Upload
others
View
10
Download
1
Embed Size (px)
Citation preview
Machine Tools
HMC Maintenance Manual (Alarm) (HM 8000/F30i Series)
1
HM 8000(F30i Series) HM8000ALE2A ㅇ
Table of Contents 1. Emergency Alarm .............................................................................................................................. 4
1.1 2001 Emg. Button or Axes Emergency ....................................................................................... 4
1.2 2002 Main Spindle Servo Alarm .................................................................................................. 6
1.4 2004 Hyd. Pump Motor Overload .............................................................................................. 16
1.5 2005 Hyd. Pressure Down Alarm ................................................................................................. 18
1.6 2006 Spindle Gear Shift Check Switch Alarm .......................................................................... 21
1.7 2007 Main Power Phase & ATC SW Error ................................................................................ 26
1.8 2008 PSM Power Run Alarm ..................................................................................................... 28
1.9 2011 Hyd. Pump Motor Not Run ................................................................................................ 31
1.10 2013 Spindle Stop Signal Alarm .............................................................................................. 32
1.11 2014 Invert Fault Alarm ............................................................................................................ 33
1.12 2015 Spindle Tool Unclamp Alarm........................................................................................... 37
1.13 2017 Spindle Head Oil Overflow ............................................................................................. 39
1.14 2019 Machine Model Select Keep Relay Not Set .................................................................. 41
2. Cycle Alarm........................................................................................................................................ 42
2.1 2031 Must Be Returned To Ref. Point ....................................................................................... 42
2.2 2032 External Feed Hold (OP Push Button Switch) ................................................................. 43
2.3 2033 Air Pressure down Alarm .................................................................................................. 44
2.4 2034 Coolant & Lub. Pump Overload ....................................................................................... 46
2.5 2035 External Coolant Unit Alarm ............................................................................................. 49
2.6 2036 Coolant Level Switch Low................................................................................................. 52
2.7 2037 Power Back Up Module Error ........................................................................................ 53
2.8 2040 Operator’s Door Open Alarm ............................................................................................ 55
2.9 2049 Spindle Speed Arrival Alarm ............................................................................................. 56
2.10 2050 Spindle Rotation Malfunction .......................................................................................... 63
2.11 2051 Spindle Orientation Overtime ......................................................................................... 66
2.12 2055 Spindle Tool Clamp/Unclamp Overtime Alarm .............................................................. 69
2.13 2056 Gear Shifting Overtime ................................................................................................... 72
2.14 2058 Tool No. Select Keep Relay Not Set .............................................................................. 75
2.15 2059 T-Code Command Illegal Position ................................................................................. 79
2.16 2060 M06 Command Illegal Position ...................................................................................... 88
2.17 2061 T-Code Command Over Alarm ....................................................................................... 95
2.18 2062 M06 Command Overtime Alarm ..................................................................................... 96
2
HM 8000(F30i Series) HM8000ALE2A
2.19 2063 ATC Servo Unit Alarm .................................................................................................... 111
2.20 2064 ATC Door Open ............................................................................................................. 121
2.21 2066 Splash Guard (APC) Door Open (PMG) ...................................................................... 123
2.23 2068 Pallet Change Illegal Position ....................................................................................... 131
2.24 2086 Main Changer Overtime Alarm ..................................................................................... 135
2.25 2091 B-Axis Command Error(Inc. Dec. Point) ...................................................................... 141
2.26 2093 X-Axis APC Changer Position Switch Alarm ............................................................... 143
2.27 2094 Pallet Number Command Error .................................................................................... 145
2.28 2142 Please Turn Off And On NC Power .............................................................................. 146
3. Single Block Alarm ........................................................................................................................ 147
3.1 2160 Lub. Level Low ................................................................................................................. 147
3.2 2161 Lub. Pressure Alarm ........................................................................................................ 149
3.3 2162 Parts Count End Alarm .................................................................................................... 151
3.4 2164 Oil Cooling Unit Alarm ..................................................................................................... 152
3.5 2166 Filter Changer of TSC. Alarm.......................................................................................... 162
3.6 2167 High TSC Flow Down Alarm ........................................................................................... 164
3.7 2168 Coolant Pressure Down Alarm ....................................................................................... 166
3.8 2170 Tool Life Count End Alarm .............................................................................................. 167
3.9 2171 RST Command Alarm On STL ....................................................................................... 169
3.10 2172 Tool Length Sensor Up Status ...................................................................................... 170
3.11 2173 Wait. & Mag. Pot Tool Detect ........................................................................................ 172
3.12 2175 Hyd. Unit Oil Temperature Alarm .................................................................................. 175
4. Massage Alarm ............................................................................................................................... 176
4.1 2191 Coolant Chiller Unit Alarm ............................................................................................... 176
4.2 2193 Safety Switch Locking Alarm .......................................................................................... 177
4.3 2194 Man Axis Moving Interlock .............................................................................................. 179
4.4 2195 OP- Door Close, Must Be D-Open ................................................................................. 194
4.5 2196 Screw Conveyor Overload .............................................................................................. 196
4.6 2197 Chip Conveyor Alarm or Off Mode Alarm ....................................................................... 198
4.7 2198 Auto Power Off Ready .................................................................................................... 199
4.8 2202 Machine Lock ................................................................................................................... 200
4.9 2203 Screw Conveyor CCW Manual Mode ............................................................................ 202
4.10 2204 Feedrate Override 0% ................................................................................................... 204
4.11 2205 Measurement Device Low Battery ............................................................................... 206
4.12 2206 Measurement Device Alarm ......................................................................................... 207
4.13 2207 Machine Interference Zone Error ................................................................................. 208
4.14 2208 Machine In Service Mode ............................................................................................. 213
3
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.15 2215 Tool Length Sensor Up/Down Alarm ............................................................................ 214
4.16 2218 First, There Must Be Z-Ref. Return .............................................................................. 216
4.17 2221 5-Th Clamp/Unclamp Alarm ......................................................................................... 217
4.18 2222 Program Start Check Alarm .......................................................................................... 219
4.19 2223 B-Axis Moving Interlock Alarm...................................................................................... 221
4.20 2234 Gear Shift Lost............................................................................................................... 222
4.21 2240 ATC Not Use (K7.6 Set) ................................................................................................ 226
4.22 2241 Wait. Pot or Spindle Tool data Zero ............................................................................. 227
4.23 2243 Must Be ATC M-Changer Man. 1 Cycle ....................................................................... 229
4.24 2245 ATC Door Open Close Alarm ....................................................................................... 230
4.25 2247 T-Code or M06 Commanded States ............................................................................ 233
4.26 2250 ATC OP Manual Mode .................................................................................................. 234
4.27 2251 ATC Overtime Alarm ..................................................................................................... 235
4.28 2259 Wait Pot No. = Spindle Pot No. .................................................................................... 241
4.29 2260 Tool Mag. Rotation Over Time ...................................................................................... 243
4.30 2262 ATC Magazine Guard Door Open ................................................................................ 245
4.31 2264 Tool Magazine Servo Battery Alarm ............................................................................. 249
4.32 2265 VPF Off of Tool Magazine Alarm .................................................................................. 260
4.33 2266 Servo Mag. Tool Number Error..................................................................................... 262
4.34 2270 ATC Mag. Pot Tool Out SW. Alarm............................................................................... 263
4.35 2272 ATC Sub Changer Position Check Alarm .................................................................... 265
4.36 2273 ATC Sub Tool Arm In/Out Alarm ................................................................................... 268
4.37 2321 APC Initial Position Alarm ............................................................................................. 270
4.38 2322 APC Set-Up Station Door Open ................................................................................... 273
4.39 2323 4-Th Clamp/Unclamp Alarm ......................................................................................... 277
4.40 2324 Table or Pallet Clamp Alarm ......................................................................................... 282
4.41 2325 APC Set-Up Switch Unpush ......................................................................................... 287
4.42 2326 APC OP Manual Mode .................................................................................................. 290
4.43 2333 APC Not Use (K7.7 Set) ............................................................................................... 292
4.44 2335 APC Changer Open/Close Alarm ................................................................................. 293
4.45 2336 APC Changer Up/Down Alarm ..................................................................................... 295
4.46 2337 APC Changer 180CW/CCW Alarm .............................................................................. 297
4
HM 8000(F30i Series) HM8000ALE2A
1. Emergency Alarm
1.1 2001 Emg. Button or Axes Emergency 1) Description
The Emergency Stop push-button switch on the operation panel is pressed down, or at least one Emergency Stop limit switch for the axes is tripped.
2) Cause of problem
① The Emergency Stop push-button switch on the operation panel, ATC manual OP, APC manual OP or the chip conveyor is pressed down.
② The Emergency Stop limit switch for each axis (X, Y or Z) is pressed down. ③ An error in the Emergency Stop switch on the OP, or the Emergency Stop limit switch for
each axis, or other related parts. ④ Disconnection of the wiring.
3) Action
① Check if the red mushroom push-button switch on the OP (Main OP, ATC OP, Chip Conveyor OP) is pressed down, and if so, turn the switch counter clockwise to release it.
② If the Limit switch for any axis (X, Y, or Z) is tripped, press both the Machine Ready switch and the Emergency Release switch simultaneously to enter the Machine Ready state. (If you want to return to the emergency stop state, simply release the switch.) Then, move the problem-making axis in jog or handle mode so as to remove it from the emergency stop limit switch.
③ Check the Emergency Stop push-button switch on the main OP, the Emergency Stop limit switch on the axis, and other related parts for any problem. Repair or replace the defective part if necessary.
④ Disconnection of the wiring Refer to the circuit diagram and use the electric tester to check each terminal block. If you find an error, repair or replace the defective part.
Part Name Part No. Symbol Spec. Maker
Switch, Emergency P/B ESWPB0439 SB1,5,7,8,61 KH-3046ER-RED KACON
Switch, Limit ESWLM0111 SL1.1,2.1,3.1,5.1 D4C-4332 OMRON
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Emergency Stop X8.4
(ESP.M) -SB1,5,7,8,61 I/O Module Slot 8 XJ412 (23) ESP
5
HM 8000(F30i Series) HM8000ALE2A ㅇ
Adress Symbol Coil Comment
X8.4 ESP.M Emergency Stop
A0.0 2001 OP Emergency PB or LS Off
X33.6 MRD.M Machine Ready
R650.2 APONI Auto Power On Initial Flag
R652.7 ARST Alarm Reset
Emergency Button or
Axes Emergency
6
HM 8000(F30i Series) HM8000ALE2A
1.2 2002 Main Spindle Servo Alarm 1) Description
There occurred an alarm from the main spindle drive unit. 2) Cause of problem
① An error found in the main spindle drive unit ② An error found in the spindle motor, power cable or signal cables
3) Action
① Check the alarm number that is displayed on the main spindle drive unit of the electric cabinet. Take a necessary measure according to the alarm number. ☞ Refer to "Troubleshooting by the spindle amplifier alarm" in the appendix.
② Check the spindle motor for the 3-phase power source and the feedback cable if there is a problem.
Address Symbol Coil Comment
F45.0 ALMA Spindle Alarm
Y9.2 MRY.R Machine Ready
A0.1 2002 Main Spindle Servo Alarm
R652.7 ARST Alarm Reset
Main Spindle Servo
Alarm
Alarm Display
7
HM 8000(F30i Series) HM8000ALE2A ㅇ
8
HM 8000(F30i Series) HM8000ALE2A
◈ Reference) Troubleshooting for each of the spindle amplifier alarms
Alarm No. Description Remedy
01 Motor overheated
Check the ambient temperature and the load conditions.
If the cooling fan stops operating, replace it with a new one.
02 Excessive speed deviations
Check the load conditions and correct them if excessive.
Check and correct parameter No.4082 (correction of the acceleration/deceleration of the spindle motor)
03 Fuse blown in the DC LINK area
Replace the spindle amplifier (SPM).
Check the insulation status of the spindle motor.
Check and replace the interface cable.
04 The main power has a phase missing.
Check the state of the input power supply to the PSM.
07 Excessive speed Check and correct the spindle-related parameter.
Replace the feedback cable.
09 The main circuit is overloaded.
Check and replace the cooling fan motor and the heat sink if necessary.
If the cooling fan stops operation, replace the SPM unit.
11 Excessive voltage on the DC LINK area
Check and replace the selected power supply unit if necessary.
Check the input power voltage as well as the voltage changes during motor deceleration. If the voltage exceeds 253 VAC (for the 200V system) or 530 VAC (for the 400V system), improve the power supply impedance.
12 Excessive current on the DC LINK area
Check the insulation status of the spindle motor.
Check and correct the spindle-related parameter.
Replace the spindle amplifier (SPM).
15 An error in the spindle switch or the output switch
Check if there occurred the PMC alarm, and use the ladder to check the I/O status again.
Replace the MC magnet (usually KM20/KM21)
16 RAM error Replace the SPM control printed circuit board.
18 Rom Sum Check Error Replace the SPM control printed circuit board.
19 Excessive offset of the U-phase current
Replace the spindle amplifier (SPM).
20 Excessive offset of the V-phase current
Replace the spindle amplifier (SPM).
9
HM 8000(F30i Series) HM8000ALE2A ㅇ
Alarm No. Description Remedy
21 A polarity settings error in the position sensor
Check the parameter settings by referring to the manual. (PRM N4000N0,N4001N4)
24 An error in transmission of the serial data
(An error occurred due to the noise) Separate the CNC-To-Spindle cable from the power cable, or apply a protective device such as ferrite core.
Replace the cable.
27
Disconnection of the position coder signal
Replace the position coder cable
An error in BZ sensor or a problem with the sensor interval
29 Overload in a short time Check and correct the load status.
30 Excessive current in the input circuit
Check the state of the input power supply to the PSM.
31 Motor binding
Check and correct the load status.
Replace the feedback cable (JY2 or JY5) of the spindle motor.
32 An error in the LSI internal RAM for serial data transmission
Replace the SPM control printed circuit board.
33 Charging the DC Link is insufficient.
Insufficient capacity of the DC Link (Check and replace the power supply unit if necessary)
Replace the PSM unit.
34 A parameter settings error. Correct the parameter value according to the manual. If the parameter number is unknown, connect the spindle check board to identify the parameter.
35 Excessive gear ratio data Check the parameter settings by referring to the manual.
36 Excessive position deviations Check if the position gain value is too large, and correct the value if necessary.
37 A parameter settings error of the speed detection unit
Check the parameter settings by referring to the manual.
41
The signal for one rotation of the position coder has an error.
Check the parameter settings by referring to the manual.
An error in the position coder cable
An error in BZ sensor or a problem with the sensor interval
42 The one rotation signal of the Check and replace the position coder cable if necessary.
10
HM 8000(F30i Series) HM8000ALE2A
Alarm No. Description Remedy
position coder is not found
An error in the BZ sensor signal or a problem with the sensor interval. Readjust the BZ sensor signal or the sensor interval as appropriate.
43 Differential speed position coder disconnected
Check and replace the position coder cable if necessary.
46
The one rotation signal of the position coder on threading is not found
Check the parameter settings by referring to the manual.
Check and replace the position coder cable if necessary.
An error in the BZ sensor signal or a problem with the sensor interval. Readjust the BZ sensor signal or the sensor interval as appropriate.
47 Abnormal Position Coder Signal
Check and replace the position coder cable if necessary.
An error in the BZ sensor signal or a problem with the sensor interval.
Ensure that the position coder is properly connected to the power source line. (Be careful not to entangle the line, and apply the ferrite core to the line if possible)
49 Excessive differential speed conversion value
Ensure that the calculated differential speed value (programmed S code) does not exceed the maximum motor speed. N3772 (Maximum speed - G96)
50
Excessive speed command during spindle synchronization
Ensure that the calculated speed value (programmed S code) does not exceed the maximum motor speed.
51 DC Link Under Voltage
Check the input voltage of the power supply unit.
Check the contact state of the magnet and replace MC(KM20/KM21) if necessary.
52 ITP signal error
Replace the SPM control printed circuited board.
Replace the spindle interface printed circuit board (JA41) of the CNC machine.
53 ITP signal error
Replace the SPM control printed circuited board.
11
HM 8000(F30i Series) HM8000ALE2A ㅇ
Alarm No. Description Remedy
Replace the spindle interface printed circuit board (JA41) of the CNC machine.
54 Overload Current Check and correct the overload conditions.
55 Power Line State Signal Error
Replace the magnetic contactor. Check and replace the magnetic contactor (KM10) if necessary.
Check and correct the ladder sequence. Check and replace the magnetic contactor. (KM20/KM21)
56 Internal cooling fan stopped
Replace the spindle amplifier (SPM).
57 Excessively decelerated speed
Decrease the acceleration/deceleration duty. Measure the tension of the belt. (belt type) Check and correct the acceleration / deceleration duty. (N4082)
Check the cooling condition (ambient temperature) Check the internal temperature of the electric cabinet, and check also the (cooling) fan motor if working normally.
If the cooling fan has stopped operation, replace it as it is defective.
If the regenerative resistance value is abnormal, replace the resistor.
58 The main circuit of the converter is overloaded
Check the performance of the PSM cooling fan.
Replace the spindle amplifier (SPM).
59 The cooling fan of the converter stopped
Replace the spindle amplifier (SPM).
66
Communication error between spindle and converter
Replace the signal cable.
Check and correct the wiring of the signal cable.
73 Motor Sensor Disconnection
Replace the feedback cable.
Check the shielding of the feedback cable.
Check and correct the wiring of the feedback cable.
Adjust the position and distance of the sensor.
74 CPU Test Alarm Replace the SPM control printed circuited board.
12
HM 8000(F30i Series) HM8000ALE2A
Alarm No. Description Remedy
75 CRC Test Alarm Replace the SPM control printed circuited board.
79 Initial Test Alarm Replace the SPM control printed circuited board.
81 An error in the one-rotation signal of the motor sensor
Check and correct the parameters: N4016N6 / N4017N2
Replace the feedback cable.
Adjust the position and distance of the motor sensor.
82 An error in detecting the one-rotation signal of the motor sensor
Replace the feedback cable.
Adjust the position and distance of the motor sensor.
83 Motor sensor signal error
Replace the feedback cable.
Adjust the position and distance of the motor sensor.
84 Spindle sensor disconnected
Replace the feedback cable.
Check the shielding of the feedback cable.
Replace the feedback cable.
Check and correct the spindle-related parameter.
Adjust the position and distance of the motor sensor (position coder).
85 An error in detecting the one-rotation signal of the spindle sensor
Check and correct the spindle-related parameter.
Replace the feedback cable.
Adjust the position and distance of the motor sensor (position coder).
86 Spindle Sensor One-Rotation Signal Undetected
Replace the feedback cable.
Adjust the position and distance of the motor sensor (position coder).
87 Spindle sensor signal error
The one-rotation signal of the spindle sensor is not detected. Check the wiring and adjust the position and distance of the sensor.
88 Cooling fan stopped
Replace the motor of the cooling fan that is installed in the spindle unit.
A0 A1 A2
Program Rom Error (The Control Programming Is Not Running)
If the alarm is tripped at the moment the spindle amplifier gets applied with power, this is caused by:
-. Wrong software specification.
13
HM 8000(F30i Series) HM8000ALE2A ㅇ
Alarm No. Description Remedy
-. Defective printed circuited board. Replace The SPM or SPM Control Circuited Board.
If the alarm is issued when the motor is active, check the grounding wire. If the spindle sensor signal wire is bundled together with any motor power line, separate them.
b0 Communication Error Between Amplifier Modules
Replace the communication cable between amplifier and module.
Replace the SPM or PSM control printed circuited board.
b1
Low Converter Control Power Supply Voltage (PSM Alarm:6)
Replace the PSM control printed circuit board.
b2
Excessive converter regenerative voltage (PSM alarm: 8)
Check the regenerative resistor.
The spindle motor is defective.
Check and replace the selected power supply unit if necessary.
b3
The cooling fan of the converter radiator stopped working (PSM Alarm Indication: A)
If the cooling fan stops operating, replace it with a new one.
C0 C1 C2
Communication data alarm
Replace the communication cable between CNC and SPM.
Replace the SPM control printed circuited board.
Replace the CPM side spindle interface printed circuit board (JA41).
14
HM 8000(F30i Series) HM8000ALE2A
1.3 2003 Circuit Protect Trip
1) Description The circuit protector that is installed in the electric cabinet is tripped.
2) Cause of problem
① The circuit protector is triggered. (Abnormal signal is detected) ② An error in power control ③ The circuit protector has an error itself.
3) Action
① Find out the cause that the circuit protector is tripped. ☞ (ex) If QF22 is tripped, check the secondary circuit (L+) of QF22 if it's short-circuited,
and take a necessary measure before turning the circuit protector back on. ② If the alarm occurs but no circuit protector is tripped, measure the resistance of each
contact point, and find out the defective circuit protector, and replace it with a new one. ☞ If you measure the resistance on the contact point of the circuit protector that is turned
on, you will get "0" ohm if it's normal. ③ If you have found nothing wrong in steps ① and ② above, that is thought to be caused by
the I/O circuit board. Check the I/O board and repair or replace it if necessary.
Part Name Part No. Symbol Spec. Maker
Breaker, Auxiliary ENFBX0290K QF22,23,25,28,91 C60. 26924. Of Contact Schneider
Protector, Circuit ENFBX0266K QF22, 26 C60. 24427. 3A. 1P Schneider
Protector, Circuit ENFBX0267K QF23 C60. 24428. 4A. 1P Schneider
Protector, Circuit ENFBX0551K QF28 C60. 24436. 25A. 1P Schneider
Protector, Circuit ENFBX0264K QF81 C60. 24425. 1A. 1P Schneider
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Circuit Protector Trip X2.3
(TRIP.M) -QF Input Module Slot : 7 XJ411 (15) TRIP
Circuit Protect Trip
15
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X2.3 TRIP.M Circuit Protector Trip
A0.2 2003 Circuit Protector Trip
R652.7 ARST Alarm Reset
M
-XJ411:
1L+
X2.3
15
TRIP A5
TRIP
a1
a2 TRIPA
a1
a2 TRIPC
a1
a2 TRIPD
a1
a2 TRIPE
a1
a2
TRIPA a1
a2
TRIPC
a2
TRIPD a1
a2
TRIPE
a1
a2
-QF14
-QF15
-QF22
-QF23
-QF81
-QF26
-QF27
-QF28
-QF51
Input Module (AID32E) : Slot 7
Transformer Power Source
Transformer Power Source
Y Axis/Mag. Motor Brake
ATC Motor Brake
APC Motor Brake
DC Sol. Power Source
Lub. Motor AC110V Control Circuit
C20A: 40, 41 49, 50
Circuit Protector Trip
16
HM 8000(F30i Series) HM8000ALE2A
1.4 2004 Hyd. Pump Motor Overload 1) Description
An excessive electric current is detected in the hydraulic pump motor. 2) Cause of problem
① Burn in the hydraulic pump motor or the power cable. ② The circuit breaker that detects the excessive current is overloaded or defective itself.
3) Action
① Check and replace the pump motor or the power cable if necessary. ② Check the circuit breaker for the load settings and make correction if necessary. If the
circuit breaker itself has an error, replace it with a new one.
▪ Overload settings
QM31 : 2.2 Kw : 9.6 A QM32 : 7.5 Kw : 29 A QM36 : 3.7 Kw : 17A, 2.2Kw : 10A
Part Name Part No. Symbol Spec. Maker
Breaker, Auxiliary ENFBX0290M QM31,32,36 TESYS. GVAE20. 2A Schneider
Breaker, Circuit ENFBX0285M QM31,32,36 TESYS. GV2ME16. 9-14A Schneider
Breaker, Circuit ENFBX0260M QM36 TESYS. GV2ME21. 13-18A Schneider
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Hydraulic Motor Overload
X2.1 (HOL.M)
-QM Input Module : Slot 7 XJ411 (32) HOL
17
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X2.1 HOVL.M Hydraulic Pump Motor Overload
A0.3 2004 Hydraulic Pump Motor Overload
R652.7 ARST Alarm Reset
Hyd. Pump Motor
Overload
M -XJ411:
X2.1
32
HOL
Input Module (AID32E) : Slot 7
C20A: 40, 41 49, 50
a3
a4 HOLA
a3
a4 HOLB
a3
a4
-QM31
-QM32
-QM36
Hydraulic Pump Motor (Main)
Hydraulic Pump Motor (PMG)
HOL
A4
Hydraulic Pump Motor Overload
Hydraulic Pump Motor (Fixture)
18
HM 8000(F30i Series) HM8000ALE2A
1.5 2005 Hyd. Pressure Down Alarm 1) Description
Hyd. The pressure of the power unit falls below the setting value of the Hyd. pressure switch, causing the Hyd. pressure switch to be tripped.
2) Cause of problem
① The hydraulic power unit has an error or its pressure falls below 20kg/㎠. ② Check if the hydraulic pressure switch or if any of its parts is defective.
3) Action
① Turn the pressure valve of the hydraulic power unit clockwise to adjust the pressure to 50kg/㎠.
② Check if the hydraulic power unit pressure switch has an error, or the wiring or related component parts are defective. Hyd. Check the hydraulic power unit, the pressure switch, and the wiring from the switch to the electric cabinet as well as the I/O board, and make repair or replacement if you find a problem.
Part Name Part No. Symbol Spec. Maker
Cable, Pressure Switch ECBLS0167F -WK11 BKS B19-1-05 BALUFF
Switch Pressure R37983 -SP01 EDS810-060-0-024 HYDACS
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Hyd. Pressure Check X8.3
HDPS.M -SP31 Input Module Slot 7 XJ413(6) SP31
Hydraulic Motor Run Y2.0
HYDM.R -KA31A
Output Module Slot 2
(02) KA31A
Pressure Gauge
Pressure Control Valve
19
HM 8000(F30i Series) HM8000ALE2A ㅇ
Hydraulic Pressure Down
Aux. Hyd. Pressure
O.K Flag
Hyd. Pressure O.K
Hyd. Pressure Check Time(Main)
20
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R841.0 APOKF Aux. Pressure OK Flag
R625.3 TMB20 Hyd. Pump On Check Time
F0.6 SA Servo Ready
R630.3 HPOK Hyd. Pressure OK
A0.4 2005 Hyd. Pressure Down Alarm
R652.7 ARST Alarm Reset
A0.0 2001 OP Emergency PB or LS Off
A0.1 2002 Main Spindle servo Alarm
A0.2 2003 Circuit Protect Trip
A0.3 2004 Hyd. Pump Motor Overload
A0.5 2006 Gear Shift Check SW. Alarm
A0.6 2007 Main Power Phase & ATC SW. Error
A0.7 2008 PSM Power Run Alarm
A1.2 2011 Hyd. Pump Motor Not Run
A1.4 2013 Spindle Stop Signal Alarm
A1.5 2014 Invert Unit Fault
A1.6 2015 Spindle Tool Unclamp Alarm
A2.0 2017 Spindle Head Oil Overflow
A2.2 2019 M/C Model Select Keep/R Not Set
R647.0 APOFF Auto Power Off
F1.0 AL NC Alarm
Y0.0 HYDM.R Hydraulic Motor Run
R440.2 TMB99 Hyd. Pressure Check Time(Fix.)
K11.7 KFXHYD When Motor of Hyd. Fixture Used
K7.6 KATC ATC Not Used
R440.4 TMB101 Hyd. Pressure Check Time(PMG)
R1420.7 PMGSEL PMG Operation Selected
R629.2 TMB51 Hyd. Pressure Check Time(Main)
R441.2 TMB107 Hyd. Pressure D-Time Initial
K5.0 KHPRS Hydraulic Pressure SW. Not Used
X2.0 HPRS.M Main Hydraulic Pressure
X8.3 PHYP.M PMG Hyd. Pressure
R630.0 MRYA Machine Ready Aux.
21
HM 8000(F30i Series) HM8000ALE2A ㅇ
1.6 2006 Spindle Gear Shift Check Switch Alarm 1) Description
2 or more of 3 check switches (Low, Middle, and High) on the spindle head gear range were tripped, or none of them was tripped.
2) Cause of problem
The check switch for the main spindle gear range has short-circuited or any of its component parts is defective.
3) Action
Check the gear box switch of the main spindle if it works properly on the DGN screen, and take a necessary measure.
Note 1) Spindle Gear Shifting I/O Settings
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Spindle Gear Low X6.1
(SGL.M) -SL12
Input Module : Slot 08
XJ412 (32) SL12
Spindle Gear Middle X6.2
(GSM.M) -SL13
Input Module : Slot 08
XJ412 (48) SL13
Spindle Gear High X6.3
(GSH.M) -SL14
Input Module : Slot 08
XJ412 (15) SL14
Spindle Gear Middle Y6.3
(GRM.R) -KAR52
Output Module : Slot 2
XJ401 (6) YV14
Spindle Gear High Y6.4
(GRH.R) -KAR53
Output Module : Slot 2
XJ401 (23) YV15
Spindle Gear Low Y6.5
(GRL.R) -KAR54
Output Module : Slot 2
XJ401 (38) YV16
22
HM 8000(F30i Series) HM8000ALE2A
* Hydraulic Flow Diagram of Spindle Head
Spindle Gear Shift Check Switch Alarm
Gear Shift End Flag
YV14 YV15 YV16 Cylinder Piston
SL12 SL13 SL14
P T
Tool Unclamp
P T
A B
P T
A B
P T
A B Unclamp Middle High Low
Tool Clamp
Gear Shifter L M H
Φ1.0 Φ1.2 Φ1.0 C D E
C D E
23
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R841.1 GSTEND Gear Shift End Flag
R658.6 GOK Gear Shift O.K
X6.1 GSL.M Spindle Gear Low
X6.2 GSM.M Spindle Gear Middle
X6.3 GSH.M Spindle Gear High
R658.2 GSHON Gear Shift On
A0.5 2006 Gear Shift Check Switch Alarm
R652.7 ARST Alarm Reset
F0.6 SA Servo Ready
R624.2 TMB11 Gear Shift OK Check Time
Gear Shift O.K
Gear Shift Range Low
Gear Shift Range Middle
Gear Shift Range High
Gear Shift O.K Check Time
24
HM 8000(F30i Series) HM8000ALE2A
R657.4 SGRL Spindle Gear Range Low
R657.5 SGRM Spindle Gear Range Middle
R657.6 SGRH Spindle Gear Range High
R659.5 GRL Gear Shift Low
Y6.3 SRM.R Spindle Gear Middle
K0.6 KHM1000 If HM1000, Set To 1
Y6.4 GRH.R Spindle Gear High
Y14.4 SGRL Spindle Gear Range Low
Note 3) How to move to DGN (Diagnostic)
(1) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(2) Move to the DGN screen. ① Press the soft keys one after another to move to the DGN screen. ② Press any soft key in the right corner to activate the vertical soft key bar, and press the
[STATUS] key.
Activate the vertical soft key
1 2
25
HM 8000(F30i Series) HM8000ALE2A ㅇ
(3) Enter a desired DGN address and press [SEARCH] to display the DGN screen of your choice.
Note 4) How to read DGN (Diagnostic)
ex) X 0007 0 0 1 1 0 0 1 0 Bit 1, 4 and 5 in Address X7 turn ON while Bit 0, 2, 3, 6 and 7 turn OFF.
Symbol 0 0 1 1 0 0 1 0
Bit No Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
26
HM 8000(F30i Series) HM8000ALE2A
1.7 2007 Main Power Phase & ATC SW Error 1) Description
Two of three phases of the main power are reversely connected. An error was found in the power phase error detector that checks the phases of 3-phase power source. (K0.5 was set to 1)
2) Cause of problem
① Two of the three phases are reversely connected.(The tool clamp command signal is detected in advance of the tool unclamp command signal during the ATC tool change)
② An error in the Power Phase Error Detector (-E11) or any related part 3) Action
Turn off the machine, and switch the connection of those reversed two phases. ☞ When the power phase error detector (-E11) is properly supplied with power, then the
circuit of the internal contact "a" will be turned on.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Power Phase Error Detection
X4.5 PHAL.M
-E11 Input Module : Slot 07 XJ411(38) E11A
Spindle Tool Clamp Command
X8.7 CLMD.M
-SX43 Input Module : Slot 08 XJ412(37) SX43
SX41 Home
Position (SX41)
Unclamp Command
(SX42)
Clamp Command
(SX43)
SX42
SX43
27
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X4.5 PHAL.M Power Phase Error Detection
K0.5 KPHASE Power Phase Error Detection Used
R5323.7 TCFLT Tool Clamp Command Fault
K0.6 KHM1000 If HM1000, Set To 1
K7.6 KATC ATC Not Used
A0.6 2007 Main Power Phase & ATC SW Error
R652.7 ARST Alarm Reset
X8.7 CLMD.M Spindle Tool Command_HM4D
R5323.6 TUCCFG ATC Unclamp Command Flag
R5323.7 TCFLT Tool Clamp Command Fault
R455.0 M06CDF M06 Command Flag
R652.6 ERST External Reset
F0.6 SA Servo Ready
Main Power Phase & ATC SW Error
Tool Clamp Command Fault
28
HM 8000(F30i Series) HM8000ALE2A
1.8 2008 PSM Power Run Alarm 1) Description
The power supply module has a problem while in operation. 2) Cause of problem
There was a problem with the interoperation between KM11 and the auxiliary contact point A. 3) Action
① Check the main contactor of KM11 magnetic contactor if it operates properly and the auxiliary contact point A turns on or off according to your command of ON/OFF. ☞ KM11 magnetic contactor is supposed to turn on/off according to the signal of Machine
Ready ON/OFF. ☞ If you set "K2.0=(1)" to take the command of Servo Power ON/OFF, KM11 magnetic
contactor turns off if the door is open, and turns on if the door is close. ② Check the wiring from the auxiliary contact point to the distributed I/O module B.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Power Supply(PSM) Magnetic Contact On
X4.0 (PMON.M)
-KM11 -KM12
Input Module : Slot 07
XJ411 (7) PMON
Front Door Interlock X4.3
(OSDI.M) -S11 -S12
Input Module : Slot 07
XJ411(6) OSDI
KM11 (magnet) Auxiliary contact "a"
29
HM 8000(F30i Series) HM8000ALE2A ㅇ
Input Module (AID32E) : Slot 7
X4.0
7
M XJ412:
21,36 40,41 C20C:
Power Supply (PSM) Magnetic Contactor On
-KM11
-KM12 * Shorts, iF PSM2 (KM12) Not Used
13
14
XT411
PMON
B2
13
14
30
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R629.3 TMB52 Power Module Alarm Check Time
A0.7 2008 PSM Power Run Alarm
R652.7 ARST Alarm Reset
G8.4 B.ESP Emergency Stop
X4.3 OSDI.M Operator Side Door Interlock
R438.1 TMB82 Connect Delay Time Again
X4.0 PMON.M Power Supply(PSM) Magnet On State
K2.0 KMPOFF Use Motor Power On/Off Function
F0.6 SA Servo Ready
PSM Power Run Error
Power Module Alarm Check Time
31
HM 8000(F30i Series) HM8000ALE2A ㅇ
1.9 2011 Hyd. Pump Motor Not Run 1) Description
An error in the magnetic relay that drives the hydraulic pump 2) Cause of problem
There was a problem with the interoperation between KA23 and the auxiliary contact point A. 3) Action
① Check if KA23 magnetic relay turns on/off normally, and check also if the auxiliary contact point A actually turns on/off according to a given signal.
② Check the wiring from the auxiliary contact point to the distributed I/O module B.
Address Symbol Coil Comment
R625.3 TMB20 Hyd. Pump On Check Time
Y0.0 HYDM.R Hydraulic Motor Run
A1.2 2011 Hyd. Pump Motor Not Run
R652.7 ARST Alarm Reset
Y9.2 TMB20 Hyd. Pump On Check Time
Hydraulic Motor Not Run
Hyd. Pump Check Time
32
HM 8000(F30i Series) HM8000ALE2A
1.10 2013 Spindle Stop Signal Alarm 1) Description
The main spindle drive unit causes an error in the stop signal of the spindle. 2) Cause of problem
① An error found in the main spindle drive unit ② An error found in the spindle motor, power cable or signal cables
3) Action
① Check the alarm number that is displayed on the main spindle drive unit of the electric cabinet. Take a necessary measure according to the alarm number. ☞ Refer to "Troubleshooting by the spindle amplifier alarm" in the appendix.
② Check the spindle motor for the 3-phase power source and the feedback cable if there is a problem.
Address Symbol Coil Comment
R625.4 TMB21 Spindle Stop Signal Fault Check Time A1.4 2013 Spindle Stop Signal Alarm
R625.7 ARST Alarm Reset G70.5 SFRA Spindle Forward G70.4 SRVA Spindle Reverse G70.6 ORCMA Orientation Command F45.1 SSTA Spindle Stop Confirm F45.2 SDTA Spindle Speed Detection
Spindle Stop Signal Alarm
Spindle Stop Signal Fault Check Time
33
HM 8000(F30i Series) HM8000ALE2A ㅇ
1.11 2014 Invert Fault Alarm 1) Description
The ATC driving motor was over-currented. (Motor Overload Trip) 2) Cause of problem
① The ATC motor was overloaded. ② The ATC motor or the power cable is defective. ③ The circuit breaker that detects the excessive current is overloaded or defective itself.
3) Action
① Check if ATC is mechanically stuck. If so, find the cause of problem and solve it. ② Check and replace the ATC motor or the power cable if necessary. ② Check the circuit breaker for the load settings and make correction if necessary. If the circuit
breaker itself has an error, replace it with a new one.
