Heating Circuit and D H W Controller 17588 Hq En

Embed Size (px)

Citation preview

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    1/94

    Edition 1.0

    Controller series A

    CE1P2474E

    15.10.1999

    Siemens Building TechnologiesLandis & Staefa Division

    RVP300, RVP310, RVP320

    Heating Circuit and Domestic Hot Water ControllerBasic Documentation

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    2/94

    2/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division 15.10.1999

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    3/94

    3/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division Contents 15.10.1999

    Contents

    1 Summary ........................................................................................................9

    1.1 Brief description and key features...................................................................9

    1.2 Type summary................................................................................................9

    1.3 Equipment combinations.................................................................................91.3.1 Suitable sensors .............................................................................................9

    1.3.2 Suitable room units .........................................................................................9

    1.3.3 Suitable actuators .........................................................................................10

    1.3.4 Communication.............................................................................................10

    1.3.5 Documentation..............................................................................................10

    2 Use ...............................................................................................................11

    2.1 Types of plant ...............................................................................................11

    2.2 Types of houses and buildings......................................................................112.3 Types of heating systems .............................................................................11

    2.4 Functions ......................................................................................................11

    3 Fundamentals...............................................................................................13

    3.1 Key technical features...................................................................................13

    3.1.1 Plant types with regard to heating circuit ......................................................13

    3.1.2 Plant types with regard to d.h.w. heating ......................................................13

    3.1.3 Function blocks.............................................................................................13

    3.2 Plant types ....................................................................................................13

    3.2.1 Selectable combinations ...............................................................................14

    3.2.2 Plant type 10: Space heating with mixing valve, no d.h.w. ..............................14

    3.2.3 Plant type 11: Space heating with mixing valve, d.h.w. heating with

    charging pump ..............................................................................................14

    3.2.4 Plant type 20: Space heating with district heat, no d.h.w. ...........................15

    3.2.5 Plant type 30: Space heating with mixing valve and precontrol

    with boiler, no d.h.w. .....................................................................................15

    3.2.6 Plant type 31: Space heating with mixing valve and precontrol

    with boiler, d.h.w. heating with charging pump ...............................................16

    3.3 Setting levels, function blocks and plant types .................................................16

    3.4 Heating circuit operating modes....................................................................17

    3.4.1 Automatic operation ......................................................................................17

    3.4.2 Continuously REDUCED heating..................................................................17

    3.4.3 Continuously NORMAL heating ....................................................................17

    3.4.4 Standby.........................................................................................................17

    3.5 D.h.w. operating modes................................................................................17

    3.6 Manual operation ..........................................................................................18

    3.7 Plant type and operating mode .....................................................................18

    3.8 Operational status and operational level.......................................................18

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    4/94

    4/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division Contents 15.10.1999

    4 Acquisition of measured value ..................................................................... 19

    4.1 Room temperature (A6, B5).......................................................................... 19

    4.1.1 Measurement ............................................................................................... 19

    4.1.2 Handling of faults.......................................................................................... 19

    4.1.3 Room model................................................................................................. 19

    4.2 Flow temperature (B1).................................................................................. 19

    4.2.1 Measurement ............................................................................................... 19

    4.2.2 Handling of faults.......................................................................................... 20

    4.3 Outside temperature (B9)............................................................................. 20

    4.3.1 Measurement ............................................................................................... 20

    4.3.2 Handling of faults.......................................................................................... 20

    4.4 Return temperature (B7) .............................................................................. 20

    4.4.1 Measurement ............................................................................................... 20

    4.4.2 Handling of faults.......................................................................................... 20

    4.5 D.h.w. storage tank temperature (B31) ........................................................ 21

    4.5.1 Measurement ............................................................................................... 21

    4.5.2 Handling of faults.......................................................................................... 21

    5 Function block "Enduser space heating" ...................................................... 22

    5.1 Operating lines ............................................................................................. 22

    5.2 Setpoints ...................................................................................................... 22

    5.2.1 General ........................................................................................................ 22

    5.2.2 Frost protection for the building.................................................................... 22

    5.3 Heating program........................................................................................... 22

    5.4 Holiday program........................................................................................... 23

    5.5 Heating curve............................................................................................... 23

    6 Function block "Enduser d.h.w."................................................................... 24

    6.1 Operating line............................................................................................... 24

    6.2 Setpoint ........................................................................................................ 24

    7 Function block "Enduser general" ................................................................ 25

    7.1 Operating lines ............................................................................................. 257.2 Switching program 2..................................................................................... 25

    7.3 Time of day and date.................................................................................... 25

    7.4 Indication of faults ........................................................................................ 25

    8 Function block "Plant type"........................................................................... 27

    8.1 Operating line............................................................................................... 27

    8.2 General ........................................................................................................ 27

    9 Function block "Space heating".................................................................... 28

    9.1 Operating lines ............................................................................................. 28

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    5/94

    5/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division Contents 15.10.1999

    9.2 ECO function.................................................................................................28

    9.2.1 Compensating variables and auxiliary variables ...........................................28

    9.2.2 Heating limits ................................................................................................29

    9.3 Mode of operation .........................................................................................29

    9.3.1 Switching the heating off...............................................................................29

    9.3.2 Switching the heating on...............................................................................30

    9.3.3 Operating modes and operational statuses...................................................30

    9.4 Optimization..................................................................................................30

    9.4.1 Definition and purpose..................................................................................30

    9.4.2 Fundamentals...............................................................................................30

    9.4.3 Optimization with room sensor......................................................................30

    9.4.4 Optimization with room sensor......................................................................31

    9.4.5 Process.........................................................................................................31

    9.4.6 Room model temperature .............................................................................31

    9.4.7 Optimum stop control....................................................................................32

    9.4.8 Quick setback ...............................................................................................32

    9.4.9 Optimum start control....................................................................................32

    9.4.10 Boost heating................................................................................................33

    9.5 Room functions .............................................................................................34

    9.5.1 Maximum limitation of room temperature......................................................34

    9.5.2 Room temperature influence.........................................................................35

    9.6 Heating curve................................................................................................35

    9.6.1 Purpose ........................................................................................................35

    9.6.2 Basic setting..................................................................................................35

    9.6.3 Deflection......................................................................................................36

    9.6.4 Parallel displacement of heating curve .........................................................37

    9.7 Generation of setpoint...................................................................................38

    10 Function block Actuator heating circuit".......................................................39

    10.1 Operating lines..............................................................................................39

    10.2 Limitation ......................................................................................................39

    10.2.1 Limitations of flow temperature.....................................................................39

    10.2.2 Setpoint rise..................................................................................................39

    10.3 Type of actuator............................................................................................40

    10.3.1 Two-position control......................................................................................40

    10.3.2 Three-position control ...................................................................................40

    10.4 Auxiliary variables in interconnected plants ..................................................40

    10.4.1 Excess flow temperature mixing valve / heat exchanger...............................40

    10.5 Pulse lock with three-position actuator..........................................................41

    11 Function block "Boiler"..................................................................................42

    11.1 Operating lines..............................................................................................42

    11.2 Operating mode ............................................................................................42

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    6/94

    6/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division Contents 15.10.1999

