Installation and maintenance manual
HEF2 SeriesEvaporative Humidifiers for Air Handling Units (A.H.U.)
In compliance with European Union Standards for machinery safety, it is essential to read this manual
in detail before installing units.
MH
EF2
-EN
-16-
2
HEF2 SeriesInstallation and maintenance manual
04 General description
05 Assembly of accessories delivered as parts (Recirculated Water)
06 Assembly of accessories delivered as parts (Direct Water)
07 Mechanical design, operating principles and list of components HEF2 Series (recirculated water, standard on/off)
09 Mechanical design, operating principles and list of components HEF2 Series-DW (direct water, standard on/off)
11 Mechanical design, operating principles and list of components HEF2 Series (recirculated water with stage control)
14 Mechanical design, operating principles and list of components HEF2 Series-DW (direct water, stage control)
16 Installation requirements
17 Connections, settings and regulations
18 Connections and Settings/Regulations Made (Standard - Recirculated Water)
19 Dimensional drawing HEF2 Series (Recirculated Water). Manual drain ball valve (standard)
20 Dimensional drawing HEF2 Series (Recirculated Water). Motor-zone Drain Valve (optional)
21 A Connection to the water supply for filling the water tank
22 B Connecting the drain to the water trap
23 C Electricity connection of the Fisair recirculation pump
25 D Level detector electricity connection
26 E Setting valves regulating evaporative cassette irrigation flow
26 F Adjusting the constant bleed-off regulation valve
27 Connections and settings/regulations made (Standard – Direct Water)
28 HEF2 Series-DW (Direct Water) Water supply and basin draining dimensional drawing
29 A Connection to the water supply
Contents
3
30 B Connecting the drain to the water trap
30 E Setting of the irrigation valves in each evaporative cassette
31 Connections and settings/regulations made (Optional accessories for recirculated water)
32 Connections and settings/regulations made (Optional accessories for direct water)
33 A Connection of the 24V or 230V water tank filling N.C. solenoid valve
34 B Connection of the N.C. motor-zone valve for automatic draining of the HEF2 Series (recirculated water)
40 C Flexible connector for the water supply
40 D External rigid connector for the water supply
40 E External rigid connector for draining
41 F U.V. lamp disinfection system
42 G Perimeter closure cover plates
43 H Solenoid valve(s) connection for stage control
44 J HEF2 Series-DW for duct
46 K Piping system in stainless steel
46 N Connection of the 3-way motor-zone valve to manage the water supply and the emptying of the manifold/irrigation system
46 O Motor-zone valve for emptying of the manifold/irrigation system
47 Installation and recommendations
47 Maintenance
48 Cleaning and disinfection
49 Hygiene certificate
50 LATERAL Disassembly
55 FRONT Disassembly
57 Cleaning the individual irrigation system
59 HEF2 Series List of spare parts
4HEF2 Series Installation and maintenance manual
General description
EVAPORATIVE HUMIDIFIER OPERATING PRINCIPLES
FISAIR evaporative humidifiers are units designed to increase the water vapour content of the treated air, by making use of the natural evaporation of water from its liquid phase. The air supply being treated is passed through a cellular panel dampened using an irrigation system. This panel is composed of undulating sheets of inorganic paper with stiffening and water absorbent additives.
The layout, as channels criss-crossing the panel provides a huge surface for water-air contact, which maximises water evaporation, and reduces to a minimum resistance to the movement of the air (pressure drop).
FISAIR evaporative humidifiers work in a similar way to natural processes in rivers, lakes and seas. The vapour added to the air is exclusively pure water vapour.
PROVISIONAL STORAGE
During storage, units must be kept dry and protected from the elements.
Warning: Avoid direct sunlight and sites in which temperatures can exceed 50ºC. Plastic components and derivatives could be deformed.
Thermohygrometric conditions during storage:
Temperature: [-10… 50ºC] Relative humidity: [5… 95%HR] Without condensation
HEF2 Series with recirculation
HEF2 Series with recirculation
5Fisair Air humidity control
1º
2º
½” brass fitting to be attached to the regulation
valve + bleed-off flow meter.
½” PVC-U for connecting/tightening
¾” PVC-U union for connection/tightening
1” PVC-U union for connection/tightening
Assembly of accessories delivered as parts (Recirculated Water)
1.2 Optional: A motorized zone valve is used for draining.
Note: These accessories can only be attached once the equipment is located inside the air handling unit.
1. ASSEMBLY SET (OVERFLOW + DRAINING + DRAINING VALVE)
1.1 Standard: A ball valve is used for draining.
(*) Not necesary with conductivity control.
1º
2º
1” PVC-U union for connection/tightening
¾” PVC-U union for connection/tightening
2. ASSEMBLY SET OF THE CONSTANT BLEED-OFF (*)
6HEF2 Series Installation and maintenance manual
Assembly of accessories delivered as parts (Direct Water)
1. ASSEMBLY Emptying set:
Couple ½ / V PVC-U link onto the drain outlet towards the selected hand of the water drain.
2. ASSEMBLY Water supply solenoid valve set + rigid external connection (if applicable).
Couple ½” Stainless steel link BSP.
7Fisair Air humidity control
Mechanical design, operating principles and list of componentsHEF2 Series (recirculated water, standard on/off)
5
7
421
9C
3
10
E
B6
11
A
MECHANICAL DESIGN
The humidifier comprises the following elements:
A stainless steel self-supporting chassis-water tank structure that houses the unit.
A set of evaporative cassettes of variable sizes and thicknesses, depending on the model and stainless steel surround.
A stainless steel float valve automatic control mechanism for the water supply, to maintain the appropriate level in the water tank, so the unit works correctly. This valve can be regulated in order to set it to the available water pressure in the network.
A stainless steel water tank to hold the water, which is designed so it can be completely emptied by gravity.
A pump for supplying water from the water tank to evaporative panels (technical data on page 23).
A stainless steel mechanism integrated into the water tank acting as an overflow for the system in the event of water level control faults.
A distribution collector + regulation valves with flow meter set to supply the appropriate irrigation individually to the evaporative panels.
A diversion from the water flow to the distribution collector regulates a constant flow of water, which is eliminated from the system in order to maintain a uniform amount of mineral salts in the irrigation water, which we will refer to as the “Constant bleed-off system”. (See page 26).
DROPLET SEPARATOR
Operating conditions giving rise to droplet carry-over, can be handled by adding a second PP profile panel to the humidifiers to capture the droplets being detached from the evaporative panel.
F
8
D G
A. Process air
B. Humidified air
C. Water supply
D. Overflow
E. Constant bleed-off
F. Draining
G. Water outlet to drain (draining + overflow + constant bleed-off)
1. Evaporative cassette
2. Droplet separator cassette (optional)
3. Water recirculation pump
4. Float/ball cock
5. Constant bleed-off + flow meter control valve
6. Panel irrigation + flow meter control valve
7. Filling valve/water tank level control (float valve)
8. Water tank draining valve
9. Filling solenoid valve (optional, supplied loose)
10. Max/min water level detector
11. Cut-off valve (depending on model)
Process air
8HEF2 Series Installation and maintenance manual
OPERATING PRINCIPLES
HEF2 SERIES (Recirculated water, standard on/off)
Water supply
Overflow
Bleed-off
WATER TANK
EVAPORATIVE CASSETTE 2
3
C
F
E
D
8
79
6 6
510
G
A Process air
B Humidified air
C Water supply
D Overflow
E Constant bleed-off
F Draining
GWater outlet to drain (draining + overflow + constant bleed-off)
1 Evaporative cassette
2 Droplet separator (optional)
3 Water recirculation pump
5 Bleed-off regulation valve + flow meter
6 Irrigation regulation valves + flow meter
7Float valve (regulation of supply water)
8 Draining ball valve (standar) (*)
9 Filling solenoid valve (optional, supplied loose)
10 Max/min water level detector
11 Cut-off valve (depending on model)
EVAPORATIVE CASSETTE 1
5
C8D
G
7
E
2
6
1
113
10
B
A
(*) Optionally the ball valve may be replaced by a zone motor-valve.