Breaker Application Load
Specification QM81 ATC Control Motor(0.75KW) 3.3A
Signal Address I/O Connector (Pin) Numbering
Inverter Overload X18.7
INVF4.M Input Module : Slot 6 XJ410(46) INVF
Address Symbol Coil Comment
X15.7 INVF.M Invert Overload
K0.6 KHM1000 If HM1000, Set To 1
X18.7 INVF4.M Invert Overload_HM4D
A1.5 2014 Invert Unit Fault
R652.6 ARST Alarm Reset F0.6 SA Servo Ready
Invert Unit Fault
34
HM 8000(F30i Series) HM8000ALE2A
(Reference) Inverter Alarm Details
Display Protection Function Description
Over Current
Protection
The inverter cuts off its output when the output current of the inverter flows more than 200% of the inverter rated current. The inverter will cut off its output current if the output current exceeds 200% of the rated current of the inverter.
Over Voltage
Protection
The inverter cuts off its output if the DC voltage of the main circuit increases higher than the rated value when the motor decelerates or when regenerative energy flows back to the Inverter due to a regenerative load. This fault can also occur due to a surge voltage generated at the power supply system. The inverter will cut off its output current if the direct voltage of the main circuit exceeds the rated level in a decelerated motor speed or due to a regenerative load. This protection function may be activated due to a voltage surge in the power line.
Current Limit Protection (Overload Protection)
The inverter cuts off its output if the output current of the inverter flows at 180% of the inverter rated current for more than the current limit time (S/W). The inverter will cut off its output if the output current of the inverter exceeds 180% of the specified current limit for more than the current limit time (S/W).
Heat Sink Overheat
The inverter cuts off its output if the heat sink over heats due to a damaged cooling fan or an alien substance in the cooling fan by detecting the temperature of the heat sink. The inverter will cut off its output if the cooling fan fails to operate or the heat sink is overheat from impurities inside the cooling fan.
Electronic Thermal
The internal electronic thermal of the inverter determines the overheating of the motor if the motor is overloaded and the inverter cuts off the output. The inverter cannot protect the motor when driving a multi-pole motor or when driving multiple motors, so consider thermal relays or other thermal protective devices for each motor. Overload capacity : 150% for 1 min The built-in electronic thermal sensor detects an overload of the motor, and cuts off the output of the inverter. However, this protection does not apply to a multi-polar motor or a multi-motor inverter so it is advisable to install a thermal relay or thermal protector for each motor. ☞ Overload Withstand: 1 minute at 150% of the rated current of the motor
Low Voltage Protection
The inverter cuts off It’s output of the DC voltage is below the detection level because insufficient torque or over heating of
35
HM 8000(F30i Series) HM8000ALE2A ㅇ
Display Protection Function Description
the motor can occurs when the input voltage of the inverter drops. As a reduced power voltage of the inverter causes an insufficient torque or an overheat of the motor, this protector will cut off the output DC voltage of the inverter if the detected current of the motor falls below the specified.
Input Phase Open
The inverter cuts off the output when One or more of the input(R, S, T) phase is open and the output load is over 50% of the inverter rated current for more than 1 minute. The inverter checks whether the phase is open by detecting the DC voltage of the main circuit. If there occurs an open input phase (R, S, T), the inverter still continues to operate to the extend of 50% of the rated current of the inverter. However, the inverter will cut off its output voltage if the output current stays at over 50% for more than 10 seconds. The inverter detects the direct voltage of the main circuit and check if there is any phase lost.
Output Phase Open
The inverter cuts off Its output when the One or more of the output (U, V, W) phase is open. The inverter detects the output current to check the phase open of the output. The inverter cuts off its output voltage if one or more of the output (U, V, W) phases are open. This function detects the output current of the inverter to check if there is any open phase.
BX Protection
(Instant Cut Off)
Use for the emergency stop of the inverter. The inverter instantly cuts off the output when the BX terminal is turned On, and returns to regular operation when the BX terminal is turned Off. Take caution when using this Function. Used for the emergency stop of the inverter. The inverter instantly cuts off its output voltage if the BX terminal is turned On, and resumes normal operation as soon as the BX terminal is turned Off. Care must be taken when using this function.
Inverter Overload
The inverter cuts off it’s output when the output current of the inverter flows more than the rated level (150% for 1 minute, 200% for 0.5 seconds). The inverter cuts off its output voltage if the output current of the inverter exceeds the rated level. (150% for 1 minute, 200% for 0.5 second)
External Fault A
Use this Function if the user needs to cut off the output by an external fault signal. (Normal open contact) Use this function if you need to cut off the output of the
36
HM 8000(F30i Series) HM8000ALE2A
Display Protection Function Description
inverter because of an external error signal. (Normal open contact A)
External Fault B
Use this Function if the user needs to cut off the output by an external fault signal. (Normal close contact) Use this function if you need to cut off the output of the inverter because of an external error signal. (Normal open contact B)
Operating Method when the
Frequency Reference Is Lost Operation mode in case the frequency
reference is lost
There are 3 nodes, continue operation, decelerate and stop, and free run, according to the I/O-48 [Operating method when the frequency reference is lost] setting. There are 3 operation modes (I/O-48) available if the frequency reference is lost: continuous operation, deceleration and stop, and free run.
EEPROM Error 1
The EEPROM of keypad has a fault causing parameter read/write error. This error occurs if the keypad has a mechanical error and there is an error in reading or writing parameters.
EEPROM Error 2
The ROM version of inverter and keypad is different. This alarm is tripped to prevent a copy of parameters from the keypad to the main unit when the keypad has a different software version from that of the main unit.
Inverter H/W
Fault
A fault signal is outputted when an error occurs to the control circuitry of the inverter. There are the Wdog error, The EEP error, and the ADC offset for this fault. This alarm is tripped if there is a mechanical error in the inverter. Details include: CPU errors, EEP errors, FAN errors, GF and NTC connection errors.
CPU Error
The CPU has a fault. This is a hardware error signal that is displayed from a CPU error.
EEP Error
The EEPROM On inverter main board has a fault. This is an EEPROM error signal that is displayed from a main unit control board error.
Wiring Error
The Input/Output wiring of inverter is Wrong. Check the I/O wiring of the inverter and take a necessary action.
Fan Error
The cooling fan does not locate. This is an error signal that is displayed if the cooling fan of the inverter has a rotation error.
37
HM 8000(F30i Series) HM8000ALE2A ㅇ
1.12 2015 Spindle Tool Unclamp Alarm 1) Description
With the spindle tool clamped (the signal of unclamping the spindle tool is turned off), the signal sensor switch (clamping the spindle tool) is turned off. Or, the signal sensor switch that detects the unclamping of the spindle tool is turned on.
2) Cause of problem
① An error in adjusting the Spindle Tool Clamp switch or the Spindle Tool Unclamp sensor switch
② An error in the switch itself, the wiring, or any of its component parts 3) Action
① Adjust the switch correctly ② Check the proximity switch, the wiring, and the I/O module in this sequence. Make repair
or replacement if necessary.
Part Name Part No. Symbol Spec. Maker
Cable, Proximity S/W ECBLS0170F -WK111/116 BKS B20-1-03 Balluff Switch, Proximity/PNP ESWPX0265F -SX11/15 BES516-325-E5-C-S4 Balluff
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Spindle Tool Clamp X6.0
(STCP.M) -SX11
Input Module Slot 08
XJ412 (16) SX11
Spindle Tool Unclamp X6.5
(TUCL.M) -SX15
Input Module Slot 08
XJ412 (47) SX15
Spindle Tool Unclamp Y6.0
(STUN.R) -YV11
Output Module Slot 2
XJ401 (7) YV11
Spindle Tool Clamp (SX11)
Spindle Tool Unclamp (SX12)
0.8~1.2mm
Proximity Switch Dog
38
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R841.2 SPTCLF Spindle Tool Clamp Flag
K15.1 K#A SP. Max RPM Group A (6K,8K,20K)
X6.0 STCP.M Spindle Tool Clamp
X6.5 TUCL.M Spindle Tool Unclamp
A1.6 2015 Spindle Tool Unclamp Alarm
R652.7 ARST Alarm Reset
Y14.0 STUC.R Spindle Tool Unclamp
Y6.0 STUN.R Spindle Tool Unclamp
R5325.3 4SPTCLP Spindle Tool Clamp Command
R5325.4 4SPTUNC Spindle Tool Unclamp Command
R729.1 SPTCLP Spindle Tool Clamp Command
R729.2 SPTUNC Spindle Tool Unclamp Command
F0.6 SA Servo Ready
Spindle Tool Unclamp Alarm
Spindle Tool Clamp Flag
39
HM 8000(F30i Series) HM8000ALE2A ㅇ
1.13 2017 Spindle Head Oil Overflow 1) Description
The oil level switch in the spindle head was tripped. 2) Cause of problem
① The lubricant level in the spindle head is excessive due to an error in the oil level switch. ② The oil level switch has an error or the wiring has a problem. ③ The recovery pump motor has an error.
3) Action
① Check the spindle oil drain pump. Check the drain line filter. ② Check the oil level switch, wiring cables and I/O module, and make repair or replacement
if necessary. ③ Check if the recovery pump motor synchronizes with Machine Ready properly.
Part Name Part No. Symbol Spec. Maker
Switch Float R37112 -SV11 W-105-A(300MM) A-RYUNG
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Spindle Head Oil Overflow
X6.4 (SVOF.M)
-SV11 Input Module Slot :
08 XJ412 (31) SV11
Recovery Pump Motor
Y0.6 (REVM.R)
-QM73 Output Module : Slot
1 XJ400 (A8) KM73A
Spindle Head Oil Drain Pump
Oil Level Switch (SV11)
40
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R442.6 TMB119 Spindle Head Oil Overflow Check
A2.0 2017 Spindle Head Oil Overflow
R652.7 ARST Alarm Reset
X6.4 SVOF.M Spindle Head Oil Overflow
Spindle Head Oil Overflow
Spindle Head Oil Overflow Check
41
HM 8000(F30i Series) HM8000ALE2A ㅇ
1.14 2019 Machine Model Select Keep Relay Not Set 1) Description
The operator did not configure the Keep Relay (K0.0: HM-630, K0.1: HM-800, K0.2: HM-500) settings, or configured more than one setting.
2) Action
Check the Keep Relay settings and select a value appropriate to the machine.
Keep Relay K 0.0 K 0.1 K 0.2 K0.6
Machine HM-6300 HM-8000 HM-5000 HM1000
Address Symbol Coil Comment
K0.6 KHM1000 If HM1000, Set To 1
K0.0 KHM63 ACE-HM630 Machine
K0.1 KHM80 ACE-HM800 Machine
K0.2 KHM50 ACE-HM500 Machine
A2.2 2019 Machine Model Select Keep/R Not Set
Machine Model Select K/R Not Set
42
HM 8000(F30i Series) HM8000ALE2A
2. Cycle Alarm
2.1 2031 Must Be Returned To Ref. Point 1) Description
While not restoring the reference point manually, the operator just performed the cycle start in any of the MDI, AUTO, or TAPE mode.
2) Cause of problem
The reference point was not restored after the machine turned on. 3) Action
Restore the reference point manually. (X, Y, Z axis)
Address Symbol Coil Comment
R841.4 HOMIAL Ref. Point Return ITLK Alarm
R644.4 MLKBMV B-Axis Moving At Machine Lock
R644.2 MLKF Machine Lock On Flag
A3.6 2031 Must Be Returned To Ref. Point
X33.7 ST.M Cycle Start
R635.7 AUT Auto Mode
R652.7 ARST Alarm Reset
Must Be Returned To Ref. Point
Ref. Point Return ITLK Alarm
43
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.2 2032 External Feed Hold (OP Push Button Switch) 1) Description
An error in the signal of the feed hold switch while the program is running (in AUTO mode) 2) Cause of problem
① The feed hold switch on the main OP is tripped. ② A short-circuit or defective part in the feed hold switch
3) Action
① If you have pressed the feed hold switch by necessity, release the switch to set off the alarm. Then, you can press the Cycle Start switch to resume running the program.
② Turn the feed hold switch on/off manually and check if it works properly. If not, take a necessary action.
Address Symbol Coil Comment
X29.6 SP.M Cycle Stop
R635.7 AUT Auto Mode
F0.5 STL Cycle Start
F0.4 SPL Feed Hold
R631.0 SPCLFH Spindle & Coolant At Feed Hold
R631.3 CYSTP Cycle Stop
A3.7 2032 External Feed Hold (OP Push Button SW)
Press the Feed Holder switch
Press the Cycle Start
switch
External Feed Hold (OP Push Button SW)
44
HM 8000(F30i Series) HM8000ALE2A
2.3 2033 Air Pressure down Alarm 1) Description
The air pressure switch is tripped because the air pressure falls below the specified value. 2) Cause of problem
① The factory-supplied air pressure falls below the standard (4kg). ② The air pressure switch or any of its parts is defective.
3) Action
① Increase the factory-supplied air pressure to more than 5kg/㎠. Check the air pressure measurement displayed on the gauge of the air service unit (located on the rear panel), and if it's below 4kg/㎠, turn the air pressure handle to the right. If the gauge is no further increased, this indicates the current air pressure is not appropriate. Check the factory-supplied air pressure.
② Check the air pressure switch, wiring and I/O module if there is no error. And make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Air Pressure Check X3.1
(APRS.M) -SP12 Input Module Slot : 07 XJ411 (28) SP12
Pallet Air For Table Y7.4
(PAIR.R) -KAR65
Output Module Slot : 4
XJ401 (19) YV65
Air Pressure Switch (SP12)
Air Supply Unit
45
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X3.1 APRS.M Main Air Pressure Check
R440.7 TMB104 Air Pressure Down Check D-Time
A4.0 2033 Air Pressure Down Alarm
R652.7 ARST Alarm Reset
K5.1 KAPRS Air Pressure Switch Not Used
F0.6 SA Servo Ready
Y7.4 PAIR.R Pallet Air Table
Y15.4 PAIT.R Pallet Air For Table
Air Pressure Down Alarm
Air Pressure Down Check D-Time
46
HM 8000(F30i Series) HM8000ALE2A
2.4 2034 Coolant & Lub. Pump Overload 1) Description
An excessive electric current is detected in the coolant or lubricant pump motor. 2) Cause of problem
① The coolant or lubricant pump motor, or the power cable is burnt out. ② The circuit breaker that detects the excessive current is overloaded or defective itself.
3) Action
① Check the coolant or lubricant pump motor, or the power cable, and repair or replace a defective one if found.
② Check the circuit breaker for the load settings and make correction if necessary. If the circuit breaker itself has an error, replace it with a new one.
Breaker Application Load Specification
QM10 Spindle & Y-Axis Servo Fan Motor 1.5A
QM41 Flood Coolant Pump Motor 8.0A
QM42 TSC Coolant Pump Motor 8.0A (1.5Kw), 17.0A (3.7Kw)
QM43 Shower Coolant Pump Motor 8.0A
QM44 Flushing Coolant Pump Motor 8.0A
QM45 Coolant Gun Pump Motor 2.5A
QM73 Spindle Oil Recovery Pump Motor 2.5A
QM76 Oil Mist Collector Motor 7.8A (10.2A)
QM81 ATC Motor Control With Invert 3.3A
QM85 Tool Magazine Servo Amp 10.1A
Part Name Part No. Symbol Spec.
Breaker, Motor Circuit ENFBX0255R QM10 3RV1011-1AA10(1.1-1.6A)
Breaker, Auxiliary ENFBX0290R QM10,41,42,43, QM44,45,76,81,85
3RV1901-1F(2NO)
Breaker, Motor Circuit ENFBX0259R QM41,42,76 3RV1011-1JA10 (7-10A)
Breaker, Motor Circuit ENFBX0256R QM44,73 3RV1011-1CA10 (1.8-2.5A)
Breaker, Motor Circuit ENFBX0261R QM42,45, 3RV1021-4BA10(14-20A)
Breaker, Motor Circuit ENFBX0258R QM42/43 3RV1011-1GA10(4.5-6.3A)
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Motor Overload X2.2
(MOL.M) - Input Module : Slot 07 XJ411 (48) MOL
47
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X2.2 MOL.M Coolant & Lub. Pump Overload
A4.1 2034 Coolant & Lub. Pump Overload
R652.7 ARST Alarm Reset
M -XJ411:
X2.2
48
MOL
A4
Input Module (AID32E) : Slot 7
C20A: 40, 41 49, 50
MOL
MOLA
a1
a2 -QM10 Spd.& Y-Servo Fan
Motor
A3
A4
MOLC
-QM42 T-S-C Coolant Pump Motor
A3
A4
MOLF
-QM73 Spd. Oil Recovery Pump Motor
A3
A4
MOLI
-QM81 ATC Motor Control With Invert
A3
A4
MOLD
-QM43 Shower Coolant Pump Motor
A3
A4
MOLE
-QM44 Flushing Coolant Pump Motor
A3
A4
MOLG
-QM45 Coolant Gun Pump Motor
A3
A4
MOLH
-QM76 Oil Mist Collector Motor
A3
A4
MOLJ
-QM74 Hyd. Unit Heater
A3
A4
MOLK
-QM91 APC1 Control Motor (HM1000)
A3
A4
MOLL
-QM92 APC2 Control Motor (HM1000)
A3
A4
MOLM
-QMA1
A3
A4
-QM85 Tool Magazine Servo Amp
MOLB
A3
A4 -QM41 Flood Coolant Pump
Motor
Coolant & Lub. Motor Overload
48
HM 8000(F30i Series) HM8000ALE2A
49
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.5 2035 External Coolant Unit Alarm 1) Description
An error occurred in an external coolant unit. 2) Cause of problem
① The coolant pressure of the TSC unit has decreased, or the filter of the TSC filter unit is clogged.
② The pressure switch has an error or the wiring has a problem. 3) Action
① Take necessary measures to solve the problems of both the TSC unit and the filter. ② Check the pressure switch and the wiring, and repair or replace a defective one if
necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Coolant Pressure X3.2
(TSCA.M) -SP15 Input Module Slot 07 XJ411 (44) SP15
T.S.C Filter Status X3.3
(FILT.R) -SP16 Input Module Slot 07 XJ411 (11) SP16
External Coolant Unit Alarm
High Press. Coolant Press. Check D-Time
50
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X3.2 TSCA.M T.S.C Unit AL / Coolant Over Flow
F0.6 SA Servo Ready
K9.2 KHTC.M Tank Type High Press. TSC Used
Y0.2 CLTM.R Thru-The-Tool / Spindle Coolant
R628.5 TMB46 High Press. Check D-Time
A4.2 2035 External Coolant Unit Alarm
R652.7 ARST Alarm Reset
K12.7 KCO&MD Cool. Dual high TSC or Middle TSC
X3.3 FILT.M TSC Filter Check OK
R662.1 TFSCOF TSC Pressure S/W Checking Off
51
HM 8000(F30i Series) HM8000ALE2A ㅇ
52
HM 8000(F30i Series) HM8000ALE2A
2.6 2036 Coolant Level Switch Low 1) Description
The separation chip conveyor or drum filter chip conveyor triggers the Coolant Level alarm. 2) Cause of problem
① The coolant tank runs out of coolant. ② The Level switch has an error or the wiring has a problem.
3) Action
① Refill the coolant tank with coolant. ② Check the level switch and the wiring, and repair or replace a defective one if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Coolant Level Alarm
X3.7 (COL.M)
M250 Input Module : Slot 07 XJ411 (42) M250
Address Symbol Coil Comment
X3.7 COL.M Coolant Level Alarm
F0.6 SA Servo Ready
A4.3 2036 Coolant Level Switch Low
R652.7 ARST Alarm Reset
Coolant Level Switch Low
53
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.7 2037 Power Back Up Module Error 1) Description
A device featuring the optional power backup module has an error in the main power supply unit.
2) Cause of problem
① Power failure in the workshop ② An error in the power backup module
3) Action
① check the main power supply unit of the workshop. ② If the unit has no error but the problem persists, check the power backup module and
repair or replace it if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Power Back-Up Module On Check
X2.6 (PFM.M)
Input Module : Slot 4 -XCX16 (2) PFM
Address Symbol Coil Comment
X2.6 PFM.M Power Failure Detection
F1.7 MA NC Ready
F0.6 SA Servo Ready
K2.1 KPFM Used Power Back-Up Module
A4.4 2037 Power Back-Up Power Failure Alarm
Power Back Up Module Error
54
HM 8000(F30i Series) HM8000ALE2A
55
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.8 2040 Operator’s Door Open Alarm 1) Description
The door in the main OP side is open. 2) Cause of problem
① The door in the operator's side is open. ② The door itself has an error or the wiring has a problem.
3) Action
① Close the door. ② Check the operator's side safety switch as well as the wiring, and repair or replace a
defective one if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Operator Side Door Interlock
X4.3 (OSDI.M)
-13A Input Module : Slot
07 XJ411 (6) SODI
Address Symbol Coil Comment
X4.3 OSDI.M Operator Side Door Interlock
A4.7 2040 Operator’s Door Open Alarm
R635.7 AUT Auto Mode
X33.7 ST.M Cycle Start
R652.7 ARST Alarm Reset
A25.7 2208 Machine In Service Mode
Operator’s Door Open Alarm
56
HM 8000(F30i Series) HM8000ALE2A
2.9 2049 Spindle Speed Arrival Alarm 1) Description
After the spindle rotation command (M03, M04) was instructed, the spindle has failed to reach the instructed revolutions within 20 seconds.
2) Cause of problem
① An error found in parameter settings related to the spindle ② An error found in the signal from the main spindle drive unit ③ An error found in the signal from the position coder
3) Action
① Refer to the parameter sheet that comes with the product and check the spindle-related parameters (N3700∼N4175). Take a necessary measure if an error is found.
② Check the alarm number that is displayed on the main spindle drive unit of the electric cabinet, and take a necessary measure according to the alarm number. ☞ Refer to "Troubleshooting by the spindle amplifier alarm" in the appendix.
③ Set the parameter (N4001/N4002) to ignore the position coder settings (“1”“0”), and rotate the spindle to check if the position coder is set properly. If not, take an appropriate action.
Address Symbol Coil Comment
R626.0 TMB25 Spindle Speed Arrival Check Time
A6.0 2049 Spindle Speed Arrival Alarm
R652.7 ARST Alarm Reset
A6.1 2050 Spindle Rotation Malfunction
G70.5 SFRA Spindle Forward
G70.4 SRVA Spindle Reverse
R668.0 SARINT Spindle Speed Arrival Interlock
R658.2 SGHON Gear Shift On
Spindle Speed Arrival Alarm
Spindle Speed Arrival Check Time
57
HM 8000(F30i Series) HM8000ALE2A ㅇ
(Note) Spindle-related NC Parameter Table
(TEC:TECNOMACH DIA:U.S.A)
03623 X 1 04832 S1 0Y 1 04900 S1 00000000Z 1 04911 S1 0B 0 04912 S1 05 0 04913 S1 0
03624 X 35.0 04914 S1 0Y 50.0 04950 S1 00000000Z 50.0 04959 X 00000000B 0.0 Y 000000005 0.0 Z 00000000
? SPINDLE CONTROL [4.18] B 0000000003700 L1 00100000 5 0000000003702 L1 00000100 04960 S1 0
04961 S1 004962 S1 0
03705 L1 01001010 04963 S1 0.003708 L1 00010001 04964 S1 003716 S1 0000000103717 S1 1 04970 S1 003720 S1 4096 04971 S1 003729 S1 00000001 04972 S1 003730 S1 (#) 04973 S1 0
04974 S1 003731 S1 (#) 04976 S1 0
04977 S1 003736 L1 4095 04978 S1 003740 L1 200 04979 S1 0
05006 0000000103741 S1 50003742 S1 2000 ? CANNED CYCLES [4.20]03743 S1 6000 05101 L1 1000000103744 S1 6000 ? Canned Cycle for Drilling (1/2) [4.20.1]03751 L1 501 05114 L1 M0.1
05115 L1 M1.003752 L1 2001 ? RIGID TAPPING [4.21]
05200 L1 0000100003761 L1 271 05210 L1 29
05241 S1 27003762 L1 1151
05242 S1 115003771 L1 50
05243 S1 360003772 S1 600004800 00000000 05261 S1 150004801 S1 0000000004810 S1 0 05262 S1 1500
04811 S1 0 05263 S1 1500
04821 S1 0 05271 S1 1500
04826 S1 0 05272 S1 150004831 S1 0
EDITION DATE PAGEA01 09.02.25 8484848484848
Error pulse difference between the two spindles forturning on the spindle phase synchronizationcompletion signal
Time constant for acceleration/deceleration in rigidtapping for each gear (2nd gear) ? The Value dependson their SP. Spec.
Error pulse difference between the two spindles forissuing an alarm on spindle synchronization
Time constant for acceleration/deceleration in rigidtapping for each gear (3rd gear) ? The Value dependson their SP. Spec.
Master axis of each slave spindleunder simple synchronous spindle
Time constant for acceleration/deceleration in rigidtapping extraction (first) ? The Value depends on theirSP. Spec.Time constant for acceleration/deceleration in rigidtapping extraction (second) ? The Value depends ontheir SP. Spec.Master axis of each slave spindle
under spindle synchronous control
Spindle Motor Speed W hen Switching Fromgear 1 ToGear 2, ():Optionto Gear 2 During Tapping, ():Option
Return value of high-speed peck drilling cycle
Clearance value in a peck drilling cycle
Do. From Gear 2 To Gear 3, ():Optionto Gear 2 DuringTapping, ():Option():Option 3Bit(Sig) For Rigid Tapping Of Spindle Gear Shift
Time constant for acceleration/deceleration in rigidtapping for each gear(1st gear) ? The Value depends ontheir SP. Spec.
Drift compensation value (fourth stage)
If a T code is specified in a block where G50, G04, or G10isspecified:1: The alarm (PS0245) is issued.
#2 G83 and G87 1: Specify a peck drilling cycle
Maximum spindle speed for gear 4
Maximum spindle speed for gear 1Maximum spindle speed for gear 2Maximum spindle speed for gear 3
Time elapsed prior to checking thespindle speed arrival signal
Compensation value for the offsetvoltage of spindle speed analogSpindle Motor Maximum Clamp
Position gain multiplier (fourth stage)
Drift compensation value (first stage)
Drift compensation value (second stage)
Drift compensation value (third stage)
Number of position coder pulses Position gain multiplier (first stage)
Position gain multiplier (second stage)
Data used for adjusting the gain ofthe analog output of spindle speed
Position gain multiplier (third stage)
Number of M codes for specifying aspindle positioning angle
W hether the stop position external setting-type spindleorientation function is available(Bit 2: First spindle. Bit 3: Second spindle.)
M code specifying the spindle orientation
M code releasing the spindle positioning mode
M code for specifying a spindle positioning angle
Index / Rotary TableInterval between pitch errorcompensation positions for eachaxis
Index / Rotary TableMagnification for pitch errorcompensation for each axis
HM1000 (1 PATH) NC PARAMETER NC UNIT FS31iA
NO. DATA REMARKS NO. DATA REMARKS
Maximum spindle speed in rigid tapping (3rd gear) ?The Value depends on their SP. Spec.Maximum spindle speed
Spindle Speed W hen Switching From Gear 1To Gear 2During Tapping, ():Option():Option Maximum spindle speed in rigid tapping (1st gear) ?
The Value depends on their SP. Spec.
Motor number to each spindle Position gain
Rigid tapping mode specification M code
Do. From Gear 2 To Gear 3 DuringTapping,():Option Maximum spindle speed in rigid tapping (2nd gear) ?
The Value depends on their SP. Spec.Minimum spindle speed in constantsurface speed control mode (G96)
58
HM 8000(F30i Series) HM8000ALE2A
(TEC:TECNOMACH DIA:U.S.A)
04042 S1 30 04076 S1 33
04043 S1 30 04077 S1 (#)04080 S1 80
04044 S1 3004081 S1 20
04045 S1 30 04082 S1 1004083 S1 30
04046 S1 30 04084 S1 3004085 S1 41
04047 S1 3004086 S1 100
04048 S1 10 04087 S1 11504088 S1 75
04049 S1 1004089 S1 200
04050 S1 1004051 S1 10 04090 S1 9004052 S1 90 04091 S1 100
04053 S1 90 04092 S1 100
04054 S1 50 04094 S1 0
04055 S1 50 04095 S1 004096 S1 0
04056 S1 1200 04097 S1 004057 S1 300 04098 S1 004058 S1 10004059 S1 100 04099 S1 30004060 S1 500 04100 S1 150004061 S1 500 04101 S1 9504062 S1 500 04102 S1 175204063 S1 800 04103 S1 004064 S1 100 04104 S1 450004065 S1 2500 04106 S1 4500
04108 S1 004066 S1 2500
04109 S1 2504067 S1 2500
04110 S1 92404068 S1 2515 04111 S1 252
04112 S1 20004069 S1 300004070 S1 3000 04113 S1 290
04114 S1 004071 S1 3000
04115 S1 10004072 S1 3000 04116 S1 556404073 S1 0 04117 S1 2953004074 S1 0
04118 S1 11004075 S1 10
PAGEA01 09.02.25 9848484848485
EDITION DATE
Position gain on Cs contouring control (Low) ⓐ Motor leakage constantGrid shift on servo mode ⓐ Regular-time voltage compensation coefficient for
high-speed zone/regular-time motor voltage coefficientReference position return speed onCs contouring control/servo mode ⓐ Acceleration-time voltage compensation coefficient
for high-speed zone/acceleration-time motor voltagecoefficientDetection level for orientation completion signal
Position gain on servo mode/spindlesynchronization control (Low)
ⓐ Secondary current coefficientⓐ Criterion level for saturation related to the voltagecommand/PW M command clamp valuePosition gain on Cs contouring control (High)
Position gain on Cs contouringcontrol (Medium High)
ⓐ Slip constantⓐ Slip compensation coefficient for a high-speedzone/slip compensation coefficient at decelerationPosition gain on Cs contouring
control (Medium Low) ⓐ PW M command clamp value at deceleration
Ordinary orientation: Rate of change ⓐ Current loop proportional gainPosition gain on servo mode/spindlesynchronization control (High)
ⓐ Current loop integral gainⓐ Velocity at which the current loopintegral gain is zeroPosition gain on servo mode/spindle
synchronization control (Medium ⓐ Filter time constant for processing saturation relatedto the voltage commandPosition gain on servo mode/spindle
synchronization control (Medium ⓐ Current conversion constant
Position gain on orientation (Medium High) ⓐ Output limit for motor output specifications
Position gain on orientation (Medium Low) ⓐ Excitation voltage saturation speed at no-load
Position gain on orientation (Low) ⓐ Base speed limit ratio
Gear ratio (Medium High) Maximum speed for positionfeedback signal detectionGear ratio (Medium Low)
Gear ratio (Low) Delay time for motor excitationPosition gain on orientation (High) ⓐ Base speed of motor output specifications
Velocity loop integral gain on Cscontouring control (High)
Disturbance torque compensationconstant (acceleration feedback
Velocity loop integral gain on Cscontouring control (Low)
Adjusted output voltage of speedometer
Adjusted output voltage of loadGear ratio (High) Feedback gain of spindle speed
Velocity loop integral gain on orientation (Low) Overload detection levelVelocity loop integral gain on servo mode/spindlesynchronization control (High)
Rate of change in position gain during referenceposition return on servo mode
Velocity loop integral gain on servo mode/spindlesynchronization control (Low)
Rate of change in position gain during referenceposition return on Cs contouring control
Velocity loop integral gain on velocitycontrol mode (High)
Overspeed levelLevel for detecting excess velocitydeviation when motor is restrainedⓐ Velocity loop integral gain on
velocity control mode (Low) Level for detecting excess velocitydeviation when motor rotatesVelocity loop integral gain on orientation (High)
Velocity loop proportional gain onservo mode (Low)
Setting of acceleration/deceleration time
ⓐ Motor voltage on velocity control mode
Velocity loop proportional gain on Cscontouring control (High)
Motor voltage on orientationMotor voltage on servomode/spindle synchronization
Velocity loop proportional gain on Cscontouring control (Low) Motor voltage on Cs contouring control
Velocity loop proportional gain onorientation (High)
Ordinary orientation: Motor speedlimit value on orientation
Velocity loop proportional gain onorientation (Low)
Orientation stop position shiftⓐ Regenerative power limit for high-speed zone/regenerative power limitVelocity loop proportional gain on
servo mode (High) Delay time until motor power is cut off
HM1000 (1 PATH) NC PARAMETER NC UNIT FS31iA
NO. DATA REMARKS NO. DATA REMARKS
59
HM 8000(F30i Series) HM8000ALE2A ㅇ
(TEC:TECNOMACH DIA:U.S.A)
04119 S1 29 04330 S1 0
04120 S1 0 04334 S1 004336 S1 0
04121 S1 504340 S1 0
04122 S1 004123 S1 30 04341 S1 004127 S1 142 04344 S1 0
04345 S1 004128 S1 105 04346 S1 0
04351 S1 004129 S1 0 04352 S1 0000000004130 S1 25700 04353 S1 00000000
04355 S1 004131 S1 0 04356 S1 0
04133 S1 320 04357 S1 004134 S1 13004135 S1 0 04358 S1 0
04160 S1 0 04361 S1 004162 S1 0 04362 S1 0
04363 S1 004163 S1 0 04364 S1 0
04369 S1 004169 S1 004170 S1 0 04384 S1 004171 S1 0
04385 S1 004172 S1 0
04386 S1 004173 S1 0 04387 S1 0
04388 S1 004174 S1 0 04391 S1 0
04215 S1 0 04392 S1 0
04224 S1 0 04393 S1 004225 S1 0 04394 S1 0000000004248 S1 0 04395 S1 0000000004249 S1 0 04396 S1 0000000004250 S1 0 04397 S1 0000000004320 S1 0 04398 S1 0000000004321 S1 0 04399 S1 00000000
04400 S1 0000000004322 S1 0 04401 S1 00000000
04402 S1 0000000004323 S1 0 04403 S1 0000000004326 S1 0 04406 S1 0
04328 S1 0 04408 S1 004409 S1 0
PAGEA01 09.02.25 9848484848485
EDITION DATE
Motor acceleration at deceleration time (Low)
Acceleration limitation start speed atdeceleration time (High)
Acceleration/deceleration time constant at return to thereference position in Cs contouring control
Command multiplication for spindleorientation by position coder
Fine acceleration/deceleration time constant
Feed-forward timing adjustment coefficient
Motor acceleration at decelerationtime (Medium High)Motor acceleration at decelerationtime (Medium Low)
Spindle load monitor observer gain 1Spindle load monitor observer gain 2Motor acceleration at deceleration time (High)
Maximum amplitude in dual position feedback Resonance elimination filter 1 : damping
Dual position feedback zero w idthSpindle load monitor torque constant
Denominator of arbitrary gear ratiobetween motor sensor and spindle
Spindle EGB : synchronization ratio numerator
Spindle EGB : synchronization ratio denominator
Numerator of arbitrary gear ratiobetween motor sensor and spindle
Resonance elimination filter 1 :attenuation center frequency
Primary delay time constant in dualposition feedback
Resonance elimination filter 1 :attenuation bandwidth
Current overload alarm detection level Spindle EGB : Maximum acceleration/deceleration valuein automatic phase matchingDenominator of arbitrary gear ratio between motor
sensor and spindle (High) Spindle EGB : time constant for free-running phase matchingNumerator of arbitrary gear ratio
between motor sensor and spindle Spindle EGB : master side detector pulse count
Integral gain of velocity loop during cutting feed on Cscontouring control mode (High)
Load meter compensation 1Load meter compensation 2
Integral gain of velocity loop during cutting feed on Cscontouring control mode (Low)
Load meter compensation 3Spindle synchronization orientationdeceleration coefficientⓐ Temperature monitoring time constant
Motor model code Spindle sensor signal amplituderatio compensationⓐ Motor overheat detect level (2-word)
Grid shift during Cs contouringcontrol mode l (2-word)
Spindle sensor signal phasedifference compensation
Hysteresis of speed detection level Number of spindle sensor arbitrary teeth
ⓐ Secondary current coefficient for rigid tappingⓐ Current loop proportional gain speedcoefficient/current phase delay compensationcoefficient Motor sensor signal amplitude ratio compensation
Time constant for velocity detectingfilter (on Cs contouring control)
Motor sensor signal phasedifference compensation
Short-time overload detection time Unexpected disturbance torque detection level
ⓐ Value displayed on load meter atmaximum output
Advanced preview feed-forward coefficient
Spindle motor speed command detection levelⓐ Compensation coefficient between the specificationand TRUE base/maximum torque curve compensationcoefficient
Incomplete integration factorCurrent detection offset
ⓐ Deceleration-time excitation current change timeconstant/excitation current change time constant
Acceleration limitation start speed atdeceleration time (Low)
ⓐ Dead-band rectangular wavecomponent zero voltage/dead-band
Number of motor sensor arbitrary teeth
Switching point used for an acceleration/decelerationtime constant used for spindle synchronization controlTime constant for changing the
torque (TCMD filter time constant) Bell-shaped acceleration/deceleration time constantduring spindle synchronizationTime constant for velocity detecting filter
NO. DATA REMARKS NO. DATA REMARKS
HM1000 (1 PATH) NC PARAMETER NC UNIT FS31iA
60
HM 8000(F30i Series) HM8000ALE2A
(TEC:TECNOMACH DIA:U.S.A)
04410 S1 0
04411 S1 0
04412 S1 0
04413 S1 0
04414 S1 0
04415 S1 0
04416 S1 0
04417 S1 0
04418 S1 004419 S1 0
04420 S1 0
04421 S1 004422 S1 0
04423 S1 0
04424 S1 004498 S1 0
04499 S1 0
04500 S1 0
04501 S1 0
04502 S1 0
04503 S1 0
04508 S1 0
PAGEA01 09.02.25 9848484848485
EDITION DATE
Denominator of arbitrary gear ratio between spindlesensor and spindle (Low)
Numerator of arbitrary gear ratio between spindle sensorand spindle (Low)
Rate of change in acceleration at soft start/stop
Resonance elimination filter 3 :attenuation bandwidthResonance elimination filter 3 : damping
Spindle EGB master side : numerator of arbitrary gearratio between motor sensor and spindle
Denominator of arbitrary gear ratio between spindlesensor and spindle (High)
Numerator of arbitrary gear ratio between spindle sensorand spindle (High)
Resonance elimination filter 4 :attenuation center frequencyResonance elimination filter 4 :attenuation bandwidthResonance elimination filter 4 : damping
Spindle EGB master side : denominator of arbitrary gearratio between motor sensor and spindle
Disturbance input function :disturbance torque commandDisturbance input function : motorspeed command for measurementResonance elimination filter 2 :attenuation center frequencyResonance elimination filter 2 :attenuation bandwidthResonance elimination filter 2 : damping
Resonance elimination filter 3 :attenuation center frequency
Disturbance input function :measurement frequency intervalDisturbance input function : numberof measurements per frequency
Disturbance input function :measurement start frequencyDisturbance input function :measurement end frequency
NO. DATA REMARKS NO. DATA REMARKS
HM1000 (1 PATH) NC PARAMETER NC UNIT FS31iA
61
HM 8000(F30i Series) HM8000ALE2A ㅇ
(Note) To change the parameter settings
(1) Set the mode switch in the main OP to "MDI".
