Upload
sohail-forouzan-sepehr
View
1.728
Download
34
Tags:
Embed Size (px)
Citation preview
A single copy of this
publication is licensed to
on
This is an uncontrolled copy - not for contract use
Concrete Society
This is an uncontrolled copy. Ensure use of the most current version of this document by searching the Construction Information Service at http://uk.ihs.com
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Historical approaches to the designof concrete buildings and structures
A cement and concrete industry publication
Technical Report No. 70
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Acknowledgements
The work of preparing this Technical Report was partly funded by John Doyle Construction
Limited using the proceeds from winning the CONSTRUCT Award for Innovation and Best
Practice 2008. The award was given for the use of Twin-Wall Hybrid RC Cores at More London 7.
The Concrete Society acknowledges the contributions of the people who provided
information and guidance during the preparation of this document, including members of
The Society's Standing Committees. Particular thanks are due to the following:
Simon Hartshome (Highways Agency)
Dawn Humm (Hurst Peirce and Malcolm)
Patjansen (Gifford)
Tony Jones (Arup)
Deborah Lazarus (Arup)
Stuart Matthews (BRE)
Edwin Trout (The Concrete Society)
Published by The Concrete Society
CCIP-049
Published July 2009
ISBN 978-1-904482-57-4
© The Concrete Society
The Concrete Society
Riverside House, 4 Meadows Business Park, Station Approach, Blackwater, Camberley, Surrey GU17 9AB
Tel: +44 (0)1276 607140 Fax: +44 (0)1276 607141 www.concrete.org.uk
CCIP publications are produced by The Concrete Society (www.concrete.org.uk) on behalf of
the Cement and Concrete Industry Publications Forum - an industry initiative to publish technical
guidance in support of concrete design and construction.
CCIP publications are available from the Concrete Bookshop at www.concretebookshop.com
Tel: +44 (0)7004 607777
All advice or information from The Concrete Society is intended for those who will evaluate the significance and limitations of itscontents and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting fromsuch advice or information is accepted by The Concrete Society or its subcontractors, suppliers or advisors. Readers should notethat publications are subject to revision from time to time and should therefore ensure that they are in possession of the latestversion.
Printed by 4edge Ltd, Hockley, UK.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Historical approaches to the design ofconcrete buildings and structures
Contents
List of tables
1. Introduction
1.1 Development of Codes and Standards
1.2 Appraisal and repair
1.3 Scope and format
2. Development of concrete and concrete structures
2.1 Concrete
2.2 Concrete structures
3. Development of design codes
4. Development of materials standards
4.1 Units
4.2 Concrete constituents
4.2.1 Calcium chloride as an accelerator
4.2.2 High alumina cement (HAC)
4.3 Mix proportions and strength
4.3.1 Buildings and other structures
4.3.2 Highway and railway structures
4.4 Design exposure conditions
4.4.1 Buildings and other structures
4.4.2 Bridges
IV
1
1
2
2
4
4
4
6
9
9
9
9
9
10
11
19
24
25
27
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
4.5 Reinforcement and prestressing
4.5.1 Detailing symbols
4.5.2 Imperial bar sizes
4.5.3 Yield stresses
4.5.4 Fabric
4.5.5 Early reinforcement systems
4.5.6 Early prestressing systems
5. Design
5.1 Loading
5.2 Reinforcement design strengths
5.3 Bending and axial load
5.3.1 Buildings
5.3.2 Bridges
5.4 Shear and punching in reinforced concrete
5.4.1 Buildings
5.4.2 Bridges
5.5 Shear in prestressed concrete
5.5.1 Buildings
5.5.2 Bridges
5.6 Fire resistance
5.7 Bond and anchorage
5.7.1 Buildings
5.7.2 Bridges
5.8 Serviceability
5.8.1 Buildings
5.8.2 Bridges
5.9 Robustness
5.10 Analysis
5.10.1 Frame analysis
5.10.2 Slabs
28
29
29
30
30
30
31
32
32
33
34
34
37
39
39
43
48
48
50
52
56
56
58
60
60
63
65
67
67
68
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
6. Guidance relating to specific types of structures
6.1 Precast systems
6.1.1 Concrete frames
6.1.2 Precast floor and roof units
6.1.3 Large panel systems
6.1.4 On-site construction
6.1.5 Non-traditional houses
6.1.6 Standard bridge beams
6.1.7 Bearings for precast units
6.2 Foundations
6.3 Water-retaining structures
6.4 Houses: in-situ construction
6.5 Other structures
7. General information on concrete deterioration
7.1 Alkali-silica reaction (ASR)
7.2 Sulfate attack
7.3 Mundic
7.4 Clinker concrete
8. Other sources of information
References
Further reading
Appendix A. Proprietary floors
Appendix B. Non-traditional houses: precast and constructed in-situ
70
70
70
71
11
73
73
73
74
74
75
80
80
81
81
81
82
82
83
85
89
90
92
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
List of tables
Table 1 Some key steps in the development of Codes and Standards
Table 2 Publication dates for main Codes
Table 3 Publication dates for highway bridge design Standards
Table 4 Approximate conversion table.
Table 5 Designations of some concrete mixes
Table 6 Detailing symbols
Table 7 Specified yield stresses
Table 8 Loading Codes for buildings
Table 9 Highway loading Standards
Table 10 Design stresses for reinforcement
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Introduction 1
1. Introduction
There are many instances in which an engineer is asked to appraise an existing building,
or other structure, perhaps due to a planned change of use or as part of a refurbishment
process. A common example might be an office block built in the 1960s, although with
the move towards conservation, it is likely that many earlier buildings and structures will
be refurbished or upgraded rather than being demolished and replaced. As a first stage in
this process, it is useful to have as much information as possible about the structure, such
as what Code or Standard it was designed to, what the concrete and steel strengths were
likely to have been at the time of construction, what design approaches were adopted, what
proprietary precast concrete units were available, etc. The aim of this Technical Report is
to provide an outline of this information and to list some of the relevant publications and
other sources of readily available information, up to about 1990. (Although this Report is
primarily intended to cover UK practice, many British Codes and Standards were, and are,
used abroad and hence the guidance should be equally applicable overseas.)
1.1 Development of Codesand Standards
To engineers familiar with modern design Codes, some of the approaches adopted by earlier
Codes will appear strange. This Technical Report summarises the key changes that have
occurred in successive Codes in the UK up to about 1990, for example in the design for
shear and the provision of shear reinforcement. Some of the key points are given in Table 1.
Date Key points in design guidanceTable 1Some key steps in the development of Codes
and Standards.
The emphasis in this report is on the information contained in the structural Codes and
Standards, which are concerned with the strength of the concrete for design purposes and
generally do not consider the concrete constituents. It is only recently that there has been
crossover between the materials Standards and the structural Standards with, for example,
the required cover being related to the type of cement being used. However, the use of
some materials, such as high alumina cement (HAC), is covered by the structural Standards
and these are mentioned where appropriate.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
1.2 Appraisal and repair This document is not intended to cover the process of the appraisal of a structure nor
materials testing as these are well covered elsewhere. General guidance on appraisal may
be found in the Institution of Structural Engineers Appraisal of existing structures®, which
deals with all types of construction materials, not just concrete. It covers aspects such as
the reasons for an appraisal, the approval process itself, testing and monitoring. Also
included is some guidance on the use of modified materials partial safety factors when
assessing the structural capacity.
All aspects of the assessment of concrete bridges are covered in the Concrete Bridge
Development Group's Guidance on the assessment of concrete bridges®. The Highways
Agency's Design Manual for Roads and Bridges® contains a number of Standards for the
assessment of concrete bridges. Network Rail has its own Standards for the assessment
of railway bridges'4'.
Guidance on the reuse of concrete buildings is given in BSRIA Guidance Note GN 8/99,
Refurbishment of concrete buildings-structural and services options® and has been reviewed
by Gold'6'. The reuse of components, such as piles, is covered by CIRIA Report X332, Building
with reclaimed components and materials -A design handbook for reuse and recycling®.
General aspects of the deterioration of concrete structures are not dealt with in detail in
this document as they are well covered elsewhere. However, some forms of deterioration
are specifically related to structures of a certain age, such as reinforcement corrosion due
to the inclusion of calcium chloride in the concrete. These are considered in this document,
particularly when guidance concerning their use has been incorporated into later Codes.
Defects may be visible on the surface of the concrete; Concrete Society Technical Report 54,
Diagnosis of deterioration in concrete structures®, describes their appearance and significance.
Technical Report 22, Non-structural cracks in concrete®, describes the various types (plastic
settlement, plastic shrinkage, early thermal contraction, etc.) that may occur and explains
the principles that govern their formation.
This document does not cover the repair of concrete structures. Reference should be made
to the European Standard EN 1504'10' for general guidance and to publications such as
Concrete Society Technical Report 69, Guide to the repair of concrete structures with
reference to BS EN 7504'11' and those from the Concrete Repair Association.
1.3 Scope and format This Report is intended to give a general overview of the requirements contained in the
relevant British Standards and Highways Agency/Department of Transport documents
available at the time, supported by other appropriate publications. The emphasis of this
Report is on the design of reinforced and prestressed concrete buildings, bridges and other
structures, concrete was widely used for housing in the 1950s and 1960s. There were a
variety of precast concrete systems, some of which were less successful than others'12',
which are mentioned briefly. In addition, there were a number of proprietary precast
concrete frame systems used for industrial and commercial buildings, some details of
which are included.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Introduction 1
The reader should generally refer to the original cited document for further information.
However, this may be difficult in some cases, particularly when considering some of the
older Standards. For this reason alternative references have been given in some cases, such
as some of the Handbooks to the British Standards'1"8' and to the various editions of
Reinforced concrete designers' handbook^, which reproduce much of the material in the
Standards. Additionally, further sources of information are given in Chapter 8.
Rather than summarise the information given in each Code or Standard in turn, this
Report is divided into topics. Thus, for example, Section 4.3 shows how specified concrete
mix proportions and strength have changed over the years and Section 5.4 looks at how
the guidance relating to the design for shear and punching, and the provision of shear
reinforcement, has developed.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
2. Development of concrete and concretestructures
The aim of this chapter is to give a very brief overview of the development of concrete
and of its use in structures.
2.1 Concrete Joseph Aspdin's patent of 1824 for Portland cement (so called due to its resemblance when
hardened to Portland stone) is often considered as a landmark in the history of cement
production, although in reality the material was closer to a hydraulic lime than a modern
cement. Further developments by William Aspdin, and Isaac Johnson in the 1850s, led to
the production of cements very similar to those of today.
Up to about the mid-1950s, concrete was made only with Portland cement. At that time,
fly ash (or pulverised fly ash, pfa) was introduced on a small scale and the first Standard,
BS 3892, Pfaforuse in concrete, was published in 1965. However, fly ash was not commercially
marketed until the mid-1970s. Ground granulated blastfurnace slag (ggbs) became com-
mercially available in the Midlands and north of England in the mid-1960s, extending to the
south of England in the 1980s. (Concrete Society Technical Report 40'20' gives information
on the introduction and development of fly ash and ggbs.) Silica fume (or microsilica)
became commercially available in the 1970s.
2.2 Concrete structures The development of concrete and its use in structures has been reviewed in various
publications, such as those by Hurst'21', Newby'22', Somerville'23' and Sutherland'24'.
Stanley'25' gives a brief overview of the history of concrete.
Unreinforced concrete was used for the construction of some houses in the first half of
the 19th century, but the concept of reinforced concrete did not appear until William
Wilkinson's patent in 1854. Concrete was widely used for the construction of industrial
buildings and, in particular, cotton and woollen mills, during the second half of the 19th
century, chiefly because of its fire resistance. By the 1890s concrete was being used
extensively for bridges and other civil engineering applications. The first multi-storey
reinforced concrete building in Britain was Weavers Mill in Swansea, which was completed
in 1898 using the Hennebique reinforcement system. Prestressed concrete was developed
between the First and Second World Wars, following the lead of Freyssinet.The first ready-
mixed concrete plants started to operate in the early 1930s.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of concrete and concrete structures 2
Chrimes'26' traces the use of concrete for bridges in the British Isles from its 19th century
origins to the outbreak of the Second World War. The publication contains many photographs
and working drawings of early bridges and has over 200 references. The earliest known UK
example of a mass concrete bridge was on the District Line, near Cromwell Road, London,
built in about 1865.The use of reinforced concrete for bridges began in the first decade of
the 20th century, mainly using the Hennebique system. Other systems followed, including
Monier, Kahn, Considere and Coignet. The first reinforced concrete rail bridge was built in
Dundee in 1903. By the 1930s there were about 2000 reinforced concrete bridges in the UK.
Smith'27' has reviewed the development of concrete bridges in the UK since 1940, starting
with the application of prestressed concrete in bridges during the Second World War. The
publication concentrates on bridges built during the first and second decades after the war,
concluding with a brief overview of later developments. By the 1950s concrete bridges had
been built using the Freyssinet and Magnel systems. In the UK a stock of emergency pre-
stressed concrete beams had been held during the Second World War and used afterwards
in permanent bridgeworks. The first major prestressed concrete road bridge was the
replacement for Northam Bridge, Southampton, in 1954.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
t
3. Development of design codes
The first National Design Code for concrete structures was published in 1934, although
regulations for reinforced concrete had been introduced in London in 1915. Prior to the
development of Codes, designs were either proprietary or were in accordance with textbooks,
such as Reinforced concrete simply explained by Oscar Faber'28'. There were also various
guidance documents issued by The Institution of Structural Engineers (then known as The
Concrete Institute) and others.
Over the years, new Codes have been introduced. The publication dates for the main design
Codes for buildings and other structures up until 1990 are given Table 2; those for bridges are
given in Table 3. Invariably there was some overlap at each transition between an old and
a new Code. In addition, Codes are subject to revision before they are eventually replaced.
Often the Amendments are relatively trivial, for example correcting typographical errors,
but sometimes they have major implications for design. The more important changes are
identified in the following sections.
Table 2Publication dates for main Codes.
Date Design Code
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of design codes
Some Codes listed in Table 2 were accompanied by Handbooks when they were originally
published, as follows:
• 1934 Code of Practice, Scott and Clanville(13>
• CP114,Scottefa/.(14>
• CP 115, Walley and Bate'15'
• CP 110, Bate eta/.f16'
• BS 5337, Anchoreta/.<17>
• BS 8110, Rowe eta/.f18'
Note that Scott and Glanville'13' and Scott eta/.'14' reproduce the whole of the Code of
Practice to which they refer. The other Handbooks have to be read in parallel with the
relevant Standard.
The British Standards Institution (BSI) maintains an archive of withdrawn Codes and
Standards; copies of withdrawn British Standards may be obtained through the BSI
Knowledge Centre (contact [email protected]).
In parallel with the national Codes and Standards, aspects of design may have been
covered by local by-laws. This is particularly so in London, as detailed in subsequent
sections of this Report.
The design of concrete highway bridges has always been covered by their own Standards
and Specifications, although many of these have made reference to the Codes for the
design of buildings. Initially these were issued by the Ministry of Transport (which became
the Department of Transport and then the Highways Agency), see Table 3. In 1978 the
first Standard was issued by BSI (BS 5400), but this was not implemented until 1983 by
the Highways Agency in BD 17/83 (which contained a large number of amendments and
additions, most of which were incorporated into the subsequent version of BS 5400). Thus
in the interim there were two sets of guidance available.
Table 3, and the subsequent discussions in this Technical Report, considers only the main
bridge design Standards and not the guidance issued for other 'special' structures, such as
those given in Section 2 of the Design Manual for Roads and Bridges.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Table 3Publication dates for highway bridge design
Standards.
The Highways Agency maintains an archive of superseded bridge standards. Enquiries
should be addressed to [email protected] (note the underscore).
There are relatively few 'historic' concrete railway bridges. It would appear that they were
generally designed to in-house guidance documents, rather than using the highways
Standards. Initially the guidance documents were prepared by the different Regions but later
common guidance was prepared, such as British Railways Board Technical Note 18, Design
of reinforced or prestressed concrete, which was issued in 1968. Railway archive material
has been transferred to the National Archives in Kew (www.nationalarchives.gov.uk).
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
4. Development of materials standards
This chapter reviews the way in which the concrete and steel strengths in successive
Codes and Standards have developed over the years.
4.1 Units
Table 4Approximate conversion table.
It should be noted that earlier Codes and Standards (up to the late 1960s) were written in
imperial units (pounds-force, feet and inches). In the following sections the original units
have been used throughout to avoid confusion. The following approximate values may be
used to convert from imperial units to metric units:
For ease of reference, approximate metric values are given in brackets in the text after the
imperial values.
4.2 Concrete constituents This report is chiefly concerned with the structural design of reinforced and prestressedconcrete. Structural Codes have generally assumed that the concrete constituents beingused would be sound and will not cause any long-term durability problems. However,there are two materials, namely calcium chloride and high alumina cement, that havecaused problems and have been subsequently banned; their early use is summarisedbelow and in the relevant parts of Section 4.3.
4.2.1 Calcium chloride as anaccelerator
Calcium chloride was used as an accelerating admixture in concrete up until the mid-1970s.Changing attitudes to its use in British Codes have been reported by Pullar-Strecker'29'. Atthe time that early codes were drafted, it was not appreciated that the use of calciumchloride would lead to corrosion of embedded reinforcement. As experience developed,so the guidance changed, and the use of calcium chloride was effectively banned in 1977.
4.2.2 High alumina cement(HAC)
High alumina cement (HAC), also known as calcium aiuminate cement (CAC), differs fromPortland cement, being composed of calcium aluminates rather than calcium silicates. Itsrapid strength development made HAC popular from 1950 to 1970. However, mineralogical'conversion' sometimes caused reductions in concrete strength and increased vulnerabilityto chemical attack. As experience developed, so the guidance changed.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
HAC concrete was effectively banned for use in new structural concrete in the UK following
a few well-publicised collapses in the 1970s. Time and experience have shown that the
primary causes of these collapses were poor construction details or chemical attack, rather
than problems with the concrete itself. Most HAC concrete in the UK went into precast
beams. It is estimated that up to 50,000 buildings with similar beams remain successfully
in service today in the UK. The beams can be found in public and industrial buildings such as
schools, flats and business units. The prerequisite for maintaining their structural integrity
is the provision of a stable, dry environment.
If the presence of HAC is suspected, confirmation requires chemical or laboratory testing
of samples. (HAC concrete tends to be darker than concretes using Portland cement, which
can be an aid to identification.) If the presence of HAC is confirmed, professional advice
on its condition may be required. However, it is important to remember that the majority
of these buildings are performing perfectly adequately. The Building Research Establishment
(BRE) has produced various relevant publications, see for example Special Digest 3<30' and
Dunstereta/'31'32).
4.3 Mix proportions andstrength
Letters or Roman numerals were used in some earlier Codes and Specifications to identify
standard concrete mixes, see Table 5; details are given in subsequent Sections under the
relevant Code or Specification. It should be noted that in some documents the standard
mixes were listed in ascending order of strength (for example Mix C was stronger than Mix A)
while in others it was the other way round (Mix III was weaker than Mix I), which could
cause confusion. In other early documents the mixes were referred to by their proportions,
either by volume of cement and aggregates or by weight of cement and volume of aggregates.
Some of the latter worked on the basis of 112 lbs (1 cwt or hundredweight) which was the
standard weight of a bag of cement at the time. More detailed guidance on the design of
concrete mixes, such as the appropriate water/cement ratio and suitable aggregate gradings,
was given in standard publications such as Design of concrete m/xes'33' (commonly known as
Road Note 4) which was first published in 1950 and Concrete mix design^ first published
in 1964.
As shown in the following sections, there was steady increase in the strength of the standard
concrete mixes given in successive Codes and Specifications, reflecting improved cement
properties and better quality control. Somerville*23' noted that 28-day cement strengths
increased from about 32 N/mm2 in the late 1940s to about 47 N/mm2 in the early 1990s.
Earlier cements gained strength more slowly than modem cements, and continued to gain
strength beyond the specified 28 days. This was reflected in some Codes, which allowed
an enhanced strength to be used when the structure was to be loaded at a significantly
later date; again this is detailed, where appropriate, in the following sections.
10
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
From about 1970, concrete was specified simply in terms of its strength, initially in psi
(e.g. Class 4500) and later in N/mm2 (e.g. Class 30). Note that in all the Codes and
Specifications considered, 'strength' referred to the cube strength at 28 days rather than
the modern dual method of using both cylinder and cube strengths, e.g. 40/50.
The earlier design Codes included guidance on the production of concrete and on aspects of
construction. Gradually the material aspects were transferred into Codes such as BS 1926,
Ready-mixed concrete, and BS 5328, Methods for specifying concrete including ready-mixed
concrete (which later became BS 5328, Concrete). In 1982,Teychenne<35) noted that there
were a number of confusing differences between the design Codes and the concrete Codes.
In the following sections, only the guidance in the design Codes has been considered.
The strength of the concrete in historic structures is likely to be very variable. The only
sure way of determining it is to take cores that are then tested in accordance with Part 120
of BS 1881, Testing concrete, or Parts 1 and 3 of BS EN 12504, Testing concrete in structure.
However, if design information is available, guidance on the likely minimum concrete
strength may be obtained from the Codes of Practice current at the time.
4.3.1 Buildings and other
structures
Reinforced Concrete Designers' Handbook, 1932'19'
The First Edition of 'Reynolds' gave a series of concrete Mixes A to F specified on the basis
of cementfine aggregate:coarse aggregate ratios by volume with corresponding 'standard'
working stresses for the hardened concrete; cube strengths were not given. On the assumption
that the working (or permissible) stress was one-third of the cube strength as in subsequent
Codes, the strengths for the Mixes were as follows:
Mix A
MixB
MixC
MixD
MixE
MixF
1:3:6
1:21/2:5
1:2:4
V.VA3V3
V.VA3
1:1:2
1200
1500
2100
2250
2400
2625
psi
psi
psi
psi
psi
psi
(8 N/mm2)
(10 N/mm2)
(14 N/mm2)
(16 N/mm2)
(17 N/mm2)
(18 N/mm2)
11Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
It is not clear from the Handbook whether the London County Council By-laws used the
same designation letters.
London County Council By-laws, 1938
The by-laws gave four mixes specified on the basis of cementfine aggregate:coarse
aggregate ratios by volume, equivalent to Mixes C to F in the First Edition of 'Reynolds'
detailed above, but with slightly different cube strengths as follows:
• 1:2:4 1800 psi (12 N/mm2)
• 1:12/3:31/3 1950 psi (13 N/mm2)
• V.V/z:3 2025 psi (14 N/mm2)
• 1:1:2 2250 psi (16 N/mm2)
Code of Practice for reinforced concrete, 1934
The Code specified three grades of concrete, designated 'Ordinary Grade', 'High Grade'
and 'Special Grade', with corresponding levels of control. The Explanatory statement in
the code noted that:
"... industry has at this time reached a stage in development when advantage
should be given to the engineer who is prepared to spend time and money in
producing consistently controlled concrete. In other words the day has passed
when one stress only should be permitted for a mix regardless of the care
exercised."