    11.3 Limitation...................................................................................................... 42

    11.3.1 Maximum limitation of boiler temperature:.................................................... 42

    11.3.2 Minimum limitation of boiler temperature:..................................................... 43

    11.3.3 Effect during d.h.w. heating.......................................................................... 43

    11.4 Two-position control ..................................................................................... 43

    11.4.1 Control with a single-stage burner................................................................ 43

    11.4.2 Control with a two-stage burner.................................................................... 44

    11.4.3 Frost protection for the boiler ....................................................................... 45

    11.4.4 Protective boiler startup................................................................................ 45

    11.4.5 Protection against boiler overtemperatures.................................................. 46

    11.5 Operation mode of pump M1........................................................................ 47

    12 Function block "Setpoint of return temperature limitation"............................ 48

    12.1 Operating line............................................................................................... 48

    12.2 Description ................................................................................................... 48

    12.3 Limit value of return temperature.................................................................. 48

    12.3.1 Acquisition of measured value ..................................................................... 48

    12.3.2 Mode of operation ........................................................................................ 48

    12.3.3 Mode of operation with a single unit (with no bus)........................................ 49

    12.3.4 Mode of operation in interconnected plants.................................................. 49

    13 Function block "District heat"........................................................................ 50

    13.1 Operating lines ............................................................................................. 50

    13.2 Limitation...................................................................................................... 50

    13.2.1 Maximum limitation of primary return temperature ....................................... 50

    13.2.2 Integral action time....................................................................................... 51

    14 Function block "D.h.w." ................................................................................ 52

    14.1 Operating lines ............................................................................................. 52

    14.2 Assignment of d.h.w. heating ....................................................................... 52

    14.3 Program for d.h.w. circulating pump............................................................. 52

    14.4 Frost protection for d.h.w.............................................................................. 52

    14.5 Release of d.h.w. heating............................................................................. 52

    14.5.1 Function ....................................................................................................... 52

    14.5.2 Release programs........................................................................................ 53

    14.5.3 D.h.w heating during the holiday period ....................................................... 54

    14.6 D.h.w. priority and flow temperature setpoint ............................................... 54

    14.6.1 Settings ........................................................................................................ 54

    14.6.2 D.h.w. priority ............................................................................................... 54

    14.6.3 Absolute priority ........................................................................................... 54

    14.6.4 Shifting priority ............................................................................................. 55

    14.6.5 No priority..................................................................................................... 55

    14.6.6 Flow temperature setpoint............................................................................ 55

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    7/94

    7/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division Contents 15.10.1999

    14.6.7 Maximum selection .......................................................................................55

    14.6.8 D.h.w.............................................................................................................56

    14.7 Type of d.h.w. charging.................................................................................56

    14.8 D.h.w. temperature and d.h.w. switching differential.....................................56

    14.9 Boost of d.h.w. charging temperature ...........................................................57

    14.10 Maximum d.h.w. charging time .....................................................................57

    14.11 Legionella function........................................................................................57

    14.12 Forced charging............................................................................................58

    14.13 Protection against discharging......................................................................58

    14.13.1 Purpose ........................................................................................................58

    14.13.2 Mode of operation.........................................................................................58

    14.14 Manual d.h.w. charging.................................................................................59

    15 Function block "Multi-functional relay"...........................................................60

    15.1 Operating lines..............................................................................................60

    15.2 Functions ......................................................................................................60

    15.2.1 No function....................................................................................................60

    15.2.2 Relay energized in the event of fault.............................................................60

    15.2.3 Relay energized, if there is demand for heat.................................................60

    15.2.4 Circulating pump...........................................................................................61

    15.2.5 Type of d.h.w. chatging.................................................................................62

    16 Function block "Service functions and general settings" ...............................63

    16.1 Operating lines..............................................................................................63

    16.2 Display functions...........................................................................................63

    16.2.1 Hours run counter .........................................................................................63

    16.2.2 Software version ...........................................................................................63

    16.3 Commissioning aids......................................................................................63

    16.3.1 Simulation of outside temperature ................................................................63

    16.3.2 Relay test......................................................................................................64

    16.3.3 Sensor test....................................................................................................64

    16.4 Auxiliary functions.........................................................................................65

    16.4.1 Frost protection for the plant .........................................................................6516.4.2 Manual overriding of operating mode (contact H1) .......................................65

    16.4.3 Pump overrun ...............................................................................................66

    16.4.4 Pump kick .....................................................................................................66

    16.4.5 Winter-/summertime changeover..................................................................66

    16.4.6 Gain of locking signal....................................................................................66

    16.5 Entries for LPB..............................................................................................67

    16.5.1 Source of time of day....................................................................................67

    16.5.2 Source of outside temperature......................................................................68

    16.5.3 Addressing of devices...................................................................................68

    16.5.4 Bus power supply..........................................................................................69

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    8/94

    8/94

    Siemens Building Technologies Basic documentation RVP300, 310, 320 CE1P2474E

    Landis & Staefa Division Contents 15.10.1999

    16.5.5 Bus loading number ..................................................................................... 69

    17 Function block Locking functions" ................................................................ 70

    17.1 Operating line............................................................................................... 70

    17.2 Locking the settings...................................................................................... 70

    18 Communication ............................................................................................ 71

    18.1 Combination with room units ........................................................................ 71

    18.1.1 General ........................................................................................................ 71

    18.1.2 Combination with room unit QAW50 ............................................................ 71

    18.1.3 Combination with room unit QAW70 ............................................................ 71

    18.1.4 Combination with central unit OZW30.......................................................... 73

    18.2 Communication with other devices............................................................... 73

    18.2.1 Data bus....................................................................................................... 73

    19 Handling....................................................................................................... 74

    19.1 Operation ..................................................................................................... 74

    19.1.1 General ........................................................................................................ 74

    19.1.2 Analog operating elements........................................................................... 76

    19.1.3 Digital operating elements............................................................................ 76

    19.1.4 Setting levels and access rights ................................................................... 77

    19.2 Commissioning............................................................................................. 78

    19.2.1 Installation instructions................................................................................. 78

    19.2.2 Operating lines ............................................................................................. 78

    19.3 Installation.................................................................................................... 78

    19.3.1 Mounting location......................................................................................... 78

    19.3.2 Mounting choices ......................................................................................... 78

    19.3.3 Electric installation........................................................................................ 79

    20 Engineering .................................................................................................. 80

    20.1 Connecting terminals.................................................................................... 80

    20.2 Connection diagrams ................................................................................... 81

    20.2.1 Low voltage side .......................................................................................... 81

    20.2.2 Mains voltage side........................................................................................ 81

    21 Mechanical design........................................................................................ 83

    21.1 Basic design................................................................................................. 83

    21.2 Dimensions .................................................................................................. 83

    22 Technical data.............................................................................................. 84

    22.1 RVP300........................................................................................................ 84

    22.2 RVP310........................................................................................................ 84

    22.3 RVP320........................................................................................................ 85

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    9/94

    9/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Summary 15.10.1999

    1 Summary

    1.1 Brief description and key features

    The controllers RVP3... are multi-functional heating controllers for use in residentialand non-residential buildings.

    It is suited for weather-compensated flow temperature control of heating zones with

    or without room temperature influence and for demand-dependent control of heatgenerating equipment (precontrol, RVP320)

    It is used in plants with own heat generating equipment or with a district heat connec-tion (RVP300)

    With regard to d.h.w. heating, the types RVP310 and RVP320 are suited for plantswith d.h.w. storage tanks and electric immersion heaters

    The controllers RVP300 and RVP320 have 2 types of plants preprogrammed. Whena certain type of plant is selected, all functions and settings required for that particular

    plant will be activated

    A multi-functional relay provides additional control functions, if required

    Heating curve adjustment is digital. A setting knob is used for making room tempera-ture readjustments (L&S-standard).