9Fisair Air humidity control
MECHANICAL DESIGN
The humidifier is composed of the following elements:
A stainless steel self-supporting chassis-water tank structure that houses the unit.
A set of evaporative panels of variable sizes and thicknesses, depending on the model and stainless steel surround.
A stainless steel water tank to hold the water, which is designed so it can be completely emptied by gravity.
A distribution collector + regulation valves with flow meter set to supply the appropriate irrigation individually to the evaporative panels.
DROPLET SEPARATOR
Operating conditions giving rise to droplet carry-over, can be handled by adding a second PP profile panel to the humidifiers to capture the droplets being detached from the evaporative panel.
A. Process air
B. Humidified air
C. Water supply
D. Draining
F. Water outlet to drain (draining + overflow)
1. Evaporative cassette
2. Droplet separator cassette (optional)
3. Panel irrigation control valve + flow meter
4. Water supply solenoid valve (optional, remove valves 5 and 7)
5. Water supply ball valve (standard)
6. Ball valve for manifold draining + water distribution draining (standard) (*)
7. 3-way motor valve for automatic water feeding and automatic emptying of the water manifold + water distribution (optional, remove valves 4, 5 and 6)
(*) Optionally the ball valve may be replaced by a zone motor-valve.
Mechanical design, operating principles and list of componentsHEF2 Series-DW (direct water, standard on/off)
Process air
4
6
5 7C
D1 2
BA
3
10HEF2 Series Installation and maintenance manual
A Process air
B Humidified air
C Water supply
D Draining
1 Evaporative cassette
2 Droplet separator (optional)
3 Irrigation regulation valves + flow meter
4 Water supply ball valve (standard)
5Water supply solenoid valve (optional, remove valves 5 and 7)
6Ball valve for manifold draining + water distribution draining (standard) (*)
7
3-way motor valve for automatic water feeding and automatic emptying of the water manifold + water distribution (optional, remove valves 4, 5 and 6)
WATER TANK
C
D
EVAPORATIVE CASSETTE 1 EVAPORATIVE CASSETTE 2
3
75 4
3
6
OPERATING PRINCIPLE
HEF2 SERIES-DW (Direct water, standard on/off)
Codo D32
45
D
7
3
2
C
A
B
1
6
(*) Optionally the ball valve may be replaced by a zone motor-valve.
11Fisair Air humidity control
Mechanical design, operating principles and list of componentsHEF2 Series (recirculated water with stage control)
MECHANICAL DESIGN
The humidifier is composed of the following elements:
A stainless steel self-supporting chassis-water tank structure that houses the unit.
A set of evaporative panels of variable sizes and thicknesses, depending on the model and stainless steel surround.
A stainless steel float valve automatic control mechanism for the network water supply, to maintain the appropriate level in the water tank, so the unit works correctly. This valve can be regulated in order to set it to the available water pressure in the network.
A stainless steel water tank to hold the water, which is designed so it can be completely emptied by gravity.
A pump for supplying water from the water tank to the evaporative panels (technical data on page 23).
A stainless steel mechanism integrated into the water tank acting as an overflow for the system in the event of water level control faults.
The first stage is controlled with the pump on/off. The irrigation of cassette 1 is controlled.
The other stages are controlled by opening the solenoid valve of each stage.
A distribution collector + regulation valves with flow meter set to supply the appropriate irrigation individually to the evaporative panels.
A diversion from the water flow to the distribution collector regulates a constant flow of water, which is eliminated from the system in order to maintain a uniform amount of mineral salts in the irrigation water, which we will refer to as the “Constant bleed-off system”. (See page 26.)
DROPLET SEPARATOR
Operating conditions giving rise to droplet carry-over, can be handled by adding a second PP profile panel to the humidifiers to capture the droplets being detached from the evaporative panel.
[Note]
Each stage can include the irrigation of more than one cassette. The configuration of stages is variable and defined by the client.
Process air
12HEF2 Series Installation and maintenance manual
A. Process air
B. Humidified air
C. Water supply
D. Overflow
E. Constant bleed-off
F. Draining
G. Water outlet to drain (draining + overflow + constant bleed-off)
1. Evaporative cassette
2. Droplet separator cassette (optional)
3. Water recirculation pump
4. Float/ball
5. Constant bleed-off control valve + flow meter
7. Stage 1 panel irrigation control valve + flow meter
8. Stage 2 panel irrigation control valve + flow meter
9. Stage 2 N.C. solenoid valve
11. Filling/control valve for the water basin level (float valve)
12. Water basin draining valve (**)
13. Filling solenoid valve (optional)
14. Min/max water level detector
15. Cut-off valve (depending on model)
(*) With a maximum of 5 stages for the HEF2E
with 5 cassettes
(**) Optionally the ball valve may be replaced
by a zone motor-valve
BA7
3
8
9
515
G
C
E
11
12
1413
F
D4
1 2
OPERATING PRINCIPLE FOR 2-STAGE CONTROL (*)
512D
G
11
1
8
9
2
7
C
3
14
E B
A
13Fisair Air humidity control
OPERATING PRINCIPLE
HEF2 SERIES (Recirculated water with 2 stage control)
WLD
Water supply
Overflow
Bleed-off
EVAPORATIVE CASSETTE 1
WATER TANK
EVAPORATIVE CASSETTE 2
3
C
E
8
97
5
13 11
12
G
F
D
C Water supply
D Overflow
E Constant bleed-off
F Draining
G Water outlet to drain (draining + overflow + constant bleed-off)
3 Water recirculation pump
5 Bleed-off regulation valve + flow meter
7 Irrigation regulation valve + flow meter (stage 1)
8 Irrigation regulation valve + flow meter (stage 2)
9 N.C. solenoid valve (stage 2)
11 Float valve (supply water regulation)
12 Water tank draining valve
13N.C. filling solenoid valve (optional, supplied loose)
14 Min/max water level detector
14HEF2 Series Installation and maintenance manual
MECHANICAL DESIGN
The humidifier is composed of the following elements:
A stainless steel self-supporting chassis-water tank structure that houses the unit.
A set of evaporative panels of variable sizes and thicknesses, depending on the model and stainless steel surround.
A stainless steel water tank to hold the water, which is designed so it can be completely emptied by gravity.
A distribution collector + regulation valves with flow meter set to supply the appropriate irrigation individually to the evaporative panels.
An N.C. irrigation control solenoid valve for each stage/evaporative cassette.
DROPLET SEPARATOR
Operating conditions giving rise to droplet carry-over, can be handled by adding a second PP profile panel to the humidifiers to capture the droplets being detached from the evaporative panel.