For Ordinary Grade concrete, four nominal mixes were specified on the basis of cementfine
aggregate:coarse aggregate ratios by volume, with corresponding 28-day cube strengths,
as follows:
Mix 1
Mix II
Mix III
Mix IV
1:1:2
1:1.2:2.4
1:1.5:3
1:2:4
2925
2775
2550
2250
psi
psi
psi
psi
(20 N/mm2;
(19 N/mm2)
(18 N/mm2)
(16 N/mm2)
Though the same mix proportions were given for High Grade concrete, additional control
was required, leading to strengths that were about 30% higher, as follows:
Mix
Mix
Mix
Mix
I
II
III
IV
1:1:2
1:1.2:2.4
1:1.5:3
1:2:4
3750
3600
3300
2850
psi
psi
psi
psi
(26 N/mm2)
(25 N/mm2)
(23 N/mm2)
(20 N/mm2)
12Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
Further control, including control of the water/cement ratio, was required for Special Grade
concrete, which could lead to strengths not more that 25% greater than the corresponding
High Grade concrete mix.
Interestingly, the Code noted that concrete that failed to reach its specified strength at
28 days should not be condemned if subsequent tests at 56 days gave a strength of at
least 10% more than the 28-day strength. This reflected the relatively slow rate of gain of
concrete strength at the time and the continuing gain in strength after 28 days.
The Code permitted the use of Portland cement, Portland-blastfurnace cement and high
alumina cement, but did not differentiate between the various cements in the above
mixes and strengths. The Handbook'13' advised that the use of high alumina cement should
be limited to Mix IV, i.e. 1:2:4.
London County Council By-laws, 1938
Here mixes were given both on the basis of cementfine aggregate:coarse aggregate ratios
by volume and on the basis of weight of cement (lb):fine aggregate (cu. ft):coarse
aggregate (cu. ft). Six mixes were given for structural applications, with corresponding 28-
day cube strengths as follows:
Mix
Mix
Mix
Mix
Mix
Mix
1
II
III
IA
IIA
IIIA
1:1:2
1:1Vz:3
1:2:4
1:1:2
1:1V2:3
1:2:4
112:iy4:2y2
112:1 VSSVA
W2-2Vr5
-]1Z:VA:ZVz
112:17/s:33/4
112:2y2:5
2925
2550
2250
3750
3300
2850
psi
psi
psi
psi
psi
psi
(20 N/mm2)
(18 N/mm2)
(16 N/mm2)
(26 N/mm2)
(23 N/mm2)
(20 N/mm2)
Note that, in terms of strength, the LCC Mixes I, II and III correspond with the 1934 Code
of practice for reinforced concrete Mixes I, II and IV, which could cause confusion.
There were an additional four mixes, using all-in aggregate, with corresponding 28-day
cube strengths as follows:
Mix IV
MixV
Mix VI
Mix VII
1:6
1:8
1:10
1:12
112:7y2
112:10
112:12y2
112:15
1480 psi (10 N/mm2)
1110 psi (8 N/mm2)
740 psi (5 N/mm2)
370 psi (3 N/mm2)
The above information was also given in Reinforced concrete simply explained^ and in
Practical examples of reinforced concrete design^.
13
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Code of practice for the design and construction of reinforced concrete structures for
the storage of liquids, 1938
The Code specified minimum concrete grades in terms of weight of cement (lb):fine
aggregate (cu. ft):coarse aggregate (cu. ft) as follows:
• 112:2:4 for general use
• 112:214:5 for slabs greater than 24 inches (610 mm) thick
CP114, Structural use of normal reinforced concrete in buildings, 1948
The Code was the first to assume that design was entrusted to:
"Structural or civil engineers experienced in reinforced concrete and that the
execution is carried out under the direction of a qualified engineer."
As a consequence of this, the different levels of quality control considered in the 1934
Code were no longer included in CP 114:1948, as:
"It is felt that proper supervision must be assumed and provided for all
reinforced concrete, and is an essential part of the cost of the work. No work
ought to be done without it as it is impossible to calculate the disastrous
effect which may result... from a failure to produce a specified mixture."
Specification was still on the basis of cementfine aggregatexoarse aggregate ratios by
volume, with the introduction of a clause dealing with the control of the water/cement
ratio. The number of standard mixes was reduced from four to three. The minimum 28-
day cube strengths, using Portland cement or Portland-blastfurnace cement, were slightly
higher than those for the High Grade mixes, as follows:
• 1:1:2 4500 psi (31 N/mm2)
• 1:11/2:3 3750 psi (26 N/mm2)
• 1:2:4 3000 psi (21 N/mm2)
For a 1:2:4 mix using high alumina cement, a strength of 5000 psi (35 N/mm2) was
specified at two days.
Calcium chloride was permitted, with the following guidance in the section dealing with
Work in cold weather.
"Calcium chloride may be used to accelerate the rate of hardening - usually
V/z% by weight of cement will prove sufficient and there are dangers associated
with excess."
14Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
CP 114.100, Suspended concrete floors and roofs, 1950
The sub-Code used the same standard mixes as in CP 114:1948, defined by volume, with
the same 28-day strengths. However, it suggests that the cement content, and ideally the
aggregate contents, should be determined by weight. While CP 114:1948 gave general
guidance on the control of the water content in the mix, CP 114.100 specified maximum
water/cement ratios of 0.43, 0.51 and 0.58 for the three standard mixes when using
uncrushed gravel aggregates; the sub-Code suggested that a slight increase would be
necessary for other aggregates. When "compacting by vibration" the maximum values
should be reduced by 20%.
Surprisingly, high alumina cement comes before Portland cement and Portland-blastfurnace
cement in the Code's list of suitable cements in the Code. However, it does warn that:
"High alumina cement may be unsuitable for use with certain aggregates ....
The user can only be guided by previous experience in determining whether it
is suitable for use with such aggregates."
The sub-Code gives the same guidance as CP 114:1948 on the use of calcium chloride.
CP 114, Structural use of reinforced concrete in buildings, 1957
The nominal mixes and their associated strengths were the same as in the 1949 version.
The Code allowed the permissible stresses in compression to be increased by the following
percentages for members loaded significantly later than 28 days:
• 2 months
• 3 months
• 6 months
• 12 months
10%
16%
20%
24%
The guidance on calcium chloride was modified to:
"Calcium chloride may be used to accelerate the rate of hardening of Portland
cement concrete but not more than 2% by weight of cement should be used."
On the use of high alumina cement, the 1957 version warns that:
"High alumina concretes are sometimes unsatisfactory in warm, moist
conditions. The cement should be only used in accordance with the
manufacturer's recommendations".
15Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
CP 115, The structural use of prestressed concrete in buildings, 1959
The Code contained no nominal mixes but specified minimum 28-day cube strengths of
6000 psi (41 N/mm2) for pre-tensioned concrete and 4500 psi (31 N/mm2) for post-
tensioned concrete. It required the use of Portland cement or Portland-blastfurnace cement,
indicating that other cements might be desirable in certain circumstances but they should
only be used with the engineer's approval. Again it warned against the use of high alumina
cement.
This appears to be the first Code to consider the risk of corrosion resulting from the use of
calcium chloride, saying:
"Calcium chloride should not be used when steam curing is employed. Until
more is known about corrosion, the use of calcium chloride cannot be
recommended. There may be dangers associated with excess."
CP 2007, Design and construction of reinforced and prestressed concrete structures
for the storage of water and other aqueous liquids, 1960
Guidance inCP 2007 is generally in line with CP 114 and CP 115, but the Code recommends
two nominal mixes, specified on the basis of weight of cement (lb):fine aggregate (cu. ft):
coarse aggregate (cu. ft) but referred to in the Code on the basis of cementfine aggregate:
coarse aggregate ratios by volume, with a corresponding 28-day strength, as follows:
• 112:2:4 1:1.6:3.2 3600 psi (25 N/mm2)
• 112:2y2:5 1:2:4 3600 psi (25 N/mm2)
Note that both mixes were required to have the same 28-day strength; the 1:2:4 mix was
suggested for use in thicker sections.
London Building (Construction) By-laws, 1964
The 1964 by-laws appear to use the same concrete mixes as in the 1938 by-laws, (see
page 13) but they are referred to as Grades I to III and lAto IIIA rather than 'Mixes'.
CP 116, The structural use of precast concrete, 1965
The Code specified five Grades of concrete, with specified 28-day cube strengths as follows:
Grade A
Grade
Grade
Grade
Grade
B
C
D
LLJ
3000
3750
4500
6000
7500
psi
psi
psi
psi
psi
(21
(26
(31
(41
N/mm2)
N/mm2)
N/mm2)
N/mm2)
(52 N/mm2)
16Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
The guidance on the use of calcium chloride was more definite than that in CP 115:1959,
saying:
"Calcium chloride is not recommended either as an admixture or internally
mixed with cement in any form of prestressed work. The total amount of
calcium chloride in conventionally reinforced concrete should not exceed 2%
(1.5% anhydrous CaCl2) and should be dissolved in some of the mixing water.
When calcium chloride is used in concrete, not less that 25 mm of cover
should be given to all steel unless permanent protection is provided."
Guidance on the use of high alumina cement, similar to that in Appendix Bof CP 114:1959,
was included in the main body of the Code. It stated that high alumina cement concrete
should not be used in wet or humid conditions at temperatures above about 27°C without
prior consultation with the manufacturer.
CP 114, Structural use of reinforced concrete in buildings - Metric version, 1969
Three Nominal Mixes were given (as in the 1957 version), with 28-day cube strengths
using Portland cement or Portland-blastfurnace cement of 30, 25.5 and 21 N/mm2. In
addition a Table of Standard Mixes by weight was included for the three concrete strengths,
30, 25.5 and 21 N/mm2. The Code contained the same percentage increases in permissible
stress for members loaded at later than 28 days as in CP 114:1957.
The strength of the 1:2:4 high alumina cement mix was specified as 40 N/mm2 at two
days. The Code warns against the use of high alumina cement in warm moist conditions
and contains Appendix B which gives guidance on approaches for reducing the harmful
effects of conversion.
Reinforced Concrete Designer's Handbook(19)
The Ninth Edition of the Handbook gave the same information asCP 114:1969 (for 19 mm
aggregate only) but defined the mixes in terms of the letters A, B and C; Standard Mix A
was equivalent to the 21 N/mm2 mix in CP 114, Mix B was equivalent to 25.5 N/mm2 and
Mix C was equivalent to 30 N/mm2. The Handbook also included Designed Mixes D and E,
with 28-day cube strengths of 40 and 50 N/mm2 respectively.
CP 110, The structural use of concrete, 1972
Described as 'The Unified Code', CP 110 brought together the separate Codes relating to
reinforced, prestressed and precast concrete. Design in CP 110 (and all subsequent Codes)
was based on specified concrete strength grades, from 20 N/mm2 up to 50 N/mm2.
Minimum concrete grades were specified for different types of element, as follows:
20 N/mm2
30 N/mm2
40 N/mm2
reinforced concrete
post-tensioned prestressed concrete
pre-tensioned prestressed concrete
17Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The Code again gave a table of design strengths at different ages, but in the form of actual
strengths for a given concrete grade, rather than the percentage increases given in earlier
Codes. (The percentage increases were similar but the concrete strengths were rounded.)
The Code permitted a range of cement types, which did not include high alumina cement.
The Code specified the amount of anhydrous calcium chloride, i.e. the material containing
no water, stating that:
"In concrete containing embedded metal calcium chloride must not be added
in such proportion that the total from the admixture and the total from the
aggregates exceeds 1.5% by weight of cement. Calcium chloride should never
be used in prestressed concrete."
An amendment in May 1977 effectively outlawed the use of calcium chloride as an
accelerating admixture because:
"Experience shows that corrosion of prestressing tendons, reinforcement and
embedded metal usually results from the combination of factors including
excess addition of calcium chloride ... departure from specified mix proportions,
poor compaction, inadequate cover and poor detail design."
BS 8110, Structural use of concrete, 1985
Minimum strengths were not clearly stated in BS 8110, but by implication they may be
assumed to be as follows:
20 N/mm2
25 N/mm2
30 N/mm2
reinforced concrete
precast concrete
prestressed concrete (slightly lower than in CP 110)
Section 6, Concrete: materials, specification and construction, banned the use of calcium
chloride, stating that:
"Calcium chloride and chloride-based admixtures should never be added in
reinforced concrete, prestressed concrete and concrete containing embedded
metal."
It also placed a limit on the total chloride content in the mix from other sources.
Section 6 also gave guidance on avoiding alkali-silica reaction.
18Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
BS 8007, Code of practice for design of concrete structures for retaining aqueous
liquids, 1987
While it generally refers to BS 8110, Structural use of concrete, BS 8007 specified a 35 N/mm2
concrete with a minimum cement content of 325 kg/m3 (compared with 300 kg/m3 in
BS 8110) and a maximum water/cement ratio of 0.50 (compared with 0.55 in BS 8110),
which was classed as grade C35A.
The Code specified maximum cement contents for reinforced concrete of 400 kg/m3 of
ordinary Portland cement or cements containing ggbs or 450 kg/m3 for cements containing
fly ash. For prestressed concrete the quantities could be increased to 500 kg/m3 and
550 kg/m3 respectively.
4.3.2 Highway and railway
structures
The guidance for highway and railway structures has always been somewhat different
from that for buildings.
Ministry of Transport, 1945
Four nominal mixes were specified on the basis of cementfine aggregate:coarse aggregate
ratios by volume and also weight of cement (lb):fine aggregate (cu. ft):coarse aggregate
(cu. ft), with corresponding 28-day cube strengths as follows:
1:2:4
1:12/3:3V3
1:1i/2:3
1:1:2
112
112
112
112
21/2
2Vi
:17/s:
:VA
:5
2:41/6
21/2
2250
2580
2700
3600
psi
psi
psi
psi
(16 N/mm2)
(18 N/mm2)
(19 N/mm2)
(25 N/mm2)
Note that these are the same ratios as given in CP 114:1948 but the 28-day strengths are
somewhat lower. The details are also given in the Third Edition of Reinforced concrete
designers' handbook^.
Ministry of War Transport Memorandum 557, Bridge design and construction, 1945
(reprinted 1949)
Three nominal mixes were given on the basis of weight of cement (lb):fine aggregate (cu. ft):
coarse aggregate (cu. ft), with corresponding 28-day cube strengths as follows:
MixA
MixB
MixC
150:2:4
120:2:4
90:2:4
3600 psi (25 N/mm2)
3300 psi (23 N/mm2)
2850 psi (20 N/mm2)
These mixes were the same as Mixes II, III and IV for High Grade concrete in the 1934
Code of Practice for reinforced concrete, which was current at the time.
19Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Ministry of Transport, Specification for Road and Bridge Works (First Edition), 1951
A range of concrete Classes were given, specified on the basis of the maximum aggregate/
cement ratio, with the maximum water/cement ratio and the 28-day cube strength given
for the stronger mixes. For Classes A to C the maximum aggregate size was % inch (19 mm).
For Classes D and E the maximum aggregate size was 114 inches (38 mm), indicated by 1
after the letter, or 214 inches (64 mm), indicated by 2 after the letter. The values were as
follows:
5500 psi (38 N/mm2)
5000 psi (35 N/mm2)
4500 psi (31 N/mm2)
3200 psi (22 N/mm2)
Class AClass B
Class C
Class D1
Class D2
Class E1
Class E2
4.2:14.5:1
6:1
7:1
8.5:1
9:1
10:1
0.43
0.5
0.55
0.65
not specified
not specified
not specified
Recommended proportions of finexoarse material (in cu. ft) per 112 Ib of cement were
given for Classes D2, E1 and E2 for both angular and irregular aggregate.
For prestressed concrete, the Specification required a maximum water/cement ratio of
0.4 and a 28-day strength of 5500 psi (38 N/mm2). For piles, Class B was required.
Ministry of Transport, Specification for Road and Bridge Works (Second Edition), 1957
The same designations of concrete Classes were given, but the proportions and properties
were different; the 28-day strengths were significantly lower. The Classes were now specified
on the basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), for
both irregular and angular aggregates, with corresponding 28-day cube strengths. As
before, for Classes A to C the maximum aggregate size was % inch (19 mm). For Classes
D and E the maximum aggregate size was 114 inches (38 mm), indicated by 1 after the
letter, or 214 inches (64 mm), indicated by 2 after the letter.
For angular aggregate the values were as follows:
Class A
Class B
Class C
Class D1
Class D2
Class E1
Class E2
112:2:3
112:21/4:3
112:2V2:3V2
V\2AVA:6
112:414:7
112:51/4:7V2
0.5
0.55
0.6
0.65
0.65
not specified
not specified
3600 psi (25 N/mm2)
3300 psi (23 N/mm2)
2850 psi (20 N/mm2)
2400 psi (17 N/mm2)
2400 psi (17 N/mm2)
For irregular aggregate, the proportions were slightly different but the 28-day strengths
were the same.
20Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
The Specification mentions calcium chloride but gives no guidance on its use, simply
saying that it should be of a good industrial grade and from an approved source. The use
of high alumina cement was permitted, apparently without any restrictions.
Ministry of Transport Memorandum 785, Permissible working stresses in concrete
and reinforcing bars for highway bridges and structures, 1961
Three nominal mixes were specified on the basis of weight of cement (lb):fine aggregate
(cu. ft):coarse aggregate (cu. ft) as in Memorandum 557 but with increased 28-day cube
strengths, as follows:
• Mix A
• MixB
• MixC
150:2:4
120:2:4
90:2:4
4200 psi (29 N/mm2)
3750 psi (26 N/mm2)
3000 psi (21 N/mm2)
This would appear to be the only document that specified a standard amount of aggregate
and varied the amount of cement to give the various mixes; the general approach was to
specify varying amounts of aggregates to be used with a standard weight or volume of
cement.
Ministry of Transport, Specification for Road and Bridge Works (Third Edition), 1963
A range of concrete Classes with specified 28-day cube strengths were given. For Classes
A to E, the total volume of aggregate (cu. ft) per 112 Ib of cement was given; it was
suggested that the proportion of coarse:fine aggregate would normally be 2:1 but could
be varied between 11/2:1 and 3:1. Details were as follows:
Class A
Class B
Class C
Class D
Class E
Class X
Class Y
Class Z
112:472
112:55/8
112:71/2
112:972
112:10V4
Not specified
Not specified
Not specified
4200 psi
3750 psi
3000 psi
2400 psi
strength
7500 psi
6000 psi
4200 psi
(29 N/mm2)
(26 N/mm2)
(21 N/mm2)
(17 N/mm2)
not specified
(52 N/mm2)
(41 N/mm2)
(29 N/mm2)
In addition the maximum aggregate size was given. For example, D.IV2 indicated a 2400 psi
(17 N/mm2) concrete with a 11/2 inch (38 mm) maximum aggregate size.
Strangely, maximum water/cement ratios, which were given in the Second Edition, were
not given for Classes A to E in the Third Edition, the amount of water being simply limited to:
"that required to produce a dense concrete with sufficient workability to enable
it to be placed and compacted."
For Classes X to Z, which were 'special' concretes, the water/cement ratio was limited to 0.5.
21Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The guidance on calcium chloride and the use of high alumina cement was the same as
in the Second Edition. There was a general statement that:
"Admixtures shall not be used without the specific approval, in writing, of the
Engineer".
British Rail Midland Region, Drawing Office Handbook, circa 1960
Four nominal mixes were specified on the basis of cementfine aggregate:coarse aggregate
ratios by volume, with corresponding 28-day cube strengths, as follows:
Mix A
MixB
MixC
MixD
MixA1
1:11/z:3
1:2:4
1:3:6
1:4:8
not specified
4000 psi (28 N/mm2)
3000 psi (21 N/mm2)
1500 psi (10 N/mm2)
no specified strength
7000 psi (48 N/mm2) (for prestressed concrete)
British Rail Southern Region, Specification for Norwood High Street Bridge, 1968
This Specification gave various standard mixes as follows: S (standard mix), Y (contractor
designed mix), A-E (as CP 116), LWT (lightweight concrete) and RH (rapid hardening).
Note: It is not clear whether this was a standard Southern Region specification or whether it
was specific to this contract.
Ministry of Transport Memorandum 577/2, Reinforced concrete for highway
structures: materials, workmanship, design requirements and permissible stresses,
1968
The Memorandum listed four Classes of concrete, specified by their 28-day cube strengths,
as follows:
Class 7500
Class 6000
Class 4500
Class 3000
7500 psi (52 N/mm2)
6000 psi (41 N/mm2)
4500 psi (31 N/mm2)
3000 psi (21 N/mm2)
Minimum cement contents were given for the various maximum aggregate sizes and a
maximum cement content given for all mixes.
Technical Memorandum BE 10, Reinforced concrete for highway structures, 1968
BE 10 stated that concrete should be in accordance with Clause 1601 of the DOE Specification
and noted that Classes higher than 30 would not generally be required for reinforced
concrete. Tables in the Memorandum cover three Classes of concrete, namely 22.5 N/mm2,
30 N/mm2 and 37.5 N/mm2.
22Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
Technical Memorandum BE 20, Prestressed concrete for highway structures, 1969
Two classes were specified for prestressed concrete, Class 7500 (52 N/mm2) and Class 6000
(41 N/mm2). There was also an 'exceptional' class, Class 9000 (60 N/mm2), though the
Memorandum suggests that this should be avoided because of the difficulty of maintaining
the strength and because of the shrinkage associated with high cement contents.
BE 1/73: Reinforced concrete for highway structures and BE 2/73: Prestressed
concrete for highway structures, 1973
As in BE 10, BE 1/73 stated that concrete should be in accordance with Clause 1601 of the
DOE Specification and noted that classes higher than 30 would not generally be required
for reinforced concrete. Tables in the Memorandum again covered three Classes of
concrete, namely 22.5 N/mm2, 30 N/mm2 and 37.5 N/mm2. BE 2/73 noted that concrete
should generally be Class 52.5 or Class 45. Higher strengths could only be used when
economically justifiable and account was taken of the possible difficulty in maintaining
the strength.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the Highways Agency until the
publication of BD 17/83.)
In BS 5400:1978, and subsequent versions, design was based on specified concrete strength
grades, from 20 N/mm2 up to 60 N/mm2. By implication in various tables, minimum
concrete grades were specified for different types of element: 20 N/mm2 for reinforced
concrete, 30 N/mm2 for post-tensioned prestressed concrete and 40 N/mm2 for pre-
tensioned prestressed concrete.
The Code gave the same increase in design strengths at different ages as in CP 110.
The requirements for materials and workmanship were covered in BS 5400 Part 7,
Specification for materials and workmanship, concrete, reinforcement and prestressing
tendons. The use of calcium chloride was totally banned by the clause stating that:
"Calcium chloride or admixtures containing calcium chloride shall not be used
in structural concrete containing reinforcement, prestressing or other embedded
metal."
BE 1/73: Reinforced concrete for highway structures (including Amendment No. 1),
1979
The strength classes were the same as in the 1973 versions of the document, namely
22.5 N/mm2, 30 N/mm2 and 37.5 N/mm2.
23Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BD 17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
This adopted the concrete strength Grades in BS 5400 (20 N/mm2 up to 60 N/mm2).
However, a restriction was placed on the use of enhanced strengths at ages greater than
28 days, with a footnote to the table stating that:
"Increased strengths at these ages should be used only if it has been
demonstrated to the satisfaction of the Engineer that the materials to be used
are capable of producing these higher strengths."
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
The revised version of the Code contained the same restrictions on the use of enhanced
concrete strengths.
4.4 Design exposureconditions
Early codes paid little attention to the exposure conditions and hence to the durability of
concrete.
