terminal with 2 clamping units per pole 5-pole per pole 8 x 0,75 mm² f, 6 x 1,5 mm² sol / f, 4 x 2,5 mm² sol / f, 2 x 4 mm² sol / f cable entries via knockouts, order ASS separately (see cable entry systems LES) "weatherproof" resistant to weather influences (UV due to solar radiation, protected against rainwater, temperature resistant, impact resistant, etc.) saltwater-proof "offshore applications" lid fasteners sealable without accessories retaining strap and external brackets for wall fixing included colour: black, RAL 9011 rated insulation voltage U i = 690 V a.c./d.c. current carrying capacity 20 A tightening torque for terminal 0,5 Nm material PC-GFS (polycarbonate) Degree of protection: IP 66 / IP 67 temporary submersion up to 1 meter, max. 15 minutes width 93 mm height: 93 mm depth 62 mm Weight 0,137 kg in accordance with IEC 60670-22 in accordance with DNV GL - Certificate No: TAE00000EE Russian Maritime Register of Shipping, technical documentation is approved by the letter No. 250-A-1180-108795 Drawings Dimension drawing ”Weatherproof“ for outdoor installation KF 0202 B 1.5-2.5 mm², Cu 3~ Page 1 of 3 Gustav Hensel GmbH & Co. KG * Gustav -Hensel-Str. 6 * 57368 Lennestadt * Germany * Telef on: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: January 4. 2017

hensel demo pdf - Farnell element14 › datasheets › 2256948.pdf · Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0

  • Upload
    others

  • View
    29

  • Download
    0

Embed Size (px)

Citation preview

Page 1: hensel demo pdf - Farnell element14 › datasheets › 2256948.pdf · Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0

terminal with 2 clamping units per pole5-pole per pole 8 x 0,75 mm² f, 6 x 1,5 mm² sol / f, 4 x 2,5 mm² sol / f, 2 x 4 mm² sol / fcable entries via knockouts, order ASS separately (see cable entry systems LES)"weatherproof" resistant to weather influences (UV due to solar radiation, protected against rainwater, temperature resistant,impact resistant, etc.)saltwater-proof"offshore applications"lid fasteners sealable without accessoriesretaining strap and external brackets for wall fixing includedcolour: black, RAL 9011

rated insulation voltage Ui = 690 V a.c./d.c.

current carrying capacity 20 A

tightening torque for terminal 0,5 Nm

material PC-GFS (polycarbonate)

Degree of protection: IP 66 / IP 67 temporary submersion up to 1 meter, max. 15 minutes

width 93 mm

height: 93 mm

depth 62 mm

Weight 0,137 kg

in accordance with IEC 60670-22

in accordance with DNV GL - Certificate No: TAE00000EE Russian Maritime Register of Shipping, technical documentation isapproved by the letter No. 250-A-1180-108795

Drawings

Dimension drawing

”Weatherproof“ for outdoor installation

KF 0202 B1.5-2.5 mm², Cu 3~

Page 1 of 3Gustav Hensel GmbH & Co. KG * Gustav -Hensel-Str. 6 * 57368 Lennestadt * Germany * Telef on: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: January 4. 2017

Page 2: hensel demo pdf - Farnell element14 › datasheets › 2256948.pdf · Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0

Detail mass

Box walls

Operating and ambient conditionsApplication area Suitable for for outdoor installation (harsh environment and/or

outdoor). To reduce the formation and accumulation of condensed water seetechnical information.

Resistant to occasional cleaning procedures (direct jet)

Ambient temperature Average value over 24 hours + 55 °C Maximum value + 70 °C Minimum value - 25 °C

Relative humidity 50% at 40° C short-time 100% at 25° C

Fire protection in the event of internal faults Demands placed on electrical devices from standards and laws Minimum requirements - Glow wire test in accordance with IEC 60695-2-11: - 650°C for boxes and cable glands

”Weatherproof“ for outdoor installation

KF 0202 B1.5-2.5 mm², Cu 3~

Page 2 of 3Gustav Hensel GmbH & Co. KG * Gustav -Hensel-Str. 6 * 57368 Lennestadt * Germany * Telef on: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: January 4. 2017

Page 3: hensel demo pdf - Farnell element14 › datasheets › 2256948.pdf · Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0

- 650°C for boxes and cable glands - 850°C for parts of insulating material necessary to retain currentcarrying parts in position

Burning behaviour Glow wire test IEC 60695-2-11: 960 °C UL Subject 94: V-0 flame-retardant self-extinguishing

Degree of protection against mechanical load IK09 (10 Joule)

Toxic behaviour halogen-free silicone-free "halogen-free" in accordance with the examination of the cablesand insulated wires - corrosiveness of fumes - as per IEC 60 754-2

Note: For material properties see technical data.

”Weatherproof“ for outdoor installation

KF 0202 B1.5-2.5 mm², Cu 3~

Page 3 of 3Gustav Hensel GmbH & Co. KG * Gustav -Hensel-Str. 6 * 57368 Lennestadt * Germany * Telef on: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: January 4. 2017