R-407C Herm. Scroll Ice protectionsystem (WSAN only)

(1) VERSION:4S Standard4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -8°C inclusive.

(2) EXCHANGER APPROVALS:4CE PED (European test).

(3) ENERGY EFFICIENCY:4T Temperate climate

Liquid chillers and heat pumps of the WSAT and WSAN series are units designed for outdoor installation and best energy efficiency in relation to their reduced size.The availability of the double refrigerant and water circuitrecommends use of this series for process applications.

Guida_2011_v26.indd 78Guida_2011_v26.indd 78 22/03/11 14:3922/03/11 14:39

Page 8: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

7979

BB2

B1

A

A2

C

A1

82 102 122 142 162 182 202 222 2424 kW 20,7 25,7 28,1 33,8 37,5 43,4 52,7 56,9 62,9

kW 7,47 8,48 10,2 12,2 13,3 17,4 18,7 22,1 24,1- 2,77 3,03 2,75 2,77 2,82 2,50 2,82 2,57 2,61- 3,49 3,82 3,48 3,49 3,55 3,15 3,55 3,24 3,29

4 kW - - - 38,3 41,7 50,7 59,7 65,5 71,3kW - - - 12,1 13,9 17,6 20,0 22,2 24,3- - - - 3,16 3,00 2,88 2,98 2,95 2,94- 2- 2 SCROLLdB(A) 60 59 59 60 60 60 61 61 62V/Ph/Hz 400/3/50+N

82 102 122 142 162 182 202 222 2421435 1530 1530 1563 1563 1563 2098 2098 2098678 678 678 1107 1107 1107 1107 1107 11071000 1530 1530 1570 1570 1570 1570 1570 1570

4 800 800 800 900 900 900 900 900 900800 800 800 900 900 900 900 900 900800 800 800 900 900 900 900 900 900800 800 800 900 900 900 900 900 900220 275 280 380 480 485 580 585 590

HY

DRO

NIC

dimensions and functional spaces

accessories

technical data

■ Accessories supplied separately.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; ambient temperature = 35°C(2) Total input is obtained from compressor input + fan input.(3) Ambient temperature = 7°C (R.H. = 85%); internal exchanger water outlet temperature 45°C

4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

Series WSAT and WSAN derive from the corresponding series ELFOEnergy Medium

■ 4 Rubber antivibration mounts■ 4 High and low pressure gauges■ 4 Steel mesh filter on water side■ 4 Manifold for single water circuit ■ 4 Remote control with remote microprocessor control ■ 4 Serial communication module PC/BMS MODBUS for 1 unit

(Master)■ 4 Serial communication module PC/BMS MODBUS from 2 to 254

units (Slave)■ 4 Daily and weekly programming clock ■ 4 Phase monitor ■ 4 Coil protection grilles on external air side

WSAT only:■ 4 Device for operation at low outside temperatures with variable fan

speed

Key to symbols:

Data referred to the following conditions:

dimensions and clearances

SizesCooling capacity WSAT (1)Total input WSAT (1)(2)Total EER at 100% WSAT (1)ESEER WSATHeating capacity (3)Total input (2)(3)COP

Number of refrigerant circuitsNumber and type of compressorsSound pressure level (4)Power supply

Guida_2011_v26.indd 79Guida_2011_v26.indd 79 22/03/11 14:3922/03/11 14:39

Page 9: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

80

WSAT-XSC2 WSAN-XSC2 80D÷240F

SPINCHILLER24

4

HYDROPACK

ECOBREEZEFCR-410AAIR

WSAT-XSC2 EXC - -(3)

-(4)

80D SC(5)

CE(6)(2)(1)

EEV

NEW

WSAT-XSC2

(cooling)WSAN-XSC2

(heating)

HY

DRO

NIC

functions and features

available configurations

Water chillerWSAT-XSC2: cooling onlyWSAN-XSC2: reversible heat pump

Air cooledOutdoor installationCapacity from 197 to 657 kW

The Eurovent A Class SPINchiller2 water chillers and heat pumps provide the highest seasonal efficiency. They're designed to be installed outdoor and feature uneven scroll compressors mounted in the same circuit, electronic expansion valves and high efficiency plate type evaporators.

SPINchiller² shows an unmatched seasonal efficiency ESEER and is available in two versions: EXCELLENCE and PREMIUM. The standard version EXCELLENCE offers the highest efficiency both at full and at part load. Also the PREMIUM version offers high efficiency at part load but favour also the compact dimensions being therefore extremely competitive.

Thanks to its features, SPINchiller² offers:

4selfadaptivity in different load conditions, thanks to high number of capacity steps and to the management logic that has been developed to increase the efficiency and reduce the wear of the compressors;

4high unit reliability, thanks to the double refrigerant circuit, to the proven architecture and to the components produced at high volumes;

4 low noise, thanks to the sizing of the coil and to the high efficiency fans having "winglets" blade profiles;

4easy and quick installation, thanks to the quick connections to the system, to the easy electrical connections and to the complete functional test undertaken before the shipment. The units can also be supplied with inbuilt pumps, desuperheater and storage tank, allowing all the main components of the plant to be in the unit.

Cooling only(WSAT-XSC2)

Heating-Cooling(WSAN-XSC2)

Air cooled Outdoor inst. Refrig. R-410A Ice protectionsystem

Free-Cooling(WSAT-XSC2 only)

ECOBreeze HydroPack

(1) VERSION:4EXC EXCELLENCE (Standard)4PRM PREMIUM

(2) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.In addition, exchangers are complete with antifreeze heater to protect against the risk of ice.

4R Total recoveryCarried out using braze-welded plate-type exchangers suited for 100% recovery of condensation heat for producing hot water. In addition, exchangers are complete with antifreeze heater to protect against the risk of ice.

(3) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.Two versions are available:- Unit for low temperatures only

- Unit with double operating set-point The possibility of reducing the cooling capacity depends on the working temperature.

(4) FREE-COOLING (WSAT-XSC2 only):4- Not required (Standard)4FCD Direct Free-Cooling

Version that allows cold to be recovered at no cost from the ambient when the external air temperature is lower than the system return water temperature.To avoid problems with the unit, the water system must be protected by a mixture of water and glycol based on the minimum temperatures which may occur at the place of installation.

(5) ACOUSTIC CONFIGURATION:4SC Compressor soundproofing

This set-up is obtained by inserting the compressors in a soundproofed compartment.

4EN Super SilencedThis set-up is obtained by soundproofing the compressor compartment even more and reducing the fan speed of rotation.

(6) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Electronic Expansion Valve

Herm. Scroll

Eurovent EnergyEfficiency Class

(Config. SC EXC)

Eurovent EnergyEfficiency Class (Config. EXC)

Eurovent EnergyEfficiency Class (Config. PRM)

Guida_2011_v26.indd 80Guida_2011_v26.indd 80 22/03/11 14:3922/03/11 14:39

Page 10: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

81

80D 90D 100D 110D 120D 140D 160D 170E 180F 200F 220F 240F

5800 5800 5800 5800 5800 3800 4750 4750 5800 5800 5800 58001097 1097 1115 1115 1115 2228 2228 2228 2228 2228 2228 22281825 1825 2221 2221 2221 2221 2246 2246 2246 2246 2246 22461784 2057 2171 2329 2397 2821 3125 3490 4146 4297 4525 45714800 4800 5800 5800 5800 5800 5800 3800 3800 4750 4750 47501097 1097 1097 1097 1097 1115 1115 2228 2228 2228 2228 22281825 1825 1825 1825 1825 2221 2221 2221 2221 2246 2246 22461612 1892 2102 2213 2259 2311 2423 2915 3097 3515 3558 3787

2850 2850 3800 3800 3800 4750 4750 5800 5800 5800 5800 58002233 2233 2233 2233 2233 2233 2233 2233 2233 2233 2233 22332250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 22501877 2078 2502 2658 2707 3608 3765 4591 4792 4972 5216 52674800 5800 5800 5800 5800 5800 5800 - - - - -1097 1097 1097 1097 1120 1120 1120 - - - - -1825 1825 1825 1825 2250 2250 2250 - - - - -1805 2133 2325 2399 2362 2466 2512 - - - - -

80D 90D 100D 110D 120D 140D 160D 170E 180F 200F 220F 240F

4 kW 212 254 281 309 349 392 436 474 518 562 614 657kW 67,7 81,4 90,6 99,5 112 125 140 153 166 181 194 210- 3,13 3,12 3,10 3,10 3,11 3,14 3,11 3,10 3,13 3,10 3,17 3,13- 4,63 4,55 4,46 4,44 4,37 4,60 4,46 4,57 4,62 4,63 4,60 4,44dB(A) 71 71 72 73 73 74 74 74 74 74 74 75

4 kW 197 224 254 282 320 360 400 444 471 517 544 596kW 72,5 86,1 93,1 104 116 132 147 164 177 190 209 220- 2,72 2,61 2,73 2,72 2,75 2,73 2,73 2,70 2,66 2,72 2,60 2,71- 4,20 4,10 4,21 4,22 4,12 3,93 3,88 4,12 4,05 4,08 4,11 4,14dB(A) 65 66 66 67 67 68 68 69 69 69 70 70

4 kW 204 243 265 291 329 372 419 456 487 534 572 622kW 75,4 89,4 97,6 107 120 136 153 165 179 195 211 229

2,71 2,72 2,72 2,72 2,74 2,74 2,74 2,77 2,73 2,74 2,72 2,72kW 4,38 4,39 4,40 4,36 4,15 4,31 4,06 4,40 4,36 4,30 4,25 4,18

4 kW 230 280 309 343 384 430 488 519 565 625 679 732- 71,5 87,5 95,8 107 120 133 149 161 174 191 206 223- 3,22 3,20 3,23 3,22 3,21 3,24 3,28 3,23 3,24 3,27 3,29 3,28

4 kW 194 225 250 268 317 355 397 - - - - -kW 77,5 89,2 99,4 112 124 141 158 - - - - -- 2,51 2,52 2,52 2,40 2,52 2,51 2,51 - - - - -- 4,13 4,10 4,12 3,76 3,79 3,92 3,52 - - - - -

4 kW 219 260 280 305 349 393 432 - - - - -kW 69,9 85,0 92,2 100 116 130 143 - - - - -- 3,13 3,06 3,04 3,05 3,01 3,03 3,02 - - - - -- 2- 4 SCROLL 5 SCROLL 6 SCROLLV/Ph/Hz 400/3/50

BB2

B1

A

A1

A2

C

HY

DRO

NIC

accessories

technical data

■ Accessories supplied separately.

Sizes WSAT-XSC2

SC/EN EXC Length (A) mmSC/EN EXC Width (B) mmSC/EN EXC Height (C) mmSC/EN EXC Weight in oper. kgSC/EN PRM Length (A) mmSC/EN PRM Width (B) mmSC/EN PRM Height (C) mmSC/EN PRM Weight in oper. kgWSAN-XSC2

SC/EN EXC Length (A) mmSC/EN EXC Width (B) mmSC/EN EXC Height (C) mmSC/EN EXC Weight in oper. kgSC/EN PRM Length (A) mmSC/EN PRM Width (B) mmSC/EN PRM Height (C) mmSC/EN PRM Weight in oper. kg

The above data refer to standard units.

Please refer to the technical bulletin of the unit for the required clearancesCAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; ambient temperature = 35°C(2) Internal exchanger water = 40/45°C; air at external exchanger inlet = 6,1°C W.B.

(3) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

(4) Internal exchanger water = 15/10°C; glycol 30%

4 Switchboard ventilation4 Condenser coil in copper/aluminium with acrylic coating4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium coating4 Copper/copper condenser coil

■ 4 Spring antivibration mounts 4 Finned coil protection grilles4 Hail grilles4 Shut-off valve on compressor supply and return4 High and low pressure gauges4 Hydronic group with 1 pump4 Hydronic group with 1 pump + 1 stand by4 HydroPack with 2 pumps4 HydroPack with 3 pumps4 Storage tank4 Storage tank with onboard primary circuit

■ 4 Steel mesh filter on water side 4 Set point compensation with 0-10 V signal4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Device for reducing consumption of the outdoor section fans of the

ECOBreeze4 Phase monitor4 Multifunction phase monitor4 Soft Start4 Shunt capacitors (power factor > 0,9)4 MODBUS serial connection module4 BACNet serial connection module4 LonWorks serial connection module

■ 4 Remote control with remote microprocessor control 4 Master-slave operation

Key to symbols:

Data referred to the following conditions:

dimensions and clearances

SizesWSAT-XSC2

SC EXC Cooling capacity (1)SC EXC Total inputSC EXC Total EER at 100%SC EXC ESEERSC EXC Sound pressure level (3)SC PRM Cooling capacity (1)SC PRM Total inputSC PRM Total EER at 100%SC PRM ESEERSC PRM Sound pressure level (3)

WSAN-XSC2

SC EXC Cooling capacity (1)SC EXC Total inputSC EXC Total EER at 100%SC EXC ESEERSC EXC Heating capacity (2)SC EXC Total inputSC EXC COPSC PRM Cooling capacity (1)SC PRM Total inputSC PRM Total EER at 100%SC PRM ESEERSC PRM Heating capacity (2)SC PRM Total inputSC PRM COP

Number of refrigerant circuitsNumber and type of compressorsPower supply

leave free

Guida_2011_v26.indd 81Guida_2011_v26.indd 81 22/03/11 14:3922/03/11 14:39

Page 11: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

82

WSAT-XSC 270J÷360L

ECOBREEZE

EEVHYDROPACKFCR-410AAIR

SPINCHILLER

WSAT-XSC D B -(3)

200H ST(4)

T(5)

C(6)(2)(1)

HY

DRO

NIC

functions and features

available configurations

Water chillerAir cooledOutdoor installationCapacity from 692 to 965 kW

The SPINchiller series presents a new concept of chiller offering:

4EFFICIENCY that increases as the heating load decreases, while guaranteeing maximum requested load when necessary. SPINchiller always ensures maximum comfort with very high efficiency and consequently considerable energy savings;

4a modular approach. Several basic units may be connected together to form a single structure according to the required capacity. This allows high production standardisation and therefore utmost operating RELIABILITY;

4simple unit-system combination, since these units are SELF-ADAPTINGto the characteristics of the actual system, thereby avoiding delicate, time-consuming calibrations. Easy connection to the service system plus a simple control system and easy maintenance drastically reduce work requiring specialised personnel with consequent reduction in installation costs;

4extended operating limits to keep the system running, even under exceptional start-up and load conditions;

4customisation of the unit, also for special requirements both in the civil and technological air-conditioning sphere, thanks to the many available optional accessories. The ECOBreeze and HydroPack accessories in particular enhance the qualities of flexibility and energy efficiency. The latter, for example, consistent with the concept of modularity, has two pumps in parallel to monitor the system load variations better and to regulate the water flow in the critical system starting (or restarting) stages so that outside servicing is avoided.

The innovative and hi-tech features of SPINchiller give this series a much higher quality than can generally be found on the market today.

Cooling only Air cooled Outdoor inst. Refrig. R-410A Herm. scroll Free-Cooling ECOBreeze HydroPack Electronic Expansion Valve

(1) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

4R Total recoveryCarried out using braze-welded plate-type exchangers suited for 100% recovery of condensation heat for producing hot water.

(2) LOW TEMPERATURE:4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.Two versions are available- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity depends on the working temperature. Check with our sales office.

(3) ENERGY SAVING:4FCD Direct Free-Cooling

Version that allows cold to be recovered at no cost from the ambient when the external air temperature is lower than the system return water temperature.To avoid problems with the unit, the water system must be protected by a mixture of water and glycol based on the minimum temperatures which may occur at the place of installation.

(4) ACOUSTIC CONFIGURATION:4ST Standard4SC Compressor soundproofing

This set-up is obtained by inserting the compressors in a soundproofed compartment.

4EN Super SilencedThis set-up is obtained by soundproofing the compressor compartment even more and reducing the fan speed of rotation with an uprated condensing section.

(5) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(6) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Guida_2011_v26.indd 82Guida_2011_v26.indd 82 22/03/11 14:3922/03/11 14:39

Page 12: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

83

A

A2

C

A1

B1B

B2

270J 300L 315L 330L 345L 360L 4 kW 692 748 797 860 910 965

kW 251 272 289 309 328 349- 2,75 2,74 2,76 2,78 2,78 2,76- 4,51 4,58 4,60 4,64 4,64 4,62dB(A) 81 81 81 82 82 82dB(A) 77 78 78 78 79 79

4 kW 665 719 761 819 862 925kW 257 282 298 320 337 358- 2,58 2,55 2,55 2,55 2,56 2,58- 4,59 4,61 4,61 4,62 4,63 4,67dB(A) 71 72 72 73 73 73

kW 696 754 820 878 911 965°C -6,3 -5,3 -5,8 -6,3 -1,9 -2,2- 4- 10 SCROLL 12 SCROLLV/Ph/Hz 400/3/50

270J 300L 315L 330L 345L 360L5708 6658 6658 6658 7608 76082233 2233 2233 2233 2233 22332280 2280 2280 2280 2280 2280

4 1690 1690 1690 1690 1690 1690700 700 700 700 700 700

1100 1100 1100 1100 1100 11001100 1100 1100 1100 1100 11005358 6023 6080 6114 6511 65675570 6266 6324 6357 6745 68005570 6266 6324 6357 6745 6800

HY

DRO

NIC

accessories

technical data

■ Accessories supplied separately.

SizesST/SC Cooling capacity (1)ST/SC Total inputST/SC EER EUROVENTST/SC ESEERST Sound pressure level (2)SC Sound pressure level (2)EN Cooling capacity (1)EN Total inputEN EER EUROVENTEN ESEEREN Sound pressure level (2)FREE-COOLINGSC Free-Cooling rated output (3)SC Air temp. with Free-Cooling at 100%Number of refrigerant circuitsNumber and type of compressorsPower supply

Sizes ST/SC Length (A) mmST/SC Width (B) mmST/SC Height (C) mmST/SC (A1) mmST/SC (A2) mmST/SC (B1) mmST/SC (B2) mmST Weight in oper. kgSC Weight in oper. kgEN Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water 12/7°C; ambient temperature 35°C(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

(3) Internal exchanger water 15/10°C; glycol 30%

leave free

4 Condenser coil in copper/aluminium with acrylic coating4 Copper/copper condenser coil

■ 4 Spring antivibration mounts 4 Compressor compartment and condenser coil protection grilles4 Shut-off valve on compressor supply and return4 High and low pressure gauges4 HydroPack with 2 pumps4 User side anti-ice electric heaters for hydronic group

■ 4 Steel mesh filter on water side 4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Device for reducing consumption of the outdoor section fans of the

ECOBreeze4 Phase monitor

4 Shunt capacitors (power factor > 0,9)4 Soft Start4 CAN/MODBUS serial converter kit 4 CAN/LonWorks serial converter kit

■ 4 Data logger ■ 4 Master-slave operation 4 Free contacts for compressor status

■ 4 Remote control with remote microprocessor control

Key to symbols:

Data referred to the following conditions:

dimensions and clearances

Guida_2011_v26.indd 83Guida_2011_v26.indd 83 22/03/11 14:3922/03/11 14:39

Page 13: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

84

WDATA 2.160÷2.600

HYDROPACK

EEVECO

BREEZEFCAIR

WDATA B - 2.160 ST(4)

T(5)

C(6)(3)(2)

D(1)

R-134a

Eurovent EnergyEfficiency Class

SCREWLINE

HY

DRO

NIC

functions and features

available configurations

The experience gained by Clivet in the high-capacity chiller sector has resulted in the WDATA range, with the following features:

4EFFICIENCY - New high capacity screw compressors (over 1400 kW with 2 compressors), water-cooled shell-and-tube exchangers specially developed for the gas R-134a. The air-cooled exchangers have been designed and made directly by CLIVET to ensure best adaptation to the other refrigerant circuit parts. The compressors are managed with continual adjustment of the capacity and are fitted with an economiser circuit for further operating efficiency. In this way, the best result is achieved, highlighting the performance and reducing costs; all the series is in the ENERGETICCLASS "A", with performances over 3.1;

4SELF-ADAPTATION - New, modern and intelligent electronic control directly developed by Clivet. This customisation allows better management of all the circuit components.Continual adapting of chiller operating parameters to the load conditions of the system in which it is installed reduces consumption and noise level, while the working life of the parts increases;

4STURDINESS - Load-bearing frame in enamelled hot-galvanised sheet metal with semi-hermetic double-screw compressors and shell-and-tube evaporator ensuring reliability and constant performance. All the finishes are meticulously applied to ensure the utmost weathering resistance even under extreme conditions of use.

Water chillerAir cooledOutdoor installationCapacity from 432 to 1411 kW

Cooling only Air cooled Outdoor inst. Refrig. R-134a Twin-screw semi. Free-Cooling ECOBreeze HydroPack Electronic Expansion Valve

(1) ENERGY RECOVERY:4- Standard4D Partial recovery

Carried out using tube bundle exchargers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

4R Total recoveryCarried out using tube bundle exchargers suited for 100% recovery of condensation heat for producing hot water. This version is supplied as standard with a variable-speed low temperature device.

(2) LOW TEMPERATURE:4- Not required4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.Two versions are available:- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity depends on the working temperature.

(3) ENERGY SAVING:4- Standard4FCD Direct Free-Cooling

Version that allows cold to be recovered at no cost from the ambient when the external air temperature is lower than the system return water temperature.

(4) ACOUSTIC CONFIGURATION:4ST Standard4SC Compressor soundproofing

This set-up is obtained by inserting the compressors in a soundproofed compartment.

4LN SilencedThis set-up is obtained by inserting the compressors in a soundproofed compartment and reducing the fan speed of rotation with an uprated condensing section.

