Instruction Bulletin Preliminary 10/2008 Schneider Canada Services 1 HIM1008 Instruction Bulletin SEPTEMBER 08

HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

  • Upload
    vandien

  • View
    230

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

1

HIM1008 Instruction Bulletin

SEPTEMBER 08

Page 2: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services Mississauga, ONTARIO

2

Table of Contents

1 Highway Addressable Remote Transducer (HART™)........................................................ 3 2 General Specifications........................................................................................................... 4 3 Dimensions ............................................................................................................................. 5 4 General Description ............................................................................................................... 6

4.1 Introduction........................................................................................................................ 6 4.2 Purpose ............................................................................................................................. 7 4.3 Functions........................................................................................................................... 7

4.3.1 Pass-Through ............................................................................................................ 7 4.3.2 Embedded Web Server (HTML pages) ..................................................................... 7 4.3.3 4x Registers Mapping (Holding Registers) ................................................................ 7

5 HIM 1008 Presentation ........................................................................................................... 8 6 Features................................................................................................................................... 8

6.1 Two Ethernet-Switch Ports................................................................................................ 8 6.2 4-20mA Pass-Through ...................................................................................................... 8 6.3 Built-in Filters and Resistor Terminations ......................................................................... 8 6.4 DC to DC Converter .......................................................................................................... 9

7 RS-485 Pass Through Operation .......................................................................................... 9 7.1 Connections Details .......................................................................................................... 9 7.2 Driver Details................................................................................................................... 10

8 Hardware ............................................................................................................................... 11 8.1 DIP-switches S1 and S2 ................................................................................................. 11 8.2 HE10 Connection ............................................................................................................ 11

8.2.1 HE10 Pin-Out........................................................................................................... 12 8.3 Connections for Field Devices ........................................................................................ 13

8.3.1 Passive Transmitter and Analog Input Module Connections................................... 13 8.3.2 Active Transmitter (example for a 24VDC supply Transmitter) ............................... 13 8.3.3 Smart valve .............................................................................................................. 14

9 Operation............................................................................................................................... 15 9.1 Power On Behavior ......................................................................................................... 15 9.2 LED Indications ............................................................................................................... 15

10 Holding Registers (% MW ) Memory map....................................................................... 16 11 Web Server ........................................................................................................................ 19

11.1 Ethernet Setup............................................................................................................. 19 11.1.1 Static IP Address ..................................................................................................... 19

11.2 Embedded Web Pages................................................................................................ 23 11.2.1 Home Page .............................................................................................................. 23 11.2.2 Monitoring ................................................................................................................ 23

11.2.2.1 Device Information............................................................................................ 24 11.2.2.2 Run Time Parameters ...................................................................................... 25 For Different Channels........................................................................................................ 25

11.2.3 Diagnostic Page....................................................................................................... 26 11.2.3.1 Ethernet Statistics............................................................................................. 26 11.2.3.2 HIM1008 Statistics............................................................................................ 26

11.2.4 HIM1008 Setup ........................................................................................................ 27 11.2.4.1 Configure IP...................................................................................................... 28 11.2.4.2 CommSettings .................................................................................................. 29 11.2.4.3 HIM Configuration............................................................................................. 30

11.3 Quick Connect Cable for 140 ACO 130 00 ................................................................. 33 11.4 Quick Connect Cable for 140 ACI 040 00 ................................................................... 34 11.5 Quick Connect Cable for 140 ACI/ AVI 030 00 ........................................................... 35 11.6 Quick Connect Cable for 140 ACO 020 00 ................................................................. 36

Page 3: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

3

1 Highway Addressable Remote Transducer (HART™) The HART™ protocol makes use of the Bell 202 FSK standard to superimpose digital signals at a low level on top of the 4-20mA signal. This enables two-way communication and makes it possible for additional information beyond just the normal process variable to be communicated to/from a smart field instrument. The HART™ protocol communicates without interrupting the 4-20mA signal and allows a host application (master) to get two or more digital updates per second from a field device. As the digital FSK signal is phase continuous, there is no interference with the 4-20mA signal.

