1All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EHV-CPU128 / Control Editor
Hitachi Programmable ControllerHitachi Programmable Controller
EHV series
Hitachi Industrial Equipment Systems Co., Ltd.Drive System Division
May 2006
2All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EHV-CPU Features
Instruction for use
Control Editor
Convert tool
3All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
372.5mm(W)×100mm(H)×109mm(D) for 512 pts. of I/O
Light color and round shape enables downsizing of machine, saving space in cabinet and sophisticated image.
3210 7654 111098 15141312
+163210 7654 11
10
98 15
14
13
12
1632
3210 7654 111098 15141312POWER
EH-150 modules
EHV-CPU128
Compact and Stylish1.1 Structure
4All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Replacing a battery from front facewithout dismounting CPU module
Easy installation and maintenance
Easy mounting to DIN rail
Easy mountingto base unit
1.1 Structure
5All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
7-seg LED
RUN/ERR LED
USB port
Serial port
Ethernetport
Battery
RUN swtichRetentive Clear
No DIP Switch
Packaged with- USB connector cover- RJ45 connector cover x2- Instruction manual
1.1 Structure
Note
6All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
7-seg LEDNote
Reset processing Normal Error
By user
FLASH memory being written
Error
Error
Flow of 7-Seg LED Indication
Error level can be set by Control Editor!
1.1 Structure
7All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Length of Exp. cable
8m in
tota
l
slot 0 to7 of basic base
Max. number of communication module
66Max. number of slot
4,224(using 64 pts. units)
Max. number of I/O
CautionUnit No. must be ascending sequence from the
closest unit to basic base, otherwise there is a risk of malfunction.
Communication module should be mounted 0 to 7 of basic base, otherwise it does not work.
Unit1
Unit2
Unit3
Unit4
Unit5
2m b
etw
een
units
EH-ETH, EH-RMD, EH-RMP, EH-LNK, EH-OLNK
Communication module
!
1.2 System overview
8All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
• High speed processor called “EH-SPEED” on board.• 20 ns / binary command• 2 processors running in parallel
Main processor
Operation processor
20ns
100ns
EH-CPU548 EHV-CPU128
1.3 High speed processing
9All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Comparison Table
Contact
Coil
= (16bit)
+,- (16bit)
+,- (32bit)
Timer
HitachiEHV-CPU128
MQ02H
OCJ1H-CPU6□HCommand
20 ns40 ns60 ns80 ns
800 ns2,280 ns
34 ns68 ns
102 ns170 ns306 ns272 ns
20 ns20 ns
180 ns180 ns320 ns560 ns
PLC-MIX* 12.346 14.514 21.786* : PLC performance defined by JEMA
1.3 High speed processing
10All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Refresh CycleHitachi EHV-CPU128 M Q02H
3.2ms 2.4ms 4.5ms 7.8ms* Measured point : Input : Opt-coupler logic side, Output : Relay logic side
1.3 High speed processing
11All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
WRWL*WMWN
0 - C3FF0 - 3FF, 1000 - 13FF
0 - 3FF-
0 - EFFF0 - 3FF, 1000 - 13FF, … ,7000 - 73FF
0 ~ 7FFF0 ~ 1FFFF
EH-CPU548 EHV-CPU128
* WL memory can be used as internal register in case LINK module is not used.
• Program memory 128k step (131,070 step) can be fully used only for program independent from comments.
• Data memory is expanded to 228 kwords.
!Hitachi M O F Y K
Program (step) 128k 124k 120k 117k 120k 160k
Data (word) 228k 157k 256k 160k 307k 176k
Comparison table
1.4 Large capacity program memory
12All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
1MB comment memory on board besides programmingmemory
!Hitachi M O F Y
Comment (byte) 1M Shared with program
224k
Competitors
Shared with programROM
Start SW1
X101
data flag
M14 Y205
Conveyer 1
Conveyer control
Automatic speed control
Start operation after initialization
Conveyer controlStart operation after initializationStart SW1data flagConveyer 1Automatic speed control
X101 M14 Y205
1.5 Large capacity comment memory
13All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Downloading time
128k
USB
Ethernet
RS-232C
64k32k
15
12
180
8
7
100
5
5
63
Baud rate of RS-232C is 57.6 kbps.Comment size is 8% (default).
Info.
1.5 Large capacity comment memory
[sec.]
