KVC- Capture JetHood with Supply Air and Side-Jet Technology
KVCCapture JetHood with Supply Air and Side-Jet Technology
The KVC Capture Jethood with Side-Jet technology
is a highly efficient kitchen ventilation hood that
removes contaminated air and excess heat emitted by
cooking equipment, helping to provide a comfortable
and clean environment.
The KVC hood uses the advanced Halton Capture Jet
with Side-Jet technology to improve the capture and
containment of the airflows generated by the cooking
equipment. Overall exhaust airflow rates can be
reduced up to 30% from those of traditional kitchen
hoods.
The Capture Jetwith Side-Jet technology is based
on the high entrainment efficiency of a compact, high-
velocity capture air jet. The capture air jets efficiently
induce ambient air at the critical front face area of the
hood, minimizing the spillage of the contaminated air
and maintaining good air quality in the chefs work
area.
Improved indoor air quality with reduced energy
use. Halton Capture Jetwith Side-Jet technology
reduces the exhaust airflow rates required and
improves the capture and containment efficiency
of the hood.
High efficiency grease filtration using UL andNSF classified Halton KSA multi-cyclone filters for
removal of up to 95% of particles with a size of 8
microns or above.
T.A.B. (testing and balancing) ports, which allow
accurate and effective commissioning.
AccuFlow provides a visual indicator that the
system is at design exhaust air values at the face
of the hood. A pressure transducer measures
design exhaust rate and provides a green indicator
light.
Standard LED light fixtures.
Stainless steel, welded design.
Note: Factory must be advised on any special requirements of the
Authority Having Jurisdiction at time of quote.
tem o: -
7/25/2019 HK-13 HOOD.pdf
2/13
2
KVC inches
Length 48.....168
Width 49......84
Height 24......30
5
8
1
DIMENSIONS
10
6
9
4
KVC/PC/xxxx11507/EN
KVC- Capture JetHood with Supply Air and Side-Jet Technology
Part Description
1 18 Ga. Stainless steel AISI 304
2 Exhaust duct collar
3 Capture Jet air
4 Light fixture
5 KSA grease filters
6 Integrated Capture Jet fan intake (not visible in picture)
7 Grease collection cup
8 Assembly brackets
Length Recommended Exhaust air volumes Recommended Capture Jet air volumes
48.....168 * Actual exhaust air volumes are calculated by using
the heat load based design method utilizing the Halton
H.E.L.P. (Hood Engineerin g Layout Program)
Capture Jet average pressure 0.40 WC
(without Side Jet option), 0.20 WC (with
Side Jet option).
*Average operating range from light to to heavy duty
cooking loads 135 cfm to 275 cfm per linear foot
*Airflows established by a pressure reading
*WC= Water Column
equipment. The Side Jets for enhanced performance
(7).
Construction
The KVC hood comprizes of Capture Jetwith Side-
Jet technology, airflow measurement T.A.B. ports
and KSA multi-cyclone grease filters. The hood
shall bear ETL or UL label. The ETL/UL listed rangehood without exhaust fire damper per standard 710
and be fabricated in compliance with NFPA-96, and
shall bear the NSF seal of approval.
The exposed parts are manufactured from 18 ga.
stainless steel.
The hood ends have double side wall
construction. A concealed collection cup is fitted
into the grease drain channel for easy removal of
the grease and dirt extracted by the KSA multi-cyclone filters.
QUICK DATA
2
*Hoods are ETL or UL listed for USA per UL710, and CANADA per ULC-S646 standards, and NSF certified.
3
7/25/2019 HK-13 HOOD.pdf
3/13
3
Heat spillingCapture &
containment7
KVC/xxxx/011507/EN
KVC - Capture JetHood with Supply Air and Side-Jet Technology
9 Double wall construction
10 Integrated Supply air plenum
Make up air is distributed into the space at low velocity
through the front plenum of the hood (5). The vertical
capture air improves efficiency, and allows the hood
to operate at lower exhaust airflows. Capture Jet air
(6) is used to increase air velocity in the working zone
near the cooking equipment in order to compensate
for the effects of radiant heat emitted by the cooking
Function
The kitchen hood above cooking appliances containsthe rising warm air and contaminants (1). The capture
air jets (2) direct the contaminated air toward the KSA
grease filters (3), where grease particles and other
impurities are separated from the exhaust air using the
cyclone separation principle. The extracted grease and
other air contaminants flow into a drain channel and
toward the collection tray (4).