Page 4: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

4

2 General Specifications

Specification Description Part number: HIM1008 Supply for HIM1008 24V DC (+/-10%) @ 500 mA Auxiliary input 24 VDC Supply for individual DC/DC converters

Auxiliary Input Power Supply connections provided for powering field devices via 8 individual 24V DC-DC converter @ 500mA

Built-in 24 DC/DC converter Maximum 1 Watt @ 24 V DC per Channel Continuous Short-Circuit Protection

Communication Ports:

1. Two RJ45 ports –Embedded switch. • Usage:

- Embedded Web Page for Diagnostics, Ethernet setup - Modbus TCP/IP Data Access - HART™ OPC access

2. One Removable 5-pin Terminal Block– RS485, HART™ pass-through.

• Usage: - Asset Management Software and HART™ OPC access

Field Wire Requirements 0.5….1.5 mm2 (24……16 AWG). Isolation Minimum 1 KV isolation between power supply and communication ports

Indication

1. LED1: for HART™ ‘Pass-Through’ communication status LED (Yellow) 2. LED2: for HART™ communication status LED (Yellow ) 3. LED3: Ethernet communication status LED (Yellow ) 4. LED4: Module OK/Scanning Status LED (Green ) 5. CH1-8 Over Current Fault Indication (30 mA) (Red )

Isolation • HART™ channels are transformer isolated. (1.5KV between HART™ modem and HART™ field device)

• Polarity independent connection on the HART™ side. • 30V DC isolation Channel to Channel.

No. of HART™ Device per Channel 1 device per channel. HART™ Protocol Revision 5 supported.

Secondary master device is supported. (i.e.: handheld configuration tool) Module Configuration Configuration via Ethernet port using embedded Web Pages (HTTP) DIP switches SW1 ON Position: Filtering enabled for Analog Output module DIP switches SW2 ON Position: 250 ohm termination enabled (to use for Analog Input

module) Dimensions 155mm X 47 mm X 48mm Operating Temperature 0 to 60ºC Storage Temperature -20°C to +80°C, non-operating Operating Humidity 10 - 90%, non-condensing Compliance CE, (cUL pending), RoHS, WEEE

Page 5: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

5

3 Dimensions

Page 6: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

6

4 General Description

4.1 Introduction This manual provides guidance for the installation, operation and maintenance of the Schneider Canada Services' HIM1008 (8 channels HART™ Interface Multiplexer). Typical block diagram

(1) Asset Management or HART™ OPC client connection via Serial RS485 Port. (2) Module Configuration and Asset Management Connection via Modbus/ TCP-IP.

HART Server

Plant Asset Management Software

Ch1(+) Ch1(-)...Ch4(+)Ch4(-) Ch5(+)Ch5(-)…Ch8(+)Ch8(-)

HE10 connector

CPU

HART Modem

Ch1(+) Ch1(-)

Ch4(+) Ch4(-) Ch5(+) Ch5(-)

A(+) B(+) A(-) B(-) HART Modem

Ch8(+) Ch8(-)

...

... Addressable RS-485 HART

Pass-Through

ModbusTCP Embedded

Servers HTTP FTP

SNMP

Embedded Switch

(1)

(2)

Page 7: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

7

4.2 Purpose The HIM1008 is a HART™ Interface Multiplexer unit, which allows access to 8 Channels HART™ communications on existing 4-20mA loop.

4.3 Functions At power up the module scans the 8 channels and retrieves all the HART™ Data (Manufacture ID, Device ID, etc.). This information is routed to three internal memory areas:

4.3.1 Pass-Through All the HART™ information is passed through the RS-485 and Ethernet port, for maintenance purposes and connectivity to HART OPC server and/or AMS (Asset Management Software). Acting as HART™ OPC client, a maintenance workstation PC can use this port for configuration, maintenance, calibration, diagnostics, and data access to all connected field instruments.

4.3.2 Embedded Web Server (HTML pages) Most HART™ Data can be viewed on web pages using standard web clients (Internet Explorer 7.0, Fire Fox, Netscape, etc.).

4.3.3 4x Registers Mapping (Holding Registers) All HART™ data from each detected device can be mapped to holding registers (4X). The default configuration uses 14 holding registers per channel and can be modify to meet your applications using the configuration web page. The information can be accessed using standard Modbus / TCP-IP protocol.