A. Process air
B. Humidified air
C. Water supply
D. Draining
1. Evaporative cassette
2. Droplet separator cassette (optional)
3. Panel irrigation control valve + flow meter
4. Water supply solenoid valve (optional, remove valves 6 and 8)
5. Solenoid valves N.C. for each stage
6. Water supply ball valve (standard)
7. Ball valve for manifold draining + water distribution draining (standard) (*)
8. 3-way motor valve for automatic water feeding and automatic emptying of the water manifold + water distribution (optional, remove valves 4, 6 and 7)
(*) Optionally the ball valve may be replaced by a zone motor-valve.
Mechanical design, operating principles and list of componentsHEF2 Series-DW (direct water, stage control)
B
5
3
4
7
D21
6 8C
A
Process air
15Fisair Air humidity control
46
C
8
3
2
5
1
A
B
Codo D32D
7
(*) Optionally the ball valve may be replaced by a zone motor-valve.
WATER TANK
C
D
5 5
3 3
8
7
4 6
EVAPORATIVE CASSETTE 1 EVAPORATIVE CASSETTE 2
A Process air
B Humidified air
C Water supply
D Draining
1 Evaporative cassette
2 Droplet separator (optional)
3 Irrigation regulation valves + flow meter
4Water supply solenoid valve (optional, remove valves 6 and 8)
5 Solenoid valves N.C. for each stage
6 Water supply ball valve (standard)
7Ball valve for manifold draining + water distribution draining (standard) (*)
8
3-way motor valve for automatic water feeding and automatic emptying of the water manifold + water distribution (optional, remove valves 4, 6 and 7)
16HEF2 Series Installation and maintenance manual
Installation requirements
GENERALITIES
In order to optimize maintenance/installation, humidifiers must be placed on a level waterproof surface, with a drain or run-off, so possible leaks can be dealt with during installation, set up, operation and maintenance.
Assembly inside an air handling unit must ensure the air being treated passes through the evaporative panels, by closing off the perimeters adequately to prevent possible by-passes of the air flow.
All humidifier components are employed downstream, or in other words, in the outlet of the humidified air, as standard.
LOCATION AND SERVICING SPACE
The normal location of the humidifier in the air handling system is after the pre-heating coil and before the cold/heating coil, if there is one. However, the position must be chosen by the project designer.
The area where the water basin is located must be equipped with a peep-hole (minimum diameter of 150 mm) and lighting must be provided to allow periodic visual inspections.
ASSEMBLY OF THE AIR HANDLING UNIT (A.H.U.)
HEF2 Series humidifiers are normally used in conjunction with the air handling unit or A.H.U., after the (pre) heating coil and before the cold and/or (post) heating coil, as shown in the diagram below.
Thermohygrometric operative conditions (*)
Temperature: [5… 40ºC] Relative Humidity: [5… 95%HR]
We recommend allowing for a 500 mm space before and after the unit for inspection and servicing.
Although the humidifying matrix is not combustible, it is advisable to not exceed process air temperatures of 50ºC, in the event that the pump does not work and there is no resulting irrigation, because the irrigation piping material could be deformed.
When the pump works, 40ºC should not be exceeded on the side of the pump.
To ensure complete drying of the cooling pad, after a work period, the air fan of the UTA must be working during the times set out in the following table:
Supply installation
Adiabatic humidification at cold times of year with the best energy efficiency of any humidifying system.
Air Velocity (V) m/s
Aprox. extra working time of the air fan with a temperature
between 20-25ºC
V<2 15 min
2≤V<3 12 min
3≤V<4 9 min
4≤V<5 6 min
(*) Airflow situated at the pump zone or water supply zone.
18HEF2 Series Installation and maintenance manual
CONNECTIONS AND SETTINGS/REGULATIONS MADE(STANDARD - RECIRCULATED WATER)
Connection to the water supply (connection to external water at between 1 and 6 bar)
Connection to drain to the water trap
Electricity connection to the recirculation pump
Electricity connection to the level detector
Setting of the irrigation valves in each evaporative cassette
Constant bleed-off valve setting
500 mm gaps recommended for maintenance
500 mm
G
500 mm
G
B
E FB A C D
A
A
B
C
D
E
F
G
19Fisair Air humidity control
HEF2 Series (RECIRCULATED WATER) Water supply and basin draining dimensional drawing
MANUAL DRAIN BALL VALVE (standard)
(*) 26,5mm for 570 < A < 2075mm 36,5mm for 2175 < A < 2975mm
(**) 150mm for 570 < A < 2075mm 160mm for 2175 < A < 2975mm
(****) 190mm for 570 < A < 2075mm 200mm for 2175 < A < 2975mm
(***) 125mm for 570 < A < 2075mm 135mm for 2175 < A < 2975mm
Water Supply 1/2”BSP-MInlet Type (1) y (3)
Water Supply (1)Inlet Type 1/2”BSP-M Left Outlet
(Right Outlet Symmetric)
120
120
120
125
146650
796
(*)
26,5
275
250
(***
) 12
5
(**)
150
(***
*) 1
90
A=
Wid
th H
EF
2 S
erie
s
Water Outlet To DrainPVC-U D32-F
Ball Valve
Overflow
Water Supply (2)Inlet Type 1/2”BSP-M
Water Supply (3)Inlet Type 1/2”BSP-M
Pro
cess
air
20HEF2 Series Installation and maintenance manual
HEF2 Series (RECIRCULATED WATER) Water supply and basin draining dimensional drawing
MOTOR-ZONE DRAIN VALVE (optional)
Water Supply 1/2”BSP-MInlet Type (1) y (3)
(*) 26,5mm for 570 < A < 2075mm 36,5mm for 2175 < A < 2975mm
(**) 150mm for 570 < A < 2075mm 160mm for 2175 < A < 2975mm
Water Supply (1)Inlet Type 1/2”BSP-M
120
120
120
125
168650
(*)
26,5
275
(***
) 12
5
(**)
150
(***
*) 1
90
A=
Wid
th H
EF
2 S
erie
s
Water Outlet To DrainPVC-U D32-F
Motor-Zone Valve
Water Supply (2)Inlet Type 1/2”BSP-M
Water Supply (3)Inlet Type 1/2”BSP-M
Pro
cess
air
250
Overflow
(****) 190mm for 570 < A < 2075mm 200mm for 2175 < A < 2975mm
(***) 125mm for 570 < A < 2075mm 135mm for 2175 < A < 2975mm
Left Outlet (Right Outlet Symmetric)
21Fisair Air humidity control
Connection to the water supply for filling the water tankA
WATER CONNECTIONS
Connect the water supply (A) to the ½” male BSP float valve (6) using suitable piping with a cut-off valve (1). We recommend the installation of a 0.5 mm light filter (2). The float valve can be regulated to set it to a range of water supply pressures, as shown in figure 1 on this page.
WATER TANK WATER SUPPLY
Adjust the water level of the water tank to between 3 cm below the level of the overflow by regulating the float valve.
Regulating the float valve
[Note]
The water level must never fall below the minimum water level of the pump. Water levels below this minimum irreparably harm the pump.
Figure 1
½” pitch
3/8” pitch
Float valve
Flow
(l/m
in)
1 2 5 63 40
20
40
60
80
100
120
140
Pressure (bars)
Fitted by others
A
6
2
1
Regulating by positioning the float valve vertically (25mm of play). A 20 spanner with parallel faces key is needed to carry out this operation.
[Note] 25 mm for position 2
and 40 mm for position 1 and 3 (feed water).
(*)
25m
m
110º
Regulating by swivelling the ball (110º Swing). Two 10 spanner with parallel faces key is needed to carry out this operation.