Accessories
Closure Panels - for canopies below ceiling level
Backsplash
Side Skirts (optional)
KFR - Filter Removal Tool
Recessed fluorescent
Recessed incandescent
Incandescent globe type lights
MEP - Master Electrical Panels
Face or remote mounted switch panels
Factory prepiped Fire Protection
Powder coated
Listed exhaust duct balancing damper
Custom/Design stainless steel exterior textures
Hood mounted fire cabinet
M.A.R.V.E.L. Demand Control w/ VFD by Halton
125
3
46
9
10
Side-Jets (7)
Front capture air jets (2)
7/25/2019 HK-13 HOOD.pdf
4/13
4
2
Mounting bracket 2 high (52mm)
DIMENSIONS
Estimated Crated
Shipping Weight
inches Weight
Width 48 80 lbs / ft.
Width 54 85 lbs / ft.
Width 60 90 lbs / ft.
18 ga.
WEIGHTS (LB)
**Larger Weights-consult factory
KVC/PC/xxxx11507/EN
KVC- Capture JetHood with Supply Air and Side-Jet Technology
W
H
W
L
KVC- Wall model inches
Length 40......144
Width 28......34
Height 42......48
Noted in drawings as:
* L = Length
* W = Width
* H = Height
7/25/2019 HK-13 HOOD.pdf
5/13
5
2
Mounting bracket 2 high (52mm)
DIMENSIONS
WEIGHTS (LB)
18 ga.
Estimated Crated
Shipping Weight
inches Weight
Width 48 85 lbs / lin. ft.
Width 54 90 lbs / lin. ft.
Width 60 95 lbs / lin. ft.
Width 66 100 lbs / lin. ft.
Width 72 105 lbs / lin. ft.
KVC/xxxx/011507/EN
KVC - Capture JetHood with Supply Air and Side-Jet Technology
**Larger Weights-consult factory
KVC - Is land model inches
Length 48.....168
Width 48......84
Height 24......30
Overall Width 98....168
Noted in drawing as:
* L = Length
* W = Width
* H = Height
* O = Overall Width
O
W W
H
L
O
W W
7/25/2019 HK-13 HOOD.pdf
6/13
6
KVC/PC/xxxx11507/EN
KVC- Capture JetHood with Supply Air and Side-Jet Technology
Balancing of Capture JetHoods
The capture jet and exhaust air flows are easily and
accurately determined by measuring the pressure
difference from the T.A.B. ports mounted in each
plenum. Corresponding air flows can be read from
the diagrams provided.
KVE/KVC - 2 Filters
Exhaust air flow vs. pressure differential
All T.A.B. readings assume cold conditions. Toadjust for an exhaust temperature o f 110 F,
multiply the readings by a factor of 0.93.