Mix proportions were specified on the basis of the quantities of cement and aggregate
required, such as 1:2:4 (cementfine aggregate:coarse aggregate) by volume. While it was
appreciated in the 1920s that the strength of concrete was influenced by the water/cement
ratio, there was little guidance on ratios actually required. For example, Everyday uses of
Portland cement^, published in 1921, stated that:
"The quantity of water should be just sufficient to bring water to the surface
after thorough ramming ....The concrete should be sufficiently wet... to
ensure it passing between the reinforcing bars and thoroughly surrounding
every portion of the steel."
Similarly, there was little guidance on the required cover to the reinforcement. The long-
term effects of some materials, such as calcium chloride accelerator or high alumina
cement (see Section 4.2.2), were not initially appreciated. Similarly, alkali-silica reaction
(see Section 7.1) only manifested itself fairly recently. Code requirements have been slowly
refined as experience of the materials' use in service developed.
24Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
4.4.1 Buildings and other
structuresCode of Practice for reinforced concrete, 1934
The Handbook to the Code'13) did discuss problems associated with sulfates and acidic
water (suggesting the use of high alumina cement or Portland-blastfurnace cement). The
authors also discussed problems associated with milk and other liquids. However, there
was no relevant guidance in the Code, which did not mention exposure, simply saying
that the cover to all reinforcement should be at least Vz inch (13 mm) or the diameter of
the bar, whichever was the greater. For main bars in beams and columns the minimum
cover was increased to 1 inch (25 mm) or the diameter of the bar, whichever was the
greater.
Code of practice for the design and construction of reinforced concrete structures for
the storage of liquids, 1938
The specified minimum cover was generally 1 inch (25 mm) or the bar diameter, when
using the 112:2:4 concrete. This was increased to VA inches (32 mm) or the bar diameter
when the weaker 112:21 :̂5 concrete was used. Where the surface was exposed to water
of a corrosive nature, the minimum cover was increased to 2 inches (51 mm).
CP 114, Structural use of normal reinforced concrete in buildings, 1948
The Code specified covers for only two environments, namely 'internal' and 'external,
buried or aggressive'. Minimum covers were the same as in the 1934 Code except that
the cover to the main reinforcement in columns was increased to VA inches (38 mm).
For all external work and for work against earth faces (and for internal work in aggressive
conditions) all covers were to be increased by Vz inch (13 mm). There would appear to be
no link between the required concrete properties and the exposure.
CP 114, The structural use of reinforced concrete in buildings, 1957
The Code specified covers for the same two environments asCP 114:1948, with neither
the Code nor the Handbook'14' making any link between the required concrete grade and
durability.
CP 115, The structural use of prestressed concrete in buildings, 1959
The Code made no mention of requirement to control the water/cement ratio, only
saying that:
"It is most important to maintain the water/cement ratio constant."
The two exposure conditions and the cover requirements were as in CP 114:1957.
CP 2007, Design and construction of reinforced and prestressed concrete structures
for the storage of water and other aqueous liquids, 1960
The guidance inCP 2007 was generally in line with CP 114 and CP 115, but the Code did
give guidance on 'injurious soils' saying that:
"The use of sulfate-resisting cement... may not afford a complete safeguard;
an isolating coat of bituminous or other suitable composition may be required."
25Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
London Building (Construction) By-laws, 1964
The covers given in the by-laws would appear to be largely related to fire resistance.
However, a minimum cover of V/z inches (38 mm) was required where reinforced
concrete was "exposed to the weather or is in contact with a source of damp".
CP 116, The structural use of precast concrete, 1965
This would appear to be the first Code to specifically consider durability in detail. The two
exposure conditions in CP 114 and CP 115, 'internal' and 'external' were subdivided as follows:
• Internal Non-corrosive
Corrosive, e.g. roof units subject to corrosion
Severely corrosive, e.g. roof units subject to corrosive fumes
• External Sheltered in non-industrial areas
Sheltered in industrial areas or work against non-sulfate bearing earth faces
Exposed in non-industrial areas
Exposed in industrial areas or subject to mild sulfate attack
Exposed to sea water or weak chemical attack
Subject to salt used for de-icing.
The minimum cover appropriate to each grade of concrete was specified for the various
exposure conditions. Minimum cement contents were given for reinforced concrete and
for prestressed concrete, but no values were given for water content.
CP 110, Code of practice for the structural use of concrete, 1972
The Code specified five exposure conditions, namely 'mild', 'moderate', 'severe', 'very severe'
and 'subject to de-icing salts'. Concrete grades and covers were specified for the various
exposure conditions and, for the first time, the Code gave maximum water/cement ratios.
BS 8110, Structural use of concrete, 1985
Again five exposure conditions were specified, now termed 'mild', 'moderate', 'severe',
'very severe' and 'extreme'. Maximum water/cement ratios, minimum cement contents
and minimum concrete grades were given for all five exposure conditions. The cover to
the reinforcement was related to the exposure condition and the quality of the concrete,
rather than just the grade as in CP 110.
BS 5328, Concrete, Parti: Guide to specifying concrete, which was developed from BS 8110
Section 6, Concrete: materials, specification and construction, was introduced in 1991. From
that date, BS 8110 referred to BS 5328 (and later to its replacement BS 8500) for guidance
on cover and concrete quality requirements for the different exposure conditions.
26Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
4.4.2 Bridges As with buildings, early design Standards for bridges paid little attention to durability. The
guidance has become more detailed over the years.
Ministry of War Transport Memorandum 557, Bridge design and construction, 1945
(reprinted 1949)
The Memorandum does not specifically mention exposure conditions. For retaining walls,
a minimum cover of VA inches (38 mm) was specified. For beams 1 inch (25 mm) was
specified, increasing to VA inches (38 mm) if the structure was 'exposed to sea action'.
Ministry of Transport Memorandum 577/2, Reinforced concrete for highway
structures: materials, workmanship, design requirements and permissible stresses,
1968
The Memorandum identified six different conditions of exposure, ranging from 'Not exposed
to atmosphere' to 'Exposed to sea water'. Minimum covers were specified for three Classes
of concrete, namely 3000 psi (21 N/mm2), 4500 psi (31 N/mm2) and 6000 psi (37.5 N/mm2).
For concrete in contact with the ground, minimum cement contents and maximum
water/cement ratios were given for various cement types and sulfate concentrations.
Technical Memorandum BE 10: Reinforced concrete for highway structures, 1968
BE 10 identified the same six exposure conditions as in Memorandum 577/2. Minimum
covers were specified for three Classes of concrete, namely 22.5 N/mm2, 30 N/mm2 and
37.5 N/mm2. For concrete in contact with the ground, minimum cement contents and
maximum water/cement ratios were again given for various cement types and sulfate
concentrations.
Technical Memorandum BE 20: Prestressed concrete for highway structures, 1969
BE 20 gave no guidance on aspects such as exposure and cover.
Technical Memorandum BE 1/73: Reinforced concrete highway structures and BE
2/73: Prestressed concrete highway structures, 1973
BE 1/73 identified the same six exposure conditions as BE 10, with the same minimum
covers for the same three Classes of concrete. The requirements for concrete in contact
with the ground were also unaltered. For determining the minimum cover, BE 2/73 referred
to BE 1/73, which was somewhat illogical as the concrete strengths in BE 2/73 were
normally required to be 52.5 N/mm2 or 45 N/mm2, which were higher than those covered
by BE 1/73. An additional requirement was that the cover to any duct should be at least
50 mm.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the Highways Agency until the
publication of BD 17/83.)
The Code defined three exposure conditions, namely 'moderate', 'severe' and 'very severe',
with associated nominal covers, minimum concrete grades and design crack widths. The
three exposure conditions were each illustrated by two or more examples.
27Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Technical Memorandum BE 1/73: Reinforced concrete highway structures (including
Amendment No. 1), 1979
The Amendment reduced the exposure conditions from six to four, as follows:
• Concrete exposed to abrasive action of sea water or water with pH < 4.5
• Concrete exposed to de-icing salts or sea water spray
• Concrete exposed to driving rain or alternate wetting and drying or freezing while wet
• All other surfaces
Minimum covers were given for the three grades of concrete, namely 22.5 N/mm2,
30 N/mm2 and 37.5 N/mm2.
BD 17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
The Standard amended the three exposure conditions in BS 5400, dividing 'very severe'
into 'very severe' and 'extreme'. The nominal covers for all exposure conditions were
increased, generally by 5mm though in some cases by 10 mm.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
The Code adopted the four exposure conditions in BD 17/83, namely 'moderate', 'severe',
'very severe' and 'extreme', along with the associated nominal covers and associated
minimum concrete grades.
BD 24/84, Design of concrete bridges, Use of BS 5400: Part 4:1984,1984
This document implemented the use of BS 5400: Part 4 with minor typographical
amendments, none of which dealt with the exposure conditions.
28
4.5 Reinforcement andprestressing
Just as the Codes and Standards for design have developed over the years, so the types of
reinforcement have changed and their properties have improved. In addition the methods of
identifying the different materials on reinforcement drawings have changed. The information
is summarised in the sections below and in Appendix A of Standard method ofdetailing
structural concrete®**.
Many different types of prestressing system have been available over the years, particularly
prior to the introduction of British Standards. Appendix III of Historic concrete -background
to appraisal1-391 reviews the various early types of proprietary reinforcement, from the 19th
century to about the First World War.
Knowledge of these various developments is clearly essential when assessing existing
structures. Because of the variability of reinforcement, it is advisable to determine the
properties of the reinforcement by testing samples removed from the structures, particularly
when considering structures built prior to about 1960.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
4.5.1 Detailing symbols
Table 6Detailing symbols.
The symbols used on reinforcement drawings to indicate the type of reinforcement have
been specified in various Standards over the years, as shown in Table 6.
4.5.2 Imperial bar sizes Before metrication, the generally available size range for both round and square (or
chamfered square) bars was VA inch (6 mm) to VA inches (38 mm) in the following sizes:
Imperial bar sizes
A Vis inch (5 mm) square area bar was also available for a time as were round area bars in
sizes up to 21/4 inches (57 mm).
It should be noted that in American practice the bar designation number refers to the
number of eighths of an inch in the nominal diameter, so a number 6 bar has a nominal
diameter of 3A inch (19 mm). It would appear that the system was occasionally used for
projects in the UK.
Prior to 1964 most square and chamfered square bars were of square area so that nominal
1 inch bars had an area of 1 sq. inch (645 mm2). During the late 1960s a transition to round
areas occurred with nominal 1 inch bars having an area of 0.785 sq. inches (510 mm2).
The nominal size range for twin twisted bars was from VA inch (6 mm) to VA inches (32 mm)
in the increments shown above. In addition smaller twin twisted bars were produced from
12,10, 8, 6 and 5 gauge wires (Standard Wire Gauge or SWG sizes) having diameters of
2.64, 3.4, 4.06, 4.88 and 5.38 mm respectively.
The nominal size of a twin twisted bar referred to the size of one bar in the pair and a
nominal 1 inch bar provided a steel area of 1.571 sq. inches (1010 mm2).
29Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
4.5.3 Yield stresses
Table 7Specified yield stresses.
The specified yield stresses in the Standards for reinforcement have varied over the years.
Some values are given in Table 7.
It should be noted that BD 21, The assessment of highway bridges and structures^ states that:
"Pre-1961 reinforcement may be assumed to have a characteristic strength
not greater than 230 N/mm2. For reinforcement after this date, the strength
shall be taken as specified in the appropriate design codes for the period for
high yield and mild steel bars."
4 . 5 . 4 Fabric In the past wire fabric was produced from twisted square sections and twin twistedmaterial as well as plain round drawn wire and ribbed bar. The wire was often measuredin SWG (Standard Wire Gauge) sizes whereas the fabric itself was usually described interms of its mesh type and weight per square yard. It is not practical to summarise therange or describe the expanded metal fabric, which was also used. Identification of thematerial used will require reference to contemporary literature, such as the relevant issuesof Specification^.
4.5.5 Early reinforcement
systems
In the early days of reinforced concrete (from the 1890s to 1920s), a number of proprietaryreinforcement systems were used, see Bussell'42'. Many of these were developed in France,Germany and the USA and imported into the UK. Details can be found in Appendix III ofHistoric concrete - background to appraisal^, which also covers various patented floorsystems.
30
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Development of materials standards 4
The importance of the bond between the reinforcement and the concrete was identified
at an early stage. Most of the systems are recognisable as variations on modern bars, with
a wide variety of surface characteristics. For example, the Hennebique System used plain
round (mild steel) bars with flattened 'fish tail' ends for anchorage.
A very unusual product was the Kahn bar, which consisted of a square section with two
projecting strips on diagonally opposite corners. These were slit along short lengths and
bent up to form shear reinforcement. In the USA and UK the system was adopted by the
Trussed Concrete Steel Company, which became abbreviated toTruscon.
4.5.6 Early prestressing
systems
The commercial use of prestressing in the UK began just before the Second World War.
During and just after the war it was used to overcome material shortages. The early designs
were mainly by refugee European engineers and the systems manufactured were not British.
After about 1950 various British systems were developed.
Walley'43! reviewed the early history of prestressed concrete. He discussed the materials
used and the systems for pre- and post-tensioning in use, particularly in the early days,
along with various applications.
Detailed information on systems available between 1940 and 1985 may be found in CIRIA
Report 106, Post tensioning systems for concrete in the UK: 1940-1985^4\ A number of
the systems described ceased to be used after about the 1960s. Thus, when assessing an
existing structure, identification of the type of anchorage used may give an indication of
the age of the structure.
Structural precast concrete by Glover'45' gives details of the strands, anchorages and other
components of various post-tensioning systems, as follows:
• BBRV
• CCL
• Dywidag
• Freyssinet
• Gifford-Burrow
• Gifford-Udall
• Macalloy
• Magnel-Blaton
• PSC
• PZ
• SDL
31
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
5. Design
A paper by Bussell'46) looked at the development of the understanding of reinforced concrete
behaviour, textbooks, codes and standards up to the publication of CP 114 in 1948.
Subsequent developments were reviewed briefly.
The Reinforced Concrete Designers' Handbook^ by Charles Reynolds has been one of the
standard guidance documents since it was first published in 1932. It has been constantly
revised and updated as Codes and Standards have developed. (Later editions were
additionally authored by JC Steedman.) Reynolds was also the author of Practical examples
of reinforced concrete design^. First published in 1938, designs were in accordance with
the 1934 Code and the 1938 London County Council By-laws. In 1952, Reynolds produced
Examples of the design of reinforced concrete buildings^ in line with CP 114:1948. The
Second edition, published in 1959, was updated in accordance with the 1957 version of
CP 114. In 1962, he published Basic reinforced concrete design, a textbook for students and
engineers^. Guidance on the use of CP 110 was given by Allen in Reinforced concrete
design to CP 110 simply explained^.
The following sections are not intended to be a summary of the relevant Codes but rather to
simply pick out their salient points and identify areas in which there have been significant
changes with successive Codes. Specific guidance on the design of water-retaining structures
is outlined in Section 6.3.
5.1 L o a d i n g Table 8 lists the dates of the introduction of the main loading Codes for buildings. In
addition there were local loading requirements, such as the London County Council (LCC)
Regulations for Ferroconcrete. Office loadings appear to have been largely unchanged
over the years. In the 1934 Code, office loading was given as 80 lbs/ft2, which is equal to
about 3.8 kN/m2, compared with the 4 kN/m2 that is often used these days. Mitchell's
Building Construction (1930) makes reference to the LCC Regulations for Ferroconcrete,
which required 100 lbs/ft2, or 4.8 kN/m2. Details of the design loadings for offices and
other buildings are given in the relevant Editions of Reynolds'19'.
32
Table 8Loading Codes for buildings.
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Table 9Highway loading Standards.
Design 5
Dawe'50) has reviewed the development of rules for traffic loading from their introduction
in the early 1920s up to the present day. Table 9 lists some of the key stages in this
development but there were many interim guidance notes produced by the Ministry of
Transport (laterthe Department of Transport), as detailed in Dawe's book.
Date Standard
Summaries of the loadings required for railway bridges are given in the relevant editions
of Reynolds!19).
5.2 Reinforcement designstrengths
Table 10Design stresses for reinforcement.
The reinforcement stresses to be used in design, as specified in the Code current at the
time, have changed over the years as shown in Table 10.
Standard Reinforcement
33
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
5.3 Bending and axial load In the early Codes, design was on the basis of elastic behaviour underworking loads, with
limiting 'permissible' stresses in the concrete and steel. The 1957 version of CP 114
introduced an alternative approach, namely load-factor design. Limit state design was
adopted by CP 110 in 1972, and has been used in all subsequent Codes.
5.3.1 Buildings Reinforced Concrete Designers' Handbook (First Edition), 1932(19)
Working stresses were given for six Mixes A to F, as shown below.
• Mix A
• MixB
• MixC
• MixD
• MixE
• MixF
1:3:6
VIVz-.S
1:2:4
I.VA3V3
V.VA3
1:1:2
400 psi (2.8 N/mm2)
500 psi (3.5 N/mm2)
700 psi (4.8 N/mm2)
750 psi (5.2 N/mm2)
800 psi (5.5 N/mm2)
875 psi (6.0 N/mm2)
London County Council By-laws, 1932
The by-laws used Mixes C to F as above, but with slightly reduced stresses, as follows:
1:2:4 600 psi (4.1 N/mm2)
650 psi (4.5 N/mm2)
675 psi (4.7 N/mm2)
750 psi (5.2 N/mm2)
V.VA3
1:1:2
Code of Practice for reinforced concrete, 1934Design was on the basis of elastic behaviour under working loads limited by 'permissible
stresses' in the concrete and steel. In bending, the permissible stress in the concrete was
one-third of the 28-day cube strength, namely for Ordinary Grade concrete:
Mix
Mix
Mix
Mix
I
II
III
IV
1:1:2
1:1.2:
1:1.5:
1:2:4
2.4
3
975
925
850
750
psi
psi
psi
psi
(6.7
(6.4
(5.9
(5.2
N/mm2)
N/mm2)
N/mm2)
N/mm2)
and for High Grade concrete:
Mix I
Mix II
Mix III
Mix IV
1:1:2
1:1.2:2.4
1:1.5:3
1:2:4
1250 psi (8.6 N/mm2)
1200 psi (8.3 N/mm2)
1100 psi (7.6 N/mm2)
950 psi (6.6 N/mm2)
Design equations were given for axially loaded short columns and for long columns.The
Handbook'13' gave tables for the permissible loads on square and octagonal columns for a
range of concrete mixes and amounts of reinforcement.
34Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Design 5
London County Council By-laws, 1938
The permissible stresses for the six mixes, specified on the basis of weight of cement (Ib):
fine aggregate (cu. ft):coarse aggregate (cu. ft), were as follows:
Mix I
Mix II
Mix III
MixIA
Mix HA
Mix MIA
112:11/4:2l/2112:17/s:33/4
112:214:5
112:11/4:2V2
112:17/s:33/4
112:2y2:5
975 psi (6.7 N/mm2)
850 psi (5.9 N/mm2)
750 psi (5.2 N/mm2)
1250 psi (8.5 N/mm2)
1100 psi (7.6 N/mm2)
950 psi (6.6 N/mm2)
This information was also given in Reinforced concrete simply explained^2®.
CP 114, Structural use of normal reinforced concrete in buildings, 1948
As in the 1934 Code, design was on the basis of elastic behaviour underworking loads
limited by 'permissible stresses' in the concrete and steel. These permissible stresses in
the concrete were again one-third of the corresponding 28-day cube strength, i.e.:
1:1:2 1500 psi (10.4 N/mm2)
V.V/r.3 1250 psi (8.6 N/mm2)
1:2:4 1000 psi (6.9 N/mm2)
CP 114, Structural use of reinforced concrete in buildings, 1957
In the 1957 version of CP 114, design could be either by the established permissible stress
approach or by the load-factor approach. The latter was carried out at the ultimate load,
taken as being twice the working load on the member. In the calculation of the ultimate
moment capacity for beams and slabs, the compressive stress in the concrete was limited
to two-thirds of the cube strength and the compressive stress block was limited to half the
effective depth. The reinforcement was assumed to be acting at its yield (or proof) stress.
For the design of columns, the permissible stress approach could be used for both short
and long columns. The Handbook'14' gave tabulated values for the permissible load on
short square columns with helical reinforcement for a range of column dimensions and
concrete grades. Guidance was also given for the design of short columns using the load-
factor approach. This again limited the concrete stress to two-thirds of the cube strength
but here the cube strength was to be taken as only 76% of the actual cube strength (i.e.
the stress was limited to 50% of the actual cube strength). The Handbook gave a design
chart for eccentrically loaded short columns using the loaded-factor method.
At the time, cements were such that concrete gained strength more slowly. The Code
recognised that there would be a significant gain in strength after the statutory 28 days
(see Section 4.3.1) and indicated that, where the member being designed would not
receive its full design load until a later age, the design stresses could be increased by an
appropriate amount. Some consultants regularly allowed for about a 20% increase in
concrete strength, particularly when designing columns as this would lead to a significant
reduction in the amount of reinforcement required.
35Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
CP 115, The structural use of prestressed concrete in buildings, 1959
Design of prestressed beams was on the basis of permissible stresses at working loads
followed by calculation of the ultimate strength.
London Building (Construction) By-laws, 1964
The permissible stresses in bending for the six mixes were slightly changed from those in
the 1938 By-laws, as follows:
Grade I
Grade II
Grade III
Grade IA
Grade IIA
Grade IIIA
970 psi (6.7 N/mm2)
850 psi (5.9 N/mm2)
750 psi (5.2 N/mm2)
1500 psi (10.4 N/mrrv
1250 psi (8.6 N/mm2)
1000 psi (6.9 N/mm2)
CP 110, The structural use of concrete, 1972
The Code was published in three parts. The main body of the guidance was given in Parti,
Design, materials and workmanship. Design charts for beams and columns were given in
Part 2, Design charts for singly reinforced beams, doubly reinforced beams and rectangular
columns, and Part 3, Design charts for circular columns and prestressed beams, all based on
the assumptions in Part 1. CP 110 introduced the concept of limit state design, with partial
safety factors applied both to the loads (or 'actions' in Eurocode parlance) and to the
material properties. This approach has been used by all subsequent codes.
Three characteristic strengths were specified for high yield reinforcement, namely 410 N/mm2,
425 N/mm2 and 460 N/mm2, depending on the bar diameter and the method of manu-
facture. A partial safety factor of 1.15 was applied to the characteristic steel strength.
The resistance to bending could be determined using the rectangular-parabolic concrete
stress block. Alternatively, an equivalent rectangular stress block could be used equal to
0.4/cu over the full depth of the compression zone.
BS 8110, Structural use of concrete, 1985
The Code was published in three parts, as follows:
• Pa rt 1: Code of practice for design and construction
• Part 2: Code of practice for special circumstances
B Part 3: Design charts for singly reinforced beams, doubly reinforced beams and
rectangular columns.
Design charts for circular columns were published by Batchelor and Beeby of the BCA in
Unlike CP 110, only a single characteristic strength was specified for high yield reinforcement,
namely 460 N/mm2. A partial safety factor of 1.15 was applied to the characteristic steel
strength.
36Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Design 5
While the rectangular-parabolic stress curve for concrete was the same as that given in
CP110, the simplified rectangular stress block was modified to 0.45/cu applied over a depth
of 0.9x, where x was the effective depth.
5.3.2 Bridges The design approaches for bridges mirrored those for buildings, moving from permissible
stress design to limit state design, though the latter was adopted more slowly.
