8/13/2019 Heat Load Calculation Ktm Mch
1/16
DB WB F RH% DP Grs./ lb Enthalp
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqft Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh air Fresh air
North 0 11 0.56 0.00 cfm change
East 0 11 0.56 0.00
South 119.4 13 0.56 869.23 909.792 3
West 0 164 0.56 0.00 ESHF ADP Deh. Rise eh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.79 56 15.84 4086
South East 0 11 0.56 0.00
South West 0 127 0.56 0.00
Solar heat gain through walls
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP)
East 0 23 0.44 0.00 Deh cfm ERSH / 1.08 * temp rise
South 442.2 21 0.44 4085.93 Supply cf ERSH / 1.08 * DESIRED Td
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 1399.68 16 0.48 10749.54
Floor 1399.68 16 0.48 10749.54
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
Internal heat gain
People 50 280 14000.00
Equipment kw 2.96 3410 1.00 10093.60
Volume cuft 18195.84
Total Area in sqft 1399.68 Latitude 8.29
Height ft 13 Suntime 16 :00
Space used : DEPARTMENT OF ORTHODONTICS Date : 23/01/2010
Floor lvl SECOND
HEAT LOAD ESTIMATE
Client Medical College City : KOTAYAM
8/13/2019 Heat Load Calculation Ktm Mch
2/16
Lights watts 1200 3.41 1.25 5115.00
Subtotal 55662.84
Safety factor 5% 2783.14
Room sensible heat 58445.99
SA duct gain 2.5% 1461.15
SA fan gain 5% 2922.30
Fresh Air 3 #### 2.4 1.08 7074.54
Reheat
Effective room sensible heat 69903.98
Latent heat
People 50 270 13500.00
Subtotal 13500.00
Safety factor 5% 675.00
Room latent heat 14175.00
Fresh Air 3 #### 2.4 0.68 4454.34
Effective room latent heat 18629.34
Effective room total heat 88533.32
Outdoor Air Heat
Fresh Air Sens 909.79 20 0.88 1.08 17293.33
Fresh air lat 909.79 73 0.88 0.68 39742.63
RA gain
RA fan gain
Grand Total 145569.27
Tons TR 12.13
8/13/2019 Heat Load Calculation Ktm Mch
3/16
P G CLINIC
DB WB F RH% DP Grs./ lb Enthalp
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqft Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh air Fresh air
North 0 11 0.56 0.00 cfm change
East 0 11 0.56 0.00
South 89.55 13 0.56 651.92 682.344 3
West 0 164 0.56 0.00 ESHF ADP Deh. Rise eh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.82 56 15.84 2793
South East 0 11 0.56 0.00
South West 0 127 0.56 0.00
Solar heat gain through walls
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP)
East 0 23 0.44 0.00 Deh cfm ERSH / 1.08 * temp rise
South 421.2 21 0.44 3891.89 Supply cfm ERSH / 1.08 * DESIRED Td
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 1049.76 16 0.48 8062.16
Floor 1049.76 16 0.48 8062.16
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
Internal heat gain
People 25 280 7000.00
Equipment kw 1.72 3410 1.00 5865.20
Latitude 8.29Height ft 13 Suntime 16 :00
HEAT LOAD ESTIMATE
Client Medical College City : KOTAYAM
DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECT Date : 23/01/2010
Volume cuft 13646.88
Total Area in sqft 1049.76
Floor lvl Ground Floor
8/13/2019 Heat Load Calculation Ktm Mch
4/16
Lights watts 960 3.41 1.25 4092.00
Subtotal 37625.33
Safety factor 5% 1881.27
Room sensible heat 39506.59
SA duct gain 2.5% 987.66
SA fan gain 5% 1975.33
Fresh Air 3 #### 2.4 1.08 5305.91
Reheat
Effective room sensible heat 47775.49
Latent heat
People 25 270 6750.00
Subtotal 6750.00
Safety factor 5% 337.50
Room latent heat 7087.50
Fresh Air 3 #### 2.4 0.68 3340.76
Effective room latent heat 10428.26
Effective room total heat 58203.75
Outdoor Air Heat
Fresh Air Sens 682.34 20 0.88 1.08 12969.99
Fresh air lat 682.34 73 0.88 0.68 29806.97