0.15
0.25
0.35
0.45
0.55
0.65
0.75
0.85
0.95
500 600 700 800 900 1000 1100 1200
Copyright Halton
0.20
0.30
0.40
0.50
0.60
0.70
0.80
700 800 900 1000 1100 1200 1300 1400 1500
Copyright Halton
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
800 900 1000 1100 1200 1300 1400 1500 1600 1700
Copyright Halton
0.10
0.20
0.30
0.40
0.50
0.60
900 1000 1100 1200 1300 1400 1500 1600 1700 1800
Copyright Halton
KVE/KVC - 3.5 Filters
KVE/KVC - 2.5 Filters
KVE/KVC - 3.5 Filters
7/25/2019 HK-13 HOOD.pdf
7/13
7
KVC/xxxx/011507/EN
KVC - Capture JetHood with Supply Air and Side-Jet Technology
0.10
0.20
0.30
0.40
0.50
0.60
0.70
1100 1300 1500 1700 1900 2100
Copyright Halton
0.10
0.20
0.30
0.40
0.50
0.60
0.70
1300 1500 1700 1900 2100 2300 2500
KVE/KVC - 5 Filters
KVE/KVC - 4 Filters
0.10
0.20
0.30
0.40
0.50
0.60
0.70
1600 1800 2000 2200 2400 2600 2800 3000 3200
KVE/KVC - 6 Filters
0.10
0.20
0.30
0.40
0.50
0.60
0.70
1200 1400 1600 1800 2000 2200 2400
Copyright Halton
0.10
0.20
0.30
0.40
0.50
0.60
1400 1600 1800 2000 2200 2400 2600 2800
KVE/KVC - 5.5 Filters
KVE/KVC - 4.5 Filters
0.10
0.20
0.30
0.40
0.50
0.60
1500 1800 2100 2400 2700 3000 3300
KVE/KVC - 6.5 Filters
7/25/2019 HK-13 HOOD.pdf
8/13
8
KVC/PC/xxxx11507/EN
KVC- Capture JetHood with Supply Air and Side-Jet Technology
0.10
0.20
0.30
0.40
0.50
0.60
0.70
1800 2100 2400 2700 3000 3300 3600
0.10
0.20
0.30
0.40
0.50
0.60
0.70
2100 2400 2700 3000 3300 3600 3900 4200
KVE/KVC - 8 Filters
KVE/KVC - 7 Filters
0.10
0.20
0.30
0.40
0.50
0.60
0.70
1800 2100 2400 2700 3000 3300 3600 3900
KVE/KVC - 7.5 Fil ters
7/25/2019 HK-13 HOOD.pdf
9/13
9
Suggested specifications
GeneralKitchen hood inner liner shall be constructed from
18 gauge stainless steel where exposed. The kitchen
hoods shall be supplied complete with outer casing
/ main body, inner liner, exhaust duct, pressure
measurement T.A.B. ports, Outer casing panels shall
be constructed of stainless steel with a brushed satin
finish. Each joint shall be welded and liquid tight,avoiding harmful dripping of condensation.
All exposed welds are ground and polished to
the original finish of metal. Canopy ends shall be
double sided wall construction (no single wall hoods
permitted).
ExhaustThe exhaust airflow will be based on the convective
heat generated by the appliances underneath each
hood system. Submittals shall include convective
heat calculations based on the input power of the
appliance served.
Capture Jetwith Side-Jet TechnologyThe hood shall be designed with Capture Jet
Side-Jet technology to reduce the exhaust airflow
rate required, and to improve the capture and
containment efficiency of the hood, while reducing
energy consumption. The Capture Jetair shall be
introduced through a special discharge panel and
shall not exceed 10% of the calculated exhaust
airflow. The Capture Jetdischarge velocity will be
a minimum of 1500 feet per minute. Slot or grille
type discharge shall not be used. The Capture Jet
hood with Side-Jet technology shall be internally
mounted with a speed control and will not require
a fire damper or electronic shut down in fire mode.
Supply Air PlenumThe integral front discharge make up air plenum shall
be manufactured of the same material as the hood.
The face of the plenum will be perforated stainless
steel to deliver low velocity air to the space and
to minimize room turbulence while refreshing the
occupied zone.
T.A.B. PortsThe airflows through the extractors and the Capture
Jetair chamber are to be determined through the
integral T.A.B. (Testing and Balancing) ports mounted
in the hood. The airflows are to be determined by the
pressure vs. airflow curves supplied by Halton.
AccuFlowThe Capture Jet hood will come standard with the
Halton AccuFlow indicator. The AccuFlow provides a
visual indicator that the system is at design exhaust
air values. A pressure transducer measures design
exhaust rate and this is interpreted by the AccuFlow
sensor by a steady green indicator light. Should the
system be below design airflow, the indicator light
will blink once in sequence. Should the indicator light
blink twice in sequence, the exhaust airflow is above
design.
Grease FiltersThe hood shall be equipped with KSA multi-cyclone
stainless steel grease extractors. The KSA filters
shall be NSF and UL classified. The grease extraction
efficiency is 93% on particles with a diameter of 5
microns and 98% on particles with a diameter of 15
microns or larger as tested by an independent testing
laboratory. The pressure loss over the extractor shall
not exceed 0.50 of water at flow rates approved
by U.L. for heavy load cooking. Sound levels shallnot exceed an NC rating of 55. Baffle or slot type
extractors shall not be used.