14All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EHV-CPU has Ethernet port, USB port and Serial port
Ethernet
Supervising
ASR function
Programming software
Serial
USB
HMI
Ethernet
Ethernet
USB
Serial
H-Prtcl x 4, ASR x 6
12Mbps (FullSpeed)
RS-232C/422/485,H-Prtcl/General
1.6 Improved Network Function
15All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
PROFIBUS
FL-net他社PLC 他社PLC 他社PLC
Link system
Hitachi Network
Up to 8 units of communication modules mounted(The number of modules is limited by total current consumption also.Set up your system not to exceed current supplied by power supply module.)
DeviceNet Field bus system
Slot 0-7 for communication modules (*)
(*) EH-ETH, EH-(O)LNK, EH-RMD, EH-RMP, EH-FLN2
1.6 Improved Network Function
16All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Compatibility with Existing Hitachi LINKInfo.
Monitor, Programming
×(Ver.1.03)
L/E supports only loop No.1 and 2.If EHV-CPU is connected existing Link system, the loop No. must be 1 or 2.
!
1.6 Improved Network Function
Data link … OKRemote access …L/E : To H/EH via EHV … OKC/E : To EHV via H/EH … NG(planned to be modified.)
17All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Data type1
Bit designation for word access register
Signed integer Floating point ASCII dataWR0.S = -12345DM0.S = DN100.S
DR0.FL = -1.234567DN0.FL = DN2.FL * 3.14
WR0.ASC.9 = “Hello EHV”
Word and Double word Direct programming without special command
WR0 = H4865 (He), WR1 = H6C6C (ll),WR2 = H6720 (o_), WR3 = H4548 (EH),WR4 = H5600 (V_)
b15 b0b8
WR0
WR0.F WR0.8WR0.0 = 1
1.7 Improved programming interface
18All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EXWEX u s 00 WEY u s 00
WEX u s 7F WEY u s 7F
EY
For each slot
Special use of EX,EY for :EH-DBW ... I/O dataEH-POS4 ... Status dataEH-AXH8M ... Overflow flagEH-TC8 ... Overflow flagEH-AYH8M ... Overflow flag
Expanded XY area128+128 words are assigned for each slot.It is used for following modules, and can be used as internal register for other modules.
2
u: unit No., s: slot No.
1.7 Improved programming interface
19All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Edge Coil (up) Edge Coil (down) Edge Processing Box (down)
Off delay timerTDN n
TC
Besides above, block copy, copy move, POS4 command, etc.
Comparison Box
> >= d = s1 > s2d = s1 >= s2
New Commands for EHV3
The number of above edge commands are 1024 each.The number of timer is 2,560 with all time-base available1, 10, 100, 1000ms
!
1.7 Improved programming interface
Edge Processing Box (up)
20All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
FUN 20 (WR0)[ DSRCH (WR0) ]
DSRCH (WR3, WR0, WR100, WR2) EH-CPU (FUN command) EHV-CPU
Search dataSearch area I/Oarea sizeFound data I/ONumber of data
WR0WR1WR2WR3WR4
EHV does not have FUN command that existing EH-150 has.They are modified as arithmetic or application commands for EHV.
Command format improvedEasier and more understandable
4
!
1.7 Improved programming interface
21All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EH-CPU EHV-CPU
INT ( 5 )...RTI
Same cycle time must not be duplicated.(Duplicated cycle time results in error in circuit building.)
Cyclic scanConfigurable cycle time
5
INT 0...RTI
Set by user
5ms fixed
1.7 Improved programming interface
!
22All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
In case several cyclic programs exist, shorter cycle has higher priority. So longer cycle scan may not executed as expected. To avoid this, it is recommended to set cycle time of longer scan cycle as a certain times of the shortest cycle.
How to work Cyclic scanInfo.
Expected cycle
Actual cycle
Cycle A
normal
Cycle B = 2 x Cycle A
1.7 Improved programming interfaceCyclic scan5
Cycle B
23All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Instruction for use
EHV-CPU Features
Control Editor
Convert tool
24All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EHV does not support old EH-BS3, 5, 8 (without A type).
If communication modules are mounted slot 3-A, CPU detects 58 error.
2.1 Not supported modules/unitsBase unit1
EHV does not support old EH-IOC.2nd expansion base does not work with EH-IOC. (41 Error) 1st expansion base works, but it is not covered by warranty.
I/O controller2
!
!
25All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EHV does not support EH-MEMD,MEMP.(mechanical reason)
EH-MEMP, EH-MEMD32.1 Not supported modules/units
26All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EH-IOCH and EH-IOCH2 can be mixed in one PLC system, but 5th expansion base must be EH-IOCH2
I/O Controller1
If EH-IOCH is used in 5th base, data in 5th base is not updated.
ASR function does not work with newly expanded data ”WEX, WEY, WN”
EH-ETH2
2.2 Usage restrictions
!