    All the other parameters are set digitally using the operating line principle (L&S- stan-dard)

    The RVP3... are capable of communicating with other units via LPB (Local ProcessBus)

    Key design features: Operating voltage AC 230 V, CE conformity, overall dimensionsto DIN 43700 (96 x 144 mm)

    1.2 Type summary

    The RVP3... are compact controllers that require no plug-in modules.

    1.3 Equipment combinations

    1.3.1 Suitable sensors

    For water temperatures:Suitable are all types of temperature sensors that use a sensing element

    LG-Ni 1000 at 0 C. The following type is presently available:

    Clamp-on temperature sensor QAD22

    Immersion temperature sensors QAE22...

    Immersion temperature sensor QAP21.3 complete with connecting cableFor the room temperature:

    Suitable are all types of temperature sensors that use a sensing element

    LG-Ni 1000 at 0 C. The following type is presently available:

    Room temperature sensor QAA24

    For the outside temperature: Outside sensor QAC22 (sensing element LG-Ni 1000 at 0 C)

    Outside sensor QAC32 (sensing element NTC 575 at 20 C)

    1.3.2 Suitable room units

    Room unit QAW50

    Room unit QAW70

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    10/94

    10/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Summary 15.10.1999

    1.3.3 Suitable actuators

    The following actuators from Landis & Staefa can be used:

    Three-position actuators with a running time of 0.5...14.5 minutesTwo-position actuators Operating voltage AC 24 V ... AC 230 V

    1.3.4 CommunicationCommunication is possible with the following units:

    All Landis & Staefa controllers with LPB communication capability SYNERGYR central unit OZW30 (from software version 3.0)

    1.3.5 Documentation

    Type of documentation Ordering number (for English)

    Data sheet RVP300 CE1N2474E

    Data sheet RVP310 CE1N2475E

    Data sheet RVP320 CE1N2476E

    Operating instructions RVP3... 74 319 0072 0Installation Instructions RVP3... 74 319 0080 0

    Data sheet QAW50 CE2N1635E

    Data sheet QAW70 CE2N1637E

    Data sheet "LPB Basic System Data" CE1N2030E

    Data sheet "LPB Basic Engineering Data" CE1N2032E

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    11/94

    11/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Use 15.10.1999

    2 Use

    2.1 Types of plant

    The RVP3... are suitable for all types of heating plant that use weather-compensated

    flow temperature control.

    With regard to d.h.w. heating, the RVP3... are suited for plants with storage tanks

    Main applications: Heating zones and d.h.w. heating with own heat generation Heating zones and d.h.w. heating with a district heat connection Interconnected plants consisting of heat generation, several heating zones and cen-

    tral or decentral d.h.w. heating

    2.2 Types of houses and buildings

    Basically, the RVP3... are suited for use in all types of houses and buildings. However,

    they have been designed especially for:

    Multi-family housesSingle-family houses

    Small to medium-size non-residential buildings

    2.3 Types of heating systems

    The RVP3... are suited for use with all standard heating systems, such as:

    Radiators ConvectorsUnder floor heating systemsCeiling heating systemsRadiant panels

    2.4 FunctionsThe RVP3... are used if one or several of the following functions is / are required:

    Weather-compensated flow temperature control Flow temperature control through a modulating seat or slipper valve (three- or two-

    position actuator)

    Weather-compensated flow temperature control and simultaneous demand- depend-ent control of the boiler temperature

    D.h.w. storage tank charging through control of a charging pump, with or without cir-culating pump

    Optimum start / stop control according to the selected weekly program Quick setback and boost heating according to the selected weekly program

    ECO function: demand-dependent switching of the heating system based on the typeof building construction and the outside temperature

    Multi-functional relay Weekly program for building occupancy with a maximum of three setback periods per

    day and daily varying occupancy schedules

    Own weekly switching program for the release of d.h.w. heating Input of one holiday period per year Automatic summer-/wintertime changeover Display of parameters, actual values, operational statuses and fault status messages Communication with other units via LPB Remote operation via room unit and external switches

    Service functions Frost protection for the plant, the boiler and the house or building Minimum or maximum limitation of the return temperature

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    12/94

    12/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Use 15.10.1999

    Minimum and maximum limitation of the flow temperature Maximum limitation of room temperature Periodic pump run Pump overrun Maximum limitation of the rate of setpoint increase Legionella function Manual d.h.w. charging

    For the preprogrammed heating and d.h.w. heating circuits and their possible combina-

    tions, refer to section 3.2 Plant types.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    13/94

    13/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Fundamentals 15.10.1999

    3 Fundamentals

    3.1 Key technical features

    The RVP3... offer two key technical features:

    RVP300 and RVP320 have two plant types pre-programmed, P310 one. Each planttype is comprised of a heating circuit and a d.h.w. circuit.

    All functions and their settings are combined in the form of function blocks

    3.1.1 Plant types with regard to heating circuit

    In terms of heating circuit, the following plant types are available:

    Heating circuit plant type no. 1 "Space heating with mixing valve" Heating circuit plant type no. 2 "Space heating with district heat" Heating circuit plant type no. 3 "Space heating with mixing valve and precontrol with

    boiler"

    3.1.2 Plant types with regard to d.h.w. heating

    In terms of d.h.w., the following plant types are available: D.h.w. plant type no. 0 "No d.h.w." D.h.w. plant type no. 1 "Storage tank with charging pump"

    3.1.3 Function blocks

    The following function blocks are available:

    Function block "Enduser space heating"Function block "Enduser d.h.w."Function block "Enduser general"Function block "Plant type"Function block "Space heating"Function block Actuator heating circuit"Function block "Boiler"Function block "Setpoint of return temperature limitation"Function block "District heat"Function block "D.h.w."Function block "Multi-functional relay" Function block "Service functions and general settings"Function block Locking functions"For each function block, the required settings are available in the form of operating

    lines. On the following pages, a description of the individual functions per block and line

    is given.

    3.2 Plant types

    The functions required for each type of plant are ready assigned. When commissioning

    the installation, the relevant plant type must be selected.

    Each plant type is comprised of a heating circuit and a d.h.w. circuit.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    14/94

    14/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Fundamentals 15.10.1999

    3.2.1 Selectable combinations

    Type ref-

    erence

    Type of heating circuit Type of d.h.w.

    heating

    RVP300 RVP310 RVP320

    10 Space heating with

    mixing valve

    No d.h.w.

    11 Space heating with

    mixing valve

    Storage tank with

    charging pump

    20 Space heating with

    district heat

    No d.h.w.

    30 Space heating with

    mixing valve and pre-

    control with boiler

    No d.h.w.

    31 Space heating with

    mixing valve and pre-

    control with boiler

    Storage tank with

    charging pump

    3.2.2 Plant type 10: Space heating with mixing valve, no d.h.w.

    B7

    N1

    A6

    B1Y1

    E2

    M2

    B9 LPB

    B5

    2

    474S01

    Space heating with weather-compensated flow temperature control (three-position or

    two-position control).

    Outside temperature signal from own sensor or data bus. With or without room tem-perature influence. Heating up and setback according to the heating program.

    No d.h.w.

    3.2.3 Plant type 11: Space heating with mixing valve, d.h.w.

    heating with charging pump

    B31

    M3

    K6

    K6

    2475S01B7

    N1

    A6

    B1Y1

    E2

    M2

    B9 LPB

    B5

    Space heating with weather-compensated flow temperature control (three-position or

    two-position control).

