WN BRAZIER ASSOCIATES INC. SUKARI GOLD PROJECT EMERSON ENGINEERING INC.
HFO SERVICE TANK - HT003 DATA SHEET R1.xlsSheet 1 of 5
TANK NAME: HFO Service Tank (HT003) PRODUCT STORED: HFODATA SHEET NUMBER: 5 DESIGNED BY: D.E. DATE: 27Oct/08REVISION NO.: 0 1REVISION DATE: 17/10/08 27Oct/08TANK GENERAL ARRANGEMENT DRAWING: 621-10-M-2004
TANK DESIGN DATAOPERATING CONDITIONS
Tank Capacity m3 - Normal: 106 m3 Working m3:Diameter: 4400 ID Shell Height: 6650Ambient Temperature Range, °C: +15 to +46°C Operating Temperature Range °C Max 90°CTank Is Heated )Yes/No):Product S.G.: 0.995 @ 15°C Flash Point °C: Min 65°CNormal Flow In, m3/h Normal Flow Out, m3/hMaximum Flow In, m3/h Maximum Flow Out, m3/hProduct Vapour Pressure: kPa @ °CPressure Vent Set @ N/A kPaVacuum Vent Set @ N/A kPa
DESIGN CONDITIONSDesign Tank Pressure: Atmospheric S.G.Design Wind Load: 1.23 kPa Altitude: 350 m Above Mean Sea LevelTank Operating Design Temperature Range: Design for Max 110°CSeismic Design: Refer to Site Conditions Plate=S235JR36 (Steel 37)Design Code: API 650 Appendix A
DETAILED DESIGN DATASee General Arrrangement Dwg No.: 621-10-M-2004Shop or Field Fabrication: Field Lifting Lugs (Yes/No): NoShell Design: API 650 10th Ed Add. 4 2005Plate Thickness, mm per Strake 6mmPlate Size, mm Length X Height: as indicatedJoints (Butt/Lap): Lap Shell Corrosion Allowance: 1 mmJoint Efficiency: 0.85 See calculation sheets
Roof Type (Supported or Self Supporting): Cone Type, Self SupportingRoof Joints (Butt/Lap): Lap Roof Plate Thickness, mm: 6mmRoof Slope, mm/m: min 19:305 Roof Corrosion Allowance, mm: 1 mmRoof Self Supporting (Yes/No): YesRoof Structural Members: No
Roof Live Load, kPa: Roof Dead (Insulation) Load, kPa:Roof Guard Rail: Yes Roof Access Stair/Ladder: Ladder, see drawingsRoof Platform or Walkway: Yes, from ladder to centre of tank.Roof Insulation (Yes/No): YesWind Girders:Remove Erecting Framing For Self Supporting Roof (Yes/No):
Bottom plate Thickness, mm: 9mm Bottom Joints (Butt/Lap): LapBottom Slope (Yes/No): Yes Slope mm/m: 25mm:305mm From/To Centre: To Centre SumpBottom Corrosion Allowance, mm: 2 mm minimumBottom Special Features (sump, etc.): Sump, with internal pipe from drain to sump with inverted elbow over sump. See detail.Anchor bolts required, see calculation sheet.Tank Insulation (Yes/No): Yes, Mineral Wool Fibre WithAl Cladding Insulation Thickness 50 mmPaint, Exterior: Yes Colour: White Interior: NoNozzles/Manhole: Yes, See drawingsInternal Piping: Yes, See DrawingsNozzles/Manhole: Yes, See drawingsInternal Heaters (Yes/No) Yes Steam Coils or Electric Heating: Steam, see drawing 621-10-M-2024
QUALITY CONTROLWeld Inspection (Radiograph/Vacuum Box/Dye Penetrant): See drawingsMill Test Reports Required (Yes/No):Quality Control Standard: Fabricator to submit QA program for Owner's ApprovalTesting: See Drawing No.: 621-10-M-2004
SUKARI GOLD PROJECT POWER PLANT TANK FARM
SukariShell Plate Calculation
Calculation of thickness by API 650 1-foot methodtank diameter<200'td Design Shell Thicknesstt Hydrostatic test shell thicknessD Nominal tank diameterH Design liquid level in feet, hieght from the bottom of the course
under consideration to maximum fluid levelG design specific gravityCA corosion allowanceSd allowable stress for design condition (API 650 3.6.2.1)St allowable stress for hydrostatic condition (API 650 3.6.2.2)
Basic formulatd= 2.6*D(H-1)G +CA
tt= 2.6*D(H-1)
Tank # HT003Tank DataMaterial S235JR
metric imperialD 4400 mm 14.44 ftH 6650 mm 21.82 ftG 0.995 0.995CAs 1 mm 0.0394 in CAF=2mm CAR=1mmSd 151855.6 Kpa 22040 psiSt 162983 KPa 23655 psiCir. 13823.01 mm 45.3511 ftmm/o 38.39724
Plate thickness based on lowest coursetd= 0.074644 intt= 0.033031 in
Shell plate shall be 3/16" plus corrosion allowance thus use 0.250 (1/4") 6 mmFloor plate shall be 1/4" plus corrosion allowance use 0.329 (3/8") 9 mm
Shell will consist of 2-2440mm courses, 1 -1770mm course
Roof plate: 1mm corrosion allowance specified, outdoor use. Recommend using 6mm plate.Rafters not required
Height of unstiffened shell = 9.47t((t/d)3).5= 90.47927 mStiffener not required
Sd
St
Dale R. Emerson, M.E., P.Eng.