27All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
(1) Modbus Slave Mode (I/O mapping)Supported I/O is only ”WX / WY / WR / WL / WM / TC”. Other I/O like WN is not supported.
EH-SIO3
(2) Simple Data Link ModeSupported I/O is only ”WR / WL / WM” with I/O range that EH-CPU548 currently supports.(WR0-C3FF, WL0-3FF, WL1000-13FF, WM0-3FF)
2.2 Usage restrictions
28All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Instruction for use
EHV-CPU Features
Control Editor
Convert tool
29All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Control EditorControl EditorC EInside CD setup.exe
User registration format
USB driver
Instruction manual
Convert Tool
DVD case
Serial, USB and LAN cables are not included with CD package.
Ver.1.03Ver.1.03
6 digits serial number XYZZZZ
X : YearY : Month (1 - 9,A,B,C)Z : Serial number 0000 - 9999
1 installation for 1 PC
Recommended PCPentium 4 (1GHz)Memory : 512MB
Supported OSWindows XP SP2Windows 2000 SP4
3.1 Overview
30All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Communication setting of Control Editor
Communication setting of CPU(only when online)
Project
Environmental settingUser programComment
Monitor
Project Tree1
Set from top to bottom
3.1 Overview
31All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
• Windows standard based operation.• Both Mouse and Keyboard operation supported.
Upload / Download / Verify
CPU Status / Circuit monitor
RUN * / STOP * / Initialize * (* : Not displayed default setting)
Offline / Online / Ondirect
I/O Set/Reset / Force output / Auto Programming
Operation2• Easy and Visual interface for other brands’ PLC users
3.1 Overview
32All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Program Sheet (Structured programming)3Multiple program sheets for multi-purpose andmulti-programmers.
Uploading
Downloading
3.1 Overview
33All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
3Program sheet can be copied easily by right mouse click after opening multiple Control Editor.
Right mouse click oncopied program sheet.
3.1 OverviewProgram Sheet (Structured programming)
34All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Open from file
Selecting “New Project”, new dialog box to configure program type will appear.
Open a last project
Start up13.2 Programming
35All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Contact
Ladder symbol input23.2 Programming
Coil
36All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Timer/Counter coil
3.2 Programming
Comparison Box
Ladder symbol input2
37All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Processing Box Commands or Formula
Box comment
Available command list
Guidance displayed by clicking command in the list
3.2 ProgrammingLadder symbol input2
38All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Horizontal line
NOT
After or while programming, execute “Build” operation. Then Control Editor will check the program and make “Object data” for CPU to execute.
3.2 ProgrammingLadder symbol input2
Draw Horizontal line
Vertical line
Delete vertical line
Connector
Circuit comment
Up edge detection
Down edge detection
(No number necessary)
(No number necessary)
Build
39All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Build
Edit Data
Object Data
Program OK?
Yes
Result
3.2 ProgrammingLadder symbol input2
Result
No
Double click to jump to error circuit.
40All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Box comment (64)
Circuit comment (128)
I/O comment (32)
( ) : Number of characters
Comment input3Each type of comment can be downloaded to CPU.
3.2 Programming
41All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
(2) Comments of “WR*** . n” are common for WR***
(1) Comments for special internal registers are prepared.
Automatically inserted
All same comment
3.2 ProgrammingComment input3
42All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
CSV Open
CSV Save
After highlightingCtrl + c / Ctrl + v
Besides CSV save/open, manual copy/paste function available after mouse highlighting
EXCEL compatibility
3.2 ProgrammingComment input3
43All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Find, Replace, Jump
Offline edit function4
Besides I/O address,comments can befound as well.
3.2 Programming
44All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Line No. : 0 to 9999 in 1 sheet independent from program.
Circuit No. : Not exist unless circuits built.
Line No. Circuit No.
3.2 ProgrammingOffline edit function4
Find, Replace, Jump
45All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Change I/O
8 blocks changed at once
3.2 ProgrammingOffline edit function4
46All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
3.2 ProgrammingOffline edit function4
Auto Programming
47All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Cross reference (Single I/O)
Click to jump the circuit
Line and Column number of designated I/O displayed.
3.2 ProgrammingOffline edit function4
48All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
I/O list starting from designated I/O displayed.
“*” sign for existing I/O.
3.2 ProgrammingOffline edit function4
Cross reference (I/O List)
49All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
I/O configuration
Module listModule type name listed
GuidanceI/O address displayedaccording to slot No.
Read I/O configuration in online
I/O configuration is downloaded with program.
3.3 Configuration1
50All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Retentive area
Retentive Area SettingTotal 16 area can be configured freely.Multiple area can be set for each I/O type with graphical indication.