CH1…CH8 HART MODEM

RS-485/Ethernet Pass-Through

Holding Reg /CH Modbus/TCP-IP

Web Server

Page 8: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

8

5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer. It contains 8 channels and two HART™ modem. 1 8 Channel Connectors 2 S1 Switch/Ch for Built-In Filter 3 S2 Switch/Ch for 250 Ohms

Termination Resistor 4 Auxiliary input 24 Vdc Supply for

individual DC/DC converters 5 Current Limit Indications per CH

6 24 Vdc Supply for HIM1008 7 HE10 Connector for 4-20 mA, 8 Channels

toward PLC 8 RS485 HART Pass-Through port 9 RJ45 Shielded Ethernet built-In two port Switch

6 Features

6.1 Two Ethernet-Switch Ports The HIM1008 is equipped with two Shielded Ethernet Switch ports, used to daisy chain multiple modules.

6.2 4-20mA Pass-Through The 4-20mA signals for each channel are accessible via the HE10 connector. Various ‘quick connect’ cables are available for easy connection to PLC analog input/output modules.

6.3 Built-in Filters and Resistor Terminations The HIM1008 has two set of 8 'dip switches'. Each channel has one 'dip switches' assigned from each of the sets. The first switch is used to enable the filtering of the HART information when a “smart” valve is used. The second switch is used to provide internal 250 Ohms resistor loop impedance when the PLC analog input does not provide it.

Page 9: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

9

6.4 DC to DC Converter The HIM1008 has 2 X 24 V DC power inputs; both can be supplied with one source. The first 24Vdc input is used to supply HIM1008 and the second 24Vdc supply input is re-distributed to supply the 'loop current’ for each channel. The supply of each channel is isolated using a DC to DC converter. The DC to DC converter can deliver 1W to the connected load.

7 RS-485 Pass Through Operation

7.1 Connections Details The Pass-Through port is the RS 485 port. It can be configured as 2 wire or 4 wire depending on the need. Connection details for the port:

To use the port in the 2 wire mode short the RX+ and TX + externally and use it as the +ve (B) line. Short RX- and TX- externally and use it as the –ve (A) line for the communication.

CH8 CH7

CH6 CH5 CH4 CH3 CH2

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

DC

CH1

Page 10: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

10

7.2 Driver Details The port supports the HART™ protocol. Communication baud rate supported are 9600, 19200 and 38400. The user has access to all 8 Channels as the HIM1008 acts as a multiplexer.

Page 11: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

11

8 Hardware To connect field devices, 3.81mm pitch 8X6 pole double deck connector is used; six poles per channel are needed. For the control system analog input or output module, the Quick Connect HE10 connectors are used (please refer to Appendix A for a list of available cables and pin-out diagrams).

8.1 DIP-switches S1 and S2 Switch S1: In case of actuator/output type of devices (e.g. Valve Positioner), this switch should be used for selecting the internal filter for these devices. Switch S2: In case of transmitter type devices, this switch should be used for selecting the 250 � terminations.

Switch S1 Status

Switch S2 Status Result

ON OFF Output type device used. Filter selected.

OFF ON Transmitter type device used. 250-Ohm termination selected.

ON ON No Analog card used.

8.2 HE10 Connection The HE10 connection is used to connect the analog input or output module of the control system. A series of 'Quick-Connect ' cables are available for the following analog IO cards: ACO 130 00 High Density Analog Out I/O Module (8 Ch) ACI 040 00 High Density Analog In I/O Module (16 Ch) ACI/AVI 030 00 I/O Analog In Module (8 Ch Differential) ACO 020 00 I/O Analog Out Module (4 Ch)

Page 12: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

12

8.2.1 HE10 Pin-Out

Page 13: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

13

8.3 Connections for Field Devices

8.3.1 Passive Transmitter and Analog Input Module Connections

8.3.2 Active Transmitter (example for a 24VDC supply Transmitter)

Page 14: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

14

8.3.3 Smart valve

Caution: “Ch-x +24V” and “Ch-x GND” are the outputs of the internal Dc to Dc converter. NOTE: Do not connect outside power to it. Please refer to wiring diagram to connect external supply