(2) Press the “OFS/SET” key in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(3) Press the [SETTING] button. ▪ The Setting screen appears where the cursor is positioned
at the “PARAMETER WRITE” item on the top. ※ If the screen is not displayed as shown in the right
picture, move to the first page of the Setting Parameter menu (“0” “NO.SRH”) and press the Page Up button three times. Then, you will see the right screen properly.
(4) Enter the number of 1, and keep pressing the INPUT and EXEC keys.
★ The “SW0100 Parameter Enable Switch ON” alarm will occur.
62
HM 8000(F30i Series) HM8000ALE2A
(5) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(6) Press the 〔PARAMETER〕 key in the soft key bar.
▪ You will see the Parameter setting screen.
☞ About the soft key bar Find a desired parameter number.
Ex) If calling parameter #4175: Enter the number of "4175" and press the [NO.SRH]soft key in the key bar to move to the Parameter N4175 screen with the cursor positioned at the number.
Used to turn ON (1) the BIT-format parameter. Ex) Press this to turn ON (1) only the highlighted BIT-format parameters.
Used to turn OFF (0) the BIT-format parameter. Ex) Press this to turn OFF (0) only the highlighted BIT-format parameters.
Used to increase or decrease a word-format parameter by adding or subtracting data. Ex) If you want to add to or subtract from the existing data included in the
parameter, enter a data value to add or subtract (In subtraction, add "-" in front of the data value.) and press this button.
Used to enter a parameter value in the word format. Ex) Regardless of the existing data, enter a data value and press this button.
The data value will be entered immediately and properly. (7) Select a navigation button that is suitable to your needs, and use it to adjust the value as
necessary. (8) When done, move back to “SETTING” and turn off “PARAMETER WRITE”(“1” ‘0”).
Then, press the “RESET” key to release the alarm.
63
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.10 2050 Spindle Rotation Malfunction 1) Description
The spindle rotation command is instructed under the condition where the spindle is prohibited from rotating.
2) Cause of problem
After the machine starts initially, the rotation command is instructed with no revolution (S-code command) specified.
3) Action
Instruct the spindle rotation command after instructing S-Code.
Spindle Rotation Malfunction
Initial S-Function On
64
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X35.6 SROT.M Manual Spindle Rotation
R654.2 SBY Spindle Stand-By
R649.6 DCL Operator Door Close Confirm
R654.1 SBYA Spindle Stand-By Aux
R635.6 MAN Manual Mode
F0.6 SA Servo Ready
R600.0 M03 Spindle Forward (CW) Rotation
R600.1 M04 Spindle Reverse (CCW) Rotation
R659.1 SFON Initial S-Function On
R626.1 TMB26 Spindle Rotation Overtime
R653.0 MEND M-Function End
R1649.2 S3601AL Command Error Over S3600
K16.7 KMTM150 Used Variable Orientation Func
Gear Shift On
Spindle Gear Range Low
Spindle Gear Range Middle
Spindle Gear Range High
65
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R658.2 GSHON Gear Shift On
A6.1 2050 Spindle Rotation Malfunction
R652.7 ARST Alarm Reset
R603.2 M29 Rigid Tapping
F7.2 SF S Function Strobe
R1649.0 M150SF Multi M150 And SF Command
R1649.1 M150CD Multi Only M150 Command
R657.0 SGL Spindle Gear Low
R657.4 SGRL Spindle Gear Range Low
R657.1 SGM Spindle Gear Middle
R657.5 SGRM Spindle Gear Range Middle
R657.2 SGH Spindle Gear High
R657.6 SGRH Spindle Gear Range High
X6.1 GSL.M Spindle Gear Low
Y6.3 GRM.R Spindle Gear Middle
K0.6 KHM1000 If HM1000, Set to 1
Y14.3 SGRM.R Spindle Gear Middle
X6.2 GSM.M Spindle Gear Middle
Y6.4 GRH.R Spindle Gear High
Y14.4 SGRH.R Spindle Gear High
X6.3 GSH.M Spindle Gear High
66
HM 8000(F30i Series) HM8000ALE2A
2.11 2051 Spindle Orientation Overtime 1) Description
Since the spindle orientation command was instructed in manual or auto mode, no completion signal is output within 15 seconds.
2) Cause of problem
① An error in parameter settings related to the spindle orientation ② An error in the position coder or defect in feedback cable
3) Action
① Check the parameters (N4042 ~ N4080) related to spindle orientation if they are set properly. If not, change the settings as appropriate.
② Check the safety switch, and wiring between sensor and spindle head terminal box, and between terminal box and spindle drive unit of the electric cabinet, and make repair or replacement if you encounter a problem.
Address Symbol Coil Comment
R625.5 TMB22 Orientation Check Time
A6.2 2051 Spindle Orientation Overtime
R652.7 ARST Alarm Reset
R602.0 M19 Spindle Orientation
R618.2 M150 Spindle Multi Orientation
R653.0 MEND M-Function End
Spindle Orientation Overtime
Orientation Check Time
67
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
G70.6 ORCMA Orientation Command
X4.2 OSDO.M Machine Door Unlock By Key Switch
R727.2 MORC Man Spindle Orientation Command
F45.7 ORARA Spindle Orientation Complete
68
HM 8000(F30i Series) HM8000ALE2A
(TEC:TECNOMACH DIA:U.S.A)
04042 S1 30 04076 S1 33
04043 S1 30 04077 S1 (#)04080 S1 80
04044 S1 3004081 S1 20
04045 S1 30 04082 S1 1004083 S1 30
04046 S1 30 04084 S1 3004085 S1 41
04047 S1 3004086 S1 100
04048 S1 10 04087 S1 11504088 S1 75
04049 S1 1004089 S1 200
04050 S1 1004051 S1 10 04090 S1 9004052 S1 90 04091 S1 100
04053 S1 90 04092 S1 100
04054 S1 50 04094 S1 0
04055 S1 50 04095 S1 004096 S1 0
04056 S1 1200 04097 S1 004057 S1 300 04098 S1 004058 S1 10004059 S1 100 04099 S1 30004060 S1 500 04100 S1 150004061 S1 500 04101 S1 9504062 S1 500 04102 S1 175204063 S1 800 04103 S1 004064 S1 100 04104 S1 450004065 S1 2500 04106 S1 4500
04108 S1 004066 S1 2500
04109 S1 2504067 S1 2500
04110 S1 92404068 S1 2515 04111 S1 252
04112 S1 20004069 S1 300004070 S1 3000 04113 S1 290
04114 S1 004071 S1 3000
04115 S1 10004072 S1 3000 04116 S1 556404073 S1 0 04117 S1 2953004074 S1 0
04118 S1 11004075 S1 10
PAGEA01 09.02.25 9848484848485
EDITION DATE
Position gain on Cs contouring control (Low) ⓐ Motor leakage constantGrid shift on servo mode ⓐ Regular-time voltage compensation coefficient for
high-speed zone/regular-time motor voltage coefficientReference position return speed onCs contouring control/servo mode ⓐ Acceleration-time voltage compensation coefficient
for high-speed zone/acceleration-time motor voltagecoefficientDetection level for orientation completion signal
Position gain on servo mode/spindlesynchronization control (Low)
ⓐ Secondary current coefficientⓐ Criterion level for saturation related to the voltagecommand/PW M command clamp valuePosition gain on Cs contouring control (High)
Position gain on Cs contouringcontrol (Medium High)
ⓐ Slip constantⓐ Slip compensation coefficient for a high-speedzone/slip compensation coefficient at decelerationPosition gain on Cs contouring
control (Medium Low) ⓐ PW M command clamp value at deceleration
Ordinary orientation: Rate of change ⓐ Current loop proportional gainPosition gain on servo mode/spindlesynchronization control (High)
ⓐ Current loop integral gainⓐ Velocity at which the current loopintegral gain is zeroPosition gain on servo mode/spindle
synchronization control (Medium ⓐ Filter time constant for processing saturation relatedto the voltage commandPosition gain on servo mode/spindle
synchronization control (Medium ⓐ Current conversion constant
Position gain on orientation (Medium High) ⓐ Output limit for motor output specifications
Position gain on orientation (Medium Low) ⓐ Excitation voltage saturation speed at no-load
Position gain on orientation (Low) ⓐ Base speed limit ratio
Gear ratio (Medium High) Maximum speed for positionfeedback signal detectionGear ratio (Medium Low)
Gear ratio (Low) Delay time for motor excitationPosition gain on orientation (High) ⓐ Base speed of motor output specifications
Velocity loop integral gain on Cscontouring control (High)
Disturbance torque compensationconstant (acceleration feedback
Velocity loop integral gain on Cscontouring control (Low)
Adjusted output voltage of speedometer
Adjusted output voltage of loadGear ratio (High) Feedback gain of spindle speed
Velocity loop integral gain on orientation (Low) Overload detection levelVelocity loop integral gain on servo mode/spindlesynchronization control (High)
Rate of change in position gain during referenceposition return on servo mode
Velocity loop integral gain on servo mode/spindlesynchronization control (Low)
Rate of change in position gain during referenceposition return on Cs contouring control
Velocity loop integral gain on velocitycontrol mode (High)
Overspeed levelLevel for detecting excess velocitydeviation when motor is restrainedⓐ Velocity loop integral gain on
velocity control mode (Low) Level for detecting excess velocitydeviation when motor rotatesVelocity loop integral gain on orientation (High)
Velocity loop proportional gain onservo mode (Low)
Setting of acceleration/deceleration time
ⓐ Motor voltage on velocity control mode
Velocity loop proportional gain on Cscontouring control (High)
Motor voltage on orientationMotor voltage on servomode/spindle synchronization
Velocity loop proportional gain on Cscontouring control (Low) Motor voltage on Cs contouring control
Velocity loop proportional gain onorientation (High)
Ordinary orientation: Motor speedlimit value on orientation
Velocity loop proportional gain onorientation (Low)
Orientation stop position shiftⓐ Regenerative power limit for high-speed zone/regenerative power limitVelocity loop proportional gain on
servo mode (High) Delay time until motor power is cut off
HM1000 (1 PATH) NC PARAMETER NC UNIT FS31iA
NO. DATA REMARKS NO. DATA REMARKS
69
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.12 2055 Spindle Tool Clamp/Unclamp Overtime Alarm 1) Description
It has passed 10 seconds since the position sensor switch of the spindle tool unclamp cylinder did not match with the applicable instruction.
2) Cause of problem
① An error in adjusting the position sensor switch ② An error in the wiring or any of its component parts
3) Action
① An error in adjusting the position sensor switch Check the sensor indicator displayed on the proximity switch (located in the rear of the spindle tool unclamping cylinder) and correct it according to the indicator.
② An error in the wiring or any of its component parts Check the proximity switch, the wiring from the proximity switch to the electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
Part Name Part No. Symbol Spec. Maker
Cable, Proximity/Switch ECBLS0170T - WWAKRT4-2 Turck
Switch, Proximity/PNP ESWPX0265F -SX11/15 BES516-325-E5-C-S4 Balluff
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Spindle Tool Clamp X6.0
(TCL.M) -SX11 Input Module : Slot 08 XJ412 (16) SX11
Spindle Tool Unclamp
X6.5 (TUCL.M)
-SX15 Input Module : Slot 08 XJ412 (47) SX15
Spindle Tool Unclamp
Y14.0 (STUC.R)
-YV11 Output Module : Slot 05 XA107 (10) YV11
70
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R626.5 TMB30 Spindle Clamp / Unclamp Check Time
A6.6 2055 Spindle Tool CL / UNCL Overtime Alarm
R652.7 ARST Alarm Reset
A1.6 2015 Spindle Tool Unclamp Alarm
Spindle Tool CL/UNC Overtime Alarm
Spindle Tool CL/UNC Overtime Alarm
Spindle Tool Unclamp (SX11)
Spindle Tool Clamp (SX15)
Spindle Tool Unclamp (SX11)
Spindle Tool Clamp (SX15)
71
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
Y14.0 STUC.R Spindle Tool Unclamp
Y6.0 STUN.R Spindle Tool Unclamp
X6.0 STCP.M Spindle Tool Clamp
K15.1 K#A Spindle Max. RPM Group A(6K,8K,20K)
X6.5 TUCL.M Spindle Tool Unclamp
F0.6 SA Servo Ready
72
HM 8000(F30i Series) HM8000ALE2A
2.13 2056 Gear Shifting Overtime 1) Description
The gear shifting is not complete within 40 seconds after the command was instructed. 2) Cause of problem
① An error found in the solenoid valve for shifting the main spindle gear, or short-circuit of or error in the gear-shift switch
② An error found in the hydraulic cylinder that shifts the gears, or the shift gear itself is defective.
3) Action
① Check the solenoid valve, limit switch, wiring cables and I/O module, and make repair or replacement if you encounter a problem.
② Turn off the machine and loosen the tube connector that is connected to the cylinder. Move the cylinder piston up or down to check if it works normally. If you feel it's clamped somewhere, repair it as necessary.
Part Name Part No. Symbol Spec.
Switch, Limit ESWLM0018A -SL12,13,14 WLD2
Solenoid Valve R30699A -YV14 K-DG4V-3-2A-M-U7-H-DI
Solenoid Valve R30691A -YV15,16 K-DG4V-3-6C-M-U7-H-DI
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Spindle Gear Low X6.1
(GSL.M) -SL12
Input Module Slot : 08
XJ412 (32) SL12
Spindle Gear Middle X6.2
(GSM.M) -SL13
Input Module Slot : 08
XJ412 (48) SL13
Spindle Gear High X6.3
(GSH.M) -SL14 Input Module Slot :08 XJ412 (15) SL14
Spindle Gear Low Y14.5
(GRM.R) -YV16 Output Module Slot 2 XJ401 (38) KAR54
Spindle Gear Middle Y14.3
(GRM.R) -YV14 Output Module Slot 2 XJ401 (6) KAR52
Spindle Gear High Y14.4
(GRH.R) -YV15 Output Module Slot 2 XJ401 (23) KAR53
73
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R625.7 TMB24 Gear Shift Overtime A6.7 2056 Gear Shift Overtime Alarm
R652.7 ARST Alarm Reset
R658.2 GSHON Gear Shift On R657.0 SGL Spindle Gear Low
R657.4 SGRL Spindle Gear Range Low
Gear Shift O.K Check Time
Gear Shift Overtime
Gear Shift On
Spindle Gear Range Low
Spindle Gear Range Middle
Spindle Gear Range High
74
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R657.1 SGM Spindle Gear Middle
R657.5 SGRM Spindle Gear Range Middle R657.2 SGH Spindle Gear High
R657.6 SGRH Spindle Gear Range High X6.1 GSL.M Spindle Gear Low
Y6.3 GRM.R Spindle Gear Middle
K0.6 KHM1000 If HM1000, Set To 1
Y14.3 SGRM.R Spindle Gear Middle
X6.2 GSM.M Spindle Gear Middle
Y6.4 GRH.R Spindle Gear High
Y14.4 SGRH.R Spindle Gear High
X6.3 GSH.M Spindle Gear High
* Hydraulic Flow Diagram of Spindle Head
Cylinder
Piston
SL12 SL13 SL14
YV14
YV15 YV16
P T
Tool Unclamp
P T
A B
P T
A B
P T
A B Unclamp Middle High Low
Tool Clamp
Gear Shifter
L M H
Φ1.0 Φ1.2 Φ1.0
C D E
C D E
75
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.14 2058 Tool No. Select Keep Relay Not Set 1) Description
An error in the Keep Relay setting that specifies the maximum number of tool pots. 2) Cause of problem
The Keep Relay setting that enables you to select the maximum number of tool pots is not specified, or more than one setting is found.
3) Action
Check the Keep Relay settings and select a value appropriate to the machine.
Address Symbol Coil Comment
R700.0 TOLSOK Tool No. Select Keep Relay Set O.K K6.3 K40TS Tool Magazine 40Tools Used K6.4 K60TS Tool Magazine 60Tools Used K6.2 K90TS Tool Magazine 90Tools Used K6.6 K120TS Tool Magazine 120Tools Used K6.0 KMATRX Matrix Tool Magazine Is Used K7.6 KATC ATC Not Used A7.1 2058 Tool No. Select Keep Relay Not Set
Tool No. Select Keep Relay Not Set
Tool No. Select Keep Relay Set O.K
76
HM 8000(F30i Series) HM8000ALE2A
(Note) To change the Keep Relay settings
(1) Set the mode switch in the main OP to "MDI".
(2) Press the “OFS/SET” key in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(3) Press the [SETTING] button. ▪ The Setting screen appears where the cursor is positioned
at the “PARAMETER WRITE” item on the top. ※ If the screen is not displayed as shown in the right
picture, move to the first page of the Setting Parameter menu (“0” “NO.SRH”) and press the Page Up button three times. Then, you will see the right screen properly.
(4) Enter the number of 1, and keep pressing the INPUT and EXEC keys.
★ The “SW0100 Parameter Enable Switch ON” alarm will occur.
77
HM 8000(F30i Series) HM8000ALE2A ㅇ
(5) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(6) Move to the Keep Relay screen.
① Press the soft keys one after another to move to the Keep Relay screen. ② Press to activate the vertical soft key in the lower right corner and press the
[KEEP RELAY] key. Activate the
vertical soft key 1 2
78
HM 8000(F30i Series) HM8000ALE2A
(7) Enter a desired Keep Relay number and press [SEARCH], or move the cursor to the Keep
Relay item and enter 1 or 0. Then, press the INPUT button. (8) When done, move back to “SETTING” and turn off “PARAMETER WRITE”(“1” ‘0”).
Then, press the “RESET” key to release the alarm.
K-Relay K6.6 K6.5 K6.4 K6.3 K6.2 K6.1 K6.0
No. of Tools 120 Tools
60 Tools 40 Tools 90 Tools Matrix
79
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.15 2059 T-Code Command Illegal Position 1) Description
When the tool magazine or ATC waiting pot had not been initialized, a tool was called (T_:). 2) Cause of problem
① A positioning error in switches that check the home position of ATC or tool magazine ② Defective component part in the switch
3) Action
① Check if the switch works properly on the DGN screen, and adjust the distance from the dog as appropriate.
② Check the Limit Switch, wiring cables and I/O module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Mag. Tool Pot Int. Tool Out
X10.0 (TPOT.M)
-SL39 Input Module Slot 8, 9 XJ413 (16) SL39
ATC Sub Changer Home Position
X10.3 (SCHP.M)
-SX33 Input Module Slot 8, 9 XJ413 (15) SX33
ATC Sub Changer Arm In
X10.1 (SCAI.M)
-SL31 Input Module Slot 8, 9 XJ413 (32) SL31
ATC Sub Changer Arm Out
X10.2 (SCAO.M)
-SL32 Input Module Slot 8, 9 XJ413 (48) SL32
ATC Waiting Pot Spindle Side
X7.6 (WPSS.M)
-SL36 Input Module Slot 8,9 XJ412 (10) SL36
ATC Waiting Pot Mag. Side
X7.7 (WPMS.M)
-SL37 Input Module Slot 8,9 XJ412 (42) SL37
※ T-Code Initial Position
Address X07.6 X07.7 X10.0 X10.1 X10.2 X10.3
Status 1 0 0 1 0 1
T-Code Command Illegal Position
80
HM 8000(F30i Series) HM8000ALE2A
T-Code Initial Position
Alarm 2059 / 2060 Aux D-Time
2059B
2059A
HD40 T-Code Initial Position
Mag. Tool Pot Tool Out Interlock
81
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R446.0 TMB145 Alarm 2059/2060 Aux D-Time
A7.2 2059 T-Code Command Illegal Position
R652.7 ARST Alarm Reset
A32.5 2262 ATC Magazine Guard Door Open
K7.6 KATC ATC Not Use
R730.5 2059B 2059B
R730.6 2060B 2060B
R732.5 2059A 2059A
F212.4 TMN-FM ATC Manual Mode From Matrix
F218.5 MTC-FM Manual Tool Pot Call From Matrix
F218.6 MTR-FM Manual Tool Pot Return From Matrix
K6.0 KMATRX Matrix Tool Magazine Is Used
R701.6 TFINP T-Code Initial Position
R460.0 TTF T-Code Strobe
R455.0 M06CDF M06 Command Flag
R702.0 TCCMDA T-Code Command Aux
R2401.4 TCCMDF T-Code Command Flag
R702.2 RTCCMD Re-Charge T-Code Command
R708.2 STSECH Spindle Tool Search
R605.2 M45 Spindle Tool No. Set
R700.2 WPTNCM Same Tool Is Commanded With Wait. Pot
R718.4 TSMDM ATC Sub Changer Manual Mode
R842.1 ATCALM ATC Alarm
R701.5 TFNP2 T-Code Initial Position2 (M6)
R701.7 TFIN3 T-Code Initial Position (RTCCMD)
R701.2 TFNP1 T-Code Initial Position1 (TCMDF)
K0.6 KHM1000 If HM1000 Set To 1
R717.2 TFINPA HM4D T-Code Initial Position
X7.7 WPMS.M Waiting Pot Magazine Side
X7.6 WPSS.M Waiting Pot Spindle Side
X10.3 SCHP.M Sub Changer Home Position
X10.1 SCAI.M Cub Changer Arm In
82
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X10.2 SCAO.M Cub Changer Arm Out
R5300.3 MTOI.M Magazine Tool Pot Tool Out Interlock
F216.2 WPDT-F Waiting Pot Tool Detect
F216.4 WPS-FM Waiting Pot Spindle Side S/w
F216.5 WPM-FM Waiting Pot Magazine Side S/w
F219.1 SCI-FM ATC Sub Changer Initial Position
X10.0 TPOT.M Magazine Tool Pot –Out Confirm
SL36 SL37 SL39
SX35
SX34
SX33 SL32 SL31
83
HM 8000(F30i Series) HM8000ALE2A ㅇ
(Reference) How to move to DGN (Diagnostic)
(1) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(2) Move to the DGN screen.
① Press the soft keys one after another to move to the DGN screen. ② Press any soft key in the right corner to activate the vertical soft key bar, and press the
[STATUS] key.
(3) Enter a desired DGN address and press [SEARCH] to display the DGN screen of your choice.
Activate the vertical soft key
1 2
84
HM 8000(F30i Series) HM8000ALE2A
◈Tool Search Sequence Chart
Tool Search Start (T _ _;)
No
★ AL 2250 “ATC OP Manual Mode” occurs ATC Sub Changer O.P Auto Mode?
▪ Turn the mode switch in the manual OP to Auto.
Yes
Searched tool No =Spd. Tool No? Yes
No
Searched tool No =Wait. Tool No? Yes
★ Tool Search Complete
No
Double Tool Search? Yes
★ 1st Tool to Tool Magazine, And 2nd Tool In Valid
No
TMG & ATC Initial Position? No
★ AL 2059 “T-Code Command Illegal Position” occurs
Confirmed : X7.7(WPMS.M) –SL37 Wait. Pot Mag. Side X7.6(WPSS.M) –SL51 Wait. Pot Spd. Side X10.3(SCHP.M) –SX41 Sub Chan. Home Pos. X10.1(SCAI.M) –SL44 Sub Changer Arm In X10.2(SCAO.M) –SL32 Sub Changer Arm Out
On
On
On Off
Off Yes
1 Sub Changer Mag. Pot Position Output : Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
Completed : X10.4(SCPP.M) –SX34 Sub Chan. Mag. Pos. On
On Off
Sub Changer Pot Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
Confirmed : X10.4(SCPP.M) –SX34 Sub Chan. Mag. PosOn
Yes
2 Sub Changer Arm Out ▪ Output: Y12.1(SCAT.R) –YV32 Sub Changer Arm Out On
Completed : X10.2(SCAO.M) –SL32 Sub Changer Arm Out On
85
HM 8000(F30i Series) HM8000ALE2A ㅇ
Sub Changer Arm Out O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.2(SCAO.M) –SL32 Sub Changer Arm Out X10.1(SCAO.M) –SL31 Sub Changer Arm In
On
Off
Yes
3 Sub Changer Wait. Pot Position Output : Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
Completed : X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos On
On Off
Sub Changer Waiting Pot Pos.? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
Confirmed : X10.5(CAWP.M)–SX35 Sub Chan.Wait. Pot Pos. On
Yes
4 Sub Changer Arm In On
Completed : X10.1(SCAO.M) –SL31 Sub Changer Arm In On
Sub Changer Arm In O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.1(SCAO.M) –SL31 Sub Changer Arm In X10.2(SCAO.M) –SL32 Sub Changer Arm Out
On Off
Yes
5 Sub Changer Home Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
▪ Completed: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. On
Off On
Sub Changer Home Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. On
Yes
6 Waiting Pot Spindle Side ▪ Output: Y12.0(WPSS.R) –YV40 Waiting Pot Spd. Side On
▪ Completed: X7.6(WPSS.M) –SL36 Waiting Pot Spindle Side On
Waiting Pot Spindle Side? No
★ AL 2291 “Waiting Pot Spd/Mag. Side Alarm” occurs
▪ Check: X7.6(WPSS.M) –SL36 Waiting Pot Spindle Side X7.7(WPMS.M) –SL32 Waiting Pot Mag. Side
On Off
Yes
Tool Search Finish
86
HM 8000(F30i Series) HM8000ALE2A
◈ Tool Re-Charge Step Sequence Chart
M06 M-Function End
4 Sub Changer Mag. Pot Position
▪ Completed: X10.4(SCPP.M) –SX34 Sub Chan. Mag. Pos. On
▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On On
Off
Off
Sub Changer Pot Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.4(SCPP.M) –SX34 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos.
On
1 Waiting Pot Magazine Side ▪ Output: Y2.7(WPMS.R) –YV30 Waiting Pot Mag. Side On
▪ Completed: X7.7(WPMS.M) –SL32 Waiting Pot Mag. Side On
Waiting Pot Spindle Side? No
★ AL 2291 “Waiting Pot Spd/Mag. Side Alarm” occurs
▪ Check: X7.6(WPSS.M) –SL36 Waiting Pot Spindle Side X7.7(WPMS.M) –SL32 Waiting Pot Mag. Side On
Off
Yes
2 Sub Changer Wait. Pot Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
▪ Completed: X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos. On
On Off
Sub Changer Waiting Pot Pos.? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.4(SCPP.M) –SX34 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos. On Yes
3 Sub Changer Arm Out ▪ Output: Y12.1(SCAT.R) –YV32 Sub Changer Arm Out On
▪ Completed: X10.2(SCAO.M) –SL32 Sub Changer Arm Out On
Sub Changer Arm Out O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.2(SCAO.M) –SL32 Sub Changer Arm Out X10.1(SCAO.M) –SL31 Sub Changer Arm In
On
Off
Yes
Yes Go to “A”
Off Off
Off
Off
87
HM 8000(F30i Series) HM8000ALE2A ㅇ
Yes
6 Sub Changer Home Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
▪ Completed: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. On
On Off
Sub Changer Home Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.4(SCPP.M) –SX34 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos.
On
Off
On
Yes
ATC Re-Charge End
5 Sub Changer Arm In ▪ Output: Y2.5(SBAI.R) –YV31 Sub Changer Arm In On
▪ Completed: X10.1(SCAO.M) –SL31 Sub Changer Arm In On
Sub Changer Arm In O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.1(SCAO.M) –SL31 Sub Changer Arm In X10.2(SCAO.M) –SL32 Sub Changer Arm Out
On Off
Yes
A
Off Off
88
HM 8000(F30i Series) HM8000ALE2A
2.16 2060 M06 Command Illegal Position 1) Description
A tool change was instructed (by M06 or manually) in other than the home position. 2) Cause of problem
① The tool had not been called before the instruction. ② A tool change command (M06:) was instructed while the tool magazine, the main
changer, the sub changer or the waiting pot was not in the initial state. 3) Action
① You should call a tool before instructing to change it. T_ _ ; M06 ; or T_ _ M06 ;
② Check the switch on the DGN screen and adjust the distance from the dog as appropriate, or check the switch, wiring cables and I/O module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Number
ing
ATC Waiting Pot Mag. Side
X7.7 (WPMS.M
) -SL37 Input Module Slot 8,9 XJ413 (42) SL37
ATC Waiting Pot Spindle Side
X7.6 (WPSS.M) -SL36 Input Module Slot 8,9 XJ413 (10) SL36
ATC Sub Chg. Home Position
X10.3 (SCHP.M) -SX33 Input Module Slot 8,9 XJ413 (15) SX33
ATC Sub Chg. Arm In
X10.1 (SCAI.M) -SL31 Input Module Slot 8,9 XJ413 (32) SL31
Mag. Tool Pot Int. Tool Out
X10.0 (TPOT.M) -SL39 Input Module Slot 8,9 XJ413 (16) SL39
Main Changer Arm Home Pos.
X8.5 (CAHP.M)
-SX41 Input Module Slot 08 XJ412 (38) SX41
Spd. Tool Unclamp Command
X8.6 (ULMD.M)
-SX42 Input Module Slot 08 XJ412 (22) SX42
Spindle Tool Clamp Command
X8.7 (CLMD.M)
-SX43 Input Module Slot 08 XJ412 (37) SX43
89
HM 8000(F30i Series) HM8000ALE2A ㅇ
※ T-Code Initial Position
Address X07.6 X07.7 X10.0 X10.1 X10.2 X10.3 X8.5 X8.6 X8.7
Status 0 1 0 1 0 1 1 0 0
Alarm 2059 / 2060 Aux D-Time
2060B
2060A
M06 Initial Position
M06 Command Illegal Position
90
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R446.0 TMB145 Alarm 2059/2060 Aux D-Time
A7.3 2060 M06 Command Illegal Position
R652.7 ARST Alarm Reset
A32.5 2262 ATC Magazine Guard Door Open
K7.6 KATC ATC Not Use
R730.5 2059B 2059B
R730.6 2060B 2060B
R73206 2060A 2060A
R709.1 M06INP M06 Initial Position
R739.4 M231INP M231 Initial Position
R2401.7 TCCMDF T-Code Command Flag
R702.0 TCCMDA T-Code Command Aux
R702.2 RTCCMD Re-Charge T-Code Command
R455.0 M06CDF M06 Command Flag
R708.2 STSECH Spindle Tool Search
R842.1 ATCALM ATC Alarm
R466.0 M06INPA HM4D M06 Initial Position
K0.6 KHM1000 If HM1000 Set To 1
HM4D M06 Initial Position
Mag. Tool Pot Tool Out Interlock
91
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R466.1 M06INPB HM10 M06 Initial Position
X7.7 WPMS.M Waiting Pot Magazine Side
X7.6 WPSS.M Waiting Pot Spindle Side
X10.3 SCHP.M Sub Changer Home Position
X10.1 SCAI.M Cub Changer Arm In
R5300.3 MTOI.M Magazine Tool Pot Tool Out Interlock
K6.0 KMATRX Matrix Tool Magazine Is Used
F216.2 WPDT-F Waiting Pot Tool Detect
R719.6 ATCMMD ATC Main OP manual Mode
R724.5 1CYATC Manual ATC Change 1 Cycle
F216.5 WPM-FM Waiting Pot Magazine Side S/w
F216.4 WPS-FM Waiting Pot Spindle Side S/w
F219.1 SCI-FM ATC Sub Changer Initial Position
X8.5 CAHP.M Main Changer Arm Home Position
X.8.6 MLMD.M Spindle Tool Unclamp Command
X8.7 CLMD Spindle Tool Clamp Command
X10.0 TPOT.M Magazine Tool Pot –Out Confirm
SL36 SL37 SL39
SX35
SX34
SX33 SL32 SL31
92
HM 8000(F30i Series) HM8000ALE2A
(Reference) How to move to DGN (Diagnostic)
(1) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(2) Move to the DGN screen.
① Press the soft keys one after another to move to the DGN screen. ② Press any soft key in the right corner to activate the vertical soft key bar, and press the
[STATUS] key.
(3) Enter a desired DGN address and press [SEARCH] to display the DGN screen of your choice.
Activate the vertical soft key
1 2
93
HM 8000(F30i Series) HM8000ALE2A ㅇ
◈ Tool Change (M06) Sequence Chart
1 ATC Change Position & M19
Spindle Orientation? No
Yes
ATC Change Position? No
Yes
2 ATC Door Open Command
Tool Change Start (M06)
ATC Door Open O.K? No
Yes
M06 Command Initial Position? No
Yes
▪ Return Y, Z to 2nd reference point & Spindle Orientation ▪ Program : G91 G30 Y0 Z0 M19 ;
▪ Completed: X12.1(ATDO.M) –SL51 ATC Door Open
▪ Check: X12.1(ATDO.M) –SL51 ATC Door Open X12.2(ATDC.M) –SL52 ATC Door Close
On Off
On
▪ Check: X7.7(WPMS.M) –SL37 Wait. Pot Mag. Side X7.6(WPSS.M) –SL51 Wait. Pot Spd. Side X10.3(SCHP.M) –SX41 Sub Chan. Home Pos. X10.1(SCAI.M) –SL44 Sub Changer Arm In X10.4(SCMP.M) –SX41 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX41 Sub Chan. Wait Pos. X10.0(TPOT.M) –SL33 Tool Pot Tool Out Int. X8.5 (CAHP.M) -SX41 M-Chen. Arm Home Pos.
★ AL 2060 “M06 Command Illegal Position” occurs
No
Yes
★ AL 2245“ATC Door Open /Close Alarm” occurs
★ AL 2060 “M06 Command Illegal Position” occurs
▪ Check: Perform the tool search. Program : T _ _;
3 ATC Changer Motor Rotation Run
Tool Unclamp Comm. SW On?
Yes
On
Off
On
On
On Off
Off On
▪ Output: Y3.4(CMFW.R) –KM81F ATC Motor Forward On
▪ Check: X8.6(MLMD.M) –SX42 Tool Unclamp Comm. On
▪ Output: Y3.0(ATDO.R) –YV38 ATC Door Open On
94
HM 8000(F30i Series) HM8000ALE2A
4 Tool Unclamp Sol. On Command ▪ Output: Y14.0(STCP.R) –YV11 Spindle Tool Unclamp On
Tool Clamp Comm. SW On?
▪ Check: X8.7(CLMD.M) –SX43 Spindle Clamp Comm.
Yes
On
5 Tool Unclamp Sol. Off Command ▪ Output: Y14.0(STCP.R) –YV11 Spindle Tool Unclamp Off
Changer Arm Home Position? ▪ Check: X8.5(CAHP.M) –SX41 Changer Arm Home Pos. On
Yes
6 ATC Changer Rotation Motor Stop ▪ Output: Y3.4(CMFW.R) –KM81F ATC Motor Forward
Off
7 ATC Door Close Command ▪ Output: Y3.1(ATDC.R) –YV38 ATC Door Close
On
▪ Completed: X13.2(CAHP.M) –SL52 ATC Door Close On
No
ATC Door Close O.K? No
Yes
★ AL 2245“ATC Door Open /Close Alarm” occurs
★ AL 2062“M06 Command Overtime” occurs
▪ Check: X12.1(ATDO.M) –SL51 ATC Door Open X12.2 (ATDC.M) –SL52 ATC Door Close On
Off
M06 completed
95
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.17 2061 T-Code Command Over Alarm 1) Description
A T code that is not appropriate to the machine is instructed. 2) Cause of problem
A larger pot number than the pot count available in the machine is called. 3) Action
Check the number of the spindle tool data and waiting tool data in "PMC" > "D-Data" and correct it appropriately and try again.