    Outside temperature signal from own sensor or data bus. With or without room tem-

    perature influence. Heating up and setback according to the heating program.

    Charging of d.h.w. storage tank through control of the charging pump. D.h.w. control with

    temperature sensor or control thermostat. Circulating pump or electric immersion heaterare optional.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    15/94

    15/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Fundamentals 15.10.1999

    3.2.4 Plant type 20: Space heating with district heat, no

    d.h.w.

    B9

    M2

    E2

    B7

    N1

    Y1

    B1B5A6

    2474S02

    LPB

    E3

    Space heating with district heat connection, with weather-compensated flow tempera-

    ture control acting on the valve in the primary return (three-position or two-position

    control).

    Outside temperature signal from own sensor or data bus. With or without room tem-

    perature influence. Heating up and setback according to the heating program.

    No d.h.w.

    3.2.5 Plant type 30: Space heating with mixing valve and

    precontrol with boiler, no d.h.w.

    2476S01

    B7

    N1

    A6

    B1Y1

    E2

    M2

    B9 LPB

    B5B2E1 M1

    Space heating with weather-compensated flow temperature control (three-position or

    two-position control). Simultaneous demand-dependent control of the boiler tempera-

    ture, two-position control through control of the burner.

    Outside temperature signal from own sensor or data bus. With or without room tem-

    perature influence. Heating up and setback according to the heating program.

    No d.h.w.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    16/94

    16/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Fundamentals 15.10.1999

    3.2.6 Plant type 31: Space heating with mixing valve and

    precontrol with boiler, d.h.w. heating with charging pump

    2476S02

    B31

    M3

    K6

    K6

    B7

    N1

    A6

    B1Y1

    E2

    M2

    B9 LPB

    B5B2E1 M1

    Space heating with weather-compensated flow temperature control (three-position or

    two-position control). Simultaneous demand-dependent control of the boiler tempera-

    ture, two-position control through control of the burner.

    Outside temperature signal from own sensor or data bus. With or without room tem-

    perature influence. Heating up and setback according to the heating program.

    Charging of d.h.w. storage tank through control of the charging pump. D.h.w. control with

    temperature sensor or control thermostat Circulating pump or electric immersion heater

    are optional.

    A6 Room unit QAW50 or QAW70 E3 Heat exchanger

    B1 Flow sensor LPB Data bus

    B2 Boiler temperature sensor K6 Electric immersion heater/circulating pump

    B31 Storage tank temperature sensor / thermostat 1 M1 Circulating pump

    B5 Room temperature sensor M2 Heating circuit pump

    B7 Return temperature sensor M3 Charging pump

    B9 Outside sensor N1 Controller RVP3...

    E1 Heat generator (boiler) Y1 Heating circuit mixing valve

    E2 Load (space)

    3.3 Setting levels, function blocks and plant types

    Plant typeOperational

    level

    Function block

    10 11 20 30 31

    End user space heating

    End user d.h.w. heating

    Enduser

    End user general

    Plant type

    Space heating

    Actuator heating circuit

    Boiler:

    Setpoint of return temperature limitation

    District heat

    D.h.w.

    Multi-functional relay

    Heating

    engineer

    Service functions and general settings

    Locking level Locking functions

    The above table shows

    the assignment of function blocks to the three operational levels the function blocks activated with the different plant types

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    17/94

    17/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Fundamentals 15.10.1999

    3.4 Heating circuit operating modes

    The heating circuit operating mode is selected on the controller by pressing the respec-

    tive button. Also, the operating mode can be changed by bridging terminals H1-M.

    3.4.1 Automatic operation

    Automatic changeover from NORMAL to REDUCED temperature, and vice versa,

    according to the weekly program entered Automatic changeover to holiday mode, and back, according to the holiday schedule

    entered

    Demand-dependent switching of the heating system in function of the room and out-side temperature while giving consideration to the building's thermal inertia (ECO

    function)

    Remote operation from a room unit (optional) Frost protection is ensured

    3.4.2 Continuously REDUCED heating

    Continuous heating to the REDUCED temperature

    With ECO functionNo holiday modeRemote operation from a room unit not possibleFrost protection is ensured

    3.4.3 Continuously NORMAL heating

    Continuous heating to NORMAL temperature

    No ECO functionNo holiday modeRemote operation from a room unit not possible

    Frost protection is ensured

    3.4.4 Standby

    Heating is switched off, but is ready to operate Frost protection is ensured

    3.5 D.h.w. operating modes

    D.h.w. heating is switched on and off by pressing the respective button:

    ON (button is lit): D.h.w. heating takes place independent of the heating circuits op-

    erating mode and control. The d.h.w. can be heated in one of three different ways: According to the entered switching program 2

    According to the entered heating circuit program (1 h)

    Continuously (24 hours a day)

    During the entered holiday period, d.h.w. heating and the circulating pump are deac-

    tivated when using controllers with no bus connection (with data bus, depending on

    the setting made).

    OFF (button dark): No d.h.w. Frost protection is ensured

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    18/94

    18/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Fundamentals 15.10.1999

    3.6 Manual operation

    The RVP3... can be switched to manual operation. In that case, the control will be

    switched off.

    In manual operation, the various regulating units behave as follows:

    Heating circuit mixing valve: no power present, but valve can be controlled manuallywith the manual operation buttons ( and ):

    Three-position actuators: can be driven to any position by pressing (close) und

    (open).

    Two-position actuators: power supply to the actuator can be switched on by pressing

    and off by pressing .

    The heating circuit pump M2 is continuously running.

    Boiler: The two burner stages are continuously on. The circulating pump M1 is con-tinuously running

    D.h.w. charging pump: The charging pump is continuously running Circulating pump K6: It is continuously running. Electric immersion heater K6: It is continuously released. Multi-functional relay: It is continuously energized.Manual operation also negates any overriding of the controller's operating mode

    (bridging of H1M).

    3.7 Plant type and operating mode

    Depending on the type of plant selected, the following operating modes are available:

    Plant type

    10, 20, 30 YES YES YES YES NO YES

    11, 31 YES YES YES YES YES YES

    3.8 Operational status and operational level

    The user selects the required operating mode by pressing the respective button. Each

    operating mode has a maximum of two operational statuses with the exception of op-

    erating mode "Continuously NORMAL heating" (only one operational status possible).

    When the ECO function is active, and in the case of quick setback, the operational

    status is always OFF.

    When the operational status is ON, there is a maximum of three operational levels, de-

    pending on the operating mode. The operational level is determined by the heating

    program and the holiday program.

    OFF ON OFF ON OFF ON ON

    Operating mode

    Operational status

    Operational level

    2522B03e

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    19/94

    19/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Acquisition of measured value 15.10.1999

    4 Acquisition of measured value

    4.1 Room temperature (A6, B5)

    4.1.1 Measurement

    The following choices exist:

    A room temperature sensor QAA24 can be connected to terminal B5 A room unit QAW50 or QAW70 can be connected to terminal A6 Two units can be connected to the terminals. In that case, the RVP3... can ascertain

    the average of the two measurements. The other room unit functions will not be af-

    fected by averaging

    4.1.2 Handling of faults

    If there is a short-circuit or open-circuit in one of the two measuring circuits, the control

    responds as follows, depending on the room temperature source (setting on operating

    line 65):

    No sensor (operating line 65 = 0):A short-circuit or open-circuit has no impact on the control. A fault status message

    will not be generated

    Room unit sensor QAW... (operating line 65 = 1):In the event of a short-circuit or open-circuit, the control continues to operate de-

    pending on the function of the room model. A fault status message will be generated.