Page 15: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

15

9 Operation

9.1 Power ON Behavior • OK LED Flashing slow : HIM1008 Update connection window (up to 10 Sec) • OK LED Flashing rapid : HIM1008 Internal test (up to 10 Sec) • Ethernet OK LED steady on: Ethernet enabled • HART OK LED flashing: HIM1008 scanning for field devices (up to 20 sec) • HART OK LED steady: At least one device found and connected

9.2 LED Indications • 8 x LED Current Limitations (RED): Over current indication >= 30 mA • OK LED (Green): HIM 1008 health • Ethernet OK (Yellow): Ethernet configuration • HART OK: Field device (transmitter/smart valve) connection status • Pass-Through (Yellow): RS-485 Pass-through activity

Table 2: HIM1008 LED indications Name Color Status Description

ON Over Current : Loop Current >= 30 mA Over Current LED (one per Channel) OFF Normal Operation: Loop Current < 30mA

Flashing slow In IBM mode : used for Firmware upgrade Flashing rapid Internal test ON Normal Operation

OK LED

OFF HIM1008 Power Supply not connected Hardware failure: Call your regional office

Ethernet OK ON Ethernet Port ON

Flashing Scanning for HART™ Field Device

ON At least One Device Connected

HART OK

OFF No Devices detected ON Flashing RS-485 pass through connected and data

transmitting is active. Pass-Through

OFF No Connection

Page 16: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

16

10 Holding Registers (% MW ) Memory map HIM1008 supports Modbus function code 03 (Read Holding Registers), 16 (Write Holding registers) and 23 (read/write Holding registers). When using the IO Scanning function to read the HIM holding register, the Unit ID as to be set to 1. Default memory map between HART™ values and Modbus registers (4X, % MW).

Holding Register No.

IEC Map Description Data type Bytes

40004 %MW3 CH-0 Current Value Float 4 40006 %MW5 CH-0 Percentage Value Float 4 40008 %MW7 CH-0 Device Status Word 4 40010 %MW9 CH-0 Primary Variable Float 4 40012 %MW11 CH-0 Secondary Variable Float 4 40014 %MW13 CH-0 Tertiary Variable Float 4 40016 %MW15 CH-0 Quaternary Variable Float 4 40018 %MW17 CH-1 Current Value Float 4 40020 %MW19 CH-1 Percentage Value Float 4 40022 %MW21 CH-1 Status Word 4 40024 %MW23 CH-1 Primary Variable Float 4 40026 %MW25 CH-1 Secondary Variable Float 4 40028 %MW27 CH-1 Tertiary Variable Float 4 40030 %MW29 CH-1 Quaternary Variable Float 4 40032 %MW31 CH-2 Current Value Float 4 40034 %MW33 CH-2 Percentage Value Float 4 40036 %MW35 CH-2 Status Word 4 40038 %MW37 CH-2 Primary Variable Float 4 40040 %MW39 CH-2 Secondary Variable Float 4 40042 %MW41 CH-2 Tertiary Variable Float 4 40044 %MW43 CH-2 Quaternary Variable Float 4 40046 %MW45 CH-3 Current Value Float 4 40048 %MW47 CH-3 Percentage Value Float 4 40050 %MW49 CH-3 Status Word 4 40052 %MW51 CH-3 Primary Variable Float 4 40054 %MW53 CH-3 Secondary Variable Float 4 40056 %MW55 CH-3 Tertiary Variable Float 4

Page 17: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

17

40058 %MW57 CH-3 Quaternary Variable Float 4 H Register No. IEC Map Description Data type Bytes