(5) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(6) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Unit listed on www.eurovent-certification.com

Guida_2011_v26.indd 84Guida_2011_v26.indd 84 22/03/11 14:3922/03/11 14:39

Page 14: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

85

2.160 2.180 2.190 2.200 2.240 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.6005704 5704 5704 5704 6654 6654 6654 6654 7612 7612 9512 9512 11414 114142239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 22392220 2220 2220 2220 2220 2220 2370 2370 2400 2400 2400 2400 2400 2400

4 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690700 700 700 700 700 700 700 700 700 700 700 700 700 7001100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 11001100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 11004447 4460 4732 5089 5260 5282 5589 6095 6424 6940 7522 8486 9487 100214727 4740 5012 5369 5626 5648 5939 6414 6844 7360 7942 9019 9829 10363

5704 5704 6654 6654 6654 6654 7612 7612 9512 9512 9512 11414 11414 -2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 -2220 2220 2220 2220 2220 2220 2400 2400 2400 2400 2400 2400 2400 -

4 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 -700 700 700 700 700 700 700 700 700 700 700 700 700 -1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 -1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 -4727 4856 5403 5817 5933 5955 6577 6970 7490 7859 8251 9652 10301 -

2.160 2.180 2.190 2.200 2.240 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.600- - - - - - - - - -

4 kW 435 471 522 564 616 699 767 835 882 935 1016 1138 1272 1411kW 140 150 167 180 198 225 247 268 284 300 328 366 408 452- 3,11 3,14 3,13 3,13 3,11 3,11 3,11 3,12 3,11 3,12 3,10 3,11 3,12 3,12- 3,83 3,73 3,89 3,94 3,93 4,02 4,02 4,09 4,09 4,14 3,96 4,04 4,03 4,08dB(A) 77 77 78 78 78 78 79 79 79 80 81 81 82 82dB(A) 74 74 75 75 76 76 76 76 76 77 78 78 79 79

4 kW 432 467 517 561 614 694 769 829 877 932 1020 1143 1287 -kW 138 150 165 180 198 224 247 267 281 299 329 368 413 -- 3,13 3,11 3,13 3,12 3,10 3,10 3,11 3,10 3,12 3,12 3,10 3,11 3,12 -- 3,95 3,93 3,94 4,01 4,04 4,12 4,12 4,16 4,12 4,14 4,15 4,15 4,13 -dB(A) 71 71 72 72 72 73 73 73 73 74 75 76 76 -

kW 458 492 546 590 641 724 795 864 915 970 1050 1182 1320 1463°C 0,0 -0,5 -1,0 -2,0 -1,0 -2,5 -3,8 -5,1 -6,2 -7,1 -3,7 -5,5 -3,5 -5,0kW 454 488 541 586 639 718 793 851 909 960 1055 1184 1334 -°C -2,0 -1,9 -1,6 -2,2 -3,3 -5,1 -6,8 -8,0 -4,3 -5,0 -6,5 -4,6 -6,5 -- 2

2 DSWV/Ph/Hz 400/3/50

B

B2

B1

A

A2

C

A1

HY

DRO

NIC

accessories

technical data

Sizes ST/SC Length (A) mmST/SC Width (B) mmST/SC Height (C) mmST/SC (A1) mmST/SC (A2) mmST/SC (B1) mmST/SC (B2) mmST Weight in oper. kgSC Weight in oper. kg

LN Length (A) mmLN Width (B) mmLN Height (C) mmLN (A1) mmLN (A2) mmLN (B1) mmLN (B2) mmLN Weight in oper. kg

The above data refer to standard units.

CAUTION!For trouble-free operation of the unit it is essential to maintain the clearances in green.

leave free

(*) The programme applies to air-cooled water chillers up to 600 kW and water-cooled water chillers up to 1500 kW.

(1) Internal exchanger water = 12/7°C; external air temperature 35°C(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions. (3) Internal exchanger water = 15/10°C; glycol 30% (4) DSW = twin-screw compressor

Data referred to the following conditions:

dimensions and clearances

SizesEurovent (*)

ST/SC Cooling capacity (1)ST/SC Total inputST/SC EER EUROVENTST/SC ESEERST Sound pressure level (2)SC Sound pressure level (2)LN Cooling capacity (1)LN Total inputLN EER EUROVENTLN ESEERLN Sound pressure level (2)

FREE-COOLINGSC Free-Cooling rated output (3)SC Air temp. with Free-Cooling at 100%LN Free-Cooling rated output (3)LN Air temp. with Free-Cooling at 100%Number of refrigerant circuitsNumber and type of compressors (4)Power supply

■ Accessories supplied separately.

Key to symbols:

4 Condenser coil in copper/aluminium with acrylic coating4 Copper/copper condenser coil4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment■ 4 Spring antivibration mounts 4 Compressor compartment and condenser coil protection grilles4 HydroPack with 2 pumps4 HydroPack with 3 pumps4 Set point compensation with 4-20 mA signal4 Set point compensation with 0-10 V signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Device for reducing consumption of the outdoor section variable

speed fans (phase-cut)

4 Device for reducing consumption of the outdoor section fans of the ECOBreeze

4 Magnetothermal circuit breakers4 Shunt capacitors (power factor > 0,9)4 MODBUS serial connection module4 BACNet serial connection module4 LonWorks serial connection module4 Master-slave operation

■ 4 Remote control with remote microprocessor control 4 Compressor suction shut-off valves4 Soft Start

Guida_2011_v26.indd 85Guida_2011_v26.indd 85 22/03/11 14:3922/03/11 14:39

Page 15: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

86

WDATB 2.160÷2.600

HYDROPACK

EEVECO

BREEZEFCAIR

WDATB B - 2.160 ST(4)

T(5)

C(6)(3)(2)

D(1)

R-134a

SCREWLINE

HY

DRO

NIC

functions and features

available configurations

The experience gained by Clivet in the high-capacity chiller sector has resulted in the WDATB range, with the following features:

4EFFICIENCY - New high capacity screw compressors (over 1380 kW with 2 compressors), water-cooled shell-and-tube exchangers specially developed for the gas R-134a. The air-cooled exchangers have been designed and made directly by CLIVET to ensure best adaptation to the other refrigerant circuit parts. The compressors are managed with continual adjustment of the capacity and are fitted with an economiser circuit for further operating efficiency. In this way, the best result is achieved, highlighting the performance and reducing costs; all the series is in the ENERGETICCLASS "B"

4SELF-ADAPTATION - New, modern and intelligent electronic control directly developed by Clivet. This customisation allows better management of all the circuit components.Continual adapting of chiller operating parameters to the load conditions of the system in which it is installed reduces consumption and noise level, while the working life of the parts increases;

4STURDINESS - Load-bearing frame in enamelled hot-galvanised sheet metal with semi-hermetic double-screw compressors and shell-and-tube evaporator ensuring reliability and constant performance. All the finishes are meticulously applied to ensure the utmost weathering resistance even under extreme conditions of use.

Water chillerAir cooledOutdoor installationCapacity from 375 to 1384 kW

Cooling only Air cooled Outdoor inst. Refrig. R-134a Twin-screw semi. Free-Cooling ECOBreeze HydroPack Electronic Expansion Valve

(1) ENERGY RECOVERY:4- Standard4D Partial recovery

Carried out using tube bundle exchargers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

4R Total recoveryCarried out using tube bundle exchargers suited for 100% recovery of condensation heat for producing hot water. This version is supplied as standard with a variable-speed low temperature device.

(2) LOW TEMPERATURE:4- Not required4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.Two versions are available:- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity depends on the working temperature.

(3) ENERGY SAVING:4- Standard4FCD Direct Free-Cooling

Version that allows cold to be recovered at no cost from the ambient when the external air temperature is lower than the system return water temperature.

To avoid problems with the unit, the water system must be protected by a mixture of water and glycol based on the minimum temperatures which may occur at the place of installation.

(4) ACOUSTIC CONFIGURATION:4ST Standard4SC Compressor soundproofing

This set-up is obtained by inserting the compressors in a soundproofed compartment.

4LN SilencedThis set-up is obtained by inserting the compressors in a soundproofed compartment and reducing the fan speed of rotation with an uprated condensing section.

4EN Super SilencedWith reference to the LN set-up, the fan speed of rotation is reduced even more with a larger condensing section and the Kit for Low Outdoor Temperature is standard supply with variable speed fans.The compressors are enclosed in a soundproofed compartment.

4CN Compact Super LownoiseWith reference to the LN version the fanspeed is reduced and the low ambient kit with fan at variable speed is supplied as a standard. The compressors are enclosed in a soundproof compartment.

(5) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(6) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Unit listed on www.eurovent-certification.com

Eurovent EnergyEfficiency Class

(Config. ST, SC, LN, EN)

Guida_2011_v26.indd 86Guida_2011_v26.indd 86 22/03/11 14:3922/03/11 14:39

Page 16: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

87

2.160 2.180 2.190 2.200 2.240 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.6004754 4754 5704 5704 5704 5704 5704 5704 6654 6654 6654 7612 9512 114142239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 22392220 2220 2220 2220 2220 2220 2370 2370 2370 2370 2370 2400 2400 24003680 3781 4227 4603 4759 4780 5241 5698 5775 6010 6567 7723 8263 91154080 4181 4507 4883 5039 5060 5471 5918 6175 6410 6967 8143 8683 95375704 5704 5704 6654 6654 6654 6654 6654 7612 7612 9512 9512 11414 114142239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 22392220 2220 2220 2220 2220 2220 2370 2370 2370 2370 2370 2400 2400 24004337 4350 4623 5503 5543 5680 5987 6473 6844 7002 7860 8791 9330 98195704 6654 6654 6654 7612 7612 9512 9512 9512 9512 11414 11414 11414 -2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 -2220 2220 2220 2220 2220 2220 2370 2370 2400 2400 2400 2400 2400 -4337 4970 5234 5887 6349 6423 6838 7236 7408 7419 8137 9289 9562 -4754 4754 4754 4754 4754 5704 6654 6654 6654 6654 6654 9512 9512 95122239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 2239 22392220 2220 2220 2220 2220 2220 2370 2370 2370 2370 2370 2400 2400 24004008 4032 4143 4341 4708 4897 5812 6248 6259 6270 6584 8559 8831 9759

4 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690700 700 700 700 700 700 700 700 700 700 700 700 700 7001100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 11001100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100

2.160 2.180 2.190 2.200 2.240 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.600- - - - - - - - -

4 kW 423 462 502 535 588 669 751 807 855 905 994 1108 1239 1384kW 145 157 170 183 202 231 258 278 294 309 343 382 427 478- 2,92 2,94 2,95 2,92 2,91 2,90 2,91 2,90 2,90 2,92 2,90 2,90 2,90 2,90- 3,72 3,71 3,75 3,78 3,84 3,85 3,88 3,90 4,00 3,99 3,93 3,91 3,86 3,86dB(A) 76 77 78 78 78 78 79 79 79 80 81 81 82 82dB(A) 74 74 75 75 75 75 76 76 76 77 78 78 79 79

4 kW 423 456 496 532 584 662 743 801 855 895 991 1112 1241 1375kW 146 156 170 183 201 228 256 275 294 309 342 383 426 474- 2,90 2,92 2,92 2,91 2,91 2,90 2,90 2,91 2,90 2,90 2,90 2,90 2,91 2,90- 3,75 3,82 3,79 3,72 3,90 3,91 3,93 3,97 4,04 3,98 3,93 3,93 3,90 3,90dB(A) 71 71 72 72 72 73 73 73 73 74 75 76 76 77

4 kW 417 456 498 538 590 668 744 796 851 893 996 1099 1216 -kW 143 157 171 184 203 230 256 272 293 306 342 378 419 -- 2,92 2,90 2,91 2,92 2,91 2,90 2,91 2,93 2,90 2,92 2,91 2,91 2,90 -- 3,82 3,79 3,80 3,80 3,86 3,89 3,96 4,03 4,05 4,03 3,97 4,00 3,94 -dB(A) 64 65 65 66 66 68 68 68 68 68 69 70 70 -

4 kW 375 418 453 498 545 617 681 730 775 830 910 1020 1127 1273kW 148 164 181 198 216 245 268 288 310 330 364 404 449 505- 2,53 2,55 2,50 2,51 2,52 2,52 2,55 2,53 2,50 2,52 2,50 2,53 2,51 2,52- 3,37 3,18 3,22 3,31 3,42 3,44 3,49 3,42 3,42 3,36 3,48 3,35 3,35 3,32dB(A) 65 65 65 67 67 68 69 69 69 69 70 71 71 72

kW 443 481 524 556 610 693 774 841 887 941 1026 1144 1280 1434°C -2,5 -2,5 -1,2 -2,0 -2,5 -4,2 -5,8 -7,2 -6,4 -7,3 -7,9 -9,9 -6,7 -5,5kW 445 476 519 551 602 689 766 824 883 927 1023 1148 1282 1416°C -1,5 -2,5 -2,8 -2,0 -3,4 -4,5 -6,1 -7,4 -8,5 -9,5 -7,5 -8,0 -7,0 -7,5- 2

2 DSWV/Ph/Hz 400/3/50

B

B2

B1

A

A2

C

A1

HY

DRO

NIC

accessories

technical data

Sizes ST/SC Length (A) mmST/SC Width (B) mmST/SC Height (C) mmST Weight in oper. kgSC Weight in oper. kgLN Length (A) mmLN Width (B) mmLN Height (C) mmLN Weight in oper. kgEN Length (A) mmEN Width (B) mmEN Height (C) mmEN Weight in oper. kgCN Length (A) mmCN Width (B) mmCN Height (C) mmCN Weight in oper. kg

(A1) mm(A2) mm(B1) mm(B2) mm

The above data refer to standard units.

CAUTION!For trouble-free operation of the unit it is essential to maintain the clearances in green.

leave free

■ Accessories supplied separately.Key to symbols:

(*) The programme applies to air-cooled water chillers up to 600 kW and water-cooled water chillers up to 1500 kW.

1) Internal exchanger water 12/7°C; external air temperature 35°C(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions. (3) Internal exchanger water 15/10°C; glycol 30% (4) DSW = twin-screw compressor

Data referred to the following conditions:

dimensions and clearances

SizesEurovent (*)

ST/SC Cooling capacity (1)ST/SC Total inputST/SC EER EUROVENTST/SC ESEERST Sound pressure level (2)SC Sound pressure level (2)LN Cooling capacity (1)LN Total inputLN EER EUROVENTLN ESEERLN Sound pressure level (2)EN Cooling capacity (1)EN Total inputEN EER EUROVENTEN ESEEREN Sound pressure level (2)CN Cooling capacity (1)CN Total inputCN EER EUROVENTCN ESEERCN Sound pressure level (2)

FREE-COOLINGSC Free-Cooling rated output (3)SC Air temp. with Free-Cooling at 100%LN Free-Cooling rated output (3)LN Air temp. with Free-Cooling at 100%Number of refrigerant circuitsNumber and type of compressors (4)Power supply

4 Condenser coil in copper/aluminium with acrylic coating4 Copper/copper condenser coil4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment■ 4 Spring antivibration mounts 4 Compressor compartment and condenser coil protection grilles4 HydroPack with 2 pumps4 HydroPack with 3 pumps4 Set point compensation with 4-20 mA signal4 Set point compensation with 0-10 V signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Device for reducing consumption of the outdoor section variable

speed fans (phase-cut)

4 Device for reducing consumption of the outdoor section fans of the ECOBreeze

4 Magnetothermal circuit breakers4 Shunt capacitors (power factor > 0,9)4 MODBUS serial connection module4 BACNet serial connection module4 LonWorks serial connection module4 Master-slave operation

■ 4 Remote control with remote microprocessor control 4 Compressor suction shut-off valves4 Soft Start

Guida_2011_v26.indd 87Guida_2011_v26.indd 87 22/03/11 14:3922/03/11 14:39

Page 17: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

88

WDAT-HT 2.180÷2.600

AIR

WDAT-HT D 2.600 ST(2)

T(3)

C(4)(1)

R-134a HYDROPACK

EEVECO

BREEZE

Eurovent EnergyEfficiency Class

SCREWLINE

HY

DRO

NIC

functions and features

available configurations

Water chillerAir cooledOutdoor installationCapacity from 459 to 1535 kW

Cooling only Air cooled Outdoor inst. Refrig. R-134a Twin-screw semi.

(1) ENERGY RECOVERY:4- Standard4D Partial recovery

Carried out using tube bundle exchargers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

(2) ACOUSTIC CONFIGURATION:4ST Standard4SC Compressor soundproofing

This set-up is obtained by inserting the compressors in a soundproofed compartment.

(3) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(4) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

ECOBreeze HydroPack Electronic Expansion Valve

The air-cooled liquid chillers in the WDAT-HT range are the ideal solution in torrid climates with high outdoor temperatures.Equipped with high capacity twin screw compressors, R134a refrigerant and shell and tube evaporators, they are also characterised by:

4outdoor installation with operation up to 58°C

4high energy efficiency at full or partial loads: all the units have a Eurovent class A rating

4minimum environmental impact, thanks to lower CO2 emissions and the low refrigerant content achieved with dry expansion technology

4high levels of reliability and reduced maintenance costs, thanks to the heavy duty components used. External heat exchangers are also available with a specific cladding, to preserve their heat exchange properties over time

4easy installation thanks to the quick connections with the main circuit, electrical wiring enablement and complete functional testing before delivery. The on-board accessories, such as the pump assemblies and heat recovery units, lead to a further reduction in system planning and development times and costs.

Guida_2011_v26.indd 88Guida_2011_v26.indd 88 22/03/11 14:4022/03/11 14:40

Page 18: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

89

2.180 2.200 2.220 2.240 2.280 2.320 2.360 2.420 2.450 2.480 2.510 2.540 2.570 2.6004 kW 413 471 534 592 665 782 871 925 995 1075 1150 1202 1281 1349

TON 118 135 153 169 190 223 249 264 284 307 329 343 366 385kW 164 188 212 235 263 310 345 367 394 428 457 478 509 534- 2,52 2,51 2,52 2,52 2,53 2,52 2,52 2,52 2,53 2,51 2,52 2,51 2,52 2,53dB(A) 80 81 81 81 82 82 83 83 84 84 84 85 85 85dB(A) 77 78 79 79 79 79 80 80 81 81 81 82 82 82- 2- 2 DSWV/Ph/Hz 400/3/50

2.180 2.200 2.220 2.240 2.280 2.320 2.360 2.420 2.450 2.480 2.510 2.540 2.570 2.6005700 5700 5700 6650 6650 7600 9500 9500 10450 11400 11400 11400 11900 119002233 2233 2233 2233 2233 2233 2233 2233 2233 2233 2233 2233 2233 22332250 2250 2250 2250 2250 2250 2400 2400 2400 2400 2400 2400 2500 2500

4 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690 1690700 700 700 700 700 700 700 700 700 700 700 700 700 7001100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 11001100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100

B

B2

B1

A

A2

C

A1

HY

DRO

NIC

accessories

technical data

■ Accessories supplied separately.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water 12/7°C; ambient temperature 46°C(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions. (3) DSW = twin-screw compressor

4 Condenser coil in copper/aluminium with acrylic coating4 Condenser coil in copper/copper4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment■ 4 Spring antivibration mounts 4 Compressor compartment and condenser coil protection grilles4 Set point compensation with 4-20 mA signal4 Set point compensation with 0-10 V signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Compressor suction shut-off valves4 Device for reducing consumption of the outdoor section variable

speed fans (phase-cut)4 Hydropack with 2 pumps

4 Hydropack with 3 pumps4 General isolating switch4 Magnetothermal circuit breakers4 Shunt capacitors (power factor > 0,9)4 CAN/MODBUS serial converter kit 4 CAN/LonWorks serial converter kit

■ 4 Master-slave operation 4 Free contacts for compressor status4 Free contacts for compressor status and enabling4 Clean contacts for compressor enabling and status, local/off/BMS

selector■ 4 Remote control with remote microprocessor control

Key to symbols:

Data referred to the following conditions:

dimensions and clearances

SizesCooling capacity (1)Cooling capacity (1)Total input (1)EER EUROVENT (1)

ST Sound pressure level (2)SC Sound pressure level (2)Number of refrigerant circuitsNumber and type of compressors (3)Power supply

leave free

Guida_2011_v26.indd 89Guida_2011_v26.indd 89 22/03/11 14:4022/03/11 14:40

Page 19: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

9090

WSA-EE WSN-EE 17÷91

ELFOENERGY SMALL

R-407CAIR

WSN-EE 17S(1)

CE(2)

T(3)

4

4

HY

DRO

NIC

functions and features

available configurations

Water chillerWSA-EE: cooling onlyWSN-EE: reversible heat pump

Air cooledIndoor installationCapacity from 4,47 to 22,6 kW

The liquid chillers and heat pumps of the ELFOEnergy WSA-EE and WSN-EEseries are units designed for indoor installation and best energy efficiency in relation to their reduced size.The ELFOEnergy series has been the turning point in the evolution of chillers.Every unit has been conceived and made by applying state-of-the-art technology, emphasising the qualities of EFFICIENCY, SELF-ADAPTATIONand EASY INSTALLATION that distinguish this product.Thanks to its constructional and electronic peculiarities, ELFOEnergypermits:

4adaptability of operating parameters to the load conditions of the connected system, thereby optimising consumption, efficiency and working life of the parts;

4easy, quick installation thanks to the standard hydronic group and the factory test carried out prior to dispatch.

4use of a centrifugal fan, which allows the air from the condensing section to be ducted.

Air cooled Indoor inst. Refrig. R-407C Herm. Scroll(sizes 31÷91)

ELFOControl Ice protectionsystem (WSN-EE only)

(1) VERSION:4S Standard4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -8°C inclusive.Two versions are available- Unit for low temperatures only- Unit with double operating set-point

(2) EXCHANGER APPROVALS:4CE PED (European test)

(3) ENERGY EFFICIENCY:4T Temperate climate

Herm. Rotary(sizes 17÷25)

Cooling only(WSA-EE)

Heating-Cooling(WSN-EE)

Vary Flow(sizes 17÷31)

Guida_2011_v26.indd 90Guida_2011_v26.indd 90 22/03/11 14:4022/03/11 14:40

Page 20: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

9191

17 21 25 31 41 51 61 71 81 91

4 kW 4,47 5,37 7,14 8,50 10,7 12,9 14,9 17,0 18,8 22,6kW 1,76 2,18 2,91 3,39 4,55 5,23 6,12 6,76 7,73 8,91- 2,54 2,46 2,45 2,51 2,35 2,47 2,43 2,51 2,43 2,54- 2,84 2,88 2,70 2,88 2,62 2,75 2,77 2,86 2,77 2,86kPa 52 42 44 32 149 129 123 105 114 87

4 kW 4,37 5,24 7,13 8,39 10,6 12,5 14,5 17,0 18,7 22,4kW 1,77 2,28 2,93 3,38 4,47 5,25 6,16 6,67 7,57 8,85- 2,47 2,30 2,43 2,48 2,37 2,38 2,37 2,55 2,47 2,53- 2,76 2,74 2,68 2,86 2,63 2,67 2,69 2,89 2,78 2,87

4 kW 4,79 5,74 7,67 9,16 11,4 13,6 15,8 18,8 20,6 24,7kW 1,88 2,35 3,00 3,67 4,82 5,73 6,41 7,56 8,06 9,76- 2,55 2,44 2,56 2,50 2,37 2,37 2,46 2,49 2,56 2,53

4 kW 4,22 5,08 6,77 8,17 10,1 11,8 13,8 16,4 18,0 21,9kW 1,79 2,28 2,90 3,64 4,78 5,47 6,29 7,41 7,91 9,56- 2,36 2,23 2,33 2,24 2,11 2,16 2,19 2,21 2,28 2,29

4 kW 3,20 3,91 5,30 6,57 7,81 8,90 10,5 12,4 13,5 17,1kW 1,67 2,20 2,74 3,72 4,72 5,39 6,20 7,26 7,80 9,33- 1,92 1,78 1,94 1,77 1,66 1,65 1,69 1,70 1,73 1,83kPa 53 44 44 34 150 132 126 105 114 89Pa 60 60 60 60 100 100 100 100 100 100°C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10°C 53 52,5 53,5 52 52 51,5 52 50,5 53 51,5I/s 0,21 0,25 0,34 0,40 0,51 0,60 0,71 0,81 0,89 1,07dB(A) 39 40 42 43 47 48 48 51 52 53V/Ph/Hz 230/1/50 400/3/50+N

B

B2

A

C

A1

17 21 25 31 41 51 61 71 81 91

838 838 982 982 1206 1206 1206 1516 1516 1516561 561 647 647 724 724 724 760 760 760649 649 648 648 721 721 721 1045 1045 1045

4 500 500 500 500 500 500 500 500 500 500200 200 200 200 200 200 200 200 200 20083 89 121 130 168 176 180 256 320 329

838 838 982 982 1206 1206 1206 1516 1516 1516560 560 649 649 724 724 724 760 760 760649 649 648 648 721 721 721 1043 1043 1043

4 500 500 500 500 500 500 500 500 500 500150 150 200 200 200 200 200 200 200 20084 90 122 131 169 177 181 260 323 332

HY

DRO

NIC

Data referred to the following conditions:

technical data

(1) A35 / W7 internal exchanger water 12/7°C; external air temperature 35°CA7 / W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2 / W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5 / W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles.