75 mm
22HEF2 Series Installation and maintenance manual
Connecting the drain to the water trapB
DRAINING CONNECTIONS
Connect the ø32 mm common outlet (female/glued PVC-U) for the draining / overflow / constant bleed-off (3), with no cut-off valve, to the network. A cut-off valve (4) (manual or automatic depending on specifications) is included to control drainage. *
The connection of the water outlet to the drainage must include a water trap (5) high enough (2H) to exceed the pressure in the system, so the water tank can be completely emptied, for hygiene reasons. The system will also have the normal slope of typical drainage lines.
Recovering water from the humidification process into the drinking water mains is absolutely prohibited.
Draining valve opening
Draining valve closure
PVC-U ø32 mm (glued)
* HEF2 Seriess are supplied with a manual ball valve for draining as standard
2H
2H
HH
2H
Water trap for positive pressures
Water trap for negative pressure
Hmin. (mm)= P(Pa)/10 P= Total fan pressure
B
34
Fitted by others
5
23Fisair Air humidity control
Connect the electricity supply line to the terminal box of the water irrigation pump using a suitable connection (IP54 or higher).
The protection and operation of the electricity supply to the pump must be determined by the project designer of the system.
The humidifier must be disconnected automatically when the system fails to ease working conditions according to sanitary standard VDI6022. FISAIR recommends including our BASIC CONTROL PANEL (CCB)
WIRING DIAGRAM THREE PHASE PUMP
C
STAR CONNECTION
(400V/III/50Hz)
U1 V1 W1
X1
TRIANGULAR CONNECTION
(230V/III/50Hz)
U1 V1 W1
X1
Electricity connection of the Fisair recirculation pump
U1 V1 W1
426
513
PE
X0
X1
400V/3Ph/50Hz
L2
L1
L3
PE
PnPump
4
I1
_.__._
-..-A
I>
U
240W 0,4..0,63A
0,25..0,4A
60W
I(A) P(W)
0,1..0,16A
A bordo de unidad.Inside unit.
Ejecución por otros.Not included.
125W
24HEF2 Series Installation and maintenance manual
WIRING DIAGRAM
SINGLE PHASE PUMP
0
1
SEL 1-2 5-63-4
DescripciónNombre
Seccionador para aislamiento electricoI1
X0 Caja exterior
X1 Caja de conexión bomba (IP55)
In (240W)= 0,52A (400V/III/50Hz)
In (125W)= 0,38 A (400V/III/50Hz)
In (60W)= 0,12A (400V/III/50Hz)
In (50W)= 0,48A (230V/IN/50Hz)
Power Rating
U1 V1
42
13
PE
X0
230V/1N/50Hz
N
L1
PE
PnPump
3
I1
_.__._
-..-A
I>
U
0,4..0,63A
I(A) P(W)
A bordo de unidad.Inside unit.
Ejecución por otros.Not included.
Name Description
Exterior box
Pump connection box (IP55)
Isolator for electrical insulation
50W
25FISAIR PUMP CAPACITY CURVES
Level detector electricity connectionD
1. Minimum level detector (low level):
The minimum level must be connected to protect the workings of the recirculation pump as shown in the diagram in figure 1.
2. Maximum level detector (high level):
The maximum level is used as a security system in the event of a possible failure of the float valve of the water feed. It must not be used to regulate the water feed. If it has a solenoid valve, this level must be connected to this valve to shut off for safety. The connection must be made as shown in the diagram in figure 1.
(Vmax = 110Vac)
pump
Filling solenoid valve
min. level
max. level
S2
S1
Common High level
N.O Low level
N.O High level
High level
Low level
Common Low level
N.C High level
N.C Low level
[Important note] Maximum connection 110 Vac
Figure 1
26HEF2 Series Installation and maintenance manual
Adjust the irrigation valves of the evaporative cassettes so their surfaces are uniformly wet. The empirical value of approximately 1 litre/second for each square metre of irrigation surface is enough to exceed the water needed for evaporation. Generally, it is just necessary to ensure the irrigation of the panels has excess water falling into the water tank.
The importance of constant bleed-off based on conductivity
Water evaporates because the water vapour pressure is higher in the evaporative panel than in the air passing through it. Since only the water evaporates, dissolved mineral salts remain in solution, which gradually increases their concentration, despite new water being added to compensate for the evaporation.
In order to prevent the formation of mineral deposits on the surfaces of the evaporative panel (giving rise to a progressive increase in air pressure drop and reducing operational performance) it is essential to drain off some of the recirculated water to the network during the evaporation.
Bleed-off based on the COC (cycle of concentration).
Bleed-off = Evaporation (COC-1)
Cycle of concentration COC based on conductivity (100-1000 µS/cm)
Comment: Always in line with the recommended parameters of the drinking water supply.
• 100 µS/cm = 9 COC• 550 µS/cm = 6 COC• 1000 µS/cm = 2 COC
Calculation example:
• Based on drinking water network parameters• Water evaporation= 3.23 l/min • Water conductivity= 550 µS/cm• COC= 6• Bleed-off = 3.23/(6-1)= 0.65 l/min
Regulation valve with flow meter to adjust the bleed-off. It is regulated using a screwdriver as shown in figure 1.
Initial approximate settings can be made as 10% of the total flow of the irrigation. By regularly observing the state of the panels (on the air input side), after 1 or 2 weeks in use, if there are no white mineral deposits on the surfaces, the bleed-off flow can be reduced, or on the other hand, if there are lime deposits, it can be increased.
Analytical parameters of the drinking water network (Recommended)
• Hardness of the water ( CaCO3): 50-170 ppm • Chlorine ( Cl): <55 ppm • PH: 6-8 • Silica (SiO): <30 ppm • Iron ( Fe): <0.2 ppm • Oils and grease: <2 ppm • Total dissolved solids: <550ppm • Total alkalinity ( CaCo3): 50-170 ppm • Suspended solids: <5 ppm
Setting valves regulating evaporative cassette irrigation flow
Adjusting the constant bleed-off regulation valve
E
F
Regulating with a flat head screwdriver
where shown
Regulation valve + ½” brass flow meter
for adjusting the irrigation of each cassette
Excess irrigation water is important to ensure constant and superficial washing of the panels.
Example of irrigation x cassette:
Cassette width (500mm) and panel thickness (150mm)
0.5mx0.15mx60= 4.5L/min
[Note] The flow in L/min for each cassette can be found on the HEF2 Series selection sheet.
[Note] The flow of the constant bleed-off cannot fall below 0.3 L/min. The flow in L/min of the bleed-off can be found on the HEF2 Series selection sheet.
Figure 1
27Fisair Air humidity control
Connection to the water supply (connection to external water at between 1 and 6 bar)
Connecting the drain to the water trap
Setting of the irrigation valves in each evaporative cassette
500 mm gaps recommended for maintenance
1/2” ball valve to cut off water feed
1/2” ball valve for draining manifold and irrigation system
CONNECTIONS AND SETTINGS/REGULATIONS MADE (STANDARD – DIRECT WATER)
500 mm
G
500 mm
G
B
A
B
E
G
H
I
E H AI B
A
28HEF2 Series Installation and maintenance manual
HEF2 Series-DW (DIRECT WATER) Water supply and basin draining dimensional drawing
Water Supply 1/2”BSP-MInlet Type (1) y (3)
12,5
140500
640
(*)
26,5
(***
) 12
5
(**)
150
Inlet Type (1)Water Supply 1/2”BSP-M
12,5
12,5
125
A=
Wid
th H
EF
2 S
erie
s
Water Outlet To DrainPVC-U D32-F
Inlet Type (3)Water Supply 1/2”BSP-M
(*) 26,5mm for 570 < A < 2075mm 36,5mm for 2175 < A < 2975mm
(**) 150mm for 570 < A < 2075mm 160mm for 2175 < A < 2975mm
(***) 125mm for 570 < A < 2075mm 135mm for 2175 < A < 2975mm
Pro
cess
air
Left Outlet (Right Outlet Symmetric)
29Fisair Air humidity control
Connection to the water supply A
WATER SUPPLY
Connect the water supply (A) to the ½” male BSP (6) using suitable piping with a cut-off valve (1). We recommend the installation of a 0,5 mm filter light (2).