    Room temperature sensor QAA24 (operating line 65 = 2):In the event of a short-circuit or open-circuit, the control continues to operate de-

    pending on the function of the room model. A fault status message will be generated.

    Average value (operating line 65 = 3):In the event of a short-circuit or open-circuit in one of the two measuring circuits, the

    control continues to operate with the normally working measuring circuit. A faultstatus message will be generated.

    In the case of a short-circuit or open-circuit in both measuring circuits, the control

    continues to operate depending on the function of the room model. Two fault status

    messages will be generated

    Automatic mode (operating line 65 = 4):Since the controller itself decides how it acquires the room temperature, no fault

    status messages can be generated

    4.1.3 Room model

    The RVP3... features a room model. It simulates the development of the room tem-

    perature. In plants with no measurement of the room temperature, it can provide certainroom functions (e.g. quick setback).

    For more details, refer to section 9.4.6 Room model temperature.

    4.2 Flow temperature (B1)

    4.2.1 Measurement

    The flow temperature is acquired with one sensor. It must have a sensing element LG-

    Ni 1000 .

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    20/94

    20/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Acquisition of measured value 15.10.1999

    4.2.2 Handling of faults

    A short-circuit or open-circuit in the measuring circuit is identified and indicated as a

    fault. In that case, the plant responds as follows:

    Plants with three-position control:The heating circuit pump M2 continues to run and the mixing valve will close

    Plants with two-position control:The heating circuit pump M2 continues to run and the actuator is de-energized.

    4.3 Outside temperature (B9)

    4.3.1 Measurement

    The outside temperature is acquired with the outside sensor. This may be a QAC22 or

    QAC32:

    QAC22: sensing element LG-Ni 1000 at 0 C QAC32: sensing element NTC 575 at 20 CThe controller automatically identifies the type of sensor used.

    In interconnected plants, the outside temperature signal is made available via LPB.

    Controllers having their own sensor pass the outside temperature signal to the databus.

    4.3.2 Handling of faults

    If there is a short-circuit or open-circuit in the measuring circuit, the controller responds

    as follows, depending on the outside temperature source:

    Controller not connected to the data bus (LPB):The control operates with a fixed value of 0 C outside temperature. A fault status

    message will be generated.

    Controller connected to the data bus (LPB):If the outside temperature is available via the data bus, it will be used. A fault status

    message will not be generated (this is the normal status in interconnected plants!). If

    there is no outside temperature available on the data bus, however, the control uses

    a fixed value of 0 C outside temperature. In that case, a fault status message will be

    generated

    4.4 Return temperature (B7)

    4.4.1 Measurement

    The return temperature is acquired with a sensor having a sensing element LG-

    Ni 1000 . This measured value is required for the minimum and maximum limitation of

    the return temperature.In interconnected plants, the return temperature with plant type 1x can be acquired via

    the data bus. Controllers with plant type 10 and connected sensor pass the return

    temperature signal to the data bus.

    4.4.2 Handling of faults

    If there is a short-circuit or open-circuit in the measuring circuit, and if the controller re-

    quires the return temperature, it responds as follows:

    If, on the data bus, there is a return temperature from a controller of the same seg-ment available, it is used (only with plant type no. 1x). No fault status message will

    be generated since this is the normal status in inconnected plants

    If, on the data bus, there is no return temperature available, the return temperaturelimitation functions will be deactivated and a fault status message generated

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    21/94

    21/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Acquisition of measured value 15.10.1999

    4.5 D.h.w. storage tank temperature (B31)

    4.5.1 Measurement

    The d.h.w. storage tank temperature can be acquired:

    with a sensor having a sensing element LG-Ni 1000 .with a thermostat

    4.5.2 Handling of faults

    The controller's response to faults in the measuring circuit depends on the type of

    d.h.w. demand (setting on operating line 126):

    with a d.h.w. storage tank temperature sensor (operating line 126 = 0):If there is a short-circuit or open-circuit in the measuring circuit, a fault status mes-

    sage will be generated The d.h.w. will no longer be heated and the charging pump is

    deactivated.

    with a d.h.w. storage tank thermostat (operating line 126 = 1):If, in measuring circuit B31, there is neither an open-circuit (thermostat open) nor a

    short-circuit (thermostat closed), a fault status message will be generated. The d.h.w.

    will no longer be heated and the charging pump is deactivated.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    22/94

    22/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Enduser space heating" 15.10.1999

    5 Function block "Enduser spaceheating"

    This function block contains settings that the enduser himself can make.

    5.1 Operating lines

    Line Function, parameter Unit Factory

    setting

    Range

    1 Setpoint of NORMAL heating C 20.0 0...35

    2 Setpoint of REDUCED heating C 14.0 0...35

    3 Setpoint of holiday mode / frost protection C 10.0 0...35

    4 Weekday (for heating program) 1-7 1...7, 1-7

    5 First heating period, start of NORMAL heating hh:mm 06:00 --:-- / 00:00...24:00

    6 First heating period, start of REDUCED heating hh:mm 22:00 --:-- / 00:00...24:00

    7 Second heating period, start of NORMAL heating hh:mm --:-- --:-- / 00:00...24:00

    8 Second heating period, start of REDUCED heating hh:mm --:-- --:-- / 00:00...24:00

    9 Third heating period, start of NORMAL heating hh:mm --:-- --:-- / 00:00...24:00

    10 Third heating period, start of REDUCED heating hh:mm --:-- --:-- / 00:00...24:00

    12 Date of first day of holiday dd:MM --:-- --:-- / 01.01. ... 31.12.

    13 Date of last day of holiday dd:MM --:-- --:-- / 01.01. ... 31.12.

    14 Heating curve, flow temperature setpoint TV1 at

    an outside temperature of 15 C

    C 30 20...70

    15 Heating curve, flow temperature setpoint TV2 atan outside temperature of 5 C

    C 60 20...120

    5.2 Setpoints

    5.2.1 General

    The setpoints of the NORMAL and the REDUCED room temperature and of frost pro-

    tection for the plant / holiday mode are entered directly in C room temperature. They

    are independent of whether or not the control uses a room temperature sensor.

    5.2.2 Frost protection for the building

    The lowest valid room temperature setpoint always corresponds to at least the setpoint

    of holiday mode / frost protection (setting on operating line 3), even if lower values have

    been entered as the setpoints of the NORMAL and the REDUCED room temperature

    (settings on operating lines 1 and 2).

    If a room temperature sensor is used and the room temperature falls below the holiday

    / frost protection setpoint, ECO if available will stop OFF until the room temperature

    has risen 1 C above the holiday / frost protection setpoint.

    5.3 Heating program

    The heating program of the RVP3... provides a maximum of three heating periods perday. Also, every weekday may have different heating periods.

    Note:

    The entries to be made are not the switching times, but the periods of time during which

    the NORMAL room temperature shall apply. Usually, these periods of time are identical

    to the building's occupancy times. The actual switching times for the change from the

    REDUCED to the NORMAL room temperature, and vice versa, are calculated by the

    optimization function. ( Precondition: optimization is acivated).

    Using the setting "1-7" on operating line 4, it is possible to enter a heating program that

    applies to all days of the week. This simplifies the settings: If the weekend times differ,

    enter the times for the entire week first, and then change days 6 and 7 as required.