(4) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(5) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water

7°C.(6) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat

exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.(7) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10

m from the external surface of the unit in open field conditions.

SizesWSA-EE

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (4)ESEER (5)Pump working head (6)

WSN-EEA35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (4)ESEER (5)

A7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

Pump working head (6)Air side available static pressure (6)Minimum external air temperatureMaximum water temperatureWater flow rate (6)Sound pressure level (7)Power supply

dimensions and clearancesSizes WSA-EELength (A) mmWidth (B) mmHeight (C) mm

(A1) mm(B2) mm

Weight in oper. kgWSN-EELength (A) mmWidth (B) mmHeight (C) mm

(A1) mm(B2) mm

Weight in oper. kg

The above data refer to standard units.CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances

in green.

accessories

■ Accessories supplied separately.

■ 4 Rubber antivibration mounts 4 Condenser coil in copper/aluminium with acrylic coating4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment4 Copper/copper condenser coil

■ 4 Serial communication module (MODBUS) 4 Device for operation with low external air temperature with variable

fan speed through inverter (sizes 71÷91)■ 4 Steel mesh filter on water side ■ 4 Remote keyboard for user, to control the unit main functions■ 4 Service keypad (cable from 1,5 metres)

■ 4 Phase monitor ■ 4 Set point compensation with according to outdoor enthalpy ■ 4 Double temperature control kit, set point compensation 4-20 mA,

3-way valve4 Supply voltage 230/1/50 (for sizes 31-41)4 Supply voltage 400/3/50+N (for sizes 17÷25)4 Unit without hydronic group

WSA-EE only:■ 4 Device for operation with low external air temperature with variable

fan speed (sizes 17÷61)■ 4 Set point compensation with fresh air sensor

Key to symbols:

Guida_2011_v26.indd 91Guida_2011_v26.indd 91 22/03/11 14:4022/03/11 14:40

Page 21: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

92

WSA-XEE WSN-XEE 122÷402

4

4

AIR

WSA-XEE 142S(1)

400T(2)

1PUHE(3)

ELFOENERGY DUCT MEDIUM NEW

Eurovent EnergyEfficiency Class

EEVECO

BREEZER-410A

-(4)

-(5)

-(6)

-(7)

-(8)

MO(9)

HY

DRO

NIC

functions and features

available configurations

Water chillerWSA-XEE: cooling onlyWSN-XEE: heat pump

Air cooledIndoor installationCapacity from 36 to 101 kW

Cooling only(WSA-XEE)

Heating-Cooling(WSN-XEE)

Air cooled Indoor inst. Herm. Scroll

(1) LOW TEMPERATURE:4S Standard4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.

4DSPB Double set-point for water low temperature (Brine)

(2) SUPPLY VOLTAGE:4400T Supply voltage 400/3/50

(3) HYDRONIC GROUP USER SIDE:41PUHE Inverter pump for primary circuit (standard)41PUS Standard pump41PUM Single pump with larger discharge head42PUS Standard double pump42PUM Double pump with larger discharge head4- Not required

(4) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 25% of the total unit heat.

4R Total recovery

Carried out using braze-welded plate-type exchangers suited for 100% recovery of the total unit heat.

(5) CONDENSER COIL:4CCS Standard condenser coil4CCCA Condenser coil in copper/aluminium with acrylic coating4CCCA1Condenser coil in copper/aluminium with Energy Guard DCC Aluminium treatment

(6) SOFT STARTER:4- Not required (standard)4SFSTR Device for inrush current reduction for 400/3/50

(7) SHUNT CAPACITORS (COSFI > 0,9):4- Not required (standard)4PFCP Shunt capacitors (cosfi > 0,9)

(8) REDUCED OUT. SECT. FAN CONSUMPTION:4CREFB Device for the reduction of ECOBreeze type outdoor section fan consumption

(Standard)4- Not required

(9) AIR SUPPLY:4MO Horizontal air supply (standard)4M5 Upward air supply

Available from the 2nd semester 2011

ECOBreezeElectronic Expansion Valve

Refrig. R-410A

The chillers and heat pumps of WSA-XEE and WSN-XEE series are indoor units with ducted condensation.

Thanks to his special design ELFOEnergy Duct Medium main features are:

4Versatility: different combinations of inlet and outlet plug fans enable to connect easily the unit to the air ducts and to have high available head;

4High energy efficiency: ELFOEnergy Duct Medium besides being in Eurovent efficiency class A at full load grants high seasonal power efficiency thanks to the innovative cooling circuit optimized for partial load operation and the DST (Dynamic Supply Temperature) return control logic;

4Easy installation: the units are very compact and are supplied with high efficiency pumps on board; therefore the available space for other purposes is increased and the installations costs are reduced.

Guida_2011_v26.indd 92Guida_2011_v26.indd 92 22/03/11 14:4022/03/11 14:40

Page 22: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

93

122 162 182 222 262 302 352 402

4 kW 36,0 41,8 49,3 58,3 67,8 78,3 88,3 101kW 12,2 14,3 17,0 20,7 23,7 27,2 31,2 36,5- 2,94 2,92 2,91 2,81 2,86 2,88 2,83 2,76- 3,90 4,07 4,15 4,04 4,01 4,02 4,07 3,97

4,16 4,30 4,41 4,32 4,25 4,27 4,31 4,18kPa 59 55 45 43 39 52 44 44

4 kW 33,2 38,2 43,4 52,1 61,9 71,4 79,2 -kW 12,9 15,1 18,7 22,1 24,6 28,3 33,7 -- 2,58 2,53 2,32 2,36 2,51 2,52 2,35 -

4 kW 41,3 47,9 55,9 65,1 77,3 88,3 97,9 -kW 12,7 14,7 17,7 20,5 23,5 27,0 30,6 -- 3,25 3,26 3,16 3,18 3,29 3,27 3,20 -kPa 75 73 68 63 51 65 63 -

4 kW 42,2 49,0 57,1 66,5 79,4 90,3 100 -kW 10,3 11,9 14,4 16,9 19,6 22,4 25,2 -- 4,09 4,12 3,96 3,94 4,05 4,03 3,96 -kPa 46 42 32 34 26 49 46 -- 1- 2 SCROLLdB(A) 60 61 64 65 66 67 67 68V/Ph/Hz 400/3/50

122 162 182 222 262 302 352 402

1450 1450 1850 1850 2250 2650 2650 2650780 780 780 780 780 780 780 7801997 1997 1997 1997 1997 1997 1997 1997

4 1000 1000 1000 1000 1000 1000 1000 1000500 500 500 500 500 500 500 500100 100 100 100 100 100 100 1001300 1300 1300 1300 1300 1300 1300 1300

1450 1850 1850 2250 2650 2650 2650 -780 780 780 780 780 780 780 -1997 1997 1997 1997 1997 1997 1997 -

4 1000 1000 1000 1000 1000 1000 1000 -500 500 500 500 500 500 500 -100 100 100 100 100 100 100 -1300 1300 1300 1300 1300 1300 1300 -

A

A1

A2

BB2

C

B1

(*)

HY

DRO

NIC

dimensions and functional spaces

accessories

technical data

■ Accessories supplied separately.

Sizes WSA-XEELength (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

WSN-XEELength (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

The above data refer to standard units.CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances

in green.

PRELIMINARY DATA(1) Internal exchanger water 12/7°C; air entering external exchanger 35°C(2) Total input is obtained from the compressor input + fan input - the proportional part of the fan to supply the

available head to installation input + auxiliary circuit input.(3) Ambient temperature 7°C D.B./ 6°C W.B.; internal exchanger water outlet temperature 45°C(4) Fresh air temperature 7°C D.B./ 6°C W.B.; internal exchanger water temperature 30/35°C(5) The total absorbed power is calculated adding the compressors power input + the fan power input - the

proportional part of the fan to supply the available head to installation input + the power absorbed by the pump - the proportional part of the pump to supply the available head to installation input + the power absorbed by the auxiliary circuit.

(6) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

(7) DST = Dynamic Supply Temperature: return control logic.

Key to symbols:

Data referred to the following conditions:

dimensions and clearances

SizesApplication with terminal unitsWSA-XEE

Cooling capacity (1)Total input (1)(2)EER EUROVENT (1)ESEER EUROVENT (1)

Seasonal efficiency DST (7)Pump working head (1)WSN-XEE

Cooling capacity (1)Total input (1)(2)EER EUROVENT (1)Heating capacity (3)Total input (2)(3)COP EUROVENT (3)

Pump working head (1)Application with radiant panelsWSN-XEE

Heating capacity (4)Total input (4)(5)COP (EN:14511:2008) (4)

Pump working head (4)Number of refrigerant circuitsNumber and type of compressorsSound pressure level (6)Power supply

■ 4 Rubber antivibration mounts ■ 4 Serial communication module to supervisor (MODBUS)■ 4 Serial communication module to supervisor (BACnet) ■ 4 Serial communication module to supervisor (LonWorks) ■ 4 Steel mesh filter on water side (when unit is in “without hydronic

group” configuration)

■ 4 High and low pressure gauges■ 4 Remote interface kit to microprocessor unit■ 4 Phase monitor to check the presence and correct sequence of the

power supply phases

(*) Optional

Guida_2011_v26.indd 93Guida_2011_v26.indd 93 22/03/11 14:4022/03/11 14:40

Page 23: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

94

WRA WRN 404÷604

4

4

R-407CAIR

WRA 404D(1)

ST(3)

C(5)

B(2)

T(4)

HY

DRO

NIC

functions and features

available configurations

Water chillerWRA: cooling onlyWRN: reversible heat pump

Air cooledIndoor installationCapacity from 100 to 144 kW

The liquid chillers and heat pumps of the WRA and WRN series are units designed for indoor installation and best energy efficiency in relation to their reduced size.Use of low-rev centrifugal fans and special thermal and acoustic insulation of the cabinet have resulted in highly reduced noise levels.The head pressures available with centrifugal fans enable wide ducting for air return and cooled air discharge to be installed.

Cooling only(WRA)

Heating-Cooling(WRN)

Air cooled Indoor inst. Refrig. R-407C Herm. Scroll Ice protectionsystem

(1) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 25% of the total unit heat.

(2) LOW TEMPERATURE:4- Not required4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -7°C inclusive.Two versions are available:- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity depends on the working temperature.

(3) ACOUSTIC CONFIGURATION:4ST Standard

(4) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(5) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Guida_2011_v26.indd 94Guida_2011_v26.indd 94 22/03/11 14:4022/03/11 14:40

Page 24: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

9595

BB1

B2

A

A2

C

A1

404 464 524 564 604

4 kW 100 111 121 137 144kW 45,5 50,1 56,7 60,9 68,2- 2,20 2,22 2,14 2,25 2,11

4 kW 100 109 118 132 140kW 43,7 49,4 55,5 62,1 68,0- 2,28 2,21 2,13 2,13 2,07

4 kW 112 124 137 152 163kW 42,7 48,2 54,1 60,6 66,3Pa 90 90 90 120 90- 2- 4 SCROLLdB(A) 61 61 61 63 64V/Ph/Hz 400/3/50

404 464 524 564 6043308 3308 3308 3308 33081155 1155 1155 1155 11552275 2275 2275 2275 2275

4 500 500 500 500 500500 500 500 500 50070 70 70 70 70

1300 1300 1300 1300 13001530 1590 1620 1710 1740

HY

DRO

NIC

■ Accessories supplied separately.

SizesWRA

Cooling capacity (1)Total inputTotal EER at 100%

WRNCooling capacity (1)Total inputTotal EER at 100%Heating capacity (2)Total input

Max. working static pressureNumber of refrigerant circuitsNumber and type of compressors (3)Sound pressure level (4)Power supply

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; external air temperature 35°C;(2) External exchanger water = 40/45°C; ambient temperature = 7°C (R.H. = 85%)(3) RCP = reciprocating

(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

4 Condenser coil in copper/aluminium with acrylic coating4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment4 Copper/copper condenser coil

■ 4 Spring antivibration mounts ■ 4 Rubber antivibration mounts 4 High and low pressure gauges

■ 4 Steel mesh filter on water side 4 Uprated electric fan motor4 4/8-pole electric fan motor4 Horizontal air supply4 Upward air supply4 Magnetothermal circuit breakers4 Compressor and fan thermal cutouts

4 Phase monitor4 Daily and weekly programming clock4 Shunt capacitors (power factor > 0,9)4 Serial communication module PC/BMS MODBUS for 1 unit

(Master)■ 4 Remote control with remote microprocessor control WRA only:4 Anti-ice electric heater to protect the internal exchanger

WRN only:4 Condensate collecting tray with electric heater

Key to symbols:

Data referred to the following conditions:

accessories

technical data

dimensions and clearances

Guida_2011_v26.indd 95Guida_2011_v26.indd 95 22/03/11 14:4022/03/11 14:40

Page 25: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

96

WSA-SC 65D÷100D

SPINCHILLER

EEVHYDROPACKR-407CAIR

WSA-SC 65DR(1)

SC(3)

C(5)

B(2)

T(4)

HY

DRO

NIC

functions and features

available configurations

Water chillerAir cooledIndoor installationCapacity from 173 to 257 kW

The SPINchiller series presents a new concept of chiller.The WSA-SC units are designed for indoor installation with ducted discharge for chilled water solutions. These units offer:4EFFICIENCY that increases as the heating load decreases, while

guaranteeing maximum requested load when necessary. SPINchiller always ensures maximum comfort with very high efficiency and consequently considerable energy savings;

4simple unit-system combination, since these units are SELF-ADAPTINGto the characteristics of the actual system, thereby avoiding delicate, time-consuming calibrations. Easy connection to the service system plus a simple control system and easy maintenance of all the most sensitive parts drastically reduce work requiring specialised personnel with consequent reduction in installation costs;

4The particular abundance of optional accessories allows customisation of the unit, also for special requirements both in the civil and technological air-conditioning sphere. In particular the optional for the HydroPack water circulating unit, consistent with the concept of modularity, has several pumps in parallel (up to 3), to monitor the system load variations better and to regulate the water flow in the critical system starting (or restarting) stages so that outside servicing is avoided.

The innovative and hi-tech features of SPINchiller give this series a much higher quality than can generally be found on the market today.

(1) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

4R Total recoveryCarried out using braze-welded plate-type exchangers suited for 100% recovery of condensation heat for producing hot water.

(2) LOW TEMPERATURE:4- Not required4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -7°C inclusive.Two versions are available:- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity depends on the working temperature.

(3) ACOUSTIC CONFIGURATION:4SC Compressor soundproofing (Standard)

(4) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(5) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Cooling only Air cooled Indoor inst. Refrig. R-407C Herm. Scroll HydroPack Electronic Expansion Valve

Guida_2011_v26.indd 96Guida_2011_v26.indd 96 22/03/11 14:4022/03/11 14:40

Page 26: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

97

BB1

B2

A

A2

C

A1

(*)

65D 70D 75C 75D 80D 90C 90D 100D4 kW 173 182 200 198 212 237 231 257

kW 66,9 71,1 75,7 79,0 82,0 94,4 92,0 102- 2,55 2,54 2,63 2,50 2,53 2,46 2,44 2,41- 2,80 2,82 3,90 2,77 2,86 3,85 2,67 2,67Pa 90 50 50 60 90 90 120 120- 2 1 2 1 2- 4 SCROLL 3 SCROLL 4 SCROLL 3 SCROLL 4 SCROLLdB(A) 72 73 73 74 74 74 75 76V/Ph/Hz 400/3/50

65D 70D 75C 75D 80D 90C 90D 100D4400 4400 4400 4400 4400 4400 4400 44001140 1140 1140 1140 1140 1140 1140 11402270 2270 2270 2270 2270 2270 2270 2270

4 900 900 900 900 900 900 900 900900 900 900 900 900 900 900 9001300 1300 1300 1300 1300 1300 1300 1300

(**)2135 2312 2118 2176 2258 2385 2437 2474

HY

DRO

NIC

■ Accessories supplied separately.

SizesCooling capacity (1)Total inputEER EUROVENTESEER

Max. working static pressureNumber of refrigerant circuitsNumber and type of compressorsSound pressure level (2)Power supply

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

The above data refer to standard units.

(**) Space depending on the type of installation.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; external air temperature 35°C;(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

4 Condenser coil in copper/aluminium with acrylic coating4 Condenser coil in copper/aluminium with Energy Guard DCC

Aluminium treatment■ 4 Spring antivibration mounts 4 Shut-off valve on compressor supply and return4 High and low pressure gauges4 HydroPack with 2 pumps4 HydroPack with 2 pumps + 1 in stand-by4 HydroPack with 3 pumps4 HydroPack with 3 pumps + 1 spare onboard4 User side anti-ice electric heaters for hydronic group

■ 4 Steel mesh filter on water side 4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor

4 Set point compensation with according to outdoor enthalpy4 Uprated electric fan motor4 4/8-pole electric fan motor4 Kit for low external temperatures with variable fan speed with

inverter4 Horizontal air supply4 Upward air supply4 Phase monitor4 Shunt capacitors (power factor > 0,9)4 CAN/MODBUS serial converter kit 4 CAN/LonWorks serial converter kit

■ 4 Master-slave operation 4 Free contacts for compressor status

■ 4 Remote control with remote microprocessor control

Key to symbols:

Data referred to the following conditions:

accessories

technical data

dimensions and clearances

(*) OPTIONAL

Guida_2011_v26.indd 97Guida_2011_v26.indd 97 22/03/11 14:4022/03/11 14:40

Page 27: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

98

WSHF-XSC 65D÷180F

SPINSAVER

EEV

R-410AH2O

WSHF-XSC 150F C(3)

EN(2)

-(1)

44

PATENTPENDING

HY

DRO

NIC

functions and features

available configurations

Monobloc unitSimultaneous and independent heating and cooling

Water cooledIndoor installationCapacity from 173 to 500 kW

SPINSAVER is the high efficiency monobloc unit for centralised systems, able to provide both simultaneous and independent heating and cooling.

SPINchiller technology offers high seasonal efficiency, using several Scroll compressors per circuit and working together with the innovative built-in automatic hydraulic switch system in SPINSAVER. In fact, hot and cold fluids are produced simultaneously in all load conditions with maximum energy recovery. The source is therefore only activated to exchange any excess energy, with considerable savings in terms of extraction circuit pumping energy. As a result, total primary energy savings can reach up to 50%.

Thanks to its effective production combination, SPINSAVER is therefore the ideal solution for civil and industrial applications with centralised “four-pipe” type installations.

Heating-Cooling Water cooled Indoor inst. Outdoor inst.(Optional)

Refrig. R-410A Herm. Scroll Electronic Expansion Valve

(1) SYSTEM TYPE:4- System with terminal units4PR System with radiant panels, induction terminal units or

chilled beams

(2) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by inserting the compressors in a soundproofed compartment.

(3) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Guida_2011_v26.indd 98Guida_2011_v26.indd 98 22/03/11 14:4022/03/11 14:40

Page 28: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

99

A1

A

A2 B1B

B2

C

65D 70D 75D 80D 85D 90D 100D 110D 115D 120D 135E 150F 165F 180F

4 kW 173 182 199 208 224 254 276 297 314 330 360 391 444 5004 kW 224 237 257 269 289 327 356 383 407 428 466 506 574 646

kW 51,4 55,2 58,4 61,8 65,1 73,4 80,1 86,8 93,3 98,4 107 116 130 148- 7,73 7,59 7,80 7,72 7,88 7,91 7,89 7,83 7,72 7,70 7,74 7,76 7,83 7,74

4 kW 212 227 243 255 272 311 341 364 385 404 443 480 539 608kW 32,6 34,8 37,9 39,9 43,6 47,4 52,2 55,7 59,6 62,4 68,2 74,6 83,6 94,4- 6,50 6,51 6,41 6,38 6,25 6,56 6,54 6,54 6,46 6,48 6,50 6,46 6,45 6,44

4 kW 224 237 257 269 289 327 356 383 407 428 466 506 574 646kW 51,4 55,2 58,4 61,8 65,1 73,4 80,1 86,8 93,3 98,4 107 116 130 148- 4,36 4,29 4,40 4,36 4,43 4,45 4,44 4,41 4,36 4,35 4,37 4,38 4,41 4,37- 2- 4 SCROLL 5 SCROLL 6 SCROLLdB(A) 73 74 74 74 74 74 76 76 76 76 76 76 77 77dB(A) 64 64 65 65 66 66 67 68 68 68 68 68 68 69V/Ph/Hz 400/3/50

65D 70D 75D 80D 85D 90D 100D 110D 115D 120D 135E 150F 165F 180F4266 4266 4266 4266 4266 4266 4266 4266 4266 4266 4723 4723 4723 4723850 850 850 850 850 850 850 850 850 850 850 850 850 850

2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 20004 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000700 700 700 700 700 700 700 700 700 700 700 700 700 700

HY

DRO

NIC

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Cooling circuit water 7/12°C; heating circuit water 45/40°C; (2) Cooling circuit water 7/12°C; source circuit water 15/25°C; (3) Heating circuit water 40/45°C; source circuit water 12/7°C;

(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions. Heating circuit water 30/35°C; Cooling circuit water 7/12°C

■ 4 Rubber antivibration mounts kit 4 Outdoor installation (only for acoustic configuration EN)4 Shut-off valve on compressor return4 High and low pressure gauges

■ 4 Steel mesh mechanical filter. To be mounted at the exchanger inlet 4 Phase monitor4 Shunt capacitors (power factor > 0,9)4 Soft Start

4 MODBUS serial converter kit 4 LonWorks serial converter kit4 BACnet serial converter kit4 Free contacts for compressor status

■ 4 Remote control microprocessor unit for repeat commands

Key to symbols:

Data referred to the following conditions:

accessories

technical data

dimensions and clearances

■ Accessories supplied separately.