In the HEF2 Series-DW, when the temperature of the feed water is below the dew point of the downstream air flow after the wetting panel, FISAIR recommends to isolate the stainless steel manifold and pipes to prevent possible condensations. To work according to hygienic certificate VDI6022 (ISO846) the isolations should also meet that standards
Fitted by others
6
2 1
30HEF2 Series Installation and maintenance manual
Connecting the drain to the water trapB
PVC-U ø32 mm (glued)
DRAINING CONNECTIONS
Connect the ø32 mm common outlet (female/glued PVC-U) for the draining / overflow / constant bleed-off (3), with no cut-off valve, to the network.
The connection of the water outlet to the drainage must include a water trap (5) high enough (2H) to exceed the pressure in the system, so the water tank can be completely emptied, for hygiene reasons. The system will also have the normal slope of typical drainage lines.
Recovering water from the humidification process into the drinking water mains is absolutely prohibited.
2H
Water trap for positive pressures
Water trap for negative pressure
Hmin. (mm)= P(Pa)/10 P= Total fan pressure
2H
HH
2H
3
Fitted by others
5B
Adjust the irrigation valves of the evaporative cassettes so their surfaces are uniformly wet. The empirical value of approximately 0,4 litre/second for each square metre of irrigation surface is enough to exceed the water needed for evaporation. Generally, it is just necessary to ensure the irrigation of the panels has excess water falling into the water tank.
Excess irrigation water is important to ensure constant and superficial washing of the panels.
Example of irrigation x cassette:
Cassette width (500mm) and panel thickness (150mm)
0,5 x 0,15 x 24= 1,8 L/min
Setting of the irrigation valves in each evaporative cassette
E
Regulating with a flat head screwdriver
where shown
Regulation valve + ½” brass flow meter
for adjusting the irrigation of each cassette
[Note] The flow in L/min for each cassette can be found on the HEF2 Series selection sheet.
31Fisair Air humidity control
CONNECTIONS AND SETTINGS/REGULATIONS MADE(OPTIONAL ACCESSORIES FOR RECIRCULATED WATER)
Connection of the water tank filling solenoid valve. This solenoid valve is supplied loose for installation by others
Connection of the zone motor-valve for automatic draining. This motor valve is supplied assembled
Flexible connector for the water supply
External rigid connector for the water supply
External rigid connector for draining
UV light disinfection system
Perimeter closure cover plates
Solenoid valve(s) connection for stage control
Basic control panel with conductivity control CCB + C (*)
HEF2 series for duct
Piping system in stainless steel
Basic Control Panel CCB (*)
Stage control panel CCE (*)
Stage control panel with control by conductivity CCE + C (*)
(*) Go to the corresponding control panel manual.
H
A
D
E
B
C
G
H
I
J
K
L
M
P
E D
A
BH
C
A
B
C
D
E
F
G
32HEF2 Series Installation and maintenance manual
CONNECTIONS AND SETTINGS/REGULATIONS MADE (OPTIONAL ACCESSORIES FOR DIRECT WATER)
H
A
D
E
N C
G
E AO NH
Connection of the water basin filling solenoid valve. This solenoid valve is supplied loose for installation by others
Flexible connector for the water supply
External rigid connector for the water supply
External rigid connector for draining
UV light disinfection system
Perimeter closure cover plates
Solenoid valve(s) connection for stage control
HEF2 series-DW for duct
Piping system in stainless steel
Connection of the 3-way motor-zone valve to manage the water feed and emptying of the manifold/irrigation system
Motor-zone valve for emptying the manifold/irrigation system
H
J
K
N
O
A
C
D
E
F
G
33Fisair Air humidity control
Connection of the 24V or 230V water basin filling N.C. solenoid valve (supplied loose for installation by others) (*)A
G ½” brass water filling N.C. solenoid valve
24V connector (L1+N+T) 230V connector (L1+N+T)
230V or 24V coil (50/60 Hz)
44
101,
5
72
L1/N L1/N
40½”
G
(*) In the HEF2 series of recirculated water this solenoid valve must always be installed upstream of the float valve.
In the HEF2 series-DW (Direct Water), this solenoid valve manages the water feed of the irrigation system (it will be supplied assembled on the unit). Eliminates the standard 1/2” ball valve and makes it impossible for the 3-way motor-zone valve to be assembled.
In the case of HEF2 series of recirculated water, the maximum level must manage this solenoid valve.It is used as a security system in the event of a possible failure of the float valve.It must not be used for regulating the water feed. The float valve is responsible for the regulation.
34HEF2 Series Installation and maintenance manual
Figure 1: Type I motor-zone valve
Connection of the N.C. motor-zone valve for automatic draining of the HEF2 series (recirculated water)
B
CASE 1: HEF2 series (recirculated water) with the filling solenoid valve and without CCB (basic control panel). This case will assemble the type I motor-zone valve.
CASE 2: HEF2 series (recirculated water) with the filling solenoid valve and with a CCB (basic control panel). This case will assemble the type II motor-zone valve.
CASE 3: HEF2 Series (recirculated water) without the filling solenoid valve and without CCB (basic control panel). This case will assemble the type II motor-zone valve.
TYPE I MOTOR-ZONE VALVE (3 points control)
Technical data
AC 24 V supply(SELV/PELV)
Operating voltage / Frequency AC 24 V ± 20% / 50/60 Hz
Power consumption 2 VA / 1W
AC 230 V supplyOperating voltage / Frequency AC 230 V ± 10 % / 50/60 Hz
Power consumption 2 VA / 1 W
Function dataNominal torque 5 Nm
Runtime for 90° rotary angle 125 s
Auxiliary switches
Contact rating 6 A resistive, 2 A inductive
Voltage (no mixed operation AC 24 V / AC 230 V) AC 24...230 V
Switching range for auxiliary switches 5°...90°
Setting increments 5°
Connection cablesCross-section 0,75 mm2
Standard length 0,9 m
Degree of protection of housing Degree of protection as per EN 60 529 IP 54
Protection class
Insulation class EN 60 730
AC 24 V, feedback potentiometer lll
AC 230 V, auxiliary switch ll
Environmental conditions
Operation / Transport IEC 721-3-3 / IEC 721-3-2
Temperature -32...+55 °C / -32...+70 °C
Humidity (non-condensing) < 95% r. F. / < 95% r. F.
Weight 0,48 Kg.
35Fisair Air humidity control
Electric Diagram connections
Dimensions
GDB13..1 / GLB13..1
3 points control AC 24 V
3 points control AC 230 V
GDB13..1 / GLB13..1
36HEF2 Series Installation and maintenance manual
Adjusting: A, B Auxiliary contacts
Factory setting
A= 5ºB= 85º
Cable labeling
PinCable
MeaningCode Nr. Color Abbrev.