Light FixturesHood lights shall be U.L. Listed LED fixtures,
suitable for grease hoods. 20 Watts per fixture, 50
foot candles at cooking surface. Option: Recessed
fluorescent, recessed incandescent or incandescent
globe type lighting. The lighting shall be suitable for
single phase power supply.
Control PanelThe master electrical panel consisting of one starter
per motor with overload protection will be supplied.Control panel to hood or remote mounted.
Fire Suppression SystemThe kitchen hood fire extinguishing system shall
protect the kitchen hood against grease fires by a
completely automatic fire control system, which
consists of wet chemical. The fire detection system
shall be capable of detecting fire in the hood,
duct, or surface equipment and shall automatically
discharge liquid extinguishing agent into the plenum
chamber, exhaust duct collar, and cooking appliance
areas to ensure against reignition or re-flash.
System components shall include a spring-loaded
fusible link detector, wall mounted emergency pull
stations, wall mounted automan and cabinet, and a
mechanical gas valve installed in the gas line serving
the cooking equipment. System installation shall be
made by an authorized representative of the system
manufacturer and conform to U.L. 300 requirements
and local codes.
KVC/xxxx/011507/EN
KVC - Capture JetHood with Supply Air and Side-Jet Technology
7/25/2019 HK-13 HOOD.pdf
10/13
Low pH Agent
Proven Design
Reliable Gas Cartridge Operation
Aesthetically Appealing
UL Listed Meets Requirements of UL 300
ULC Listed Meets Requirements of ULC/ORD-C1254.6
CE Marked
The ANSULR-102 Restaurant Fire Suppression System is an auto-
matic, pre-engineered, fire suppression system designed to protectareas associated with ventilating equipment including hoods, ducts,plenums, and filters. The system also protects auxiliary grease extractionequipment and cooking equipment such as fryers; griddles and rangetops; upright, natural charcoal, or chain-type broilers; electric, lava rock,mesquite, or gas-radiant char-broilers; and woks.
The system is ideally suitable for use in restaurants, hospitals, nursinghomes, hotels, schools, airports, and other similar facilities.
Use of the R-102 system is limited to indoor applications or locationsthat provide weatherproof protection within tested temperature limita-tions. The regulated release and tank assemblies must be mounted in anarea where the air temperature will not fall below 32 F (0 C) or exceed130 F (54 C).The system must be designed and installed within theguidelines of the UL/ULC Listed Design, Installation, Recharge, andMaintenance Manual.
The restaurant fire suppression system is a pre-engineered, wet chemi-cal, cartridge-operated, regulated pressure type with a fixed nozzleagent distribution network. It is listed with Underwriters Laboratories, Inc.(UL/ULC).
004215
The system is capable of automatic detection and actuation as well asremote manual actuation. Additional equipment is available for buildingfire alarm panel connections, electrical shutdown and/or interface, andmechanical or electrical gas line shut-off applications.
The detection portion of the fire suppression system allows for auto-matic detection by means of specific temperature-rated alloy typefusible links, which separate when the temperature exceeds the ratingof the link, allowing the regulated release to actuate.
A system owners guide is available containing basic informationpertaining to system operation and maintenance. A detailed technicamanual, including system description, design, installation, recharge aresetting instructions, and maintenance procedures, is available to qufied individuals.
The system is installed and serviced by authorized distributors that atrained by the manufacturer.
The basic system consists of an ANSUL AUTOMANregulated relea
assembly which includes a regulated release mechanism and a wetchemical storage tank housed within a single enclosure. Nozzles withblow-off caps, detectors, cartridges, agent, fusible links, and pulleyelbows are supplied in separate packages in the quantities needed fofire suppression system arrangements.
Additional equipment includes a remote manual pull station(s), mechical and electrical gas valves, and electrical switches for automaticequipment and gas line shut-off. Accessories can be added such asalarms, warning lights, etc., to installations where required.
Additional tanks and corresponding equipment can be used in multiparrangements to allow for larger hazard coverage. Each tank is limiteto a listed maximum amount of flow numbers.