SizesCOOLING 100% - HEATING 100%

Cooling capacity (1)Heating capacity (1)Total inputOverall efficiency

COOLING 100% - HEATING 0%Cooling capacity (2)Total inputEER at full load

COOLING 0% - HEATING 100%Heating capacity (3)Total inputCOP at full load

Number of refrigerant circuitsNumber and type of compressorsST Sound pressure level (4)EN Sound pressure level (4)Power supply

Guida_2011_v26.indd 99Guida_2011_v26.indd 99 22/03/11 14:4022/03/11 14:40

Page 29: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

100

WRH WRHN 102÷422

4

4

R-407CH2O

WRH-2 S(1)

CE(2)

S(4)

102 B(3)

HY

DRO

NIC

functions and features

available configurations

Water chillerWRH: cooling onlyWRHN: reversible heat pump

Water cooledIndoor installationCapacity from 27,1 to 144 kW

The water-water chillers and heat pumps with hermetic compressors in the WRH and WRHN series are water-cooled units designed for indoor installation. They may be used in modern civil and industrial service systems because of their limited overall size and low noise levels. They only require water and electrical connections, since the units are fully assembled and tested in the factory. The WRHN units are fitted with reversing valve on the refrigerant circuit, thereby considerably reducing installation and maintenance costs.

(1) VERSION:4S Standard

(2) EXCHANGER APPROVALS:4CE PED (European test)

(3) LOW TEMPERATURE:4- Not required4B Low temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -7°C inclusive.

(4) OPERATION (WRH only):4H Reversibility on water circuit

Version that allows water-water heat pump operation with reversibility on the water circuit. It is suited to civil and industrial hot water production. The external exchangers are clad with closed-cell insulating material.

Cooling only(WRH)

Heating-Cooling(WRHN)

Water cooled Indoor inst. Refrig. R-407C Herm. Scroll Water circuit reversal (WRH)

functions and features

available configurations

Guida_2011_v26.indd 100Guida_2011_v26.indd 100 22/03/11 14:4022/03/11 14:40

Page 30: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

101

102 142 162 182 202 222 242 292 322 362 422

4 kW 27,1 36,5 40,3 47,5 55,9 61,8 68,4 89,4 104 119 144kW 6,97 8,86 10,7 12,9 14,4 16,3 17,9 20,1 25,2 28,8 36,0- 3,89 4,12 3,77 3,68 3,88 3,79 3,82 4,26 4,13 4,13 4,00- 4,55 4,45 4,28 4,11 4,37 4,29 4,35 5,06 4,54 4,37 4,67

4 kW 32,4 43,6 49,2 58,1 68,0 75,4 83,2 106 125 143 176

4 kW 27,2 36,2 39,4 46,8 54,8 61,1 67,3 86,5 102 118 144kW 7,14 9,3 11,0 13,7 15,6 17,4 19,3 22,9 27,1 31,2 38,4- 3,81 3,88 3,58 3,42 3,51 3,51 3,49 3,77 3,76 3,78 3,75- 4,72 4,82 4,23 3,90 4,09 4,09 4,04 4,55 4,09 3,93 4,20

4 kW 32,1 42,7 47,3 57,2 66,4 74,0 81,5 102 123 141 173kW 9,40 12,3 14,4 18,4 20,7 23,1 25,4 27,9 32,8 37,6 46,2- 3,41 3,47 3,28 3,11 3,21 3,20 3,21 3,65 3,75 3,75 3,74l/s 1,3 1,7 1,9 2,2 2,6 2,9 3,2 4,1 4,9 5,6 6,9- 2- 2 SCROLLdB(A) 53 53 62 62 63 64 65 66 66 66 66V/Ph/Hz 400/3/50

BB2

C

B1A

A1

A2

mod

on

102 142 162 182 202 222 242 292 322 362 422802 802 802 802 802 802 802 1062 1062 1062 1062602 602 602 602 602 602 602 580 580 580 580790 790 915 915 915 915 915 1538 1538 1538 1538

4 300 300 300 300 300 300 300 300 300 300 300300 300 300 300 300 300 300 300 300 300 300500 500 500 500 500 500 500 500 500 500 500300 300 300 300 300 300 300 300 300 300 300

177 197 245 247 257 263 268 447 487 517 577

187 207 255 257 269 275 280 470 510 540 600

HY

DRO

NIC

■ Accessories supplied separately.

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7 °C; water temperature at external exchanger outlet = 30/35°C(2) Water at external exchanger inlet = 10 °C; internal exchanger waterr = 42/50 °C (sizes 102÷242);

internal exchanger water = 45/50 °C (sizes 292÷422)

(3) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

(4) Water at external exchanger inlet = 10 °C; water temperature at internal exchanger outlet 45°C

■ 4 Manifold for unit with double exchanger ■ 4 Serial communication module PC/BMS MODBUS for 1 unit

(Master) ■ 4 Serial communication module PC/BMS MODBUS from 2 to 254

units (Slave) ■ 4 Steel mesh filter on water side ■ 4 Daily and weekly programming clock ■ 4 Phase monitor

■ 4 Pressure-controlled valve ■ 4 Remote control with remote microprocessor control 4 Supply voltage 400/3/50 without neutral

WRHN 292÷422 only:4 Low water temperature source side4 Device for inrush current reduction for 400/3/50 units4 Shunt capacitors (power factor > 0,9)4 Free Contacts External Signal

Key to symbols:

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

WRHWeight in oper. kgWRHNWeight in oper. kg

dimensions and clearances

accessories

dimensions and clearances

technical data

SizesWRH

Cooling capacity (1)Total input (1)Total EER at 100%ESEERHeating capacity WRHH (2)

WRHNCooling capacity (1)Total input (1)Total EER at 100%ESEERHeating capacity (4)Total inputCOP

Water flow rate (External Exchanger) (1)Number of refrigerant circuitsNumber and type of compressorsSound pressure level (3)Power supply

Guida_2011_v26.indd 101Guida_2011_v26.indd 101 15/03/11 17:1315/03/11 17:13

Page 31: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

102

WSH-XSC 65D÷180F

SPINCHILLER

HYDROPACK

EEV

R-410AH2O

WSH-XSC D(2)

75D C(6)

B(3)

EN(4)

T(5)

-(1)

HY

DRO

NIC

functions and features

available configurations

Water chillerWater cooledIndoor/outdoor installationCapacity from 195 to 560 kW

The WSH-XSC units belong to the SPINchiller family and therefore feature high energy efficiency, self-adaptation and reliability.

4Compactness: when designing the unit special attention was paid to reducing the dimensions of the front as much as possible. The width in the units up to 560 kW capacity has been reduced to just 85 cm so that they can pass through normal doorways.

4Special attention has been paid to making connection to the service system easy so that work requiring specialised personnel is drastically reduced thereby allowing installation costs to be cut considerably. This same policy ensured that attention was paid to easiness of controls and maintenance on all the most sensitive parts.

4EFFICIENCY that increases as the heating load decreases, while guaranteeing maximum requested load when necessary. SPINchiller always ensures maximum comfort with very high efficiency and consequently considerable energy savings;

4The particular abundance of optional accessories allows customisation of the unit, also for special requirements both in the civil and technological air-conditioning sphere. In particular the optional for the HydroPack water circulating unit, consistent with the concept of modularity, has several pumps in parallel (up to 3), to monitor the system load variations better and to regulate the water flow in the critical system starting (or restarting) stages so that outside servicing is avoided.

The innovative and hi-tech features of SPINchiller give this series a much higher quality than can generally be found on the market today.These indoor water-cooled units may be combined with the dry coolers of the REM series.

Cooling only Water cooled Outdoor inst. Indoor inst. Refrig. R-410A Herm. Scroll Water circuit reversal

HydroPack Electronic Expansion Valve

(1) OPERATION:4- Standard unit (cooling only)4H Heat pump with water circuit reversal

(2) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

4R Total recoveryCarried out using braze-welded plate-type exchangers suited for 100% recovery of condensation heat for producing hot water.

(3) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.

Two versions are available:- Unit for low temperatures only- Unit with double operating set-point.

(4) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by inserting the compressors in a soundproofed compartment.

(5) APPLICATION:4T Tower water

(6) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Guida_2011_v26.indd 102Guida_2011_v26.indd 102 15/03/11 17:1315/03/11 17:13

Page 32: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

103

A1

A

A2 B1B

B2

C

65D 70D 75D 80D 85D 90D 100D 110D 115D 120D 135E 150F 165F 180F4 kW 195 207 223 234 251 286 312 334 353 371 406 440 497 560

kW 41,5 44,5 47,6 50,3 53,7 59,8 65,4 70,5 75,7 79,6 86,6 94,2 106 120- 4,70 4,65 4,68 4,65 4,67 4,78 4,77 4,74 4,66 4,66 4,69 4,67 4,69 4,67- 6,11 6,15 5,87 6,03 5,88 6,02 5,99 6,15 6,09 6,07 6,10 6,28 6,21 6,24

4 kW 224 237 257 269 289 327 356 383 407 428 466 506 574 646kW 51,2 55,0 58,2 61,6 64,9 73,2 79,9 86,6 93,1 98,2 107 115 130 147- 4,38 4,31 4,42 4,37 4,45 4,47 4,46 4,42 4,37 4,36 4,36 4,40 4,42 4,39- 2- 4 SCROLL 5 SCROLL 6 SCROLLdB(A) 73 74 74 74 74 74 76 76 76 76 76 76 77 77dB(A) 64 64 65 65 66 66 67 68 68 68 68 68 68 69V/Ph/Hz 400/3/50

65D 70D 75D 80D 85D 90D 100D 110D 115D 120D 135E 150F 165F 180F2510 2510 2510 2510 2510 2510 2510 2510 2510 2510 2976 2976 2976 2976850 850 850 850 850 850 850 850 850 850 850 850 850 850

1890 1890 1890 1890 1890 1890 1890 1890 1890 1890 1890 1890 1890 18904 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000700 700 700 700 700 700 700 700 700 700 700 700 700 700

HY

DRO

NIC

■ Accessories supplied separately.

SizesCooling capacity (1)Total input (1)EER EUROVENTESEERHeating capacity (2)Total input (2)COP

Number of refrigerant circuitsNumber and type of compressorsST Sound pressure level (3)EN Sound pressure level (3)Power supply

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; external exchanger water = 30/35°C; (2) Internal exchanger water = 12/7°C; external exchanger water = 40/45°C;

(3) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

■ 4 Rubber antivibration mounts 4 Outdoor installation4 Shut-off valve on compressor supply and return4 High and low pressure gauges4 HydroPack with 2 pumps4 Hydropack supply side with 2 pumps4 HydroPack with 2 pumps + 1 in stand-by4 Hydropack supply side with 2 pumps + 1 in stand-by4 HydroPack with 3 pumps4 Hydropack supply side with 3 pumps4 Connection set exchanger with hydronic group (supply side)4 Connection set exchanger with hydronic group (user side)4 Supply side anti-ice electric heaters for hydronic group4 User side anti-ice electric heaters for hydronic group4 Steel mesh filter on supply side 4 Steel mesh filter on user side 4 2-way modulating valve

4 Set point compensation with 0-10 V signal4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Phase monitor4 Shunt capacitors (power factor > 0,9)4 Soft Start4 CAN/MODBUS serial converter kit 4 CAN/LonWorks serial converter kit4 Data logger

■ 4 Master-slave operation 4 Free contacts for compressor status

■ 4 Remote control with remote microprocessor control

Key to symbols:

Data referred to the following conditions:

accessories

technical data

dimensions and clearances

Guida_2011_v26.indd 103Guida_2011_v26.indd 103 15/03/11 17:1415/03/11 17:14

Page 33: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

104

WDH-HE 2.220÷2.600

EEV

H2O

WDH-HE B(1)

2.300 T(3)

CE(4)

ST(2)

R-134a

Eurovent EnergyEfficiency Class

-

SCREWLINE NEW

HY

DRO

NIC

Water chillerWater cooledIndoor installationCapacity from 633 to 1711 kW

The SCREWLine WDH-HE units are water chillers with extremely high efficiency that feature:

4MORE EFFICIENCY, MORE VALUE - The innovative technology allows unbeatable efficiency both at full and at part load reaching a 12% better result compared to a A class unit. The required energy to maintain the required conditions will be consequently reduced and will increase the commercial value of the building.

4PERFECT FOR THE GREEN BUILDINGS - The extremely high efficiency values answer the requirements of the most demanding certification bodies like ECBC and LEED. The refrigerant is also Ecocompatible and its amount into the unit is much lower than most of the units available in the market especially the ones with flooded evaporator. This will allow to get more certification credits.

4RELIABLE TECHNOLOGY - The superb energetic performances derive from the use of high performances double screw compressors with economiser, electronic expansion valve and innovative shell and tube heat exchanger especially developed for the R134a refrigerant. Using two compressors allows also higher reliability, flexibility and lower inrush current.

4MORE FLEXIBILITY FOR THE APPLICATIONS - It's suitable for the different types of terminals, like fancoils, radiant systems and chilled beams and it's also available in the low temperature configuration (Brine) suitable for applications that require high dehumidification or in the industrial processes. It's also compatible with the use with different thermal sources that are widely used in the big plants like cooling towers, dry coolers and geothermal systems.

Cooling only Water cooled Indoor inst. Refrig. R-134a Twin-screw semi. Electronic Expansion Valve

(1) LOW TEMPERATURE:4- Not required4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity by shuttering the compressor depends on the working temperature.

(2) ACOUSTIC CONFIGURATION:4ST Standard

(3) ENERGY EFFICIENCY:4P Well water4T Tower water

(4) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

functions and features

available configurations

Unit listed on www.eurovent-certification.com

Guida_2011_v26.indd 104Guida_2011_v26.indd 104 15/03/11 17:1415/03/11 17:14

Page 34: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

105

2.220 2.230 2.240 2.260 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.600- -

4 kW 633 677 730 782 829 901 976 1045 1108 1226 1391 1549 1711kW 113 121 130 139 148 161 174 184 195 216 244 272 300- 5,60 5,60 5,62 5,63 5,60 5,60 5,61 5,68 5,68 5,68 5,70 5,69 5,70- 6,61 6,66 6,63 6,69 6,67 6,66 6,62 6,64 6,65 6,64 6,67 6,61 6,67dB(A) 80 80 82 82 83 83 83 82 82 82 82 82 83- 2- 2 DSWV/Ph/Hz 400/3/50

BB1

B2A

A2

C

A1

2.220 2.230 2.240 2.260 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.6004900 4900 4900 4900 4900 4900 4900 4900 4900 4900 4970 4970 49701460 1460 1460 1520 1520 1520 1520 1620 1620 1620 1620 1620 16202000 2000 2000 2090 2090 2090 2090 2240 2240 2370 2410 2410 2410700 700 700 700 700 700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700 700 700 700 700 700

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 10001400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 14004400 4450 4500 4750 4800 5100 5450 6320 6360 7000 7480 8000 8250

HY

DRO

NIC

■ Accessories supplied separately.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(*) The programme applies to air-cooled water chillers up to 600 kW and water-cooled water chillers up to 1500 kW.

(1) Internal exchanger water = 12/7°C; external exchanger water = 30/35°C;

(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions;

(3) DSW = twin-screw compressor

■ 4 Rubber antivibration mounts ■ 4 Pressure-controlled valve■ 4 Remote control with remote microprocessor control4 MODBUS serial connection module4 BACNet serial connection module4 LonWorks serial connection module4 Master-slave operation4 Soft Start

4 Set point compensation with 4-20 mA signal4 Set point compensation with 0-10 V signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Magnetothermal circuit breakers4 Shunt capacitors (power factor > 0,9)4 Switchboard ventilation

Key to symbols:

Data referred to the following conditions:

WDH-HEEurovent (*)ST Cooling capacity (1)ST Total inputST EER EUROVENTST ESEERST Sound pressure level (2)Number of refrigerant circuitsNumber and type of compressors (3)Power supply

Sizes ST Length (A) mmST Width (B) mmST Height (C) mmST (A1) mmST (A2) mmST (B1) mmST (B2) mmST Weight in oper. kg

accessories

technical data

dimensions and clearances

The above data refer to standard units.

Guida_2011_v26.indd 105Guida_2011_v26.indd 105 15/03/11 17:1415/03/11 17:14

Page 35: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

106

WDH 2.160÷2.600

EEV

H2O

WDH-3 R(2)

2.300 CE(7)

B(3)

EN(5)

T(6)

CLA(4)

R-134a

-(1)

SCREWLINE

HY

DRO

NIC

functions and features

available configurations

Water chillerWater cooledIndoor installationCapacity from 408 to 1537 kW

The experience gained by Clivet in the high-capacity chiller sector has resulted in the WDH series, with the following features:

4EFFICIENCY - Eurovent energy efficiency Class A and B thanks to the new high capacity screw compressors and to the shell-and-tube exchangers specially developed for the gas R-134a: the best compromise to boost efficiency while limiting costs. The compressors are managed with continuous adjustment of the capacity. The heat exchangers are specifically sized for best adaptation to the other parts of the refrigerant circuit. The latter is fitted with an economiser exchanger for further operating efficiency;

4SELF-ADAPTATION - New, modern and intelligent electronic control directly developed by Clivet. This customisation allows better management of all the circuit components.Continual adapting of chiller operating parameters to the load conditions of the system in which it is installed reduces consumption while the working life of the parts increases;

4STURDINESS - Load-bearing frame in enamelled hot-galvanised sheet metal with semi-hermetic double-screw compressors and shell-and-tube evaporator ensuring reliability and constant performance.

These units may be combined with the dry coolers of the REM series.

Cooling only Water cooled Indoor inst. Refrig. R-134a Twin-screw semi. Water circuit reversal (WDHH)

Electronic Expansion Valve

(1) OPERATION:4- Standard unit (cooling only)4H Heat pump with water circuit reversal

(2) ENERGY RECOVERY:4- Not required (Standard)4D Partial recovery

Carried out using tube bundle exchargers suited for recovering the desuperheating heat up to a maximum of 15% of the total unit heat.

4R Total recoveryCarried out using tube bundle exchargers suited for 100% recovery of condensation heat for producing hot water.

(3) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.- Unit for low temperatures only- Unit with double operating set-point

The possibility of reducing the cooling capacity by shuttering the compressor depends on the working temperature.

(4) ENERGY EFFICIENCY CLASS:4CLA Class "A"

Energy efficiency with EER greater than or equal to 5,05.4CLB Class "B"

Energy efficiency with EER inclusive between 4,65 and 5,05 .

(5) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by inserting the compressors in a soundproofed compartment.

(6) APPLICATION:4P Well water4T Tower water

(7) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Unit listed on www.eurovent-certification.com

Eurovent EnergyEfficiency Class(Config. CLA)

Eurovent EnergyEfficiency Class(Config. CLB)

Guida_2011_v26.indd 106Guida_2011_v26.indd 106 15/03/11 17:1415/03/11 17:14

Page 36: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

107

2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600-

4 kW 468 536 610 697 758 831 900 960 1011 1169 1209 1248 1448 1537kW 92,6 106,1 119 137 150 164 177 188 199 230 238 247 286 303- 5,05 5,05 5,14 5,07 5,05 5,08 5,07 5,09 5,07 5,08 5,07 5,06 5,06 5,08- 5,75 5,75 5,85 5,77 5,75 5,78 5,78 5,80 5,77 5,78 5,77 5,76 5,76 5,78

4 kW 548 627 727 814 892 976 1056 1131 1197 1375 1424 1472 1720 1812kW 111 126 150 168 185 203 221 236 251 285 295 305 346 380dB(A) 81 81 83 83 84 84 84 83 83 83 83 83 84 84dB(A) 72 73 74 74 75 74 74 74 75 74 73 74 77 77

BB1

B2A

A2

C

A1

2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.6003534 3534 3601 3601 3729 4061 4361 4361 4361 4657 4657 4657 4678 46783831 3831 3831 3831 4250 4336 4746 4746 4746 4746 4746 4746 4746 47461398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 14251711 1711 2018 2018 2018 2018 2018 2018 2018 2146 2146 2146 2146 21461891 1891 1891 1891 2182 2182 2182 2182 2182 2245 2245 2245 2245 2245

4 700 700 700 700 700 700 700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700 700 700 700 700 700 7001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 10001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15002926 2995 3577 3726 4122 4602 5074 5093 5112 5931 6028 6075 6118 61523254 3323 3900 4053 4463 4919 5519 5538 5557 6376 6473 6520 6563 6597

2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.6003526 3526 3534 3534 3534 3933 3894 3902 3902 3902 3902 4678 4678 46783820 3820 3831 3831 3831 4233 4233 4316 4316 4316 4316 4749 4749 47491398 1398 1398 1425 1425 1425 1425 1425 1425 1425 1425 1425 1425 14251640 1640 1871 1871 1871 1980 1980 2083 2083 2083 2083 2083 2083 21461781 1781 1891 1891 1891 2106 2106 2182 2182 2182 2182 2182 2182 2245

4 700 700 700 700 700 700 700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700 700 700 700 700 700 7001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 10001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15002576 2612 3201 3264 3304 3656 3988 4367 4377 4411 4542 5384 5393 58812808 2845 3211 3294 3308 3654 3975 4195 4206 4234 4375 5240 5245 5728

2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600

4 kW 408 455 562 620 698 773 828 903 952 993 1049 1171 1295 1458kW 87,0 97,5 119 131 148 163 178 188 197 209 224 247 272 309- 4,69 4,67 4,73 4,72 4,71 4,73 4,66 4,80 4,82 4,74 4,68 4,74 4,75 4,72- 5,55 5,52 5,60 5,58 5,56 5,59 5,51 5,68 5,70 5,60 5,53 5,60 5,62 5,58

4 kW 473 528 649 718 809 894 962 1039 1095 1148 1217 1358 1503 1692kW 108 120 147 162 185 202 219 232 244 259 276 304 338 382dB(A) 81 81 82 82 83 83 83 83 83 83 83 84 84 84dB(A) 72 73 73 73 74 75 76 76 76 76 76 76 77 77- 2- 2 DSWV/Ph/Hz 400/3/50

HY

DRO

NIC

■ Accessories supplied separately.