Ministry of War Transport Memorandum 557, Bridge design and construction, 1945
(reprinted 1949)
The permissible stresses in bending were given for three concrete Mixes, specified on the
basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), as follows:
Mix A
MixB
MixC
150:2:4
120:2:4
90:2:4
1200 psi (8.3 N/mm2)
1100 psi (7.6 N/mm2)
950 psi (6.6 N/mm2)
Permissible stresses in direct loading were 80% of those in bending.
Ministry of Transport Memorandum 785, Permissible working stresses in concrete
and reinforcing bars for highway bridges and structures, 1961
The permissible stresses in bending were again given for three concrete Mixes, specified
on the basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), as in
Memorandum 557, but increase slightly follows:
Mix A 150:2:4
MixB 120:2:4
MixC 90:2:4
1400 psi (9.7 N/mm2)
1250 psi (8.6 N/mm2)
1000 psi (6.9 N/mm2)
Permissible stresses in direct loading were 76% of those in bending.
Ministry of Transport Memorandum 577/2, Reinforced concrete for highway
structures: materials, workmanship, design requirements and permissible stresses,
1968
The elastic design approach was based on that in CP 114. The permissible stresses in
bending were one-third of the 28-day concrete strength and in direct compression, the
stresses were approximately one-quarter of the 28-day strength. Stresses were given for
three Classes of concrete, as follows:
Class 6000 Bending 2000 psi (13.8 N/mm2)
Class 4500 Bending 1500 psi (10.4 N/mm2)
Class 3000 Bending 1000 psi (6.9 N/mm2)
Direct 1500 psi (10.4 N/mm2)
Direct 1140 psi (7.9 N/mm2)
Direct 760 psi (5.2 N/mm2)
37
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BE 10: Reinforced concrete for highway structures, 1968
As in Memorandum 577/2, the elastic design approach was based on that in CP 114. The
permissible stresses in bending were again one-third of the 28-day concrete strength and
in direct compression the stresses were one-quarter of the 28-day strength. Stresses were
now given for three Classes of concrete, as follows:
ClassClass
Class
37.530
22.5
Bending 12.
Bending 10
Bending 7.5
5 N/mm2
N/mm2
N/mm2
Direct 9.5
Direct 7.6
Direct 5.7
N/mm2
N/mm2
N/mm2
BE 1/73: Reinforced concrete for highway structures, 1973
The elastic design approach was based on that in CP 114 and CP 116, with the same
permissible stresses as in BE 10. In addition to the elastic design approach, the ultimate
moment of resistance of reinforced concrete parapet walls and bridge supports was
determined using a rectangular-parabolic stress-strain curve for the concrete with a
maximum compressive stress of 0.44uw. Alternatively a rectangular stress block 0.4uw
over the full depth of the neutral axis could be used. The tensile stress in the reinforcement
was "derived from the appropriate stress-strain curves supplied by the manufacturer".
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the Highways Agency until the
publication of BD 17/83.)
The Code was closely based on CP 110:1972, with the same specified characteristic strengths
for the reinforcement (410 N/mm2, 425 N/mm2 and 460 N/mm2) and the same approach
for the design of members in bending. The equivalent rectangular stress block was taken
as 0.4/cu over the full depth of the compression zone. BS 5400 referenced the design charts
in Parts 2 and 3 of CP 110.
BE 1/73: Reinforced concrete for highway structures (including Amendment No. 1),
1979
The design approach was unchanged from the 1973 version.
BD 17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
Although the Standard contained a significant number of amendments, these were largely
matters of clarification and did not affect the approach to design for flexure. One minor
change was that only two specified characteristic strengths were given the reinforcement,
namely 425 N/mm2 and 460 N/mm2.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
Most of the editorial changes identified in BD 17/83 were incorporated in the 1984
edition of BS 5400: Part 4.
38Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BD 24/84, Design of concrete bridges, Use of BS 5400: Part 4:1984,1984
This document implemented the use of BS 5400: Part 4 with minor typographical
amendments.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1990
Again there were no significant differences in the design approach, with the equivalent
rectangular stress block equal to 0.4/cu over the full depth of the compression zone.
However, reference was now made to the design charts in Part 3 of BS 8110:1985.
5.4 Shear and punching in
reinforced concreteThe approaches to designing for shear and for punching have changed significantly over
the years, as outlined in the following sections.
5.4.1 Buildings Reinforced Concrete Designers' Handbook (First Edition), 1932
Permissible shear stresses were given for the six Mixes A to F, as follows:
Mix A
MixB
MixC
MixD
MixE
MixF
1:3:6
1:2y2:5
1:2:4
1:1%:3V3
1:iy2;3
1:1:2
40 psi (0.28 N/mm2)
50 psi (0.35 N/mm2)
60 psi (0.41 N/mm2)
63 psi (0.43 N/mm2)
65 psi (0.45 N/mm2)
70 psi (0.48 N/mm2)
Code of Practice for reinforced concrete, 1934
The applied shear stress on the cross-section, s, was determined on the basis of a uniform
distribution as follows:
s = S/ba
where
S =
b =
a =
applied shear force
breadth of the section
lever arm.
Permissible shear stresses were given for Ordinary Grade concrete (see Section 4.3.1), as
follows:
• Mix I 1:1:2 98 psi (0.68 N/mm2)
a Mix II 1:1.2:2.4 93 psi (0.64 N/mm2)
• Mix III 1:1.5:3 85 psi (0.59 N/mm2)
B Mix IV 1:2:4 75 psi (0.52 N/mm2)
39Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
And for High Grade concrete as follows:
• Mix
• Mix
• Mix
• Mix
1
II
III
IV
1:1:
1:1.
1:1.
1:2
2
2:2.4
5:3
:4
125 psi (0.86 N/mm2)
120 psi (0.83 N/mm2)
110 psi (0.76 N/mm2)
95 psi (0.66 N/mm2)
The permissible shear stress for Special Grade concrete was one-thirtieth of the 28-day
cube strength (the same proportion as for the other Grades) but not more than 150 psi
(1.04 N/mm2).
Where the applied shear stress exceeded the permissible stress, shear reinforcement was
required to carry all the shear force. However, the Code required that the shear stress
should not exceed four times the permissible value. The spacing of the stirrups should not
exceed the lever arm. There was no requirement to provide a minimum amount of shear
reinforcement in members.
For the punching shear resistance of slabs, the Code identified two critical sections, namely
at a distance of one effective depth from the column head and at the perimeter of the
drop if used. The shear stresses should not exceed the permissible values given above; no
guidance was given on the provision of shear reinforcement.
London County Council By-laws, 1938
The permissible shear stresses for the six mixes, specified on the basis of weight of
cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), were as follows:
Mix
Mix
Mix
Mix
Mix
Mix
III
III
IA
HA
IIIA
11Z:11/4:21/2
112:17/s:33/4
112:21/2:5
-]-\2:VA:2V2
112:17/s:33/4
112:2y2:5
98 psi (0.68 N/mm2)
85 psi (0.59 N/mm2)
75 psi (0.52 N/mm2)
125 psi (0.86 N/mm2)
110 psi (0.76 N/mm2)
95 psi (0.66 N/mm2)
CP114, Structural use of normal reinforced concrete in buildings, 1948
The approach was the same as in the 1934 Code except that the permissible stresses in
shear were increased slightly, with the following values for the three concrete grades:
1:1:2
1:iy2:3
1:2:4
130 psi (0.90 N/mm2)
115 psi (0.79 N/mm2)
100 psi (0.69 N/mm2)
Again, if the permissible stress was exceeded, all the shear had to be carried on shear
reinforcement. The spacing of the stirrups should not exceed the lever arm. There was no
requirement for minimum shear reinforcement.
40Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The approach for the punching shear resistance of slabs was modified somewhat from
that in the 1934 Code. The critical perimeters were now at a distance of half the slab
depth from the face of the column or, if column heads or drops were used, at a distance
of half the total depth from the column head or drop. The shear stresses on the critical
perimeters should not exceed the permissible values. Again there was no guidance on the
provision of shear reinforcement.
CP 114.102, Floors and roofs of flat slab construction, 1950
The design for shear and for punching shear were the same as in CP 114:1948.
CP 114, Structural use of reinforced concrete in buildings, 1957
The general guidance was the same as in CP 114:1948, although the symbols used were
different. As before, where the applied shear exceeded the capacity of the concrete, all
the shear force had to be carried on shear reinforcement. There was no requirement for
minimum shear reinforcement.
London Building (Construction) By-laws, 1964
The permissible shear stresses for the six mixes were slightly changed from those in the
1938 by-laws, as follows:
Grade I
Grade II
Grade III
Grade IA
Grade IIA
Grade IIIA
97 psi (0.67 N/mm2)
85 psi (0.59 N/mm2)
75 psi (0.52 N/mm2)
130 psi (0.90 N/mm2)
115 psi (0.79 N/mm2)
100 psi (0.69 N/mm2)
CP 114, Structural use of reinforced concrete in buildings - metric version, 1969
Permissible stresses in shear were given for the specified nominal mixes as follows:
1:1:2
1:2:4
0.9 N/mm2
0.8 N/mm2
0.7 N/mm2
The design approach was the same as in the previous versions of CP 114 except that there was
now a requirement for nominal shear reinforcement when the applied shear did not exceed
the shear capacity. The required cross-sectional area of the nominal shear reinforcement
was 0.15% of the horizontal area of the concrete at the section under consideration (or
0.12% if high yield steel was used). Nominal shear reinforcement was not required for
slabs, footings, bases, pile caps and members of minor importance. However, the Code
did warn that:
"A conservative approach should be used when calculating the resistance to
shear of members without shear reinforcement, as recent research has indicated
that, in some circumstances, the margin of safety may be lower than desirable."
41Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
CP110, The structural use of concrete, 1972
The approach to designing for shear was radically different from that in previous Codes.
For beams, the shear stress on the cross-section, v, was determined from:
v=V/bd
where
V = shear force due to ultimate loads
b = breadth of the section
d = effective depth.
The allowable shear stress on the concrete section was a function of the concrete grade
(specified values of 20 N/mm2, 25 N/mm2, 30 N/mm2 and 40 N/mm2 or more) and the
amount of tension reinforcement in the cross-section.
If the applied shear stress exceeded the allowable shear stress, shear reinforcement,
designed on the basis of a simple 45° truss, was provided to carry the balance, i.e.:
Total shear capacity = capacity of the concrete plus the capacity of the links.
A minimum area of links was required for beams, equal to 0.12% of the horizontal area
when using high-yield steel and 0.2% with mild steel. (The requirement for high-yield steel
was the same as in CP 114:1969. However, that for mild steel was a significant increase.)
Minimum links were not requiredfor members of minor importance or where the maximum
applied shear stress was less than half the allowable value.
Values were given for the maximum shear stress that could be applied to the cross-section,
which were a function only of the concrete grade, ranging from 3.35 N/mm2 for grade 20
concrete to 4.75 N/mm2 for 40 or more (i.e. about 0.75V/cu where/cu was the characteristic
concrete cube strength). For lower reinforcement percentages these maximum values
were significantly greater than the four times allowed byCP 114.
The Code introduced an allowance for increased shear capacity for beams loaded close to
the support. Where the distance from the support, av, was less than 2c/ (where d equalled
the effective depth) the shear capacity of the concrete could be multiplied by a factor of
2c//av, provided it did not exceed the maximum concrete capacity.
For solid slabs, the maximum shear stress due to ultimate loads was not to exceed half the
appropriate value for a beam. Guidance was given on designing for punching shear, which
was calculated on a critical perimeter at a distance of 1.5 times the overall slab thickness, h,
from the face of the loaded area, resulting in a square/rectangular perimeter with rounded
corners. The shear stress on the perimeter was checked using the same approach as for
beams but with addition of a factor that was related to the depth of the slab; higher shear
stresses were permitted for shallower slabs, with a multiplier ranging from 1.0 for slabs
250 mm or more thick to 1.2 for 150 mm or less. (In 1976, the multipliers were amended to
1.0 for slabs 300 mm or more thick and 1.3 for 150 mm or less.)
42Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
If the shear stress on the perimeter at 1.5/) exceeded the allowable value, shear reinforcement
was provided on the perimeter and a similar amount on a perimeter at a distance 0.75/?
inside it. Stresses were determined on perimeters progressively 0.75/) out from the critical
perimeter until the shear stress could be carried by the concrete alone.
The maximum shear stress was limited to half the maximum for beams.
BS 8110, Structural use of concrete, 1985
The basic approach to the design of the shear capacity of beams was similar to that in CP 110:
1972. One significant difference was that the depth factor applied to slabs, which increased
the shear capacity of shallower slabs, was extended to beams as well. The design concrete
shear stress, vc, was expressed both in tabular form and also as the following equation:
vc=0.79[100AJbvd)033 ifJZ5)03S {400/d)025/y
where
As = area of tensile reinforcement
bv = section breadth
d = effective depth
/cu = characteristic cube strength of concrete, which should not be taken as greater
than 40
y = partial safety factor taken as 1.25.
Rather than specifying a minimum area of shear links as in CP 110:1972, the requirement
was that they should provide a shear capacity of 0.4 N/mm2, although the resulting area
was similar.
The maximum shear stress was limited to 0.8V/cu but not more than 5 N/mm2, which
was a slight increase on the values in CP 110:1972.
The approach to punching shear was also similar, but the perimeter was now taken as
rectangular (rather than rectangular with rounded corners) at1.5offrom the loaded area.
The maximum design shear stress was limited, as for beams, to 0.8V/cu but not more than
5 N/mm2. The amount of reinforcement required was to be distributed evenly around the
zone on at least two perimeters; note that this differed from the guidance in CP 110. (An
amendment in March 1993 identified two separate situations, namely v< 1.6vc and 1.6v
<v< 2vc, effectively imposing an upper limit of 2vc.)
5.4.2 Bridges The development of the design approaches for shear and punching in bridges mirrored
those for buildings.
43Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Ministry of War Transport Memorandum 557, Bridge design and construction, 1945
(reprinted 1949)
The permissible shear stresses in bending were given for three concrete mixes, specified on
the basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), as follows:
MixA 150:2:4
MixB 120:2:4
MixC 90:2:4
120 psi (0.83 N/mm2)
110 psi (0.76 N/mm2)
95 psi (0.66 N/mm2)
Maximum shear stresses were 2Vz times the permissible values, i.e. 300 psi (2.1 N/mm2),
275 psi (1.9 N/mm2) and 238 psi (1.6 N/mm2) respectively. Where the shear stress exceeded
the permissible value, shear reinforcement was required to carry all the shear force. The
permissible stress in the steel was 18,000 psi (125 N/mm2). Minimum shear reinforcement
was required in beams to carry two-thirds of the permissible stress, i.e. 80 psi (0.6 N/mm2),
73 psi (0.5 N/mm2) or 63 psi (0.4 N/mm2), depending on the mix. There was no requirement
for minimum shear reinforcement in slabs.
Ministry of Transport Memorandum 785, Permissible working stresses in concrete
and reinforcing bars for highway bridges and structures, 1961
The permissible shear stresses were again given for three concrete mixes, specified on the
basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), as in
Memorandum 557, but increased slightly as follows:
MixA 150:2:4
MixB 120:2:4
MixC 90:2:4
125 psi (0.86 N/mm2)
115 psi (0.79 N/mm2)
100 psi (0.69 N/mm2)
Ministry of Transport Memorandum 577/2, Reinforced concrete for highway
structures: materials, workmanship, design requirements and permissible stresses,
1968
The approach to the design for shear was the same as in CP114. Permissible shear stresses
were given for two Classes of concrete, as follows:
Class 4500
Class 3000
130 psi (0.90 N/mm2)
100 psi (0.69 N/mm2)
It was noted that when Class 6000 concrete was used, the permissible shear stress for
Class 4500 concrete should be used.
As in CP 114, when the applied shear force exceeded the permissible value, all the shear force
had to be carried on shear reinforcement. The maximum shear stress should not exceed four
times the permissible value. The permissible stresses in shear reinforcement were as follows:
• Mild steel 20,000 psi (140 N/mm2) for bar sizes up to VA inches (38 mm)
18,000 psi (125 N/mm2) for bars sizes over VA inches
B High yield steel 25,000 psi (175 N/mm2)
44Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Design 5
There is no mention of stirrup spacing. However, as Memorandum 577/2 refers back to
CP 114, presumably the spacing should not exceed the lever arm.
Where the applied shear stress did not exceed the permissible value, there was a require-
ment for minimum links to carry two-thirds of the permissible stress. Minimum links were
not required in slabs.
There was no guidance on designing for punching shear.
BE 10: Reinforced concrete for highway structures, 1968
Basically the approach to designing for shear was the same as in Memorandum 577/2
(i.e. permissible stress approach) but there were some adjustments to bring it more into
line with CP 110 (limit state design). Shear stresses were determined assuming a uniform
stress throughout the lever arm depth. Permissible shear stresses for reinforced concrete,
except for solid slabs without shear reinforcement, were given for two Classes of concrete,
as follows:
• Class 30 0.87 N/mm2
• Class 22.5 0.72 N/mm2
It was noted that when Class 37.5 concrete was used, the permissible shear stress for
Class 30 concrete should be used.
As in 577/2, when the applied shear force exceeded the permissible value, all the shear
force had to be carried on shear reinforcement. The maximum shear stress should not
exceed four times the permissible value. The permissible stresses in shear reinforcement
were as follows:
• Mild steel 140 N/mm2 for bar sizes up to 40 mm
125 N/mm2 for bars sizes over 40 mm
• High-yield steel 175 N/mm2
The stirrup spacing should, presumably, not exceed the lever arm.
Again, where the applied shear stress did not exceed the permissible value, minimum links
were required to carry two-thirds of the permissible stress and there was no guidance on
designing for punching shear.
BE 1/73: Reinforced concrete for highway structures, 1973
The basic approach to designing for shear in beams was the same as in BE 10, but there
were some additional clauses, which brought the document more into line with CP 110.
An increased shear capacity was permitted for beams loaded close to the support. Where
the distance from the support, a, was less than 2d (where d equalled the effective depth),
the shear capacity of the concrete could be multiplied by a factor of Zd/a, provided it did .
not exceed the maximum concrete capacity. The increased shear capacity could not exceed
twice the basic permissible stress.
45Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
For solid slabs without shear reinforcement, the permissible shear stresses were related to
the Class of concrete (22.5 N/mm2, 30 N/mm2 and 37.5 N/mm2) and the percentage of
flexural tensile steel (<0.25 to >3.0). (BE 1/73 notes that the values given were based on
those on CP 110, but multiplied by Vi-5 to remove the partial safety factor and multiplied
by 2 so that they are directly applicable to unfactored working stress design.)
For shallow slabs, the permissible shear stress was modified by a multiplier which ranged
from 1.0 for slabs 250 mm or more thick and 1.2 for 150 mm or less. Again, the increased
shear capacity could not exceed twice the basic permissible stress.
For punching shear, the critical section was taken at a distance of 1.5/7 from the face of
the column, where h was the overall slab depth, on a rectangular perimeter with rounded
corners.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the Highways Agency until the
publication of BD 17/83.)
The approach was basically the same as in CP 110:1972. A minimum area of links was
required for beams, equal to 0.12% of the horizontal area when using high yield steel and
0.2% with mild steel. Minimum links were not required for members of minor importance
or where the maximum applied shear stress was less than half the allowable value.
The approach for punching shear was the same as in CP 110:1972, with the 1976 amendment
to the multipliers taking account of increased shear capacity for shallower slabs (multiplier
| s o f 1.0 for slabs >300 mm thick ranging up to 1.3 for 150 mm or less). The necessary
amount of shear reinforcement was provided on the perimeter under consideration and
an equal amount on a perimeter 0.75/7 inside it, where h was the overall slab depth.
BE 1/73: Reinforced concrete for highway structures (including Amendment No. 1),
1979
The design approach for shear was the same as in the 1973 version.
BD 17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
There were a number of editorial changes but the basic approach to the design for shear
in beams was the same as in BD 5400:1978. One significant change introduced by the
Standard was that the table of values for the multiplier | s was extended so that the shear
of members deeper than 500 mm was now reduced, with those for shallower members
being unchanged (i.e. multiplier of 0.71 for slabs >2000 mm thick ranging up to 1.3 for
150 mm or less). The multiplier was now applied to beams as well as slabs.
46Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BD 17/83 introduced a check on the area of longitudinal reinforcement in the tensile
zone,As, such that:
V vs " (d-dc/Z)
where
A^= cross-sectional area of two legs of a link
d = effective depth
dc = depth of concrete in compression.
The Standard introduced significant modifications to the design approach for punching
shear. The critical perimeter was now located at 1.5c/, where cfwas the effective depth of
the slab, rather than at 1.5/J. While the guidance in BS 5400 was limited to loads applied
near the middle of a slab, the Standard introduced modified perimeters for loads near the
edge of a slab or the corner of a cantilever slab. Guidance was also given on the shear
capacity of voided slabs, which was not covered in BS 5400.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
The approach to the design of the shear capacity of beams was similar to that in previous
versions of BS 5400 Part 4, with the incorporation of the majority of the amendments
listed in BD 17/83. The design concrete shear stress, vc, was again expressed in tabular
form but was also given by the following equation:
where
k=
bv=
/ c u=
y =
(/cu/25)°3
area of tensile reinforcement
section breadth
characteristic cube strength of concrete, which should not be taken as greater
than 40
partial safety factor taken as 1.25.
Neither the table nor the equation for vc took any account of the depth of the member. As
before, this was covered by the multiplier £s. As in BD 17/83, the values of |s, which was
given as equal to (500/d)°2S, increased the shear capacity of shallow members and reduced
the capacity of deep members. The tabulated values of £s were the same as in BD 17/83
but slightly rounded (e.g. 0.84 became 0.85).
The maximum shear stress was limited to 0.75V/cu but not more than 4.75 N/mm2, i.e.
the same values as previously although the table was removed.
47Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Minimum links to carry a shear stress of 0.4 N/mm2 were required for all beams, unlike
BS 5400: Part 4:1984 where they were not required for members of minor importance or
where the maximum applied shear stress was less than half the allowable value.
The check on the area of longitudinal reinforcement in the tensile zone,/\s, was modified to:
As>V/{Z(0.87fy)}
where
/ = characteristic strength of the reinforcement
V = shear force due to ultimate loads at the section under consideration.
As in BD 17/83, the critical punching shear perimeter was taken at a distance of 1.5c/from
the loaded area and perimeters were given for loads near the edge of a slab or the corner
of a cantilever as well as near the middle of a slab.
BD 24/84, Design of concrete bridges, Use of BS 5400: Part 4:1984,1984
This document implemented the use of BS 5400: Part 4 with minor typographical
amendments.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1990
The approach to the design of the shear capacity of beams was the same as in BS 5400:
1984, except that/\s was now defined as additional longitudinal reinforcement in the
tensile zone in excess of that required to carry bending.
5.5 Shear in prestressed
concrete
As with reinforced concrete, the requirements for shear in prestressed concrete have
developed over the years.
5.5.1 Buildings CP 115, The structural use of prestressed concrete in buildings, 1959
The Code gave guidance on design for shear in uncracked sections. The principal tensile
stress due to prestress, bending and shear at working loads was compared with limiting
values of 125 psi (0.86 N/mm2), 150 psi (1.04 N/mm2) and 175 psi (1.21 N/mm2) for
specified works cube strengths of 4500 psi (31 N/mm2), 6000 psi (41 N/mm2) and 7500 psi
(52 N/mm2) respectively. When these stresses were exceeded, shear reinforcement was
required, with the proportion of the stress to be carried by the reinforcement depending
on the level of stress; when the shear stress exceeded 1.5 times the limiting value, all the
shear was carried by the reinforcement. A check was also required at ultimate load.