23.3 Configuration
Retentive area is downloaded with program.
51All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Operation Parameters
Error level display setting
What’s system processing time?In case of very short scan time, main processor may not have sufficient time for communication.To avoid this, system processing time can be inserted in every scan end.
System processing time added.
Operation mode in scan time added inOperation parameters, which was inspecial internal output bit.
Operation Parameters Setting3
3.3 Configuration
Operation parameters are downloaded with program.
52All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Link ParametersLink Parameters Setting
Separated setting windowClear mode at RUN/STOP added
Note : Configure LINK assignment in I/O configuration, otherwise Link parameters setting window is not active.Note : In case of no sending area (receiving only), check off “Send data”.
43.3 Configuration
Link parameters are downloaded with program.
53All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
FL-net Parameters
Note : Configure FL-net assignment in I/O configuration, otherwise FL-net parameters setting window is not active.
FL-net Parameters SettingFL-net configuration function added,which was separated tool.
53.3 Configuration
FL-net parameters are downloaded with program.
54All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Connect USB, serial or Ethernet cable between PC and CPU module,Select communication type accordingly,Go online.
3.4 Online setting
Control Editor Communication Setting1
55All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Communication Port SettingSerial port
None / 0 - 31
RS-232C
Protocol 1(1:1)
38.4kbps
Default setting
Port Mode
Port type
Baud rate
Protocol
St. No.
2 This is optional setting.Configure if necessary.
3.4 Online setting
Programming port
Port parameters are configured directly in online mode.They are updated after rebooting of CPU.
56All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Ethernet port
IP address(common for task code/ASR)
Port No.
Enable
Protocol
Timeout
Enable
3004-3007
TCP/IP
30s
Default
3
3.4 Online settingThis is optional setting.Configure if necessary.
Port parameters are configured directly in online mode.They are updated after rebooting of CPU.
Communication Port Setting
57All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Ethernet port (ASR)EnablePort No.ProtocolSend/Receive modeDestination (IP address, port No.)
Send timingCycleTime base to send The number of retryIntervalData area
6ch.
4
Port parameters are configured directly in online mode.They are updated after rebooting of CPU.
3.4 Online setting
Communication Port Setting This is optional setting.Configure if necessary.
58All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Calendar clock settingEasy to adjust PC clock
Current datain CPU
Default data is taken from PC clock.
Default data is 0:00 ‘00 1st Jan. 2000. If battery is empty, calendar data will be default value.
5
3.4 Online settingThis is optional setting.Configure if necessary.
Calendar data is configured directly in online mode.It is updated immediately.
59All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Enable/Disable
Server address
Access interval
Time zoneDefault is Japan (GMT+9:00).
NTP setting6
3.4 Online settingThis is optional setting.Configure if necessary.
NTP parameters are configured directly in online mode.They are updated after rebooting of CPU.Time zone can be changed in user program.
60All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Ethernet ASR function NTP client function
Ethernet
SNTP server
EHV CPU is able to read clock datafrom NTP*1 server or SNTP*2 serverin the network.
*1 Network Time Protocol*2 Simple Network Time Protocol
ASR stands for Automatic Sending/Receiving.EHV CPU is able to send or receive any data to/from host computer or devices in the network in cyclic timing or event timing.
Ethernet module (EH-ETH) has the same function,but EHV CPU is configured by Control Editor whileEH-ETH is by special web page.
ASR and NTP73.4 Online setting
61All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Download RUN
RUN switchor
Remote operation by RUN icon
Remote operation works only when RUN switch in STOP position.
3.5 Operation
Download RUN
RUN switch
1
62All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Status bar
Status indicationOffline/Online/On-directRUN / STOPOwn CPU / Remote CPUUSB / serial / Ethernet
Status bar indication2
3.5 Operation
Online
Online
ON-Direct
Offline Own st.
Own st.
Own st.
Own st.
63All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Circuit MonitorWhen mouse pointer on, monitor data is displayedin tool tip.
1
Incomplete circuits can be monitored.!
Tool tip for monitor
3.6 Monitor
64All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Floating point data is single precision (32 bits) based on IEEE754, which can be monitored in hexadecimal mode.
Floating point format can be directly monitored in decimal monitoring mode.
3.6 MonitorCircuit Monitor1
65All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Separated circuit can be monitored in one window.1
[00003]
[00377]
3.6 MonitorCircuit Monitor (Random circuit)1
66All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Data type (single I/O)
I/O Monitor2Data type (all I/O)
Multiple sheets
3.6 Monitor
67All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
CPU Status monitor1CPU parameters and status in one window.One click to clear error.