RA gain
RA fan gain
Grand Total 100980.71
Tons TR 8.42
8/13/2019 Heat Load Calculation Ktm Mch
5/16
OPERATION THEATRE
DB WB F RH% DP Grs./ lb Enthalp
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqf Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh air Fresh air
North 0 11 0.56 0.00 cfm change
East 29.85 11 0.56 183.88
South 59.7 13 0.56 434.62 454.896 3
West 0 164 0.56 0.00 ESHF ADP eh. Rise eh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.88 56 15.84 2111
South East 0 11 0.56 0.00
South West 0 127 0.56 0.00
Solar heat gain through walls
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP)
East 110.55 23 0.44 1118.77 Deh cfm ERSH / 1.08 * temp rise
South 221.1 21 0.44 2042.96 Supply cf ERSH / 1.08 * DESIRED Td
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 699.84 16 0.48 5374.77
Floor 699.84 16 0.48 5374.77
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
Internal heat gain
People 10 280 2800.00
Equipment kw 2.48 3410 1.00 8456.80
Volume cuft 9097.92
Total Area in sqft 699.84 Latitude 8.29Height ft 13 Suntime 16 :00
EPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELE Date : 23/01/2010
Floor lvl Ground Floor
HEAT LOAD ESTIMATE
Client Medical College City : KOTAYAM
8/13/2019 Heat Load Calculation Ktm Mch
6/16
Lights watts 720 3.41 1.25 3069.00
Subtotal 28855.56
Safety factor 5% 1442.78
Room sensible heat 30298.34
SA duct gain 2.5% 757.46
SA fan gain 5% 1514.92
Fresh Air 3 #### 2.4 1.08 3537.27
Reheat
Effective room sensible heat 36107.99
Latent heat
People 10 270 2700.00
Subtotal 2700.00
Safety factor 5% 135.00
Room latent heat 2835.00
Fresh Air 3 #### 2.4 0.68 2227.17
Effective room latent heat 5062.17
Effective room total heat 41170.16
Outdoor Air Heat
Fresh Air Sens 454.90 20 0.88 1.08 8646.66
Fresh air lat 454.90 73 0.88 0.68 19871.31
RA gain
RA fan gain
Grand Total 69688.14
Tons TR 5.81
8/13/2019 Heat Load Calculation Ktm Mch
7/16
STERILISATION AREA
DB WB F RH% DP Grs./ lb Enthalp
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqf Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh air Fresh air
North 0 11 0.56 0.00 cfm change
East 0 11 0.56 0.00
South 0 13 0.56 0.00 37.947 3
West 0 164 0.56 0.00 ESHF ADP Deh. Rise eh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.73 56 15.84 161
South East 0 11 0.56 0.00
South West 0 127 0.56 0.00
Solar heat gain through walls
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP)
East 0 23 0.44 0.00 Deh cfm ERSH / 1.08 * temp rise
South 0 21 0.44 0.00 Supply cf ERSH / 1.08 * DESIRED Td
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 58.38 16 0.48 448.36
Floor 58.38 16 0.48 448.36
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
Internal heat gain
People 3 280 840.00
Equipment kw 0.08 3410 1.00 272.80
Latitude 8.29Height ft 13 Suntime 16 :00
HEAT LOAD ESTIMATE
Client Medical College City : KOTAYAM
EPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELE Date : 23/01/2010
Volume cuft 758.94
Total Area in sqft 58.38
Floor lvl Ground Floor
8/13/2019 Heat Load Calculation Ktm Mch
8/16
Lights watts 40 3.41 1.25 170.50
Subtotal 2180.02
Safety factor 5% 109.00
Room sensible heat 2289.02
SA duct gain 2.5% 57.23
SA fan gain 5% 114.45
Fresh Air 3 37.95 2.4 1.08 295.08
Reheat
Effective room sensible heat 2755.77
Latent heat
People 3 270 810.00
Subtotal 810.00
Safety factor 5% 40.50
Room latent heat 850.50
Fresh Air 3 37.95 2.4 0.68 185.79
Effective room latent heat 1036.29
Effective room total heat 3792.06
Outdoor Air Heat
Fresh Air Sens 37.95 20 0.9 1.08 721.30