    The entries are sorted and overlapping heating periods combined.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    23/94

    23/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Enduser space heating" 15.10.1999

    5.4 Holiday program

    One holiday period per year can be entered. At 00:00 of the first day of the holiday pe-

    riod, changeover to the setpoint of frost protection / holiday mode takes place. At 24:00

    of the last day of the holiday period, the RVP3... will change to NORMAL or REDUCED

    heating in accordance with the time switch settings.

    The settings of the holiday period will be cleared as soon as it has elapsed.

    Depending on the entry made on operating line 121, the holiday function will switch off

    d.h.w. heating and the circulating pump.

    The holiday program is only active in AUTO mode.

    5.5 Heating curve

    The heating curve can be adjusted on operating lines 14 and 15. For details, refer to

    section 9.6 Heating curve.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    24/94

    24/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Enduser d.h.w." 15.10.1999

    6 Function block "Enduser d.h.w."This function block contains one settings for d.h.w. heating that the enduser himself can

    make.

    6.1 Operating line

    Line Function, parameter Unit Factory

    setting

    Range

    26 Setpoint of d.h.w. temperature C 55 20...100

    6.2 Setpoint

    The setpoint of the d.h.w. temperature is to be entered in C. When using a thermostat,

    it must be made certain that the setpoint entered here agrees with the setpoint of the

    thermostat. If there is a differential, the charging temperature cannot be correctly cal-

    culated (charging temperature = setpoint [operating line 26] + boost of charging tem-

    perature [operating line 127]).

    If d.h.w. heating is switched to the electric immersion heater, the setpoint adjustment is

    inactive in that case, since the thermostat of the electric immersion heater will ensure

    temperature control of the d.h.w. storage tank.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    25/94

    25/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Enduser general" 15.10.1999

    7 Function block "Enduser general"This function block contains settings that the enduser himself can make, as well as the

    indication of faults.

    7.1 Operating lines

    Line Function, parameter Unit Factory

    setting

    Range

    31 Weekday for switching program 2 1-7 1...7, 1-7

    32 Start of first ON period hh:mm 06:00 --:-- / 00:00...24:00

    33 End of first ON period hh:mm 22:00 --:-- / 00:00...24:00

    34 Start of second ON period hh:mm --:-- --:-- / 00:00...24:00

    35 End of second ON period hh:mm --:-- --:-- / 00:00...24:00

    36 Start of third ON period hh:mm --:-- --:-- / 00:00...24:00

    37 End of third ON period hh:mm --:-- --:-- / 00:00...24:00

    38 Time of day hh:mm 00:00...23:59

    39 Weekday 1...7

    40 Date dd:MM 01.01. ... 31.12.

    41 Year jjjj 1995...2094

    50 Indication of faults 0...255

    7.2 Switching program 2

    Switching program 2 of this function block can be used for one or several of the follow-

    ing functions:

    As a time switch program for the circulating pump As a time switch program for the release of d.h.w. heatingSwitching program 2 of the RVP3... affords up to three ON periods per day. Also, every

    weekday may have different ON periods.

    As with the heating program, it is not the "switching times" that are to be entered, but

    the periods of time during which the program or the controlled function shall be active.

    Using the setting "1-7" on operating line 31, it is possible to enter a switching program

    that applies to all days of the week. This simplifies the settings: If the weekend times

    are different, first enter the times for the entire week, then change days 6 and 7 as re-quired.

    The entries are sorted and overlapping ON periods combined.

    7.3 Time of day and date

    The RVP3... have a yearly clock to enter the time of day, weekday and date.

    The changeover from summer- to wintertime, and vice versa, is automatic. Should the re-

    spective regulations change, the changeover dates can be adjusted (refer to chapter 16

    Function block "Service functions and general settings").

    7.4 Indication of faults

    The following faults are indicated:

    Number Fault

    10 Open-circuit or short-circuit in the outside sensor's measuring circuit (B9)

    20 Open-circuit or short-circuit in the measuring circuit of the boiler sensor (B2)

    30 Open-circuit or short-circuit in the measuring circuit of the flow sensor (B1)

    40 Open-circuit or short-circuit in the measuring circuit of the return sensor (B7)

    50 Fault in the measuring circuit of the d.h.w. storage tank sensor / thermostat

    (B31)

    60 Open-circuit or short-circuit in the measuring circuit of the room sensor (B5)

    61 Open-circuit or short-circuit in the measuring circuit of the room unit's sen-sor (A6)

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    26/94

    26/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Enduser general" 15.10.1999

    62 Wrong room unit connected

    81 Short-circuit on data bus (LPB)

    82 Same bus address exists on the data bus (LPB) several times

    100 Two clock masters on the data bus (LPB)

    140 Inadmissible bus address or inadmissible plant type

    If a fault occurs, the LCD displays Er.

    In interconnected plants, the address (device and segment number) of the controller

    causing the fault is indicated on all the other controllers, but no address is displayed onthe controller causing the fault. No address will appear on the controller causing the

    fault.

    Example of display in interconnected plants:

    2474Z03

    50

    20

    06

    02

    = operating line

    = error number

    = segment number (LPB)

    = device number (LPB)

    The fault status message disappears only after rectification of the fault. There will be no

    acknowledgement!

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    27/94

    27/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Plant type" 15.10.1999

    8 Function block "Plant type"This function block only contains the selection of the plant type.

    8.1 Operating line

    Line Function, parameter Factory setting Range

    51 Plant type RVP300 10 10, 20RVP310 11 11

    RVP320 31 30, 31

    8.2 General

    When commissioning the plant with RVP300 or RVP320, the respective plant type must

    be entered first. This ensures that the functions required for the specific type of plant,

    the parameters and operating lines for the settings and displays will be activated.

    All plant-specific variables and operating lines for the other plant types will then be

    dead. They will not be displayed.

    RVP310: The plant type is ready selected (11).

    Example of a selection:

    3

    0

    = Heating circuit type no. 3

    = D.h.w. circuit type no. 0

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    28/94

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    29/94

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    30/94

    30/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    9.3.2 Switching the heating on

    The heating will be switched on again only when allthree of the following conditions

    are satisfied:

    The actual outside temperature has fallen 1 C below the current ECO heating limit The composite outside temperature has fallen 1 C below the current ECO heating limit The attenuated outside temperature has fallen 1 C below the "ECO day" heating

    limit

    9.3.3 Operating modes and operational statuses

    The ECO function is performed depending on the operating mode:

    Operating mode or operational status ECO function Actual heating limit

    Automatic operation Active ECO day or ECO night

    Continuously REDUCED

    heating

    Active ECO night

    Continuously NORMAL

    heating

    Inactive

    Standby Active ECO night

    Frost protection / holiday

    mode

    Active ECO night

    Manual operation Inactive

    9.4 Optimization

    9.4.1 Definition and purpose

    Operation of the heating system is optimized. EN 12098 defines optimization as "auto-

    matic shifting of the switch-on and switch-off points aimed at saving energy". This

    means that:

    Switching on and heating up as well as switching off are controlled such that duringbuilding occupancy times the required room temperature level will always be ensured

    The smallest possible amounts of energy will be used to achieve this objective

    9.4.2 Fundamentals

    It is possible to select or set:

    The type of optimization: either with room temperature sensor / room unit or based onthe room model

    The maximum limit value for the heating-up time The maximum limit value for optimum shutdown Quick setback: yes or noTo perform the optimization function, the controller makes use of the actual room tem-

    perature acquired by a room temperature sensor or room unit or the room model.