ActuatorsAC 24 V
G 1 red RD System potential AC 24 V
Y1 6 purple VT Position signal AC 0 V, clockwise
Y2 7 orange OG Position signal AC 0 V, counter-clockwise
ActuatorsAC 230 V
N 4 blue BU Neutral conductor
Y1 6 black BK Control signal AC 230 V, clockwise
Y2 7 white WH Control signal AC 230 V, counter-clockwise
Auxiliary switch
Q11 S1 grey/red GY RD Switch A Input
Q12 S2 grey/blue GY BU Switch A Normally closed contact
Q14 S3 grey/pink GY PK Switch A Normally open contact
Q21 S4 black/red BK RD Switch B Input
Q22 S5 black /blue BK BU Switch B Normally closed contact
Q24 S6 black /pink BK PK Switch B Normally open contact
37Fisair Air humidity control
TYPE II MOTOR-ZONE VALVE(2 points control)
Datos técnicos
AC 24 V DC 24…48 V supply (SELV/PELV)
Operating voltage AC / Frequency AC 24 V ± 20 % / 50/60 Hz
Operating voltage (DC) DC 24…48 V ±20 %
Power consumption AC: 5 VA / 3.5 W // DC: 3.5 W
AC 230 V supplyOperating voltage / Frequency AC 230 V ± 10 % / 50/ 60 Hz
Power consumption 7 VA / 4.5 W
Function data
Nominal torque 7 Nm
Runtime for rotary angle 90° (motor operation) 90 s
Closing time with return spring (on power failure) 15 s
Auxiliary switch
AC power supply
Switching voltage AC 24...230 V
Nominal current res./ind. 6 A / 2 A
DC power supply
Switching voltage DC 12..30 V
Nominal current DC 2 A
Switching range for auxiliary switches / Setting increments 5°...90° / 5°
Connection cablesCross-section 0,75 mm2
Standard length 0,9 m
Degree of protection of housing Degree of protection as per EN 60 529 IP 54
Protection class
Insulation class EN 60 730
AC/DC 24 V, feedback potentiometer lll
AC 230 V, auxiliary switch ll
Environmental conditions
Operation / Transport IEC 721-3-3 / IEC 721-3-2
Temperature −32...+55 °C / −32...+70 °C
Humidity (non-condensing) < 95% r. h. / < 95% r. h.
Weight 1.2 kg.
In case 2, when this motor-zone valve is connected to the CCB (Basic Control Panel), it will be necessary to connect the S4 cables (Black/Red) and S6 ones (Black/Pink) to the “Feedback” connection J15 (See page 13 of the basic control panel CCB manual)
38HEF2 Series Installation and maintenance manual
Electric Diagram connections
Dimensions
GMA12..1 / GMA32..1
2 points control AC 24 V
2 points control AC 230 V
39Fisair Air humidity control
Manual positioning
Cable labeling
PinCable
MeaningCode No. Color Abbrev.
Actuators AC 24 V DC 24…48 V
G 1 red RD System potential AC 24 V/DC 24…48 V
G0 2 black BK System neutral
ActuatorsAC 230 V
L 3 brown BN Phase AC 230 V
N 4 blue BU Neutral conductor
Auxiliary switch
Q11 S1 grey/red GY RD Switch A input
Q12 S2 grey/blue GY BU Switch A normally-closed contact
Q14 S3 grey/pink GY PK Switch A normally-open contact
Q21 S4 black/red BK RD Switch B input
Q22 S5 black/blue BK BU Switch B normally-closed contact
Q24 S6 black/pink BK PK Switch B normally-open contact
Adjusting: A, B Auxiliary contacts
Factory setting
A= 5ºB= 85º
Position Block Unblock
40HEF2 Series Installation and maintenance manual
Flexible connector for the water supply
External rigid connector for the water supply
External rigid connector for draining
C
D
E
542 mm
X (defined by the client)
Teflon seal
½”
coni
cal B
SP
½” conical B
SP
Flexible filling pipe made of ½“ AISI304 stainless steel.
Length 542 mm
[Note]
It will be delivered unassembled, it must be connected to the inlet of the float valve in the case of recirculated water. In the case of direct water it will be connected to the input 1/2 “BSP-M.
A ½” – 3/8” reduction is supplied when the float valve is 3/8”.
Rigid ½” ASI304 steel filling pipe. (It will be supplied disassembled)
Male/glued ø32 PVC draining pipe. (It will be supplied disassembled)
D
E
41Fisair Air humidity control
U.V. lamp disinfection system (*)F
ULTRAVIOLET LAMP
Concerns related to pathogenic organisms in the water causing illnesses and contaminating industrial processes, have led FISAIR S.L. to provide the optional integration of ultraviolet technology in its evaporative units. This type of system eliminates bacteria, viruses and other pathogens, prevents their reproduction, and results in completely safe drinking water.
U.V. radiation is one band of the electromagnetic spectrum. It has more energy than visible light. The irradiation of germs present in the water with U.V. light harms their DNA molecules (figure 1) in a number of ways, which prevents cell division and kills them. The most harmful radiation for germs has a wavelength of 254 nanometres. The DNA exposed to this energy can only absorb up to a maximum, after which there is an irreparable inactivation of the growth of the pathogens.
The only control panel that includes it as standard, is the panel in which the U.V. lamp is integrated (figure 2).
Figure 1 DNA molecule damage caused
by U.V. light
Figure 2 Control panel
ULTRAVIOLET LIGHT DISINFECTION SYSTEM + WATER FILTERS
50μ water filters
5μ water filters
Cut-off valve U.V. light Control valve
Solenoid valve (*)
TREATED WATER TO THE
HEF2 SERIES WATER SUPPLY
UNTREATED WATER
Cut-off valve
M8 attachment points
Control valve
BSP ½” connector
BSP ½” connector
Warning!!! To avoid unnecessary blockages in the filters of the system, the water should be made to circulate through the by-pass when the appropriate settings are being made to the irrigation of the cassettes and the cellular panel is being washed during installation.
(*) This valve is the optional water supply valve.
A A
A A
A
42HEF2 Series Installation and maintenance manual
Perimeter closure cover platesG
a Unassembled cover plates
a
c Anchor points
c
b Assembled cover plates
b
c
c
c
43Fisair Air humidity control
Figure 1: HEF2 series (recirculated water) with 3 stages
3rd stage solenoid valve
2nd stage solenoid valve
1st stage without solenoid valve (managed by the on / off switch of the pump)
Figure 2: HEF2 series-DW (direct water) with 3 stages.
3rd stage solenoid valve
2nd stage solenoid valve
1st stage solenoid valve
Solenoid valve(s) connection for stage controlH
CASE 2: (figure 2) HEF2 series-DW (direct water)
• Each stage manages the irrigation of 1 cassette
• For each stage there will be a solenoid valve located
after the regulating flow irrigation valve. (*)
• 5 stages as Maximum to manage the biggest HEF2
with 5 cassettes
CASE 1: (figure 1) HEF2 series (recirculated water)
Each stage manages the irrigation of 1 cassette.
• The first stage is managed
with the ON / OFF switch of the pump •
The following stages (from 2 to 5) will be managed by a solenoid valve located after the regulating flow irrigation valve. (*)
(*) To connect the valves refer to page 35. point A.