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(*) The programme applies to air-cooled water chillers up to 600 kW and water-cooled water chillers up to 1500 kW.

(1) Internal exchanger water = 12/7°C; external exchanger water = 30/35°C;(2) Internal exchanger water = 12/7°C; external exchanger water = 40/45°C;

(3) DSW = twin-screw compressor(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

4 Cooling only operation4 Operation with reversibility on water circuit

■ 4 Rubber antivibration mounts 4 Shut-off valve on compressor supply and return

■ 4 Pressure-controlled valve 4 Set point compensation with 0-10 mA signal4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 General isolating switch

4 Magnetothermal circuit breakers4 Soft Start4 Shunt capacitors (power factor > 0,9)4 CAN/MODBUS serial converter kit 4 CAN/LonWorks serial converter kit

■ 4 Master-slave operation 4 Free contacts for compressor status4 Free contacts for compressor status and enabling

■ 4 Remote control with remote microprocessor control

Key to symbols:

Data referred to the following conditions:

WDH-3 CLAEurovent (*)Cooling capacity (1)Total inputEER EUROVENTESEERHeating capacity (2)Total input

ST Sound pressure level (4)EN Sound pressure level (4)

WDH-3 CLAST Length (A) mmEN Length (A) mmST-EN Width (B) mmST Height (C) mmEN Height (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

ST Weight in oper. kgEN Weight in oper. kg

WDH-3 CLBST Length (A) mmEN Length (A) mmST-EN Width (B) mmST Height (C) mmEN Height (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

ST Weight in oper. kgEN Weight in oper. kg

accessories

technical data

dimensions and clearances

WDH-3 CLBEurovent (*)Cooling capacity (1)Total inputEER EUROVENTESEERHeating capacity (2)Total input

ST Sound pressure level (4)EN Sound pressure level (4)Number of refrigerant circuitsNumber and type of compressors (3)Power supply

Guida_2011_v26.indd 107Guida_2011_v26.indd 107 15/03/11 17:1415/03/11 17:14

Page 37: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

108

REM 75C÷2.440

REM 100D

H2OAIR

ST(1)

T(2)

HY

DRO

NIC

Liquid chillerAir cooledOutdoor installationCapacity from 195 to 980 kW

The REM dry coolers may be combined with all the water-cooled water coolers and are made so as to occupy the least space possible.Remote dispersal of heat into the ambient air means that noise can be transferred to where it causes least disturbance.They are available in various soundproofing configurations and with various exchanger coils for best adaptation to their surroundings.Great care has been taken over all the finishes to ensure maximum resistance to weathering even under extreme conditions of use.

Air cooled Outdoor inst. Refrig. Water

(1) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by reducing the fan speed of rotation

(2) ENERGY EFFICIENCY:4T Temperate climate (Standard)

functions and features

available configurations

Guida_2011_v26.indd 108Guida_2011_v26.indd 108 15/03/11 17:1415/03/11 17:14

Page 38: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

109

75C 75D 100D 135F 150F 2.200 2.230 2.260 2.280 2.300 2.360 2.400 2.4403250 3050 3050 4550 4550 5090 5090 5090 6200 6200 7250 7250 72501095 2195 2195 2195 2195 2326 2326 2326 2326 2326 2326 2326 23262030 1930 1930 1930 1930 1910 1910 1910 1910 1910 1910 1910 1910

4 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000700 700 700 700 700 700 700 700 700 700 700 700 7001300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 13001300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300

A

A1

A2B

B2

C

B1

75C 75D 100D 135F 150F 2.200 2.230kW 195 248 297 354 436 491 548l/s 16300 24900 23800 36650 34700 49850 49000n° 3 4 6 8dB(A) 57 58 58 60 60 61 61kW 154 203 235 299 345 402 445l/s 12000 18900 17650 27650 25700 37700 37000n° 3 4 6 8dB(A) 48 51 51 53 53 54 54V/Ph/Hz 400/3/50

2.260 2.280 2.300 2.360 2.400 2.440kW 608 686 760 816 883 980l/s 47750 60900 59300 83650 81900 79000n° 8 10 12dB(A) 61 62 62 63 63 63kW 481 555 600 683 725 790l/s 35500 45950 43950 64850 62500 60000n° 8 10 12dB(A) 54 55 55 56 56 56V/Ph/Hz 400/3/50

HY

DRO

NIC

■ Accessories supplied separately.

4 Exchanger coil in copper/aluminium with acrylic coating4 Copper/copper exchanger coil4 Service switches for enabling fans4 Fan speed control kit4 Power and control board with isolating switch

Key to symbols:

The above data refer to standard units.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Data in accordance with EN 1048 - Ethylene glycol 34% - External air temperature 25°C - Tin = 40°C - Tout = 35°C

(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10 m from the external surface of the unit in open field conditions.

SizesST Rated output (1)ST Air flow rateST Number of fansST Sound pressure level (2)EN Rated output (1)EN Air flow rateEN Number of fansEN Sound pressure level (2)Power supply

SizesST Rated output (1)ST Air flow rateST Number of fansST Sound pressure level (2)EN Rated output (1)EN Air flow rateEN Number of fansEN Sound pressure level (2)Power supply

Data referred to the following conditions:

leave free

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 109Guida_2011_v26.indd 109 15/03/11 17:1415/03/11 17:14

Page 39: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

110

ME 17÷422

+CE

ME 17S(1)

CE(2)

B(3)

R-407C

HY

DRO

NIC

functions and features

available configurations

Water chillerCondenserlessIndoor installationCapacity from 4,8 to 138 kW

The condenserless water chillers of the ME series are units designed for indoor installation to be matched with a remote condenser.These units are particularly suitable for noise-sensitive environments and for resolving problems concerning the space occupied by a packaged chillers.The condenserless water chillers in the ME series have been designed for combination with the air-cooled condensers of the CE series.

Cooling only Condenserless Indoor inst. Refrig. R-407C Herm. Scroll

(1) VERSION:4S Standard4P Pump

Includes water circulating pump, expansion tank, differential pressure switch, filling unit with pressure gauge, water side safety valve and air valve. (only sizes 17÷51)

(2) EXCHANGER APPROVALS:4CE PED (European test)

(3) LOW TEMPERATURE:4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -7°C inclusive.

Guida_2011_v26.indd 110Guida_2011_v26.indd 110 15/03/11 17:1415/03/11 17:14

Page 40: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

111

17 21 25 31 41 51 61 71 81 91 101 1214 kW 4,79 5,99 7,28 8,39 10,8 12,8 15,3 17,1 18,8 22,5 26,3 32,3

kW 1,49 1,91 2,23 2,64 3,12 3,86 4,47 5,07 5,84 7,12 8,19 10,1- 3,21 3,14 3,26 3,18 3,46 3,32 3,42 3,37 3,22 3,16 3,21 3,20- 1- 1 SCROLLdB(A) 49 49 49 49 50 50 50 50 59 59 60 62V/Ph/Hz 230/1/50 400/3/50

BB2

C

B1

A1

A

A2

BB2

C

B1

A1

A2

A

17÷121

17 21 25 31 41 51 61 71 81 91 101 121402 402 402 402 402 402 402 402 402 402 402 402487 487 487 487 602 602 602 602 602 602 602 602790 790 790 790 790 790 790 790 915 915 915 915

4 300 300 300 300 300 300 300 300 300 300 300 300300 300 300 300 300 300 300 300 300 300 300 300500 500 500 500 500 500 500 500 500 500 500 500300 300 300 300 300 300 300 300 300 300 300 30077 80 85 87 91 92 93 93 113 113 113 119

102÷422

102 142 162 182 202 222 242 292 322 362 4224 kW 25,7 34,2 37,5 45,1 52,5 58,5 64,5 82,1 96,9 113 138

kW 7,69 10,1 11,7 14,3 16,4 18,3 20,1 24,9 29,4 33,9 41,6- 3,34 3,39 3,21 3,15 3,20 3,20 3,21 3,30 3,30 3,33 3,32- 2- 2 SCROLLdB(A) 53 53 62 62 63 64 65 66 66 66 66V/Ph/Hz 400/3/50

102 142 162 182 202 222 242 292 322 362 422802 802 802 802 802 802 802 580 580 580 580602 602 602 602 602 602 602 1062 1062 1062 1062790 790 915 915 915 915 915 1538 1538 1538 1538

4 300 300 300 300 300 300 300 300 300 300 300300 300 300 300 300 300 300 300 300 300 300500 500 500 500 500 500 500 500 500 500 500300 300 300 300 300 300 300 300 300 300 300158 193 232 232 239 245 250 410 445 468 520

HY

DRO

NIC

dimensions and functional spaces

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; dew point = 50°C (2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

■ 4 Manifold for unit with double exchanger ■ 4 Serial communication module PC/BMS MODBUS for 1 unit

(Master) ■ 4 Serial communication module PC/BMS MODBUS from 2 to 254

units (Slave) ■ 4 Steel mesh filter on water side ■ 4 Daily and weekly programming clock ■ 4 Phase monitor ■ 4 Remote control with remote microprocessor control

4 Supply voltage 400/3/50 without neutral (sizes 17-21)■ 4 Liquid line solenoid valve

Data referred to the following conditions:

SizesCooling capacity (1)Total input (1)EER EUROVENT

Number of refrigerant circuitsNumber and type of compressorsSound pressure level (2)Power supply

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

accessories

technical data

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

■ Accessories supplied separately.

Key to symbols:

dimensions and clearances

SizesCooling capacity (1)Total input (1)EER EUROVENT

Number of refrigerant circuitsNumber and type of compressorsSound pressure level (2)Power supply

Guida_2011_v26.indd 111Guida_2011_v26.indd 111 15/03/11 17:1415/03/11 17:14

Page 41: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

112

CE 25÷602

CE 71

R-407CAIR

ST(1)

T(2)

HY

DRO

NIC

Remote condenserAir cooledOutdoor installationCapacity from 9,1 to 277 kW

The remote air-cooled condensers in the CE series are designed for connecting to the indoor evaporating units of the ME.They are available in three soundproofing versions: standard (ST), low noise (LN) and extra low noise (EN), to satisfy even the severest of requirements in terms of noise limits.They are fitted with axial-flow fans with open inlet and outlet, suitable for installation outdoors, with large exchange surfaces and fan speed adjustment (optional) to optimise the cooling performance of the coupled units.All the units comply with Clivet’s high quality standards and undergo severe tests during assembly.

Cooling only Air cooled Outdoor inst. Refrig. R-407C

(1) ACOUSTIC CONFIGURATION:4ST Standard4LN Silenced4EN Super Silenced

(2) FAN CONNECTION (sizes 302÷602):4S Star connection4T Delta connection

functions and features

available configurations

Guida_2011_v26.indd 112Guida_2011_v26.indd 112 15/03/11 17:1415/03/11 17:14

Page 42: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

113

25 31 41 51 61 71 91 101 121 141 161 181 2011110 1110 1110 1790 1760 1760 1840 1840 1840 2690 2690 2690 2690490 490 490 490 490 490 500 595 595 595 595 595 595585 585 585 585 590 590 735 1170 1170 1215 1215 1215 1215

4 700 700 700 700 700 700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700 700 700 700 700 700550 550 550 550 550 550 700 1100 1100 1200 1200 1200 1200550 550 550 550 550 550 700 1100 1100 1200 1200 1200 120035 40 50 60 75 80 85 110 125 150 155 190 225

A

A2C

A1

A

B1 B B2

25 31 41 51 61 71 91 101 121 141 161 181 201kW 9,10 12,1 13,5 17,3 20,2 24,2 29,7 34,5 41,3 51,5 60,0 72,7 79,5l/s 1039 961 910 1956 2538 2150 2542 3911 3707 6617 6488 6195 5981dB(A) 56 55 55 58 59 57 59 61 61 71 70 70 70kW 6,62 8,70 9,57 12,9 15,3 18,1 21,6 25,7 30,3 43,8 50,5 58,9 63,2l/s 639 606 577 1233 1614 1413 1615 2467 2343 5086 4945 4560 4337dB(A) 43 43 42 46 46 45 46 49 48 63 62 62 62kW 5,86 7,50 8,19 11,3 13,7 16,1 19,1 22,6 26,2 37,5 42,8 48,7 51,3l/s 533 497 475 1015 1362 1201 1363 2030 1923 3981 3849 3509 3290dB(A) 40 40 39 43 44 42 44 46 45 55 54 54 53n°/mm 1/450 2/450 3/450 4/450 3/630V/Ph/Hz 230/1/50V/Ph/Hz 400/3/50

302 322 402 452 502 552 602kW 110 141 158 170 213 238 277kW 95,9 119 129 149 180 195 233l/s 12271 11659 11092 18426 17517 16673 23375l/s 9539 8938 8407 14330 13435 12643 17932dB(A) 74 74 74 76 76 76 77dB(A) 67 67 67 69 69 69 70kW 93,7 118 128 145 177 193 229kW 84,7 103 110 132 155 165 201l/s 9167 8733 8323 13765 13119 12510 17506l/s 7720 7224 6789 11597 10858 10161 14493dB(A) 67 67 67 69 69 69 70dB(A) 62 62 62 64 64 64 65kW 71,1 84,6 88,4 111 127 133 166kW 59,7 68,5 70,6 93,0 103 106 138l/s 5843 5507 5199 8776 8276 7818 11045l/s 4518 4201 3932 6789 6316 5914 8430dB(A) 58 58 58 60 60 60 61dB(A) 52 52 52 54 54 54 55n°/mm 2/800 3/800 4/800V/Ph/Hz 400/3/50

302 322 402 452 502 552 6023097 3097 3097 4407 4407 4407 5717820 820 820 820 820 820 8201495 1495 1495 1495 1495 1495 1495

4 700 700 700 700 700 700 700700 700 700 700 700 700 7001450 1450 1450 1450 1450 1450 14501450 1450 1450 1450 1450 1450 1450303 336 368 427 475 523 617

HY

DRO

NIC

■ Accessories supplied separately.

4 Condenser coil in copper/copper4 Condenser coil with double circuit

■ 4 Mounts for horizontal condenser coil installation4 Fan switch (sizes 302÷602)

■ 4 Liquid receiver kit ■ 4 Low temperature liquid receiver kit 4 Low external air temperature pressure-switch device4 Sub-cooling circuit

4 General isolating switch (sizes 25÷201)■ 4 Packing in wooden case

Key to symbols:

The above data refer to vertical coil version with horizontal airflow.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

SizesST Rated output (1)ST Air flow rateST Sound pressure level (2)LN Rated output (1)LN Air flow rateLN Sound pressure level (2)EN Rated output (1)EN Air flow rateEN Sound pressure level (2)Number and diameter of fansST/LN Power supplyEN Power supply

(1) Fresh air 35°C - Dew point 52,5°C(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

Data referred to the following conditions:

Sizes

ST Rated output (1)∆Y

ST Air flow rate∆Y

ST Sound pressure level (2)∆Y

LN Rated output (1)∆Y

LN Air flow rate∆Y

LN Sound pressure level (2)∆Y

EN Rated output (1)∆Y

EN Air flow rate∆Y

EN Sound pressure level (2)∆Y

Number and diameter of fansPower supply

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 113Guida_2011_v26.indd 113 15/03/11 17:1415/03/11 17:14

Page 43: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

114

MSE-SC 65D÷180F

SPINCHILLER

CEM

+

MSE-SC D(1)

100D CE(5)

EEVHYDROPACKR-407C

B(2)

T(4)

EN(3)

HY

DRO

NIC

functions and features

available configurations

The MSE-SC units belong to the SPINchiller family and therefore feature high energy efficiency, self-adaptation and reliability.They are conderserless units that may be combined with the remote condensers of the CEM series. Thanks to indoor installation and remote dispersal of heat into the ambient air, the noise may be transferred to where it causes less disturbance.

4Compactness: the width in the units up to 500 kW capacity has been reduced to just 85 cm so that they can pass through normal doorways.

4Easy connection to the service system plus a simple control system and easy maintenance drastically reduce work requiring specialised personnel and therefore installation costs.

4EFFICIENCY that increases as the heating load decreases, while guaranteeing maximum requested load when necessary.

4The particular abundance of optional accessories allows customisation of the unit, also for special requirements both in the civil and technological air-conditioning sphere. In particular the optional for the HydroPack water circulating unit, consistent with the concept of modularity, has several pumps in parallel (up to 3), to monitor the system load variations better.

The innovative and hi-tech features of SPINchiller give this series a much higher quality than can generally be found on the market today.

Water chillerCondenserlessIndoor/outdoor installationCapacity from 174 to 487 kW

(1) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

(2) LOW TEMPERATURE:4- Not required4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -7°C inclusive.Two versions are available:- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity by shuttering the compressor depends on the working temperature.

(3) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by inserting the compressors in a soundproofed compartment.

(4) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(5) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Cooling only Condenserless Indoor inst. Refrig. R-407C Herm. Scroll HydroPack Electronic Expansion Valve

Guida_2011_v26.indd 114Guida_2011_v26.indd 114 15/03/11 17:1415/03/11 17:14

Page 44: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

115

A1

A

A2 B1B

B2

C

65D 70D 75C 75D 80D 90C 90D 100D 110D 120D 135F 150F 165F 180F 4 kW 174 184 205 196 206 248 238 271 305 332 360 405 447 487

kW 55,1 58,0 60,9 60,8 63,7 75,9 72,4 81,1 91 101 109 122 137 152- 3,15 3,17 3,37 3,22 3,23 3,27 3,28 3,34 3,34 3,27 3,32 3,33 3,27 3,21dB(A) 72 73 76 74 75 76 76 76 76 76 78 79 80 80dB(A) 67 67 70 68 69 71 70 71 71 70 72 73 74 74- 2 1 2 1 2- 4 SCROLL 3 SCROLL 4 SCROLL 3 SCROLL 4 SCROLL 6 SCROLLV/Ph/Hz 400/3/50

65D 70D 75C 75D 80D 90C 90D 100D 110D 120D 135F 150F 165F 180F2510 2510 2626 2510 2510 2626 2510 2510 2510 2510 2976 2976 2976 2976850 85 0 850 850 850 850 850 850 850 850 850 850 850 850

1876 1876 1876 1876 1876 1876 1876 1876 1876 1876 1876 1876 1876 18764 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000700 700 700 700 700 700 700 700 700 700 700 700 700 700

1172 1235 1169 1310 1363 1169 1478 1576 1576 1576 2070 2241 2241 22411253 1316 1264 1391 1445 1264 1560 1658 1658 1658 2212 2382 2382 2382

HY

DRO

NIC

■ Accessories supplied separately.

4 Connection to CEM remote condensers■ 4 Rubber antivibration mounts 4 Outdoor installation4 Shut-off valve on compressor supply and return4 High and low pressure gauges4 HydroPack with 2 pumps4 HydroPack with 2 pumps + 1 in stand-by4 HydroPack with 3 pumps

■ 4 Steel mesh filter on user side4 User side anti-ice electric heaters for hydronic group4 Connection set exchanger with hydronic group (user side)4 Set point compensation with 4-20 mA signal

4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 Phase monitor4 Shunt capacitors (power factor > 0,9)4 CAN/MODBUS serial converter kit 4 CAN/LonWorks serial converter kit

■ 4 Master-slave operation 4 Free contacts for compressor status

■ 4 Remote control with remote microprocessor control

Key to symbols:

SizesST/EN Cooling capacity (1)ST/EN Total inputST/EN EER EUROVENTST Sound pressure level (2)EN Sound pressure level (2)Number of refrigerant circuitsNumber and type of compressorsPower supply

(1) Internal exchanger water = 12/7°C; condensing temperature = 50°C (2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

ST Weight in oper. kgEN Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

technical data

dimensions and clearances

Guida_2011_v26.indd 115Guida_2011_v26.indd 115 15/03/11 17:1415/03/11 17:14

Page 45: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

116

MDE 2.160÷2.600

+

CEM

MDE-3 D(1)

2.420 CE(5)

EEV

B(2)

T(4)

EN(3)

R-134a

SCREWLINE

HY

DRO

NIC

functions and features

available configurations

Water chillerCondenserlessIndoor installationCapacity from 439 to 1385 kW

(1) ENERGY RECOVERY:4- Not required4D Partial recovery

Carried out using tube bundle exchargers suited for recovering the desuperheating heat up to a maximum of 20% of the total unit heat.

(2) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -7°C inclusive.Two versions are available- Unit for low temperatures only- Unit with double operating set-point The possibility of reducing the cooling capacity by shuttering the compressor depends on the working temperature.

(3) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by inserting the compressors in a soundproofed compartment.

(4) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(5) EXCHANGER APPROVALS:4CE PED (European test)4C Clivet (In-house test)

Cooling only Condenserless Indoor inst. Refrig. R-134a Twin-screw semi. Electronic Expansion Valve

The liquid chillers in the MDE range are units for indoor installation and are ideal in combination with the remote condensers in the CEM range. They are particularly suited in civil and industrial sector systems in the following applications:

4Buildings with architectural value - The chiller is normally installed in a service room and therefore completely concealed from sight, whereas the outdoor exchange section can be positioned remotely.

4Extremely low noise emission - Separated from the chiller, the outdoor exchange section can be selected and sized as required to reduce noise emission.

4Particularly severe climates - The two section solution makes it possible to avoid having an outdoor water system and therefore having to perform the winter emptying needed to protect it against freezing. With MDE, the pipes between the two sections contain a refrigerant fluid and not water.

The energy efficiency of the entire range is particularly high: all sizes use two compact two screw semi-hermetic compressors with continuous adjustment of the supplied cooling capacity. The shell and tube evaporators are specifically optimised to operate with ecological R134a refrigerant fluid and are provided with a standard electronic expansion valve.The MDE units are supplied standard with a double acting economiser, which further improves performance levels: The refrigerant supercooling involves greater cooling capacity, and injecting the refrigerant in a gaseous state into the compressor involves lower consumption.

