WN BRAZIER ASSOCIATES INC. SUKARI GOLD PROJECT EMERSON ENGINEERING INC. HFO SERVICE TANK - HT003 DATA SHEET R1.xls Sheet 1 of 5 TANK NAME: HFO Service Tank (HT003) PRODUCT STORED: HFO DATA SHEET NUMBER: 5 DESIGNED BY: D.E. DATE: 27Oct/08 REVISION NO.: 0 1 REVISION DATE: 17/10/08 27Oct/08 TANK GENERAL ARRANGEMENT DRAWING: 621-10-M-2004 TANK DESIGN DATA OPERATING CONDITIONS Tank Capacity m3 - Normal: 106 m3 Working m3: Diameter: 4400 ID Shell Height: 6650 Ambient Temperature Range, °C: +15 to +46°C Operating Temperature Range °C Max 90°C Tank Is Heated )Yes/No): Product S.G.: 0.995 @ 15°C Flash Point °C: Min 65°C Normal Flow In, m3/h Normal Flow Out, m3/h Maximum Flow In, m3/h Maximum Flow Out, m3/h Product Vapour Pressure: kPa @ °C Pressure Vent Set @ N/A kPa Vacuum Vent Set @ N/A kPa DESIGN CONDITIONS Design Tank Pressure: Atmospheric S.G. Design Wind Load: 1.23 kPa Altitude: 350 m Above Mean Sea Level Tank Operating Design Temperature Range: Design for Max 110°C Seismic Design: Refer to Site Conditions Plate=S235JR36 (Steel 37) Design Code: API 650 Appendix A DETAILED DESIGN DATA See General Arrrangement Dwg No.: 621-10-M-2004 Shop or Field Fabrication: Field Lifting Lugs (Yes/No): No Shell Design: API 650 10th Ed Add. 4 2005 Plate Thickness, mm per Strake 6mm Plate Size, mm Length X Height: as indicated Joints (Butt/Lap): Lap Shell Corrosion Allowance: 1 mm Joint Efficiency: 0.85 See calculation sheets Roof Type (Supported or Self Supporting): Cone Type, Self Supporting Roof Joints (Butt/Lap): Lap Roof Plate Thickness, mm: 6mm Roof Slope, mm/m: min 19:305 Roof Corrosion Allowance, mm: 1 mm Roof Self Supporting (Yes/No): Yes Roof Structural Members: No Roof Live Load, kPa: Roof Dead (Insulation) Load, kPa: Roof Guard Rail: Yes Roof Access Stair/Ladder: Ladder, see drawings Roof Platform or Walkway: Yes, from ladder to centre of tank. Roof Insulation (Yes/No): Yes Wind Girders: Remove Erecting Framing For Self Supporting Roof (Yes/No): Bottom plate Thickness, mm: 9mm Bottom Joints (Butt/Lap): Lap Bottom Slope (Yes/No): Yes Slope mm/m: 25mm:305mm From/To Centre: To Centre Sump Bottom Corrosion Allowance, mm: 2 mm minimum Bottom Special Features (sump, etc.): Sump, with internal pipe from drain to sump with inverted elbow over sump. See detail. Anchor bolts required, see calculation sheet. Tank Insulation (Yes/No): Yes, Mineral Wool Fibre WithAl Cladding Insulation Thickness 50 mm Paint, Exterior: Yes Colour: White Interior: No Nozzles/Manhole: Yes, See drawings Internal Piping: Yes, See Drawings Nozzles/Manhole: Yes, See drawings Internal Heaters (Yes/No) Yes Steam Coils or Electric Heating: Steam, see drawing 621-10-M-2024 QUALITY CONTROL Weld Inspection (Radiograph/Vacuum Box/Dye Penetrant): See drawings Mill Test Reports Required (Yes/No): Quality Control Standard: Fabricator to submit QA program for Owner's Approval Testing: See Drawing No.: 621-10-M-2004 SUKARI GOLD PROJECT POWER PLANT TANK FARM

hfo service tank - ht003 data sheet r1.pdf

Embed Size (px)

Citation preview

Page 1: hfo service tank -  ht003 data sheet r1.pdf

WN BRAZIER ASSOCIATES INC. SUKARI GOLD PROJECT EMERSON ENGINEERING INC.