SYSTEM DESCRIPTION
APPLICATION
FEATURES
R-102 RESTAURANT
FIRE SUPPRESSION SYSTEMS
Data/Specifications
004
7/25/2019 HK-13 HOOD.pdf
11/13
Wet Chemical Agent The extinguishing agent is a mixture of organicsalts designed for rapid flame knockdown and foam securement ofgrease related fires. It is available in plastic containers with instructionsfor wet chemical handling and usage.
Agent Tank The agent tank is installed in a stainless steel enclosure
or wall bracket.The tank is constructed of stainless steel.Tanks are available in two sizes: 1.5 gallon (5.7 L) and 3.0 gallon(11.4 L). The tanks have a working pressure of 110 psi (7.6 bar), a testpressure of 330 psi (22.8 bar), and a minimum burst pressure of 660 psi(45.5 bar).
The tank includes an adaptor/tube assembly. The adaptor assemblyincludes a chrome-plated steel adaptor with a 1/4 in. NPT female gasinlet, a 3/8 in. NPT female agent outlet, and a stainless steel agent pick-up tube. The adaptor also contains a bursting disc seal which helps toprevent the siphoning of agent up the pipe during extreme temperaturevariations.
Regulated Release Mechanism The regulated release mechanism isa spring-loaded, mechanical/pneumatic type capable of providing theexpellant gas supply to one, two, or three agent tanks depending on thecapacity of the gas cartridge used. It contains a factory installed regula-
tor deadset at 110 psi (7.6 bar) with an external relief of approximately180 psi (12.4 bar). It has automatic actuation capabilities by a fusible linkdetection system and remote manual actuation by a mechanical pullstation.
The regulated release mechanism contains a release assembly, regula-tor, expellant gas hose, and agent storage tank housed in a stainlesssteel enclosure with cover.The enclosure contains knock-outs for 1/2 in.conduit. The cover contains an opening for a visual status indicator.
It is compatible with mechanical gas shut-off devices; or, when equippedwith a field or factory-installed switch and manual reset relay, it iscompatible with electric gas line or appliance shut-off devices.
Regulated Actuator Assembly When more than two agent tanks (orthree 3.0 gallon (11.4 L) tanks in certain applications) are required, theregulated actuator is available to provide expellant gas for additional
tanks. It is connected to the cartridge receiver outlet of the regulatedrelease mechanism providing simultaneous agent discharge. It containsa regulated actuator deadset at 110 psi (7.6 bar) with an external reliefof approximately 180 psi (12.4 bar). It has automatic actuation capabili-ties using pressure from the regulated release mechanism cartridge.
The regulated actuator assembly contains an actuator, regulator, expel-lant gas hose, and agent tank housed in a stainless steel enclosure withcover.The enclosure contains knockouts to permit installation of theexpellant gas line.
Discharge Nozzles Each discharge nozzle is tested and listed withthe R-102 system for a specific application. Nozzle tips are stamped withthe flow number designation (1/2, 1, 2, or 3). Each nozzle must have ametal or rubber blow-off cap to keep the nozzle tip orifice free of cookinggrease build-up.
Agent Distribution Hose Kitchen appliances manufactured with orresting on casters (wheels/rollers) may include an agent distributionhose as a component of the suppression system. This allows the appli-ance to be moved for cleaning purposes without disconnecting the appli-ance fire suppression protection. The hose assembly includes arestraining cable kit to limit the appliance movement within the range(length) of the flexible hose.
Flexible Conduit Flexible conduit allows for quicker installations andthe convenience of being able to route the cable over, under and around
obstacles. Flexible conduit can be used as a substitute for standardEMT conduit or can be used with EMT conduit.
Flexible conduit can be used only with the Molded Remote Manual PullStation.
Pull Station Assembly The remote manual pull station is made out ofa molded red composite material. The red color makes the pull stationmore readily identifiable as the manual means for fire suppressionsystem operation.
The pull station is compatible with the ANSUL Flexible Conduit.