40060 %MW59 CH-4 Current Value Float 4 40062 %MW61 CH-4 Percentage Value Float 4 40064 %MW63 CH-4 Status Word 4 40066 %MW65 CH-4 Primary Variable Float 4 40068 %MW67 CH-4 Secondary Variable Float 4 40070 %MW69 CH-4 Tertiary Variable Float 4 40072 %MW71 CH-4 Quaternary Variable Float 4 40074 %MW73 CH-5 Current Value Float 4 40076 %MW75 CH-5 Percentage Value Float 4 40078 %MW77 CH-5 Status Word 4 40080 %MW79 CH-5 Primary Variable Float 4 40082 %MW81 CH-5 Secondary Variable Float 4 40084 %MW83 CH-5 Tertiary Variable Float 4 40086 %MW85 CH-5 Quaternary Variable Float 4 40088 %MW87 CH-6 Current Value Float 4 40090 %MW89 CH-6 Percentage Value Float 4 40092 %MW91 CH-6 Status Word 4 40094 %MW93 CH-6 Primary Variable Float 4 40096 %MW95 CH-6 Secondary Variable Float 4 40098 %MW97 CH-6 Tertiary Variable Float 4 40100 %MW99 CH-6 Quaternary Variable Float 4 40102 %MW101 CH-7 Current Value Float 4 40104 %MW103 CH-7 Percentage Value Float 4 40106 %MW105 CH-7 Status Word 4 40108 %MW107 CH-7 Primary Variable Float 4 40110 %MW109 CH-7 Secondary Variable Float 4 40112 %MW111 CH-7 Tertiary Variable Float 4 40114 %MW113 CH-7 Quaternary Variable Float 4

460000 %MW59999

CH-0 connection status MSB, channel connected 15’s LSB exchange count Word 2

460001 %MW60000

CH-1 connection status MSB, channel connected 15’s LSB exchange count Word 2

Page 18: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

18

H Register No. IEC Map Description Data type Bytes

460002 %MW60001

CH-2 connection status MSB, channel connected 15’s LSB exchange count Word 2

460003 %MW60002

CH-3 connection status MSB, channel connected 15’s LSB exchange count Word 2

460004 %MW60003

CH-4 connection status MSB, channel connected 15’s LSB exchange count Word 2

460005 %MW60004

CH-5 connection status MSB, channel connected 15’s LSB exchange count Word 2

460006 %MW60005

CH-6 connection status MSB, channel connected 15’s LSB exchange count Word 2

460007 %MW60006

CH-7 connection status MSB, channel connected 15’s LSB exchange count Word 2

460008 %MW60007 HIM health status Word 2 460009 %MW60008 HIM Port status Word 4

460011 %MW60010

HIM rescan mode 8th LSB mode 7’s LSB manual mode mask Word 2

Page 19: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

19

11 Web Server

11.1 Ethernet Setup

11.1.1 Static IP Address Ethernet default setting IP Address: 10.10.10.10 SubnetMask: 255.255.255.0 Gateway: 10.10.10.1

• Connect a cross-over OR a straight-through cable (automatic detected)

• Change the PC Ethernet settings to match the 10.10.10.xxx network.

Example: Control Panel > Network Settings > TCP/IP Properties Change to

Page 20: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

20

• Open an Internet Browser and type the IP address of the HIM 10.10.10.10 (Internet

Explorer 7 is used in this example) • The HIM1008’s home page should be loaded

• Click on the “ Setup “ tab and the Login window pop up, User Name: USER and

Password : USER. Then Setup menu appear and you can select the device IP configuration.

Page 21: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

21

• Click on the “ Configure IP “, and change to the desired IP address

• Click “Update Configuration“ and a message will pop-up to Confirm Changes

Page 22: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

22

• Click “ OK “ and a confirmation page will appear

• The HIM1008 will automatically reboot with the new address.

Page 23: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

23

11.2 Embedded Web Pages

11.2.1 Home Page

11.2.2 Monitoring

Page 24: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

24

11.2.2.1 Device Information

Different Channel Status

Page 25: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

25

11.2.2.2 Run Time Parameters

For Different Channels

Page 26: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

26

11.2.3 Diagnostic Page

11.2.3.1 Ethernet Statistics

11.2.3.2 HIM1008 Statistics

Page 27: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

27

11.2.4 HIM1008 Setup

Page 28: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

28

11.2.4.1 Configure IP

Page 29: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

29

11.2.4.2 CommSettings

Communication Settings OPC HART Server Baud rate Select the baud rate for the RS-485 port for operation (not for update) HIM ID Enter HIM1008 address for the RS-485 communication. Rescan Mode Auto: the HIM1008 rescan all free channels every 30 sec to detect newly connected device. Manual: the HIM1008 will rescan only the channel setting selection for newly connected device. Channel setting Enter the channel you want to rescan when in manual (in HEX format).