Guida_2011_v26.indd 116Guida_2011_v26.indd 116 15/03/11 17:1415/03/11 17:14

Page 46: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

117

2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.600kW 439 469 559 614 698 770 835 879 923 974 1002 1148 1262 1385kW 131 137 162 176 198 219 239 251 263 276 286 326 358 401- 3,35 3,42 3,45 3,49 3,53 3,52 3,49 3,50 3,51 3,53 3,50 3,52 3,53 3,45- 2- 2 DSWdB(A) 81 81 83 83 84 84 84 83 83 83 83 83 84 84dB(A) 72 73 74 74 75 74 74 74 75 74 73 74 77 77V/Ph/Hz 400/3/50

BB1

B2A

A2

C

A1

2.160 2.180 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.420 2.450 2.480 2.540 2.6003709 3579 3840 3690 3690 4071 4075 4075 4075 4075 4075 4694 4694 46941244 1244 1244 1271 1271 1244 1271 1271 1271 1271 1271 1271 1271 12711485 1485 1485 1617 1617 1617 1617 1617 1617 1617 1617 1690 1690 1690

4 700 700 700 700 700 700 700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700 700 700 700 700 700 700700 700 700 700 700 700 700 700 700 700 700 700 700 7001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15002240 2290 2829 2885 2905 3596 3909 3994 3992 4012 4122 5157 5197 52772469 2581 3105 3161 3181 3922 4248 4320 4320 4340 4408 5644 5684 5764

HY

DRO

NIC

■ Accessories supplied separately.

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Internal exchanger water = 12/7°C; condensing temperature = 50°C;(2) DSW = twin-screw compressor

(3) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

4 Connection to CEM remote condensers■ 4 Rubber antivibration mounts 4 Shut-off valve on compressor supply and return4 Set point compensation with 4-20 mA signal4 Set point compensation with fresh air sensor4 Set point compensation with according to outdoor enthalpy4 General isolating switch4 Magnetothermal circuit breakers4 Shunt capacitors (power factor > 0,9)

4 CAN/MODBUS serial converter kit4 CAN/LonWorks serial converter kit

■ 4 Master-slave operation 4 Free contacts for compressor status4 Free contacts for compressor status and enabling

■ 4 Remote control with remote microprocessor control

Key to symbols:

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

ST Weight in oper. kgEN Weight in oper. kg

accessories

technical data

dimensions and clearances

SizesCooling capacity (1)Total inputEER EUROVENT

Number of refrigerant circuitsNumber and type of compressors (2)ST Sound pressure level (3)EN Sound pressure level (3)Power supply

Guida_2011_v26.indd 117Guida_2011_v26.indd 117 15/03/11 17:1415/03/11 17:14

Page 47: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

118

CEM 75C÷2.440

CEM 100D

AIR

T(2)

ST(1)

C(3)

HY

DRO

NIC

Remote condenserAir cooledOutdoor installationCapacity from 250 to 1200 kW

The CEM remote condensers may be combined with all the remote condenser liquid chillers and are made so as to occupy the least space possible.Remote condensation means that noise can be transferred to where it causes least disturbance, thereby achieving a highly appreciable working wellbeing.They are available in various soundproofing configurations and with various exchanger coils for best adaptation to their surroundings.Use of the condensation control gives the CEM remote condensers, latent load permitting, the extra possibility of obtaining considerably lower noise levels than a packaged chiller.Great care has been taken over all the finishes to ensure maximum resistance to weathering even under extreme conditions of use.

Air cooled Outdoor inst.

(1) ACOUSTIC CONFIGURATION:4ST Standard4EN Super Silenced

This set-up is obtained by reducing the fan speed of rotation.

(2) ENERGY EFFICIENCY:4T Temperate climate (Standard)

(3) EXCHANGER APPROVALS:4CE PED (European test)4C CLIVET (In-house test)

functions and features

available configurations

Cooling only

Guida_2011_v26.indd 118Guida_2011_v26.indd 118 15/03/11 17:1415/03/11 17:14

Page 48: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

119

75C 65D 90D 100D 105F 120F 135F 150F 2.230 2.280 2.300 2.400 2.4403250 2950 2950 2950 4250 4250 4250 4250 4880 5900 5900 7050 70501095 2195 2195 2195 2195 2195 2195 2195 2326 2326 2326 2326 23262030 1930 1930 1930 1930 1930 1930 1930 1910 1910 1910 1910 1910

4 700 700 700 700 700 700 700 700 700 700 700 700 7001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 10001300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 13001300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300

A

A1

A2B

B2

C

B1

75C 65D 90D 100D 105F 120F 135FkW 250 280 332 380 410 495 576l/s 16100 25800 24600 23500 38800 37000 35300n° 3 4 6dB(A) 57 58 58 58 60 60 60kW 200 240 276 308 350 412 462l/s 12200 19350 18450 18000 28900 27600 26400n° 3 4 6dB(A) 48 51 51 51 53 53 53V/Ph/Hz 400/3/50

150F 2.230 2.280 2.300 2.400 2.440kW 650 770 834 990 1070 1200l/s 43800 55700 57800 54200 80000 77900n° 8 10 12dB(A) 61 61 62 62 63 63kW 524 620 678 786 890 1000l/s 32700 41600 43200 40500 59750 58200n° 8 10 12dB(A) 54 54 55 55 56 56V/Ph/Hz 400/3/50

HY

DRO

NIC

■ Accessories supplied separately.

4 Condenser coil in copper/aluminium with acrylic coating4 Condenser coil in copper/copper4 Service switches for enabling fans4 Kit for low external temperatures with variable fan speed (1 gas

circuit)4 Kit for low external temperatures with variable fan speed (2 gas

circuits)4 Power and control board with isolating switch (1 gas circuit)

4 Power and control board with isolating switch (2 gas circuits)4 Single gas circuit

Key to symbols:

The above data refer to standard units.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

SizesST Rated output (1)ST Air flow rateST Number of fansST Sound pressure level (2)EN Rated output (1)EN Air flow rateEN Number of fansEN Sound pressure level (2)Power supply

SizesST Rated output (1)ST Air flow rateST Number of fansST Sound pressure level (2)EN Rated output (1)EN Air flow rateEN Number of fansEN Sound pressure level (2)Power supply

(1) Fresh air 30°C - Dew point 45°C(2) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

10 m from the external surface of the unit in open field conditions.

leave free

Data referred to the following conditions:

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 119Guida_2011_v26.indd 119 15/03/11 17:1415/03/11 17:14

Page 49: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

120

GPA M0÷M9

GPA -(1)

1(2)

150(3)

H2O

HY

DRO

NIC

Pumping unitWith storage tankIndoor (GPA 65)/outdoor (GPA 150) installationCapacity from 0,3 to 0,9 kW

The GPA pumping units are designed for connection to Clivet units for producing chilled or hot water. They come complete with all the necessary electrical and water components for trouble-free operation of the system.

The performance range of the installed centrifugal pumps makes the units suitable for all types of service systems.The units may be used on systems with primary and secondary circuit.

(1) PUMP CAPACITY:4- M0, M1, M2, M3, M4, M5, M6, M7, M8, M9

(2) No. PUMPS:41 Single pump (Always)

(3) STORAGE TANK CAPACITY:4150 from 65 to 150 litres

Indoor inst.(GPA 65)

Outdoor inst.(GPA 65)

Refrig. Water

available configurations

functions and features

Guida_2011_v26.indd 120Guida_2011_v26.indd 120 15/03/11 17:1515/03/11 17:15

Page 50: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

121

BB2

C

C1

B1A

A1A2

BB2

C

C1

B1A

A1

A2

GPA 65

M0 M1 M2 M3 M4 M5 M6 M7 M8 M9470600790

4 6006007001000600140

GPA 150

M0 M1 M2 M3 M4 M5 M6 M7 M8 M96007901186

4 600600600600600240

M0 M1 M2 M3 M4 M5 M6 M7 M8 M9

kW 0,30 0,45 0,30 0,45 0,55 0,75 0,45 0,55 0,75 0,90A 0,80 1,20 0,80 1,20 1,50 2,00 1,20 1,50 2,00 2,40

L 8kPa 800kPa 150kPa 600V/Ph/Hz 400/3/50

L 65

L 150

HY

DRO

NIC

dimensions and functional spaces

■ Accessories supplied separately.

The above data refer to standard units.CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances

in green.

4 65-litre tank capacity4 150-litre tank capacity

■ 4 Hose kit 0,8 m ■ 4 Hose kit 1,5 m ■ 4 Hose kit 2,0 m■ 4 Ball valve kit for connection to the system 4 Set-up for operation as primary circuit and fittings for secondary

circuitKey to symbols:

GPA 65 Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm(C1) mm

Weight in oper. kg

GPA 150 Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm(C1) mm

Weight in oper. kg

accessories

technical data

Sizes2-pole electric pump

Rated outputRated absorbed current

Expansion tankCapacityMaximum pressureStandard pressure

Safety valve calibrationPower supplyGPA 65Storage tank capacityGPA 150Storage tank capacity

dimensions and clearances

Guida_2011_v26.indd 121Guida_2011_v26.indd 121 15/03/11 17:1515/03/11 17:15

Page 51: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

122

GP1 GP2 00÷12

GP 1(1)

00(2)

300(4)

H2O

1(3)

HY

DRO

NIC

functions and features

available configurations

GP1Pumping unit to be combined with our units for the production of chilled or hot water, complete with all the indispensable water and electrical parts for correct operation of a central water plant.

GP2These differ from the GP1 because, in addition to the pumping and control functions, they also provide for water storage.The capacity of the tanks is 300 - 500 - 2x300 - 2x500 litres.

Pumping unitWith storage tankOutdoor installationCapacity from 0,5 to 2,6 kW

(1) STORAGE TANK:41 Without storage tank42 With storage tank

(2) PUMP CAPACITY:400 From 00 to 12

(3) No. PUMPS:41 Single pump42 Double pump

(4) STORAGE TANK CAPACITY:4300 From 300 to 1000 litres

Outdoor inst. Refrig. Water

Guida_2011_v26.indd 122Guida_2011_v26.indd 122 15/03/11 17:1515/03/11 17:15

Page 52: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

123

BB2

C

C1

B1A

A1

A2

00 1 2 3 4 5 6 7 8 9 10 11 12

kW 0,50 0,60 0,90 1,10 0,80 1,20 1,10 1,50 2,00 2,30 1,50 2,10 2,60A 0,80 1,10 1,80 2,00 1,60 2,20 2,00 2,80 3,60 4,40 2,80 3,60 4,50

L 12 x GP1 16 x GP2 (300L - 500L) 24 x GP2 (600L) 32 x GP2 (1000L)kPa 800kPa 150L 300 - 500 - 600 - 1000kPa 600V/Ph/Hz 400/3/50

00 1 2 3 4 5 6 7 8 9 10 11 12616 (GP1.1 - GP1.2) 831 (GP2.1 - 300-500) 1356 (GP2.2 - 600-1000)514 (GP1.1 - GP1.2) 831 (GP2.1 - 300-500) 867 (GP2.2 - 600-1000)

1299 (GP1.1 - GP1.2) 1502 (300) 2225 (500) 1502 (600) 2225 (1000)4 300 (GP1) 600 (GP2)

600600600500

70

130xGP2 (300) 170xGP2 (500) 205xGP2 (600) 260xGP2 (1000)

HY

DRO

NIC

dimensions and functional spaces

■ Accessories supplied separately.

■ 4 Hose kit 1,5 m (1 exchanger x 1”) ■ 4 Hose kit 1,5 m (2 exchanger x 1”) ■ 4 Hose kit 1,5 m (1 exchanger x 2”-2”1/2) 4 Supply voltage 400/3/50+N

Only GP1:4 One pump4 Two pumps

Only GP2:4 Storage tank 300 litres 1 Pump4 Storage tank 300 litres 2 Pumps4 Storage tank 500 litres 1 Pump4 Storage tank 500 litres 2 Pumps4 Storage tank 600 litres 1 Pump

4 Storage tank 600 litres 2 Pumps4 Storage tank 1000 litres 1 Pump4 Storage tank 1000 litres 2 Pumps4 Three-way valve kit for storage tank from 300 litres to 500 litres4 Three-way valve kit for storage tank from 600 litres to 1000 litres4 8 kW Add. el. heater for storage tank from 300 litres to 500 litres4 8 kW Add. el. heater for storage tank from 600 litres to 1000 litres4 12 kW Add. el. heater for storage tank from 300 litres to 500 litres4 12 kW Add. el. heater for storage tank from 600 litres to 1000 litres4 16 kW Add. el. heater for storage tank from 600 litres to 1000 litres4 24 kW Add. el. heater for storage tank from 600 litres to 1000 litres

Key to symbols:

GP1 GP22-pole electric pump

Rated outputRated absorbed current

Expansion tankCapacityMaximum pressureStandard pressure

Storage tank capacity (GP2)Safety valve calibrationPower supply

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm(C1) mm

GP1Weight in oper. kgGP2Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

technical data

dimensions and clearances

Guida_2011_v26.indd 123Guida_2011_v26.indd 123 15/03/11 17:1515/03/11 17:15

Page 53: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

124

GP7 60÷63

GP7 S(1)

60(2)

1(4)

H2O

2(3)

HY

DRO

NIC

functions and features

available configurations

Pumping unitWith storage tankOutdoor installationCapacity from 1,5 to 4 kW

Pumping units with storage tank to be combined with units for the production of chilled or hot water, complete with the indispensable water and electrical parts for correct operation of the system. They have been designed for connection to our medium power units and come with steel tanks with a capacity of 2 x 300 and 2 x 500 litres.The range of capacity and head of the pumps makes these units suited to many types of systems.

Outdoor inst. Refrig. Water

(1) VERSION:4S Standard

(2) PUMP TYPE:4CE 60, 61, 62, 63

(3) No. PUMPS:41 Single pump42 Double pump

(4) STORAGE TANK CAPACITY:41 600 litres42 1000 litres

Guida_2011_v26.indd 124Guida_2011_v26.indd 124 15/03/11 17:1515/03/11 17:15

Page 54: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

125

AA2

C

C1

A1B

B1

B2

60 61 62 63

kW 1,50 2,20 3,00 4,00A 3,60 4,90 6,50 8,50

L 24 (600L) 32 (1000L)kPa 800kPa 150L 600 1000kPa 600V/Ph/Hz 400/3/50

60 61 62 631355911

1505 x (600L) 2225 x (1000L)4 600

600300600500

1355 1360 1390 1395

HY

DRO

NIC

dimensions and functional spaces

■ Accessories supplied separately.

4 600-litre tank capacity4 1000-litre tank capacity4 12 kW additional electric heaters4 8 kW additional electric heaters4 Water side protection differential pressure switch

Key to symbols:

GP72-pole electric pump

Rated outputRated absorbed current

Expansion tankCapacityMaximum pressureStandard pressure

Storage tank capacitySafety valve calibrationPower supply

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm(C1) mm

Weight in oper. kgThe above data refer to pumping units with 2 operating pumps and 1000 l storage tank.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

technical data

dimensions and clearances

Guida_2011_v26.indd 125Guida_2011_v26.indd 125 15/03/11 17:1515/03/11 17:15

Page 55: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

126

GPM 60÷99

GPM S(1)

60(2)

1(5)

H2O

2(3)

A(4)

HY

DRO

NIC

functions and features

available configurations

The GPM pumping units are modular and designed for connection to units for the production of chilled or hot water.They come complete with all the indispensable electrical and water components for correct operation of the system.They have been designed for connection to our high power units and may be supplied either separately or integrated into the structure of the chillers with semi-hermetic compressors.The range of capacity and head of the pumps makes these units suited to many types of systems, also thanks to the possibility of having a primary or primary/secondary circuit.The GPM units are factory assembled and tested and are ready for operation as soon as they are connected to the electricity and water supplies.

Pumping unitWith storage tankIndoor/outdoor installationCapacity from 1,5 to 11 kW

Indoor inst. Outdoor inst. Refrig. Water

(1) VERSION:4S Standard4P Primary/secondary

(2) PUMP TYPE

(3) No. PUMPS:41 Single pump42 Double pump

(4) SET-UP:4A Packaged (separate)4M Packaged with unit

(5) Packaged with unit:41 1200 litres42 2400 litres

Guida_2011_v26.indd 126Guida_2011_v26.indd 126 15/03/11 17:1515/03/11 17:15

Page 56: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

127

60 61 62 63 68 69 70 71 78 79 802040126025202113

4 700700700700

1902 1906 1915 1924 1926 1922 1932 1960 1976 1978 20243804 3812 3830 3848 3852 3844 3864 3920 3952 3956 4048

B

B2

C

B1

A

A1

A2

83 85 87 90 91 92 93 94 98 992040126025202113

4 700700700700

1929 1945 1964 1954 1954 1983 2048 2060 2068 20703858 3890 3928 3908 3908 3966 4096 4120 4136 4140

60 61 62 63 68 69 70 71 78 79 80- 2

kW 1,5 2,2 3,0 4,0 2,2 3,0 4,0 5,5 5,5 7,5 11,0A 3,6 4,9 6,5 8,5 4,9 6,5 8,5 11,5 11,5 15,5 22,0

L 74kPa 800kPa 150L 1200 (2400 optional)kPa 600V/Ph/Hz 400/3/50

83 85 87 90 91 92 93 94 98 99- 4

kW 0,8 1,5 2,2 1,1 1,5 2,2 4,0 5,5 5,5 7,5A 2,1 3,6 5,2 2,8 3,6 5,2 8,7 12,4 12,4 15,8

L 74kPa 800kPa 150L 1200 (2400 optional)kPa 600V/Ph/Hz 400/3/50

HY

DRO

NIC

■ Accessories supplied separately.

The above data refer to standard units.

4 Water side differential pressure switch4 Silenced 4-pole pumps4 2 kW anti-ice electric heater with safety thermostat

■ 4 Shut-off valves for connection to the system (P version only)

Key to symbols:

GPM Length (A) mm

1200L Width (B) mm2400L Width (B) mm

Height (C) mm(A1) mm(A2) mm(B1) mm(B2) mm

1200L Weight in oper. kg2400L Weight in oper. kg

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

GPM Length (A) mm

1200L Width (B) mm2400L Width (B) mm

Height (C) mm(A1) mm(A2) mm(B1) mm(B2) mm

1200L Weight in oper. kg2400L Weight in oper. kg

accessories

technical data

GPMNo polesElectric pump

Rated outputRated absorbed current

Expansion tankCapacityMaximum pressureStandard pressure

Storage tank capacitySafety valve calibrationPower supply

dimensions and clearances

GPMNo polesElectric pump

Rated outputRated absorbed current

Expansion tankCapacityMaximum pressureStandard pressure

Storage tank capacitySafety valve calibrationPower supply

Guida_2011_v26.indd 127Guida_2011_v26.indd 127 15/03/11 17:1515/03/11 17:15

Page 57: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

128

ELFOSPACE OUT-V e OUT-H 3÷31

ELFOSPACE

ELFOSPACE OUT-H

H2O

-(6)

3 R3(1)

TR(2)

-(3)

SX(4)

-(5)

OUT-H

OUT-V

ELFOSPACE OUT-V -(6)

3 R3(1)

TR(2)

-(3)

SX(4)

-(5)

-(7)

-(7)

HY

DRO

NIC

ELFOSpace OUT is the cased water terminal for use in the commercial sector.Muted lines that blend in with any decor.The available controls are simple and user-friendly, satisfying the most varied of requirements, with top-of-the-range electronic control designed for connection to the ELFOControl or general supervisors.Low noise operation and easy to clean.These are the concepts behind the development of ELFOSpace, the last generation room terminal unit that is ideal for any installation.Ten sizes available with an almost countless number of accessories for resolving any service application requirement.The ELFOSpace OUT-V series has been designed specifically for cased vertical installation and the ELFOSpace OUT-H range for cased horizontal installation.

Water terminal unitCased vertical and horizontal indoor installationCapacity from 1,5 to 9 kW

Heating-Cooling Indoor inst. Cased vertical inst. (OUT-V)

Cased horizontal inst. (OUT-H)

Refrig. Water ELFOControl

(1) AIR RETURN:4R3 Return from below (Standard)4RP Rear return

(2) CONTROLS:4TR Fan terminal block (Standard)4TRM Terminal block with minimum safety thermostat4CTS Clivet.Talk.Terminal Space electronics4CTR Clivet.Talk.Terminal Room electronics

(3) WATER COIL / ELECTRIC HEATER:4- Not required (Standard)4B14T 1-row additional coil for 4-pipe syst. (sizes 3,7,11,17,25)4RE With electric heater

(4) WATER FITTINGS:4SX Left-hand fittings (Standard)4DX Right-hand fittings

(5) VALVES:

4- Not required (Standard)4KBI2 2-pipe system water balancing kit42V2 2-way on/off valve 2-pipe system43V2 3-way on/off valve 2-pipe system410V2 3-way 0-10V valve 2-pipe system4KBI4 4-pipe system water balancing kit (sizes 3,7,11,17,25)42V4 2-way on/off valve 4-pipe system (sizes 3,7,11,17,25)43V4 3-way on/off valve 4-pipe system (sizes 3,7,11,17,25)410V4 3-way 0-10V valve 4-pipe system (sizes 3,7,11,17,25)

(6) ADDITIONAL TRAY:4- Not required (Standard)4BRODX With additional tray r.h. water fittings4BROSX With additional tray l.h. water fittings

(7) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

Necessary configuration strings for supplying the unit with the indicated elements/accessories already mounted on the appliance.Certain accessories may also be supplied separately, as indicated in the “accessories supplied separately” list.

References for position of fittings:- vertical fan coils: right and left defined by standing in front of the appliance;- horizontal fan coils: right and left defined by standing in the airflow (with the air

blowing on your face).