K-Relay K6.6 K6.5 K6.4 K6.3 K6.2 K6.1 K6.0
No. of Tools 120
Tools 60 Tools 40 Tools 90 Tools Matrix
Address Symbol Coil Comment
R710.0 TNOVER Tool No. Over Command Error R700.1 TFSTB TF Strobe
A7.4 2061 T-Code Command Over Alarm
R652.7 ARST Alarm Reset
K7.6 KATC ATC Not Use
R9000.1 X < Y Compare X < Y
R7002.4 TZERCF Tool No. Zero Command Flag
R4012.2 1T0COMMD T0 Command
R710.2 TNZERO Tool No. Zero Command
Tool No. Over Command Error
T-Code Command Over Alarm
96
HM 8000(F30i Series) HM8000ALE2A
2.18 2062 M06 Command Overtime Alarm 1) Description
The tool change command (M06) was instructed but not completed within 10 seconds. 2) Cause of problem
In most cases, this happens if a tool is stuck in the changer arm while it is changed.
3) Action
Move the changer arm to the home position manually and find and resolve the cause of trouble.
M06 Command Overtime Aux
M06 Command Overtime Alarm
M06 Command Overtime
M06 Command Overtime Aux 2
97
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R625.6 TMB23 M06 Command Overtime A7.5 2062 M06 Command Overtime Alarm
R652.7 ARST Alarm Reset
A7.2 2059 T-Code Command Illegal Position
A7.3 2060 M06 Command Illegal Position
A30.0 2241 Waiting Pot or Spindle Tool Data Zero
K7.6 KATC ATC Not Use
R714.2 STSECB Spindle Tool Search Aux.
K0.6 KHM1000 If HM1000 Set To 1
R714.6 4STSECB Spindle Tool Search Aux.
R730.0 TMB23C M06 Command Overtime Aux.
R631.3 CYSTP Cycle Stop
A31.1 2250 ATC OP Manual Mode
A32.5 2262 ATC Magazine Guard Door Open
R2401.7 TCCMDF T-Code Command Flag
R702.2 RTCCMD Re-Charge T-Code Command
R708.2 STSECH Spindle Tool Search
R736.0 TMB23A M06 Command Overtime Aux.
R736.1 TMB23B M06 Command Overtime Aux. 2 R649.6 DCL Operator Door Close Confirm
K16.7 KMTM150 Used Variable Orientation Func.
F218.5 MTC-FM Manual Tool Pot Call From matrix
F218.6 MTR.FM Manual Tool Pot Return From matrix
K6.0 KMATRX Matrix Tool Magazine Is Used
Y10.3 SVON.R TMG Servo On
R711.4 SPSTSH Spindle Tool Search Keep
K18.7 KUCENT Keep U-Center Is Used
R600.3 M06 ATC Change Macro Call
F0.5 STL Cycle Start
R5321.0 MANM06 Manual ATC Cycle Command
X12.1 ATDO.M ATC Door Open
K10.3 KATVDR ATC Door Not Used
98
HM 8000(F30i Series) HM8000ALE2A
▣ Return to the home position of the ATC changer arm
If the changer arm is stopped for any reason while changing the tools (M06), you must return the changer arm to the home position manually.
However, the countermeasures may differ according to the cause of trouble. So please find out the exact cause before restoring or repairing the machine.
(1) If the changer arm is stuck while trying to pull out a tool from the spindle (in the state of
Tool Unclamp) In most cases, this happens when the changer arm is stuck in the spindle while trying to pull out a tool after tool unclamping is performed
, causing to trigger the " 2062 M06 Command Over Time” alarm.
(2) If the changer arm is stuck in the spindle after changing a tool (in the state of Tool Clamp) In most cases, this happens when the changer arm gripper is stuck in a tool after the changer arm changed the tool and performed the tool clamping
, causing to trigger the " 2062 M06 Command Overtime” alarm.
(3) If the changer arm has stopped operation irrelevantly to the spindle This happens if the machine is emergency stopped or there occurs a power failure while performing the tool changing.
▶ ATC Recovery
1) If this happens due to the emergency stop or power failure, take an appropriate measure to solve the problem and turn power back on before entering Machine Ready.
2) Turn the mode switch in the main OP to “JOG”.
99
HM 8000(F30i Series) HM8000ALE2A ㅇ
3) Press the CUSTOM1 button from the button bar of the main OP. ☞ The “PMC Switch” screen appears.
4) Press the MANUAL soft key from the bottom soft
key bar. ☞ The “ATC APC Manual Switch” screen appears.
5) Press the ATC-ON soft key from the bottom soft key
bar. ☞ From the “ATC APC Manual Switch” screen, you
will notice that the “ATC Manual Mode” is turned on.
6) Depending on the operation that you want to perform, select “TOOL CHANGE STEP
REVERSE” (6-1), (6-3) or “TOOL CHANGE STEP FORWARD” (6-2).
100
HM 8000(F30i Series) HM8000ALE2A
6-1) If the changer arm is stuck while trying to pull out a tool from the spindle From the “ATC Manual Switch” screen, select “TOOL CHANGE STEP REVERSE”. ☞ If the machine is in the state of tool unclamping, manually perform the tool clamping
before proceeding. ▪ How to confirm the state of spindle tool unclamping
Check if the spindle emits the collet air (in MDI or Auto mode), or check if the button indicator of Tool Unclamp on the manual OP turns on.
6-2) If the changer arm is stuck in the spindle after changing a tool
From the “ATC Manual Switch” screen, select “TOOL CHANGE STEP FORWARD”.
6-3) If the changer arm has stopped operation irrelevantly to the spindle (in the state of Spindle Unclamp) From the “ATC Manual Switch” screen, select “TOOL CHANGE STEP REVERSE”.
7) Repeat pressing briefly the “START” button in the
ATC manual OP until the main changer arm moves to the home position where it doesn't move further.
For 6-1 above: In this case, the changer arm is stuck in the spindle for a reason while changing a tool.
Return the changer arm to the home position and find the cause by performing the tool unclamping manually.
※ If the manual tool unclamping does not work at all, gently impact on the tool to remove it with the hammer. Then, check the tool kick distance, the state of the unclamp cylinder, collet, and the tapering side of the spindle or tool to find out the cause of trouble and take a necessary measure.
For 6-2 above: This happens when the gripper of the changer arm is stuck in the tool. If the problem persists after following the steps below, use a rubber hammer to impact on the end of the changer arm so that the gripper can be removed. Then, pull out the changer arm and return it to the home position. Find out the cause of trouble and take a necessary action. (check the tool and check also if ATC is aligned properly)
For 6-3 above: This kind of trouble shooting will be made manually while the tools are inserted in the changer arm. Just in case of a fall of the tool, prepare a shock absorber such as wood palette under the machine, so that it can protect the machine from the possible fall.
101
HM 8000(F30i Series) HM8000ALE2A ㅇ
① If the spindle is in the process of tool clamping, manually perform the tool unclamping. ▪ How to confirm the state of spindle tool
unclamping Check if the spindle emits the collet air (in MDI or Auto mode), or check if the button indicator of Tool Unclamp on the manual OP turns on.
② Repeat briefly pressing the “START” button
until the tool in the changer arm inserts to the spindle completely.
☞ An excessive number of pressing may get the changer arm off of the spindle, causing a fall of the tool. So you must stop pressing the button when the tool is inserted nearly to the end of the spindle.
③ Press the Tool Clamp button to manually perform the tool clamping on the spindle.
☞ Ensure that the Unclamp button should be turned off.
④ Repeat briefly pressing the “START” button until the changer arm reaches the home position and wouldn't move further.
☞ If the main changer arm doesn't move further even by your pressing the “START” button, this indicates that the main changer arm reaches its home position.
Then, the “2243 Must Be ATC M-Changer Man. 1 Cycle” alarm will be displayed on the NC screen.
8) From the "ATC Manual Switch" screen, select
“TOOL CHANGE 1 CYCLE”, and press the “START” button to perform the tool changing automatically. Then, the alarm 2067 will be released and the ATC home position will be restored.
☞ If the Tool Change 1 Cycle operation is not performed, check the “Conditions of Manual Tool Change 1 Cycle” below:
※Conditions of Manual Tool Change 1 Cycle ① ATC Door Open (X12.1), or If there is no door at all: K10.3 (ATC Door Not Used) ② Both Y and Z axes are in the ATC change positions (Y-axis and Z-axis 2nd reference
points): This will be ignored if alarm AL2243 has occurred.
102
HM 8000(F30i Series) HM8000ALE2A
③ Switch the mode selection switch on the ATC manual OP to “MA NUAL”. ④ M06 Initial Position
▪ Waiting Pot Spindle Side(X10.3), ▪ Sub Changer Home Position(X10.3), ▪ Sub Changer Arm In (X10.1), ▪ ATC Main Changer Home Position (X8.5) ▪ Operator Door Close Confirm (X4.1, X4.3)
⑤ Servo Ready 7) From the “ATC Manual Switch”, select “DOOR
CLOSE” and press the “START” button to close the door.
8) From the PMC DATA screen, check the tool number (D450) in the spindle as well as the tool
number (D452) in the waiting pot, and make correction if necessary. When each axis returns to their respective home position, ATC troubleshooting is completed.
D450 : Tool number in the spindle
D452 : Tool number in the waiting pot
103
HM 8000(F30i Series) HM8000ALE2A ㅇ
※ Reference) Adjusting the position of the ATC arm (centering)
* If you re-assemble the ATC arm, you must perform the centering of the spline and ATC arm.
1) Preparations for centering the ATC arm ① Move the Y and Z axes to their respective
secondary reference point. ▪ Program : G91 G30 Y0 Z0 ;
② Clamp a spline-specific centering fixture into the spline and perform the spline orientation. ▪ Program : M19 ;
③ Insert the arm fixture to the changer arm, and move the changer arm to the change position manually.
2) Loosen the bolt on the locking element, and
install the ATC arm fixture at the end of the arm.
※ Reference) ATC Arm Fixture
Centering Fixture
25
100
20
30
42 42 M10×1.25 Tap
Φ11 Drill
▪Necessary Parts 3-BB10×40
15
30
Locking Element
Fixture
104
HM 8000(F30i Series) HM8000ALE2A
3) Move the ATC changer arm slowly to find out the exact position. ① Use the push bolts on both sides and the pull bolt in the center to adjust the gap between
changer arm fixture and spline fixture to 3.2mm.
② While impacting on the end of the changer arm using a plastic hammer, fit the centering
fixture to the end smoothly.
③ Leave the fixture in the current position and
tighten the element locking bolts from inch by inch to as tight as possible.
④ Remove the fixture and tighten the element
locking bolts in the fixture place from inch by inch to as tight as possible.
Gap: 3.2mm
Fixture
Push Bolt
Push Bolt
Pull Bolt
105
HM 8000(F30i Series) HM8000ALE2A ㅇ
* Insert the intended tool into the spline or tool boy, and move the changer arm near the tool manually. Then, release the changer motor brake and rotate the arm manually until it contacts on the tool. Check inside of the taper area and make a gap between. ▪ Correction Target: 0.3∼0.5mm
4) Install C60075314A cap.
▪ 4-BB5×8
5) Insert all the covers that were previously removed to their respective position, and perform the test run to check if they are installed properly.
0.3∼0.5mm
3.2±0.2mm
Changer Arm
Cap
Cap
106
HM 8000(F30i Series) HM8000ALE2A
※ Reference) Reset the reference point for ATC servo magazine
If the ATC sub changer and the tool pot of the magazine do not align properly due to mis-position of the ATC servo pot, you must restore the reference point of the ATC servo magazine manually. 1) Move the tool pot #1 to the changer position, and install the centering fixture between tool pot
and sub changer.
2) Change the value of "Keep Relay K12.2" to 1.
▪ K12.2(KMATC) : If you want to adjust the position of ATC changer, set it to 1. (This will control the servo motor regardless of the changer arm position)
3) Press the MODE key on the start screen [r 0000] of the servo drive to display [ rd-off ].
[ rd-off ] : Ready to operate the jog run
4) From the [ rd-off ] screen, press the down arrow button to display [ Jog.run ].
[ Jog.run ] : Switch to the jog run mode
Sub Changer Centering
Fixture
Centering Fixture
107
HM 8000(F30i Series) HM8000ALE2A ㅇ
5) From the [Jog.run] screen, press the SET key to display [ Jr.0000].
[ Jr.0000 ] : Jog run mode
6) From the [Jr.0000 ] screen, use the up/down arrow keys to
rotate the magazine in a desired direction. In such a way, adjust the pot position.
Fine-tune the magazine position
▪ If you want to fine-tune the magazine position, set parameter #27 to a lower value.
※ Centering the tool pot of the tool magazine
Use the up/down arrow buttons on the [ Jr.0000 ] screen, or press the rotation button on the manual operation panel. While holding the button, insert the center bar into the centering fixture until it is inserted smoothly. ▪ When completed, the coordinates of the tool magazine will match with the actual position.
108
HM 8000(F30i Series) HM8000ALE2A
7) When the centering of the tool magazine's tool pot is completed, press the SET key. [ Jog.run ] : Return to the jog run mode
8) In the [ Jog.run ] screen, press the MODE key to display [ rd-off ].
[ rd-off ] : Ready to operate the jog run
9) In the [ rd-off ] screen, press the up arrow key to display [ Org.S - - ]. [ Org.S - - ] : Origin mode
10) From the [Org.S - - ] screen, press and hold the SET key for 7 seconds. The screen will
blink and switch to [r 0001 ]. [ r 0001 ] : Return to the start screen
11) Turn off the machine and turn it back on. This is the completion of resetting the reference
point.
109
HM 8000(F30i Series) HM8000ALE2A ㅇ
◈ Tool Change (M06) Sequence Chart
1 ATC Change Position & M19
Spindle Orientation? No
Yes
ATC Change Position? No
Yes
2 ATC Door Open Command
Tool Change Start (M06)
ATC Door Open O.K? No
Yes
M06 Command Initial Position? No
Yes
▪ Return Y, Z to 2nd reference point & Spindle Orientation ▪ Program : G91 G30 Y0 Z0 M19 ;
▪ Completed: X12.1(ATDO.M) –SL51 ATC Door Open
Confirmed: X12.1(ATDO.M) –SL51 ATC Door Open X12.2(ATDC.M) –SL52 ATC Door Close
On Off
On
Confirmed: X7.7(WPMS.M) –SL37 Wait. Pot Mag. Side X7.6(WPSS.M) –SL51 Wait. Pot Spd. Side X10.3(SCHP.M) –SX41 Sub Chan. Home Pos. X10.1(SCAI.M) –SL44 Sub Changer Arm In X10.4(SCMP.M) –SX41 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX41 Sub Chan. Wait Pos. X10.0(TPOT.M) –SL33 Tool Pot Tool Out Int. X8.5 (CAHP.M) -SX41 M-Chen. Arm Home Pos.
★ AL 2060 “M06 Command Illegal Position” occurs
Tool Search O.K?
No
Yes
★ AL 2245“ATC Door Open /Close Alarm” occurs
★ AL 2060 “M06 Command Illegal Position” occurs
▪ Check: Perform the tool search. Program : T _ _;
3 ATC Changer Motor Rotation Run
Tool Unclamp Comm. SW On?
Yes
On
Off
On
On
On Off
Off On
▪ Output: Y3.4(CMFW.R) –KM81F ATC Motor Forward On
▪ Check: X8.6(MLMD.M) –SX42 Tool Unclamp Comm. On
▪ Output: Y3.0(ATDO.R) –YV38 ATC Door Open On
110
HM 8000(F30i Series) HM8000ALE2A
4 Tool Unclamp Sol. On Command ▪ Output: Y14.0(STCP.R) –YV11 Spindle Tool Unclamp On
Tool Clamp Comm. SW On?
▪ Check: X8.7(CLMD.M) –SX43 Spindle Clamp Comm.
Yes
On
5 Tool Unclamp Sol. Off Command ▪ Output: Y14.0(STCP.R) –YV11 Spindle Tool Unclamp Off
Changer Arm Home Position? ▪ Check: X8.5(CAHP.M) –SX41 Changer Arm Home Pos. On
Yes
6 ATC Changer Rotation Motor Stop ▪ Output: Y3.4(CMFW.R) –KM81F ATC Motor Forward
Off
7 ATC Door Close Command ▪ Output: Y3.1(ATDC.R) –YV38 ATC Door Close
On
▪ Completed: X13.2(CAHP.M) –SL52 ATC Door Close On
No
ATC Door Close O.K? No
Yes
★ AL 2245“ATC Door Open /Close Alarm” occurs
★ AL 2062“M06 Command Overtime” occurs
▪ Check: X12.1(ATDO.M) –SL51 ATC Door Open X12.2 (ATDC.M) –SL52 ATC Door Close On
Off
M06 completed
111
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.19 2063 ATC Servo Unit Alarm 1) Description
The servo motor inverter that drives the tool magazine tripped an alarm. 2) Cause of problem
① An error in the servo motor inverter ② An error in the servo motor or the wiring
3) Action
Refer to the servo motor manual, and repair or replace the defective part. ☞ Refer to "Troubleshooting by the servo drive alarm".
Signal Address Device Symbol I/O Connector
(Pin) Numbering
TMG Servo Alarm X13.7
(TALM.M) - Input Module : Slot 7,9 XJ413 (33) ALM
Address Symbol Coil Comment
X13.7 TALM.M TMG Servo Alarm
A7.6 2063 ATC Servo Unit Alarm
R652.7 ARST Alarm Reset
K7.6 KATC ATC Not Use
ATC Servo Unit Alarm
112
HM 8000(F30i Series) HM8000ALE2A
Tool Magazine Servo Amp
113
HM 8000(F30i Series) HM8000ALE2A ㅇ
◈ Refer to "Troubleshooting by the servo drive alarm".
(1) UV (Under Voltage) Alarm : This alarm warns that the main unit is running out of direct voltage.
Message on the front
display
Description This alarm is tripped when the internal DC link voltage falls below the set value.
Troubleshooting
▪ Measure the input voltage on the drive terminal box to check if the tester reads between 200V and 220V. If not, take a necessary measure to adjust the voltage to between 200V and 220V.
▪ Check if the motor has a short circuit. If so, replace the motor cables
wherever applicable. ▪ Then, turn off the servo drive and turn it back on. See if there occurs the
same alarm. If so, replace the drive because this alarm is tripped from the defective drive.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
(2) OH (Over Heat) Alarm : This is a overheat alarm.
Message on the front
display
Description This alarm is tripped if the internal IPM device is overheat or has an error.
Troubleshooting
▪ Turn off the servo drive and wait until it cools down. Then, turn it back on and see if the same alarm occurs again. If the problem persists, replace the drive because the IPM module of the drive is defective.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Select two from L1, L2, and L3, and measure the voltage between two terminals.
114
HM 8000(F30i Series) HM8000ALE2A
(3) OV (Over Voltage) Alarm : This alarm warns that the direct voltage to the main unit is excessive.
Message on the front
display
Description This alarm is tripped when the internal DC link voltage falls below the set value.
Troubleshooting
▪ Measure the input voltage on the drive terminal box to check if the tester reads between 200V and 220V. If not, take a necessary measure to adjust the voltage to between 200V and 220V.
▪ Remove the drive and disconnect the regenerative resistor connector to
check if the regenerative resistor (installed at a side of the drive) measures at 26Ω. If not, replace the resistor.
▪ Check if the motor has a short circuit. If so, replace the motor cables
wherever applicable. ▪ Then, turn off the servo drive and turn it back on. See if there occurs the
same alarm. If so, replace the drive because this alarm is tripped from the defective drive.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Regenerative Resistor
Connector
Power Board (PAB)
Regenerative Resistor
Select two from L1, L2, and L3, and measure the voltage between two terminals.
115
HM 8000(F30i Series) HM8000ALE2A ㅇ
(4) CO Alarm : An alarm that is tripped from an encoder signal error
Message on the front
display
Description This alarm occurs if the signal from the encoder has an error.
Troubleshooting
▪ Disconnect the encoder data transfer cable from the servo drive, and reconnect it as it may be connected improperly.
▪ Check the wiring of the encoder data transfer cable, and replace it if necessary.
▪ Check if the motor encoder connector is short-circuited. If so, replace the
motor.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder data cable
Motor Encoder Connector
116
HM 8000(F30i Series) HM8000ALE2A
(5) OS (Over Speed) Alarm : This is an over-speed alarm.
Message on the front
display
Description This alarm occurs when the motor speed exceeds the limit.
Troubleshooting
▪ Disconnect the encoder data transfer cable from the servo drive, and reconnect it as it may be connected improperly.
▪ Check the wiring of the encoder data transfer cable, and replace it if
necessary. ▪ Check if the motor has a short circuit. If so, replace the motor cables
wherever applicable. ▪ Check if the motor encoder connector is short-circuited. If so, replace the
motor.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder data cable
Motor Encoder Connector
117
HM 8000(F30i Series) HM8000ALE2A ㅇ
(6) OL (Over Load) Alarm : This is an overload alarm.
Message on the front
display
Description
▪ This alarm occurs if the overload state of the servo motor lasts for more than specified.
▪ Overload detection time 250% ~ : 1 second, 220% ~ : 24 seconds, 200% ~ : 48 seconds 180% ~ : 96 seconds, 160% ~ : 192 seconds, 150% ~ : 384 seconds 140% ~ : 769 seconds, 130% ~ : 1536 seconds
Troubleshooting
▪ Check if the parameters are set properly. ▪ This alarm occurs if the magazine has a tool overload or asymmetric load,
or has a mechanical error. Turn the magazine manually while increasing parameter no. 10 and parameter no. 11 by 10 until the magazine rotates smoothly.
▪ Disconnect the motor power cable and the encoder data transfer cable from the servo drive, and reconnect them as they may be connected improperly.
▪ Check the wiring of the motor power cable and the encoder data transfer cable, and replace them if necessary.
▪ Then, turn off the servo drive and turn it back on. See if there occurs the same alarm. If so, replace the drive because this alarm is tripped from the defective drive.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder data cable
118
HM 8000(F30i Series) HM8000ALE2A
(7) OC (Over Current) Alarm : This is an over-current alarm.
Message on the front
display
Description This alarm is tripped when the motor is over-currented.
Troubleshooting
▪ Check if the acceleration parameter (No. 29) and the deceleration parameter (No. 30) are set to less than specified.
▪ Check the wiring of the motor power cable, and replace it if necessary. Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the
magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
(8) SE Alarm : This is a double interruption alarm.
Message on the front
display
Description This alarm occurs if the CPU or the MCB of the servo drive has an error.
Troubleshooting
▪ Reset the parameters of the servo drive, and set them as appropriate again. ▪ Then, turn off the servo drive and turn it back on. See if there occurs the
same alarm. If so, replace the drive because this alarm is tripped from the defective drive (a MCB error).
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
(9) PE (Parameter Error) Alarm : This is a parameter error alarm.
Message on the front
display
Description This alarm occurs if the parameters of the servo drive are out of the set range.
Troubleshooting
▪ Reset the parameters and the compensation values of the servo drive, and set them as appropriate again.
▪ Then, turn off the servo drive and turn it back on. See if there occurs the same alarm. If so, replace the drive because this alarm is tripped from the defective drive (a MCB error).
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
119
HM 8000(F30i Series) HM8000ALE2A ㅇ
(10) rP (Residue Pulse) Alarm(ALP-rP) : This alarm occurs due to an excessive position deviation.
Message on the front
display
Description This alarm occurs if the residue pulse (RP) exceeds the limit specified for parameter no. 19 while the servo drive is controlling the position information.
Troubleshooting
▪ Check if parameter no. 19 of the residue pulse is set to less than specified. ▪ Disconnect the encoder data transfer cable from the servo drive, and
reconnect it as it may be connected improperly. ▪ Check if the motor has a short circuit. If so, replace the motor encoder
cables wherever applicable. ▪ Check if the motor encoder connector is short-circuited. If so, replace the
motor.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder data cable
Motor Encoder Connector
120
HM 8000(F30i Series) HM8000ALE2A
(11) EN (Battery) Alarm : This alarm occurs due to an encoder backup battery error.
▪ The servo drive that is connected to the motor consumes the battery for driving itself if no main (external) power is applied.
▪ Battery life (Max current consumption: 150㎂) 1.44 ~ 1.5 years at 25℃ 0.89 ~ 0.96 year at 75℃
Message
on the front display
Description This alarm is tripped when the encoder backup battery of the servo drive is discharged or loose.
Troubleshooting
▪ Replace the encoder backup battery of the servo drive. ▪ Remove the servo drive and check the backup battery of the internal
encoder if the battery connector is connected properly. If you find an error from the servo drive, replace the servo drive.
Note) The servo drive alarm is tripped to protect the servo drive, the motor, and the magazine. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder backup battery connector
Main Control Board (MCB)
Encoder backup battery
121
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.20 2064 ATC Door Open 1) Description
The ATC door is open. 2) Cause of problem
① The signal of closing the door was lost since the door was open abnormally (not in Auto mode or in Manual mode).
② The switch detecting that the ATC door is closed, or any of its component parts has an error.
3) Action
① The switch detecting that the ATC door is closed was adjusted incorrectly. ② Check if there is any problem with the switch or the wiring. If so, repair or replace the
defective part.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
ATC Door Open X12.1
(ATDO.M) -SD51 Input Module Slot 09 XJ413 (24) SD51
ATC Door Close X12.2
(ATDC.M) -SD52 Input Module Slot 09 XJ413 (39) SD52
ATC Door Open Alarm D-Time
ATC Door Open
122
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X12.2 ATDC.M ATC Door Close
K0.6 KHM1000 If HM1000, Set To 1
Y3.1 ATDC.R ATC Door Close
R628.4 TMB45 ATC Door Open Alarm D-Time
A7.7 2064 ATC Door Open
R635.7 AUT Auto Mode
X33.7 ST.M Cycle Start
R652.7 ARST Alarm Reset
A30.4 2245 ATC Door Open/Close Alarm
K10.3 KATCDR ATC Door Not Used
K7.6 KATC ATC Not Used
R709.0 ATCMST ATC macro Start
R455.0 M06CDF M06 Command Flag
R2401.7 TCCMDF T-Code Command Flag
R702.2 MATCDO Manual Door Open Command
R728.6 MATCDC Manual Door Close Command
R407.2 M222 ATC Door Open
R407.3 M223 ATC Door Close
A31.2 2251 ATC Overtime Alarm
A32.3 2260 Tool Magazine Rotation Overtime
R719.7 TMMDON ATC Manual Mode On
F0.6 SA Servo Ready
ATC Door Close Check(SL51)
ATC Door Open Check(SL52)
123
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.21 2066 Splash Guard (APC) Door Open (PMG) 1) Description
The splash guard door was open. (This alarm applies only to PMG machines) 2) Cause of problem
① The signal of closing the splash guard door was lost since the door was open abnormally (not in Auto mode or in Manual mode).
② The switch detecting that the splash guard door is closed, or any of its component parts has an error.
3) Action
① The switch detecting that the splash guard door is closed was adjusted incorrectly. ② Check if there is any problem with the switch or the wiring. If so, repair or replace the
defective part.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Splash Guard 1 Close
X16.1 (SG1C.M)
-SL8B Input Module : Slot 10 XJ414 (24) SL8B
Splash Guard 2 Close
X16.3 (SG2C.M)
-SL8D Input Module : Slot 10 XJ414 (6) SL8D
Splash Guard(APC) Door Open
124
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R4037.7 SGDC1/2 Splash Guard Door Close 1/2
R453.5 TMB206 Command Delay Time
A8.1 2066 Splash Guard(APC) Door Open
R635.7 AUT Auto Mode
X33.7 ST.M Cycle Start
R652.7 ARST Alarm Reset
R1420.7 PMGSEL PMG Operation Selected
K0.0 KHM63 ACE H63 Machine
K0.1 KHM80 ACE H80 Machine
K10.4 KSGDOR Splash Guard Door Not Used
K0.6 KHM1000 If HM1000, Set To 1
X16.1 SG1C.M Splash Guard 1 Close
X16.3 SG2C.M Splash Guard 2 Close
A41.2 2331 Splash Guard Door Open/Close Alarm
R635.6 TMB27 Splash Guard Door Close Check Time
A8.1 MAN Manual Mode
K10.4 KSGDOR Splash Guard Door Not Used
K7.7 KAPC APC Not Used
R4038.0 4SGDOP Splash Guard Door Open Command
R4038.2 4SGDCL Splash Guard Door Close Command
R763.4 MAPCSP Manual APC Stop
R4033.7 APUNLD APC Unload Command
R4034.5 APCLD APC Load Command
R631.3 CYSTP Cycle Stop
F0.6 SA Servo Ready
M259 Command Delay Time
125
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.22 2067 APC Overtime Alarm
1) Description A command of M60 (Pallet Change), M61 (APC Unload) or M62(APC Load) was instructed but not complete within 150 seconds since then.
2) Cause of problem
An error in adjusting the detection switch for each sequence, the solenoid valve, the wiring, or any of related component parts
3) Action
If there is an error in adjusting the detection switch for each sequence or any of related component parts, an alarm occurs for each error sequence, according to which troubleshooting shall be made. ☞ Refer to the “Pallet Change Sequence” chart
APC Overtime Alarm
APC Overtime Alarm AUX. 2
126
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R759.1 2067A1 HM10 APC Overtime Alarm Aux.
R759.2 2067A2 HM4D APC Overtime Alarm Aux. 2
R456.0 TMB220 HM4D APC Overtime Check Time
R652.7 ARST Alarm Reset
A10.3 2084
A10.4 2085
A9.1 2074
A9.2 2075
A9.3 2076
HM4D APC Overtime Check
127
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
A40.2 2323 4-th CL/UNCL Alarm
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000, Set To 1
R759.0 APCMST APC Macro Start
A25.3 2204 Feedrate Override 0%
R607.2 M61 APC 1 Unload
R607.3 M62 APC 1 Load
R755.7 SETUP Set Up
R1420.7 PMGSEL PMG Operation Selected
R1013.2 SETEN Set-Up Enable Condition
R4030.2 4PMGMST PMG Macro Start
R608.3 M70 Pallet or Station Index
R1002.1 PMGROT Table Side Search (PMG Rotation)
R1010.0 NO-SET Set-Up Not Found
K0.0 KHM63 ACE-H63 Machine
K0.1 KM80 ACE-H80 Machine
A40.1 2322 APC Set Up Station Door Open
K10.2 KAUTDR Auto Door for Setup Door Used
R430.1 TM26 APC Auto Door Close Check Time
R649.6 DCL Operator Door Close Confirm
R648.6 M250A Door interlock Bypass On Aux.
Y12.1 SZAT.R Sub Changer Arm Out
Y12.2 SCS1.R Sub Changer Position 1
K6.3 K40TS Tool Magazine 40Tools Used
K6.4 K60TS Tool Magazine 50Tools Used
R631.3 CYSTP Cycle Stop
X40.2 PMMD.M APC OP Manual Mode-HM4D
F0.5 STL Cycle Start
128
HM 8000(F30i Series) HM8000ALE2A
※ Pallet Changing (M60) Sequence Chart
Pallet Change Start (M60)
No APC Home Position
O.K ?
Yes
1 Pallet Change(Home) Position ▶ Return X to 2nd ref. point / return Y,Z,B to 1st ref. point
Program : G91 G28 Z0.; G91 G28 Y0.; G91 G30 X0.; G91 G28 B0.;
▪ Check: X axis: 2nd ref. point / Y,Z,B: 1st ref. point
Manual APC O.P Auto Mode ?
▪ From the APC manual OP, turn the mode switch to Auto. ▪ Check: X40.2(PMMD.M) –SA91 APC Manual Mode Yes
★ AL 2326 “APC OP Manual Mode” occurs No
APC Initial Position? No
★ AL 2068 “Pallet Change Initial Position Alarm” occurs
▪ Check: X18.5(P18F.M) –SX75 APC 180CW Position X18.6(P18R.M) –SX76 APC 180CW Position X8.2(SUIT.M) –S12 Set-up Door Interlock X18.0(AHOM.M) –SX70 APC Home Position X19.1(APDN.M) –SX81 APC Down X18.1(APOP.M) –SX71 APC Pos. 0/Arm Open
On
On
On
Yes
On
On
On
On
Set-Up Switch On ?
▪Press the Set-Up switch on the APC manual OP. ▪ Check: X40.1(SETU.M) –SB92 Set Up
★ AL 2325 “APC Set-Up Switch Unpush” occurs No
On Yes
2 APC Arm Close ▪ Output: Y12.7(APCL.R) –YV71 APC Arm Close On
▪ Completed: X18.3(SPCL.M) –SX73 APC Arm Close On
APC Arm Close O.K ? No
★ AL 2335 “APC Changer Open/Close Alarm” occurs
▪ Check: X18.3(SPCL.M) –SX73 APC Arm Close X18.1(SPOP.M) –SX71 APC Arm Open
On Off Yes
Go To “A”
129
HM 8000(F30i Series) HM8000ALE2A ㅇ
3 Pallet Unclamp ▪ Output: Y15.0(PAUC.R) –YV61 Pallet Unclamp On
▪ Completed: X7.1(PTCL.M) –SP62 Pallet Clamp
Pallet Unclamp O.K ? No
★ AL 2327 “Pallet Clamp/Unclamp Alarm” occurs
▪ Check: X7.1(PTCL.M) –SP62 Pallet Clamp Off Yes
A
Off
4 APC Changer Up ▪ Output: Y13.3(APUL.R) –YV75 APC Up On
▪ Completed: X19.0(APUP.M) –SX81 APC Up On
APC Changer Up O.K ? No
★ AL 2336 “APC Changer Up/Down Alarm” occurs
▪ Check: X19.0(APUP.M) –SX81 APC Up X19.1(APDN.M) –SX82 APC Down
On Off Yes
APC 180 CW Stopper Out ▪ Output: Y13.7(P8RR.R) –YV75 APC 180CW Stop. Out On
▪ Completed: X19.4(P9FO.M) –SX85 APC 180CW Stop. Out On
APC 180 CW Stopper Out O.K? No
▪ Check: X19.4(P9FO.M) –SX85 APC 180CW Stop. Out On
Yes
5 APC 180 CW Rotation ▪ Output: Y13.1(PCW.R) –YV73 APC Rota. 180CW On
▪ Completed: X18.5(P18F.M) –SX75 APC 180CW Position On
APC 180CW Rotat. End O.K ? No
★ AL 2337 “APC Changer 180CW/CCW Alarm” occurs
▪ Check: X18.5(P18F.M) –SX75 APC 180CW Position X18.6(P18R.M) –SX76 APC 180CCW Position
On Off Yes
APC 180 CCW Position O.K? No
Yes
▪ Check: X18.5(P18F.M) –SX75 APC 180CW Position X18.6(P18R.M) –SX76 APC 180CCW Position
“1” “2”
Go to “1”
Go to “B”
4.1
130
HM 8000(F30i Series) HM8000ALE2A
B
7 Pallet Clamp ▪ Output: Y15.1(PACL.R) –YV62 Pallet Clamp On
▪ Completed: X7.1(PTCL.M) –SP62 Pallet Clamp
Pallet Clamp O.K ? No
★ AL 2327 “Pallet Clamp/Unclamp Alarm” occurs
▪ Check: X7.1(PTCL.M) –SP62 Pallet Clamp Yes
6 APC Changer Down ▪ Output: Y13.4(APDV.R) –YV75 APC Down On
▪ Completed: X19.1(APDN.M) –SX82 APC Down On
APC Changer Down O.K ? No
★ AL 2336 “APC Changer Up/Down Alarm” occurs
▪ Check: X19.0(APUP.M) –SX81 APC Up X19.1(APDN.M) –SX82 APC Down On
Off Yes
On
On
8 APC Arm Open ▪ Output: Y12.7(APCL.R) –YV71 APC Arm Close On
▪ Completed: X18.1(SPOP.M) –SX71 APC Arm Open On
APC Arm Open O.K ? No
★ AL 2335 “APC Changer Open/Close Alarm” occurs
▪ Check: X18.1(SPOP.M) –SX71 APC Arm Open X18.3(SPCL.M) –SX73 APC Arm Close
On Off Yes
6.1 APC 180 CW Stopper In ▪ Output: Y13.7(P8RR.R) –YV75 APC 180CW Stop. Out
▪ Completed: X19.4(P9FO.M) –SX85 APC 180CW Stop. Out
APC 180 CW Stopper In O.K? No
▪ Check: X19.4(P9FO.M) –SX85 APC 180CW Stop. Out
Yes
Off
Off
Off
Pallet Change Finish
“1”
5.1 APC 180 CCW Rotation ▪ Output: Y13.1(PCW.R) –YV73 APC Rota. 180CCW On
▪ Completed: X18.6(P18R.M) –SX76 APC 180CCW Position On
APC 180 CCW Rotat. End O.K ? No
★ AL 2337 “APC Changer 180CW/CCW Alarm” occurs
▪ Check: X18.5(P18F.M) –SX75 APC 180CW Position X18.6(P18R.M) –SX76 APC 180CCW Position On
Off Yes
131
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.23 2068 Pallet Change Illegal Position 1) Description
A command of M60, M61, M62, M63 or M64 was instructed when the APC was not in the initial operation state.
2) Cause of problem
① An error in adjusting the switch that checks the initial conditions of APC ② An error in the switch, the wiring, or any of its related parts
3) Action
① An error in adjusting the switch that checks the initial conditions of APC Find the error-causing switch by referring to the ladder diagram or the DGN screen. Correct the switch as appropriate and try again.
