HOME INSPECTION REPORT PREPARED FOR: KENNETH PRIVETT & ROSIMER PRIVETT PROPERTY AT: 2800 SW 154 AVE DAVIE, FLORIDA PREPARED BY: KBC BUILDING INSPECTIONS, INC. ENGINEERING, CONSTRUCTION MANAGEMENT & REAL ESTATE INSPECTION SERVICES 8724 SUNSET DRIVE #427, MIAMI, FL. 33173-3512 TELEPHONE: (305662-5073 / FAX: (305) 553-3735

HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

HOME INSPECTION REPORT

PREPARED FOR:

KENNETH PRIVETT & ROSIMER PRIVETT

PROPERTY AT: 2800 SW 154 AVE

DAVIE, FLORIDA

PREPARED BY:

KBC BUILDING INSPECTIONS, INC. ENGINEERING, CONSTRUCTION MANAGEMENT & REAL ESTATE INSPECTION SERVICES

8724 SUNSET DRIVE #427, MIAMI, FL. 33173-3512 TELEPHONE: (305662-5073 / FAX: (305) 553-3735

Page 2: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

Page 1 of 20

KBC BUILDING INSPECTIONS, INC. ENGINEERING, CONSTRUCTION MANAGEMENT & INSPECTION SERVICES

INSPECTION REPORT

CLIENT INFORMATION:

Client Name: Kenneth Privett &

Rosimer Privett

Telephone no.:

INSPECTION INFORMATION:

Date of Inspection: 08-12-19

Location: 2800 SW 154 Ave

Inspector: G. Fagundo

G. Fagundo, jr

(HI-4019)

A. Fernandez

Building Use: Residential Commercial Other

Type of Inspection:

Comprehensive Package Appliances

Roof Pool/Hot Tub/Spa

Structural Sprinkler System

Plumbing Water Quality

Electrical Townhouse Package

A/C & Heating System Termite

Present at Inspection:

Client Selling Agent

Seller Listing Agent

GENERAL INFORMATION:

KBC Building Inspections, Inc. has performed the inspection(s) in accordance with the conditions

established in the Service Agreement with the Client. The inspection did not involve destructive

testing; therefore, surface materials were not removed during the inspection. When there were

numerous similar items to be checked (i.e., windows, doors, electrical switches/receptacles, etc.),

a spot check of a representative number was performed. KBC Building Inspections, Inc. does not

check gas lines, appliances, etc. for leaks; therefore, if the property is serviced with gas, the Client

should obtain a satisfactory gas utility safety inspection. Repair work should not be performed

based solely upon this Inspection Report. Prior to the closing date, an appropriate licensed

contractor specializing in the specific area of expertise should further evaluate the system or item

to offer a recommendation for repair. Changes can occur to this property between the time of this

inspection and the closing date of the sale. The Client should personally inspect the property prior

to the closing date to confirm that nothing has been changed, altered or damaged.

Page 3: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 2 of 20

DEFINITION OF EVALUATION TERMS:

N/A Not applicable and/or not inspected.

Normal Item is in normal condition for its age, in the opinion of the inspector.

N/R Item needs repair or replacement. Item is not functioning, is in an unsafe condition,

or has deteriorated in the opinion of the inspector.

W.D.O. Item shows indication of deterioration, possibly due to wood destroying organisms;

consult pest infestation expert.

R/C Please refer to comments provided.

Note: When the terms N/R and/or W.D.O. are used throughout this report, we recommend that

an appropriate licensed contractor or professional specializing in the specific area of expertise be

called in to further evaluate the system.

All cost estimates included in this report are only approximate. If a more detailed estimate

is required, it is recommended that the Client obtain a cost estimate from a Licensed

Contractor or Technician who specializes in the specific area of expertise. Cost estimates for

cosmetic repairs are not included in this report.