(1) AIR RETURN:4R3 Return from below (Standard)4RF Front return

(2) CONTROLS:4TR Fan terminal block (Standard)4TRM Terminal block with minimum safety thermostat4HID-F1 3-speed selector + on/off4HID-F2 Bulb thermostat4HID-F3 Bulb thermostat with remote S/W4HID-F4 Bulb thermostat with minimum safety thermostat4HID-F5 Bulb thermostat with electric heater control4HID-F6 Electronic multifunction room thermostat4CTS Clivet.Talk.Terminal Space electronics4CTRD Clivet.Talk.Terminal Room electronics with unit on-board

display(3) WATER COIL / ELECTRIC HEATER:

4- Not required (Standard)4B14T 1-row additional coil for 4-pipe syst. (sizes 3,7,11,17,25)4RE With electric heater

(4) WATER FITTINGS:4SX Left-hand fittings (Standard)4DX Right-hand fittings

(5) VALVES:4- Not required (Standard)4KBI2 2-pipe system water balancing kit42V2 2-way on/off valve 2-pipe system43V2 3-way on/off valve 2-pipe system410V2 3-way 0-10V valve 2-pipe system4KBI4 4-pipe system water balancing kit (sizes 3,7,11,17,25)42V4 2-way on/off valve 4-pipe system (sizes 3,7,11,17,25)43V4 3-way on/off valve 4-pipe system (sizes 3,7,11,17,25)410V4 3-way 0-10V valve 4-pipe system (sizes 3,7,11,17,25)

(6) ADDITIONAL TRAY:4- Not required (Standard)4BRV With additional tray

(7) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

functions and features

available configurations

Guida_2011_v26.indd 128Guida_2011_v26.indd 128 15/03/11 17:1515/03/11 17:15

Page 58: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

129

3 5 7 9 11 15 17 21 25 314 kW 1,51 1,96 2,54 3,03 3,73 4,21 5,49 6,37 7,44 9,03

kW 1,18 1,43 1,89 2,14 2,71 3,02 4,00 4,49 5,13 6,16kW 0,05 0,05 0,07 0,07 0,09 0,09 0,12 0,12 0,14 0,14

4 kW 3,65 4,24 5,51 6,08 7,74 8,69 11,5 12,7 14,3 17,1l/s 97,2 100 120 124 180 185 271 279 398 409- CFGdB(A) 34 - 40 - 44 35 - 41 - 46 35 - 42 - 47 38 - 44 - 49 42 - 49 - 54V/Ph/Hz 230/1/50

3 5 7 9 11 15 17 21 25 31670 670 870 870 1070 1070 1270 1270 1470 1470220 220 220 220 220 220 220 220 220 220470 470 470 470 470 470 470 470 470 470

4 20 20 20 20 20 20 20 20 20 2020 20 20 20 20 20 20 20 20 20250 250 250 250 250 250 250 250 250 25090 90 90 90 90 90 90 90 90 9014 14 16 17 23 24 26 28 30 32

A

A1

A2

B B1

A

A1

A2

CC1

B

C

C1

ELFOSpace OUT-V

ELFOSpace OUT-H

HY

DRO

NIC

■ Accessories supplied separately.

■ 4 HID-E1 3-speed selector + on/off for wall mounting ■ 4 HID-E2 Simplified room control E/I+3V+on/off for wall mounting ■ 4 HID-E3 Multi-function room control for wall mounting ■ 4 HID-E4 Multi-function room control for 0-10V valves ■ 4 Minimum hot water temperature thermostat ■ 4 Remote air sensor for HID-E2, HID-E3 and HID-E4 ■ 4 Control device for several units with single room control■ 4 HID-T2 electronic room control■ 4 HID-TI2 flush-mounted electronic ambient control ■ 4 HID-T3 electronic room control with humidity sensor■ 4 RS485 remote communication serial port ■ 4 2-pipe water balancing kit = ball valve+balancing valve ■ 4 4-pipe water balancing kit = 2 ball valves + 2 balancing valves

(sizes 3-7-11-17-25)■ 4 2-way ON/OFF valve kit for 2-pipe systems ■ 4 3-way ON/OFF valve kit for 2-pipe systems■ 4 3-way 0-10V valve kit for 2-pipe systems ■ 4 Manual fresh air dampe ■ 4 On/off motorized fresh air outlet damper

ELFOSpace OUT-V only:■ 4 HID-F1 Control mounted on unit: 3 speed selector + off ■ 4 HID-F2 Control mounted on unit: BULB thermostat (3 speed.+off+E/

l+Temp.selection)■ 4 HID-F4 Control mounted on unit: BULB thermostat + minimum

thermostat ■ 4 Additional condensate collecting tray for vertical installation ■ 4 Supporting feet with cladding for cased vertical units h=90mm ■ 4 Supporting feet with cladding for cased vertical units h=155mm ■ 4 Supporting feet with cladding h=155mm and intake grille for cased

vertical units ■ 4 Rear decor panel for cased vertical units without supporting feet ■ 4 Rear decor panel for cased vertical units with supporting feet

h=90mm ■ 4 Rear decor panel for cased vertical units with supporting feet

h=155mm ELFOSpace OUT-H only:■ 4 Additional condensate collecting tray for horizontal installation

(fittings to right)■ 4 Additional condensate collecting tray for horizontal installation

(fittings to left)Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (max. speed)Fan type (3)Sound pressure level (min-med-max) (4)Power supply

(1) Ambient air temperature: 27°C; 50% R.H. - Temp. water at inlet 7°C, temp. water at outlet 12°C - Max. speed (nominal).

(2) Ambient air temperature: 20°C - Inlet water temperature 70°C, outlet water temperature 60°C - Max. speed (nominal).

(3) CFG = centrifugal fan(4) Sound pressure in free field at a distance of 1 m. Values calculated from sound power measured in echo

chamber to ISO 3741 - ISO 3742

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(C1) mm

Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

leave free

leave free

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 129Guida_2011_v26.indd 129 15/03/11 17:1515/03/11 17:15

Page 59: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

130

ELFOSPACE IN-V e IN-H 3÷31

ELFOSPACE

H2O

IN-H

IN-V

ELFOSPACE IN-H -(6)

3 R3(1)

TR(2)

-(3)

SX(4)

-(5)

-(7)

ELFOSPACE IN-V -(7)

3 R3(2)

TR(3)

-(4)

SX(5)

-(6)

-(8)

MS(1)

HY

DRO

NIC

ELFOSpace IN is the uncased water terminal for use in the commercial sector.The available controls are designed to satisfy the most varied of requirements, with top-of-the-range electronic control designed for connection to the ELFOControl or general supervisors.Low noise operation and easy to maintain.These are the concepts behind the development of ELFOSpace, the last generation room terminal unit that is ideal for any installation.Ten sizes available with an almost countless number of accessories for resolving any service application requirement.The ELFOSpace IN-V series has been designed specifically for uncased vertical installation and the ELFOSpace IN-H series for uncased horizontal installation.

Water terminal unitUncased vertical and horizontal indoor installationCapacity from 1,5 to 9 kW

Heating-Cooling Indoor inst. Uncased vertical inst. (IN-V)

Uncased horizontal inst. (IN-H)

Refrig. Water ELFOControl

Necessary configuration strings for supplying the unit with the indicated elements/accessories already mounted on the appliance.Certain accessories may also be supplied separately, as indicated in the “accessories supplied separately” list.

References for position of fittings:- vertical fan coils: right and left defined by standing in front of the appliance;- horizontal fan coils: right and left defined by standing in the airflow (with the air

blowing on your face).

functions and features

available configurations

(1) AIR RETURN:4R3 Return from below (Standard)4RP Rear return

(2) CONTROLS:4TR Fan terminal block (Standard)4TRM Terminal block with minimum safety thermostat4CTS Clivet.Talk.Terminal Space electronics4CTR Clivet.Talk.Terminal Room

(3) WATER COIL / ELECTRIC HEATER:4- Not required (Standard)4B14T 1-row additional coil for 4-pipe syst. (sizes 3,7,11,17,25)4RE With electric heater

(4) WATER FITTINGS:4SX Left-hand fittings (Standard)4DX Right-hand fittings

(5) VALVES:4- Not required (Standard)

4KBI2 2-pipe system water balancing kit42V2 2-way on/off valve 2-pipe system43V2 3-way on/off valve 2-pipe system410V2 3-way 0-10V valve 2-pipe system4KBI4 4-pipe system water balancing kit (sizes 3,7,11,17,25)42V4 2-way on/off valve 4-pipe system (sizes 3,7,11,17,25)43V4 3-way on/off valve 4-pipe system (sizes 3,7,11,17,25)410V4 3-way 0-10V valve 4-pipe system (sizes 3,7,11,17,25)

(6) ADDITIONAL TRAY:4- Not required (Standard)4BRODX With additional tray r.h. water fittings4BROSX With additional tray l.h. water fittings

(7) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

(1) AIR SUPPLY:4MS Standard supply4MR 90° supply

(2) AIR RETURN:4R3 Return from below (Standard)4RF Front return

(3) CONTROLS:4TR Fan terminal block (Standard)4TRM Terminal block with minimum safety thermostat4HID-F1 3-speed selector + on/off4HID-F2 Bulb thermostat4HID-F3 Bulb thermostat with remote S/W4HID-F4 Bulb thermostat with minimum safety thermostat4HID-F5 Bulb thermostat with electric heater control4HID-F6 Electronic multifunction room thermostat4CTS Clivet.Talk.Terminal Space electronics4CTR Clivet.Talk.Terminal Room

(4) WATER COIL / ELECTRIC HEATER:4- Not required (Standard)4B14T 1-row additional coil for 4-pipe syst. (sizes 3,7,11,17,25)

4RE With electric heater(5) WATER FITTINGS:4SX Left-hand fittings (Standard)4DX Right-hand fittings

(6) VALVES:4- Not required (Standard)4KBI2 2-pipe system water balancing kit42V2 2-way on/off valve 2-pipe system43V2 3-way on/off valve 2-pipe system410V2 3-way 0-10V valve 2-pipe system4KBI4 4-pipe system water balancing kit (sizes 3,7,11,17,25)42V4 2-way on/off valve 4-pipe system (sizes 3,7,11,17,25)43V4 3-way on/off valve 4-pipe system (sizes 3,7,11,17,25)410V4 3-way 0-10V valve 4-pipe system (sizes 3,7,11,17,25)

(7) ADDITIONAL TRAY:4- Not required (Standard)4BRV With additional tray

(8) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

Guida_2011_v26.indd 130Guida_2011_v26.indd 130 15/03/11 17:1515/03/11 17:15

Page 60: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

131

3 5 7 9 11 15 17 21 25 314 kW 1,51 1,96 2,54 3,03 3,73 4,21 5,49 6,37 7,44 9,03

kW 1,18 1,43 1,89 2,14 2,71 3,02 4,00 4,49 5,13 6,16kW 0,045 0,045 0,065 0,065 0,085 0,085 0,12 0,12 0,14 0,140

4 kW 1,78 2,09 2,72 3,01 3,83 4,29 5,67 6,29 7,08 8,47l/s 97,2 100 120 124 180 185 271 279 398 409Pa 40 40 40 40 60 60 60 60 60 60- CFGdB(A) 34 - 40 - 44 35 - 41 - 46 35 - 42 - 47 38 - 44 - 49 42 - 49 - 54V/Ph/Hz 230/1/50

3 5 7 9 11 15 17 21 25 31450 450 650 650 850 850 1050 1050 1250 1250545 545 745 745 945 945 1145 1145 1345 1345215 215 215 215 215 215 215 215 215 215450 450 450 450 450 450 450 450 450 450

4 200 200 200 200 200 200 200 200 200 200100 100 100 100 100 100 100 100 100 100250 250 250 250 250 250 250 250 250 25090 90 90 90 90 90 90 90 90 9014 14 16 17 23 24 26 28 30 32

A

A1

A2

B B1

C1

CD

A1

A2

CC1

B

ELFOSpace IN-V

ELFOSpace IN-H

HY

DRO

NIC

■ Accessories supplied separately.

■ 4 HID-E1 3-speed selector + on/off for wall mounting ■ 4 HID-E2 Simplified room control E/I+3V+on/off for wall mounting ■ 4 HID-E3 Multi-function room control for wall mounting ■ 4 HID-E4 Multi-function room control for 0-10V valves ■ 4 Minimum hot water temperature thermostat ■ 4 Remote air sensor for HID-E2, HID-E3 and HID-E4 ■ 4 Control device for several units with single room control■ 4 HID-T2 electronic room control■ 4 HID-TI2 flush-mounted electronic ambient control ■ 4 HID-T3 electronic room control with humidity sensor■ 4 RS485 remote communication serial port ■ 4 2-pipe water balancing kit = ball valve+balancing valve ■ 4 2-way ON/OFF valve kit for 2-pipe systems ■ 4 3-way ON/OFF valve kit for 2-pipe systems ■ 4 3-way 0-10V valve kit for 2-pipe systems ■ 4 4-pipe water balancing kit = 2 ball valves + 2 balancing valves

(sizes 3-7-11-17-25)■ 4 Sub-frame in galvanised sheet metal■ 4 Pre-painted panel with supply and return grilles■ 4 Manual fresh air damper for vert. and horiz. installation■ 4 Motorized ON/OFF fresh air outlet damper■ 4 Straight air supply plenum■ 4 Straight air intake plenum■ 4 90° air supply plenum■ 4 90° air intake plenum■ 4 Telescopic extension 0-100 mm (suitable for connection to any

plenum)

■ 4 Air distribution duct with flexible joint■ 4 Air return duct with flexible joint■ 4 Air supply plenum with round fittings + thermal and acoustic

insulating lining■ 4 Air intake plenum with round fittings and air filter■ 4 Terminal plenum with circular connections ■ 4 Air supply grille without air filter (suitable for connection to any

plenum)■ 4 Aluminium air supply grille without air filter■ 4 Air intake grille with air filter (suitable for connection to any plenum)■ 4 Aluminium air intake grille with air filterELFOSpace IN-V only:■ 4 HID-F1 Control mounted on unit: 3 speed selector + off ■ 4 HID-F2 Control mounted on unit: BULB thermostat (3 speed.+off+E/

l+Temp.selection)■ 4 HID-F4 Control mounted on unit: BULB thermostat + minimum

thermostat ■ 4 Additional condensate collecting tray for vertical installation ■ 4 Supporting feet for uncased vertical units h=90mm ■ 4 Supporting feet for uncased vertical units h=155mm ELFOSpace IN-H only:■ 4 Additional condensate collecting tray for horizontal installation

(fittings to right)■ 4 Additional condensate collecting tray for horizontal installation

(fittings to left)

Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (max. speed) (3)Max. working static pressure (4)Fan type (5)Sound pressure level (min-med-max) (6)Power supply

(1) Ambient air temperature: 27°C; 50% R.H. - Temp. water at inlet 7°C, temp. water at outlet 12°C - Max. speed (nominal).

(2) Ambient air temperature: 20°C - Inlet water temperature 45°C, outlet water temperature 40°C - Max. speed (nominal).

(3) Air flow rate at maximum speed with available head of 0 Pa

(4) Working static pressure at fan maximum speed (5) CFG = centrifugal fan(6) Sound pressure in free field at a distance of 1 m. Values calculated from sound power measured in echo

chamber to ISO 3741 - ISO 3742

Data referred to the following conditions:

Sizes IN-V Length (A) mmIN-H Length (A) mmWidth (B) mmHeight (C) mm

(A1) (*) mm(A2) (**) mm(B1) mm(C1) mm

Weight in oper. kgThe above data refer to standard units.(*) water fittings side(**) elect. supply side

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 131Guida_2011_v26.indd 131 15/03/11 17:1515/03/11 17:15

Page 61: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

132

ELFOSPACE BOX2 7÷41

ELFOSPACE

ELFOSPACE BOX2 7

H2O

CC2(2)

230M(1)

-(3)

-(4)

-(5)

HY

DRO

NIC

The ELFOSpace BOX2 terminal unit has been designed for installation in suspended ceilings without requiring any extra part for operation. The unit has an intake grille and four-way outlet with adjustable diffuser flaps for changing airflow direction.The ELFOSpace BOX2 is therefore suited for use in environments such as shops, restaurants, hotels and gyms, where the excellent outflowing air control makes them ideal air-conditioning units:

4available in version for 2 and 4-pipe systems;

4available in electro-mechanical or electronic version with set-up for connection to ELFOControl or general supervisors;

4possibility of controlling several units from a single point;

4suited for installation in standard suspended ceilings with 600 x 600 mm module;

4 the unit comes with a condensate drain pump (500 mm vertical).

Water terminal unitCassette-type indoor installationCapacity from 2,68 to 11 kW

Heating-Cooling Indoor inst. Uncased horizontal inst. Refrig. Water ELFOControl

(1) SUPPLY VOLTAGE:4230M 230/1/50 (Standard)

(2) COIL CONFIGURATION:4CC2 Coil configuration with 2-pipe system (Standard)4CC4 Coil configuration with 4-pipe system (sizes

7,11,21,31)

(3) HEATING ELECTRIC HEATERS:4- Not required (Standard)4RE Heating elctric heaters

(4) ELECTRONIC VERSION:4- Not required (Standard)4CTS Clivet.Talk.Terminal Space electronics

(5) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

functions and features

available configurations

Guida_2011_v26.indd 132Guida_2011_v26.indd 132 15/03/11 17:1515/03/11 17:15

Page 62: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

133

7 11 15 21 31 41

4 kW 2,84 4,62 5,38 6,58 10,1 11,9kW 2,04 3,22 3,80 4,60 7,00 8,30kW 0,044 0,068 0,09 0,077 0,12 0,17

4 kW 3,10 5,12 5,86 7,26 11,1 13,2l/s 144 197 244 317 417 506l/s 0,13 0,21 0,24 0,29 0,45 0,53- RADdB(A) 24/31/36 24/36/44 32/40/50 24/31/39 25/31/44 25/39/49V/Ph/Hz 230/1/50

7 11 15 21 31 41

572 572 572 819 819 819572 572 572 819 819 819296 296 296 329 329 329670 670 670 965 965 965670 670 670 965 965 96541 41 41 59 59 59

4 500 500 500 500 500 500500 500 500 500 500 500100 100 100 100 100 100100 100 100 100 100 10027 27 27 45 45 45

E

B

B2

B1

D

A

A1

A2C

F

7 11 15 21 31 41

4 kW 2,89 4,21 4,83 6,76 9,37 10,8kW 2,05 2,96 3,44 4,72 6,57 7,69kW 0,044 0,068 0,09 0,077 0,12 0,17

4 kW 3,46 3,35 3,79 9,10 8,56 9,80l/s 144 197 244 317 417 506- RADdB(A) 24/31/36 24/36/44 32/40/50 24/31/39 25/31/44 25/39/49V/Ph/Hz 230/1/50

HY

DRO

NIC

■ Accessories supplied separately.

■ 4 HID-E2 Simplified room control E/I+3V+on/off for wall mounting ■ 4 HID-E3 Multi-function room control for wall mounting ■ 4 Remote air sensor for electromechanical thermostats ■ 4 Control device for several units with single room control■ 4 HID-T2 electronic room control■ 4 HID-TI2 flush-mounted electronic ambient control ■ 4 HID-T3 electronic room control with humidity sensor■ 4 RS485 remote communication serial port

■ 4 3-way ON/OFF valve kit for 2-pipe systems ■ 4 3-way ON/OFF valve kit for 4-pipe systems (sizes 7,11,21,31)■ 4 Connection for fresh air intake■ 4 Connection for additional air supply■ 4 Fairing for uncased installation

Key to symbols:

SizesELFOSpace BOX-2T (2-pipe system)

Cooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (max. speed)Water flow rateFan type (3)Sound pressure level (min-med-max) (4)Power supply

(1) Ambient air at 27°C; 50% R.H.; water at inlet 7°C and outlet 12°C(2) Ambient air at 20°C; water at inlet 50°C and outlet 40°C(3) RAD = radial-blade fan

(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

Data referred to the following conditions:

Sizes ELFOSpace BOX2Indoor unit length (A) mmIndoor unit width (B) mmIndoor unit height (C) mmFront panel length (D) mmFront panel width (E) mmFront panel height (F) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

The above data refer to standard units.CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

SizesELFOSpace BOX-4T (4-pipe system)

Cooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (max. speed)Fan type (3)Sound pressure level (min-med-max) (4)Power supply

(1) Ambient air at 27°C/19,5°C W.B.; water at inlet 7°C and outlet 12°C(2) Ambient air at 20°C D.B.; water at inlet 50°C and outlet 40°C(3) RAD = radial-blade fan

(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

Data referred to the following conditions:

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 133Guida_2011_v26.indd 133 15/03/11 17:1515/03/11 17:15

Page 63: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

134

ELFOSPACE WALL 3÷17

ELFOSPACE

ELFOSPACE WALL 3

H2O

230M(1)

HY

DRO

NIC

ELFOSpace Wall is a range of cased water terminals that are cleverly designed for quick, easy and discrete installation in the space above doors or at mid-height on walls. These exceptionally low noise units also feature air flow direction control and come with all the components needed for installation and start-up (template, three-way valve and infrared remote control).

Water terminal unitIndoor installation, wall-mounted, casedCapacity from 1,20 to 5,30 kW

Heating-Cooling Indoor inst. Cased vertical inst. Refrig. Water

(1) SUPPLY VOLTAGE:4230M 230/1/50 (Standard)

functions and features

available configurations

Guida_2011_v26.indd 134Guida_2011_v26.indd 134 15/03/11 17:1615/03/11 17:16

Page 64: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

135

C

A

A1

A2

C2

C1

3 5 7 9 15 174 kW 1,51 1,71 2,05 2,51 3,25 4,62

kW 1,13 1,26 1,56 1,82 2,36 3,254 kW 1,63 1,80 2,33 2,64 3,32 4,66

l/s 0,07 0,08 0,1 0,12 0,15 0,22l/s 100 106 117 122 186 191- TGZdB(A) 37/39/43 37/39/43 41/43/46 41/43/46 42/46/49 42/46/49V/Ph/Hz 230/1/50

3 5 7 9 15 17870 870 1030 1030 1160 1160176 238 196 258 198 260270 270 320 320 330 330

4 100 100 100 100 100 100100 100 100 100 100 100

190 (*)80 80 80 80 80 8012 13 14 14,5 17 17,5

HY

DRO

NIC

■ Accessories supplied separately.

■ 4 Electronic wall-mounting room thermostat

Key to symbols:

The above data refer to standard units.(*) Overhead installation

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

SizesCooling capacity (1)Sensible cooling capacityHeating capacity (2)

Water flow rateAir flow rate (max. speed)Fan type (3)Sound pressure level (min-med-max) (4)Power supply

(1) Ambient air 27°C/19°C W.B., inlet water 7°C and water flow-rate as in the table(2) Ambient air 20°C/19°C D.B., water at inlet 45°C and outlet 40°C(3) TGZ = cross-flow fan

(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions. Values calculated from sound power measured in echo chamber to ISO 3741 - ISO 3742

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(C1) mm(C2) mm

Weight in oper. kg

accessories

technical data

Guida_2011_v26.indd 135Guida_2011_v26.indd 135 15/03/11 17:1615/03/11 17:16

Page 65: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

136

ELFODUCT CFD 7÷41

ELFODUCT

ELFODUCT CFD 7

H2O

-(8)

230M6 VS(1)

DX(2)

2T(3)

CW3R(4)

DHS(6)

PO(7)

-(9)

-(10)

-(11)

-(5)

-(12)

HY

DRO

NIC

The ELFODuct CFD units are ideal air-treatment terminal units for installations where ducted air distribution is necessary.The units are designed for installation in suspended ceilings and are distinguished by their compactness and extremely low noise levelsbecause they are fitted with packaged centrifugal fans, that is, every impeller has its own external rotor motor on rubber antivibration mounts. When ductwork is extensive this solution ensures that the fan impeller is not overhung and therefore produces no vibrations, which would make the environment noisy.The 7-11-15-21 sizes may be supplied in a shorter version for space saving purposes.The main features are:

4various available controls, from simple speed control through to the electronic control set-up for connection to ELFOControl or general supervisors;

4available in version for 2 and 4-pipe systems with various types of coils (3 rows, 4 rows, 2+1 rows, 2+2 rows, 3+1 rows, 3+2 rows);

4wide choice of aeraulic accessories (plenum for round ducts, intake plenum with filter);

4electric heaters;4low and high head-pressure fans for air distribution through

ductwork.