48
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Design 5
CP 110, The structural use of concrete, 1972
The code required design for shear at the ultimate limit state only, giving guidance for beams
both for sections uncracked and cracked in flexure. The background giving the derivation
of the equations in the Code was given in some detail in the Handbook to the Code'14'.
For uncracked sections the approach was similar to that in CP 115:1959, with a limit
being placed on the principal tensile stress at the centroidal axis,/ , equal to 0.24V/cu,
where/cu was the characteristic concrete cube strength. The shear capacity of the
uncracked section, Vco, was given by:
where
/q>= compressive stress at the centroid due to prestress.
An allowance could be made for the effects of any inclined or vertical prestress at the
section under consideration.
CP 110:1972 introduced an equation for the ultimate shear resistance of a section cracked
in flexure, Vcr, as follows:
V =
where
d =
Mn =
1 -0 .55-^ -/ppu
V
effective depth to the centroid of the tendons
moment necessary to produce zero stress in the concrete at the level of the
centroid of the tendons
effective prestress in the tendons after all losses
characteristic strength of the tendons/P.
/ pu
V, M = shear force, bending moment at the section considered
vc = shear capacity .
Minimum shear reinforcement equivalent to a shear stress of 0.4 N/mm2 was required
for all beams, unless lightly loaded or deemed to be of minor importance. Designed shear
reinforcement followed the same approach as for reinforced beams with the exception
that a closer spacing of links was required when the applied shear force exceeded 1.8 times
the capacity of the cracked concrete cross-section. The maximum shear stress was again
0.75V/cu but the table of values was from grade 30 to 60 and over.
BS 8110, Structural use of concrete, 1985
The approach in the Code to the shear resistance of uncracked sections was the same as
in CP 110:1972.
The equation for sections cracked in flexure was also the same as in CP 110:1972 but the
term Mo was now defined as the moment to cause zero stress in the concrete at the
extreme tension fibre rather than at the level of the centroid of the tendons.
49Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
5.5.2 Bridges The equations used for the design for shear in prestressed concrete bridges were generally
similar to those for buildings.
BE 20: Prestressed concrete for highway structures, 1969
The Memorandum gave no guidance on design for shear, so presumably design was in
accordance with CP 115:1959.
BE 2/73: Prestressed concrete highway structures, 1973
The shear capacity of the uncracked section, Qcw, was based on limiting the tensile stress
at the centroid, as in CP 115 and CP 110. However, the equation was a modified version of
that in CP 110, as follows:
Qcw = 0.67k/V(f t2
where
/ = compressive stress at the centroid due to prestress
/ t = principal tensile stress = 0.294Vuw
d = overall depth of the section
uw= cube strength.
The shear capacity of sections cracked in flexure, Qcm, was calculated from:
Qcm = 0 .045W> w +{Q/M)Mc
where
M = moment at section due to ultimate load
Q = shear force at section due to ultimate load
Mc= cracking moment at the section considered= (o.45V«w+/ep)//y
where
fe = stress due to prestress only at the extreme tensile fibre, at a distance y from the
centroid and / is the second moment of area.
There was a requirement that the spacing of the stirrups along a member should not exceed
the effective depth. When the applied shear exceeded 1.8 times the shear capacity of the
section (the lesser of Qcw and Qcm), the maximum spacing was reduced to half the effective
depth.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the Highways Agency until the
publication of BD 17/83.)
For uncracked sections the approach was modified from that in BE 2/73 and was the same
as in CP 110:1972, with a limit being placed on the principal tensile stress at the centroidal
axis,/t, equal to 0.24V/cu, where /cu was the characteristic concrete cube strength.
50Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The shear capacity of uncracked sections, Vco, was given by:
where
/ = compressive stress at the centroid due to prestress.
However, the guidance on sections cracked in flexure was significantly different from that
in CP110. For Class 1 structures (no tensile stresses permitted) and Class 2 structures
(tensile stresses permitted but no visible cracking) the ultimate shear resistance, Vcr, was
calculated from:
Va = 0.037W/cu + {Mt/M)V
where
M = moment at section due to ultimate load
Vt = shear force at section due to ultimate load
Mt = cracking moment at the section considered
= (0.37V/cu + 0.8/pt)//y
where
/ 1 = stress due to prestress only at the tensile fibre distancey from the centroid
which has a second moment of inertia /.
For Class 3 structures (tensile stresses permitted but crack widths limited) Vcr was
calculated from:
Vcr=[\-0.55(fpJp]vcbd + M0
where
Mo= moment necessary to cause zero stress in the concrete at depth d
/ P e = effective prestress in the tendon after all losses have occurred
/ = characteristic strength of the tendon.
An expression was given for determining the effective prestress when there was both
stressed and unstressed reinforcement at the section being considered.
For sections uncracked in flexure, 0.8 times the vertical component of any inclined pre-
stressing force could be added to Vco. No such allowance was made for sections cracked
in flexure.
BD17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
The approach was the same as in BS 5400:1978 but the equations and definitions were
modified slightly to clarify that stresses due to prestress were after losses had taken place
and appropriate safety factors, as follows:
51Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BD 17/83 introduced a clause dealing with the calculation of shear in the transmission
zone of pre-tensioned members, which was taken as the greater of the shear capacity of
the reinforced section (ignoring the area of the tendons) and the capacity of the cracked
or uncracked prestressed section, assuming a linear increase in the stress in the tendons.
The expressions for Vcr were unaltered but Mt was now given by:
with the requirement that the appropriate partial safety factor should be applied t o / t .
With inclined tendons, the shear capacity of uncracked sections could again be modified
but the factor of 0.8 applied to the vertical component was replaced by the appropriate
partial safety factor. Again, no allowance was made for sections cracked in flexure.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
It would appear that all the modifications given in BD 17/83 were included in the 1984
version of BS 5400: Part 4.
BD 24/84, Design of concrete bridges, Use of BS 5400: Part 4:1984,1984
This document implemented the use of BS 5400: Part 4 with minor typographical
amendments.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1990
There were no significant changes from the 1984 version of BS 5400 Part 4.
5.6 Fire resistance Early concrete was considered to be fireproof and early proprietary designs, prior to the
introduction of national Codes, were marketed as such. More precise design guidance for
fire resistance has gradually developed with the introduction of successive Codes.
London County Council Reinforced Concrete Regulations: 1915
Columns were required to have a cover of VA inches (38 mm) or the bardiameter if this
was greater.
Code of Practice for reinforced concrete, 1934
There was no mention of fire resistance in the design sections of the Code, although
Appendix 1, General building clauses, states that:
52
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
"For all buildings which are required to be of a specified degree of fire resistance,
the grade of fire resistance of the elements of structure and the incombustible
and non-inflammable properties of materials shall be stipulated in accordance
with British standard specification of fire resistance, incombustibility and non-
inflammability of building materials and structures No. 476."
BS 476, Fire tests on building materials and structures, was first issued in 1932; it was
revised in 1953 and subsequently split into a number of Parts.
CP 114, Structural use of normal reinforced concrete in buildings, 1948
The Code stated that:
"Consideration should be given to the fire resistance of reinforced concrete
members to see that they provide the grade of fire resistance for the particular
occupancy and size of a building or compartment as laid down in the Code of
Functional Requirements, Chapter IV, Precaution against fire."
It considered the performance of two types of aggregate in fire, namely Class 1 (limestone,
brick and artificial aggregates such as foamed slag) and Class 2 (all natural aggregates
other than limestone). A table gave the thickness of walls and floors required for various
fire periods, as follows:
• Walls:
• Thickness ranging from 3 inches (75 mm) for a Vz hour period to 9 inches (230 mm)
for 6 hours with Class 2 aggregates.
• Thickness ranging from 3 inches (75 mm) for a Vfe hour period to 8 inches (200 mm)
for 6 hours with Class 1 aggregates.
• Solid slabs:
• Thickness ranging from 3Vz inches (90 mm) for a Vz hour period to 7 inches (180 mm)
for 6 hours (aggregate Class not specified).
• Hollow tile floors:
• Thickness of concrete slab ranging from 2V2 inches (65 mm) for a Vz hour period to
6 inches (150 mm) for 6 hours with Class 2 aggregates.
The only mention of the required cover to the reinforcement was for hollow tile floors,
where V2 inch (13 mm) was specified for Vz hours, % inch (19 mm) for 1 or 2 hours, and
1 inch (25 mm) for 4 hours. (Minimum covers for durability were specified elsewhere.)
53Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The guidance for columns was less explicit, based on the adequacy of specified column
sizes, as follows:
• Small columns (10 to 12 inches across, 250 to 305 mm across):
• Class 2 aggregate 'satisfactory' for resistance of 1 hour.
• Class 1 aggregate 'desirable' for resistance of 2 hours.
• Larger columns:
• Any aggregate may be used to obtain resistance of 2 hours.
• Class 1 aggregate (or a mesh placed centrally in the cover) can be used to obtain a
resistance of 4 hours.
CP 114, Structural use of reinforced concrete in buildings, 1957
The main body of the Code states that:
"Statutory requirements for fire resistance of buildings, expressed in terms of
periods of fire resistance of various elements of structure, when tested in
accordance with BS 476, Fire tests on building materials and structures, as laid
down in the London building by-laws and in the building by-laws of those
local authorities who have adopted one of the models issued by the Ministry
of Housing and Local Government or the Department of Health for Scotland."
An appendix gives tables of fire resistance for various types of elements (similar to those for
Class 2 aggregates in CP 114:1948), with the addition of the specification of the minimum
cover to the reinforcement for all members. The tables may be summarised as follows:
• Walls:
• Minimum cover 1 inch (25 mm).
• Minimum thickness ranging from 3 inches (75 mm) for a Vz hour period to 9 inches
(230 mm) for 6 hours.
a Floors:
• Minimum thickness ranging from 2Vz inches (65 mm) or 3Vi inches (90 mm),
depending of the form of construction, fora Vz hour period to 5 inches or 6 inches
for 4 hours.
• Minimum cover Vz inch (13 mm) for periods less than 2 hours and 1 inch (25 mm)
for 4 hours.
• Columns:
• Minimum thickness ranging from 6 inches (150 mm) for a Vz hour period to 18 inches
(460 mm) for 6 hours (with the provision for the thicknesses for 4 hours and 2 hours
to be reduced if mesh is placed in the cover).
• Beams:
• Minimum cover ranging from Vz inch (13 mm) for a Vz hour period to 2Vi inches
(65 mm) for 4 hours.
It was noted that the values were conservative when limestone was used for the coarse
aggregate, and reduced values for the minimum column were suggested.
54Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Design 5
London Building (Constructional) By-laws, 1964
Schedule VI of the By-laws gives minimum thicknesses for walls, stairs, columns and beams
for periods ranging from 1 hour to 4 hours, with provision for reduced thicknesses when
elements are covered with plaster. Also given are minimum covers to the reinforcement,
which, confusingly, are stated as being to the main reinforcement in some tables and
simply 'cover to reinforcement' elsewhere.
CP 116, The structural use of precast concrete, 1965
The Code suggested that the fire resistance of precast elements should be determined in
accordance with Part 1 of BS 476, Fire tests on building materials and structures. In the
absence of results from actual fire test, the notional fire resistance could be obtained from
tables of covers and minimum dimensions, which were very similar to those in CP 114:1957
The Code also gave information on the additional protection provided by different types
of plaster.
CP 110, The structural use of concrete, 1972
The guidance in CP 110 was significantly more detailed than that in CP 114, although many of
the dimensions were similar. Additional information on the behaviour of concrete elements
in fire was given in the Handbook'16'. Covers were defined as average values rather than
minimum values, considering only the tension reinforcement. The contents of the various
tables can be summarised as follows:
• Beams:
• For siliceous aggregates, average cover from 15 mm fora Vz hour period to 65 mm
for 4 hours, with minimum thickness of 80 mm and 280 mm respectively.
• For lightweight aggregates, average cover from 15 mm for a Vz hour period to 50 mm
for 4 hours, with minimum thicknesses of 80 mm and 250 mm respectively.
• Floors (both reinforced and prestressed):
• A range of average covers and overall dimensions depending on the form of
construction (e.g. solid slab, cored slab, hollow box, ribbed floor with hollow infill
blocks, inverted channels).
• Columns (without additional protection):
• For siliceous aggregates, minimum thickness ranging from 150 mm for Vz hour
period to 450 mm for 4 hours with all faces exposed, and 75 mm to 180 mm with
only one face exposed.
• For limestone aggregate or lightweight aggregate, minimum thickness ranging from
150 mm for Vz hour period to 300 mm for 4 hours with all faces exposed.
• Walls (with at least 1% of vertical reinforcement, exposed on one side only):
• For siliceous aggregates, minimum thickness ranging from 75 mm for Vz hour
period to 180 mm for 4 hours.
Additional information was given regarding the effects of protective layers, such as plaster.
55
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BS 8110, Structural use of concrete, 1985
The basic approach to the design for fire resistance in BS 8110:1985 differed from that in
CP 110:1972 in various respects. Nominal covers were specified to all reinforcement
including links rather than the average cover to the tensile reinforcement. The differing
behaviour of various types of natural aggregates was combined into 'dense' concrete,
although lightweight concrete was still included. Nominal covers for various elements
(for dense concrete) were given in Part 1, Code of practice for design and construction, as
follows:
• Beams:
• Simply supported: 20 mm for a 0.5 hour period to 70 mm for 4 hours.
• Continuous: 20 mm for a 0.5 hour period to 50 mm for 4 hours.
• Floors:
• Simply supported: 20 mm for a 0.5 hour period to 55 mm for 4 hours.
• Continuous: 20 mm for a 0.5 hour period to 45 mm for 4 hours.
• Ribs:
• Simply supported: 20 mm for a 0.5 hour period to 65 mm for 4 hours.
• Continuous: 20 mm for a 0.5 hour period to 55 mm for 4 hours.
• Columns:
• Simply supported: 20 mm for a 0.5 hour period to 25 mm for 4 hours.
Part 1 also gave minimum dimensions for members for fire resistances from 0.5 to 4 hours.
Section 4 of Part 2, Code of practice for special circumstances, gave significantly more
details on designing for fire resistance and included curves of the variation of concrete and
steel strengths with temperature. It should be noted that in Part 2, 'cover' was defined as
being to the main reinforcement rather than to all reinforcement as in Parti.
5.7 Bond and anchorage As with other aspects of design, the checks for the bond between the reinforcement and
the concrete have moved from permissible stresses underworking loads in the early Codes
to ultimate limit state design in more modern Codes.
5.7.1 Buildings Code of Practice for reinforced concrete, 1934
Permissible bond stresses were given for Ordinary Grade concrete (see Section 4.3.1), as
follows:
123 psi (0.85 N/mm2)
118 psi (0.81 N/mm2)
110 psi (0.76 N/mm2)
100 psi (0.69 N/mm2)
Mix IMix II
Mix III
Mix IV
1:1:21:1.2:2.4
1:1.5:3
1:2:4
56Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
and for High Grade concrete as follows:
Mix
Mix
Mix
Mix
1II
III
IV
11
1
1
:1:2:1.2:
:1.5:
:2:4
2.4
3
150 psi (1.04 N/mm2)
145 psi (1.00 N/mm2)
135 psi (0.93 N/mm2)
120 psi (0.83 N/mm2)
The permissible bond stress for Special Grade concrete was one-thirtieth of the 28-day
cube strength plus 25 psi (the same proportion as for the other Grades) but not more
than 150 psi (1.04 N/mm2).
The local bond stress, sh, was determined from:
sb = S/ao
where
5 = total shear across the section
a = lever arm
o = sum of the perimeters of the tensile reinforcement.
sb was limited to twice the permissible bond stress.
The required anchorage lengths (using smooth reinforcing bars) were determined considering
the actual tension in the bar and assuming a uniform bond stress along the anchorage
not exceeding the permissible value.
London County Council By-laws, 1938
The permissible bond stress for the six mixes, specified on the basis of weight of cement (Ib):
fine aggregate (cu. ft):coarse aggregate (cu. ft), was as follows:
123 psi (0.83 N/mm2)
110 psi (0.76 N/mm2)
100 psi (0.69 N/mm2)
150 psi (1.04 N/mm2)
135 psi (0.93 N/mm2)
120 psi (0.83 N/mm2)
This information is also given in Reinforced concrete simply explained^.
CP 114, Structural use of normal reinforced concrete in buildings, 1948
The same approach was adopted as in the 1934 Code, except that the permissible average
bond stresses (i.e. anchorage bond stresses) and local bond stresses were stated for each
of the nominal mixes as follows:
• Mix• Mix
• Mix
• Mix
• Mix
• Mix
III
III
IA
IIA
IIIA
112:1V4:21/2112:17s:33/4
112:272:5
112:1V4:21/2
112:178:33/4
112:272:5
1:1:2
1:172:3
1:2:4
Average 150 psi (1.04 N/mm2)
Average 135 psi (0.93 N/mm2)
Average 120 psi (0.83 N/mm2)
Local 220 psi (1.52 N/mm2)
Local 200 psi (1.38 N/mm2)
Local 180 psi (1.24 N/mm2)
57Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
CP 114, Structural use of reinforced concrete in buildings, 1957
The Code used the same approach and the same permissible stresses as in CP 114:1948.
London Building (Construction) By-laws, 1964
The By-laws gave permissible bond stresses (for both average and local bond), as follows:
Average bond
Grade I 116 psi (0.80 N/mm2)
Grade II 102 psi (0.70 N/mm2)
Grade III 90 psi (0.62 N/mm2)
Grade IA 150 psi (1.04 N/mm2)
Grade IIA 135 psi (0.93 N/mm2)
Grade IIIA 120 psi (0.83 N/mm2)
Local bond
175 psi (1.21 N/mm2)
153 psi (1.06 N/mm2)
135 psi (0.93 N/mm2)
220 psi (1.52 N/mm2)
200 psi (1.38 N/mm2)
180 psi (1.24 N/mm2)
CP 110, The structural use of concrete, 1972
The Code used a similar approach to that in CP 114:1957 (although the notation was changed)
but the local and anchorage bond stresses were now at the ultimate limit state. Values
were now given for both plain and deformed bars for concrete grades 20, 25, 30 and >40.
Two types of deformed bar were identified in an appendix to the Code, namely Type 1,
twisted bar, and Type 2, ribbed bar, with bond stresses being increased by 30% forType 2.
BS 8110, Structural use of concrete, 1985
Anchorage bond stress, fbu, was determined from:
with tabulated values of the coefficient /? that depended on the type of bar and the
direction of loading. There would appear to be no limit applied to/cu in the equation, but
the table of anchorage bond lengths as multiples of bar size only gave values for concrete
strengths 25, 30, 35 and 40.
There was no longer a specific check for local bond stresses.
5.7.2 Bridges The treatment of bond in the design of bridges was similar to that for buildings.
Ministry of War Transport Memorandum 557, Bridge design and construction, 1945
(reprinted 1949)
The permissible bond stresses in bending were given for three concrete mixes, specified on
the basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), as follows:
• MixA 150:2:4 145 psi (1.00 N/mm2)
• Mix B 120:2:4 135 psi (0.93 N/mm2)
• MixC 90:2:4 120 psi (0.83 N/mm2)
Unlike later highway guidance, the Memorandum did not distinguish between average
and local bond stresses.
58Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Ministry of Transport Memorandum 785, Permissible working stresses in concrete
and reinforcing bars for highway bridges and structures, 1961
The permissible bond stresses were again given for three concrete mixes, specified on the
basis of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft), with the
same values for average bond as in Memorandum 557, but with the addition of local bond
stresses, as follows:
Mix A
MixB
MixC
150:2
120:2
90:2:-
:4
:4
A
Average bond
145 psi (1.00 N/mm2)
135 psi (0.93 N/mm2)
120 psi (0.83 N/mm2)
Local bond
210 psi (1.45
200 psi (1.38
180 psi (1.24
N/mm2)
N/mm2)
N/mm2)
These values could be increased by 25% when cold-twisted or deformed bars were used.
Ministry of Transport Memorandum 577/2, Reinforced concrete for highway
structures: materials, workmanship, design requirements and permissible stresses,
1968
The Memorandum gave average and local permissible bond stresses for plain bars under
HA loading for two classes of concrete as follows:
Class 4500
Class 3000
Average bond
150 psi (1.04 N/mm2)
120 psi (0.83 N/mm2)
Local bond
220 psi (1.52 N/mm2)
180 psi (1.24 N/mm2)
For deformed bars, the permissible stresses were increased by 40%. When Class 6000
concrete was used, bond stresses were limited to those for Class 4500. A 25% overstress
was permitted under HB loading.
BE 10, Reinforced concrete for highway structures, 1968
The permissible bond stresses for plain bars under HA loading were similar to those in
577/2 but rationalised slightly as follows:
Class 30
Class 22.5
Average bond1.00 N/mm2
0.85 N/mm2
Local bond1.47 N/mm2
1.27 N/mm2
For deformed bars, the permissible stresses were again increased by 40%. When Class 37.5
concrete was used, bond stresses were limited to those for Class 30. A 25% overstress was
permitted under HB loading.
BE 1/73: Reinforced concrete for highway structures, 1973
The average and local permissible bond stresses were the same as in BE 10, but various
overstresses were permitted under different loading combinations.
59Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the HighwaysAgency until the
publication of BD17/83.)
Ultimate local and anchorage bond stresses were given for both plain and deformed bars for
concrete grades 20, 25, 30 and >40. The stresses were the same as those in CP 110:1972,
with values given for different types of deformed bars, namely Type 1 (twisted) and Type 2
(ribbed).
BE 1/73: Reinforced concrete for highway structures (including Amendment No. 1),
1979
The bond stresses were the same as in BE 10 and in BE 1/73:1973, except that the 40%
increase for deformed bars was modified to 25% forType 1 deformed bars and by 40%
for Type 2 deformed bars.
BD 17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
The ultimate local and anchorage bond stresses were unaltered from those in BS 5400:1978.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
The ultimate local and anchorage bond stresses were the same as in BS 5400:1978.
BD 24/84, Design of concrete bridges, Use of BS 5400: Part 4:1984,1984
This document implemented the use of BS 5400: Part 4 with minor typographical
amendments.
5 . 8 S e r v i c e a b i l i t y Because spans were relatively limited, early codes were mainly concerned with strength
rather than serviceability. Guidance on span/depth ratios was introduced in 1957 and
methods for calculating crack widths in 1972.
5.8.1 Buildings 1934: Code of Practice for reinforced concrete
The Code gave no guidance on serviceability, presumably because spans were relatively
short and hence deflections and cracking were not likely to be a problem.
CP 114, Structural use of normal reinforced concrete in buildings, 1948
The Code noted that:
"Reinforced concrete subject to bending action in a building should possess
adequate stiffness to prevent such deflection or deformation as might impair
the strength or efficiency of the structure, or produce cracks in finishes or in
superimposed partitions, etc."
However it gave no guidance as to how this was to be achieved.
60Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
CP 114, Structural use of reinforced concrete in buildings, 1957
The Code gave the same general guidance but introduced maximum span/depth ratios
for beams and slabs, based on the overall depth. For beams the ratios were:
Simply supported
Continuous
Cantilever
20
25
10
The Handbook'14' pointed out that the values were based on experience with stress of
18,000 psi (125 N/mm2) in the reinforcement. Higher stresses were permitted by the
Code and hence the Handbook suggested that the ratios should be reduced, although it
did not give any further guidance.