Page 4: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 3 of 20

ROOF:

Main Roof: Asphalt Shingles Attic: Yes No

Sloping Flat Accessible

Inaccessible

Roof No. 2 Surface: N/A Limited Access

Sloping Flat Storage/Obstructions

Attic Insulation:

Roof No. 3 Surface: N/A Batt Other

Sloping Flat Loose N/A

Component: N/A Normal N/R W.D.O. R/C

Flashing

Fascias

Soffits

Ridge

Gutters

Downspouts

Vent Piping Penetration

Ventilators Penetration

Chimney Penetration

Wood Trusses

Wood Rafters

Wood Joists

Roof Sheathing

Attic Ventilation

Visible Water Penetration No Yes, refer to comments.

Comments:

1. Evaluation of all components is based on visible roof surface and not on the life expectancy

of the roof system. No thermal or material content evaluation of insulation was performed.

2. Roof is in poor condition, improper shingles used on ridge. It appears that roof was not

professionally installed. It is recommended that roof be replaced. Approx. $16,000. (see

fig. 1)

3. SE corner of roof is damaged and improperly repaired. Area is currently being held up

by temporary lally columns. Approx. $2,500 to reinforce and repair area. (see fig. 2)

4. Underside of rear porch roof needs to be redone. Approx. $500. (see fig. 3)

5. No roof insulation noted. Approx. $2,000 to install.

Page 5: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 4 of 20

EXTERIOR:

Component: N/A Normal N/R W.D.O. R/C

Exterior Siding

Stairways/Landings/Railings

Balconies/Railings

Decks/Railings

Patios/Porches

Window Trim

Exterior Doors

Door Frame & Trim

Sliding Doors

Garage Doors

Walkways/Driveways

Grading & Drainage

Retaining Walls

Comments:

1. Due to rust and generally poor condition, front door needs to be replaced. Approx. $700.

2. Rear exterior door needs to be replaced. Approx. $500. (see fig. 4)

3. South exterior (grarge) door is improperly installed. It is recommended that door and

frame be replaced. Approx. $500. (see fig. 5)

4. South exterior overhead doors and tracks need to be replaced. Approx. $4,800.

5. Rear sliding glass doors at living room have been removed. Approx. $3,000 to install.

(see fig. 6)

6. Front porch columns appear to have been removed. It is strongly recommended that

columns be reinstalled. Approx. $1,500. (see fig. 7)

7. It should be noted that north area of yard is very wet and muddy. Multiple puddles of

water observed and soil is very loose. There appears to be no water piping in the area,

but it is strongly recommended that area be monitored for further signs of water.

Page 6: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 5 of 20

FLOOR:

Type: Concrete Slab Wood Frame

Crawl Space: None Inspected No Access

Crawl Space Walls: N/A Block/Brick Concrete

Component: N/A Normal N/R W.D.O. R/C

Concrete Slab

Crawl Space

Joist/Girders

Ventilation

Floors

Tiles

Other:

Comments:

1. Landing at rear exterior door needs to be replaced with a concrete slab. Approx. $150. (see

fig. 8)

Page 7: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 6 of 20

INTERIOR:

Component: N/A Normal N/R W.D.O. R/C

Walls

Ceilings

Doors

Windows

Stairway/Railings

Balconies/Railings

Fireplace

Cabinets/Countertops

Comments:

1. Surfacing materials and/or obstructions such as wall coverings, furniture, etc. were not

removed during the visual inspection; therefore, the condition of the wall, floor or ceiling

behind or under such item was not evaluated.

2. Master bathroom window has a damaged glass pane. Approx. $100 to replace. (see fig.

8)

3. Two damaged glass panes noted at NW bedroom. Approx. $200 to replace.

4. Front porch window frames are damaged. Approx. $200 to repair. (see fig. 9)

5. It should be noted that windows throughout house are in fair-to-poor condition and are

not protected by any impact-resistant materials.

6. Water stains noted at NE bedroom south wall. This appears to be from a previous water

leak at adjacent bathroom. (see fig. 10)

7. Ceiling at NW corner of garage is damaged. Approx. $75 to repair. (see fig. 11)

8. Kitchen cabinets and countertops are water-damaged throughout. Approx. $9,000 to redo

kitchen cabinets and countertops.