Page 30: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

30

11.2.4.3 HIM Configuration

HIM-1008 Module Configuration Source Select HART for a read command or Modbus TCP for a write command

Page 31: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

31

HART Configuration Channel (0 to 7) Enter the channel you when to communicate with. Command length Enter the length of the HART command (16 bits register). Type RC : Read command RC 2 response: Bytes 0-3: Current (mA) floating point formatted Bytes 4-7: Percentage of range floating point formatted Bytes 8-11: Device status RC 3 response: Bytes 0-3: Primary variable floating point formatted Bytes 4-7: Secondary variable floating point formatted Bytes 8-11: Third variable floating point formatted Bytes 12-15: Fourth variable floating point formatted UC: Universal command CP: Common practice command DR: Device specific read command DW: Device specific write command NOTE: Please refer to instrument manual for the complete list of supported HART command. [xxx-xxx] Enter the HART command number,

- UC range from 0 to 30. - CP range from 32 to 121 - DX range from 128 to 999

Modbus Configuration Type Select register type the command or respond for that HART command. Address Enter the address the command or respond for the HART command.

Page 32: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

32

Appendix A: Quick Connect Cables Quick-Connect cable offer expands continuously, please contact Schneider Canada Services for latest availability.

Analog Cards Quick Connect ACO 130 00 QCHIM08ACO1300Y ACI 040 00 QCHIM08ACI0400Y ACI/AVI 030 00 QCHIM08AxI0300x ACO 020 00 QCHIM08ACO0200

Page 33: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

33

11.3 Quick Connect Cable for 140 ACO 130 00

Page 34: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

34

11.4 Quick Connect Cable for 140 ACI 040 00

Page 35: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

35

11.5 Quick Connect Cable for 140 ACI/ AVI 030 00

Page 36: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

36

11.6 Quick Connect Cable for 140 ACO 020 00

Page 37: HIM1008 Manual REV3 2008 10 01 - Schneider Electric · This manual provides guidance for the installation, ... 5 HIM 1008 Presentation HIM1008 is a HART™ Interface Multiplexer

Instruction Bulletin Preliminary 10/2008 Schneider Canada Services

37

Sales and Services CALGARY Bay 288 2880 - 45th Ave. South East Calgary, AB T2B 3M1 Sales Tel: (403) 214-3130 Fax: (403) 243-4770 Services Tel: (403) 214-3160 Fax: (403) 243-1596 CAMBRIDGE 150 Pinebush Road, Unit #6 Cambridge, ON N1R 8J8 Tel: (519) 621-5756 Fax: (519) 621-5393 EDMONTON 12825 - 144th Street Bonaventure Industrial Park Edmonton, AB T5L 4N7 Tel: (780) 453-3561 Fax: (780) 451-5085 HALIFAX 110 Chain Lake Drive, Unit 3-G Halifax, NS B3S 1A9 Sales Tel: (902) 450-0360 Fax: (902) 450-1034 Services Tel: (902) 450-0360 Fax: (902) 450-1034 LONDON 1940 Oxford Street East Units 8 & 9 London, ON N5V 4L8 Tel: (519) 451-4453 Fax: (519) 451-4435 MISSISSAUGA 6675 Rexwood Road Mississauga, ON L4V 1V1 Sales Tel: (905) 678-7000 Fax: (905) 678-7870 Services Tel: (905) 678-5109 Fax: (905) 678-9814 MONTRÉAL 825, rue Bancroft Pointe-Claire, QC H9R 4L6 Sales Tel: (514) 697-4790 Fax: (514) 697-9529 Services Tel: (514) 697-4790 Fax: (514) 697-8906 OTTAWA 850 Industrial Avenue, Unit 6 Ottawa, ON K1G 4K2 Tel: (613) 247-7171 Fax: (613) 247-7177 QUÉBEC 355, rue Marais, Bureau 185 Ville Vanier, QC G1M 3N8 Tel: (418) 688-9500 Fax: (418) 688-2642