44HEF2 Series Installation and maintenance manual
HEF2 series-DW for ductJ
HEF2 SERIES FOR DUCT (RECIRCULATED WATER) Main Levels + Water supply and basin draining connections
A = Width HEF2 Series
Water outlet to drainPVC-U D32-F (type L outlet)
Water outlet to drain PVC-U D32-F (type R outlet)
Water outlet to drainPVC-U D32-F (type L outlet)
Water supply 1/2”BSP-M
(1) & (3) Inlet types
Water supply 1/2”BSP-M
(3) Inlet types
Water supply 1/2”BSP-M
(1) Inlet types
Hig
th H
EF
2 S
erie
s
15 15
120
125 (*)
26,5
650
(**)
150
860
250
125
330
210
125
111
ø10
Process air
Pro
cess
air
(*) 26,5mm for 570 < A < 2075mm 36,5mm for 2175 < A < 2975mm
(**) 150mm for 570 < A < 2075mm 160mm for 2175 < A < 2975mm
45Fisair Air humidity control
HEF2 SERIES-DW FOR DUCT (DIRECT WATER) Main Levels + Water supply and basin draining connections
A = Width HEF2 Series
Water outlet to drainPVC-U D32-F (type L outlet)
Water outlet to drain PVC-U D32-F (type R outlet)
Water outlet to drainPVC-U D32-F (type L outlet)
Water supply 1/2”BSP-M
(1) & (3) Inlet types
Water supply 1/2”BSP-M
(3) Inlet types
Water supply 1/2”BSP-M
(1) Inlet types
Hig
th H
EF
2 S
erie
s
15 15
168
125 (*)
26,5
(**)
192
500
710
25
25
125
210
168
168
111
ø10
Process air
Pro
cess
air
(*) 26,5mm for 570 < A < 2075mm 36,5mm for 2175 < A < 2975mm
(**) 192mm for 570 < A < 2075mm 202mm for 2175 < A < 2975mm
46HEF2 Series Installation and maintenance manual
Piping system in stainless steel
Connection of the 3-way motor-zone valve to manage the water supply and the emptying of the manifold/irrigation system (figure 1)
Motor-zone valve for emptying of the manifold/irrigation system (figure 2)
K
N
O
All pipes, elbows, tees, etc., in stainless steel except the draining/overflow panoply which continues in PVC-U.
All the valves remain in brass or bronze.
When designed to work at high temperatures (painting cabins, ovens, heating coils...), the draining/overflow panoply will be in stainless steel. Consult FISAIR for more information.
To manage the water supply and the emptying of the manifold/irrigation system of the HEF2 Series-DW (direct water) the type II motor-zone valve is assembled (page 39). The actuator will be the same as the two way valve.
To manage the emptying of the manifold/irrigation system of the HEF2 Series-DW (direct water) the type I motor-zone valve is assembled (page 36).
Type II motor-zone valve (3 ways)
Water supply
Water flow to basin
Water flow to manifold/irrigation system
Water flow from manifold/irrigation system
Type I motor-zone valve (2 way)
ASSEMBLIES WATER FLOW DIRECTION
WATER SUPPLY FLOW
DIRECTION
DRAINING MANIFOLD FLOW
DIRECTION
Figure 1
Figure 2
47Fisair Air humidity control
Installation and recommendations
Maintenance
GENERALITIES
FISAIR HEF2 Series evaporative humidifiers essentially work by means of the irrigation of the evaporative panels. Humidifiers execute their function whenever air currents pass through them and the water pump irrigates the panels.
Note: To remove superficial inorganic material/dust on the panels and to prevent its transmission to working areas, we recommend leaving the water irrigation pump on for 6 hours, with no air flow, in order to wash the panels. Subsequently, the washing water must be emptied before starting up the unit as per normal.
To ensure the correct operation, according to the hygienic standard VDI6022, maintenance should be performed regularly as directed, and it is also necessary to keep a maintenance record.
GENERALITIES
Humidifier components are very easy to maintain, because the only active parts are the irrigation pump and the float valve. The following elements require some kind of maintenance:
Once a month, the irrigation pump: The most important thing is to monitor to ensure dirt does not obstruct the suction impulsion circuit and electricity consumption is lower than the power rating shown on its plate.
Once a year, the float valve: This must be inspected on a regular basis to ensure its mechanical closure and opening works correctly.
Once a year, the control valves: These must be inspected to ensure their mechanical regulatory function works correctly.
Once a year, the solenoid valves (if applicable): These must be inspected to ensure their mechanical closure and opening works correctly.
HEF2 SERIES WITH EXTERIOR AIR OR INSTALLED IN AN AHU OUTDOORS
All units using the HEF2 Series with exterior air must stop the pump and drain the water tank in the event of preheater faults. Units for adiabatic cooling of the return air must drain the water tank water during the winter.
OPERATIONAL PERFORMANCE CONTROL
Humidifiers work with excess panel irrigation. If evaporative performance is to be regulated, this is not done by controlling the quantity of irrigation water but rather:
Regulating the number of cassettes in operation. The FISAIR HEF2 can be equipped with the components necessary for external control or may also include FISAIR stage control panel CCE.
Alternatively, by controlling irrigation operation times, so the humidity/temperature regulator acts on the pump working time.
Once every three months, the evaporative panels: Their operating life basically depends on the correct use of the constant bleed-off system for mineral salts which prevents the formation of superficial lime deposits, from the supply of drinking or industrial water. If they are not maintained properly, the panels have to be replaced more often, because the flow of air through them can be blocked by these deposits.
Once a year, the irrigation: Take the steps described on the page entitled “Cleaning the individual irrigation system”.
In the interests of correct maintenance, it is advisable to make regular observations on the days after installing the system, to understand the specific behaviour of the installation, so the draining and cleaning programmes can be set. Similarly, during long periods of inactivity (summer for humidification for comfort, and winter for evaporative refrigeration) it is essential to completely drain and clean the water tank.
48HEF2 Series Installation and maintenance manual
Cleaning and disinfection
Evaporative humidification: A natural method that does not carry bacteria.
The operational features of evaporative humidifiers are based on the natural effect of the water evaporation when an air flow goes through/by a wet surface (is the same natural principle that occurs when water evaporates from waterfalls, rivers, lakes, seas...).
Evaporation means that the water leaves the humidifier as pure vapour (gas). Minerals and eventual pollutants stay in the water and can be eventually drained / eliminated.
With no droplets or aerosols carry over, the bacteria can’t be transferred to the humidified air. It is important to use a droplet separator when its needed.
The evaporative humidifiers work with water temperatures below 24°C, very far from the optimal growth temperatures of the bacteria present in the water, essentially Legionella pneumophila, with an optimum growth temperature of 37-41ºC.
The water basin, manifold, irrigation system and the other components of the HEF2 series are specially designed for there to be complete emptying by gravity, without the aid of mechanical elements.
Based on the quality of treated air and water supply, a cleaning and emptying inspection plan should be established.
Evaporative humidifiers must be cleaned regularly to prevent contamination. All surfaces of the components (panel, pipes and especially the water basin) should be disinfected with an appropriate solution.
You must pay special attention to cleaning the piping system, especially in bends and junctions; the cleaning process must reach all ends of the system.
In the case of the panels, the use of chemical disinfectants for daily maintenance is not recommended because it could reduce the efficiency of the panel and its useful life. If the use of chemicals is necessary, either for a long period of inactivity or any other reason, an effective method is to dip the panels in chlorine disinfectant such as sodium hypochlorite (bleach) or sodium percarbonate.