② Check the switches, the wiring, and the I/O module in this sequence. Make repair or replacement if necessary. ☞ APC initial conditions
Address X18.5 X18.6 X7.2 X7.5 X8.2 X18.0 X19.1 X18.1 X4.3
Status 1 0
1 1 1 1 1 1 1 0 1
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC 180 CW Position
X18.5 (P18F.M)
-SX75 Input Module Slot
08,10 XJ410 (47) SX75
APC 180 CCW Position
X18.6 (P18R.M)
-SX76 Input Module Slot
08,10 XJ410 (30) SX76
Table Clamp X7.2
(BCLP.M) -SL63 Input Module Slot 08 XJ412 (11) SL63
Tool Measure Sensor Down Check
X7.5 (TLDN.M)
-SD62 Input Module Slot 08 XJ412 (43) SD62
Set Up Door Interlock
X8.2 (SUIT.M)
-S12 Input Module Slot 08 XJ412 (39) S12
APC Home Position X18.0
(AHOM.M -SX70
Input Module Slot 08,10
XJ410 (46) SX70
APC Changer Down X19.1
(APDN.M) -SX82 Input Module Slot 10 XJ413 (28) SX82
APC Pos. 0/Arm Open
X18.1 (APOP.M)
-SX71 Input Module Slot
08,10 XJ410 (32) SX71
Operator Side Door Interlock
X4.3 (OSDI.M)
-S13A Input Module Slot 07 XJ411 (06) S13A
132
HM 8000(F30i Series) HM8000ALE2A
Pallet Change Illegal Position
M61/M62 Command Illegal Position
M06 Illegal Position Alarm Aux.
133
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R759.3 2068A1 HM10 Pallet Change Illegal Position
R456.1 TMB221 M61/M62 Command Illegal Position
A8.3 2068 Pallet Change Illegal Position
R782.3 M60CHK Illegal Position Alarm Check
A9.5 2078 APC Set-Up Station Door Open
K10.2 KAUTDR Auto Door For Set Up Door Is Used
R430.1 TM26 Auto Door Close Check Time
F102.3 MV4
K0.6 KHM1000 If HM1000 Set to 1
R607.1 M61 APC Pallet 1 Loading
R607.2 M62 APC Pallet 2 Loading
R760.0 M61CD Pallet 1 Loading Command
R761.0 M62CD Pallet 2 Loading Command
R782.2 APCINP APC Initial Position
R755.7 SETUP APC Set Up
R1420.7 PMGSEL PMG Operation Selected
R1013.2 SETEN Set Up Enable Condition
Y10.3 SVON.R TMG Servo On
K6.3 K40TS Tool Magazine 40Tools Used
K6.4 K60TS Tool Magazine 60Tools Used
R760.7 M61MAN APC1 Unload(M61) M Func. End
APC Illegal Position
134
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R761.7 M62MAN APC1 Load(M62) M Func. End
A10.3 2084 APC Set Up Station Door Open
A9.1 2074
A9.2 2075
A9.3 2076
A40.2 2023 4-th CL/UNCL Alarm
K7.7 KAPC APC Not Used
X18.5 P18F.M APC180CW Position
X18.6 P18R.M APC180CCW Position
X7.2 BCLP.M Table Clamp
K8.5 KROTAR Rotary Table Used
X7.5 TLDN.M Tool Length Sensor Down
K0.7 KTLENG Moving Type Tool Measure is Used
X8.2 SUIT.M Set-Up Door Interlock-HM4D
K10.5 KSETDR Set-Up Door Interlock Not Used
K16.2 KSSPDR Set-Up Supplier Door Not Used
X18.0 AHOM.M APC Home Position
X70.6 SEAR.M Set-Up Arm Return
X19.1 APDP.M APC Down
X18.1 APOP.M APC Position 0/Open
Y15.5 PRUL.R Pallet Rotation Unlock
R756.7 ST2728 Spindle Tool No. 27or28
A41.6 2335 APC Changer Open/Close Alarm
A41.7 2336 APC Changer Up/Down Alarm
A42.0 2337 APC Changer 180CW/CCW Alarm
R648.6 M250A Door Interlock Bypass On Aux.
X4.3 OSDI.M Operator Side Door Interlock
135
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.24 2086 Main Changer Overtime Alarm 1) Description
The main changer arm home position signal (X8.5) has not been instructed within 5 seconds since the main changer motor rotation command (Y3.4) was instructed.
2) Cause of problem
In most cases, this happens if a tool is stuck in the changer arm while it is changed. 3) Action
Move the changer arm to the home position manually and find and resolve the cause of trouble.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Main Changer Arm Home Position
X8.5 (CAHP.M)
-SX41 Input Module Slot 08 XJ412 (38) SX41
Address Symbol Coil Comment
R439.7 TMB96 4D Main Changer Check Delay Alarm
A10.5 2086 Main Changer Overtime Alarm
R652.7 ARST Alarm Reset
R635.7 AUT Auto Mode
K0.6 KHM1000 If HM1000 Set To 1
Pallet Change Illegal Position
4D Main Changer Check Delay Time
136
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
Y3.4 CMFW.R Change Motor Forward_HM4D
R5324.5 4ATCS10 Do.10 (Main Changer Home Check)
X8.5 CAHP.M Main Changer Arm Home_ HM4D
▣ Return to the home position of the ATC changer arm
If the changer arm is stopped for any reason while changing the tools (M06), you must return the changer arm to the home position manually.
However, the countermeasures may differ according to the cause of trouble. So please find out the exact cause before restoring or repairing the machine.
(1) If the changer arm is stuck while trying to pull out a tool from the spindle (in the state of
Tool Unclamp) In most cases, this happens when the changer arm is stuck in the spindle while trying to pull out a tool after tool unclamping is performed
, causing to trigger the " 2062 M06 Command Over Time” alarm.
(2) If the changer arm is stuck in the spindle after changing a tool (in the state of Tool Clamp) In most cases, this happens when the changer arm gripper is stuck in a tool after the changer arm changed the tool and performed the tool clamping
, causing to trigger the " 2062 M06 Command Overtime” alarm.
(3) If the changer arm has stopped operation irrelevantly to the spindle This happens if the machine is emergency stopped or there occurs a power failure while performing the tool changing.
▶ ATC Recovery
1) If this happens due to the emergency stop or power failure, take an appropriate measure to solve the problem and turn power back on before entering Machine Ready.
2) Turn the mode switch in the main OP to “JOG”.
137
HM 8000(F30i Series) HM8000ALE2A ㅇ
3) Press the CUSTOM1 button from the button bar of the main OP. ☞ The “PMC Switch” screen appears.
4) Press the MANUAL soft key from the bottom soft
key bar. ☞ The “ATC APC Manual Switch” screen appears.
5) Press the ATC-ON soft key from the bottom soft key
bar. ☞ From the “ATC APC Manual Switch” screen, you
will notice that the “ATC Manual Mode” is turned on.
6) Depending on the operation that you want to perform, select “TOOL CHANGE STEP
REVERSE” (6-1), (6-3) or “TOOL CHANGE STEP FORWARD” (6-2).
138
HM 8000(F30i Series) HM8000ALE2A
6-1) If the changer arm is stuck while trying to pull out a tool from the spindle Turn the mode selection switch on the ATC manual OP to “TOOL CHANGE STEP REVERSE”. ☞ If the machine is in the state of tool unclamping, manually perform the tool clamping
before proceeding. ▪ How to confirm the state of spindle tool unclamping: Check if the spindle emits the collet
air (in MDI or Auto mode), or check if the button indicator of Tool Unclamp on the manual OP turns on.
6-2) If the changer arm is stuck in the spindle after changing a tool
Turn the mode selection switch on the ATC manual OP to “TOOL CHANGE STEP FORWARD”.
6-3) If the changer arm has stopped operation irrelevantly to the spindle (in the state of Spindle Unclamp) Turn the mode selection switch on the ATC manual OP to “TOOL CHANGE STEP REVERSE”.
7) Repeat pressing briefly the “START” button in the
ATC manual OP until the main changer arm moves to the home position where it doesn't move further.
For 6-1 above: In this case, the changer arm is stuck in the spindle for a reason while changing a tool.
Return the changer arm to the home position and find the cause by performing the tool unclamping manually.
☞ If the manual tool unclamping does not work at all, gently impact on the tool to remove it with the hammer. Then, check the tool kick distance, the state of the unclamp cylinder, collet, and the tapering side of the spindle or tool to find out the cause of trouble and take a necessary measure.
For 6-2 above: This happens when the gripper of the changer arm is stuck in the tool. If the problem persists after following the steps below, use a rubber hammer to impact on the end of the changer arm so that the gripper can be removed. Then, pull out the changer arm and return it to the home position. Find out the cause of trouble and take a necessary action. (check the tool and check also if ATC is aligned properly)
For 6-3 above: This kind of trouble shooting will be made manually while the tools are inserted in the changer
139
HM 8000(F30i Series) HM8000ALE2A ㅇ
arm. Just in case of a fall of the tool, prepare a shock absorber such as wood palette under the machine, so that it can protect the machine from the possible fall.
① If the spindle is in the process of tool clamping,
manually perform the tool unclamping. ☞ How to confirm the state of tool unclamping:
Check if the spindle emits the collet air (in MDI or Auto mode), or check if the button indicator of Tool Unclamp on the manual OP turns on.
② Repeat briefly pressing the “START” button
until the tool in the changer arm inserts to the spindle completely.
☞ An excessive number of pressing may get the changer arm off of the spindle, causing a fall of the tool. So you must stop pressing the button when the tool is inserted nearly to the end of the spindle.
③ Press the Tool Clamp button to manually perform the tool clamping on the spindle.
☞ Ensure that the Unclamp button should be turned off.
④ Repeat briefly pressing the “START” button until the changer arm reaches the home position and wouldn't move further.
☞ If the main changer arm doesn't move further even by your pressing the “START” button, this indicates that the main changer arm reaches its home position.
Then, the “2243 Must Be ATC M-Changer Man. 1 Cycle” alarm will be displayed on the NC screen.
8) Turn the mode selection switch in the ATC manual
OP to “TOOL CHANGE 1 CYCLE”, and press the “START” button to perform the tool changing automatically. Then, the alarm 2067 will be released and the ATC home position will be restored.
☞ If the Tool Change 1 Cycle operation is not performed, check the “Conditions of Manual Tool Change 1 Cycle” below:
140
HM 8000(F30i Series) HM8000ALE2A
※Conditions of Manual Tool Change 1 Cycle ① ATC Door Open (X12.1), or If there is no door at all: K10.3 (ATC Door Not Used) ② Both Y and Z axes are in the ATC change positions (Y-axis and Z-axis 2nd reference
points): This will be ignored if alarm AL2243 has occurred. ③ Switch the mode selection switch on the ATC manual OP to “MA NUAL”. ④ M06 Initial Position
▪ Waiting Pot Spindle Side(X10.3), ▪ Sub Changer Home Position(X10.3), ▪ Sub Changer Arm In (X10.1), ▪ ATC Main Changer Home Position (X8.5) ▪ Operator Door Close Confirm (X4.1, X4.3)
⑤ Servo Ready 7) Turn the switch to “DOOR CLOSE” and press the
START button to close the door.
8) From the PMC DATA screen, check the tool number (D450) in the spindle as well as the tool
number (D452) in the waiting pot, and make correction if necessary. When each axis returns to their respective home position, ATC troubleshooting is completed.
D450 : Tool number in the spindle
D452 : Tool number in the waiting pot
141
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.25 2091 B-Axis Command Error(Inc. Dec. Point) 1) Description
The coordinate instruction on the B axis is invalid. 2) Cause of problem
A number that is not a multiple of 1 degree (i.e., not an integer) was entered in the B-axis coordinate (angle) instruction. ex) A decimal point or a special character “/” is used
3) Action
Check the coordinate value and correct a non-integer number or character.
Address Symbol Coil Comment
R600.7 M10 B-Axis(Table) Clamp
F102.0 MV1
B-Axis Command Error(Inc.Dec.Point)
B-Axis Command Error
142
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
F102.1 MV2
F102.2 MV3
R753.0 BDATA1 B-Axis Data Compare(.020<.XXX)
R753.1 BDATA2 B-Axis Data Compare(.980>.XXX)
F0.5 STL Cycle Start
K0.6 KHM1000 If HM1000 Set to 1
R750.5 BCMDER B-Axis Command Error
R435.4 TMB61 B-Axis Command Error D-Time
A11.2 2091 B-Axis Command Error(Inc. Dec. Point)
R652.7 ARST Alarm Reset
R750.2 BACLP B-Axis(Table) Clamp Command
R801.3 AL45IT AL45 Interlock Release
R801.0 BUNCLP B-Axis Unclamp By VM4
K8.5 KROTAR Rotary Table Used
R9000.0 X=Y Compare X=Y
143
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.26 2093 X-Axis APC Changer Position Switch Alarm 1) Description
One or more axes from X, Y, Z and B are not in the APC changer home position while the pallet change instruction (M60, M61 or M62) was performing.
2) Cause of problem
One or more axis-feeding blocks of the macro program are deleted. 3) Action
Check the macro program of changing pallets and find the cause of problem. Correct the program as necessary.
O9021(M60 APC UNLOAD/LOAD PROGRAM) (2010.01.08_V.A4_YJ YOO) G31 IF[#3010EQ-1]GOTO600 IF[#1019EQ1]GOTO600 #105=#4003 G31 IF[#1031NE1]GOTO8 IF[#1007EQ1]GOTO5 IF[#1006NE1]GOTO401 GOTO8 G31 N5IF[#1006EQ1]GOTO402 GOTO8 N8#1109=1 N10IF[#1001NE1]GOTO10 #1109=0 N20IF[#1001EQ1]GOTO20 M78 M10 G91G28Z0. G91G28Y0. G91G30X0. G91G28B0. G31 N30IF[#1015NE1]GOTO30
IF[#1009EQ1]GOTO100 IF[#1010EQ1]GOTO200 GOTO400 N100M61 GOTO300 N200M62 N300 G31 IF[#1007EQ1]GOTO500 IF[#1031NE1]GOTO500 N310#1133=BCD[#982] #1115=1 IF[#1012NE1]GOTO310 #1115=0 GOTO500 N400#140=10 G65P9999 N401#140=11 G65P9999 N402#140=12 G65P9999 N500G[#105] N600 M99
144
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R607.1 M61 APC Pallet 1 Loading
R607.2 M62 APC Pallet 2 Loading
R782.0 APCHP APC Home Position
A11.4 2093 X-Axis APC Change Position switch Alarm
R652.7 ARST Alarm Reset
R1420.7 PMGSEL PMG Operation Selected
K0.2 KHM50 ACE-H50 Machine
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000 Set to 1
F91.4 ZPY Y-Axis 1st Ref. Return
F94.2 ZPZ Z-Axis 1st Ref. Return
R635.7 AUT Auto Mode
K1.4 KYZAPC
R635.6 MAN Manual Mode
F94.3 ZPB B-Axis 1st Ref. Return
F96.0 ZP2X X-Axis 2nd Ref. Return
X-Axis APC Change Position SW Alarm
APC Home Position
145
HM 8000(F30i Series) HM8000ALE2A ㅇ
2.27 2094 Pallet Number Command Error 1) Description
The PMG machine called pallet no. 0, which is a wrong number. 2) Cause of problem
The PMG machine called pallet no. 0, or it called a larger number of pallets than allowed. 3) Action
Check the allowed number of pallets (see PMC data D752 and D754) for the PMG machine, and correct the number to call as appropriate.
Address Symbol Coil Comment
R1001.6 PNZERO Pallet number Command Error
R1001.7 PNOVER Pallet No. Over Command Error
A11.5 2094 Pallet number Command Error
R652.7 ARST Alarm Reset
R1420.7 PMGSEL PMG Operation Selected
K0.0 KHM63 ACE-H63 Machine
K0.1 KHM80 ACE-H80 Machine
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000 Set to 1
Pallet Number Command Error
146
HM 8000(F30i Series) HM8000ALE2A
2.28 2142 Please Turn Off And On NC Power 1) Description
In the Machine Lock state, activate the B axis to reboot NC. 2) Cause of problem
The B axis was activated in the state of Machine Lock. 3) Action
Turn off the main power and turn it back on. Then, set the reference point for each axis manually before restarting the machine.
Address Symbol Coil Comment
R644.4 MLKBMV B-Axis Moving At Machine Lock
R644.2 MLKF Please Turn Off And On NC Power
R644.0 MLKA Machine Lock All Axis
F102.3 MV4
F0.5 STL Cycle Start
G44.1 MLK All Axis Machine
G108.2 ZMLK Z-Axis Machine Lock
R644.1 MLKZ Machine Lock Z-Axis
Please Turn Off And On NC Power
B-Axis Moving At Machine Lock
B-Axis Moving At Machine Lock
147
HM 8000(F30i Series) HM8000ALE2A ㅇ
3. Single Block Alarm
3.1 2160 Lub. Level Low 1) Description
The lubricant tank that supplies lubricant to the axial guide ways, the ball screws, and the bearings has run out of lubricant.
2) Cause of problem
① The lubricant tank has insufficient lubricant. ② An error in the lubricant level switch of the tank or related parts, or problem with the wiring
cables 3) Action
① Refill the lubricant tank in the rear of the machine with lubricant (way lubricant). (it is recommended to make a rule to refill the tank once every 3 or 4 days (based on 8 hours per day))
② Check the lubricant tank, connection line between tank and terminal block of the electric cabinet, and input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Lub. Level Check X5.0
(LUB.M) -SV51
Input Module Slot : 07
XJ411 (3) SV51
Address Symbol Coil Comment
X5.0 LUB.M Lub. Level Low
A19.7 2160 Lub. Level Low
R652.7 ARST Alarm Reset
Lub. Level Low
148
HM 8000(F30i Series) HM8000ALE2A
Lub. Level Lub. Level
Switch
149
HM 8000(F30i Series) HM8000ALE2A ㅇ
3.2 2161 Lub. Pressure Alarm 1) Description
After the lubricant motor of the lubricant tank that supplies lubricant to machine components such as guide ways, ball screws and bearings started driving, the pressure does not increase to a specified level (15Kg/㎠), or it does not fall back to the specified level within 10 seconds ever since.
2) Cause of problem
① The lubricant supply line (Lub. Hose, Lub. Pipe, Lub. Tube, etc) is loose or has a leak. ② An error in the distributor value ③ An error in the lubricant tank or related parts, or a problem with the wiring cables
3) Action
① Check the lubricant supply line (Lub. Hose, Lub. Pipe, Lub. Tube, etc) and make repair or replacement if necessary.
② If there is no particular problem with the lubricant supply line but the lubricant is supplied intensively to a specific component, this is thought to be caused by a defective distributor valve. If this is the case, replace it with a new one.
③ Check the lubricant tank, connection line between tank and terminal block of the electric cabinet, and input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Lub. Pressure Check X5.1
(LPRS.M) -SP51
Input Module Slot : 07
XJ411 (20) SP51
Lub. Pressure Switch
Lub. Pressure Gage
150
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R841.6 LPRSAL Lub. Pressure Alarm
A20.0 2161 Lub. Oil Pressure Down
R373.6 AL50R AL50 Reset
R652.7 ARST Alarm Reset
R620.0 TM01 Guide Way Lub. Motor On Time
R691.0 NO-MOV No Movement Each Axis
Y0.4 LUBM.R Lubrication For Guide Way
X5.1 LPRS.M Lub. Pressure Check
X5.2 LMS.M Lub. Manual Start
R623.3 TMB4 Lub. Pressure Check D-Time
Lub. Oil Pressure Down
Lub. Pressure Alarm
Lub. Pressure Check D-Time
151
HM 8000(F30i Series) HM8000ALE2A ㅇ
3.3 2162 Parts Count End Alarm 1) Description
The parts count reaches the limit. 2) Cause of problem
The count of the machined parts reaches the maximum value. 3) Action
Adjust the parts count settings, or reset it.
Address Symbol Coil Comment
F62.7 PRTSF Parts Count(NC) Max
A20.1 2162 Parts Count End Alarm
? RUN HOUR AND PARTS COUNT [4.36]06700 L1 0000000106710 L1 5406711 L1 406712 L1 4
#0 Part count (0:M02/30,1:M54)M code that counts the number of machined parts
Number of machined partsTotal number of machined parts
Parts Count End Alarm
152
HM 8000(F30i Series) HM8000ALE2A
3.4 2164 Oil Cooling Unit Alarm 1) Description
An error occurred in the oil cooling unit that cools down the main spindle. 2) Cause of problem
An error in the oil cooling unit 3) Action
Refer to the oil cooling unit's manual, and check the alarm description and take a necessary action.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Oil Cooling Unit Fault X2.5
(OCFT.M) -OCFT
Input Module Slot : 07
XJ411 (47) OCFT
Oil Cooling Alarm X2.7
(OCCF.M) -OCFT1
Input Module Slot : 07
XJ411 (46) OCFT1
Address Symbol Coil Comment
X2.5 OCFT.M Oil Cooling Unit Alarm
X2.7 SOCF.M Oil Cooling Alarm
K19.5 KSOCU Special Oil Cooling Unit
R625.3 TMB20 Hyd. Pump On Check Time
R652.7 ARST Alarm Reset
A20.3 2164 Oil Cooling Unit Alarm
Oil Cooling Unit Alarm
153
HM 8000(F30i Series) HM8000ALE2A ㅇ
※ Troubleshooting for oil cooler alarms
RUN No. Cause Action
● AL 1 Overload of the oil motor pump Refer to the user manual of the pump and check the oil circuit.
● AL21 The circuit protector “F2” or “S40” is tripped.
Refer to the user manual and clean the air filter
● AL 4
The temperature switch for protecting the heater is tripped. (only applied to the heater-equipped models)
●
AL 61 Short-circuit of the master temperature sensor ▪Check the sensor if short-
circuited ▪ Check the connector if contacted loose
▪ Replace with a new sensor
AL 62 Short-circuit of the slave temperature sensor
AL 63 Short-circuit of the reference temperature sensor
● AL 71 An error in the CPU of the control board Replace the control board
AL 73 A communication error of the control board
Refer to the user manual and check DIP switch #1
The “H” and current temperature indicators blink
▪ The controlled temperature exceeds the specified upper limit.
▪ It exceeds the alarm limit.
The “45” indicator blinks.
The controlled temperature exceeds 45˚C.
The “L” and current temperature indicators blink
▪ The controlled temperature exceeds the specified lower limit.
▪ It goes below the alarm limit.
The “5” indicator blinks.
The controlled temperature goes below 5˚C.
The “FIL” indicator blinks
It's time to clean the filter. Clean the filter and reset the machine
The “●” symbol above indicates that the indicator is turned off.
154
HM 8000(F30i Series) HM8000ALE2A
☞ Troubleshooting for Kaukan Oil Cooler alarms
Item No. Cause Action
1
The machine turns on but no response is made.
1) The PCB is defective. Replace the PCB 2) Fuse A1 for power supply (SMCC-
233) is defective. Replace the fuse.
3) The power supply module SMCC-233 is defective.
Replace SMCC-233
4) The transformer is defective. Replace the transformer
2 E01
1) Negative sequence wiring of the power supply unit
Reconnect any two phases of 3 power phases (see Ch4-4)
2) Reconnect only two power phases of 3 phases
Check if three power phases are correctly wired.
3) Out of AC220±15% Check the AC power source.
3 E02
1) The pump motor overload breaker has triggered.
Reset the QFP switch to release the breaker. (Push button)
2) Resetting the QFP switch does not work (push button not released)
This is because the overload breaker is damaged. Replace QFP.
3) The pump motor is defective. Replace the motor.
4 E03
1) The compressor motor overload breaker has triggered.
Reset the QFP switch to release the breaker. (Push button)
2) Resetting the QFP switch does not work (push button not released)
This is because the overload breaker is defective. Replace QFP.
3) The compressor motor is defective. Replace the motor.
5 E04
1) The pressure switch of the refrigerant is defective.
Replace the switch.
2) Out of effective range (-10℃~45℃)
Wait until the temperature falls in the effective range.
3) The air filter is clogged. Clean the air filter. 4) The condenser is clogged. Clean the condenser.
6 E05
1) The input pipe is not connected properly.
Tighten up the pipe.
2) The input/output pipes are switched with each other.
Reconnect and tighten up the pipe.
3) The oil/water quantity is too low. Find out the cause and make a refill.
4) The woodruff key of the pump or the rotor shaft of motor is worn out.
Replace the pump or motor.
5) Unable to adjust the pump pressure Replace the pump. 6) Defective oil/water pressure switch Replace the switch. 7) Hose, oil/water filter is clogged. Clean the hose, replace the
oil/water filter (optional). 8) Excessive pump pressure Adjust the pump pressure
155
HM 8000(F30i Series) HM8000ALE2A ㅇ
Item No. Cause Action properly, or check and clean the oil/water filter if necessary.
7 E06 1) The oil/water is insufficient. Refill the tank with the oil/water.
8 E07 1) The water in the pipe is not
circulating. The input/output pipe is clogged. Cleaning
2) The float switch is burnt out. Replace the switch.
9 E08 1) The oil/water temperature is below
zero(0℃). Turn off the power and wait until the temperature increases.
2) The refrigerant switch is defective. Replace the switch. 10 E09 The oil/water sensor is defective. Replace the sensor.
11 E10 The room temperature sensor is defective.
Replace the sensor.
12 E11 Excessive oil/water temperature (adjust the effective range of STC45℃ by a technician)
Contact a technician to adjust the temperature range or improve the cooling capacity.
13 E12 1) Insufficient refrigerant Refill the refrigerant. 2) The current cooler has comparably
insufficient cooling capacity. Replace it with a larger-capacity cooler.
▶ If you encounter that the oil/water cooler is overheated during its operation, refill the refrigerant regularly.
▶ Use only the refrigerant that is specified in the nameplate, or consult with a professional.
※ Troubleshooting for Daikin oil cooler alarms
1) If no alarm occurs but the cooler works abnormally
Item No. Cause Action
1
It doesn't work at all. (The power indicator of the control panel does not turn on)
① The main power is not supplied, or the power line (L1, L2) is improperly connected.
Check the power supply line if it is connected properly.
2 The pump does not operate at all.
① The remote control items [10] and [11] are deactivated.
Check if the remote control items are active.
② The pump is locked on operation. (The pump is locked on operation by factory default)
Release the lock at the control panel.
3
The pump is operating but no oil is flowing. Oil circulation is insufficient
① The intake pipe of the pump is loose.
Tighten the packing of the piping.
② The intake strainer is clogged. Unclog the intake strainer. If the oil in the oil tank is contaminated, replace with new oil.
156
HM 8000(F30i Series) HM8000ALE2A
Item No. Cause Action with a lot of noise.
③ The oil quantity level in the oil tank has lowered.
Refill the tank with the oil
④ The pressure loss of the oil discharge pipe is great, and the pump relief valve is activated.
Replace the oil pipe with a larger-diameter one, and make the length of the pipe shorter.
⑤ The pressure loss of the oil intake pipe is great, and the pump is cavitating.
---
4
The pump is working but the compressor is not operating.
① The compressor is stopped under the temperature control.
Check if it resumes working properly after the timer setting time.
② The anti-restart timer (30 seconds) for the compressor is ticking.
Check if it works properly when the oil temperature on the mouth is 5℃ or higher.
③ The low oil temperature protection system (below 2℃ on the mouth) is active.
Check if it works properly when the oil temperature on the mouth is 5℃ or higher.
④ The low ambient temperature blocking system (below -2℃ in room temperature) is active.
Check if it works properly when the ambient temperature is 0℃ or higher.
⑤ The capacity is set to 10% in mode 9.
Switch to a proper operation mode.
5
Both pump and compressor are operating but no oil is cooling.
① There is an obstacle near the air intake/exhaust port.
Remove the obstacle.
② The air filter is clogged. Clean the air filter, ③ The room temperature is high and
the pump/compressor is load performing.
Check the catalog for the temperature range available for each model. Select an appropriate model to what you need to use.
④ The heat load is great.
⑤ The temperature is set high. Set the temperature to a proper degree.
⑥ If the temperature of the exhaust air is almost equal to the room temperature while the compressor is operating, this is because the refrigerant is insufficient.
Turn off the fail-safe switch (SW1) on the control board.
6 Operational settings are not allowed.
① If "---" is displayed on the data screen, the sensor used in the applicable operation mode is not properly connected.
Connect the temperature sensor properly.
② If "---" is displayed temporarily when you press the ENT button (right utmost), this is because the
Turn off the fail-safe switch (SW1) on the control panel.
157
HM 8000(F30i Series) HM8000ALE2A ㅇ
Item No. Cause Action fail-safe switch is turned on.
7
The alarm 【64】 and 【65】are displayed and performed differently from the previous models.
① The signal connection of the alarm output is changed partially.
The alarms [60] and [63] are compatible with the previous models (AKS5 and AKZ6 series). However, [64] and [67] are changed in the message and connection method differently from the 7 series. For more details, refer to the "How to use old models" section at the end of each instruction manual.
2) If an alarm occurs, (turn off the machine and restart it if you want to set off the alarm) Alarm
Code
Alarm
Level
Description Cause Action
AA 2 Heater overloaded (S4B1:CN4) (applicable to heater-installed models only)
① For AKZ type, no oil is running.
Check if the hydraulic circuit is connected properly, and the pump is operating normally.
① For AKZJ type, the tank has insufficient oil quantity.
Refill the oil.
A6 2
DC motor is not locked
① DC fan motor is defective.
Replace the DC fan motor.
① There is a problem in communications between fan motor and control device.
Check the connector, check for any short circuit, and replace the control device.
E1 1 System error ① The internal parameter
settings are invalid. Replace the control board.
E3 2
High pressure (high-pressure switch (S3PH:CN6) is tripped)
① The oil or room temperature is beyond the working range.
Use the machine within the working temperature range.
② There is an obstacle near the intake/exhaust opening.
Do not place any object within 500mm near the intake/exhaust port.
③ The filter is clogged or the condenser is contaminated.
Refer to Item 8 above, and clean the air filter.
④ Others Contact us (Daikin) at the
158
HM 8000(F30i Series) HM8000ALE2A
Alarm
Code
Alarm
Level
Description Cause Action
customer service team. E5 2 The
compressor is overheated. (Thermo TH6 on the emission pipe is tripped) (Compressor head thermo (S2B:CN) is tripped)
① The oil or room temperature is beyond the working range.
Use the machine within the working temperature range.
② There is an obstacle near the intake/exhaust opening.
Do not place any object within 500mm near the intake/exhaust port.
③ The filter is clogged or the condenser is contaminated.
Refer to Item 8 above, and clean up the air filter.
E6 2 The compressor (M2C) is locked.
① The compressor is defective (needs to be replaced).
Replace the compressor.
EH 1
Pump high-currented Circuit Breaker (S1B:CN3) is tripped.
① The pump is overloaded due to use of the high-viscosity oil.
Use only the operating fluid that has the viscosity range of 4 ~ 200 mm2/s within the working temperature range.
② The pump motor is over-currented because the power voltage is lower than the effective range.
Check if the power voltage is lower than the effective range, or check if there occurs a sudden voltage drop for few seconds at the startup of peripheral equipment.
③ Disconnected wiring of the pump motor
Replace the pump motor.
④ The pump is clogged with debris or the motor is defective.
Replace the pump motor.
EJ 1/2 Optional protective device is activated (OP).
① Any optional protection device is activated. (For the unit, there are some devices connected by factory default)
Check the result of detection that is performed by the protective device.
H1 2 An error in the air temperature sensor (TH5: Gas Sync Sensor) (TH3: Ambient Temp Sensor)
①The air sensors used in the control system is short-circuited.
Check if there is any defective sensor on the monitor of the operation panel ("99.9" will be displayed for a defective sensor), and check also if the sensors are connected correctly.
159
HM 8000(F30i Series) HM8000ALE2A ㅇ
Alarm
Code
Alarm
Level
Description Cause Action
FH 2
The temperature on the intake opening exceeds 60℃.
① The heat of the main body exceeds the cooling capacity of the oil corn. (choice of an inappropriate model)
If the compressor is operating at100% of its capacity in normal conditions (check this on the monitor), select a model one size bigger.
② There is an obstacle near the inlet/outlet opening, which causes deteriorating the cooling capacity.
Do not place any object within 500mm near the intake/exhaust port.
③ The unit is running under capacity suppressing control because it has exceeded the standard temperature (room temp: 35℃, oil temp: 35℃), causing deteriorated cooling capacity.
If beyond the standard temperature, the cooling capacity is lowered than the nominal capacity by the load control system. Make sure that the capacity of the oil cooling unit exceeds the heat generation of the main unit in the entire operating temperature range.
④ Temperature control is disabled as the machine is operating in mode 9 (capacity direct designation mode)
Switch to a proper operation mode. (In capacity direct designation mode, feedback control of temperature is not enabled.)
⑤ The refrigerant gas is leaking.
If the temperature of the emission air is equal to the room temperature, there is a risk of leak of the refrigerant gas. If this is the case, contact us to the customer service team.
JH 2 Error in oil temp sensor (TH2: outlet oil temp sensor) (TH4: inlet oil temp sensor)
① Short circuit of the oil temp sensors used in the control system
Check if there is any defective sensor on the monitor of the operation panel ("99.9" will be displayed for a defective sensor), and check also if the sensors are connected correctly.
J3 2 An error in the temp thermistor on the emission
① Short circuit or disconnection of the temperature thermistor of
Check if the thermistor is connected correctly.
160
HM 8000(F30i Series) HM8000ALE2A
Alarm
Code
Alarm
Level
Description Cause Action
pipe the condenser. J5 2 Error in the EV
valve outlet opening temp thermistor
① Short circuit or disconnection of the EV valve outlet opening temperature thermistor.
Check if the thermistor is connected correctly.
J6 2 An error in the temp thermistor of the condenser
① Short circuit or disconnection of the temperature thermistor of the condenser.
Check if the thermistor is connected correctly.
L0 2 Error in the compressor line of the inverter
① Defective compressor or inverter
Replace the control system or the compressor.
LC 2 Communication error between inverter and temp control CPU.
① There occurred a communication error between temperature control MICOM and inverter MICOM.
Replace the control system, or improve the power supply condition (such as noise reduction).
P3 2 Error in the temp thermistor on the cooling fin
① Short circuit or disconnection of the temperature thermistor of the control box.
Check if the thermistor is connected correctly.
P4 2 Error in the temp thermistor on the cooling fin
① Short circuit or disconnection of the temperature thermistor on the heat sink.
Check if the thermistor is connected correctly.
U0 2
Insufficient gas
① The refrigerant piping is damaged due to excessive vibration in its transportation, leading to a leak of the refrigerant gas.
Repair the damaged refrigerant piping, and refill the refrigerant gas.
U1 1
Power supply reverse-phase connection
① The power supply circuit is connected in reverse phase.
Switch the reverse phases with each other.
② The L3 phase is open. Make sure that the L3 phase is properly connected to the power supply terminal block.
U2 2 Sudden power failure • Insufficient power
① The power voltage is below about 70V.
Check if there occurs an instantaneous voltage drop at the startup of peripheral equipment.
U9 2 Communication ① Communications error Check if the communication line
161
HM 8000(F30i Series) HM8000ALE2A ㅇ
Alarm
Code
Alarm
Level
Description Cause Action
s error in other systems (communication error between slave and master)
with a slave device. is properly established with the slave device. (this error occurs only if the slave device does not make response in master-slave communication.)
UH 2 System line failure (EEPROM error)
① The parameter settings that are saved in the control board are invalid.
Replace the control board.
UJ 1/2
OP2 activated
① Any optional protection device is activated. (For the unit, there are some devices connected by factory default)
Check the result of detection that is performed by the protection device.
1E ~
- Temperature range warning 1
① The temperature of the target to be monitored has exceeded the specified range. (not a fault of the oil cooling unit)
Check the warning message.
5E - Temperature range Warning 5
162
HM 8000(F30i Series) HM8000ALE2A
3.5 2166 Filter Changer of TSC. Alarm 1) Description
The filter of the high-pressure coolant unit (TSC) is clogged, which needs to be replaced. 2) Cause of problem
① The filter of the high-pressure coolant unit (TSC) is clogged. ② Error in the filter sensor, possible disconnection of the wiring through to the terminal block
of the electric cabinet, or defective component parts. 3) Action
① Replace the filter with a new one. ② Check the filter unit, and wiring between filter unit and terminal block of the electric
cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
TSC Filter Check OK X3.3
(FILT.M) -SP16
Input Module Slot : 07
XJ411 (11) SP16
Address Symbol Coil Comment
R627.2 TMB35 Filter Abnormal Status Check Time
F0.6 SA Servo Ready
Filter Changer of TSC Alarm
Filter Abnormal Status Check time
163
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
A20.5 2166 Filter Changer of TSC. Alarm
R652.7 ARST Alarm Reset
X3.3 FILT.M TSC Filter Check OK
K12.7 KCO&MD Cool. Dual High TSC or Did TSC
K11.0 KHFLTSC High TSC Flow Switch Used
K9.2 KHTSC Tank Type High Pressure TSC Used
K4.4 KFIT Filter Check SW is Not Used
164
HM 8000(F30i Series) HM8000ALE2A
3.6 2167 High TSC Flow Down Alarm 1) Description
The high-pressure coolant unit (TSC) has insufficient coolant. 2) Cause of problem
① Coolant is not supplied properly because the filter or pump of the high-pressure coolant unit (TSC) is defective.
② An error in the coolant flow sensor, possible disconnection of the wiring through to the terminal block of the electric cabinet, or defective component parts.