HFO SERVICE TANK - HT003 DATA SHEET R1.xlsSheet 1 of 5

TANK NAME: HFO Service Tank (HT003) PRODUCT STORED: HFODATA SHEET NUMBER: 5 DESIGNED BY: D.E. DATE: 27Oct/08REVISION NO.: 0 1REVISION DATE: 17/10/08 27Oct/08TANK GENERAL ARRANGEMENT DRAWING: 621-10-M-2004

TANK DESIGN DATAOPERATING CONDITIONS

Tank Capacity m3 - Normal: 106 m3 Working m3:Diameter: 4400 ID Shell Height: 6650Ambient Temperature Range, °C: +15 to +46°C Operating Temperature Range °C Max 90°CTank Is Heated )Yes/No):Product S.G.: 0.995 @ 15°C Flash Point °C: Min 65°CNormal Flow In, m3/h Normal Flow Out, m3/hMaximum Flow In, m3/h Maximum Flow Out, m3/hProduct Vapour Pressure: kPa @ °CPressure Vent Set @ N/A kPaVacuum Vent Set @ N/A kPa

DESIGN CONDITIONSDesign Tank Pressure: Atmospheric S.G.Design Wind Load: 1.23 kPa Altitude: 350 m Above Mean Sea LevelTank Operating Design Temperature Range: Design for Max 110°CSeismic Design: Refer to Site Conditions Plate=S235JR36 (Steel 37)Design Code: API 650 Appendix A

DETAILED DESIGN DATASee General Arrrangement Dwg No.: 621-10-M-2004Shop or Field Fabrication: Field Lifting Lugs (Yes/No): NoShell Design: API 650 10th Ed Add. 4 2005Plate Thickness, mm per Strake 6mmPlate Size, mm Length X Height: as indicatedJoints (Butt/Lap): Lap Shell Corrosion Allowance: 1 mmJoint Efficiency: 0.85 See calculation sheets

Roof Type (Supported or Self Supporting): Cone Type, Self SupportingRoof Joints (Butt/Lap): Lap Roof Plate Thickness, mm: 6mmRoof Slope, mm/m: min 19:305 Roof Corrosion Allowance, mm: 1 mmRoof Self Supporting (Yes/No): YesRoof Structural Members: No

Roof Live Load, kPa: Roof Dead (Insulation) Load, kPa:Roof Guard Rail: Yes Roof Access Stair/Ladder: Ladder, see drawingsRoof Platform or Walkway: Yes, from ladder to centre of tank.Roof Insulation (Yes/No): YesWind Girders:Remove Erecting Framing For Self Supporting Roof (Yes/No):

Bottom plate Thickness, mm: 9mm Bottom Joints (Butt/Lap): LapBottom Slope (Yes/No): Yes Slope mm/m: 25mm:305mm From/To Centre: To Centre SumpBottom Corrosion Allowance, mm: 2 mm minimumBottom Special Features (sump, etc.): Sump, with internal pipe from drain to sump with inverted elbow over sump. See detail.Anchor bolts required, see calculation sheet.Tank Insulation (Yes/No): Yes, Mineral Wool Fibre WithAl Cladding Insulation Thickness 50 mmPaint, Exterior: Yes Colour: White Interior: NoNozzles/Manhole: Yes, See drawingsInternal Piping: Yes, See DrawingsNozzles/Manhole: Yes, See drawingsInternal Heaters (Yes/No) Yes Steam Coils or Electric Heating: Steam, see drawing 621-10-M-2024

QUALITY CONTROLWeld Inspection (Radiograph/Vacuum Box/Dye Penetrant): See drawingsMill Test Reports Required (Yes/No):Quality Control Standard: Fabricator to submit QA program for Owner's ApprovalTesting: See Drawing No.: 621-10-M-2004

SUKARI GOLD PROJECT POWER PLANT TANK FARM

Page 2: hfo service tank -  ht003 data sheet r1.pdf

SukariShell Plate Calculation

Calculation of thickness by API 650 1-foot methodtank diameter<200'td Design Shell Thicknesstt Hydrostatic test shell thicknessD Nominal tank diameterH Design liquid level in feet, hieght from the bottom of the course

under consideration to maximum fluid levelG design specific gravityCA corosion allowanceSd allowable stress for design condition (API 650 3.6.2.1)St allowable stress for hydrostatic condition (API 650 3.6.2.2)

Basic formulatd= 2.6*D(H-1)G +CA

tt= 2.6*D(H-1)

Tank # HT003Tank DataMaterial S235JR

metric imperialD 4400 mm 14.44 ftH 6650 mm 21.82 ftG 0.995 0.995CAs 1 mm 0.0394 in CAF=2mm CAR=1mmSd 151855.6 Kpa 22040 psiSt 162983 KPa 23655 psiCir. 13823.01 mm 45.3511 ftmm/o 38.39724

Plate thickness based on lowest coursetd= 0.074644 intt= 0.033031 in

Shell plate shall be 3/16" plus corrosion allowance thus use 0.250 (1/4") 6 mmFloor plate shall be 1/4" plus corrosion allowance use 0.329 (3/8") 9 mm

Shell will consist of 2-2440mm courses, 1 -1770mm course

Roof plate: 1mm corrosion allowance specified, outdoor use. Recommend using 6mm plate.Rafters not required

Height of unstiffened shell = 9.47t((t/d)3).5= 90.47927 mStiffener not required

Sd

St

Dale R. Emerson, M.E., P.Eng.