UL/ULC Listed CE Marked
New York City Department of Buildings
LPCB
TFRI
Marine Equipment Directive (MED)
DNV
ABS
Lloyds Register
Meets requirements of NFPA 96 (Standard for the Installation ofEquipment for the Removal of Smoke and Grease-Laden Vapors fromCommercial Cooking Equipment)
Meets requirements of NFPA 17A (Standard on Wet Chemical
Extinguishing Systems)
Order all system components through your local authorized ANSULDistributor.
ORDERING INFORMATION
APPROVALS
COMPONENTDESCRIPTION
004213
7/25/2019 HK-13 HOOD.pdf
12/13
An ANSUL R-102 Fire Suppression System shall be furnished. Thesystem shall be capable of protecting all hazard areas associated withcooking equipment.
1.0 GENERAL
1.1 References
1.1.1 Underwriters Laboratories, Inc. (UL)1.1.1.1 UL Standard 12541.1.1.2 UL Standard 300
1.1.2 Underwriters Laboratories of Canada (ULC)1.1.2.1 ULC/ORD-C 1254.6
1.1.3 National Fire Protection Association (NFPA)1.1.3.1 NFPA 961.1.3.2 NFPA 17A
1.2 Submittals
1.2.1 Submit two sets of manufacturers data sheets
1.2.2 Submit two sets of piping design drawings
1.3 System Description
1.3.1 The system shall be an automatic fire suppressionsystem using a wet chemical agent for cooking greaserelated fires.
1.3.2 The system shall be capable of suppressing fires inthe areas associated with ventilating equipment includ-ing hoods, ducts, plenums, and filters as well as auxil-iary grease extraction equipment. The system shallalso be capable of suppressing fires in areas associ-ated with cooking equipment, such as fryers; griddlesand range tops; upright, natural charcoal, or chain-typebroilers; electric, lava rock, mesquite or gas-radiantchar-broilers; and woks.
1.3.3 The system shall be the pre-engineered type havingminimum and maximum guidelines established by themanufacturer and listed by Underwriters Laboratories(UL/ULC).
1.3.4 The system shall be installed and serviced by person-nel trained by the manufacturer.
1.3.5 The system shall be capable of protecting cookingappliances by utilizing either dedicated applianceprotection and/or overlapping appliance protection.
1.4 Quality Control1.4.1 Manufacturer: The R-102 Restaurant Fire Suppression
System shall be manufactured by a company with atleast forty years experience in the design and manu-facture of pre-engineered fire suppression systems.The manufacturer shall be ISO 9001 registered.
1.4.2 Certificates: The wet agent shall be a specially formu-lated, aqueous solution of organic salts with a pHrange between 7.7 8.7, designed for flame knock-down and foam securement of grease-related fires.
1.5 Warranty, Disclaimer, and Limitations
1.5.1 The pre-engineered restaurant fire suppression systemcomponents shall be warranted for five years from dateof delivery against defects in workmanship and mate-rial.
1.6 Delivery1.6.1 Packaging: All system components shall be securely
packaged to provide protection during shipment.
1.7 Environmental Conditions
1.7.1 The R-102 system shall be capable of operating withina temperature range of 32 F to 130 F (0 C to 54C).
2.0 PRODUCT
2.1 Manufacturer
2.1.1 Tyco Fire Suppression & Building Products, OneStanton Street, Marinette, Wisconsin 54143-2542,Telephone (715) 735-7411.
2.2 Components
2.2.1 The basic system shall consist of an ANSULAUTOMAN regulated release assembly which includa regulated release mechanism and a wet chemicastorage tank housed within a single enclosure.Nozzles, blow-off caps, detectors, cartridges, agentfusible links, and pulley elbows shall be supplied inseparate packages in the quantities needed for firesuppression system arrangements. Additional equipment shall include remote manual pull station,mechanical and electrical gas valves, and electricalswitches for automatic equipment and gas line shutand building fire alarm control panel interface.
2.2.2 Wet Chemical Agent: The extinguishing agent shall a specially formulated, aqueous solution of organicsalts with a pH range between 7.7 8.7, designed fflame knockdown and foam securement of greaserelated fires.
2.2.3 Agent Tank:The agent tank shall be installed in astainless steel enclosure or wall bracket.The tank sbe constructed of stainless steel. Tanks shall be ava
able in two sizes; 1.5 gallon (5.7 L) and 3.0 gallon(11.4 L).The tank shall have a working pressure of110 psi (7.6 bar), a test pressure of 330 psi (22.8 band a minimum burst pressure of 660 psi (45.5 bar)The tank shall include an adaptor/tube assemblycontaining a burst disc union.