There would appear to be no specific mention of the control of cracking in the Code.
However, there was a requirement for a minimum amount of reinforcement in solid
slabs, namely 0.15% of the gross cross-sectional area of the concrete in both directions.
In addition, the spacing of the main reinforcement was not to exceed three times the
effective depth of the slab and spacing of the distribution reinforcement was not to
exceed five times the effective depth.
London Building (Constructional) By-laws, 1964
The by-laws used the same span/depth ratios (based on overall member depth) as CP 114:
1957.
CP 110, The structural use of concrete, 1972
The Code indicated that deflections should be limited to span/250 to avoid damage to
partitions, etc. Span/depth ratios, now based on the effective depth rather than the overall
depth, for beam spans less than 10 m were limited to:
Simply supported
Continuous
Cantilever
20
26
7
An additional table gave span/depth ratios for simply supported and continuous beams
for spans between 10 m and 20 m. Further clauses and tables gave modification factors
to account for the amount of tension and compression reinforcement present.
CP 110:1972 would appear to be the first Code to mention cracking in reinforced and
prestressed concrete, saying that:
"Cracking of concrete should not adversely affect the appearance or durability
of the structure."
61Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
It suggested the following as 'reasonable' limits:
• Reinforced concrete
• 0.3 mm or 0.004 times the cover to the main reinforcement for structures in 'very
severe' environments.
• Prestressed concrete
• Class 1 - No tensile stresses
• Class 2 -Tensile stresses but no visible cracking
• Class 3 - 0.1 mm in 'very severe' environments and 0.2 mm elsewhere.
Minimum areas of main reinforcement were specified for beams and slabs, 0.15% £>tdwhen
using high-yield reinforcement and 0.25% btd when using mild steel reinforcement where
btwasthe breadth of the section and dthe effective depth. Minimum areas of secondary
reinforcement were 0.12% btd and 0.15% btd respectively.
The Code suggested that the detailing rules would generally be control flexural cracks but
that advantage might be gained by calculating crack widths in accordance with the
following expression, given in Appendix A:
3 a c r £ m
1 + 2h-x
where
min
h =
X =
distance between point considered and the surface of the nearest longitudinal bar
average strain at the level at which cracking is considered
minimum cover
overall depth of the member
depth of the neutral axis.
BS 8110, Structural use of concrete, 1985
The guidance was somewhat more detailed than in CP 110:1972. The total deflection was
still limited to span/250 but the deflection occurring after the construction of finishes and
partitions was limited to span/500 or 20 mm, whichever was the lesser. The span/effective
depth ratios for beams up to 10 m span were the same as in CP 110:1972. Modification
factors were again given for the effects of tension and compression reinforcement.
A specific limiting crack width for reinforced concrete was not given in Parti, Code of
practice for design and construction, which simply said that:
"Cracking should be kept within reasonable bounds by attention to detail. It
will normally be controlled by adherence to the detailing rules."
62Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The guidance on the requirements for minimum reinforcement percentages were more
detailed than in CP 110, covering both sections mainly in tension and sections in flexure. For
the latter, percentages were given for both flanged beams and for rectangular solid sections.
Guidance on the calculation of crack width, if required, was given in Part 2, Code of practice
for special circumstances, using the same expression as in CP 110:1972.
5.82 Bridges Limiting crack widths for bridges were introduced in 1968, somewhat earlier than for
buildings, presumably reflecting the fact that bridges are more exposed to the environment.
Ministry of War Transport Memorandum 557, Bridge design and construction, 1945
(reprinted 1949)
The Memorandum gave no guidance on serviceability matters, such as limiting crack widths.
BE 10: Reinforced concrete for highway structures, 1968
Crack widths (excluding under HB loading and 112 kN HA loading) were limited to 0.25 mm,
with the crack width being taken as:
3.3c£a where the reinforcement perpendicular to the crack was deformed bars
3.8c£a where the reinforcement perpendicular to the crack was smooth bars
where
c = distance from the point being considered to the nearest bar running perpendicular
to the crack or the distance to the neutral axis, whichever is the lesser
£a = apparent tensile strain in the concrete at the point under consideration.
BE 1/73: Reinforced concrete for highway structures, 1973
The approach for determining the crack width was the same as in BE 10, but a crack width
of 0.30 mm was now given for HB loading, the two 112 kN wheel loads or accidental
loading.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1978
(Note that BS 5400 Part 4:1978 was not implemented by the Highways Agency until the
publication of BD 17/83.)
Unlike the general guidance given in the earlier BE documents, the design crack widths
were given for three exposure conditions, as follows:
Moderate
Severe
Very severe
0.25 mm
0.20 mm
0.10 mm
63Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The design surface crack width for beams was:
where
acr = distance from the point considered to the nearest longitudinal bar
e, = average strain at the level where cracking is being considered, ignoring tension
stiffening.
For the flanges in beam and slab construction and top flanges in rectangular voided slab or
box-beam construction the surface crack width was determined from the same expression
as in CP 110:1972, namely:
1 + 2h-x
where
£m = average strain at the level at which cracking is considered allowing for the effect
of tension stiffening, which was given by a separate equation
cmjn = minimum cover
h = overall depth of the member
x = depth of the neutral axis.
BE 1/73: Reinforced concrete for highway structures (including Amendment No. 1),
1979
The permissible crack widths were amended slightly from those in the 1973 version.
BD 17/83: Design of concrete bridges; use of BS 5400: Part 4:1978,1983
The design crackwidths were the same as in BS 5400:1978, with the addition of 0.10 mm
for the 'extreme' condition.
The crack width for solid rectangular sections was now calculated in accordance with the
BS 5400:1978 expression for flanges, modified slightly to:
1 + 2h-x I
wherecnom = recluired nominal cover to the tensile reinforcement, or the actual cover if greater.
The equation for determining em differed from that in BS 5400:1978.
64Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
For other sections, such as flanges in beam and slab construction, the crack width was
calculated from the expression:
where
£, = average strain at the level where cracking is being considered, ignoring tension
stiffening.
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1984
The amendments given in BD 17/83 were generally incorporated in BS 5400:1984.
Design crack width for 'very severe' exposure was relaxed slightly, so the widths for the
four exposure conditions were as follows:
ExtremeVery severe
Severe
Moderate
0.10 mm0.15 mm
0.25 mm
0.25 mm
The expressions for the surface crack widths were the same as in BD 17/83 except that
the notation was changed slightly and the application of 3acr£m being clarified as being
"for flanges in overall tension".
BD 24/84, Design of concrete bridges, Use of BS 5400: Part 4:1984,1984
This document implemented the use of BS 5400: Part 4 with minor typographical
amendments. It emphasised that:
"The clauses of BS 5400: Part 4 that are expressed in the form of recommenda-
tions using the word 'should' are to be considered as mandatory."
BS 5400, Steel, concrete and composite bridges, Part 4: Code of practice for design
of concrete bridges, 1990
The requirements were the same as in the 1984 version.
5.9 Robustness The progressive collapse of the Ronan Point multi-storey flats in 1968 following a gas
explosion led to the publication of Ministry of Housing and Local Government Circulars
62/68 and 71/68, requiring the appraisal of all blocks over six storeys in height built of
large precast concrete panels, and to the introduction of minimum requirements for
robustness in buildings of five or more storeys, given in an Amendment to the Building
Regulations in 1970 and an Addendum to the Code for precast concrete.
65Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Addendum No. 1 to CP 116:1965 and CP 116: Part 2:1969, Large-panel structures
and structural connections in precast concrete, 1970
This addendum to CP 116, The structural use of precast concrete, was the first to specifically
consider accidental loads and to include a requirement to avoid disproportionate collapse.
Serious damage should not involve more than three storeys or more than 70 m2 or 15%,
whichever was the lesser, of any affected storey, following removal of any one element of
the structure. Alternatively the structure should be able to resist a load of 34 kN/m2 (5 psi)
applied simultaneously with the appropriate combination of dead, applied and wind loads.
(Clearly 5 psi was selected by the drafting committee as being the critical pressure, which
was then converted to 34 kN/m2; it might have been more logical to 'round' the metric
pressure to 35 kN/m2.)
Specific robustness requirements included:
• horizontal connections between load-bearing walls and floors or roof equal to 25 kN/m
length of joint at the top of the wall and 12.5 kN/m at the bottom
• a peripheral tie at each floor and roof level capable of resisting a force of 40 kN,
without exceeding the permissible stress in the steel
• internal ties at each floor and roof level capable of carrying 25 kN/m in the direction
of the span and 12.5 kN/m transverse.
The Addendum also gave guidance on the effects of misalignment and lack of plumb,
suggesting an allowance of (12Vn)mm, where n was the number of storeys, or an eccentricity
of 20 mm across a joint.
CP 110, Code of practice for the structural use of concrete, 1972
The Code spelled out the requirements in more detail, now in limit state terms rather
than on the basis of permissible stresses. For all buildings of five or more storeys, the
following were required:
• A peripheral tie to be provided at each floor and roof level to carry a force of Ft.
• Internal ties to be provided at each floor level per metre to carry {Ft{gk + qk)/7.5}{l/5}
but not less than Ft.
• External columns and walls to be tied horizontally into the structure at each floor level
and comer columns to be tied in two directions at right angles, with a tie capable of
carrying the lesser of 2Ft and (/0/2.5)Ft, but not less than 3% of the total ultimate
vertical load at the floor level considered.
where
Ft = the lesser of (20 + 4ns) or 60, kN
ns = number of storeys
(gk + qk) = sum of average characteristic dead and imposed floor loads in kN/m2
/ = span of the tie in the direction considered, but not exceeding five times the
clear storey height
/0 = floor to ceiling height in metres.
66Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Design 5
Amendments to CP 110 in 1976 extended the requirement for internal ties and external
ties to "each floor and roof level". The requirements for stability were strengthened by the
statement that:
"The engineer responsible for the overall stability of the structure should
ensure the compatibility of the design and details of parts and components.
There should be no doubt of this responsibility for overall stability when all or
some of the design and details are not made by the engineer."
BS 8110, Structural use of concrete, 1985
The Code contained the same provisions as in CP 110:1972, although there had been
editorial changes. BS 8110:1985 introduced the concept of 'key elements' defined as
elements whose failure:
"would cause the collapse of more than a limited portion close to the element
in question".
Guidance on the design of such elements, which were required to carry an accidental
load of 34 kN/m2 in any direction, was contained in Part 2 of BS 8110. In addition there
was the requirement:
"that any vertical load-bearing element other than a key element can be
removed without causing the collapse of more than a limited portion close to
the element in question".
A later Amendment to BS 8110 extended the requirements to all buildings rather than to
those of five or more storeys.
5.10 Analysis The Handbooks to CP 110 and BS 8110'16;18' give background information on the method
of simplified frame analysis adopted by the Codes.
5.10.1 Frame analysis 1934: Code of Practice for reinforced concrete
The Code considered two loading cases:
• alternate spans loaded and all other spans unloaded
• adjacent spans loaded and all other spans unloaded.
67Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
The Code suggested that the maximum span moments could be increased by not more
than 15% provided that the support moment was reduced by the same amount.
The loading patterns were basically unaltered with the publication of successive Codes.
CP 110, The structural use of concrete, 1972
With the introduction of limit state design, the wording was amended although the
approach was unaltered. The two loading cases became:
• alternate spans loaded with total ultimate load (1.4Ck +1.6Qk) and all other spans
loaded with minimum dead load (1.0CJ
• any two adjacent spans loaded with total ultimate load (1.4Gk + 1.6Qk) and all other
spans loaded with minimum dead load (1.0Ck)
where
Gk = characteristic dead load
Qk= characteristic live load.
Obviously, the introduction of partial safety factors slightly altered the balance between
the assumed loading on loaded and unloaded spans.
5.10.2 Slabs Code of Practice for reinforced concrete, 1934
The Code gave guidance on the moments on slabs, either simply supported or fixed/
continuous on four sides. The Handbook'13' expanded the guidance in the Code considerably
for various types of loading. The Code also gave guidance on the design of flat slabs of
uniform thickness, with or without drops, with approximately equal panels. It introduced
the concept of a middle strip and a column strip and gave coefficients for the positive and
negative design moments. Guidance was given on the provision of reinforcement for both
two-way reinforcement (bars running parallel to the grid lines) and four-way reinforcement
(bars parallel to the grid lines but also on the diagonal between columns).
CP 114, The structural use of normal reinforced concrete in buildings, 1948
The Code gave the same coefficients for slabs simply supported on four sides but extended
the guidance for restrained slabs. Elastic behaviour was assumed.
CP 114.102, Floors and roofs of flat slab construction, 1950
The sub-Code extended the approach given in CP 114:1948 and gave specific guidance
on the design of flat slabs, including the division of panels into middle strips and columns
strips, the associated bending moments and the detailing of reinforcement.
CP 114, The structural use of reinforced concrete in buildings, 1957
The Code gave similar bending moment coefficients for slabs simply supported on four sides
(although expressed slightly differently), based on elastic analysis. As an alternative approach,
load-factor design could be used, with the moments determined from Johansen's yield-line
theory or other acceptable methods. The Code included guidance on the design of flat slabs.
68Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
CP 114, The structural use of reinforced concrete in buildings, 1969
The 1969 version of CP 114 gave the same guidance for the design of slabs as the earlier
version. However, an Amendment in March 1976 deleted the clauses covering flat slabs,
stating that they should be designed in accordance with CP 110 (which had been
published in 1972).
CP 110, The structural use of concrete, 1972
The moment coefficients were the same as inCP 114:1957. The Code indicated that:
"Moments and shear forces resulting from both distributed and concentrated
loads may be determined by elastic analysis such as that by Pigeaud or Wester-
gaard. Alternatively, Johansen's yield-line of Hillerborg's strip method may be
used provided the ratio between support and span moments are similar to
those obtained by the use of elastic theory; values between 1.0 and 1.5 are
recommended."
In the 1960/70s, flat slabs were frequently designed by yield line methods and as a con-
sequence the reinforcement layout may not have been in accordance with the classical
layout of bars, i.e. column and middle strips. With yield line the reinforcement tended to
be concentrated in patches over the columns. To maintain the overall compatibility with
wP/8 the span reinforcement tended to be larger than current elastic layouts which had a
secondary benefit of improving deflection control.
BS 8110, Structural use of concrete, 1985
The guidance was the same as in CP 110:1972, with the addition of a table of shear force
coefficients for rectangular panels supported on four sides.
69Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
6. Guidance relating to specific types ofstructures
While the design Codes and Standards are applicable to the majority of structures and
structural elements, additional guidance is required for some applications, as outlined in
this Chapter.
6.1 Precast systems The first British Standard Code of Practice covering the structural use of precast concrete
in general, CP116, was published in 1965. (Prior to that time guidance on standard precast
beams for bridges had been prepared by the Cement and Concrete Association, see later.)
The Code covered the design of both reinforced and prestressed units and included aspects
such as connections and workmanship.
6.1.1 Concrete frames There have been various attempts to develop 'standard' precast concrete frames for
industrial and commercial use. Various systems in the UK, Europe, Scandinavia and the
USA have been described by Diamant(52'.The Comprehensive Industrialised Building Systems
Annual 1970 compiled by Deeson*53' gives brief details of concrete, steel and timber systems
for the construction of all types of structures, from tower block, industrial buildings and
schools to houses and bus shelters. (For further information on system-built houses see
Section 6.1.5, Non-traditional houses, below.)
The Public Building Frame, developed by the Ministry of Public Building and Works in 1966,
consisted of basic precast column, beam, slab and wall units, with a range of standardised
cross-sections, as outlined in a report by Creasy'54'. The system was based on a one-foot
(305 mm) module vertically, with column spacing based on a module of two or three feet
(610 or 915 mm). The standard columns were single storey with a dowel connection. Various
precast units were used to form the floor, all with a two-inch (50 mm)-thick structural
screed. Creasy's report contains indicative design curves linking floor loading and spans.
The National Building Frame was used for the construction of low-, medium- and high-
rise buildings such as schools and factories. Some typical details of the system are given
by Elliott<55>.
The Intergrid system was developed in conjunction with the Ministry of Education as part
of the programme to aid the school building programme. It is understood that components
were manufactured by at least 18 companies and were used in over 200 buildings. Intergrid
was a horizontal two-way prestressed grid using standard precast components. The first
70Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Guidance relating to specific types of structures
generally available system was the Mark II, which was first produced in 1954, later super-
seded by Marks III, IV and V over the next 23 years. In the Mark II, the floor and roof beam
components consisted of precast lattice units 40 inches (1015 mm) long and 16 inches
(405 mm) deep. These units were assembled into beams and prestressed together, with
tendons running externally that were covered with mortar after stressing. Secondary beams
of the same depth were placed transversely between the primary beams and stressed
together to form the complete grid. Details are given in the BRE report The structural
condition ofIntergridbuildings of prestressed concrete^. The Mark III, introduced in 1959,
used monolithic units (or segmental units with internal steel ducts) for the main beams
to form the grid. In the Mark IV, introduced in 1964, the secondary beams were bolted to
the main beams, to reduce the amount of prestressing on site. The system was further
modified in 1966 (Mark IV L) and 1968 (Mark IV*) and a metric version with a 1800 mm
module was introduced in 1972. It is not clear when production of the system ceased.
The CLASP (Consortium of Local Authorities Special Programme) system was first developed
in the late 1950s by local authorities who needed to build school buildings as quickly and
cheaply as possible. Initially intended for use in areas subject to mining subsidence, the
system was based on a light steel frame with concrete floors and precast concrete cladding
panels'57'.
Attempts were made in the mid-1970s to develop a standard system for the construction
of hospitals, known as the Harness system'58'59). While a full-scale demonstration building
was constructed, the system was not widely used.
Beam-column connections
Various approaches have been adopted for the connections between precast concrete
beams and columns. Elliott'55' suggests that the number of different solutions in the 1960s
and 1970s was as great as the number of precast frame manufacturers, about 20 at the
time. Some (such as Trent around 1975) used a system of bolted cleats, while FC Precast
used billeted connections up to the mid-1970s. Dow Mac used billets from 1980 onwards.
6.1.2 Precast floor and roof
unitsMany different types of precast flooring units have been produced; Appendix A lists some
of the systems that were produced in the 1960s. Structural precast concrete by Glover'44'
and the BCSA publication, Prefabricated floors for use in steel framed buildings^ give details
of a range of precast concrete floor systems, giving the relevant dimensions, the weights
of the structural units, the load capacity per unit width and limiting spans for the loading
Standard (CP 3 Chapter V) current at the time, etc.
Wood-wool slabs
In the past, wood-wool was used extensively as permanent formwork. For example, in the
Neolith and Marlith systems wood-wool panels covered the tops of the precast trough units,
supporting the in-situ concrete. In the Spanform system, the concrete of the in-situ topping
also flowed into the voids between the wood-wool 'beam' units to form a ribbed slab.
71Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
In 1975 the Wood Wool Manufacturers Association investigated the compaction of concrete
in wood-wool formers'61'62'. The reports concluded that, with care, good compaction of
reinforced concrete ribs could be achieved. However, CIRIA Report C558 Permanent
formworkin construction^ noted that, in practice:
"Problems occurred due to the high energy absorption of the material reducing
the effectiveness of vibration, resulting in poor compaction, exacerbated in
the case of low workability concrete."
Poor compaction would tend to lead to poor durability. This was particularly so with
systems such as Spanform where it was necessary to achieve good compaction around
the reinforcing bars at the bottom of the ribs.
Reinforced autoclaved aerated concreteReinforced autoclaved aerated concrete planks (mainly under the trade names Siporex and
Durox) were used for roof slabs for a number of years. After some time in service, there was
a tendency for such planks to develop cracks on the soffit and to exhibit excessive and
progressive deflections. The large deflections could lead to ponding on the roof and damage
to the waterproof membrane, leading to water penetration. The problems in 20-year-old
units have been reviewed by BRE, see for example IP 10/96'64' and BR 445'65'. Laboratory
tests carried out on defective planks showed that they still had adequate load capacity.
When originally constructed, the reinforcement was protected by a latex-cement coating
but this had broken down, leading to localised corrosion of the reinforcement. The BRE
reports concluded that the residual service life of the units would be heavily dependent
on their moisture content.
Design guidance for autoclaved aerated concrete was given in CP 110:1972. Similarly,
guidance was given in Part 2 of BS 8110 when it was first published in 1985, but the
complete section was subsequently deleted, presumably following the in-service problems
outlined above.
Precast shellsStructural precast concrete by Glover'44' gives details of Omega precast hyperbolic paraboloid
shell units, funicular shell units, long-span roof systems and north light shell roof systems.
6.1.3 Large panel systems Large panel systems were widely adopted in the early 1960s as a solution to the shortage
of housing. Various systems were developed in Continental Europe and the major British
contractors bought licences to manufacture them in the UK. Laings bought the Jespersen
system and developed it into the 12M. Taylor Woodrow bought the Larsen Neilsen system
and renamed it Taylor Woodrow Anglian. The collapse of the Ronan Point 22-storey tower
block in 1968 following a gas explosion led to a reappraisal of the systems by BRE and the
publication of a range of reports, some relating to specific systems such as the Taylor Woodrow
Anglian system (BRE Report 63<66') and some dealing with more generic issues. The work
led to the introduction of robustness requirements in Codes, see Section 5.9 above.
72Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Guidance relating to specific types of structures
6.1.4 On-site construction There are several on-site construction systems that may be classed as 'precast' as the units
are cast in one position and then lifted into their final location. Probably the best known
was the Liftslab method, in which the floor slabs were cast on top of each other at ground
level and then jacked upon precast columns to their final location. The slabs were held in
position by wedges engaging into welded steel shear collars cast into the slab. After
installation the joints were grouted to give a moment connection. One drawback with
the system was that poor tolerances in setting the wedges supporting the slab at each
column could result in all the reaction being taken by one wedge, significantly increasing
the effective shear force.
A variation on the Liftslab system was the Jackblock system developed by Costain. Here the
top storey was constructed at ground level and then jacked up so that the top-but-one
storey could be constructed below it. The sequence was repeated until the building reached
its intended height.
6.1.5 Non-traditional houses The term 'non-traditional housing' may be used to describe all the various methods of
house building that have moved away from the traditional 'bricks and mortar'. As far as
concrete is concerned, many different systems have been developed over the years, using
combinations of precast and in-situ concrete. In some cases, many thousands of units
have been built. In other cases only a few prototypes were constructed. Some have been
successful (some examples have actually been statutorily 'listed' as being of architectural
or historic importance) while others have suffered from basic design faults.
BRE has carried out extensive investigations into the various housing systems and has
published Non-traditional houses: Identifying non-traditional houses in the UK 7978-75'12'.
This covers metal-framed and timber-framed houses as well as concrete. Some 450 housing
types are covered in detail, with brief information on a further 230. For each main type
there is an isometric drawing that provides a clear explanation of the construction details,
which will significantly help to diagnose problems and issues. Appendix B lists some of
the more common house types.
The publication comes with a CD ROM to help identify houses by type, local authority,
construction class, identifying characteristics or by any combination of these. It also
includes six Government reports on non-traditional housing.