3) Action
① Check TSC pump & motor, filter and wiring cables, and make repair or replacement if necessary.
② Check the filter unit, and wiring between filter unit and terminal block of the electric cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
TSC Filter Check OK X3.3
(FILT.M) -SP16 Input Module Slot 07 XJ411 (11) SP16
Address Symbol Coil Comment
R440.6 TMB103 Filter Abnormal Status Check Time F0.6 SA Servo Ready
A20.6 2167 High TSC Flow Down Alarm
R652.7 ARST Alarm Reset
Flow Indicator Abnormal Alarm
Flow Indicator D-Time
165
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X3.3 FILT.M TSC Filter Check OK
Y8.1 TSC2.R T.S.C Run
K9.2 KHTSC Tank Type High Pressure TSC Used
K11.0 KHFLTSC High ATC Flow Switch Used
166
HM 8000(F30i Series) HM8000ALE2A
3.7 2168 Coolant Pressure Down Alarm 1) Description
The coolant pressure alarm has occurred from the high-pressure TSC unit (with tank type or cool jet & dual, middle TSC).
2) Cause of problem
① Insufficient coolant ② Check the recovery pump motor of the coolant tank, coolant pump & motor and pressure
sensor if they work properly. Check the wiring through to the electric cabinet and make repair or replacement if necessary.
3) Action
① Refill the tank with the coolant. ② Check the pump motor, and wiring between pressure sensor of TSC unit and OP, and
between OP and terminal block of the electric cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Coolant Pressure Check
X3.2 (TSCA.M)
-SP15 Input Module Slot :
07 XJ411 (44) SP15
Address Symbol Coil Comment
X3.2 TSCA.M T.S.C Unit Alarm /Coolant Over Flow
F0.6 SA Servo Ready
A20.7 2168 Coolant Pressure Down Alarm
R652.7 ARST Alarm Reset
K5.2 KDMTSC Used TSC of Dmvg Type
Coolant Pressure Down Alarm
167
HM 8000(F30i Series) HM8000ALE2A ㅇ
3.8 2170 Tool Life Count End Alarm 1) Description
The tool change signal (of tool life cycle management) is detected. 2) Cause of problem
The tool has reached its life cycle specified in Tool Life Management, triggering the tool change request signal.
3) Action
Take an action according to the Tool Life Management instructions.
Address Symbol Coil Comment
F64.0 TLCH Tool Change Request
R652.1 M32H M02/M30 Hold
R600.3 M06 ATC Change Macro Call
F2.1 RPDO
Tool Life Count End Alarm
168
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
K8.7 KTLIFE Make Single Block Stop, Life
X33.7 ST.M Cycle Start
F0.5 STL Cycle Start
A21.1 2170 Tool Life Count End Alarm
R652.7 ARST Alarm Reset
K13.6 KFMS FMS Interface is Used
R1486.0 FMS.C FMS Mode From Screen
R6520.5 PGNFND Program Not Fount Aux.
R670.0 STFL Start Flag for brake Cace
R666.5 M286F Tool Pre Check Flag
R670.6 M288F M288 Retract Function Flag
K80.3 KTLCEA Tool Life Count End Alarm Not Used
169
HM 8000(F30i Series) HM8000ALE2A ㅇ
3.9 2171 RST Command Alarm On STL 1) Description
Immediately after NC Reset during the auto operation, the cycle start is performed in Auto mode.
3) Action
If NC reset is performed in auto operation, you must reset it again in Edit mode and then locate the program block before performing the cycle start in Auto mode.
Address Symbol Coil Comment R634.1 MEM Memory Mode R634.2 TAPE Tape Mode R835.7 FRSTAL Flag Reset Alarm X33.7 ST.M Cycle Start A21.2 2171 Reset Command Alarm On Cycle Start
R652.7 ARST Alarm Reset R835.6 RSTALM Aux. Reset Alarm
F1.1 RST NC Reset R634.0 EDIT Edit Mode R652.1 M32H M02/M30 Hold
F0.6 SA Servo Ready F0.5 STL Cycle Start
G44.1 MLK All Axis Machine Lock
Reset Command Alarm On Cycle Start
Flag Reset Alarm
Aux. Reset Alarm
170
HM 8000(F30i Series) HM8000ALE2A
3.10 2172 Tool Length Sensor Up Status 1) Description
The Pallet Change command was instructed with the tool length sensor positioned up, or the operator attempted to move the axis in Jog mode without the command of M75.
2) Cause of problem
Mistake by the operator 3) Action
Ensure that the operator positions down the tool length sensor before instructing Pallet Change or moving the axis. M75 : Tool Measure Sensor On M76 : Tool Measure Sensor Up M77 : Tool Measure Sensor Down
Tool Length Sensor Up Status
Tool Length Sensor On
Tool Length Flag
171
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R607.2 M61 APC 1 Unload
R607.3 M62 APC 1 Load
F102.0 MV1
F102.1 MV2
F102.2 MV3 Z-Axis Moving Signal
F102.3 MV4
X34.5 PJF.M Jog Feed +Direction
X34.6 NJF.M Jog Feed -Direction
R635.6 MAN Manual Mode
R800.4 SEN2 Tool Length Sensor On
R635.7 AUT Auto Mode
Y3.3 TLUP.R Tool Length Sensor Up
X7.5 TLDN.M Tool Length Sensor Down
A21.3 2172 Tool Length Sensor Up Status
R652.7 ARST Alarm Reset
R800.3 M75F Tool Length Flag
R800.6 M73F M74, 5 Not Use Flag
R652.6 ERST External Reset
R800.1 M74F Work Measure Flag
F0.6 SA Servo Ready
R609.0 M75 Tool Measure Sensor On
F1.3 DEN Distribution End
K0.7 KTLENG Moving Type Tool Meas. Is Used
172
HM 8000(F30i Series) HM8000ALE2A
3.11 2173 Wait. & Mag. Pot Tool Detect 1) Description
While any operation of Tool Change, Tool Search or Sub Changer Waiting Pot Side is performing, the switch for the tool pot tool sensor is turned on.
2) Cause of problem
① A pot that is supposed to be empty has a tool inserted by mistake. ② An error in the tool pot tool sensor of the tool magazine ③ An error in the switch, or the wiring from the switch to the electric cabinet, or any of its
component parts 3) Action
① A tool pot in the spindle where a tool is supposed to be inserted should be empty. ② An error in adjusting the position sensor switch
While checking the indicator on the proximity switch that is installed on the tool pot tool detect cylinder of the tool magazine, adjust the proximity switch as appropriate.
③ An error in wiring or component parts Check the proximity switch, the wiring from the proximity switch to the ATC terminal box and from the terminal box to the electric cabinet as well as the input module if there is a problem. Repair or replace the defective part if necessary.
Part Name Part No. Symbol Spec. Maker
Cable, Proximity Switch ECBLS0170F -WK215 BKS B20-1-03 Balluff
Switch, Proximity / PNP ESWPX0265F -SX33 BES516-325-E5-C-S4 Balluff
Signal Address Device Symbol I/O Connector
(Pin) Numbering
ATC Waiting Pot Spindle Side
X7.6 WPSS.M
-SL36 Input Module Slot :
8,9 XJ412 (10) SL36
ATC Waiting Pot Tool Detect
X11.0 WPDT.M
-SX38 Input Module Slot :
09 XJ413A(12) SX38
173
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R456.5 TMB225 Wait & Mag. Pot Detect Check Time
A21.4 2173 Wait & Mag. Pot Tool Detect
R652.7 ARST Alarm Reset
R600.3 M06 ATC Change Macro Call
X7.6 WPSS.M Waiting Pot Spindle Side_HM4D
R2401.7 TCCMDF T-Code Command Flag
R5304.3 RTCCMF Re-Change T-Code Command Flag
Wait. Pot Tool Detect(SX5A)
Wait. Pot Spindle Side (SL36)
Wait. & Magazine Pot Tool Detect
Wait & Mag. Pot Detect Check Time
174
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X11.0 WPTD.M Waiting Pot Tool Detect
R5319.2 MSCWPP Man Sub Changer Wait.Pot Pos. Command
R5304.5 MAGTOD Magazine Pot Tool Detect
K0.6 KMATRX Matrix Tool Magazine is Used
175
HM 8000(F30i Series) HM8000ALE2A ㅇ
3.12 2175 Hyd. Unit Oil Temperature Alarm 1) Description
A machine featuring a heater-equipped hydraulic unit has an excessive or oil temperature. 2) Cause of problem
① Overheat or over-cooling of the hydraulic oil ② An error in the heater of the hydraulic unit, the wiring through to the electric cabinet, and
any of its component parts 3) Action
① This problem happens because of an error in the heater of the hydraulic unit. Refer to the product manual and take a necessary measure.
② Check the heater, the heater thermometer and the electric cabinet of the hydraulic unit, and the wiring between the electric cabinet and the terminal block of the electric cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Hyd. Unit Temp High X3.4
(HYDH.M) -TH02
Input Module Slot : 07
XJ411 (27) TH02
Hyd. Unit Temp Low X3.5
(HYDL.M) -TH03
Input Module Slot : 07
XJ411 (43) TH03
Address Symbol Coil Comment
X3.4 HYDH.M Hyd. Unit Temp High
X3.5 HYDL.M Hyd. Unit Temp Low
A21.6 2175 Hyd. Unit Oil Temperature Alarm
R652.7 ARST Alarm Reset
Hyd. Unit Oil Temperature Alarm
176
HM 8000(F30i Series) HM8000ALE2A
4. Massage Alarm
4.1 2191 Coolant Chiller Unit Alarm 1) Description
The coolant chiller unit that cools the coolant has a problem. 2) Cause of problem
An error in the coolant chiller unit 3) Action
Refer to the manual of the coolant chiller unit, and check the alarm description and take a necessary action.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Coolant Chiller Unit Alarm
X4.6 (CCAL.M)
-M251 Input Module Slot :
07 XJ411 (22) M251
Address Symbol Coil Comment
X4.6 CCAL.M Coolant Chiller Unit Alarm
A23.6 2191 Coolant Chiller Alarm
R652.7 ARST Alarm Reset
K14.3 KCHILL When Chiller Used Set 1
Coolant Chiller Unit Alarm
177
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.2 2193 Safety Switch Locking Alarm 1) Description
The release key of the splash guard's door-close check safety switch is opened. 2) Cause of problem
① The release key of the safety switch is tripped. ② The safety switch has an error or the wiring has a problem.
3) Action
① Turn the release key of the safety switch to set it off. ② Check the operator's side safety switch as well as the wiring, and repair or replace a
defective one if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Main Door Unlock Key Switch
X4.2 (OSDO.M)
OSDO Input Module Slot :
07 XJ411 (39) OSDO
Operator Side Door Interlock
X4.3 (OSDI.M)
-S13A Input Module Slot :
07 XJ411 (06) S13A
Address Symbol Coil Comment
R649.1 UNLILK Unlocking in Door Lock Status
A24.0 2193 Safety Switch Unlocking Alarm
R652.7 ARST Alarm Reset
Safety Switch Locking Alarm
Unlocking In Door Lock Status
Door Lock Timer
178
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R439.0 TMB89 Door Lock Time
X4.2 OSDO.M Main Door Unlocking Key Switch
Y11.7 OSDI.M Door Open Condition
X4.3 OSDI.M Operator Side Door Interlock
179
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.3 2194 Man Axis Moving Interlock 1) Description
One of the axes (X, Y, Z or B) has tripped Axis Interlock. As a result, the Handle or Jog mode for that axis is disabled.
2) Cause of problem
① Any of ATC, APC, the table or the door was not in its initial position. Or, the sensor switch was deactivated.
② With an axis being in the reference point, the operator returned the axis to the reference point in the + direction manually.
3) Action
① Check each and every axis, and adjust the switch as appropriate or take a necessary action. ⓐ For the X axis
- APC Arm Interlock
Address X18.5 (SX75)
X18.6 (SX76)
X18.1 (SX71)
X18.3 (SL76)
Status 1 0
1 1 0 1
- Table/Pallet Unclamp Interlock
Address X7.2 (SL63)
X7.1 (SP62)
Y15.0 (YV61)
Y15.2 (YV63)
Status 1 1 0 0
- Splash Guard Door Interlock
Address X4.2 (SODO)
X4.3 (S13A)
Status 1 1
ⓑ For the Y axis
- Table/Pallet Unclamp Interlock
- APC Arm Interlock
- Splash Guard Door Interlock
- ATC Interlock
Address X8.5 (SX41)
X8.6 (SX42)
X8.7 (SX43)
X12.1 (SL51)
X12.2 (SL52)
Status 1 0 0 0 1
180
HM 8000(F30i Series) HM8000ALE2A
ⓒ For the Z axis - APC Arm Interlock
- Table/Pallet Unclamp Interlock
- ATC Interlock
- Splash Guard Door Interlock
ⓓ For the B axis
- APC Arm Interlock
- Splash Guard Door Interlock
- B-Axis (Table) Interlock
Address X7.2 (SL63) X7.1 (SP62)
Status 1 1
② When setting the reference point for each axis, turn the selection switch in the - direction,
or reverse the axis in Handle mode before resetting the reference point.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC 180 CW Position X18.5
(P18F.M) -SX75
Input Module Slot 08,10
XJ410 (47) SX75
APC 180 CCW Position X18.6
(P18R.M) -SX76
Input Module Slot 08,10
XJ410 (30) SX76
Table Clamp X7.2
(BCLP.M) -SL63 Input Module Slot 08 XJ412 (11) SL63
Tool Measure Sensor Down Check
X7.5 (TLDN.M)
-SD62 Input Module Slot 08 XJ412 (43) SD62
Set Up Door Interlock X8.2
(SUIT.M) -S12 Input Module Slot 08 XJ412 (39) S12
APC Home Position X18.0
(AHOM.M -SX70
Input Module Slot 08,10
XJ410 (46) SX70
APC Changer Down X19.1
(APDN.M) -SX82 Input Module Slot 10 XJ413 (28) SX82
APC Pos. 0/Arm Open X18.1
(APOP.M) -SX71
Input Module Slot 08,10
XJ410 (32) SX71
Operator Side Door Interlock
X4.3 (OSDI.M)
-S13A Input Module Slot 07 XJ411 (06) S13A
Pallet Clamp X7.1
(PTCL.M) -SP62 Input Module Slot 08 XJ412 (28) SP62
Main Door Unlock Key X4.2 OSDO Input Module Slot 07 XJ411 (39) OSDO
181
HM 8000(F30i Series) HM8000ALE2A ㅇ
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Switch (OSDO.M)
Pallet Unclamp Y15.0
(PAUC.R) -YV61 Output Module Slot 4 XJ403 (03) KAR57
Table Unclamp Y15.2
(TAUC.R) -YV63 Output Module Slot 4 XJ403 (35) KAR59
Main Changer Arm Home Pos.
X8.5 (CAHP.M)
-SX41 Input Module Slot 08 XJ412 (38) SX41
Spd. Tool Unclamp Command
X8.6 (ULMD.M)
-SX42 Input Module Slot 08 XJ412 (22) SX42
Spindle Tool Clamp Command
X8.7 (CLMD.M)
-SX43 Input Module Slot 08 XJ413 (37) SX43
ATC Door Open X12.1
(ATDO.M) -SL51 Input Module Slot 09 XJ413 (24) SL51
ATC Door Close X12.2
(ATDC.M) -SL52 Input Module Slot 09 XJ413 (39) SL52
Man Axis Moving Interlock
182
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
G130.0 B.ITX X-Axis Interlock
R637.0 JX Jog X-Axis Select
G130.1 B.ITY Y-Axis Interlock
R637.1 JY Jog Y-Axis Select
G130.2 B.ITZ Z-Axis Interlock
R637.2 JZ Jog Z-Axis Select
G130.3 B.IT4 B-Axis Interlock
R637.3 J4 Jog B-Axis Select
G8.0 B.IT All-Axis Interlock
X34.5 PJF.M Jog Feed + Direction
X34.6 NJF.M Jog Feed - Direction
X39.2 HX.M MPG Handle X-Axis Select
X39.3 HY.M MPG Handle Y-Axis Select
X39.4 HZ.M MPG Handle Z-Axis Select
X39.5 H4.M MPG Handle 4th-Axis Select
K3.3 K3MPG K3MPG UsedR635.4
183
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R635.4 H Handle Mode
R635.6 MAN Manual Mode
K20.0 KZPX X-Axis Ref. Point Return Keep
F94.0 ZPX X-Axis 1st Ref. Return
K20.1 KZPY Y-Axis Ref. Point Return Keep
F94.1 ZPY Y-Axis 1st Ref. Return
K20.2 KZPZ Z-Axis Ref. Point Return Keep
F94.2 ZPZ Z-Axis 1st Ref. Return
X34.3 AS4.M Jog Axis Selection 4
G43.7 ZRN Reference Point Return
F96.2 ZP2Z Z-Axis 2nd Ref. Return
F102.3 MV4
K16.3 KBXIT B-Axis Move in Z-Axis Home Pos.
A24.1 2194 Man Moving Interlock
▪ X-axis Interlock
X-Axis Interlock
APC Arm Interlock
184
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R641.5 F0% Feedrate Override 0%
R698.0 IFZONE Machine Interference Zone Error 1
R631.0 SPCLFH Spindle & Coolant at Feed Hold
R631.4 AXINT Axis Interlock by Spclfh
R641.4 AITRLS Axis interlock Release
R769.7 APCINT APC Arm Interlock
Table/Pallet Unclamp Interlock
B-Axis(Table) Clamp Check Time
185
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R731.0 ZXYINT XY-Axis Interlock by Z-Ref. Pos.
G66.0 IGNVRY Ignore Vrdy Off Alarm
R690.3 HOLDON AL88 Alarm Hold on Flag
R649.0 DINON Splash Guard Door Interlock On
R669.0 ZRNB Ref. Point Return for B-Axis
R641.1 ZRNRDY Ref. Point Return One Touch Ready
K50.1 RTIMEM Rigid Tap Interrupt Memory
R2850.5 RTRENB Rigid tape retract Enable
R752.4 TMBINT Table/Pallet Unclamp Interlock
X18.5 P18F.M APC 180 CW Position
X18.6 P18R.M APC 180 CCW Position
X18.1 APOP.M APC Pos. 0/Arm Open
K7.7 KAPC APC Not Used
X18.3 APCL.M APC Pos.90/Arm Close
K0.6 KHM1000 If HM1000, Set to 1
R772.5 APRETC APC Arm Return Confirm
Y8.4 CADV.R Pallet Changer Arm Advance
X16.1 SG1C.M Splash Guard 1 Close
X16.0 SG1O.M Splash Guard 1 Open
X16.3 SG2C.M Splash Guard 2 Close
X16.2 SG2O.M Splash Guard 2 Close
K10.4 KSGDOR Splash Guard Door Not Used
R448.4 TMB165 B-Axis(Table) Servo Off D-Time
R624.4 TMB13 B-Axis(Table) Clamp Check Time
Y7.2 TUCL.R Table Unclamp
Y15.2 TAUC.R Table Unclamp
K8.5 KROTAR Rotary Table Used
X7.1 PTCL.M Pallet Clamp
R435.2 TMB59 Pallet Unclamp Check Time
Y7.0 PUCL.R Pallet Unclamp
Y15.0 PAUC.R Pallet Unclamp
R759.0 APCMST APC Macro Start
F3.1 MH
186
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R750.5 BCMDER B-Axis Command Error
R750.4 RTCLP Table(Rotary) Clamp
X7.2 BCLP.M Table Clamp
R750.2 BACLP B-Axis(Table) Clamp Command
G126.3 SVF4 4th-Axis Servo Off
R1420.7 PMGSEL PMG Operation Selected
K0.2 KHM50 Ace-HM50 Machine
X11.7 APLK.M Arm Pin Locking
K0.1 KHM80 Ace-HM80 Machine
K0.0 KHM63 Ace-HM63 Machine
Y15.3 TACL.M Table Clamp
R797.4 4RTCLP Rotary Table Clamp
▪ Y-axis Interlock
Y-Axis Interlock
Y-Axis(Table) Interlock Aux.
187
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R725.3 BITYA Y-Axis Interlock Aux
R752.4 TMBINT Table/Pallet Unclamp Interlock
R752.6 TMBINT1 Table Unclamp Interlock
R669.0 ZRNB Ref. Point Return for B-Axis
R641.1 ZRNRDY Ref. Point Return One Touch Ready
K50.1 RTIMEM Rigid Tap Interrupt Memory
R2850.5 RTRENB Rigid tape retract Enable
X12.0 ZAIL.M Z-Axis Interlock
R718.6 ATCINT1 ATC Interlock 1
R635.4 H Handle Mode
R408.3 M231 Tool Changer M-Code Aux
R731.0 ZXYINT XY-Axis Interlock by Z-Ref. Pos.
R690.3 HOLDON AL88 Alarm Hold On Flag
R641.5 F0% Feedrate Override 0%
R698.0 IFZONE Machine Interference Zone Error 1
R631.0 SPCLFH Spindle & Coolant at Feed Hold
R631.4 AXINT Axis Interlock by Spclfh
R641.4 AITRLS Axis interlock Release
X2.6 PFM.M Power Failure Detection
K2.1 KPFM Used Power Back Up Module
R769.7 APCINT APC Arm Interlock
R649.0 DINON Splash Guard Door Interlock On
R600.3 M06 ATC Change Macro Call
ATC Interlock
188
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R757.5 APCCHG Pallet Change Command
G66.0 IGNVRY Ignore Vrdy Off Alarm
R718.7 ATCINT ATC Interlock
X8.5 CAHP.M Main Changer Arm Home_HM4D
K7.6 KATC ATC Not Used
K12.2 KMATC When Used Maintenance for ATC
X8.6 MLMD.M Spindle Tool Unclamp Command_HM4D
X8.7 CLMD Spindle Tool Clamp Command_HM4D
X12.1 ATDO.M ATC Door Open
X12.2 ATDC.M ATC Door Close
K10.3 KATCDR ATC Door Not Used
▪ Z-axis Interlock
Z-Axis Interlock
Z-Axis Interlock Aux.
189
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R725.4 BITZA Z-Axis Interlock Aux
R769.7 APCINT APC Arm Interlock
R752.4 TMBINT Table/Pallet Unclamp Interlock
R752.6 TMBINT1 Table Unclamp Interlock
R669.0 ZRNB Ref. Point Return for B-Axis
R641.1 ZRNRDY Ref. Point Return One Touch Ready
K50.1 RTIMEM Rigid Tap Interrupt Memory
R2850.5 RTRENB Rigid tape retract Enable
X12.0 ZAIL.M Z-Axis Interlock
R718.6 ATCINT1 ATC Interlock 1
G100.2 +Z Jog +Z Axis
R635.4 H Handle Mode
G43.7 ZRN Reference Point Return
R408.3 M231 Tool Changer M-Code Aux
A27.0 2217 Arm Rot. Count Error Alarm
R641.5 F0% Feedrate Override 0%
R698.0 IFZONE Machine Interference Zone Error 1
R631.0 SPCLFH Spindle & Coolant at Feed Hold
R631.4 AXINT Axis Interlock by Spclfh
R641.4 AITRLS Axis interlock Release
R600.3 M06 ATC Change Macro Call
R757.5 APCCHG Pallet Change Command
G66.0 IGNVRY Ignore Vrdy Off Alarm
ATC Door Z-Axis Interlock
190
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R718.7 ATCINT ATC Interlock
R649.0 DINON Splash Guard Door Interlock On
R730.7 ATDZIT ATC Door Z-Axis Interlock
K24.6 KATDOP ATC Door Open Keep
K14.6 KADCZ When Z-Moving After
K24.7 KATDCL ATC Door Close Keep
Y3.1 ATDC.R ATC Door Close
R635.6 MAN Manual Mode
R709.0 ATCMST ATC Macro Start
K10.3 KATCDR ATC Door Not Used
K7.6 KATC ATC Not Used
▪ B-axis Interlock
B-Axis Interlock
B-Axis Interlock Aux.
191
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R725.7 BIT4A B-Axis Interlock Aux
R769.7 APCINT APC Arm Interlock
R695.7 BXINT B-Axis Interlock by X-Axis Zone
G66.0 IGNVRY Ignore Vrdy Off Alarm
B-Axis(Table) Interlock
192
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
Y3.3 TLUP.R Tool Length Sensor Up
R649.0 DINON Splash Guard Door Interlock On
R752.5 BXIT B-Axis Interlock Disable
R648.3 BAXINT B-Axis Interlock
K16.6 KPOSSW Keep Position Switch is Used
R641.5 F0% Feedrate Override 0%
R698.0 IFZONE Machine Interference Zone Error 1
R631.0 SPCLFH Spindle & Coolant at Feed Hold
R631.4 AXINT Axis Interlock by Spclfh
R624.3 TMB12 B-Axis(Table) Servo On D-Time
R625.2 TMB19 B-Axis(Table) Servo On D-Time
F102.3 MV4
R752.1 BAINT B-Axis(Table) Interlock
X7.2 BCLP.M Table Clamp
X7.1 PTCL.M Pallet Clamp
R1420.7 PMGSEL PMG Operation Selected
K0.2 KHM50 Ace-HM50 Machine
X7.0 PTUC.M Pallet Unclamp
K0.0 KHM63 Ace-HM63 Machine
X7.3 BULP.M Table Unclamp
K0.1 KHM80 Ace-HM80 Machine
K8.5 KROTAR Rotary Table Used
Y15.3 TACL.R Table Clamp
Y15.0 PAUC.R Pallet Unclamp
G43.7 ZRN Reference point Return
K8.0 KB/ABS B-Axis S/Motor Absolute Used
K0.6 KHM1000 Ace-HM1000 Machine
193
HM 8000(F30i Series) HM8000ALE2A ㅇ
▪ Interlock on all axes
Address Symbol Coil Comment
R641.5 F0% Feedrate Override 0%
R698.0 IFZONE Machine Interference Zone Error 1
R631.0 SPCLFH Spindle & Coolant at Feed Hold
R631.4 AXINT Axis Interlock by Spclfh
R641.4 AITRLS Axis interlock Release
Y3.3 AXINT Axis Interlock by Spclfh
X7.5 TLDN.M Tool length Sensor Down
K0.7 KTLENG Moving type Tool Meas. is Used
R800.4 SEN2 Tool length Sensor On
G66.0 IGNVRY Ignore Vrdy Off Alarm
R769.7 APCINT APC Arm Interlock
R649.0 DINON Splash Guard Door Interlock On
All-Axis Interlock
194
HM 8000(F30i Series) HM8000ALE2A
4.4 2195 OP- Door Close, Must Be D-Open 1) Description
The operator did not open the operator side door or the splash guard door before pressing the Spindle Tool Unclamp button.
2) Cause of problem
The door in the operator side had not been open before the spindle tool unclamp operation was performed.
3) Action
① Be sure to open the door in the operator side before pressing the Tool Unclamp push-button switch.
② Check the operator's side safety switch as well as the wiring, and repair or replace a defective one if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Main Door Unlock Key Switch
X4.2 (OSDO.M)
OSDO Input Module Slot 07 XJ411 (39) OSDO
Operator Side Door Interlock
X4.3 (OSDI.M)
-S13A Input Module Slot 07 XJ411 (06) S13A
OP Door Close, Must By D-Open
195
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X35.7 TUN.M Spindle Tool Unclamp
R649.6 DCL Operator Door Close Confirm R648.6 M250A Door Interlock Bypass On Aux.
A24.2 2195 OP-Door Close, Must By D-Open
R652.7 ARST Alarm Reset
K10.6 KOPDOR Operator’s Door Interlock Not Used
X4.2 OSDO.M Main Door Unlocking Key Switch
X4.3 OSDI.M Operator Side Door Interlock
X16.1 SG1C.M Splash Guard 1 Close
X16.3 SG2C.M Splash Guard 2 Close
R1420.7 PMGSEL PMG Operation Selected
R4035.3 PMANM APC Man. Mode Aux.
R759.0 APCMST APC Macro Start
R757.5 APCCHG Pallet Change Command
R1159.0 PMGMST PMG Macro Start
K10.4 KSGDOR Splash Guard Door Not Used
K0.6 KHM1000 If HM1000, Set To 1
OP Door Close, Must By D-Open
196
HM 8000(F30i Series) HM8000ALE2A
4.5 2196 Screw Conveyor Overload 1) Description
The screw conveyor has an error. 2) Cause of problem
Excessive current in the screw conveyor motor 3) Action
Ensure that -QM62/63 of the electric cabinet is cut off. Check the 3-phase main wiring, the magnet (-KM62/63), and the insulation state of the motor, and make repair or replacement if necessary.
☞ Overload settings
QM62, QM63 : 0.4 KW : 3.0 A
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Screw Conveyor Overload
X2.4 (SCOL.M)
-QM63 -QM62
Input Module Slot 07 XJ411 (31) SCOL
M -XJ411:
X2.4 31
SCOL
Input Module (AID32E) : Slot 7
C20A: 40, 41 49, 50
a3
a4
SCOLA a3
a4
-QM63
-QM62
Screw Conveyor Motor 1
Screw Conveyor Motor 2
SCOL
A6
Screw Conveyor
197
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
2.4 SCOL.M Screw Conveyor Overload
A24.3 2196 Screw Conveyor Overload
Screw Conveyor Overload
198
HM 8000(F30i Series) HM8000ALE2A
4.6 2197 Chip Conveyor Alarm or Off Mode Alarm 1) Description
An error occurred in the chip conveyor. 2) Cause of problem
An alarm occurred due to an error in the chip conveyor 3) Action
① If the -QM1 brake of the chip conveyor's control box is cut off, check the 3-phase motor of the chip conveyor and take a necessary action if an error is found.
② If –TM1 or –TM2 is tripped, this happens because the rotation confirmation signal that is preceded by the rotation signal is not found. Check the chain and the -SX1 switch of the motor, and take a necessary action if an error is found.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Chip Conveyor Fault X3.6
(CCFT.M) -M241 Input Module Slot 07 XJ411 (10) M241
Address Symbol Coil Comment
X3.6 CCFT.M Chip Conveyor Fault
K9.1 KCHIP Chip Conveyor Used
A24.4 2197 Chip Conveyor Alarm or Off Mode Alarm
Chip Conv. AL or Off Mode Alarm
199
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.7 2198 Auto Power Off Ready 1) Description
The Auto Power Off toggle switch was turned on. 2) Cause of problem
The Auto Power Off toggle switch on the main OP was turned on. 3) Action
To deactivate the function, turn the toggle switch off. ☞ The Auto Power Off function will turn off NC 2 seconds after the toggle switch is turned on
and the function is set to "M30;". Then, the main NFB is tripped according to the TM1 timer settings. (Max: 5 seconds)
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Auto Power Off Ready
X36.7 (APOF.M)
-SA35 Matrix Distribution
Board XJM2 (A21) SA35
Address Symbol Coil Comment
X36.7 APOF.M Auto Power Off Ready
A24.5 2198 Auto Power Off Ready
Chip Conv. AL or Off Mode Alarm
200
HM 8000(F30i Series) HM8000ALE2A
4.8 2202 Machine Lock 1) Description
The Machine Lock Key switch on the main OP is turned on. 2) Cause of problem
① The Machine Lock Key switch on the main OP is set to All Axis or Z Axis. ② Machine Lock Key Switch, Aux. An error in the Function Lock Toggle switch, the wiring
cables or any of its component parts 3) Action
① Turn off the Machine Lock Key switch. ② Check the state of the followings: Machine Lock Key switch (-SK22), soldering inside the
OP (-WJ422), connector (-XC57A51), and pin fixation. And check also the wiring between OP and electric cabinet. Make repair or replacement if necessary.
☞ You must return all axes to their respective reference point after 2202 Machine Lock
alarm is tripped.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
All Axis Machine Lock
X36.5 (MLKA.M)
-SK21 Matrix Distribution
Board XJM2 (A19) SK21A
Z Axis Machine Lock X36.6
(MLKZ.M) -SK22
Matrix Distribution Board
XJM2 (A20) SK22A
Machine Lock
Z-Axis Machine Lock
All-Axis Machine Lock
201
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
G44.1 MLK All Axis Machine Lock
G108.2 ZMLK Z-Axis Machine Lock
R644.0 MLKA Machine Lock All Axis
A25.1 2202 Machine Lock
X36.5 MLKA.M All Axis Machine Lock
R1485.4 R_MLKA.M All Axis Machine Lock
X36.6 MLKZ.M Z-Axis Machine Lock
R1485.5 R_MLKZ.M Z-Axis Machine Lock
202
HM 8000(F30i Series) HM8000ALE2A
4.9 2203 Screw Conveyor CCW Manual Mode 1) Description
The manual toggle switch of the screw conveyor on the main OP was set to "REV." (CCW) so that the screw conveyor is rotating counter clockwise.
2) Cause of problem
The manual toggle switch of the screw conveyor on the main OP was set to "REV." (CCW)
3) Action
① Set the manual toggle switch of the screw conveyor on the main OP to "AUTO" or "FOR." (CW)
② Check the manual toggle switch (-SA38) of the screw conveyor, the soldering (SA38) of the operation panel , the connector (-XJM2) and the pins in this sequence if there is a problem. Make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Screw Conveyor CCW Manual
X37.2 (SCRW.M)
-SA38 Matrix Distribution
Board XJM2 (A22) SA38A
Screw Conveyor CW Manual
X37.1 (SCFW.M)
-SA38 Matrix Distribution
Board XJM2 (B22) SA38B
Address Symbol Coil Comment
K0.6 KHM1000 If HM1000, Set To 1
Y2.5 Y2.5 Screw Conveyor 1,2 Reverse(CCW)
R688.2 SCRV.R Screw Conv. 1,2 Reverse(CCW)
X37.2 SCRW.M Screw Conveyor CCW Manual
Screw Conv. CCW Manual Alarm
203
HM 8000(F30i Series) HM8000ALE2A ㅇ
204
HM 8000(F30i Series) HM8000ALE2A
4.10 2204 Feedrate Override 0% 1) Description
The Feedrate Override switch on the main OP is set to 0%. 2) Cause of problem
① The Feedrate Override switch on the main OP is set to 0%. ① An error in the Feedrate Override switch on the main OP, wiring cables or any of its
component parts 3) Action
① Change the Feedrate Override switch on the main OP to other than 0%. ② Check the state of the followings: Feedrate Override switch (-SR21), soldering inside the
OP and the connector (-XJM2). Make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Feedrate Override 1 X33.0
(FV1.M) -SR21
Matrix Distribution Board
XJM2 (B05) SR21A
Feedrate Override 2 X33.1
(FV2.M) -SR21
Matrix Distribution Board
XJM2 (A06) SR21F
Feedrate Override 3 X33.2
(FV3.M) -SR21
Matrix Distribution Board
XJM2 (B06) SR21B
Feedrate Override 4 X33.3
(FV4.M) -SR21
Matrix Distribution Board
XJM2 (A07) SR21E
Feedrate Override 5 X33.4
(FV5.M) -SR21
Matrix Distribution Board
XJM2 (B07) SR21C
Feedrate Override 6 X33.5
(FV6.M) -SR21
Matrix Distribution Board
XJM2 (A08) SR21G
205
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X33.0 FV1.M Feedrate Override 1
X33.1 FV2.M Feedrate Override 2
X33.2 FV3.M Feedrate Override 3
X33.3 FV4.M Feedrate Override 4
X33.4 FV5.M Feedrate Override 5
X33.5 FV6.M Feedrate Override 6
A25.3 2204 Feedrate Override 0%
Federate Override 0%
206
HM 8000(F30i Series) HM8000ALE2A
4.11 2205 Measurement Device Low Battery 1) Description
The measurement battery of the touch sensor in the interface unit has run out. 2) Cause of problem
① The measurement battery of the touch sensor in the interface unit has run out. ② An error in the battery case, wiring cables or any of its component parts
3) Action
① Replace the battery of the measurement device with a new one. ② Check the battery case, wiring cables and connector (-XJ412) in this sequence. Make
repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Measurrement Device Low Battery
X9.6 (MDLB.M)
-BAT Input Module : Slot 8 XJ412 (1) BAT
Address Symbol Coil Comment
X9.6 MDLB.M Measurrement Device Low Battery
A25.4 2205 Measurrement Device Low Battery
R652.7 ARST Alarm Reset
K3.2 KMDALM Alarm of Measuring Device Used
Measurement Device Low Battery
207
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.12 2206 Measurement Device Alarm 1) Description
An error is detected from the interface unit of the measuring touch sensor. 2) Cause of problem
An error in the measuring touch probe, interface unit, wiring cables or any of its component parts.
3) Action
Check the measuring touch probe, interface unit, wiring cables and connector (-XJ412) in this sequence. Make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Measurrement Device Alarm
X9.7 (MDAL.M)
-ARR Input Module : Slot 8 XJ412 (33) ARR
Address Symbol Coil Comment
X9.7 MDAL.M Measurrement Device Alarm
R800.1 M74F Work Measure Flag
R800.2 SEON Tool Measurrement Sensor On
A25.5 2206 Measurrement Device Alarm
R652.7 ARST Alarm Reset
K3.2 KMDALM Alarm of Measuring Device Used
Measurement Device Low Battery
208
HM 8000(F30i Series) HM8000ALE2A
4.13 2207 Machine Interference Zone Error 1) Description
The machine has entered the machine interference zone. (To prevent possible conflicts between axes)
2) Cause of problem
① The machine has entered the machine interference zone. ② An error in the machine interference zone settings
3) Action
① Rotate the problem-making axis reversely in Handle or Jog mode to remove it. ② Check the values of D860∼D868 in the PMC G data array, and correct them as
appropriate.