Water terminal unitUncased horizontal indoor installationDuctableCapacity from 2,37 to 12,3 kW

Heating-Cooling Indoor inst. Uncased horizontal inst. Refrig. Water ELFOControl

(1) CONSTRUCTIONAL CONFIGURATION:4VS Standard Version4VR Lowered version (sizes 7÷21)

(2) WATER FITTINGS: 4DX Right-hand fittings (Standard) 4SX Left-hand fittingss(3) COIL CONFIGURATION: 4CC2 Coil configuration with 2-pipe system (Standard)4CC4 Coil configuration with 4-pipe system

(4) WATER COIL:4CW3R Coil 3 rows (Standard)4CW4R Coil 4 rows4CW21R Coil 2+1 rows4CW22R Coil 2+2 rows4CW31R Coil 3+1 rows4CW32R Coil 3+2 rows

(5) AUXILIARY CONDENSATE COLLECTION TRAY:4- Not required (Standard)4CDAN For naval installations

(6) SUPPLY STATIC PRESSURE:4DHS Standard supply static pressure4DHH Supply static pressure High

(7) SUPPLY PLENUM:4PO Air supply plenum (Standard)4POC Air delivery plenum for round ducts

(8) RETURN PLENUM:4- Not required (Standard)4PIR Soundproofed return plenum

(9) AIR RETURN CONNECTION:4- Not required (Standard)4FPR Air return plenum flange

(10) ELECTRIC HEATERS:4- Not required (Standard)

4EH01 0,5 kW heating electric heaters (size 7) 4EH03 1 kW heating electric heaters (size 11) 4EH05 2 kW heating electric heaters (sizes 15-21) 4EH07 3 kW heating electric heaters (sizes 25-31)4EH08 4 kW heating electric heaters (size 41)

(11) ELECTRONIC VERSION:4- Not required (Standard)4CTS Clivet.Talk.Terminal Space electronic for HID-T2 or HID-T3

thermostats (ELFOControl)(12) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

Necessary configuration string for supplying the unit with the indicated elements/accessories already mounted on the appliance.Certain accessories may also be supplied separately, as indicated in the “accessories supplied separately” list.

References for position of horizontal fan coil fittings: right and left definedby standing in the airflow (with the air blowing on your back).

functions and features

available configurations

Guida_2011_v26.indd 136Guida_2011_v26.indd 136 15/03/11 17:1615/03/11 17:16

Page 66: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

137

7 11 15 21 25 31 414 kW 2,37 3,09 5,26 6,46 8,47 9,21 12,3

kW 1,82 2,29 3,87 4,68 6,06 6,72 8,94kW 0,07 0,07 0,13 0,15 0,20 0,22 0,30

4 kW 2,27 3,35 5,61 6,69 8,57 9,67 12,7l/s 134 160 269 316 404 466 614Pa 70 80 90- CFGdB(A) 37 39 39 40 39 42 43V/Ph/Hz 230/1/50

7 11 15 21 25 31 41525 625 885 1035 1245 1365 1665575 575 575 575 575 575 575285 285 285 285 285 285 285

4 200 200 200 200 200 200 200100 100 100 100 100 100 10015 17 24 30 35 38 46

A

A2

C

A1B

HY

DRO

NIC

■ Accessories supplied separately.

■ 4 3-way “on/off” type valve for 2-pipe system ■ 4 3-way “on/off” type valve for 4-pipe system ■ 4 Additional condensate collecting tray 4 Additional condensate collecting tray for naval installations

■ 4 HID-E1 3-speed selector + on/off for wall mounting ■ 4 HID-E2 Simplified room control E/I + 3V + on/off for wall

mounting ■ 4 HID-E3 Multi-function room control for wall mounting ■ 4 HID-T2 electronic room control ■ 4 HID-TI2 flush-mounted electronic ambient control

■ 4 HID-T3 electronic room control with humidity sensor■ 4 Remote ambient air temperature sensor (for thermostat HID-E2)

Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (max. speed) (3)Max. working static pressure (4)Fan type (5)Sound pressure level (6)Power supply

(1) Ambient air temperature: 27/19,5°C W.B. - Temp. water at inlet 7°C, temp. water at outlet 12°C standard 3 row coil - Nominal air flow rate with available head of 30 Pa.

(2) Ambient air temperature: 20°C - Inlet water temperature 45°C, outlet water temperature 40°C - standard 3 row coil - Nominal air flow rate with available head of 30 Pa.

(3) Air flow rate at maximum speed with available head of 30 Pa.(4) Maximum available working static pressure at maximum speed

(5) CFG = centrifugal fan(6) The sound levels refer to units ceiling installed without false ceiling, with nominal air flow, fan supply 230V,

maximum fan speed.The sound pressure level is referred at a distance of 1 m. from the unit surface. Measurement have been made with a unit with air return plenum complete with filter.

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm

Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 137Guida_2011_v26.indd 137 15/03/11 17:1615/03/11 17:16

Page 67: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

138

ELFODUCT CFI 25÷71

ELFODUCT

ELFODUCT CFI 25

H2O

-(3)

RF(2)

-(4)

230M(1)

HY

DRO

NIC The ELFODuct CFI units are ideal air-treatment terminal units for installations

where ducted air distribution is necessary.The units are designed for vertical installation in lining walls and are distinguished by their compactness and extremely low noise levels obtained thanks to internal and external insulation.The main features are:

4various available controls, from simple speed control through to the electronic control set-up for connection to ELFOControl or general supervisors;

4available in version for 2 and 4-pipe systems;4wide choice of aeraulic accessories (plenum for round ducts);4electric heater section with different power plus electronic power

modulation control;4high head-pressure fans for ducted air distribution.

Water terminal unitUncased vertical indoor installationDuctableCapacity from 8,7 to 21,6 kW

Heating-Cooling Indoor inst. Uncased vertical inst. Refrig. Water ELFOControl

(1) SUPPLY VOLTAGE: 4230M 230/1/504400TN 400/3/50+N (available only with the heating

electric heaters)

(2) AIR RETURN:4RF Front return (Standard)4R3 Return from below

(3) ELECTRONIC VERSION:4- Not required4CV3FS Fan 3-speed board4CTS Clivet.Talk.Terminal Space electronics

(4) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

functions and features

available configurations

Room control HID-T2 for wall-mounted remote installation with functions of:4 manual or automatic summer/winter

selection4 temperature setting4 manual setting of fan speed4 other useful functions.

Guida_2011_v26.indd 138Guida_2011_v26.indd 138 15/03/11 17:1615/03/11 17:16

Page 68: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

139

25 31 41 51 714 kW 8,70 12,7 15,2 18,7 21,6

kW 6,69 9,71 11,2 14,3 16,6kW 0,47 0,61 0,61 0,75 1,43

4 kW 9,91 14,4 16,4 21,1 24,5l/s 502 708 738 1031 1237Pa 130 140 150 230 250- CFGV/Ph/Hz 230/1/50

25 31 41 51 71903 962 1202 1202 1202290 315 315 365 365710 740 740 820 930

4 400 400 400 400 400200 200 200 200 200

1000 1000 1000 1000 100033 40 45 54 63

B

C

B1

A

A1

A2

HY

DRO

NIC

■ Accessories supplied separately.

■ 4 Hot water coil with 2 rows ■ 4 4,5 kW electric heaters (sizes 25÷31) ■ 4 6 kW electric heaters (sizes 41÷71) ■ 4 9 kW electric heaters (sizes 25÷31) ■ 4 12 kW electric heaters (sizes 41÷71) ■ 4 HID-T2 electronic room control ■ 4 HID-TI2 flush-mounted electronic ambient control ■ 4 HID-T3 electronic room control with humidity sensor■ 4 RS485 remote communication serial port ■ 4 Air supply plenum for round ducts

■ 4 HID-E1 Three-speed selector + ON/OFF for wall mounting ■ 4 HID-E2 Simplified room control E/I+3V+on/off for wall mounting ■ 4 HID-E3 Multi-function room control for wall mounting ■ 4 HID-E4 Multi-function room control for 0-10V valves

Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (max. speed) (3)Max. working static pressure (4)Fan type (5)Power supply

(1) Ambient air at 27°C, 50% R.H.; water at inlet 7°C and outlet 12°C(2) Ambient air at 20°C; water at inlet 45°C and outlet 40°C(3) Air flow rate at maximum speed with available head of 0 Pa

(4) Maximum available working static pressure at maximum speed(5) CFG = centrifugal fan

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm

Weight in oper. kgThe above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 139Guida_2011_v26.indd 139 15/03/11 17:1615/03/11 17:16

Page 69: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

140

ELFODUCT CF 25÷242

ELFODUCT

ELFODUCT CF 25

H2O

-(3)

ELFODUCT CF 91 400T(1)

MOS(2)

-(3)

CWS(4)

-(5)

-(6)

-(7)

-(2)

-(8)

230M(1)

HY

DRO

NIC

The ELFODuct CF units are ideal air-treatment terminal units for installations where ducted air distribution is necessary.They are designed for installation in suspended ceilings and are distinguished by their compactness and extremely low noise levels obtained thanks to both internal and external insulation.Sizes from 91 to 242 may be ceiling or floor mounted.The main features are:

4various available controls, from simple speed control through to the electronic control set-up for connection to ELFOControl or general supervisors;

4available in version for 2 and 4-pipe systems;4wide choice of aeraulic accessories (plenum for round ducts, fresh

air intake plenum);4electric heater section with different power plus electronic power

modulation control;4high head-pressure fans for ducted air distribution.

Water terminal unitUncased horizontal indoor installationDuctableCapacity from 8,7 to 83,8 kW

Heating-Cooling Indoor inst. Uncased horizontal inst. Refrig. Water ELFOControl

CF 25÷71 unit configuration

CF 91÷242 unit configuration

functions and features

available configurations

(1) SUPPLY VOLTAGE: 4230M 230/1/504400TN 400/3/50+N (available only with the heating

electric heaters)(2) ELECTRONIC VERSION:4- Not required

4CV3FS Fan 3-speed board4CTS Clivet.Talk.Terminal Space electronics

(3) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

(1) SUPPLY VOLTAGE: 4400T 400/3/50 without neutral4230T 230/3/50

(2) MOTOR SPECIFICATIONS:4MOS Standard motor

4MOD Double-speed motor(3) FILTER:4- Not required (Standard)4FCS Angular air filter section

(4) WATER COIL:4CWS Standard coil4CW6R 6-row coil (sizes 91-121)

(5) ADDITIONAL WATER COIL:4- Not required (Standard)4CHW2 2-row additional coil for 4-pipe syst.4CHW3 3-row additional coil for 4-pipe syst. (sizes 91-121)

(6) ELECTRIC HEATERS:4- Not required (Standard)4EH09 4,5 kW electric heaters (sizes 91-121)4EH10 6 kW electric heaters (sizes 91-121)4EH12 9 kW electric heaters (sizes 91-121)4EH14 12 kW electric heaters (sizes 91-121)4EH17 18 kW electric heaters4EH20 24 kW electric heaters (sizes 142÷242)

(7) ELECTRONIC VERSION:4- Not required (Standard)4CQEP Power switchboard (Standard)4CTS Clivet.Talk.Terminal electronics

(8) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

Room control HID-T2 for wall-mounted remote installation with functions of:4 manual or automatic summer/winter

selection4 temperature setting4 manual setting of fan speed4 other useful functions.

Guida_2011_v26.indd 140Guida_2011_v26.indd 140 15/03/11 17:1615/03/11 17:16

Page 70: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

141

25 31 41 51 71 91 121 142 162 182 202 2424 kW 8,70 12,7 15,2 18,7 21,6 29,7 40,3 46,8 52,3 58,9 75,2 83,8

kW 6,69 9,71 11,2 14,3 16,6 22,1 29,7 33,6 38,0 42,5 52,6 59,4kW 0,47 0,61 0,61 0,75 1,43 0,75 1,10 1,1 1,5 1,5 2,2 3,0

4 kW 9,91 14,4 16,4 21,1 24,5 32,1 43,1 47,9 54,5 61,0 74,4 84,4l/s 502 708 738 1031 1237 1417 1889 2120 2500 2660 3100 3620Pa 130 140 150,0 230 250 170 160 110 110 80 140 230Pa - - - - - 240 240 300 300 300 300 300- CFGdB(A) 24 55 56 57 58 43 50 51 56 52 53 53V/Ph/Hz 230/1/50 400/3/50

25 31 41 51 71 91 121 142 162 182 202 2421000 1100 1340 1340 1340 1285 1435 2010 2010 2010 2510 2510480 500 550 550 550 945 1030 750 750 750 850 850297 322 322 372 422 585 685 630 630 630 680 680

4 200 200 200 200 200 200 200 500 500 500 500 500400 400 400 400 400 400 400 500 500 500 500 50033 33 40 45 54 138 158 170 190 195 253 265

B

A1

A

C

A2A

A2

A1

B

C

A

A1

A2 B

C

25÷71

91÷121

142÷242

HY

DRO

NIC

■ Accessories supplied separately.

Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (3)Max. working static pressure (4)Max. working static pressure (5)Fan type (6)Sound pressure level (7)Power supply

(1) Ambient air at 27-19,5°C W.B.; water at inlet 7°C and outlet 12°C(2) Ambient air at 20°C; water at inlet 45°C and outlet 40°C(3) Air flow rate at maximum speed with available head of 0 Pa (sizes 25÷71); nominal air flow rate (sizes

91÷242).(4) Maximum available working static pressure at maximum speed (sizes 25÷71); max available static pressure

with standard motor. It does not take into consideration any accessory increasing the pressure drop on the airside (sizes 91÷242)

(5) Max available static pressure with high power motor. It does not take into consideration any accessory increasing the pressure drop on the airside (sizes 91÷242)

(6) CFG = centrifugal fan(7) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1

m from the external surface of the unit in open field conditions.

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm

Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

■ 4 Rubber antivibration mounts (sizes 91÷242) ■ 4 Hot water coil with 2 rows ■ 4 Hot water coil with 3 rows (sizes 91-121) ■ 4 4,5 kW electric heaters (sizes 25-31-91-121) ■ 4 6 kW electric heaters (sizes 41÷121 ) ■ 4 9 kW electric heaters (sizes 25-31-91-121)■ 4 12 kW electric heaters (sizes 41÷121) ■ 4 18 kW electric heaters (sizes 91÷242) ■ 4 24 kW electric heaters (sizes 142÷242) ■ 4 Angular air filter section (sizes 91÷242) ■ 4 HID-T2 electronic room control ■ 4 HID-TI2 flush-mounted electronic ambient control

■ 4 HID-T3 electronic room control with humidity sensor■ 4 RS485 remote communication serial port ■ 4 Fresh air mixing, recirculation (sizes 25÷121)■ 4 Air supply plenum for round ducts (sizes 25÷71)■ 4 HID-E1 3-speed selector + on/off for wall mounting (sizes 25÷71)■ 4 HID-E2 Simplified room control E/I+3V+on/off for wall mounting

(sizes 25÷71)■ 4 HID-E3 Multi-function room control for wall mounting (sizes 25÷71)■ 4 HID-E4 Multi-function room control for 0-10V valves (sizes 25÷71)■ 4 3-way 0-10V valve kit for 2-pipe systems■ 4 3-way 0-10V valve kit for 4-pipe systems (sizes 142÷242)

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 141Guida_2011_v26.indd 141 15/03/11 17:1615/03/11 17:16

Page 71: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

142

ELFODUCT CF-V 31÷242

ELFODUCT

H2O

ELFODUCT CF-V 31 230M(1)

RF(2)

-(3)

-(4)

ELFODUCT CF-V 91 400T(1)

RF(2)

SM(3)

-(6)

MOS(4)

-(5)

-(5)

-(7)

-(6)

-(8)

HY

DRO

NIC

The ELFODuct CF-V tall water terminal units have been designed for installation directly in the room or in technical spaces.The units have been designed for sending air directly into the room or with ducted distribution. They are distinguished by their compactness and extremely low noise levels obtained thanks to internal soundproofing.The main features are:

4various available controls, from simple speed control through to the electronic control set-up for connection to ELFOControl or general supervisors;

4available in version for 2 and 4-pipe systems;4choice of aeraulic accessories (plenum for front air supply or on three

sides);4electric heater section with different power plus electronic power

modulation control;4fans available with high static pressure, which allow extensive

ducting;4front air return through grille (standard) or with return from the floor

or from the rear

Water terminal unitCased vertical indoor installationDuctableCapacity from 13,6 to 89 kW

Heating-Cooling Indoor inst. Cased vertical inst. Refrig. Water ELFOControl

CF-V 31-71 unit configuration

CF-V 91-242 unit configuration

functions and features

available configurations

(1) SUPPLY VOLTAGE: 4400T Power supply 400/3/50 without neutral (Standard) 4230T Power supply 230/3/50(2) AIR RETURN: 4RF Front return (Standard)4R3 Return from below4R4 Rear return

(3) AIR FLOW RATE: 4SM Standard supply air flow-rate 4RM Reduced outlet air flow-rate(4) MOTOR SPECIFICATIONS:4MOS Standard motor

4MOD Double-speed motor(5) HOT WATER COIL:4- Not required (Standard)4CHW2 2-row hot water coil

(6) ELECTRIC HEATERS:4- Not required (Standard)4EH09 4,5 kW heating electric heaters4EH10 6 kW heating electric heaters4EH12 9 kW heating electric heaters

4EH14 12 kW heating electric heaters 4EH17 18 kW heating electric heaters4EH20 24 kW heating electric heaters (sizes 142÷242)

(7) ELECTRONIC VERSION:4- Not required (Standard)4CTS Clivet.Talk.Terminal Space electronic for HID-T2 or HID-T3 thermostats

(ELFOControl)(8) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

(1) SUPPLY VOLTAGE: 4230M Power supply 230/1/50 (Standard) 4400T Power supply 400/3/50without neutral (available only

with the heating electric heaters)(2) AIR RETURN: 4RF Front return (Standard)4R3 Return from below4R4 Rear return

(3) HOT WATER COIL:4- Not required (Standard)4CHW2 2-row hot water coil

(4) ELECTRIC HEATERS:4- Not required (Standard)

4EH09 4,5 kW heating electric heaters4EH10 6 kW heating electric heaters (sizes 41÷71)4EH12 9 kW heating electric heaters4EH14 12 kW heating electric heaters (sizes 41÷71)4EH17 18 kW heating electric heaters (size 71)

(5) ELECTRONIC VERSION:4- Not required (Standard)4CV3FS Electronic version with 3-speed board for the fan4CTS Clivet.Talk.Terminal Space electronic for HID-T2 or HID-T3 thermostats

(ELFOControl)(6) SERIAL PORT:4- Not required (Standard)

4SP1 RS485 remote communication serial port

Room control HID-T2 for wall-mounted remote installation with functions of:4 manual or automatic summer/winter

selection4 temperature setting4 manual setting of fan speed4 other useful functions.

Guida_2011_v26.indd 142Guida_2011_v26.indd 142 15/03/11 17:1615/03/11 17:16

Page 72: HYDRONIC System - Amazon S3 · HYDRONIC System The complete range of chillers, heat pumps and air handling units in large installations HYDRONIC System is the innovative evolution

143

31 41 51 71 91 101 121 142 182 202 2424 kW 13,6 19,1 21,6 27,9 36,9 44,0 48,7 65,5 75,4 83,6 89,0

kW 9,82 13,7 15,7 20,3 26,5 21,8 35,6 47,1 54,9 60,2 64,9kW 0,30 0,30 0,50 0,60 0,80 1,10 1,50 1,50 2,20 2,20 3,00

4 kW 13,1 18,1 22,6 26,2 35,9 42,3 46,6 62,0 71,5 78,4 85,7l/s 569 778 944 1166 1597 1889 2167 2638 3194 3472 3888Pa 85 93 80 70 140 170 180 140 115 145 180Pa - - - - 240 240 240 210 240 240 240- CFGdB(A) 48 49 50 51 53 56 58 58 60 62 64V/Ph/Hz 230/1/50 400/3/50

31 41 51 71 91 101 121 142 182 202 242650 850 850 1050 1050 1250 1250 1870 1870 2070 2070500 500 500 500 670 670 670 670 670 670 6701700 1700 1700 1700 2000 2000 2000 2000 2000 2000 2000

4 400 400 400 400 400 400 400 400 400 400 400400 400 400 400 400 400 400 400 400 400 4001000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

96 117 123 140 185 210 215 250 260 290 295

BB2

AA2

C

A1

HY

DRO

NIC

■ Accessories supplied separately.

Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total inputHeating capacity (2)

Air flow rate (3)Max. working static pressure (4)Max. working static pressure (5)Fan type (6)Sound pressure level (7)Power supply

(1) Ambient air 27°C/19,5°C W.B.; water at inlet 7°C; water at outlet 12°C(2) Ambient air 20°C D.B.; water at inlet 45°C; water at outlet 40°C; R.H. 50%(3) Standard air flow rate(4) Available static pressure with standard flowrate, including air filter (sizes 31÷71); available static pressure

with standard motor, including air filter (sizes 91÷242).

(5) Max available static pressure with high power motor (sizes 91÷242)(6) CFG = centrifugal fan(7) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1

m from the external surface of the unit in open field conditions.

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B2) mm

Weight in oper. kgThe above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

■ 4 HID-T2 electronic room control ■ 4 HID-TI2 flush-mounted electronic ambient control ■ 4 HID-T3 electronic room control with humidity sensor■ 4 HID-S1 local electronic room control ■ 4 RS485 remote communication serial port ■ 4 Front air supply plenum■ 4 Plenum for air supply on three sides

■ 4 3-way 0-10V valve kit for 2-pipe systems■ 4 3-way 0-10V valve kit for 4-pipe systems

accessories

dimensions and clearances

technical data