HIGH VACUUM OIL PURIFIER...HIGH VACUUM OIL PURIFIER 11 Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HIGH VACUUM OIL PURIFIER...HIGH VACUUM OIL PURIFIER 11 Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic

HIGH VACUUM OIL PURIFIER

10HIGH VACUUM OIL PURIFIER

Page 2: HIGH VACUUM OIL PURIFIER...HIGH VACUUM OIL PURIFIER 11 Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic

11HIGH VACUUM OIL PURIFIER

Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic action of the materials within the transformer, result in oxidation and cracking of the oil. The byproducts of oxidation acids, peroxide, sludge and asphaltene with the long-term effect of these byproducts resulting in an exponential increase in deterioration of the transformer and its oil. The resulting sludge buildup reduces the cooling effects of the oil driving the whole decay mechanism at an increasingly accelerated rate. The acidity or neutralization number (ASTM D-874)in the transformer becomes critical once 0.25 mg KOH/g oil level has been reached. Preventive measures must be undertaken prior to the oil acidity level reaching this point. Generally, the larger the transformer plate rating, the lower the acid number that triggers regeneration of the oil. Transformers with high acid levels require the oil to be further treated with a Fullers Earth filtration system or Regenesys reusable filter media.

Transformer Oil is not destroyed by being used, but becomes contaminated with particulates, moisture, and dissolved gasses which can be removed from the oil by the vacuum treatment method.

The Regenesys VHS series HIGH VACUUM DEHYDRATION OIL PURIFICATION SYSTEM provides an extremely cost-effective and environmentally acceptable method of extending transformer oil lifetime to over 100 years!

50/60Hz, 1-Phase

220V, 50/60Hz, 1-Phase

380V, 50/60Hz, 3-Phase

460V, 50/60Hz, 3-Phase

ALSO AVAILABLE:

DBPC Additive tankCustom SCADA and HMI interfacesOnboard office/laboratoryRemote control and monitoring

MOBILITY OPTIONS:

Skid Mounted

Trailer Mounted

Sea Container

Customized trailers

VOLTAGES

120V,

ENEMIES OF TRANSFORMER OIL

Hydrocarbons + Oxygen + Catalyst = Decay products of Oxidation

Page 3: HIGH VACUUM OIL PURIFIER...HIGH VACUUM OIL PURIFIER 11 Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic

12HIGH VACUUM OIL PURIFIER

The Regenesys VSH is designed to effectively remove dissolved, emulsified and free water, particulate, and contaminants. The high performance VHS removes 100% of free and emulsified water, air, and gases. Dissolved gases are reduced to less the 5ppm of water, from 12% gases to less than 0.25% , and particulate to an nominal value dependant on final filtration spec. on a single pass.

This is done by pulling ambient or elevated temperature oil into the unit. The oil flows through the pre –filter media before flowing into the circulation heater where the temperature is raised to 150°F ( 66°C). Oil flows from the heater into the vacuum chamber where it is exposed to a vacuum, normally 1 to 3 Torr. At this vacuum the boiling point of water is approx 40° F effectively boiling off the water and dissolved gas creating a dehydrated oil. An oil discharge pump removes the oil from the vacuum chamber and passes it through a high efficiency particulate filter rated to your spec. and then back into the transformer.

MODEL FLOW RATE (US GPH) FLOW RATE LTR/HR

VSH-100 100 380

VSH-200 200 750VSH-500 500 1900

VSH-1000 1000 3700VSH-1500 1500 5700VSH-2000 2000 7500VSH-3000 3000 11000

VSH-4000 4000 15000

Custom sizes also available

SYSTEM PRINCIPLES

Page 4: HIGH VACUUM OIL PURIFIER...HIGH VACUUM OIL PURIFIER 11 Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic

Mobile ON-SITE Services - Machine RentalsDEGASIFIERS, PCB - DECONTAMINATION

UNITS, TRANSFER PUMPING UNITS.

TRANFORMER OIL REGENERATION UNITS

SF-6 Gas Purification Units of any size.

We also provide:• Panel Design/Build

• Electrical Design of Processing Equipment

• PLC Programming, A/B, Siemens, ABB and

Omron

• HMI (Human Machine Interface) Programming

• Troubleshooting and Repairs to your

Regeneration Units and Reactivation Units

• Instrumentation Verification

• Rebuilding and Servicing of Vacuum Systems

• Upgrades to the fore mentioned Units

• Parts Sales

• Remote Access Systems

• Solar Upgrade Systems for Control Systems

OIL AND GAS PURIFICATION EXPERTS

Page 5: HIGH VACUUM OIL PURIFIER...HIGH VACUUM OIL PURIFIER 11 Transformer oils deteriorate with time. High operating temperatures, the presence of oxygen and water combined with the catalytic

FOR WORLD CLASS EQUIPMENT & SERVICES

YOUR CONTAMINATED LUBRICANTS

CONTACT US

1365 Bonhill RoadMississauga, Ontario, Canada,L5T 1M11-905-564-0044 Phone1-905-564-6061 Fax