(Note) How to correct PMC data
(1) Set the mode switch in the main OP to "MDI".
209
HM 8000(F30i Series) HM8000ALE2A ㅇ
(2) Press the “OFS/SET” key in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(3) Press the [SETTING] button. ▪ The Setting screen appears where the cursor is
positioned at the “PARAMETER WRITE” item on the top. ※ If the screen is not displayed as shown in the right
picture, move to the first page of the Setting Parameter menu (“0” “NO.SRH”) and press the Page Up button three times. Then, you will see the right screen properly.
(4) Enter the number of 1, and keep pressing the INPUT and EXEC keys.
★ The “SW0100 Parameter Enable Switch ON” alarm occurs.
(5) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(6) Locate the Data screen.
① Press the soft keys one after another to move to the Keep Relay screen. ② Press to activate the vertical soft key in the lower right corner and press the [KEEP
RELAY] key.
210
HM 8000(F30i Series) HM8000ALE2A
Activate the vertical soft key
1 2
211
HM 8000(F30i Series) HM8000ALE2A ㅇ
(7) Keep pressing the Page Down button until you see the Group No.5 (D860-D876) of the data table.
(8) Move the cursor to a desired item and enter a value. Then, press INPUT.
(9) When done, move back to “SETTING” and turn off “PARAMETER WRITE”(1 => 0). Then,
press the “RESET” key to release the alarm.
212
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R698.0 IFZONE Machine Interference Zone Error 1
K8.4 KMCIFZ M/C Interference Zone Check Not Used
R407.2 M222 ATC Door Open
R407.3 M223 ATC Door Close
R5320.5 4MATCDO Man ATC Door Open Command
R5320.6 4MATCDC Man ATC Door Close Command
R91.4 YINTLT Y-Axis Position Interlock Large Tool
G132.1 +MIT2 Y Axis +Direction Interlock
K0.6 KHM1000 If HM1000 Set To 1
A25.6 2207 Machine Interference Zone Error
R697.0 IFZN-X X-Axis Interference Zone 1
R697.1 IFZN-Y Y-Axis Interference Zone 1
R697.2 IFZN-Z Z-Axis Interference Zone 1
R800.4 SEN2 Tool Length Sensor On
Machine Interference Zone Error
213
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.14 2208 Machine In Service Mode 1) Description
For the repairing purpose, the machine is in the state of Operator Door Interlock Bypass. 2) Cause of problem
To open the operator door for the repairing reason, the Door Interlock Bypass command (M250) is instructed in MDI mode.
3) Action
① In MDI mode, instruct M251. ② Press the NC Reset button on the main OP.
Address Symbol Coil Comment
R648.6 M250A Door Interlock Bypass On Aux.
A25.7 2208 Machine In Service Mode
R410.6 M250 Machine Service Mode On
R410.7 M251 Machine Service Mode Off
F1.1 RST NC Reset
R652.1 M32H M02/M30 Hold
K51.0 KSMODE Machine Service Mode Select
F0.6 SA Servo Ready
Machine In Service Mode
Door Interlock Bypass On Aux.
214
HM 8000(F30i Series) HM8000ALE2A
4.15 2215 Tool Length Sensor Up/Down Alarm 1) Description
The Tool Length Sensor Up or Down command was instructed but not complete within 5 seconds since then. Or, the Tool Length Sensor Up or Down command was instructed on a machine that was not equipped with the tool length sensor.
2) Cause of problem
① An error in adjusting the position sensor switch ② An error in the Tool Length Sensor Up/Down switch, the wiring, or any of its component
parts ③ A program error
3) Action
① Turn the Tool Length Sensor switch up or down while adjusting the position sensor switch.
② Check the Tool Length Sensor Up/Down switch, the connector (-XJ412) and the attachment of the pin, the wiring through to the electric cabinet, and the input module (AID32E). Make repair or replacement if necessary.
③ The Tool Length Sensor Up or Down command is valid only for machines that have configured the K0.7(Moving Type Tool Meas. is Used) settings.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Tool Measure Sensor Up
X7.4 (TLUP.M)
-SD61 Input Module : Slot 8 XJ412 (27) SD61
Tool Measure Sensor Down
X7.5 (TLDN.M)
-SD62 Input Module : Slot 8 XJ412 (43) SD62
Tool Measure Sensor Up
Y3.3 (TLUP.R)
-YV67 Output Module :
Slot1 XJ412 (27) YV67
Tool Length Sensor Up/Down Alarm
215
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R436.1 TMB66 Tool Length Sensor Up/Down Check
K0.7 KTLENG Moving Type Tool Meas. is Used
R609.1 M76 Tool Measure Sensor Up
R609.2 M77 Tool Measure Sensor Down
A26.6 2215 Tool Length Sensor Up/Down Alarm
R652.7 ARST Alarm Reset
Y3.3 TLUP.R Tool Measure Sensor Up
X7.4 TLUP.M Tool Measure Sensor Up
X7.5 TLDN.M Tool Measure Sensor Down
Tool Length Sensor Up/Down Check
SD61
SD62
216
HM 8000(F30i Series) HM8000ALE2A
4.16 2218 First, There Must Be Z-Ref. Return 1) Description
With the reference point for the Z axis not being set, the operator attempted to set the reference point for the X or Y axis on a machine where the K1.3 is set to 1 (set this value to 1 if restoring the reference point for the Z axis).
2) Cause of problem
With the reference point for the Z axis not being set, the operator attempted to set the reference point for the X or Y axis.
3) Action
Restore the reference point for the Z axis before restoring the reference points for other axes.
Address Symbol Coil Comment
R731.0 ZXYINT XY-Axis Interlock By Z-Ref Position
A27.1 2218 Fiest, There Must Be Z-Ref. Return
G43.7 ZRN Reference Point Return
F94.2 ZPZ Z-Axis 1st Ref. Return
F0.6 SA Servo Ready
K1.3 KZXYIT
First, There Must Be Z-Ref. Return
First, There Must Be Z-Ref. Return
217
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.17 2221 5-Th Clamp/Unclamp Alarm 1) Description
While the optional 5th axis was enabled, the Clamp/Unclamp operation did not match the corresponding completion signal, or it has passed 100 seconds since both Clamp/Unclamp sensor signals were switched on or off simultaneously.
2) Cause of problem
① An error in adjusting the pressure switch ② An error in the wiring or any of its component parts
3) Action
① An error in adjusting the pressure switch Adjust the distance across the switches.
② An error in the wiring or any of its component parts Check the sensor switch, the wiring from the sensor switch to the electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
218
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R435.1 TMB58 5-Th Clamp/Unclamp Check Time
A27.4 2221 5-Th Clamp/Unclamp Alarm
R652.7 ARST Alarm Reset
K7.4 K5THA 5Th-Axis Used
K18.7 KUCENT Keep U-Center Is Used
R740.2 5ACLP 5th-Axis Clamp Command
X5.6 5CLP.M 5th-Axis Unit Clamp
R740.3 5AUNCP 5th-Axis Unclamp Command
X5.7 5ULP.M 5th-Axis Unit Unclamp
R604.3 M38 5th-Axis Clamp
R604.4 M39 5th-Axis Unclamp
R653.0 MEND M-Function Finish
X5.5 5NEG.M 5th-Axis Neglect
5-Th Clamp/Unclamp Alarm
5-Th Clamp/Unclamp Check Time
219
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.18 2222 Program Start Check Alarm 1) Description
In PMG (automated operation) mode, M23 was not instructed at the beginning of any program.
2) Cause of problem
In PMG (automated operation) mode, M23 was not instructed at the beginning of any program.
3) Action
In PMG (automated operation) mode, M23 should be instructed at the beginning of any program.
Program Start Check Alarm
Program Check Time
220
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R629.5 TMB54 Program Check Time
A27.5 2222 Program Start Check Alarm
R652.7 ARST Alarm Reset
F0.5 STL Cycle Start
R520.1 MILK M23 Function Interlock
R520.0 PGSTMC Program Start M Code
R643.3 MDI MDI Mode
G46.1 SBK Single Block
R602.4 M23 Program Start M Code
R634.1 MEM Memory Mode
R652.6 ERST External Reset
K18.0 KPSTP2 Pallet Mag. Stopper2 Used(Set Up)
221
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.19 2223 B-Axis Moving Interlock Alarm 1) Description
With the "K8.6" value being set to 1, the B axis was instructed to move while the X axis was not positioned in the center. (Set the value to 1 if you instruct to move the B axis only when the X axis is positioned in the center)
2) Cause of problem
The B axis was instructed to move while the X axis was not positioned in the center (X1050.). 3) Action
First, move the X axis to the center (X1050.) and then, instruct to move the B axis.
Address Symbol Coil Comment
R695.7 BXINT B-Axis Interlock By X-Axis Zone
F102.3 MV4
A27.6 2223 B-Axis Moving Interlock Alarm
R652.7 ARST Alarm Reset
K8.6 KBIZON B-Axis Is Not Used Interlock Zone
R9000.0 X=Y Compare X=Y
B-Axis Moving Interlock Alarm
B-Axis Interlock By X-Axis Zone
222
HM 8000(F30i Series) HM8000ALE2A
4.20 2234 Gear Shift Lost 1) Description
None of the High, Middle, and Low checking switches of the spindle head gear range is detected to trip.
2) Cause of problem
The check switch for the main spindle gear range has short-circuited or any of its component parts is defective.
3) Action
Check the gear box switch of the main spindle if it works properly on the DGN screen, and take a necessary measure.
Part Name Part No. Symbol Spec. Maker
Switch, Limit ESWLM0018A -SL12, 13, 14 WLD2 Hyun Jeon Co., Ltd.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Spindle Gear Low X6.1
(GSL.M) -SL12 Input Module Slot 08 XJ412 (32) SL12
Spindle Gear Middle X6.2
(GSM.M) -SL13 Input Module Slot 08 XJ412 (48) SL13
Spindle Gear High X6.3
(GSH.M) -SL14 Input Module Slot 08 XJ412 (15) SL14
Spindle Gear Middle Y14.3
(SGRM.V) -YV14 Output Module Slot 4 XJ403 (6) KAR52
Spindle Gear High Y14.4
(SGRH.V) -YV15 Output Module Slot 4 XJ403 (23) KAR53
Spindle Gear Low Y14.5
(SGRL.V) -YV16 Output Module Slot 4 XJ403 (38) KAR54
Cylinder
Piston
SL12 SL13 SL14
YV14
YV15 YV16
223
HM 8000(F30i Series) HM8000ALE2A ㅇ
Note) How to move to DGN (Diagnostic)
(1) Press the “SYSTEM” button in the right side of the main OP monitor. ▪ The following soft key bar will be displayed at the bottom.
(2) Move to the DGN screen.
① Press the soft keys one after another to move to the DGN screen. ② Press any soft key in the right corner to activate the vertical soft key bar, and press the
[STATUS] key.
(3) Enter a desired DGN address and press [SEARCH] to display the DGN screen of your choice.
Activate the vertical soft key
1 2
224
HM 8000(F30i Series) HM8000ALE2A
Reference) How to read DGN (Diagnostic)
Ex) X 0007 0 0 1 1 0 0 1 0 Bit 1, 4 and 5 in Address X7 turn ON while Bit 0, 2, 3, 6 and 7 turn OFF.
Symbol 0 0 1 1 0 0 1 0
Bit No Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Gear Shift Lost
P T
Tool Unclamp
P T
A B
P T
A B
P T
A B Unclamp Middle High Low
Tool Clamp
Gear Shifter
L M H
Φ1.0 Φ1.2 Φ1.0
C D E
Sol. C Sol. D Sol. E Low Off Off On Middle On Off On High OFF On Off
C D E
225
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R1649.0 M150SF Multi M150 And SF Command
K16.7 KMTM150 Used Variable Orientation Func.
R657.4 SGRL Spindle Gear Range Low
R657.5 SGRM Spindle Gear Range Middle
R657.6 SHRH Spindle Gear Range High
R659.0 IGSL Initial Gear Shift Low
R659.1 SFON Initial S-Function On
A29.1 2234 Gear Shift Lost
R659.5 GRL Gear Shift Low
X6.1 GSL.M Spindle Gear Low
R657.5 SGRM Spindle Gear Range Middle
R657.6 SGRH Spindle Gear Range High
Y6.3 GRM.R Spindle Gear Middle
K0.6 KHM1000 If HM1000, Set To 1
Y14.3 SGRM.R Spindle Gear Middle
X6.2 GSM.M Gear Shift Middle
Y6.4 GRH.R Spindle Gear High
Y14.4 SGRH.R Spindle Gear High
X6.3 GSH.M Spindle Gear High
Gear Shift Range Low
Gear Shift Range Middle
Gear Shift Range High
226
HM 8000(F30i Series) HM8000ALE2A
4.21 2240 ATC Not Use (K7.6 Set) 1) Description
With "K7.6" (disable ATC) being set, the tool change (M06;) or tool call (T__:) command was instructed.
2) Cause of problem
The Keep Relay settings were incorrect. 3) Action
If ATC has no particular problem, change Keep Relay "K7.6" from 1 0. Then, instruct Tool Change or Tool Search.
Address Symbol Coil Comment
K7.6 KATC ATC Not Used
R600.3 M06 ATC Change Macro Call
F7.3 TF T Function Strobe
A29.7 2240 ATC Not Used (K7.6 Set)
R652.7 ARST Alarm Reset
ATC Not Use (K7.6 Set)
227
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.22 2241 Wait. Pot or Spindle Tool data Zero 1) Description
When the waiting pot or the tool data of the spindle was set to 0, the Tool Change command was instructed.
2) Cause of problem
① The command of "T00;" is instructed so that the waiting pot is empty. ② The command of "T00;" (M06) is instructed so that the spindle tool is empty. ③ The data value of D452 (Waiting Tool No.) or D450 (Spindle Tool No.) is erased.
3) Action
① Call another tool. ☞ Just in case, ensure that the waiting pot is empty.
② Change to a different tool. ☞ Just in case, ensure that the spindle is empty.
③ Enter an actual tool number in D452 (waiting tool no.) or D450 (spindle tool no.) of the PMC DATA table.
Wait. Pot or Spindle Tool Data Zero
228
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R408.3 M231 Tool Changer M-Code Aux.
G54.0 UI1000 ATC Macro Start Finish
R711.0 WSZERO Wait. Pot & Spdl Data Zero
K0.6 KHM1000 If HM1000, Set To 1
R600.3 M06 ATC Change Macro Call
R708.3 M46F Wait. Pot & Spdl Tool Compare
R724.5 1CYATC Man ATC Change 1 Cycle
R723.2 MMCHST Man Main Changer Start
A30.0 2241 Wait. Pot or Spdl Tool Data Zero
R605.4 M47 Tool Data Compare(TN=STN) Off
R652.7 ARST Alarm Reset
R5052.7 GP2294 GP Wait. Pot and Spdl Tool Zero
229
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.23 2243 Must Be ATC M-Changer Man. 1 Cycle 1) Description
This alarm prompts the operator to perform ATC Changer Arm 1 Cycle manually so as to align the main changer arm since it was step-operated manually.
2) Cause of problem
The ATC changer arm was step-operated manually. 3) Action
Perform ATC Changer Arm 1 Cycle manually to align the main changer arm.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Main Changer Arm Home_HM4D
X8.5 (CAHP.M)
-SX41 Input Module : Slot 8 XJ412 (27) SD61
Address Symbol Coil Comment
X8.5 CAHP Main Changer Arm Home_HM4D
A30.2 2243 Must Be ATC M-Changer Man 1 Cycle
K55.4 KMSMIU ATC M-Changer Step(-) Keep
K0.6 KHM1000 If HM1000, Set To 1
R5052.7 GP2293 GP Must Be ATC Man 1 Cycle
Must Be ATC M-Changer Man. 1 Cycle
230
HM 8000(F30i Series) HM8000ALE2A
4.24 2245 ATC Door Open Close Alarm 1) Description
The ATC Door Close or Open command was instructed but not complete within 20 seconds since then. Both command signals were instructed simultaneously, or the ATC door was not closed while in APC operation.
2) Cause of problem
① An error adjusting the ATC Door Open/Close check limit switch ② The limit switch for checking ATC Door Open/Close or any of its component parts has
an error. 3) Action
① Instruct ATC Door Open/Close alternatively while adjusting both the limit switch and the dog as appropriate.
② Check the limit switch, wiring cables, and I/O module in this sequence. Make repair or replacement if necessary.
Signal Address Device Symbol
I/O Connector
(Pin) Numbering
ATC Door Open X12.1
(ATDO.M) -SL51 Input Module Slot 09 XJ413 (24) SL51
ATC Door Close X12.2
(ATDC.M) -SL52 Input Module Slot 09 XJ413 (39) SL52
ATC Door Open Y3.0
(ATDO.R) -YV37 Output Module Slot 01 XJ400 (3) KAR25
ATC Door Close Y3.1
(ATDC.R) -YV38 Output Module Slot 01 XJ400 (20) KAR26
ATC Door Close Check(SL51)
ATC Door Open Check(SL52)
231
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R627.5 TMB38 ATC Door OP/CL Check Time
K0.6 KHM1000 If HM1000, Set To 1
R763.2 MAPCST MAN APC Start
R789.5 4MPLTCL Man Pallet Clamp
R763.0 APCMAN APC manual Mode
X12.2 ATDC.M ATC Door Close
A30.4 2254 ATC Door Open/Close Alarm
R652.7 ARST Alarm Reset
K10.3 KATCDR ATC Door Not Used
R5050.6 GP2245 GP ATC Door Open/Close Alarm
X12.1 ATDO.M ATC Door Open
ATC Door Open/Close Alarm
ATC Door Open/ Close Check Time
232
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
Y3.0 ATDO.M ATC Door Open
X12.2 ATDC.M ATC Door Close
Y3.1 ATDC.R ATC Door Close
F96.2 ZP2Z Z-Axis 2nd Ref. Return
F94.2 ZPZ Z-Axis 1st Ref. Return
F0.6 SA Servo Ready
R723.4 MMCHSP Man Main Changer Stop
R719.4 MCHSP Man Changer Stop
R631.3 CYSTP Cycle Stop
233
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.25 2247 T-Code or M06 Commanded States 1) Description
A T code is being called, or the M06 command is performing. 2) Cause of problem
The ATC operation was activated while the T code was being called, or the M06 command was performing.
3) Action
Instruct a command only when the current operation is complete.
Address Symbol Coil Comment
R702.1 TCCMD T-Code Command
R702.3 TPSCMD Tool Pot Search Command
R455.1 TCCMDR Tool Change Command
R4010.4 1RTCMDF Re-Change T-Code Command Flag
R719.6 ATCMMD ATC Main OP Manual Mode
R719.2 MCHST Man Changer Start
A30.6 2247 T-Code or M06 Commanded States
R652.7 ARST Alarm Reset
K7.6 KATC ATC Not Used
T-Code or M06 Commanded States
234
HM 8000(F30i Series) HM8000ALE2A
4.26 2250 ATC OP Manual Mode 1) Description
With the ATC magazine being set to Manual mode, you set the mode selection switch of the main OP to AUTO (Edit, Memory, Tape or MDI).
3) Action
In AUTO (Edit, Memory, Tape or MDI) mode, set the mode switch on the touch panel to AUTO.
Address Symbol Coil Comment
R1484.0 RT_MANMD ATC Manual Mode From Macro Ex.
R8326.1 TMMD.M Sub Changer Manual Mode
R635.7 AUT Auto Mode
K7.6 KATC ATC Not Used
A31.1 2250 ATC OP Manual Mode
R5050.7 GP2250 GP ATC OP Manual Switch On
ATC OP Manual Mode
235
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.27 2251 ATC Overtime Alarm 1) Description
The tool call (T__;) or tool change (M06) command was instructed. However, none of the operations were complete within 45 seconds since then.
2) Cause of problem
The machine stopped operation due to an error while performing the tool search or the tool change sequence. The operator will be notified of the overtime alarm for each sequence before this ATC overtime alarm. ☞ See Appendix (ATC Troubleshooting)
3) Action
See the sequence chart or the alarm table, and solve the problem.
ATC Overtime Alarm
ATC Overtime
236
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R628.1 TMB42 ATC Over Time
A31.2 5521 ATC Overtime Alarm
R652.7 ARST Alarm Reset
K7.6 KATC ATC Not Used
R5051.0 GP2251 GP ATC Overtime
R702.0 TCCMDA T-Code Command Aux.
R2401.7 TCCMDF T-Code Command Flag
G455.0 M06CDF M06 Command Flag
R600.3 M06 ATC Change Macro Call
R408.3 M231 Tool Change M-Code Aux.
K0.6 KHM1000 If HM1000, Set to 1
R649.6 DCL Operation Door Close Confirm
R648.6 M250A Door Interlock Bypass On Aux.
R702.2 RTMDCC Re-Chare T-Code Command
R631.3 CYSTP Cycle Stop
Y9.6 TMBK.R TMG Servo Motor Brake Release
Y10.3 SVON.R TMG Servo On
A32.5 2262 ATC Magazine Guard Door Open
R718.4 TSMDM ATC Sub Changer Manual Mode
F0.6 SA Servo Ready
K6.0 KMATRX Matrix Tool Magazine is Used
237
HM 8000(F30i Series) HM8000ALE2A ㅇ
◈ Tool Change (M06) Sequence Chart
Tool Search Start (T _ _;)
No
★ AL 2250 “ATC OP Manual Mode” occurs ATC Sub Changer O.P Auto Mode?
▪ Turn the mode switch in the manual OP to Auto.
Yes
Searched tool No =Spd. Tool No? Yes
No
Searched tool No =Wait. Tool No? Yes
★ Tool Search Complete
No
Double Tool Search? Yes
★ 1st Tool to Tool Magazine, And 2nd Tool In Valid
No
TMG & ATC Initial Position? No
★ AL 2059 “T-Code Command Illegal Position” occurs
▪ Check: X7.7(WPMS.M) –SL37 Wait. Pot Mag. Side X7.6(WPSS.M) –SL36 Wait. Pot Spidle Side X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.1(SCAI.M) –SL31 Sub Changer Arm In X10.2(SCAO.M) –SL32 Sub Changer Arm Out
On
On
On Off
Off Yes
1 Sub Changer Mag. Pot Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
▪ Completed: X10.4(SCPP.M) –SX34 Sub Chan. Mag. Pos. On
On Off
Sub Changer Pot Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.4(SCPP.M) –SX34 Sub Chan. Mag. Pos. On
Yes
2 Sub Changer Arm Out ▪ Output: Y12.1(SCAT.R) –YV32 Sub Changer Arm Out On
▪ Completed: X10.2(SCAO.M) –SL32 Sub Changer Arm Out On
238
HM 8000(F30i Series) HM8000ALE2A
Sub Changer Arm Out O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.2(SCAO.M) –SL32 Sub Changer Arm Out X10.1(SCAO.M) –SL31 Sub Changer Arm In
On
Off
Yes
3 Sub Changer Wait. Pot Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
▪ Completed: X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos. On
On Off
Sub Changer Waiting Pot Pos.? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.5(CAWP.M)–SX35 Sub Chan.Wait. Pot Pos. On
Yes
4 Sub Changer Arm In ▪ Output: Y2.5(SBAI.R) –YV31 Sub Changer Arm In On
▪ Completed: X10.1(SCAO.M) –SL31 Sub Changer Arm In On
Sub Changer Arm In O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.1(SCAO.M) –SL31 Sub Changer Arm In X10.2(SCAO.M) –SL32 Sub Changer Arm Out
On Off
Yes
5 Sub Changer Home Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
▪ Completed: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. On
Off On
Sub Changer Home Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. On
Yes
6 Waiting Pot Spindle Side ▪ Output: Y12.0(WPSS.R) –YV40 Waiting Pot Spd. Side On
▪ Completed: X7.6(WPSS.M) –SL36 Waiting Pot Spindle Side On
Waiting Pot Spindle Side? No
★ AL 2291 “Waiting Pot Spd/Mag. Side Alarm” occurs
▪ Check: X7.6(WPSS.M) –SL36 Waiting Pot Spindle Side X7.7(WPMS.M) –SL37 Waiting Pot Mag. Side
On Off
Yes
Tool Search Finish
239
HM 8000(F30i Series) HM8000ALE2A ㅇ
※ Tool Recharge Step Sequence Chart
M06 M-Function End
4 Sub Changer Mag. Pot Position
▪ Completed: X10.4(SCPP.M) –SX34 Sub Chan. Mag. Pos. On
▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On On
Off
Off
Sub Changer Pot Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.4(SCPP.M) –SX34 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos.
On
1 Waiting Pot Magazine Side ▪ Output: Y2.7(WPMS.R) –YV30 Waiting Pot Mag. Side On
▪ Completed: X7.7(WPMS.M) –SL32 Waiting Pot Mag. Side On
Waiting Pot Spindle Side? No
★ AL 2291 “Waiting Pot Spd/Mag. Side Alarm” occurs
▪ Check: X7.6(WPSS.M) –SL36 Waiting Pot Spindle Side X7.7(WPMS.M) –SL32 Waiting Pot Mag. Side On
Off
Yes
2 Sub Changer Wait. Pot Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
On Off
▪ Completed: X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos. On
On Off
Sub Changer Waiting Pot Pos.? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.4(SCPP.M) –SX34 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos. On Yes
3 Sub Changer Arm Out ▪ Output: Y12.1(SCAT.R) –YV32 Sub Changer Arm Out On
▪ Completed: X10.2(SCAO.M) –SL32 Sub Changer Arm Out On
Sub Changer Arm Out O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.2(SCAO.M) –SL32 Sub Changer Arm Out X10.1(SCAO.M) –SL31 Sub Changer Arm In
On
Off
Yes
Yes Go to “A”
Off Off
Off
Off
240
HM 8000(F30i Series) HM8000ALE2A
Yes
6 Sub Changer Home Position ▪ Output: Y12.2(SCS1.R) –YV33 Sub Changer Pos. 1 Y12.3(SCS2.R) –YV34 Sub Changer Pos. 2 Y12.4(SCS3.R) –YV35 Sub Changer Pos. 3 Y12.5(SCS4.R) –YV36 Sub Changer Pos. 4
▪ Completed: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. On
On Off
Sub Changer Home Position? No
★ AL 2272 “ATC Sub Changer Pos. Check Alarm” occurs
▪ Check: X10.3(SCHP.M) –SX33 Sub Chan. Home Pos. X10.4(SCPP.M) –SX34 Sub Chan. Pot Pos. X10.5(SCWP.M) –SX35 Sub Chan. Wait. Pos.
On
Off
On
Yes
ATC Re-Charge End
5 Sub Changer Arm In ▪ Output: Y2.5(SBAI.R) –YV31 Sub Changer Arm In On
▪ Completed: X10.1(SCAO.M) –SL31 Sub Changer Arm In On
Sub Changer Arm In O.K? No
★ AL 2273 “ATC Sub Tool In/Out Alarm” occurs
▪ Check: X10.1(SCAO.M) –SL31 Sub Changer Arm In X10.2(SCAO.M) –SL32 Sub Changer Arm Out
On Off
Yes
A
Off Off
241
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.28 2259 Wait Pot No. = Spindle Pot No. 1) Description
The spindle tool number is identical to the tool number of the waiting pot. 2) Cause of problem
① D450 and D452 have the same data value. ② The same number is detected. This is because of an incorrect count of the tool number or
a manual operation by the operator. 3) Action
① Check the number of each tool, and assign a unique number to each tool. ② If you need to change only the tool number of the spindle, simply instruct “M45T****” in
MDI mode.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
TMG Servo On Y10.3
(SVON.R) - SVON
Output Module Slot : 03
XJ402 (66) SVON
D450 : Tool number of the spindle
D452 : Tool number of the waiting pot
242
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R715.4 WP=SP Wait Pot No. = Spindle Pot No.
R700.3 TCMDF T-Code Command Flag
R739.4 M231INP M231 Initial Position
R739.4 M231INP M231 Initial Position
R701.2 TFINP1 T-Code Initial Pos.1(TCMDF)
K0.6 KHM1000 If HM1000, Set To 1
R709.2 M06INP M06 Initial Position
R713.4 T0SKIPA T0 Skip Aux.
A32.2 2259 Wait pot is Spindle Same Counter
R652.7 ARST Alarm Reset
Y10.3 SVON.R TMG Servo On
K7.6 KATC ATC Used
Wait Pot Is Spindle Same Counter
243
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.29 2260 Tool Mag. Rotation Over Time 1) Description
The tool magazine fails to complete the rotation within 230 seconds after instructed to do so by the operation signal (CW: Y39.0, CCW: Y39.1).
2) Cause of problem
① The number of a tool to be inserted in the waiting pot is 0. ② The tool detection switch for the waiting pot that was supposed to be empty was tripped.
3) Action
① Instruct the T code to call tools. ② Check the proximity switch, the wiring, and the I/O module in this sequence. Make repair
or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
TMG Servo On Y10.3
(SVON.R) - SVON
Output Module Slot : 03
XJ402 (66) SVON
TMG Servo Motor Brake Release
Y9.6 (TMBK.R)
- KA85 Output Module Slot :
03 XJ402 (10) KA85
Address Symbol Coil Comment
R445.6 TMB143 ATC Mag. Rotation Overtime
A32.3 2260 Tool Mag. Rotation Overtime
Tool Mag. Rotation Over Time
Man Mag. Rotation Over time
244
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R652.7 ARST Alarm Reset
K7.6 KATC ATC Used
K0.6 KHM1000 If HM1000, Set To 1
Y10.3 SVON.R TMG Servo On
Y9.6 TMBK.R TMG Servo Motor Brake Release
R743.2 TSHPB TMG Search On By PB S/W
R446.1 TMB146 Man Mag. Rot. Overtime
R652.7 ARST Alarm Reset
A32.3 2260 Tool Mag. Rotating Overtime
K6.0 KMATRX Matrix Tool Magazine is Used
F0.6 SA Servo Ready
245
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.30 2262 ATC Magazine Guard Door Open 1) Description
The door of the tool magazine is open. 2) Cause of problem
The door of the tool magazine is open or there is an error in the switch or any of its component parts.
3) Action
Close the tool magazine door. Check the safety switch, the wiring, and the I/O module in this sequence, make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Tool Magazine Door Interlock
X12.3 (MDI2.M)
-S85A Input Module : Slot 9 XJ413 (6) S85A
Tool Magazine Door Interlock
X12.4 (MDIT.M)
-S85 Input Module : Slot 9 XJ413 (23) S85
Mag. Door Lock(Sol. Type)
Y11.6 (MDIT.R)
-KA36 Output Module Slot :
03 XJ402 (1) KA36
246
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R436.4 TMB69 Mag. Door S/W Check Time
K6.0 KMATRX Matrix Tool Magazine is Used
ATC Magazine Guard Door Open
Tool Magazine Door Interlock
Magazine Door S/W Check Time
247
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
F212.6 AL81-FM Door Open Alarm of Matrix Mag.
R635.6 MAN Manual Mode
R723.1 MSCHSP Man ATC Sub Changer Stop
R725.2 MSCHST Man Sub Changer Start
R719.3 MSCSTF Man Changer Start Flag
R5320.0 4MSCSTF Man Sub Changer Start Flag
R635.7 AUT Auto Mode
R455.0 M06CDF M06 Command Flag
R2410.7 TCCMDF T-Code Command Flag
R709.0 ATCMST ATC Macro Start
R702.7 RTCCMD Re-Charge T-Code Command
R718.0 MTMFWD Man Tool Mag. Forward
R718.1 MTMREV Man Tool Mag. Reverse
R652.7 ARST Alarm Reset
A32.5 2262 ATC Magazine Guard Door Open
K9.6 KMDINI ATC Magazine Door SW. Ignore
K7.6 KATC ATC Used
R717.7 MDIT Tool Magazine Door Interlock
X12.3 MDI2.M Tool Magazine Door Interlock
Y11.6 MDIT.R Mag. Door Lock(Sol. Type)
X12.4 MDIT.M Tool Magazine Door Interlock
248
HM 8000(F30i Series) HM8000ALE2A
249
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.31 2264 Tool Magazine Servo Battery Alarm 1) Description
A battery alarm occurred from the servo drive unit that drives the tool magazine. 2) Cause of problem
① The battery of the servo drive unit that drives the tool magazine has been discharged. ② An error in the servo drive unit or the battery case, the wiring, or the connector
3) Action
① Replace the current battery with a new one. ② Refer to the service manual of the servo drive, and make repair or replacement if
necessary. ☞ Refer to "Troubleshooting by the servo drive alarm".
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Tool Magazine Battery Alarm
X5.4 (BALM.M)
BALM Input Module Slot : 7,
9 XJ413 (19) BALM
▪ The servo drive that is connected to the motor consumes the battery for driving itself if no main (external) power is applied.
▪ Battery life (Max current consumption: 150㎂) 1.44 ~ 1.5 years at 25℃ 0.89 ~ 0.96 year at 75℃
Servo Drive Battery
250
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X5.4 BALM.M Tool Magazine Battery Alarm
A32.7 2264 Tool Magazine Battery Alarm
R652.7 ARST Alarm Reset
K7.6 KATC ATC Not Used
☞ Refer to "Troubleshooting by the servo drive alarm".
1) UV (Under Voltage) Alarm : This alarm warns that the main unit is running out of direct voltage.
Message on the front display
Description This alarm is tripped when the internal DC link voltage falls below the set value.
Troubleshooting
▪ Measure the input voltage on the drive terminal box to check if the tester reads between 200V and 220V. If not, take a necessary measure to adjust the voltage to between 200V and 220V.
▪ Check if the motor has a short circuit. If so, replace the motor cables
wherever applicable. ▪ Then, turn off the turret servo drive and turn it back on. See if there occurs
the same alarm. If so, replace the drive because this alarm is tripped from the defective drive.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Tool Magazine Servo Battery Alarm
251
HM 8000(F30i Series) HM8000ALE2A ㅇ
2) OV (Over Voltage) Alarm : This alarm warns that the direct voltage to the main unit is excessive.
Message on the front display
Description This alarm is tripped when the internal DC link voltage falls below the set value.
Troubleshooting
▪ Measure the input voltage on the drive terminal box to check if the tester reads between 200V and 220V. If not, take a necessary measure to adjust the voltage to between 200V and 220V.
▪ Remove the drive and disconnect the regenerative resistor connector to
check if the regenerative resistor (installed at a side of the drive) measures at 26Ω. If not, replace the resistor.
▪ Check if the motor has a short circuit. If so, replace the motor cables
wherever applicable. ▪ Then, turn off the turret servo drive and turn it back on. See if there occurs
the same alarm. If so, replace the drive because this alarm is tripped from the defective drive.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Regenerative Resistor
Connector
Power Board (PAB)
Regenerative Resistor
252
HM 8000(F30i Series) HM8000ALE2A
3) OH (Over Heat) Alarm : This is a overheat alarm.
Message on the front display
Description This alarm is tripped if the internal IPM device is overheat or has an error.
Troubleshooting
▪ Turn off the turret servo drive and wait until it cools down. Then, turn it back on and see if the same alarm occurs again. If the problem persists, replace the drive because the IPM module of the drive is defective.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
4) OC (Over Current) Alarm : This is an over-current alarm.
Message on the front display
Description This alarm is tripped when the motor is over-currented.
Troubleshooting
▪ Check if the acceleration parameter (No. 29) and the deceleration parameter (No. 30) are set to less than specified.
▪ Check the wiring of the motor power cable, and replace it if necessary. Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the
turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
253
HM 8000(F30i Series) HM8000ALE2A ㅇ
5) CA Alarm : This is an encoder-related alarm, against which the troubleshooting action differs according to the drive version (11 bit old drive, and 17 bit new drive).
Message on the
front display
Description 11 Bit ▪ This alarm occurs if A, B, or Z of the encoder signals has an error.
17 Bit ▪ This alarm occurs when the turret servo drive is turned on before
the encoder is reset.
Troubleshooting
11 bit
▪ Disconnect the encoder data transfer cable from the turret servo drive, and reconnect it as it may be connected improperly.
▪ Check the wiring of the encoder data transfer cable, and replace it if necessary.
▪ Check if the motor encoder connector is short-circuited. If so,
replace the motor.
17 bit
▪ Turn off the turret servo drive to reset the motor encoder. 5 seconds after the encoder is reset, turn back on the turret servo drive. The alarm will be released.
▪ This action applies to turret servo drive versions of DVSD-TT-14A through DVSD-TT-14A-04. For later versions than DVSD-TT-14A-05, the CA alarm is deleted.
Encoder Data Transfer Cable
Motor Encoder Connector
254
HM 8000(F30i Series) HM8000ALE2A
6) CO Alarm : This alarm applied to the 17-bit turret servo drive version of DVSD-TT-14A-05 or later, which is related to a signal error in the encoder.
Message on the
front display
Description This alarm occurs if the signal from the encoder has an error.
Troubleshooting
▪ Disconnect the encoder data transfer cable from the turret servo drive, and reconnect it as it may be connected improperly.
▪ Check the wiring of the encoder data transfer cable, and replace it if necessary.
▪ Check if the motor encoder connector is short-circuited. If so, replace the
motor.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder Data Transfer Cable
Motor Encoder Connector
255
HM 8000(F30i Series) HM8000ALE2A ㅇ
7) OS (Over Speed) Alarm : This is an over-speed alarm.