Plate Calcs HT003 Emerson Engineering Inc. Oct. 27/08
Note all dimensions in imperial unless specified otherwise
t= 2.6hpDGsE
Where: t= Plate thickness for course under considerationhp= Liquid hieght from top capacity level to bottom of course under considerationD= Nominal diameterG= Specific gravitys= Allowable design stressE= Joint efficiency
CA= Corrosion allowance
Tank #D= 14.50 ft 4400 mmG= 1.0s= 22040 psiE= 0.85
CA= 0.039 in.H= 21.82 ft 6650 mm
Tank hieght is 6650mm or 21.82'. This suggests 3 shell courses as follows: course 1 @8', course 2 @8', course 3 @5.82' Top capacity level is tcp= 21.82 6650 mmThen hp= course 1= 21.82 course 2= 13.82 course 3= 5.82
The calculated plate thickness requirements are as follows (the min allowable is 3/16"):
Course 1= 2.6hpDG= 0.043686 in. Min.plate= 0.18750sE
Minimum plate plus corrosion allowance is 0.2268701 in. or 1/4" plate
Course 2= 2.6hpDG= 0.027667 in. Min.plate= 0.1875sE
Minimum plate plus corrosion allowance is 0.2268701 in. or 1/4" plate
Course 3= 2.6hpDG= 0.011649 in. Min.plate= 0.1875sE
Minimum plate plus corrosion allowance is 0.2268701 in. or 1/4" plate
Roof plate: 1mm corrosion allowance specified, outdoor use. Recommend using 1/4" plate Rafters no required
Basic formula
HT003
AWWA shell plate tickness calculation
Sukari Tank Constraint Calculations
Design Criteria Date: October 27/08 Plate = S235JR Wind = 160kphTank # HT003 Location - Outside 0.10 M liters
Water Mass 62.4 lbf/ft3 Wind Load 25.6 lbf/ft2 Weight of Roof W r 1753 lbTank Diameter 14.4 ft Shell Surface Area 989 ft2 Slosh Mass W1 191356.8 lbTank Height 21.8 ft Appurtenances 1000 lb 1st Mode Mass W2 47249 lbFluid Height 21.8 ft Center of Gravity Xs 7.3 ft Site Amp Factor S 1Tank Circum. 45.4 ft Zonal Coef. Z 0.075 Diam./Height D/H 0.66Floor Plate 3/8" 2046 lb Use Factor I 1 W1/WT 0.81Shell Plate 1/4" 10092 lb Force Red. Coef. Rw 3.5 W2/WT 0.2Roof Plate 1/4" 1753 lb C1 0.074 X1/H 0.41Tank& Contents Wt 236243 lb kp 0.59 X2/H 0.8Weight of Shell Ws 12138 lb Tw 1st Mode 2.24 Lateral centroid to W1 (X1) 8.9 ftSpecific Gravity G 0.995 Wave Period Lateral centroid to W2 (X2) 17.5 ftThickness of annulus Tb 0.375 in. Yield Strength 34200 lbf Roof load Wrs 10.2 lb/ftShell overturn resit WL 2552.6 Roof/shell resit WT 277.9
(S.A./2) *wind load*C.O.G.= 92106 ft-lbf
71655 ft-lbf Equation 3-21
Restraint is required if the wind moment>(2/3)Deadload resisting moment excluding contentsAnchor bolts required for wind loading
123308 ft-lbf Equation 13-8
Resistance to Overturning due to seismic forcesEquation13-15
WL= 2552.6 Equation 13-12Wt= 277.9 Equation 13-18
0.209 Anchor bolts not required for siesmic loading
Tank Volume=
Uplift will not occur if the following is satisfied
Seismic Moment =
[M/D2(Wt+WL)] =
[M/D2(Wt+WL)] ! 0.785
2/3 Overturn Resisting Moment=
Wind Moment =
Dale R.Emerson, M.E.,P.Eng.
Siesmic Calculations HT003 Emerson Engineering Inc. Oct. 27/08