Plate Calcs HT003 Emerson Engineering Inc. Oct. 27/08

Page 3: hfo service tank -  ht003 data sheet r1.pdf

Note all dimensions in imperial unless specified otherwise

t= 2.6hpDGsE

Where: t= Plate thickness for course under considerationhp= Liquid hieght from top capacity level to bottom of course under considerationD= Nominal diameterG= Specific gravitys= Allowable design stressE= Joint efficiency

CA= Corrosion allowance

Tank #D= 14.50 ft 4400 mmG= 1.0s= 22040 psiE= 0.85

CA= 0.039 in.H= 21.82 ft 6650 mm

Tank hieght is 6650mm or 21.82'. This suggests 3 shell courses as follows: course 1 @8', course 2 @8', course 3 @5.82' Top capacity level is tcp= 21.82 6650 mmThen hp= course 1= 21.82 course 2= 13.82 course 3= 5.82

The calculated plate thickness requirements are as follows (the min allowable is 3/16"):

Course 1= 2.6hpDG= 0.043686 in. Min.plate= 0.18750sE

Minimum plate plus corrosion allowance is 0.2268701 in. or 1/4" plate

Course 2= 2.6hpDG= 0.027667 in. Min.plate= 0.1875sE

Minimum plate plus corrosion allowance is 0.2268701 in. or 1/4" plate

Course 3= 2.6hpDG= 0.011649 in. Min.plate= 0.1875sE

Minimum plate plus corrosion allowance is 0.2268701 in. or 1/4" plate

Roof plate: 1mm corrosion allowance specified, outdoor use. Recommend using 1/4" plate Rafters no required

Basic formula

HT003

AWWA shell plate tickness calculation

Page 4: hfo service tank -  ht003 data sheet r1.pdf

Sukari Tank Constraint Calculations

Design Criteria Date: October 27/08 Plate = S235JR Wind = 160kphTank # HT003 Location - Outside 0.10 M liters

Water Mass 62.4 lbf/ft3 Wind Load 25.6 lbf/ft2 Weight of Roof W r 1753 lbTank Diameter 14.4 ft Shell Surface Area 989 ft2 Slosh Mass W1 191356.8 lbTank Height 21.8 ft Appurtenances 1000 lb 1st Mode Mass W2 47249 lbFluid Height 21.8 ft Center of Gravity Xs 7.3 ft Site Amp Factor S 1Tank Circum. 45.4 ft Zonal Coef. Z 0.075 Diam./Height D/H 0.66Floor Plate 3/8" 2046 lb Use Factor I 1 W1/WT 0.81Shell Plate 1/4" 10092 lb Force Red. Coef. Rw 3.5 W2/WT 0.2Roof Plate 1/4" 1753 lb C1 0.074 X1/H 0.41Tank& Contents Wt 236243 lb kp 0.59 X2/H 0.8Weight of Shell Ws 12138 lb Tw 1st Mode 2.24 Lateral centroid to W1 (X1) 8.9 ftSpecific Gravity G 0.995 Wave Period Lateral centroid to W2 (X2) 17.5 ftThickness of annulus Tb 0.375 in. Yield Strength 34200 lbf Roof load Wrs 10.2 lb/ftShell overturn resit WL 2552.6 Roof/shell resit WT 277.9

(S.A./2) *wind load*C.O.G.= 92106 ft-lbf

71655 ft-lbf Equation 3-21

Restraint is required if the wind moment>(2/3)Deadload resisting moment excluding contentsAnchor bolts required for wind loading

123308 ft-lbf Equation 13-8

Resistance to Overturning due to seismic forcesEquation13-15

WL= 2552.6 Equation 13-12Wt= 277.9 Equation 13-18

0.209 Anchor bolts not required for siesmic loading

Tank Volume=

Uplift will not occur if the following is satisfied

Seismic Moment =

[M/D2(Wt+WL)] =

[M/D2(Wt+WL)] ! 0.785

2/3 Overturn Resisting Moment=

Wind Moment =

Dale R.Emerson, M.E.,P.Eng.

Siesmic Calculations HT003 Emerson Engineering Inc. Oct. 27/08