In the case of the use of disinfectants with chlorine, it is imperative to consider the formation of toxic chlorine gas when combined with an acid solution.
egarding disinfection of other components, the same bleach solution may be valid. The number and frequencies of the cleaning /disinfection process must be established by the installation responsible in function of the installation requirements, unit working time, water quality, air quality, etc.
To insist once more, the optimal performance is principally based on a correct irrigation regulation, a correct bleed-off regulation and a correct emtying regulation.
An additional and very good practice would be to add a water supply treatment.
Hygienic conformity test.
The HEF2E humidifiers have the “hygienic conformity test” certificate. Complying with the requirements of the following standards:
For air conditioning: • VDI 6022, part 1 (07/2011) • SWKI VA104-01 (04/2006) • VDI 3803, part 2 (02/2010)
For hospitals: • DIN 1946-4, (12/2008)
All the materials included in the HEF2E have obtained a negative result in the proliferation of pathogenic microorganisms. The non-metallic components comply with the requirements of standard DIN EN 846 “Plastics. Assessment of the action of microorganisms”
50HEF2 Series Installation and maintenance manual
LATERAL Disassembly
DISASSEMBLY OF CASSETTES AND DROPLET SEPARATORS. LATERALLY
The unit can be disassembled in a few simple steps for maintenance and/or cleaning work of the HEF2 Series.
Disassemble the collector + regulation valve set for the irrigation flow of the evaporative cassettes.
1st
Disassembly steps:
ba
Unscrew each irrigation union
c Collector + regulation valve set of the irrigation flow
Unscrew the unions
51Fisair Air humidity control
Disassemble the D25 PVC-U up-pipe to the collector.
Disassemble front cover
2nd
3rd
b
a
Unscrew the two screws
holding the piece in place
b Front cover
Unscrew the DN20 PVC-U ball valve fitting
D25 PVC-U pipe
a
52HEF2 Series Installation and maintenance manual
Disassemble the side cover
4º
Unscrew (upper screw) without removing
the screw from its bolt
Unscrew (lower screw)
Unscrew (lateral screw)
a
c
b
53Fisair Air humidity control
a
c
5º
6º
b
Unscrew
Release the pipe from the nylon clip
Removal of the droplet separators.
Disassemble the “C” piece (there is one piece for each evaporative cassette)
side view front view
54HEF2 Series Installation and maintenance manual
7º
a
Removal of evaporative cassettes
Remove the cassettes
55Fisair Air humidity control
4º
a
a
cb
b
5º
FRONT Disassembly
UNIT DISASSEMBLY. FRONT
The unit can be disassembled in easy steps for maintenance and/or cleaning work of the HEF2 Series.
Disassembly steps
1st LATERAL disassembly step 1
2nd LATERAL disassembly step 2
3rd LATERAL disassembly step 3
Bleed-off disassembly
Unscrew the brass fitting of the regulation valve + flow meter of the bleed-off
Unscrew the support
Bleed-offUnscrew the ½” PVC-U union
If the float valve is mounted on the support, disconnect the water supply
Disassemble the support + pump + level detector set (optionally the float valve can be mounted on this support)
56HEF2 Series Installation and maintenance manual
7º
8º
6º
9º
b
a
LATERAL disassembly step 6
Disassembly of the “b” piece
Removal of droplet separators
Removal of the evaporative cassettes
Unscrew the four screws (2 on each side)
57Fisair Air humidity control
1º
c
b
d
a
Cleaning the individual irrigation system
Remove the individual top piece mounted on each evaporative cassette
Remove the individual irrigation top piece
Individual top piece
Press with both hands on one of the flaps,
as shown in the image.Evaporative
cassette
58HEF2 Series Installation and maintenance manual
CLEANING THE INDIVIDUAL IRRIGATION SYSTEM OF THE WATER TANK
Clean the perforated pipe of the individual irrigation top piece
2º
Use the special brush supplied with each HEF2 Series
The out-of-reach zones of the water tank simply by hand.
Use the special brush supplied with each unit
Brush the perforated pipe as shown in the image
a
a
b
[Note]
We recommend 10 strokes swivelling 180º each time.
HE
F2
Se
rie
s In
stal
latio
n an
d m
aint
enan
ce m
anua
l
11
13
15 12
7
18
10
17
16
14
9a, 9b, 9c, 9d
2a, 2b, 2c, 2d
, 2e
1a, 1b
8a, 8b
3a, 3b
ó
an
d/o
r
4a, 4b
6a, 6b
5a, 5b, 5c, 5d
2a, 2b, 2c, 2d
, 2e
Lis
t o
f
spare
part
s
61Fisair Air humidity control
List of spare partsItem Code Component
Regulation Valve Collector Up-Pipe
1a 62341010 PE-EPDM ball valve / 25 / Glue
1b 62341005 PE-EPDM ball valve / 20 / Glue
Regulation Valve Showing Cassette and Bleed-off Flow
2a 62000050 Regulation Valve Showing Flow DN15 0.3-1.5 I/m
2b 62000055 Regulation Valve Showing Flow DN15 0.6-2.4 I/m
2c 62000060 Regulation Valve Showing Flow DN15 1-3.5 I/m
2d 62000065 Regulation Valve Showing Flow DN15 2-8 I/m
2e 62000070 Regulation Valve Showing Flow DN153-12 I/m
Draining Set, Overflow to Drain
3a 50500000 Left
3b 50500001 Right
Bleed-off set
4a 50500002 Left
4b 50500003 Right
62HEF2 Series Installation and maintenance manual
List of spare partsItem Code Component
Water Recirculation Pump
5a 65310065 Water Pump 50 W. 230V./I/50Hz.
5b 65310005 Water Pump 60 W. 230-400V./III/50Hz.
5c 65310050 Water Pump 120 W. 230-400V./III/50Hz.
5d 65310020 Water Pump 240 W. 230-400V./III/50Hz.
Water Supply Float Valve
6a 62350010 AISI 304 Stainless Steel Float Valve 3/8”
6b 62350015 AISI 304 Stainless Steel Float Valve ½”
Draining Cut-off Valve
7 62000015 ¾” F-F Chrome Brass Ball Valve Lever
8a 710900052 Way Zone Motor Valve DN20 (¾”) F-F Threaded 230V
8b 710900062 Way Zone Motor Valve DN20 (¾”) F-F Threaded 24V
63Fisair Air humidity control
List of spare partsItem Code Component
Cassette Irrigation Set
9a 50400000 For 300 mm Cassette
9b 50400001 For 400 mm Cassette
9c 50400002 For 500 mm Cassette
9d 50400003 For 600 mm Cassette
10 50400004 Cassette Irrigation Supply Set
11 14440005 Cassette Irrigation Pipe
12 50400005 Collector Pump-Bleed Off-Up Pipe Set
Max/Min Level Detector
13 64220313 Max/Min Level Detector
64HEF2 Series Installation and maintenance manual
List of spare partsItem Code Component
Irrigation Individual Distribution Nylon Clip
14 60700015 D20 mm Nylon Clip
Stainless Steel Collector
15 1st) Provide HEF2 Series Serial Nº
Droplet Separators
16
1st) Measure A in the droplet separator being replaced
2nd) Provide the HEF2 Series Serial Nº
Evaporative Cassettes
17
1st) Measure B in the evaporative cassette being replaced
2nd) Give the HEF2 Series Serial Nº
Solenoid valve
18a 71090005 Solenoid valve 24V
18b 71090006 Solenoid valve 230V
B
A