Page 8: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 7 of 20

ELECTRICAL:

Service Type: Overhead Underground

Service Line: Copper Aluminum Unknown

Household Circuits: Copper Aluminum Unknown

Type: Circuit Breaker Fuses

Component: N/A Normal N/R R/C

Exterior Wiring

Main Electrical Service

Main Panel

Interior Wiring

Switches

Receptacles

Light Fixtures

Ceiling Fans:

GFI Receptacles/Breakers: No Yes

Comments:

1. The electrical system evaluation is limited to visual observations of the components.

2. Electrical system is not properly grounded. Approx. $375 to properly ground. (see fig.

12)

3. Uncapped wiring at main panel needs to be properly capped. Approx. $20. (see fig. 13)

4. 220-volt outlet has been installed directly to main panel bus. This needs to be removed.

(see fig. 14)

5. Current main shutoff is a fuse.

6. Due to age and condition of main panel, it is strongly recommended that main panel be

replaced with a larger-capacity panel and that main shutoff be integrated into panel.

Approx. $4,000.

7. Kitchen outlets need to be replaced with GFI outlets. Approx. $225.

8. Hall bathroom outlet needs to be replaced with a GFI outlet. Approx. $75.

9. Master bathroom outlet needs to be replaced with a GFI outlet. Approx. $75.

10. Exterior outlets need to be replaced with GFI outlets. Approx. $200.

11. Kitchen light fixture needs to be replaced. Approx. $100.

12. Shutoff fuse used to power exterior well pump needs to be replaced. Approx. $300.

Page 9: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 8 of 20

HEATING & AIR CONDITIONING:

Component: N/A Normal N/R R/C

Air Conditioning

Air Handler

Condenser Unit

Heat

Ductwork

Filter

Other

Comments:

1. Heat recovery, solar systems or other supplementary systems for the heating system are

not included in this inspection.

2. There is currently no A/C installed. Approx. $5,000 to install.

3. A/C ductwork needs to be re-insulated. Approx. $2,000. (see fig. 15)

Page 10: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 9 of 20

PLUMBING:

Service for water supply system appears to be:

Municipal Water Private On-Site Water (Not Inspected)

Unknown

Water Supply Lines:

Copper PVC Cast Iron Galvanized

Polybutelene

Service for sanitary sewer system appears to be:

Municipal Water Private On-Site Water (Not Inspected) Unknown

Sanitary Sewer Lines:

PVC Cast Iron Galvanized Unknown

Component: N/A Normal N/R R/C

Water Pressure

Water Piping

Waste & Drain Piping

Kitchen Sink & Faucet

Bar Sink & Faucet

Bathroom Sink & Faucet

Bathtub & Faucet

Stall Shower & Faucet

Toilets

Bathroom Ventilation

Laundry Tub & Faucets

Comments:

1. No water analysis was performed; water softener systems and filters were not inspected.

2. Evaluation of piping was limited to visible inspection only; in-wall/under-floor piping and

other hidden plumbing components, which may exist, were not inspected.

3. Cast iron plumbing noted. All remaining cast iron piping needs to be replaced with PVC.

Approx. $20,000. (see fig. 16)

4. Master bathroom bathtub piping needs to be redone. Approx. $400. (see fig. 17)

5. Hall bathroom bathtub piping needs to be redone. Approx. $400. (see fig. 18)

6. Leak noted at hall bathroom toilet supply. Approx. $175 to repair. (see fig. 19)

7. Galvanized steel supply lines noted at well pumps. Garage well pump is improperly

installed. All galvanized supply lines, pressure tank, and both well pumps need to be

replaced. Approx. $16,000.