REGINA 30 Weist Bay Balgonie, SK S0G 0E0 Tel: (306) 791-8860 Fax: (306) 668-6828 RICHMOND 2551 Viking Way, Unit 100 Richmond, BC V6V 1N4 Sales Tel: (604) 273-3711 Fax: (604) 273-7314 Services Tel: (604) 273-3531 Fax: (604) 273-2218 SAGUENAY-LAC ST. JEAN 1700, boul. St-Paul, Bureau 100 Chicoutimi, QC G7J 4N1 Tel: (418) 549-5544 Fax: (418) 549-1901 SASKATOON 2301- I Millar Avenue Saskatoon, SK S7K 2Y1 Sales Tel: (306) 242-4046 Fax: (306) 668-6828 Services Tel: (306) 668-5588 Fax: (306) 668-6828 SUDBURY 868 Falconbridge Road, Unit 15 Sudbury, ON P3A 5K7 Tel: (705) 560-9516 Fax: (705) 560-9518 WINDSOR 217 - 2825 Lauzon Parkway Windsor, ON N8T 3C6 Tel: (519) 974-0900 1-888-490-9561 Fax: (519) 974-0820 WINNIPEG 21 Omands Creek Blvd. Winnipeg, MB R2R 2V2 Sales Tel: (204) 488-2305 Fax: (204) 488-7465 Services Tel: (204) 488-2548 Fax: (204) 489-9328 Sales MONCTON 535 Edinburg Drive, Unit 5 Moncton, NB E1E 4E3 Tel: (506) 857-0719 Fax: (506) 857-0385

SHERBROOKE 926, rue des Tourterelles, C.P. 87 St-Élie d ’Orford, QC J0B 2S0 Tel: (819) 822-3676 Fax: (819) 822-8977 ST. JOHN ’S 91 Whiteway Street St. John's, NL A1B 1K5 Tel: (709) 739-6374 Fax: (709) 739-6375 STONEY CREEK 903 Barton Street East, Unit 18 Stoney Creek, ON L8E 5P5 Tel: (905) 643-4707 Fax: (905) 643-6133 THUNDER BAY 3646 Government Road Thunder Bay, ON P7B 5E3 Tel: (807) 344-8555 Fax: (807) 344-1464 TRENTON 149 Bernard Long Road, RR #3 Trenton, ON K8V 8P6 Tel: (613) 394-0040 Fax: (613) 394-0048 VAL D’OR C.P. 218 Val d’Or, QC J9P 4P3 Tel: (819) 825-9211 Fax: (819) 825-9220 Canadian Plants Edmonton, Richmond, St-Hubert, Toronto Canadian Logistics Centre 3220 Caravelle Drive Mississauga, ON L4V 1K9 Tel: 1-800-565-6699 Tel: (905) 678-2700 Fax: (905) 678-0575 Fax: 1-800-661-6699 Training Facilities CALGARY Bay 288 2880 - 45th Ave. South East Calgary, AB T2B 3M1 Tel: (403) 214-3130 Fax: (403) 243-4770 EDMONTON 12825 -144th Street Bonaventure Industrial Park Edmonton, AB T5L 4N7 Tel: (780) 453-3561

MONTRÉAL 825, rue Bancroft Pointe-Claire, QC H9R 4L6 Tel: (514) 697-4790 Fax: (514) 697-9529 RICHMOND 2551 Viking Way, Unit 100 Richmond, BC V6V 1N4 Tel: (604) 273-3711 Fax: (604) 273-7314 TORONTO 19 Waterman Avenue Toronto ON M4V 1Y2 Tel: (416) 752-8020 Fax: (416) 752-6230 WINNIPEG 21 Omands Creek Blvd. Winnipeg, MB R2R 2V2 Tel: (204) 488-2305 Fax: (204) 488-7465

Schneider Electric Schneider Canada Services 6675 Rexwood Road Mississauga, Ontario L4V 1V1 www.schneider-electric.ca/services Tel: (905) 678-7000 Fax: (905) 678-0145

Head Office 19 Waterman Avenue Toronto, Ontario M4B 1Y2 www.schneider-electric.ca Tel: (416) 752-8020 Fax: (416) 752-6230

200

7 S

chn

eide

r C

anad

a. A

ll R

ight

s R

ese

rve

dC

May 2007

S0180IM0701EP R0