    9.4.3 Optimization with room sensor

    Using a room temperature sensor or room unit, it is possible to have optimum start and

    optimum stop control.

    To be able to optimally determine the switch-on and switch-off points, optimization

    needs to "know" the building's heating up and cooling down characteristics, always in

    function of the prevailing outside temperature. For this purpose, optimization continuallyacquires the room temperature and the respective outside temperature. It captures

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    31/94

    31/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    these variables via the room temperature sensor and the outside sensor and continu-

    ally adjusts the forward shift of the switching points. In this ways, optimization can also

    detect changes made to the building and to take them into consideration.

    The learning process always concentrates on the first heating period per day.

    9.4.4 Optimization with room sensor

    When no room temperature sensor is used, the room model onlyallows optimum start

    control.

    Optimization operates with fixed values (no learning process), based on the set maxi-

    mum heating up time and the room model.

    9.4.5 Process

    HP

    TRw TRx

    TRwTRw

    TRw

    HP Heating program

    TR Room temperaturet Time

    t1 Forward shift for early shutdown

    t2 Forward shift for the start of heating up

    t3 Quick setback

    TRw Room temperature setpoint

    TRw Setpoint of NORMAL room temperature

    TRw Setpoint of REDUCED room temperature

    TRw (with boost heating)TRx Actual value of room temperature

    9.4.6 Room model temperature

    To ascertain the room temperature generated by the room model, a distinction must be

    made between two cases:The controller is not in quick setback mode:The room temperature generated by the room model is identical to the actual room

    temperature setpoint

    The controller is in setback mode:The room temperature generated by the room model is determined according to the

    following formula:

    t

    Room model temperature TRM[C] = (TRw -TAM) *e3 * kt

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    32/94

    32/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    2522D18

    t1

    TRwT

    RM

    TRw

    TRw

    Development of room temperature as generated by the room model

    e 2.71828 (basis of natural logarithms) TR Room temperature

    kt Building time constant in hours TRM Room model temperature

    t Time in hours TRw Setpoint of NORMAL room temperature

    t1 Quick setback TRw Setpoint of REDUCED room temperature

    TAM Composite outside temperature

    9.4.7 Optimum stop control

    During the building's occupancy time, the controller maintains the setpoint of NORMAL

    heating. Toward the end of the occupancy time, the control switches to the REDUCED

    setpoint. Optimization calculates the changeover time such that, at the end of occu-

    pancy, the room temperature will be 0.5 C below the setpoint of NORMAL heating (op-

    timum shutdown).

    By entering 0 hours as the maximum optimum shutdown, optimum stop control can be

    deactivated.

    9.4.8 Quick setback

    When changing from the NORMAL temperature to a lower temperature level (RE-

    DUCED or holidays / frost), the heating will be shut down. And it will remain shut down

    until the setpoint of the lower temperature level is reached.

    When using a room temperature sensor, the effective actual value of the room tem-perature is taken into account

    When using no room temperature sensor, the actual value is simulated by the roommodel

    The duration is determined according to the following formulaTRw -TAM

    t [ h ] = 3 *kt*(-ln )

    TRw -TAMwhere:ln Natural logarithm

    kt Building time constant in hours

    t Duration of quick setback

    TAM Composite outside temperature

    TRw Setpoint of NORMAL room temperature

    TRw Setpoint of REDUCED room temperature

    9.4.9 Optimum start control

    During the building's non-occupancy times, the controller maintains the setpoint of RE-

    DUCED heating. Toward the end of the non-occupancy time, optimization switches the

    control to boost heating. This means that the selected boost will be added to the room

    temperature setpoint. Optimization calculates the changeover time such that, at the

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    33/94

    33/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    start of occupancy, the room temperature will have reached the setpoint of NORMAL

    heating.

    When the room temperature is simulated by the room model, that is, when using no

    room temperature sensor, the forward shift in time is calculated as follows:

    t [ min ] = ( TRw -TRM) *60

    where:

    t Forward shift

    TRw Setpoint of NORMAL room temperatureTRM Room model temperature

    Optimum start control with the room model takes place only if, previously, quick setback

    was effected.

    Optimum start control can be deactivated by entering 0 hours as the maximum heating

    up period.

    9.4.10 Boost heating

    For boost heating, a room temperature setpoint boost can be set.

    After changeover to the NORMAL temperature, the higher room temperature setpoint

    applies, resulting in an appropriately higher flow temperature setpoint.

    D.h.w. heating during boost heating does not affect the latter.

    t

    2522D08

    TR

    TRw

    TRx

    TRw

    TRw

    TRw

    t TimeTR Room temperature

    TRw Setpoint of NORMAL room temperature

    TRw Setpoint of REDUCED room temperature

    TRx Actual value of room temperature

    TRw Room temperature setpoint

    TRw Boost of room temperature setpoint (with boost heating)

    Duration of boost:

    When using a room temperature sensor, boost heating is maintained until the room

    temperature has reached the setpoint of NORMAL heating. Then, that setpoint will beused again

    When using no room temperature sensor, the room model calculates how long boostheating will be maintained. The duration is determined according to the following for-

    mula

    TRw -TRM1 ktt1[ h ] = 2 *TRw -TRw

    *

    20

    The duration of the boost is limited to two hours.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    34/94

    34/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    t

    2522D19

    TRM

    TR

    t1

    TRM1

    TRw

    TRw

    TRw

    TRw

    where:

    kt Building time constant in hours

    t Time

    t1 Duration of room temperature setpoint boost

    TR Room temperature

    TRw Setpoint of NORMAL room temperature

    TRw Setpoint of REDUCED room temperature

    TRM Room model temperature

    TRM1 Room model temperature at the start of boost heating

    TRw Room temperature setpoint

    TRw Boost of room temperature setpoint (with boost heating)

    9.5 Room functions

    9.5.1 Maximum limitation of room temperature

    For the room temperature, it is possible to have an adjustable maximum limitation. A

    room temperature sensor is required (sensor or room unit).

    If the room temperature lies 1 C above the limit value, the room temperature setpoint

    will be lowered by 4 C.

    Maximum limitation of the room temperature is independent of the setting used for the

    room temperature influence.

    If the room temperature lies above the limit value, the display shows .

    The reduction of the flow temperature setpoint TVwis calculated as follows:

    TVw[K] = TRw*( 1 + s )

    -1 -0,5 0,5 1 1,5 2 2,5 3

    TRw

    TR

    s Heating curve slope

    TRw Reduction of room temperature setpointTR Deviation of room temperatureTVw Reduction of flow temperature setpoint

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    35/94

    35/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    9.5.2 Room temperature influence

    The room temperature is included in the control process. A room temperature sensor is

    required (sensor or room unit).

    The gain factor for the room temperature influence can be adjusted. This indicates to

    what extent deviations of the actual room temperature from the setpoint have an impact

    on flow temperature control:

    0 = room temperature deviations have no impact on the generation of the setpoint

    20 = room temperature deviations have a maximum impact on the generation of the

    setpoint

    The change of the room temperature setpoint TRwis calculated according to the fol-

    lowing formula:

    VFTRw[K] =

    2* ( TRw-TRx)

    TRw

    TR

    TRw

    The change of the flow temperature setpoint TVwresulting from the change of the

    room temperature setpoint is calculated as follows:

    TVw[K] = TRw*( 1 + s )

    s Heating curve slope

    TRw Room temperature setpoint

    TRw Change of room temperature setpointTRw Decrease of room temperature setpoint+TRw Increase of room temperature setpointTRx Actual value of room temperature

    TR Room temperature deviation (TRw-TRx)TVw Change of flow temperature setpointVF Gain factor

    9.6 Heating curve

    9.6.1 Purpose

    With the space heating systems, flow temperature control is always weather-

    compensated. The assignment of the flow temperature setpoint to the prevailing out-

    side temperature is made via the heating curve.