Page 11: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 10 of 20

WATER HEATER:

Fuel: Electric Gas Solar Heat Recovery Other

Component: N/A Normal N/R R/C

Water Heater

Piping

Pressure Release Valve

Insulated Jacket

Other:

Comments:

1. Heat recovery, solar systems or other supplementary systems for the water heater are not

included in this inspection. 2. Water heater needs to be replaced. Approx. $750. (see fig. 20)

KITCHEN & APPLIANCES:

Exhaust Fan: Vented Ductless

Component: N/A Normal N/R R/C

Refrigerator

Range Top

Oven

Exhaust Fan

Microwave

Dishwasher

Garbage Disposal

Trash Compactor

Washer (Clothes)

Dryer (Clothes)

Other:

Comments:

1. The following items are not included as part of this inspection: icemakers, cosmetic

appearances, self-cleaning oven cycle, oven temperature calibration, water filter units, water

pressure and water levels of dishwasher, and washer (clothes), thermostatic controls,

complete operating cycles, and appliance accessories.

2. Dishwasher needs to be replaced. Approx. $800.

Page 12: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 11 of 20

PAINT:

Lead Test Performed: 3M Lead Check Swabs, LOT #AAMBB20

Test Method: One swab per area tested

Areas Tested:

South Exterior Wall

West Exterior Wall

East Exterior Wall

North Exterior Wall

Water Heater Closet

Master Bedroom Window

Garage doorframes

Kitchen Pantry

Kitchen Window

SE bedroom

Results:

No trace of lead was found at any swab location.

Areas are clear of lead, there are no recommendations at this time.

Page 13: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 12 of 20

TOTAL ESTIMATED REPAIR COSTS BY SECTION

1. Roof: $ 21,000.00

2. Exterior: $ 11,000.00

3. Floor: $ 150.00

4. Interior: $ 9,575.00

5. Electrical: $ 5,370.00

6. Heating & Air Conditioning: $ 7,000.00

7. Plumbing: $ 36,975.00

8. Water Heater: $ 750.00

9. Kitchen & Appliances: $ 800.00

10. Pool/Hot Tub/Spa $ 0

Grand Total: $ 92,620.00

All cost estimates included in this report are only approximate. If a more

detailed estimate is required, it is recommended that the Client obtain a cost

estimate from a Licensed Contractor or Technician who specializes in the

specific area of expertise. Cost estimates for cosmetic repairs are not included

in this report.

Page 14: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 13 of 20

Fig. 1 – Roof is in poor condition.

Fig. 2 – SE corner of roof is damaged and improperly repaired.

Page 15: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 14 of 20

Fig. 3 – Underside of rear porch roof needs to be redone.

Fig. 4 – Rear exterior door needs to be replaced.

Fig. 5 – South exterior (garage) door is improperly installed.

Page 16: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 15 of 20

Fig. 5 – Rear sliding glass doors at living room have been removed.

Fig. 6 – Front porch columns appear to have been removed.

Fig. 7 – Landing at rear exterior door needs to be replaced with a concrete slab.

Page 17: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 16 of 20

Fig. 8 – Master bathroom window has a damaged glass pane.

Fig. 9 – Front porch window frames are damaged.

Fig. 10 – Water stains noted at NE bedroom south wall.

Page 18: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 17 of 20

Fig. 11 – Ceiling at NW corner of garage is damaged.

Fig. 12 – Electrical system is not properly grounded.

Fig. 13 – Uncapped wiring at main panel needs to be properly capped.

Page 19: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 18 of 20

Fig. 14 – 220-volt outlet has been installed directly to main panel bus.

Fig. 15 – A/C ductwork needs to be reinsulated.

Fig. 16 – Cast iron plumbing noted.

Page 20: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 19 of 20

Fig. 17 – Master bathroom bathtub piping needs to be redone.

Fig. 18 – Hall bathroom bathtub piping needs to be redone.

Fig. 19 – Leak noted at hall bathroom toilet supply.

Page 21: HOME INSPECTION REPORT - LoopNet · 2019. 9. 19. · home inspection report prepared for: kenneth privett & rosimer privett property at: 2800 sw 154 ave davie, florida prepared by:

KBC BUILDING INSPECTIONS, INC. INSPECTION REPORT

Page 20 of 20

Fig. 20 – Water heater needs to be replaced.