6.1.6 Standard bridge beams Various standard precast prestressed concrete beams have been developed over the years.
Information on section properties, typical spans, etc. was published by the Cement and
Concrete Association'67^59'. The development of precast beams since the Second World War
has also been reviewed by Taylor'70', with aspects of the detailing of beams in the 1970s
being considered by Green'71'. Standard Tee beams for railway bridges were developed
initially for the Eastern Region and subsequently became a British Railways standard.
73Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
6.1.7 Bearings for precast
unitsThe guidance on bearings for precast concrete units has gradually developed with successive
Codes.
CP116, The structural use of precast concrete, 1965
CP116, the first Code for precast concrete, indicated that precast units should have a bearing
of at least 4 inches (102 mm) on masonry or brickwork supports and at least 3 inches
(76 mm) on steel or concrete. It suggested that these values might be reduced in special
circumstances but that consideration should be given to relevant factors such as tolerances
and the provision of continuity rods.
CP 110, The structural use of concrete, 1972
The Code gave the same guidance as in CP 116 (with the imperial dimensions changed to
metric equivalents, i.e. 100 mm and 75 mm respectively), with the additional requirement
that, when reduced bearings were used, the minimum anchorage length in the precast
unit should still be provided and precautions taken to avoid collapse due to accidental
displacement during erection.
BS 8110, Structural use of concrete, 1985
The guidance in BS 8110 was considerably expanded from that in earlier codes, with the
required bearing area being determined from the applied load and the capacity of the
concrete, e.g. 0.4/cu for concrete on concrete. Allowances were made for construction
inaccuracies and the effects of spalling at the edges of both the support and the supported
member.
6.2 Foundations The history of the development of foundations and substructures has been reviewed by
Chrimes(72'.The early 19th century saw the first use of (lime) concrete as a foundation
material in Britain. Portland cement was used in concrete from around 1865, although
the material had been in use in mortars and renders from some years earlier. Hurst'21)
notes that while it was used for the footings of 'large and important buildings' from this
time, it was another 20 years or so before it was used more generally, and later still for
'domestic buildings'. For this latter category, strip footings were originally built of corbelled
brickwork. In the late 19th century a requirement was introduced to place a layer of
unreinforced lime concrete below the brickwork, and later mass concrete was used for the
entire footing. At this same time, mass concrete composed of Portland Cement started to
be used also for retaining walls, for example in the approach ramps for the Connaught
railway tunnel beneath the Royal Docks, completed in 1878.
The London Metropolitan Buildings Act of 1844 gives prescriptive wall thicknesses relating
to height and building use, with footing depths indicated. The London Building Act of 1894
provides similar prescription and also specifies the width of footing in relation to the wall
thickness. From these it is possible to infer bearing pressures that might approach 250 kN/m2
for the heavier loading classes. These values are probably higher than would be used today
for modern construction on London Clay, but slower rates of building and use of less brittle
mortars meant settlements would not have been such an issue at that time.
74Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Guidance relating to specific types of structures
Chrimes notes that a 'plain concrete slab' was typically used towards the end of the 19th
century. This might be 150 mm where the wall footings were separate, but otherwise would
be at least 225 mm, with 300 mm being more usual. For heavy loads the raft would be
thicker, and in some cases iron rails were used as reinforcement, with steel beams as a
subsequent replacement.
Reinforced precast concrete piles were developed at the end of the 19th century and the
beginning of the 20th century; Chrimes illustrates various types, such as the Hennebique,
Considere and Coignet piles and the Mouchel hollow pile. He also reviews early forms of
in-situ piles. Prestressed precast piles were developed by Freyssinet in the 1930s. Bored
piles came into use after about 1930 and were only more generally used from the 1950s
onwards. Under-reams at the pile base to increase load-carrying capacity of single piles
followed soon afterwards. Embedded retaining walls were also developed in the 1950s
with the first diaphragm wall in the UK being installed in London in 1961.
The Third Edition of Reinforced Concrete Designers' Handbook^ published in 1946 gives
some coverage of precast piles with approaches for determining their load capacity. There
is little coverage of cast-in-situ piles with the author stating that "there are many different
patented systems". It is suggested that Mix III Ordinary Grade or Mix III High Grade in
accordance with the 1934 Code of Practice, i.e. 2550 psi (18 N/mm2) or 3300 psi (23 N/mm2),
would be suitable for precast piles.
The First Edition (1951) of the Specification for road and bridge works required a 28-day
strength of 5000 psi (35 N/mm2), which was significantly higher that the strengths
suggested by the Reinforced Concrete Designers' Handbook.
The Sixth Edition of the Reinforced Concrete Designers' Handbook (1961) gives slightly
different concrete strengths, 2450 psi (17 N/mm2) and 3600 psi (25 N/mm2), for precast
piles and indicates a cover of V/z inches (38 mm) for the main bars and 1 inch (25 mm)
for binders in accordance with CP 114. The same information is given in the Seventh
Edition (1971).
The Piling and diaphragm walling handbook^ provides an overview of the various techniques
used in the early 1970s but little in the way of design guidance. (This handbook was
published by Cementation Piling and Foundations, but is presumably representative of
industry practice.)
6.3 Water-retainingstructures
Early water-retaining structures have been described in a paper by Gould'74' and the
development of the various types of dam, with some consideration of the materials used,
by Bruggemann eta/(75).
75
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Gould and Cleland(76) reviewed the development of reinforced concrete water towers.
They noted that reinforced concrete became common after about 1900 and discussed
various aspects of water tower development, including multi-legged designs, solid-sided
towers, shafts with fins and single stem towers. The paper included over 120 references,
many of them contemporary articles describing the design and construction of specific
water towers.
The Third Edition of Reinforced Concrete Designers' Handbook^ published in 1946 gave
some guidance on the design of water-retaining structures. It suggested that Mix III Ordinary
Grade or Mix III High Grade in accordance with the 1934 Code of Practice, i.e. 2550 psi
(18 N/mm2)or3300 psi (23 N/mm2), would be suitable. For circular tanks the tensile stress
in the concrete should be limited to 175 psi (1.2 N/mm2). For elements of rectangular
tanks in bending, the compressive stress should be limited to 880 psi (6.1 N/mm2) and
the tensile stress to 250 psi (1.7 N/mm2).
Code of practice for the design and construction of reinforced concrete structures for
the storage of liquids, 1938
Published by the Institution of Civil Engineers, this was the first Code for the design of water-
retaining structures. The Introduction notes that the 1934 DSIR Code of practice for
reinforced concrete specifically excluded water-retaining structures and hence the
Institution had prepared the present document on the basis of industry best practice.
General guidance was given on the provision of joints and the selection of materials.
Design was in accordance with the DSIR Code but with certain limitations applied. As
indicated in Section 4.3.1 above, the ICE Code specified minimum concrete grades in
terms of weight of cement (lb):fine aggregate (cu. ft):coarse aggregate (cu. ft) as follows:
• 112:2:4 for general use
• 112:21/2:5 for slabs greater than 24 inches (610 mm) thick
To resist cracking, stresses were limited to 175 psi (1.2 N/mm2) in direct tension and 250 psi
(1.7 N/mm2) in bending and shear. The minimum cover was 1 inch (25 mm) or the bar
diameter for the stronger concrete and VA inches (32 mm) or the bar diameter for the
weaker concrete. Where the surface was exposed to water of a corrosive nature, the
minimum cover was increased to 2 inches (51 mm).
CP 2007: Design and construction of reinforced and prestressed concrete structures
for the storage of water and other aqueous liquids, 1960
The design approach in CP 2007 was based on that in CP 114 and CP 115, with some
modifications. The introduction to the Code noted the importance of reducing the
permeability of the concrete and controlling cracking. It said that:
"Cracking may result from excessive tensile stress in the concrete due to
applied loading, to temperature change, to drying shrinkage or to settlement
... acting either singly or in combination."
76Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Guidance relating to specific types of structures 6
Other sections of the Code recommended the use of Portland cements with lower rates
of strength development giving lower rates of heat of hydration.
As indicated in Section 4.3.1, the Code recommended two nominal concrete mixes,
1:1.6:3.2 and 1:2:4, both with a 28-day strength of 3600 psi (25 N/mm2).To restrict
cracking, tensile stresses were limited as follows:
Mix 1:1.6:3.2
Mix 1:2:4
Direct tension
190 psi (1.31 N/mm2)
175 psi (1.21 N/mm2)
Bending
270 psi (1.86 N/mm2)
245 psi (1.69 N/mm2)
The Code noted that these stresses would also limit the tensile stresses in the reinforcement;
with an assumed modular ratio of 15, a tension of 190 psi (1.3 N/mm2) in the concrete
would limit the steel stress to 2850 psi (20 N/mm2).
The Code gave guidance on the provision of movement joints and gave details of various
types of watertight joint. General guidance was given on construction, for example limiting
the size of lifts for thick walls.
The Code suggested that no separate allowance was required for stresses due to shrinkage
or temperature change in the concrete provided that the stresses were limited, care was
taken in construction and adequate movement joints were provided. However, Concrete
Society Technical Report 22 (Third Edition), Non-structural cracks in concrete® notes that:
"Walls designed to CP 2007 were extremely likely to suffer unacceptable
cracks despite warnings given in the Forward of the Code."
BS 5337: Code of practice for the structural use of concrete for retaining aqueous
liquids, 1976
The revised Code was published in 1976 and the accompanying Handbook'17' was published
in 1979. Two different design approaches were given, either in line with CP 110 (i.e. limit
state design) or in line with CP 114 and CP 115 (i.e. permissible stress design as used in
CP 2007). When designing in accordance with CP 110, the Code specified that the bond
stresses for horizontal bars in sections in direct tension should not be greater than 0.7 times
the values given in CP 110. The Handbook explains the reason for this restriction,,saying:
"Horizontal bars which are in direct tension suffer from water-gain effects and
a lack of transverse shear; hence the values are reduced."
77Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
|dlp|G||€@pes of structures
The Code defined two exposure conditions for concrete exposed to water, as follows:
• Class A Exposed to moisture or subject to alternate wetting and drying
• Class B Exposed to continuous or almost continuous contact with liquid
with crack widths in reinforced concrete of 0.1 mm and 0.2 mm respectively. The
following expression was given for determining the surface crack width due to flexure:
4 -5I 3 f~
1 + 2 5 ' cr min
h-x
where
acr = distance between point considered and the surface of the nearest longitudinal bar
sm = average strain at the level at which cracking is consideredcmin = minimum coverh = overall depth of the member
x = depth of the neutral axis.
Alternatively, crack widths could be assumed to be satisfactory if the steel stresses were
limited as follows:
Class A
Class B
Plain bars85 N/mm2
115 N/mm2
Deformed bars100 N/mm2
130 N/mm2
When using the CP114/CP 115 approach, the concrete stresses were limited, as in CP 2007,
but they were related to two Grades of concrete and not to the exposure Class, as follows:
Grade 30
Grade 25
Direct tension1.44 N/mm2
1.31 N/mm2
Bending2.02 N/mm2
1.84 N/mm2
While the earlier code had identified the problem of early thermal stresses, it only gave
guidance on modifying the concrete and the construction process. BS 5337 introduced
the concept of a critical reinforcement ratio, pcrit, given by:
Peril = fa/fy
where
fa = direct tensile strength of the immature concrete taken as 1.15 N/mm2 for Grade 25
concrete and 1.3 N/mm2 for Grade 30 concrete
/ = characteristic strength of reinforcement but not exceeding 425 N/mm2.
When the amount of reinforcement exceeded the critical ratio, the likely maximum
spacing of cracks, smax, was given by:
78Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Guidance relating to specific types of structures
where
(fa/fb) = ratio of the tensile strength of the concrete to the bond strength, taken as 1.0
for plain bars, Vs for deformed Type 1 bars and 2A for Type 2 bars
0 = diameter of the reinforcing bar
p = actual ratio of steel provided.
It was suggested that, under normal climatic conditions, the maximum crack width, wmax,
could be related to smax as follows:
where
a
r.= coefficient of thermal expansion of concrete
= fall in temperature between peak and ambient.
It was suggested that 7", should be taken as >30°C for concreting during the summer and
as >20°C for concreting during the winter, with both values increased for cement contents
above 340 kg/m3 and wall thicknesses above 400 mm. The Code also indicated that there
would be a further temperature fall, T2, due to seasonal variations, but gave no indication
what values should betaken. However, the Handbook suggests 20°C for casting in summer
and 10°C for winter.
An Amendment in June 1982 gave further information on the parameters on which the
values for 71 had been based. It suggested that lower values could be used with lower
ambient conditions, but should never be less than 20°C for walls and 15°C for slabs.
BS 8007: Code of practice for design of concrete structures for retaining aqueous
liquids, 1987
The design approach adopted by the Code was fully in accordance with BS 8110 and the
option for permissible stress design was finally dropped. The exposure conditions were the
same as in BS 8110, with a nominal cover of at least 40 mm and crack widths for 'very
severe' exposure conditions limited to 0.2 mm.
The approach to dealing with early thermal effects was the same as in BS 5337, but some-
what modified as follows:
• When determining pcrit, only one value for/ct was given, namely 1.6 N/mm2 for Grade
C35A concrete.
• For deformed bars, only Type 2 was considered with (fct/fb) given as 0.67.
• More detailed guidance was given for determining I, with values given for different
section thicknesses, formwork materials and cement contents. For further information
reference was made to CIRIA Report 91(77l Again, no guidance was given for the
seasonal drop in temperature, Tr
• The expression for calculating crack widths in flexure was modified to bring it into line
with BS 8110, namely:
1+2h-x
79
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
f l l l l
6.4 Houses: in-situconstruction
Between the 1930s and the late 1950s there were a large number of different systems for
constructing houses in situ. As with the precast systems covered earlier, the BRE has carried
out extensive investigations into the various systems, and has published information in
Non-traditional houses: Identifying non-traditional houses in the UK 7978-75'12'. See also
Section 6.1.5. Appendix B lists some of the more common types.
Some of the systems (e.g. those of George Wimpey and the Scottish Special Housing
Association) were constructed using no-fines concrete. This consists of a single-size coarse
aggregate coated in a cement slurry with no fine aggregate addition. Because it does not
contain any fine aggregate the fresh concrete cannot segregate and consequently it can be
dropped from a height. Formwork pressures are lower than for normal concrete so shutters
can be lighter and pour height lifts greater. BRE Report BR 191 entitled The renovation of
no-fines housing1?® records that around 450 000 housing units were constructed between
about 1945 and the early 1980s. No-fines concrete was used for the main load-bearing
structure in about 85% of the units. In the remainder it was simply used for infill panels.
The report concludes that the structural performance of most no-fines buildings was
satisfactory, although there were problems with condensation and water ingress in some
cases. In addition the open texture of the concrete causes problems if buildings are upgraded,
for example with the fixing of replacement windows.
6.5 Other structures Concrete is widely used in many types of structures other than those specifically covered
earlier in this report. Developments of its use in some types of structures have been
reviewed by various authors, as follows:
• Sharp'79' considered marine structures, from coastal protection schemes to oil and gas
production platforms.
• Information on the development of shell roof structures is given by Morice and
Tottenham'80' and by Anchor'81'. See Section 6.1.2 above for information on precast
concrete shells.
• Muir Wood'82' surveyed the use of cast-in-situ, precast and sprayed tunnel linings from
about 1880 to the present.
• The development of concrete roads from the 1860s to the present has been reviewed
by West'83'.
• Weiler'84' has reviewed the use of concrete in military applications from the early 19th
century to the Second World War.
80Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
General information on concrete deterioration 7
7. General information on concretedeterioration
Properties of concrete by Neville'85', which was first published in 1963, is one of the
definitive works of reference on concrete, giving information on a wide range of materials.
Lea's chemistry of cement and concrete^, which was first published in 1935, deals with
the chemical and physical properties of cements and concretes, including durability.
The Concrete Society website (www.concrete.org.uk) includes the information system
ConcreteatYourFingertips, which contains over 900 'nuggets' of information on a wide
range of concrete-related topics, some of which have been reproduced in this publication.
7.1 Alkali-silica reaction(ASR)
ASR is the most common form of alkali-aggregate reaction. It occurs when the alkaline
pore fluid and siliceous minerals in some aggregates react to form a calcium alkali silicate
gel. This gel absorbs water, producing a volume expansion which can disrupt the concrete.
The main external evidence for damage to concrete due to ASR is cracking. In unrestrained
concrete the cracks have a characteristic random distribution often referred to as 'map
cracking' where there is a network of fine cracks bounded by a few larger cracks. However,
the only reliable evidence for diagnosing ASR as the cause of damage is by microscopic
examination of the interior of concrete to identify positively the presence of the gel, of
aggregate particles which have reacted and the presence of internal cracking, characteristic
of that induced by ASR.
Guidance notes aimed at minimising the risk of alkali-silica reaction were first published by
the Cement and Concrete Association in1983'87' and Concrete Society Technical Report 30,
Alkali-silica reaction-minimising the risk of damage to concrete^ was published in 1987.
The introduction of specifications to limit alkali content and reactive aggregates in concrete
has meant that no confirmed incidence of ASR has been noted in the UK in structures
built since the mid-1980s.
A report by the Institution of Structural Engineers'89) considers the structural effects of ASR.
7.2 Sulfate attack Sulfates react with concrete, resulting in an expansive formation of ettringite or gypsum
in hardened concrete causing cracking and exfoliation. If there is a continuous supply of
sulfate, through movement of groundwater, the cracks will allow contact with more concrete
surface and the reaction can lead to a softening and further disintegration of the concrete.
A rare form of sulfate attack is through the formation of thaumasite as a result of the
reaction between calcium silicates in cement, calcium carbonate in limestone aggregates
and sulfates usually from an external source.
81Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
This reaction causes the concrete to soften and progressively disintegrate from the contact
surface. For this reaction to occur, the following conditions must apply:
• temperature below 15°C
• consistently high relative humidity
• supplies of calcium, sulfate and carbonate
• initial presence of reactive alumina (0.4-1.0%).
7.3 M u n d i c The equity value of many mainly pre-1950 houses in Devon and Cornwall has been
adversely affected by uncertainties in the nature of the concrete building material used in
their original construction. Mundic is a Cornish word used to describe a mineral of iron
containing sulfur, known as pyrite or iron pyrites. This mineral occurs frequently in the
lodes or veins of tin and copper mined for centuries throughout Cornwall and Devon. Vast
quantities of mine waste were extracted and dumped on the surface. During the early part
of the 20th century builders used this cheap and readily available source of aggregate for
the production of concrete blocks and concrete for construction. In the presence of moisture,
the pyrites chemically alters and expands causing concrete to deteriorate. In the 1950s,
Standards for aggregates used in concrete minimised this contamination. Whilst it is still
possible that some properties built after 1950 may be affected, the problem is more likely
to affect concrete properties built between 1900 and 1950.
7.4 Clinker concrete Clinker, the fused or sintered ashes remaining from the combustion of coal, was used as a
form of artificial aggregate in concrete for various applications such as jack arches and filler
joist slabs prior to about the 1930s. However, the use of clinker for reinforced concrete
applications was specifically prohibited by the structural Codes, such as the 1934 Code of
Practice for reinforced concrete. However, the Code did suggest that prohibited materials
could be used if tests showed that the requirements for strength and durability could be
achieved.
The Handbook to the 1934 Code'13' suggested that:
"Clinker, breeze or coke breeze concretes are unsuitable for use in contact
with any reinforcement or steel work. They are as a rule somewhat permeable
and ... together with the sulphur compounds contained usually result in
corrosion of any steel in contact with them."
82Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Other sources of information 8
8. Other sources of information
Appendix 1 of Historic concrete - background to appraisal^ provides a comprehensive list
of sources of further information on historic concrete. Some of the key sources are listed
below.
Technical information on the original construction of the structure being investigated
may be available in articles in contemporary magazines and periodicals, such as:
• Civil Engineering and Public Works Review (1906-1989)
• CONCRETE (1966 onwards)
• Concrete and Constructional Engineering (1906-1966)
• Proceedings of the Institution of Civil Engineers (1837 onwards)
• Reinforced Concrete Review (1945-1961)
• Structural Concrete (1962-1966)
• The Builder (1843-1966)
• Transactions of the Concrete Institute (now The Institution of Structural Engineers)
(1909-1922)
• The Structural Engineer (1923 onwards)
It may be necessary to carry out a library search to obtain additional background information
relating to the structure or to the materials/systems used in its construction. The Concrete
Society's library contains more than 130,000 books, journal and magazine articles, standards,
conference proceedings, details of trade names, etc. dealing with all aspects of concrete
and its use in construction. Contact [email protected].
The libraries of the Institution of Civil Engineers ([email protected]), the Institution of
Structural Engineers ([email protected]) and the Royal Institute of British Architects
([email protected]) are obviously less specialised and hold publications on the complete
spectrum of construction materials. The ICE Library also administers an international e-
mail discussion group Civil Engineering Heritage Exchange (CEHX); contact mike.
The Consultants Tracker, developed by The Institution of Structural Engineers, is intended to
help trace a firm of civil and structural engineering consultants that has merged, been taken
over, closed down or changed its name. Co to www.istructe.org/library/consultanttracker.asp.
The Concrete Year Book$°\ published annually from 1924 onwards, gives guidance on
contemporary Standards, materials and design approaches. It also contains a useful list of
trade names and brands. Similarly Specification^, published by Architectural Press annually
since 1898, gives information on proprietary systems and materials, with specification
clauses and product information arranged by type of work and supported by indexes and
articles. It was a standard work of reference well into the 1960s and 1970s.
83Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
As indicated earlier, The Highways Agency maintains an archive of superseded bridge
standards. Enquiries should be addressed to [email protected]
(note the underscore).
Copies of withdrawn British Standards may be obtained through the BSl Knowledge Centre,
which holds a comprehensive collection of Standards going back to the 1900s. Each
amended version of a Standard is available, enabling developments to be traced. Copies
of Standards can be purchased either as PDFs or as hard copies. Enquiries should be
addressed to [email protected].
The National Archives in Kew (www.nationalarchives.gov.uk) hold some material relating
to the development of the railways in the UK.
84Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
References
References
1 INSTITUTION OF STRUCTURAL ENGINEERS. Appraisal of existing structures (Third Edition),
Institution of Structural Engineers, London, 2009.
2 CONCRETE BRIDGE DEVELOPMENT GROUP. Guidance on the assessment of concrete bridges,
Technical Guide No. 9, The Concrete Society (on behalf of the Concrete Bridge Development
Group), Camberley, 2007.
3 HIGHWAYS AGENCY. Design manual for roads and bridges, Highways Agency, London. Available at
http:/www.standardsforhighways.co.uk/dmrb/index.htm
4 NETWORK RAIL, NR/GN/CIV/025. Underbridgeassessment, Network Rail, 2006.
5 GOLD, CA and MARTI N, AT. Refurbishment of concrete buildings -structural and services options,
GN 8/99, Building Services Research and Information Association, Bracknell, 1999.
6 GOLD, C. Recycling concrete buildings for the 21st century, CONCRETE, Vol. 33, No. 7, July/August
1999, pp. 46-47.
7 CONSTRUCTION INDUSTRY RESEARCH AND INFORMATION ASSOCIATION. Building with
reclaimed components and materials-A design handbook for reuse and recycling (Author Addis, B),
Report X332, CIRIA, London, 2006.
8 THE CONCRETE SOCIETY. Diagnosis of deterioration in concrete structures: Identification of defects,
evaluation and development of remedial action, Technical Report 54, The Concrete Society,
Camberley, 2000.
9 THE CONCRETE SOCIETY. Non-structural cracks in concrete, Technical Report 22 (Third Edition),
The Concrete Society, Camberley, 1992. (NOTE: This Report is currently being revised and updated.)