    9.6.2 Basic setting

    The setting of the heating curve is made via two operating lines. The following settings

    are required:

    Flow temperature setpoint at an outside temperature of 5 C Flow temperature setpoint at an outside temperature of 15 CThe basic setting during commissioning is made according to the planning documenta-

    tion or in agreement with local practices.It is made on operating lines 14 and 15.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    36/94

    36/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    Operating line Setpoint

    14 TV1, current flow temperature setpoint at an outside

    temperature of 15 C

    15 TV2, current flow temperature setpoint at an outside

    temperature of 5 C

    2474Z06

    120

    110

    100

    90

    80

    70

    60

    40

    30

    20

    10

    20 15 10 5 0 -5

    50

    -10 -15 -20 -30

    BZ 14 BZ 15

    TVw

    TA

    Basic setting of heating curveBZ 14 Setting on operating line 14, flow temperature setpoint at 15 C outside temperature

    BZ 15 Setting on operating line 15, flow temperature setpoint at 5 C outside temperature

    TA Outside temperature

    TVw Flow temperature setpoint

    9.6.3 Deflection

    The heat losses of a building are proportional to the difference between room tem-perature and outside temperature. By contrast, the heat output of radiators does not in-

    crease proportionally when the difference between radiator and room temperature in-

    creases. For this reason, the radiators' heat exchanger characteristic is deflected. The

    heating curve's deflection takes these properties into consideration.

    In the range of small slopes (e.g. with underfloor heating systems), the heating curve is

    practically linear due to the small flow temperature range and therefore corresponds

    to the characteristic of low temperature heating systems.

    The slope s is determined according to the following formula:

    TVw(5)TVw(+15)

    s = 20 K

    s Heating curve slope

    TVw(5) Flow temperature setpoint at an outside temperature of 5 CTVw(+15) Flow temperature setpoint at an outside temperature of 15 C

    The heating curve is valid for a room temperature setpoint of 20 C.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    37/94

    37/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    9.6.4 Parallel displacement of heating curve

    The heating curve can be displaced parallel with the setting knob for room temperature

    readjustments. The readjustment can be made by the enduser and covers a maximum

    range of 4.5...+4.5 C room temperatureThis parallel displacement of the heating curve is calculated as follows:

    Parallel displacement TFlow= ( TKnob)*( 1 + s )

    20 10 0 -10 -20 -30

    90

    80

    70

    60

    50

    40

    30

    2522D10

    100

    0

    1010

    0

    30

    TRw

    TA

    TV

    Parallel displacement of heating curve

    s Slope

    TA Outside temperature

    TV Flow temperature

    TRw Room temperature setpoint

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    38/94

    38/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Space heating" 15.10.1999

    9.7 Generation of setpoint

    Weather-compensated control is used with all plant types. The setpoint is generated in

    function of the outside temperature via the heating curve. The temperature used is the

    compositeoutside temperature.

    SYNERGYROZW30

    1 + s

    20 C

    1 + s

    2474B01e

    scomposite outsidetemperatur

    setting knobroom unit *

    heating curve

    setting knobon controller

    flow temperaturesetpoint TVw

    room setpoint

    or

    operating line1, 2 oder 3

    LPB Data bus

    OZW30 SYNERGYR central unit

    s Slope

    * Active only with room unit level

    The impact of the central unit OZW30 is described in section 18.1.4 Combination with

    central unit OZW30.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    39/94

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    40/94

    40/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block Actuator heating circuit" 15.10.1999

    The rate of increase of the flow temperature setpoint can be limited to a maximum. In

    that case, the maximum rate of increase of the flow temperature setpoint is the selected

    temperature per unit of time (C per hour). This function:

    prevents cracking noise in the piping protects objects and construction materials that are sensitive to quick temperature in-

    crease (e.g. antiquities)

    prevents excessive loads on heat generating equipmentThis function can be deactivated (setting ---).

    10.3 Type of actuator

    On operating line 88, it is possible to select the type of actuator (type of control):

    0 = Two-position control

    1 = Three-position control

    10.3.1 Two-position control

    The two-position control operates as weather-compensated flow temperature control.

    The flow temperature is controlled through ON / OFFof the regulating unit (mixing

    valve). The switching differential can be adjusted on operating line 89.

    2474D01

    ON

    OFF

    TVw

    SD2

    SD2

    TV

    ON Actuator operating

    OFF Actuator without power supply

    SD Switching differntial (operating line 89)

    TV Flow temperature

    TVw Flow temperature setpoint

    10.3.2 Three-position control

    The three-position control operates as weather-compensated PI flow temperature con-

    trol. The flow temperature is controlled through a modulating regulating unit (slipper or

    seat valve). Owing to the I-part, there is no control offset.

    10.4 Auxiliary variables in interconnected plants

    10.4.1 Excess flow temperature mixing valve / heat exchanger

    In interconnected plants, an excess flow temperature mixing valve resp. heat ex-

    changer can be entered on the RVP3... . This is a boost of the respective heating

    zone's flow temperature setpoint. The higher setpoint is delivered to the heat generat-

    ing equipment as the heat demand signal (in the controller itself or via data bus).

    The excess mixing valve or heat exchanger temperature is set on the controller thatdrives the mixing valve (controller N2 in the example below) (operating line 84).

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    41/94

    41/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block Actuator heating circuit" 15.10.1999

    Example:

    N2

    wN2wN1 = wN2+ w 2

    522S07

    wN2 + w

    w

    N1 Boiler temperature controller (heat generation)

    N2 Flow temperature controller (heating zone)

    wN1 Setpoint of boiler temperature controller

    wN2 Setpoint of flow temperature controller

    w (set on control ler N2)

    10.5 Pulse lock with three-position actuator

    If, during a period of time that equals five times the running time, the three-position ac-

    tuator has received only closing or only opening pulses, additional closing pulses deliv-

    ered by the controller will be locked. This minimizes the strain on the actuator.

    For safety reasons, the controller delivers a one-minute closing pulse at 10-minute in-

    tervals.

    An opening pulse negates the pulse lock.

  • 8/9/2019 Heating Circuit and D H W Controller 17588 Hq En

    42/94

    42/94

    Siemens Building Technologies Basic documentation RVP300, RVP310, RVP320 CE1P2474E

    Landis & Staefa Division Function block "Boiler" 15.10.1999

    11 Function block "Boiler"Function block "Boiler" acts as a two-position controller and is used for direct burner

    control. The function block operates either as demand-dependent boiler temperature

    controller of a common flow, which supplies heat to one or several consumers.

    11.1 Operating lines

    Line Function, parameter Unit Factory setting

    Range

    91 Operating mode of boiler 0 0...2

    92 Maximum limitation of boiler temperature C 95 25...140

    93 Minimum limitation of boiler temperature C 10 5...140

    94 Switching differential of boiler C 6 1...20

    95 Minimum limitation of burner running time min 4 0...10

    96 R