Message on the front display
Description This alarm occurs when the motor speed exceeds the limit.
Troubleshooting
▪ Disconnect the encoder data transfer cable from the turret servo drive, and reconnect it as it may be connected improperly.
▪ Check the wiring of the encoder data transfer cable, and replace it if
necessary. ▪ Check if the motor has a short circuit. If so, replace the motor cables
wherever applicable. ▪ Check if the motor encoder connector is short-circuited. If so, replace the
motor.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder Data Transfer Cable
Motor Power Connector
256
HM 8000(F30i Series) HM8000ALE2A
8) OL (Over Load) Alarm : This is an overload alarm.
Message on the front display
Description
▪ This alarm occurs if the overload state lasts for more than specified. ▪ Overload detection time 250% ~ : 1 second, 220% ~ : 24 seconds, 200% ~ : 48 seconds 180% ~ : 96 seconds, 160% ~ : 192 seconds, 150% ~ : 384 seconds 140% ~ : 769 seconds, 130% ~ : 1536 seconds
Troubleshooting
Use the Keep Relay settings to set the turret to be in the state of Unclamp. Turn the turret manually and see if it rotates smoothly. If not, increase parameter no. 10 and parameter no. 11 by 10 and check the turret again. If the problem persists, the turret itself has a problem. ▪ Check if the parameters are set properly. (Note) For the 11-bit AS turret servo drive of DASD-CT15SPXC-05 or later
versions, and the 17-bit new turret servo drive of DVSD-TT-14A-04 or later versions, parameter no. 4 is set to 2048 by default. If you change the value, you will have the overload alarm.
▪ This alarm occurs if the turret has a tool overload or asymmetric load, or has a mechanical error. Turn the turret manually while increasing parameter no. 10 and parameter no. 11 by 10 until the turret rotates smoothly.
▪ If you are using a separate Clamp/Unclamp solenoid relay, the turret will be clamped and overload the turret motor if the relay has an error, causing the overload alarm to be tripped. If this is the case, check the relay and take a necessary measure.
▪ Disconnect the motor power cable and the encoder data transfer cable from the turret servo drive, and reconnect them as they may be connected improperly.
▪ Check the wiring of the motor power cable and the encoder data transfer cable, and replace them if necessary.
▪ Then, turn off the turret servo drive and turn it back on. See if there occurs the same alarm. If so, replace the drive because this alarm is tripped from the defective drive.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Motor Power Cable
Encoder Data Transfer Cable
257
HM 8000(F30i Series) HM8000ALE2A ㅇ
9) SE Alarm : This is a double interruption alarm.
Message on the front display
Description This alarm occurs if the CPU or the MCB of the turret servo drive has an error.
Troubleshooting
▪ Reset the parameters of the turret servo drive, and set them as appropriate again.
▪ Then, turn off the turret servo drive and turn it back on. See if there occurs the same alarm. If so, replace the drive because this alarm is tripped from the defective drive (a MCB error).
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
10) PE (Parameter Error) Alarm : This is a parameter error alarm.
Message on the front display
Description This alarm occurs if the parameters of the turret servo drive are out of the set range.
Troubleshooting
▪ Reset the parameters and the position correction values of the turret servo drive, and set the parameters again as appropriate and set the reference point again.
▪ Then, turn off the turret servo drive and turn it back on. See if there occurs the same alarm. If so, replace the drive because this alarm is tripped from the defective drive (a MCB error).
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
258
HM 8000(F30i Series) HM8000ALE2A
11) RP (Residue Pulse) Alarm(ALP-rP) : This alarm occurs due to an excessive position deviation.
Message on the front display
Description This alarm occurs if the residue pulse (RP) exceeds the limit specified for parameter no. 19 while the turret servo drive is controlling the position information.
Troubleshooting
▪ Check if parameter no. 19 of the residue pulse is set to less than specified. ▪ Disconnect the encoder data transfer cable from the turret servo drive, and
reconnect it as it may be connected improperly. ▪ Check if the motor has a short circuit. If so, replace the motor encoder
cables wherever applicable. ▪ Check if the motor encoder connector is short-circuited. If so, replace the
motor.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder Data Transfer Cable
Motor Encoder Connector
259
HM 8000(F30i Series) HM8000ALE2A ㅇ
12) EN (Battery) Alarm : This alarm occurs due to an encoder backup battery error.
▪ The servo drive that is connected to the motor consumes the battery for driving itself if no main (external) power is applied.
▪ Battery life (Max current consumption: 150㎂) 1.44 ~ 1.5 years at 25℃ 0.89 ~ 0.96 year at 75℃
Message on the
front display
Description This alarm is tripped when the encoder backup battery of the turret servo drive is discharged or loose.
Troubleshooting
▪ Replace the encoder backup battery of the turret servo drive. ▪ Remove the turret servo drive and check the backup battery of the internal
encoder if the battery connector is connected properly. If you find an error from the servo drive, replace the servo drive.
Note) The turret servo drive alarm is tripped to protect the servo drive, the motor, and the turret unit. You restart the drive and release the alarm doesn't mean either the drive or the motor has an error. You do not need to replace any of these two.
Encoder Backup Battery Connector
Main Control Board (MCB)
Encoder Backup Battery
260
HM 8000(F30i Series) HM8000ALE2A
4.32 2265 VPF Off of Tool Magazine Alarm 1) Description
The position of the servo motor that drives the tool magazine is unknown. 2) Cause of problem
An error in the servo drive unit or the battery case, the wiring, or the connector 3) Action
Find and replace a defective part
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Tool Magazine Battery Alarm
X13.4 (VPF.M)
VPF Input Module Slot : 7,
9 XJ413 (19) VPF
Address Symbol Coil Comment
R702.1 TCCMD T-Code Command
R702.2 RTCCMD Re-Charge T-Code Command
R455.1 TCCMDR Tool Change Command
R836.2 VPF1C VPF Off of Tool Magazine
R443.6 TMB127 VPF Check Time
A33.0 2265 VPF Off of Tool Magazine
R652.7 ARST Alarm Reset
VPF Off of Tool Magazine Alarm
VPF Off of Tool Magazine
261
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
F0.6 SA Servo Ready
K7.6 KATC ATC Not Used
Y10.3 SVON.R TMG Servo On
X13.4 VPF.M TMG Servo Verify
K6.0 KMATRX Matrix Tool Magazine is Used
262
HM 8000(F30i Series) HM8000ALE2A
4.33 2266 Servo Mag. Tool Number Error 1) Description
The tool number could not be detected within 10 seconds after the tool magazine started to rotate.
2) Cause of problem
An error in the servo motor or the servo drive unit 3) Action
Check the servo motor and the servo drive unit if they work normally. Replace any defective part.
Address Symbol Coil Comment
R836.0 TX=YER Tool Search Error
R443.4 TMB125 Tool Compare Check Time
A33.1 2266 Servo Mag. Tool Number Error
R652.7 ARST Alarm Reset
K7.6 KATC ATC Not Used
K6.0 KMATRX Matrix Tool Magazine is Used
R710.6 WTP=0 Wait. Tool Pot Tool Data “0”
R713.4 T0SKIPA T0 Skip Aux.
Servo Mag. Tool Number Error
Tool Compare Check Time
263
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.34 2270 ATC Mag. Pot Tool Out SW. Alarm 1) Description
The position sensor on the hydraulic cylinder that performs the Tool Pull Out operation turned off.
2) Cause of problem
① An error in adjusting the Tool Magazine Tool Pull Out limit switch ② An error in the limit switch or any of its electric parts
3) Action
① An error in adjusting the position sensor switch Adjust the limit switch on the hydraulic cylinder that performs the Tool Magazine Pot Tool Out operation as appropriate.
② An error in the wiring or any of its component parts Check the limit switch, the wiring from the limit switch to the electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Tool Pull-Out Confirm
Y12.6 (TPOC.R)
-YV39 Input Module Slot : 02 XJ401 (30) KAR39
Mag. Tool Pot-Out Confirm
X10.0 (TPOT.M)
-SL39 Input Module Slot : 09 XJ413 (16) SL39
Mag. Tool Pot-Out Confirm Switch
Mag. Tool Pot-Out Confirm Switch
264
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
Y4.6 TLPO.R Tool Pull-Out Confirm
K0.6 KHM1000 If1000, Set To 1
Y12.6 TPOC.R Tool Pool Out Confirm
X10.0 TPOT.M Mag. Tool Pot-Out Confirm
R5300.3 MTOI.M Mag. Tool Pot Tool Out Interlock
K7.6 KATC ATC Not Used
K6.0 KMATRX Matrix Tool Magazine is Used
A33.5 2270 ATC Mag. Pot Tool Out SW. Alarm
ATC Mag. Pot Tool Out SW. Alarm
265
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.35 2272 ATC Sub Changer Position Check Alarm 1) Description
An operation signal (Home Position, Mag. Position, Pot Position) of the sub changer was instructed. However, none of the operations were complete within 10 seconds since then. Or, the position switch of the sub changer was turned off.
2) Cause of problem
① An error in adjusting the position switch of the sub changer ② An error in the position switch of the sub changer, the wiring, or any of its component
parts 3) Action
① An error in adjusting the position sensor switch Adjust the proximity switch on the rear of the sub changer as appropriate.
② An error in the wiring or any of its component parts Check the proximity switch, the wiring from the proximity switch to the electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Sub Changer Home Position
X10.3 (SCHP.M)
-SX33 Input Module : Slot 8,
9 XJ413 (15) SX33
Sub Changer Mag. Pot Position
X10.4 (SCMP.M)
-SX34 Input Module : Slot 8,
9 XJ413 (31) SX34
Sub Changer Wait. Pot Position
X10.5 (SCWP.M)
-SX35 Input Module : Slot 9 XJ413 (47) SX35
ATC Sub Changer Position Check Alarm
266
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R626.7 TMB32 Tool Changer Pos. Check Time
A33.7 2272 ATC Sub Changer Pos. Check Alarm
R352.7 ARST Alarm Rest
K7.6 KATC ATC Not Used
Y4.2 SCP1.R Sub Changer Position 1
Y4.3 SCP2.R Sub Changer Position 2
Y4.4 SCP3.R Sub Changer Position 3
Y4.5 SCP4.R Sub Changer Position 4
K0.6 KHM1000 If HM1000, Set To 1
Y12.2 SCS1.R Sub Changer Position 1
Y12.3 SCS2.R Sub Changer Position 2
Y12.4 SCS3.R Sub Changer Position 3
Y12.5 SCS4.R Sub Changer Position 4
X10.3 SCHP.M Sub Changer Home Position
Tool Changer Position Check Time
267
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
X10.4 SCMP.M Sub Changer Mag. Pot Position
X10.5 SCWP.M Sub Changer Wait. Pot Position
F0.6 SA Servo Ready
R723.1 MSCHSP Man ATC Sub Changer Stop
R631.3 CYSTP Cycle Stop
Home Pos. (SX33)
Mag. Pot Pos. (SX34)
Wait Pot Pos. (SX35)
268
HM 8000(F30i Series) HM8000ALE2A
4.36 2273 ATC Sub Tool Arm In/Out Alarm 1) Description
The Sub Changer Arm In/Out operation was instructed. However, none of the operations were complete within 5 seconds since then. Or, both the Sub Changer Arm In/Out position switches were turned on or off.
2) Cause of problem
① An error in adjusting the Sub Changer Arm In/Out position switch ② An error in the position switch of the sub changer, the wiring, or any of its component
parts 3) Action
① An error in adjusting the position sensor switch ② Adjust the Sub Changer Arm In/Out proximity switch as accurate as possible. ③ An error in the wiring or any of its component parts
Check the proximity switch, the wiring from the proximity switch to the electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Sub Changer Arm In
X10.1 (SCAI.M)
-SX31 Input Module : Slot 9 XJ413 (32) SX31
Sub Changer Arm Out
X10.2 (SCAO.M)
-SX32 Input Module : Slot 9 XJ413 (48) SX32
ATC Sub Tool Arm In/Out Alarm
Arm In (SL32)
Arm Out (SL31)
269
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R627.0 TMB33 Tool Arm In/Out Check Time
A34.0 2273 ATC Sub Tool Arm In/Out Alarm
R352.7 ARST Alarm Rest
K7.6 KATC ATC Not Used
Y4.0 SCAI.R Sub Changer Arm In
K0.6 KHM1000 If HM1000, Set To 1
Y2.5 Y2.5
X10.1 SCAI.M Sub Changer Arm In
Y4.1 SCAO.R Sub Changer Arm Out
Y12.1 SCAT.R Sub Changer Arm Out
X10.2 SCAO.M Sub Changer Arm Out
F0.6 SA Servo Ready
R723.1 MSCHSP Man ATC Sub Changer Stop
R631.3 CYSTP Cycle Stop
ATC Arm In/Out Check Time
270
HM 8000(F30i Series) HM8000ALE2A
4.37 2321 APC Initial Position Alarm 1) Description
APC is not in the initial operating conditions. 2) Cause of problem
① An error in adjusting the position sensor switch ② An error in the APC position sensor switch or any of its electric parts
3) Action
① An error in adjusting the position sensor switch Adjust the APC proximity switch as correct.
② An error in the wiring or any of its component parts Check the switch, the wiring from the switch to the electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
※ APC Initial Position
Address X18.5 X18.6 X18.1 X18.3
Status 0(Off) or1 (On) 1(On) or 0(Off) 1(On) 0(Off)
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC 180 CW Position
X18.5 (P18F.M)
-SX75 Input Module : Slot
8,10 XJ410 (47) SX75
APC 180 CCW Position
X18.6 (P18R.M)
-SX76 Input Module : Slot
8,10 XJ410 (30) SX76
APC Pos.0/ Arm Open
X18.1 (APOP.M)
-SX71 Input Module : Slot
8,10 XJ410 (32) SX71
APC Pos.90/ Arm Close
X18.3 (APLC.M)
-SL73 Input Module : Slot
8,10 XJ410 (15) SL73
APC Initial Position Alarm
271
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R769.7 APCINT APC Arm Interlock
R757.5 APCCHG Pallet Change Command
R759.0 APCMST APC Macro Start
K0.6 KHM1000 If HM1000, Set To 1
R607.2 M61 APC 1 Unload
R607.3 M62 APC 1 Load
K7.7 KAPC APC Not Used
R635.7 AUT Auto Mode
X18.5 P18F.M APC 180 CW Position
X18.6 P18R.M APC 180 CCW Position
X18.1 APOP.M APC Pos.0/Arm Open
X18.3 APCL.M APC Pos.90/Arm Close
R772.5 APRETC APC ARM Return Confirm
Y8.4 CADV.R Pallet Changer Arm Advance
X16.1 SG1C.M Splash Guard 1 Close
X16.0 SG1O.M Splash Guard 1 Open
X16.3 SG2C.M Splash Guard 2 Close
X16.2 SG2O.M Splash Guard 1 Open
K10.4 KSGDOR Splash Guard Door Not Used
X14.1 ARET.M Pallet Changer Arm 1 Return
X14.3 RETS.M Pallet Changer Arm Return Slowdown
APC Arm Interlock
272
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X14.0 AADV.M Pallet Changer Arm 1 Advance
X14.4 PMPS.M Pallet Changer Arm 1 Middle Position
X15.1 AAB2.M Pallet Changer Arm 2 Return
X15.3 ABS2.M Pallet Changer Arm 2 Return Slowdown
X15.0 AAF2.M Pallet Changer Arm 2 Advance
X15.4 ABP2.M Pallet Changer Arm 2 Middle Position
APC CCW (SX76)
APC CW (SX75)
APC 180 CCW Position (SX76)
APC 180 CW Position (SX75)
APC Arm Open(SX71)
APC Arm Close (SL73)
0.8~1.2mm
Proximity Switch Dog
273
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.38 2322 APC Set-Up Station Door Open 1) Description
The APC set-up station door was open. 2) Cause of problem
① The set-up station door was open. ② An error in the safety switch that detects the door opening, the wiring, or defective
component parts 3) Action
① Close the set-up station door. ② Check the safety switch that detects the door is open, the wiring from the switches to the
electric cabinet as well as the I/O module if there is a problem. Repair or replace the defective part if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Setup Door Interlock 2_HM4D
X8.1 (SSDI2.M)
-S13 Input Module : Slot 8 XJ412 (24) S13
Setup Door Interlock_HM4D
X8.2 (SUIT.M)
-S12 Input Module : Slot 8 XJ412 (39) S12
Setup Door Open Y37.1
(SETD.R) -E12
Matrix Distribution Board
XJM3 (A18) -KA38
APC Set-Up Station Door Open
274
HM 8000(F30i Series) HM8000ALE2A
HD4D Set-Up Door Interlock Check
APC Set-Up Station Door Open
275
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R762.0 2322A1 HM10 APC Set-Up Station Door Open
R762.1 2322A2 HM4D APC Set-Up Station Door Open
R456.7 TMB227 HM4D Setup Door Interlock Check Time
R635.6 MAN Manual Mode
R763.4 MAPCSP Manual APC Stop
R763.2 MAPCST Manual APC Start
R788.3 4MAPSTF Manual APC Start Flag
R635.7 AUT Auto Mode
R760.0 M61CD APC1 Unload Command
R761.0 M62CD APC2 Load Command
X29.1 SETU.M Set Up
X72.3 SEU2.M Set Up 2
R652.7 ARST Alarm Reset
A40.1 2322 APC Set-Up Station Door Open
K10.2 KAUTDR Auto Door for Setup Door Used
R1026.1 MCHAST Man Pallet Changer Start
R1056.2 MCHASP Man Pallet Changer Stop
R1075.2 MSESTP Man Set-Up Stop
R1063.1 MSEUST Manual APC Start
R1056.3 MCHASTF Man Pallet Changer Start Flag
R1075.3 MSESTF Manual Set-Up Start Flag
R1003.7 MPMROT Man. Magazine Rotation Keep
R1001.5 PMGINX Pallet Search Command
R1071.0 SETPUL Set-Up Pallet Unload Command
R1072.0 SETPLD Set-Up Pallet Load Command
Set-Up Door Open
276
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
A40.1 2322 APC Set-Up Station Door Open
K8.3 KDCLAR Alarm Reset By Door Close
K10.5 KSETDR Set-Up Door Interlock Not Used
R1420.7 PMGSEL PMG Operation Selected
K11.3 KSET Set-Up Station Not Used
K7.7 KAPC APC Not Used
K18.3 KSEITK Setup Station Interlock is Used, PMG
R762.3 SETDIT Setup Door Open
K19.3 KMPS Used Multi Pallet Station
X8.2 SUIT Setup Door Interlock_HM4D
X8.1 SDI2.M Setup Door Interlock2_HM4D
Y37.1 SETD.R Setup Door Open
R1385.7 PSETDCL Setup Door Close From MPS
Set Up Door Interlock (S12)
Set-Up Station Door Interlock
277
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.39 2323 4-Th Clamp/Unclamp Alarm 1) Description
It has passed 15 seconds since the position signal of the pallet or the table clamp/unclamp operation did not match the corresponding instruction signal.
2) Cause of problem
① An error in adjusting the position switch that checks the position of the pallet or table Clamp/Unclamp operation
② An error in the position switch that checks the position of the pallet or table Clamp/Unclamp operation, or any of its component parts
3) Action
① Adjust the position switch that checks the position of the pallet or table Clamp/Unclamp operation as accurate as possible.
② Check the switch, the wiring cables, and the I/O module in this sequence. Make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Pallet Unclamp Y15.0
(PAUC.R) -KAR57 Output Module : Slot 4 XJ403 (3) -YV61
Pallet Clamp Y15.1
(PACL.R) -KAR58 Output Module : Slot 4 XJ403 (20) -YV62
Table Unclamp(I) Y15.2
(TAUC.R) -KAR59 Output Module : Slot 4 XJ403 (35) -YV63
Table Clamp Y15.3
(TACL.R) -KAR60 Output Module : Slot 4 XJ403 (2) -YV64
Pallet Unclamp(R) X7.0
(PTUC.M) -SP61 Input Module : Slot 8 XJ412 (12) -SP61
Pallet Clamp X7.1
(PTCL.M) -SP62 Input Module : Slot 8 XJ412 (28) -SP62
Table Clamp X7.2
(BCLP.M) -SL63 Input Module : Slot 8 XJ412 (44) -SL63
Table Unclamp(R) X7.3
(BULP.M) -SP65 Input Module : Slot 8 XJ412 (11) -SP65
278
HM 8000(F30i Series) HM8000ALE2A
4-Th Clamp/ Unclamp Alarm
279
HM 8000(F30i Series) HM8000ALE2A ㅇ
B-Axis(Table) Clamp/ Unclamp Check Time
280
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R626.4 TMB29 B-Axis(Table) Cl/Uncl Check Time
F0.6 SA Servo Ready
K8.5 KROTAR Rotary Table Used
X7.2 BCLP.M Table Clamp
K0.0 KHM63 Ace-HM63 Machine
X7.1 PTCL.M Pallet Clamp
K0.1 KHM80 Ace-HM80 Machine
R457.0 TMB228 B-Axis(Table) Cl/Uncl Check Time
R841.5 BACLPF B-Axis(Table) Clamp Flag
R1420.7 PMGSEL PMG Operation Selected
K0.2 KHM50 Ace-HM50 Machine
A40.2 2323 4-th Clamp/Unclamp Alarm
R652.7 ARST Alarm Reset
K7.5 K4THA 4th-Axis Not Used
R4030.2 4PMGMST PMG Macro Start
Y7.0 PUCL.R Pallet Unclamp
K0.6 KHM1000 If HM1000, Set To 1
Y15.0 PAUC.R Pallet Unclamp
X7.1 PTCL.M Pallet Clamp
R4005.5 K80PMG Keep Relay HM80 for PMG
R841.5 BACLPF B-Axis(Table) Clamp Flag
X7.2 BCLP.M Table Clamp
R1114.7 4PMUC.R PMG Pallet Unclamp
X7.0 PTUC.M Pallet Unclamp
Y7.2 TUCL.R Table Unclamp
Y15.2 TAUC.R Table Unclamp
Y7.3 TCLP.R Table Clamp
281
HM 8000(F30i Series) HM8000ALE2A ㅇ
Pallet Clamp (SP62)
Table Clamp (SL63)
282
HM 8000(F30i Series) HM8000ALE2A
4.40 2324 Table or Pallet Clamp Alarm 1) Description
The pallet or the table is not in the state of being clamped. 2) Cause of problem
① An error in adjusting the position switch that checks the position of the pallet or table Clamp/Unclamp operation
② An error in the position switch that checks the position of the pallet or table Clamp/Unclamp operation, or any of its component parts
3) Action
① Adjust the position switch that checks the position of the pallet or table Clamp/Unclamp operation as accurate as possible.
② Check the switch, the wiring cables, and the I/O module in this sequence. Make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Pallet Unclamp Y7.0
(PUCL.R) -KAR57 Output Module : Slot 2 XJ401 (3) -YV61
Pallet Clamp Y7.1
(PCLP.R) -KAR58 Output Module : Slot 2 XJM3 (20) -YV62
Table Unclamp Y7.2
(TUCL.R) -KAR59 Output Module : Slot 2 XJ401 (35) -YV63
Table Clamp Y7.3
(TCLP.R) -KAR60 Output Module : Slot 2 XJ401 (2) -YV64
Pallet Unclamp X7.0
(PTUC.M) -SX61 Input Module : Slot 8 XJ412 (12) -SX61
Pallet Clamp X7.1
(PTCL.M) -SX62 Input Module : Slot 8 XJ412 (28) -SX62
Table Unclamp X7.2
(BCLP.M) -SL63 Input Module : Slot 8 XJ412 (44) -SL63
Table Clamp X7.3
(BULP.M) -SL65 Input Module : Slot 8 XJ412 (11) -SL65
283
HM 8000(F30i Series) HM8000ALE2A ㅇ
Table or Pallet Clamp Alarm
Table(B-Axis) Clamp Alarm D-Time
284
HM 8000(F30i Series) HM8000ALE2A
Table/Pallet Unclamp Interlock
B-Axis or Pallet Unclamp Interlock
B-Axis(Table) Servo Off D-Time
285
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R628.3 TMB44 Table(B-Axis) Clamp Alarm D-Time
R759.0 APCMST APC Macro Start
R637.0 JX Jog X-Axis Select
R637.1 JY Jog Y-Axis Select
R637.2 JZ Jog Z-Axis Select
X34.6 NJF.M Jog Feed -Direction
X34.5 PJF.M Jog Feed +Direction
R634.6 JOG Jog Mode
X28.2 HX.M MPG Handle X Axis Select
X28.3 HY.M MPG Handle Y Axis Select
X28.4 HZ.M MPG Handle Z Axis Select
G70.4 SRVA Spindle Reverse
G70.5 SFRA Spindle Forward
R635.4 H Handle Mode
R752.4 TMBINT Table/Pallet Unclamp Interlock
R752.7 PALINT B-Axis or Pallet Unclamp Interlock
R752.6 TMBINT1 Table Unclamp Interlock
X7.1 PTCL.M Pallet Clamp
K0.6 KHM1000 If HM1000, Set To 1
X7.0 PTCL.M Pallet Unclamp
K8.5 KROTAR Rotary Table Used
Y7.0 PUCL.R Pallet Unclamp
Y15.0 PAUC.R Pallet Unclamp
R760.0 M61CD APC 1 Unload Command
R761.0 M62CD APC 1 Load Command
R770.0 M63CD APC 2 Unload Command
R771.0 M64CD APC 2 Load Command
R608.3 M70 Pallet or Station Index
R607.2 M61 APC 1 Unload
R607.3 M62 APC 1 Load
F0.5 STL Cycle Start
R757.5 APCCHG Pallet Change Command
286
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
X36.3 DRN.M Dry Run
Y13.6 P8FR.R APC Rotation 180 CW Stopper Out
Y13.7 P8RR.R APC Rotation 180 CCW Stopper Out
R1420.7 PMGSEL PMG Operation Selected
R767.6 PLTCL Pallet(Table) Clamp Command
R765.3 4PLTCL Pallet Clamp Command
R767.7 PLTUNC Pallet(Table) Unclamp Command
R4030.5 4PLD/UL Pallet Load/Unload
F0.5 STL Cycle Start
F0.4 SPL Feed Hold
R448.4 TMB165 B-Axis(Table) Servo Off D-Time
R624.4 TMB13 B-Axis(Table) Clamp Check Time
Y12.2 TAUC.R Table Unclamp
R752.4 TMBINT Table/Pallet Unclamp Interlock
R435.2 TMB59 Pallet Unclamp Check Time
F3.1 MH
Y7.2 TUCL.R Table Unclamp
X7.2 BCLP.M Table Clamp
R750.2 BACLP B-Axis(Table) Clamp Command
Pallet Clamp (SP62)
Table Clamp (SL63)
287
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.41 2325 APC Set-Up Switch Unpush 1) Description
When the M60 (Pallet Change), M61 (APC 1 Load), M62(APC 2 Load) command was instructed, the operator did not press the Set-Up switch on the APC manual OP.
2) Cause of problem
① The operator put a workpiece on the table deck but did not press the Set-Up switch. ② An error in the Set-Up push-button switch or any of its component parts
3) Action
① After you put a workpiece on the table deck, press the Set-Up push-button switch on the APC manual OP. ▪ The indicator of the Set-Up switch turns yellow.
② Check the Set-Up related switches, the wiring cables from the switches to the electric cabinet, and the input module in this sequence if there is a problem. Make repair or replacement if necessary.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
Set Up X29.1
(SETU.M) -SB92 Matrix Distribution
Board XJM3 (A06) SB92
APC Set-Up Switch Unpush
288
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R759.0 APCMST APC Macro Start
R757.5 APCCHG Pallet Change Command
R755.7 SETUP Set Up
R761.7 M62MEN APC 1 Load(M62) M Function End
R771.7 M64MEN APC 2 Load(M64) M Function End
R1420.1 RPMG Pallet Schedule Operator By CW
R1159.0 PMGMST PMG Macro Start
R607.2 M61 APC 1 Unload
R607.3 M62 APC 1 Load
R1010.0 No-Set Set-Up Not Found
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000, Set To 1
289
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
R762.2 2325A1 HM4D APC APC Setup SW Unpush Aux.
A40.4 2325 APC Set-Up Switch Unpush
R774.5 SETUA Setup Aux. for HM4Digt
K4.6 KFIX Hyd. Fixture Used
R755.0 SETUP1 Set Up 1
K10.7 KSETUP Set-Up Switch Unpush Used
K10.2 KAUTDR Auto Door for Setup Door Used
R430.1 TM26 APC Auto Door Close Check Time
R774.6 SEUPA Setup Aux.
290
HM 8000(F30i Series) HM8000ALE2A
4.42 2326 APC OP Manual Mode 1) Description
With the mode toggle switch on the APC manual OP being set to Manual, the mode switch on the main OP was set to one of Edit, Memory, Tape or MDI mode.
2) Cause of problem
① The mode toggle switch on the APC manual OP was set to Manual. ② An error in the mode toggle swish or any of its component parts
3) Action
① Set the mode toggle switch on the APC manual OP to AUTO. ② Check the mode toggle switch, and the wiring between the switch and the electric
cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC OP Manual Mode_HM4D
X29.2 (SETU.M) -SA91
Matrix Distribution Board
XJM3 (B06) SA91
Address Symbol Coil Comment
R1484.1 RP_MANMD APC Manual Mode from Executer
R1420.1 RPMG Pallet Schedule Operation By CW
R635.7 AUT Auto Mode
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000, Set To 1
X29.2 PMMD.M APC OP Manual Mode_HM4D
R763.0 APCMAN APC Manual Mode
A40.5 2326 APC OP Manual Mode
APC OP Manual Mode
291
HM 8000(F30i Series) HM8000ALE2A ㅇ
292
HM 8000(F30i Series) HM8000ALE2A
4.43 2333 APC Not Use (K7.7 Set) 1) Description
With "K7.7" (disable APC) being set, a pallet change command (M60;, M61;, M62;) was instructed.
2) Cause of problem
The Keep Relay settings were incorrect. 3) Action
If APC has no error, set "Keep Relay K7.7" from 1 0 and perform the pallet change operation.
Address Symbol Coil Comment
K7.7 KAPC APC Not Used
R607.1 M60 APC Pallet Change
R607.2 M61 APC 1 Unload
R607.3 M62 APC 1 Load
A41.4 2333 APC Not Use (K7.7 Set)
R352.7 ARST Alarm Rest
APC Not Use (K7.7 Set)
293
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.44 2335 APC Changer Open/Close Alarm 1) Description
It has passed 5 seconds since the APC Changer Arm Open/Close sensor signal did not match the corresponding instruction signal, or both sensor signals turned on simultaneously.
2) Cause of problem
① An error in adjusting the APC Changer Arm Open/Close position sensor switch ② An error in the APC Changer Arm Open/Close position sensor switch, or any of related
parts 3) Action
① Adjust the APC Changer Arm Open/Close position sensor switch as accurate. ② Check the sensor switch, and the wiring between the sensor switch and the electric
cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC Pos.90/Arm Open
X18.1 (APOP.M) -SX71
Input Module : Slot 8,10
XJ410 (32) SX71
APC Pos.90/Arm Close
X18.3 (APCL.M) -SL73
Input Module : Slot 8,10
XJ410 (15) SL73
APC Arm Close Y12.7
(APCL.R) -YV71 Output Module : Slot 4 XJ403 (46) KAR40
APC Arm Open Y13.0
(APOP.R) -YV72 Output Module : Slot 4 XJ403 (12) KAR41
APC Arm Open(SX71)
APC Arm Open Slow Down (SX72)
APC Arm Close Slow Down (SX74)
APC Arm Close (SL73)
294
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R456.2 TMB222 APC Changer Open/Close Check Time
A41.6 2335 APC Changer Open/Close Alarm
R652.7 ARST Alarm Reset
K7.7 KAPC APC Not Used
R1420.7 PMGSEL PMG Operation Selected
K0.2 KHM50 Ace-HM50 Machine
K0.6 KHM1000 If HM1000, Set To 1
Y12.7 APCL.R APC Arm Close
X18.3 APCL.M APC Pos.90/Arm Close
X19.1 APDN.M APC Down
Y13.0 APOP.R APC Arm Open
X18.1 APOP.M APC Pos.0/Arm Open
R763.4 MAPCSP Man APC Stop
R631.3 CYSTP Cycle Stop
APC Changer Open/Close Alarm
APC Changer Open/ Close Check Time
295
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.45 2336 APC Changer Up/Down Alarm 1) Description
It has passed 5 seconds since the APC Changer Up/Down sensor signal did not match the corresponding instruction signal, or both sensor signals turned on simultaneously.
2) Cause of problem
① An error in adjusting the APC Changer Up/Down position sensor switch ② An error in the APC Changer Up/Down position sensor switch, or any of related parts
3) Action
① Adjust the APC Changer Arm Up/Down position sensor switch as accurate. ② Check the sensor switch, and the wiring between the sensor switch and the electric
cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC UP X19.0
(APUP.M) -SX81 Input Module : Slot 10 XJ410 (12) SX81
APC Down X19.1
(APDN.M) -SX82 Input Module : Slot 10 XJ410 (28) SX82
APC Up Y13.3
(APUP.R) -YV75 Output Module : Slot 4 XJ403 (11) KAR44
APC Down Y13.4
(APDN.R) -YV76 Output Module : Slot 4 XJ403 (27) KAR45
APC Up (SX83)
APC Down (SX84)
APC Up (SX83)
APC Down (SX84)
0.8~1.2mm
Proximity Switch Dog
296
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R456.3 TMB223 APC Changer Up/Down Check Time
A41.7 2336 APC Changer Up/Down Alarm
R652.7 ARST Alarm Reset
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000, Set To 1
Y13.3 APUP.R APC Up
X19.0 APUP.M APC Up
Y13.4 APDN.R APC Down
X19.1 APDN.M APC Down
R763.4 MAPCSP Man APC Stop
R1420.7 PMGSEL PMG Operation Selected
R1056.2 MCHASP Man Pallet Changer Stop
K0.2 KHM50 Ace-HM50 Machine
R631.3 CYSTP Cycle Stop
APC Changer Up/Down Alarm
APC Changer Up/ Down Check Time
297
HM 8000(F30i Series) HM8000ALE2A ㅇ
4.46 2337 APC Changer 180CW/CCW Alarm 1) Description
It has passed 5 seconds since the APC Changer Up/Down sensor signal did not match the corresponding instruction signal, or both sensor signals turned on simultaneously.
2) Cause of problem
① An error in adjusting the APC Changer Up/Down position sensor switch ② An error in the APC Changer Up/Down position sensor switch, or any of related parts
3) Action
① Adjust the APC Changer Arm Up/Down position sensor switch as accurate. ② Check the sensor switch, and the wiring between the sensor switch and the electric
cabinet as well as the input module, and make repair or replacement if you encounter a problem.
Signal Address Device Symbol I/O Connector
(Pin) Numbering
APC Rotation 180 CW
Y13.1 (PCW.R) -YV73 Output Module : Slot 4 XJ403 (28) KAR42
APC Rotation 180 CCW
Y13.2 (PCCW.R) -YV74 Output Module : Slot 4 XJ403 (44) KAR43
APC Up Y13.3
(APUP.R) -YV75 Output Module : Slot 4 XJ403 (11) KAR44
APC 180 CW Position
X18.5 (F18F.M) -SX75
Input Module : Slot 8,10
XJ410 (47) SX75
APC 180 CCW Position
X18.6 (F18R.M) -SX76
Input Module : Slot 8,10
XJ410 (30) SX76
APC UP X19.0
(APUP.M) -SX81 Input Module : Slot 10 XJ410 (12) SX81
298
HM 8000(F30i Series) HM8000ALE2A
Address Symbol Coil Comment
R456.4 TMB224 APC Changer 180CW/CCW Check Time
A42.0 2337 APC Changer 180CW/CCW Alarm
R652.7 ARST Alarm Reset
K7.7 KAPC APC Not Used
K0.6 KHM1000 If HM1000, Set To 1
Y13.1 PCW.R APC Rotation 180 CW
X18.5 P18F.M APC 180 CW Position
Y13.2 PCCW.R APC Rotation 180 CCW
X18.6 P18R.M APC 180 CCW Position
X19.0 APUP.M APC Up
Y13.3 APUP.R APC Up
R763.4 MAPCSP Man APC Stop
R1420.7 PMGSEL PMG Operation Selected
R1056.2 MCHASP Man Pallet Changer Stop
APC Changer 180CW/CCW Alarm
APC Changer180CW/ CCW Check Time
299
HM 8000(F30i Series) HM8000ALE2A ㅇ
Address Symbol Coil Comment
K0.2 KHM50 Ace-HM50 Machine
R631.3 CYSTP Cycle Stop
A9.5 2078 APC Set-Up Station Door Open
K10.2 KAUTDR Auto Door for Setup Door Used
R430.1 TM26 APC Auto Door Close Check Time
F0.6 SA Servo Ready
APC CCW (SX82)
APC CW (SX81)
APC 180 CCW Position (SX82)
APC 180 CW Position (SX81)
0.8~1.2mm
Proximity Dog
300
HM 8000(F30i Series) HM8000ALE2A
HMC Maintenance Manual HM 8000 Revision History
Version Year/Month Revision history Created by
01 2012. 10 Created a draft (HM8000ALE2A) Jung, Sam
Young
02
03
04
05
06
07
08
09
10