3.7 Online function
68All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
ON buttonOFF buttonON/OFF button
Address Up/Down
Double click to repeat the history area
Set buttonReset button
I/O Set / Reset2
Easier function for both bit and word area
3.7 Online function
69All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EHV CPU is able to memory user’s operation.
Error in red, and operation in black colorUp to 32 data stored(Old data is overwritten by later data)Data is stored in WRFEFF to WRFFFFNot possible to clear the history data(CPU initializing does not clear the data)If battery is empty, history data will be lost
CPU History3
3.7 Online function
70All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Program in CPU can be changed while CPU running,which is called Online change.Online change works only On-direct mode
Programming (edit)
Programming (OBJ)
Download
RUN
On/Offline
Go On-Direct mode
Program change
Program in CPU also changed
Build
Build
Online
On-Direct
Online change13.8 Online-change
71All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
(1) High speed Online change by double memory
(2) Manual online change mode (optional) available
Online change of EHV CPU2
3.8 Online-change
72All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Impossible - I/O configuration - Link parameters- FL-net parameters- Comments
Possible- Program- Operation parameters- Retentive area
Some parameters are out of target of online change.
Remarks in Online change33.8 Online-change
73All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
9 contacts + 1 coil
WR200=200WR201=201
WR100=100
WR100 = 100WR101 = 101
LEW
CE
Invisible
occupies 5 elements
occupies 3 elements
No space “ ” input
Max. 19 lines
Max. 32 lines
Programming13.9 Difference from LEW
11 contacts + 1 coil
74All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Processing box and coil in parallel
Any circuits after connector symbol
3.9 Difference from LEWProgramming1
75All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
(1) No number necessary for DIF/DFNThe number of DIF/DFN is limited.(512 each DIF/DFN)Over usage leads to error in circuit building.
(2) Auto completion (auto-horizontal line) is not available yet.Draw horizontal line by icon , [F11] or right mouse click menu
!
3.9 Difference from LEWProgramming1
76All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Shift A+
Shift B+
Shift C+
Shift C+
Shift M+
Shift P+
Shift H+
Shift V+
LEW CE
F5
F6
F8
Ctrl + F8
F7
F9
F12
F11Shift +
Customized by [Tool]-[Option]-[Keyboard Setting]
Vertical line
LEW
CE
Keyboard Setting2参 考
3.9 Difference from LEW
77All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
PCControl EditorHDD等
Program (Edit)
Parameters(I/O config., Retentive, etc.)
CPU
Monitor
Program (OBJ)
Parameters(I/O config., Retentive, etc.)
CPU communication(IP, Serial, etc.)
Program (OBJ)
CPU communication(IP, Serial, etc.)
PRJ FileParameters
(I/O config., Retentive, etc.)
CNV File
CSV data
Program (Edit)
Comment CommentComment
File formatInfo.
78All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
EnvironmentalParameters
Operation parameters
I/O configuration
Retentive area
Module parameters (Link, FL-net)
CPUcommunication
Serial communicationEthernet port
Calendar clock Built in Clock
NTP client
IP address
Parameters for task code
Parameters for ASR
Date
Server address, interval, etc.
Baud rate, Protocol, etc.
EHV CPU has following parameters.
Online settingDownloaded with user program
ParametersInfo.
79All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Click the icon to openproject tree window
Double click to open each parameters setting
ParametersInfo.
80All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Instruction for use
EHV-CPU Features
Control Editor
Convert tool
81All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
Convert Tool
Control EditorEXCELLadder Editor
CSV file
IOT file
Open CSV
PRN file PRJ FileOpen file
Ladder Program
I/O comment
Save CSV
Edit
Open PRN file to convertto PRJ file
I/O comment
Ladder program
I/O comment
Note : Copy and paste manually for circuit comment, memo comment and box comment.
4.1 Convert Tool
82All Rights Reserved, Copyright © 2006, Hitachi Industrial Equipment Systems Co., Ltd.
WR0 = 15ADRIO ( WR1 , WR100 ) ADRIO ( WR2 , WR200 )FUN 42 ( WR0 )
Example : Binary ASCII command
Description
15 characters from WR100 are convertedto ASCII data and stored in WR200
Binary data
WR100=H1234WR101=H5678WR102=H9ABCWR103=HDEF0
ASCII data
WR200=H3132WR201=H3334
・・・WR207=H4445WR208=H4620
PRN file
WR0 = 15DR1 = ADR( WR100 )DR2 = ADR( WR200 )WREFF0.ASC.30 = "Warning! Check ASC cmd."
Converted
ASC (WR200, WR100, 15)
Impossible to convert FUN command with ADRIO command
Manually converted by users
4.2 Remarks of conversion