2.2.4 Regulated Release Mechanism: The regulated releamechanism shall be a spring-loaded,mechanical/pneumatic type capable of providing theexpellant gas supply to one or two agent tanksdepending on the capacity of the gas cartridge usedthree 3.0 gallon (11.4 L) agent storage tanks in certapplications. It shall contain a factory installed regultor deadset at 110 psi (7.6 bar) with an external relieof approximately 180 psi (12.4 bar).
It shall have the following actuation capabilities: auto
matic actuation by a fusible link detection system anremote manual actuation by a mechanical pull statio
The regulated release mechanism shall contain arelease assembly, regulator, expellant gas hose, anagent storage tank housed in a stainless steel enclosure with cover. The enclosure shall contain knock-ofor 1/2 in. conduit.The cover shall contain an openinfor a visual status indicator.
It shall be compatible with mechanical gas shut-offdevices; or, when equipped with a field or factory-installed switch(es), it shall be compatible with electgas line or appliance shut-off devices, or connectionto a building fire alarm control panel.
2.2.5 Regulated Actuator Assembly: When more than twoagent tanks or three agent tanks in certain applicatiare required, the regulated actuator shall be availab
to provide expellant gas for additional tanks. It shall connected to the cartridge receiver outlet of the reglated release mechanism providing simultaneous agdischarge. The regulator shall be deadset at 110 ps(7.6 bar) with an external relief of approximately180 psi (12.4 bar).The regulated actuator assemblyshall contain an actuator, regulator, expellant gas hoand agent tank housed in a stainless steel enclosurwith cover. The enclosure shall contain knockouts topermit installation of the expellant gas line.
2.2.6 Discharge Nozzles: Each discharge nozzle shall betested and listed with the R-102 system for a specifapplication. Nozzles tips shall be stamped with the fnumber designation (1/2, 1, 2, or 3). Each nozzle shhave a metal or rubber blow-off cap to keep the noztip orifice free of cooking grease build-up.
SPECIFICATIONS
7/25/2019 HK-13 HOOD.pdf
13/13
2.0 PRODUCT (Continued)
2.2 Components (Continued)
2.2.7 Distribution Piping: Distribution piping shall beSchedule 40 black iron, chrome-plated, or stainlesssteel conforming to ASTM A120, A53, or A106.
2.2.8 Detectors: The detectors shall be the fusible link styledesigned to separate at a specific temperature.
2.2.9 Cartridges: The cartridge shall be a sealed steel pres-sure vessel containing either carbon dioxide or nitro-gen gas.The cartridge seal shall be designed to be
punctured by the releasing device supplying therequired pressure to expel wet chemical agent fromthe storage tank.
2.2.10 Agent Distribution Hose: An optional agent distributionhose shall be available for kitchen appliances manu-factured with or resting on casters (wheels/rollers).This shall allow the appliance to be moved for clean-ing purposes without disconnecting the appliance firesuppression protection. Hose assembly shall include arestraining cable kit to limit the appliance movementwithin the range (length) of the flexible hose.
2.2.11 Flexible Conduit:The manufacturer supplying theRestaurant Fire Suppression System shall offer flexi-ble conduit as an option to rigid EMT conduit for theinstallation of pull stations and/or mechanical gasvalves. The flexible conduit shall be UL Listed and
include all approved components for proper installa-tion.
2.2.12 Pull Station Assembly: The Fire Suppression Systemshall include a remote pull station for manual systemactuation.The pull station shall be designed to includea built-in guard to protect the pull handle. The pullstation shall also be designed with a pull handle toallow for three finger operation and shall be red incolor for quick visibility.
3.0 IMPLEMENTATION
3.1 Installation
3.1.1 The R-102 fire suppression system shall be designed,installed, inspected, maintained, and recharged inaccordance with the manufacturers listed instructionmanual.
3.2 Training
3.2.1 Training shall be conducted by representatives of themanufacturer.
SPECIFICATIONS