10 BRITISH STANDARDS INSTITUTION, BS EN 1504. Products and systems for the repair and protection
of concrete structures-Definitions, requirements, quality controland evaluation of conformity, Part 1:
Definitions, Part 2: Surface protection systems for concrete, Part 3: Structural and non-structural
repair, Part 4: Structural bonding, Part 5: Concrete injection, Part 6: Anchoring of reinforcing bars,
Part 7: Reinforcement corrosion protection, Part 8: Quality control and evaluation of conformity,
Part 9: General principles for the use of products and systems, Part 10: Site application of products
andsystems, and quality control of the works, BSI, London, various dates.
11 THE CONCRETE SOCIETY. Guide to the repair of concrete structures with reference to BS EN 1504,
Technical Report 69, The Concrete Society, Camberley, 2009.
12 HARRISON, H, MULLIN, S, REEVES, B and STEVENS, A. Non-traditional houses: Identifying non-
traditional houses in the UK 1918-75, BRE, Garston, Watford, 2004.
13 SCOTT, WL and GLANVILLE, WH. Explanatory handbook on the Code of Practice for reinforced
concrete as recommended by the Reinforced Concrete Structures Committee of the Building
Research Board, Concrete Publications Limited, London, 1934. (Second Edition published 1939.)
14 SCOTT, WL, GLANVILLE, W and THOMAS, FG. Explanatory handbook on the BSCode of Practice for
reinforced concrete, Concrete Publications Limited, London, 1950 (revised 1957, Second Edition 1965).
15 WALLEY, F and BATE, SCC. A guide to the BS Code of Practice for prestressed concrete, CP 115:1959,
Cement and Concrete Association (now Mineral Products Association -Cement), Camberley, 1961.
16 BATE, SCC eta/. Handbook to the Unified Code for structural concrete (CP 110:1972), Cement and
Concrete Association (now Mineral Products Association-Cement), Camberley, 1972.
17 ANCHOR, RD etal. Handbook on BS 5337:1976 (the structural use of concrete for retaining
aqueous liquids), Cement and Concrete Association (now Mineral Products Association - Cement),
Camberley, 1979 (Second Edition 1983).
18 ROWE, RE etal. Handbook to British Standard BS 8110:1985, Structural Use of Concrete, Palladian
Publications Limited, London, 1987.
85Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
19 REYNOLDS, CE. Reinforced Concrete Designers' Handbook (First Edition). Concrete Publications
Limited, London, 1932. Subsequent editions (the later ones co-authored with JC Steedman) were
published as follows: Second Edition 1939, Third Edition 1946, Fourth Edition 1948 (revised 1951
and 1954), Fifth Edition 1957, Sixth Edition 1961 (revised 1964), Seventh Edition 1971 (revised
1972), Eighth Edition 1974, Ninth Edition 1981, Tenth Edition 1988
20 THE CONCRETE SOCIETY. The use ofggbsandpfa in concrete, Technical Report 40, The Concrete
Society, Camberley, 1991.
21 HURST, BL. Concrete and the structural use of cements in England before 1890, Historic concrete-
background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), ThomasTelford, London,
2001, pp. 45-65. Also in Proceedings of the Institution of Civil Engineers: Structures and Buildings,
Vol. 116, No. 3 and 4, August/November 1996, pp. 283-294.
22 NEWBY, F. The innovative use of concrete by engineers and architects, Historic concrete -
background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London,
2001, pp. 11-44. Also in Proceedings of the Institution of Civil Engineers: Structures and Buildings,
Vol. 116, No. 3 and 4, August/November 1996, pp. 264-282.
23 SOMERVILLE, G. Cement and concrete as materials; changes in properties and performance,
Historic concrete-background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas
Telford, London, 2001, pp. 105-116. Also in Proceedingsof the Institution of Civil Engineers: Structures
and Buildings, Vol. 116, No. 3 and 4, August/November 1996, pp. 335-434.
24 SUTHERLAND, RJM. Understanding historic concrete, Proceedings of the Institution of Civil Engineers:
Structures and Buildingsyol 116, No. 3 and 4,1996, pp. 255-263.
25 STANLEY, CC. Highlights in the history of concrete, Cement and Concrete Association (now Mineral
Products Association -Cement), Camberley, 1979.
26 CHRIMES, MM. The development of concrete bridges in the British Isles prior to 1940, Historic
concrete-background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford,
London, 2001, pp. 211-249. Also in Proceedings of the Institution of Civil Engineers: Structures and
Buildingsyol 116, No. 3 and 4, August/November 1996, pp. 404-431.
27 SMITH, WJR. UK concrete bridges since 1940, Historic concrete - background to appraisal
(Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London, 2001, pp. 251-273. Also
in Proceedings of the Institution of'Civil Engineers, Structures and fiu/W/ngs, Vol. 116, No. 3 and 4,
August/November 1996, pp. 432-448.
28 FABER, O. Reinforced concrete simply explained, Oxford University Press, 1922 (Third Edition 1944).
29 PULLAR-STRECKER, P. Corrosion damaged concrete; assessment and repair, Published on behalf of the
Construction Industry Research and Information Association, London, by Butterworths, London, 1987.
30 BUILDING RESEARCH ESTABLISHMENT. HAC concrete in the UK, BRE Press, Garston, Watford, 2002.
31 DUNSTER, A, BIGLAND, D, HOLTON, I and REEVES, B. Durability of ageing high alumina cement
(HAC) concrete: A literature review and summary of BRE research findings, Report 386, Building
Research Establishment, Garston, Watford, 2000.
32 DUNSTER, A, BIGLAND, D, REEVES, B and HOLTON, I. The durability of pre-cast HAC concrete in
buildings, Information Paper IP 8/00, Building Research Establishment, Garston, Watford, 2000.
33 ROAD RESEARCH LABORATORY. Design of concrete mixes, Road Note No. 4, HMSO, London, 1950.
34 MclNTOSHJD. Concrete mix design, Cement and Concrete Association (now Mineral Products
Association - Cement), Camberley, 1964.
35 TEYCHENNE, DC. Codesand standards-time for harmonisation, CONCRETE, Vol. 16, No. 8,
August 1982, pp. 10-12.
36 REYNOLDS, CE. Practical examples of reinforced concrete design, Concrete Pu blications Limited,London, 1938.
37 THE CEMENT MARKETING COMPANY. Everyday uses of Portland cement-a practical handbook on
the economical employmentof Portland cement (Fourth Edition), The Cement Marketing Company
Limited, London, 1921 (First Edition published 1909.)
86
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
References
38 THE INSTITUTION OF STRUCTURAL ENGINEERS/THE CONCRETE SOCIETY. Standard method of
detailing structural concrete. A manual for best practice (Third Edition), The Institution of Structural
Engineers, London, 2006.
39 SUTHERLAND, J, HUMM, DandCHRIMES, M (Eds). Historic concrete -backgroundto appraisal,
Thomas Telford, London, 2001.
40 HIGHWAYS AGENCY, BD 21. Design manual for roads and bridges, Volume 3: Highway structures:
inspection and maintenance, Section 4: Assessment, Part 3: The assessment of highway bridges and
structures, The Highways Agency, London, 2001.
41 Specification, Architectural Press (now EMAP), published annually since 1898.
42 BUSSELL, MN.The era of the proprietary reinforcing systems, Historic concrete-backgroundto
appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London, 2001, pp. 68-82.
Also in Proceedings ofthe Institution of Civil Engineers, Buildings and Structures, Vol. 116, No. 3 and 4,
August/November 1996, pp. 295-316.
43 WALLEY, F. Prestressing, Historic concrete-background to appraisal (Sutherland, J, Humm, D and
Chrimes, M, Eds), Thomas Telford, London, 2001, pp. 191-210.Also in Proceedings ofthe Institution of
Civil Engineers, Structures and Buildings, Vol. 116, No. 3 and 4, August/November 1996, pp. 390-403.
44 AUDRPM,Alar\dTURUm,EH.Posttensioning systems forconcreteintheUK: 1940-1985, Report 106,
CIRIA, London, 1985.
45 GLOVER, CW. Structural precast concrete, CR Books Limited, London, 1964.
46 BUSSELL, M N. The development of reinforced concrete: design theory and practice, Historic concrete
-background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London,
2001, pp. 83-103. Also in Proceedings ofthe Institution of Civil Engineers: Structures and Buildings,
Vol. 116, No. 3 and 4, August/November 1996, pp. 317-334.
47 REYNOLDS, CE. Examples ofthe design of reinforced concrete buildings, Concrete Publications
Limited, London, 1952 (revised 1959).
48 REYNOLDS, CE. Basic reinforced concrete design, a textbook for students and engineers, Volume 1:
Elementary, Volume 2: More advanced design, Concrete Publications Limited, London, 1962.
49 ALLEN, AH. Reinforced concrete design to CP 110 simply explained, Cement and Concrete Association
(now Mineral Products Association - Cement), Camberley, 1974.
50 DAWE, P. Traffic loading on highway bridges, Thomas Telford, London, 2003.
51 BATCHELOR, WG and BEEBY, AW. Charts forthe design of circular columns to BS 8110, Report 43.503,
British Cement Association (now Mineral Products Association - Cement), Camberley, 1990.
52 DIAMANT, R. Industrialised Building: 50 international methods, Iliffe Books, London, 1969.
53 DEESON, AFL. The Comprehensive Industrialised Building Systems Annual 1970, Morgan-Grampian
(Publishers) Ltd, West Wickham, Kent, 1970.
54 CREASY, LR. The Public Building Frame, Cement and Concrete Association (now Mineral Products
Association - Cement), 1966.
55 ELLIOTT, KS. Multi-storey precast concrete framed structures, Blackwell Science, Oxford, 1996.
56 BUILDING RESEARCH ESTABLISHMENT. The structural condition of Intergrid buildings of prestressed
concrete, HMSO on behalf of BREandthe Department of the Environment, London, 1978.
57 MINISTRY OF EDUCATION. The Story of CLASP, Building Bulletin 19, Ministry of Education,
London, 1961.
58 BEEBY, AW, READ, JB and LEWIS, HE. The Harness Hospital system, Part 2: Testing of a prototype
structure, Proceedings ofthe Institution of Civil Engineers, Part 1, Design and Construction, Vol. 60,
Issue 3, August 1976, pp. 423-443.
59 LEWIS, HE and TAYLOR, N. The Harness Hospital system, Part 1: Design of a standard structure
and construction of a prototype, Proceedings ofthe Institution of Civil Engineers, Part 1, Design and
Construction, Vol. 60, Issue 3, August 1976, pp. 401-423.
60 BRITISH CONSTRUCTIONAL STEELWORK ASSOCIATION. Prefabricated floors for use in steel
framed buildings, Publication M2, BCSA, London, 1964 (revised 1965 and 1977).
87Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
61 GAZE, A and THOM PSON, MS. Investigation into the compaction of reinforced concrete ribs in wood
wool formers - 50 mm slump concrete, Wood Wool Slab Manufacturers Association, London, 1975.
62 LEVITT, M and GAZE, Al. Investigation into the compaction of reinforced concrete ribs in wood wool
formers -120 mm slump concrete. Wood Wool Slab Manufacturers Association, London, 1975.
63 CONSTRUCTION INDUSTRY RESEARCH AND INFORMATION ASSOCIATION. Permanent
formwork in construction (Author Wrigley, RG), Report C558, CIRIA, London, 2001.
64 CURRIE, RJ and MATTHEWS, SL. Reinforced autoclaved aerated concrete planks designed before
1980, Information Paper IP 10/96, Building Research Establishment, Garston, Watford, 1996.
65 MATTHEWS, S, NARAYANAN, N and GOODIER, A. Reinforced autoclaved aerated concrete panels;
review of behaviour and developments in assessment and design, Report BR 445, Building Research
Establishment, Garston, Watford, 2002.
66 BUILDING RESEARCH ESTABLISHMENT. The structural performance of Ronan Point and otherTaylor
WoodrowAnglian Buildings, Report 63, BRE, Garston, Watford, 1985.
67 CEMENT AND CONCRETE ASSOCIATION. Standard beam sections for prestressed bridges, C&CA
(now Mineral Products Association - Cement), Camberley.
1. InvertedT beams for spans 25-55 ft (2nd edition 1963, addendum 1966)
2. Box beams for spans 40-85 ft (1963)
3. Box section beams for spans from 85-120 ft (1964)
4.1 section beams from 40-85 ft (1964)
5.1 section beams for spans from 85-129 ft (published 1964)
68 SOMERVILLE, G and TILLER, RM. Standard bridge beams for spans 7-36 m, Report 46.005, Cement
and Concrete Association (now Mineral Products Association - Cement), Camberley, 1970.
69 MANTON, BH and WILSON, CB. MoT/C&CA standard bridge beams, Report 46.012, Cement and
Concrete Association (now Mineral Products Association - Cement), Camberley, 1971 (Revised 1975).
70 TAYLOR, HPJ. The precast concrete bridge beam - the first 50 years, The Structural Engineer, Vol. 76,
No. 21, November 1998, pp. 407-414.
71 GREEN, JK. Detailing for standard prestressed concrete bridge beams, Report 46.018, Cement andConcrete Association (now Mineral Products Association - Cement), Camberley, 1973.
72 CHRIMES, MM. Concrete foundations and sub-structures: a historic review, Historic concrete -
background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London,
2001, pp. 117-163. Also in Proceedings of the Institution of Civil Engineers: Structures and Buildings,
Vol. 116, No. 3 and 4, August/November 1996, pp. 344-372.
73 ANON. Piling and diaphragm walling handbook, Cementation Piling and Foundations,
Rickmansworth, circa 1970.
74 GOULD, M. Water-retaining structures in Britain before 1920, Historic concrete -background to
appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London, 2001, pp. 323-341.
75 BRUGGEMANN, DA, HOLLOCK, KJ and SIMS, GP. Historic concrete in dams, Historic concrete -
background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London,
2001, pp. 343-357.
76 GOULD, MH and CLELAND, DJ. Development of design form of reinforced concrete watertowers,
Proceedings of the Institution of Civil Engineers, Structures and Buildings, Vol. 146, No. 1, February
2001, pp. 3-16.
77 HARRISON, TA. Early-age thermal crack control in concrete, Report 91, CIRIA, London, 1981.
78 WILLIAMS, AW and WARD, GC. The renovation of no-fines housing, Report BR 191, Building Research
Establishment, Garston, Watford, 1991.
79 SHARP, B. Reinforced and prestressed concrete in maritime structures, Historic concrete-
background to appraisal (Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London,
2001, pp. 275-302. Also in Proceedings of the Institution of Civil Engineers: Structures and Buildings,
Vol. 116, No. 3 and 4, August/November 1996, pp. 449-469.
88
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
References
80 MORICE, P and TOTTENHAM, H. The early development of reinforced concrete shells, Historic
concrete-background to appraisal (Sutherland, J, Humm, DandChrimes, M, Eds), Thomas Telford,
London, 2001, pp. 165-175. Also in Proceedings of the Institution of Civil Engineers: Structures and
Buildings, Vol. 116, No. 3 and 4, August/November 1996, pp. 373-380.
81 ANCHOR, R. Concrete shell roofs, 1945-65, Historic concrete-background to appraisal
(Sutherland, J, Humm, D and Chrimes, M, Eds), Thomas Telford, London, 2001, pp. 177-189. Also in
Proceedings of the Institution of Civil Engineers: Structures and Buildings,Vo\. 116, No. 3 and 4,
August/November 1996, pp. 381-389.
82 MUIRWOOD, A. Concrete in tunnels, Historic concrete -background to appraisal (Sutherland, J,
Humm, D and Chrimes, M, Eds), Thomas Telford, London, 2001, pp. 315-322.
83 WEST, G. Concrete roads, Historic concrete - background to appraisal (Sutherland, J, Humm, D and
Chrimes, M, Eds), Thomas Telford, London, 2001.
84 WEILER, J. Military, Historic concrete -background to appraisal (Sutherland, J, Humm, D and
Chrimes, M, Eds), Thomas Telford, London, 2001.
85 NEVILLE, AM. Properties of concrete (Third Edition), Longman, Essex, 1995.
86 HEWLETT, PC (Ed.). Lea's chemistry of cement and concrete (Fourth Edition), Arnold, London, 1998.
87 HAWKINS, MR (Chairman of Working Party). Minimising the risk of alkali-silica reaction -guidance
notes. A report of a Working Party, Report 97.304, Cement and Concrete Association (now Mineral
Products Association - Cement), Camberley, 1983.
88 THE CONCRETE SOCIETY. Alkali-silica reaction - minimising the riskof damage to concrete.
Guidance notes and model specification clauses, Technical Report 30, The Concrete Society,
Camberley, 1987 (Revised Edition 1995, Third Edition 1999).
89 INSTITUTION OF STRUCTURAL ENGINEERS. Structural effects of alkali-silica reaction, Institution
of Structural Engineers, London, 1992.
90 ANON. The Concrete Year Book, Concrete Publications Limited, London, published annually from
1924 onwards.
Further reading BECKMANN, P and BOWLES, R. Structural aspects of building conservation (Second Edition),
McGraw-Hill Book Company, London, 2004.
BEEBY, AW and HAWES, FL. Action and reaction in concrete design, 1935-1985, Reprint 3/86,
Cement and Concrete Association (now Mineral Products Association -Cement), Camberley, 1986.
BREBBIA, CA and FREWER, RJB. Structural repair and maintenance ofhistorical buildings,Vol. 111,
Computational Mechanics Publications, Southampton, 1993.
CONSTRUCTION INDUSTRY RESEARCH AND INFORMATION ASSOCIATION. Structural
renovation of traditional buildings, Report 111, CIRIA, London, 1994.
HART, WO. Construction of buildings in London, Greater London Council, 1958.
KNOWLES, CC and PITT, PH. The history of Building Regulation in London 7789-7972, Architectural
Press, London, 1972.
LEY, AJ. A history ofBuilding Controlin Englandand'Wales 1840-1'990, RICS Books, London, 2000.
MACDONALD, S (Ed.). Concrete building pathology, Blackwell Science Ltd, Oxford, 2003.
PARKINSON, G, SHAW, G, BECK.JKand KNOWLES, D. Appraisal and repair of masonry, Thomas
Telford, London, 1996.
89
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
WM
Appendix A. Proprietary floors
A wide range of proprietary precast concrete floor systems have been produced over the
years. The list below is taken from Prefabricated floors for use in steel framed buildings,
published by BCSA'60', which gives the properties and safe load capacities of various
systems available in the 1960s. Those marked with an asterisk (*) are also described in
Structural precast concrete by Glover'45'.
• Allison T-beam floor
• Anglian prestressed floor
• Armocrete precast floor
• Arrow precast floor
• Atlas-Omnia trough slab
• Bison precast or prestressed hollow floor; solid or hollow plank floor*
• Blatchford's channel floor beam; prestressed double tee unit; precast trough floor,
precast hollow floor
• BRC hollow steel mould floor
• Chipcrete lightweight composite floor
• Corite hollow floor*
• Croft precast hollow floor
• Dabro Cheam precast hollow block floor; Shere precast composite system
• Dow-mac single-core hollow beams; twin-core hollow beams
• Ebor Duron trough beam; Duron hollow beam
• Evanstone (single core hollow beam)
• Evercrete channel floor beam; hollow beam
• Filigree beam and block floor; wideslab floor*
• Fram precast X joist floor; composite floor*
• Girling precast floor; prestressed floor*
• Greenwood's Greecon floor; hollow beam floor; Myko floor
• Gypklith precision beams
• HBS self-centering floor
• Helicon precast trough floor: precast hollow floor
• Invictus (single-core beams, triple-core beams or channels)
• Kaiser floor
• Lyncrete precast floor
• Marley floor and roof beams
• Marlith wood-wool floor and roof formers*
• Matthews precast channels; precast hollow beam
• Milbank composite floor*
• Musker
• Neolith wood-wool floor units
a Omnia semi-precast hollow block floor*
• Parcrete precast composite system
a Pierhead prestressed concrete floor; composite floor
• Rapid floor
90
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Appendix A
• Shockcrete precast floor
• Siegwart precast trough floor: precast hollow floor*
• Sindall floor
• Smith's fireproof floor
• Spancrete prestressed composite floor
• Spanform wood-wool composite floor
• Stahlton
• Stotam Roth prestressed floor: prestressed plank floor
• Stuarts precast trough floor; precast hollow floor
• Tembo prestressed floor*
• Thermaflor
• Tilecast floor*
• Trent and Hoveringham prestressed floor
• Triad composite floor
• Truscon Type 1 & 2 floor units; mini-tee unit*
• Truspan prestressed hollow floor
• Viking floor
Also included in Prefabricated floors for use in steel framed buildings are three steel-concrete
systems:
• Hoiorib composite floor (similar to modern steel decking)
• Q-floor (similar to modern steel decking)
• QC-floor (using a flat steel plate with an upstand).
Structural precast concrete also gives details of:
• Bradfords precast floors
• Eagle floors and roofs
• Siporex floor and roof slabs
91
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Appendix B. Non-traditional houses:precast and constructed in-situ
Details of a large number of system-built houses are given in Non-traditional houses;
identifying non-traditional houses in the UK 7978-75(12>. A list of the more common types is
given below; the criterion for inclusion in Non-traditional houses is that more than 1000
were built.
Precast Airey
Boot Pier and Panel
Camus
Dorran (includes Myton, Newland andTarran)
Gregory
Intergrid
Kenkast
Orlit (Types I and II)
Reema Hollow Panel
Smith
Stent
Underdown (including Winget)
Wates
Woolaway
Bison Wallframe
Bryant Low Rise
Cornish (Types I and II)
Glasgow Foamed Slag
HSSB System
Jestersen 12M
Lecaplan (Types A and B)
Parkinson
Skarne
Spacemaker
Taylor Woodrow Anglian
Unity (Types I and II)
Whitson-Fairhurst
XW
Constructed in-situ Boswell
Duo-Slab
Farrans No-Fines
Mowlem
Schindler
Universal
Diatomite
Easiform (Types I and
Fidler
Parkwell
Unit No-Fines
Wimpey No-Fines
92
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society
There are many instances in which an engineer is asked to
appraise an existing building, or other structure, perhaps due to
led change of use or as part of a refurbishment process,
i example might be an office block built in the 1960s,
although with the move towards conservation, it is likely that
many earlier buildings and structures will be refurbished or
upgraded rather than being demolished and replaced. As a first
stage in this process, it is useful to have as much information
as possible about the structure, such as what Code or Standard
t was designed to, what the concrete and steel strengths were
likely to have been at the time of construction, what design
pproaches were adopted, what proprietary precast concrete
units were available, etc.
The aim of this Technical Report is to provide an outline of this
information and to list some of the relevant publications and other
sources of readily available information, up to about 1990. (Although
this Report is primarily intended to cover UK practice, many British
Codes and Standards were, and are, used abroad and hence the guidance
should be equally applicable overseas.)
CCIP-049
Published July 2009
ISBN 978-1-904482-57-4
© The Concrete Society
Riverside House, 4 Meadows Business Park,
Station Approach, Blackwater, Camberley, Surrey, CUV 9AB
Tel: +44 (0)1276 607140 Fax: +44 (0)1276 607141
wwwconcrete.org.uk
Licensed copy: mouchelic, Mouchel International Consultants, 27/10/2009, Uncontrolled Copy, ®The Concrete Society