Fresh air lat 37.95 73 0.9 0.68 1657.65
RA gain
RA fan gain
Grand Total 6171.00
Tons TR 0.51
8/13/2019 Heat Load Calculation Ktm Mch
9/16
DB WB F RH% DP Grs./ lb Enthalpy
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqft Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh air Fresh air
North 0 11 0.56 0.00 cfm change
East 119.4 11 0.56 735.50
South 0 13 0.56 0.00 758.16 3
West 0 164 0.56 0.00 ESHF ADP Deh. Rise eh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.83 56 15.84 2998
South East 0 11 0.56 0.00
South West 0 127 0.56 0.00
Solar heat gain through walls
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP)
East 582.6 23 0.44 5895.91 Deh cfm ERSH / 1.08 * temp rise
South 0 21 0.44 0.00 Supply cf ERSH / 1.08 * DESIRED Td
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 1166.4 16 0.48 8957.95
Floor 1166.4 16 0.48 8957.95
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
Internal heat gain
People 25 280 7000.00
Equipment k 1.64 3410 1.00 5592.40
Volume cuft 15163.2
Total Area in sqft 1166.4 Latitude 8.29Height ft 13 Suntime 16 :00
pace used : DEPARTMENT OF CONSERVATIVE DENTISTR Date : 23/01/2010
Floor lvl THIRD (P.G CLINIC)
HEAT LOAD ESTIMATE
Client Medical College City : KOTAYAM
8/13/2019 Heat Load Calculation Ktm Mch
10/16
Lights watts 720 3.41 1.25 3069.00
Subtotal 40208.72
Safety factor 5% 2010.44
Room sensible heat 42219.16
SA duct gain 2.5% 1055.48
SA fan gain 5% 2110.96
Fresh Air 3 758.16 2.4 1.08 5895.45
Reheat
Effective room sensible heat 51281.04
Latent heat
People 25 270 6750.00
Subtotal 6750.00
Safety factor 5% 337.50
Room latent heat 7087.50
Fresh Air 3 758.16 2.4 0.68 3711.95
Effective room latent heat 10799.45
Effective room total heat 62080.50
Outdoor Air Heat
Fresh Air Sen 758.16 20 0.88 1.08 14411.11
Fresh air lat 758.16 73 0.88 0.68 33118.85
RA gain
RA fan gain
Grand Total 109610.46
Tons TR 9.13
8/13/2019 Heat Load Calculation Ktm Mch
11/16
U G CLINIC
DB WB F RH% DP Grs./ lb Enthalpy
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqft Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh a Fresh air
North 0 11 0.56 0.00 cfm change
East 0 11 0.56 0.00
South 179.1 13 0.56 1303.85 1364.7 3
West 0 164 0.56 0.00 ESHF ADP eh. Rise Deh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.84 56 15.84 6430 1.Plain Glass( cl E) hasSouth East 0 11 0.56 0.00 2.Light & Equipmnet lo
South West 0 127 0.56 0.00 3.Roof facor,as normal
Solar heat gain through walls 4.Roof factor to be fill
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP) 5.Ceiling facor to be fill
East 0 23 0.44 0.00 Deh cfm ERSH / 1.08 * temp rise 6.Floor facor when ,we
South 663.3 21 0.44 6128.89 Supply cf ERSH / 1.08 * DESIRED Td 7.The caliculation tabl
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 2099.52 16 0.48 16124.31
Floor 2099.52 16 0.48 16124.31
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
13 Suntime 16 :00
Volume cuft 27293.76
Height ft
HEAT LOAD ESTIMATE
Medical College City : KOTAYAM
ace used : DEPARTMENT OF CONSERVATIVE DENTIST Date : 23/01/2010
Client
THIRD
2099.52 Latitude 8.29Total Area in sqft
Floor lvl
8/13/2019 Heat Load Calculation Ktm Mch
12/16
Internal heat gain
People 50 280 14000.00
Equipment k 7.08 3410 1.00 24142.80
Lights watts 2400 3.41 1.25 10230.00
Subtotal 88054.17
Safety factor 5% 4402.71
Room sensible heat 92456.88
SA duct gain 2.5% 2311.42
SA fan gain 5% 4622.84
Fresh Air 3 1364.69 2.4 1.08 10611.81
Reheat
Effective room sensible heat 110002.96
Latent heat
People 50 270 13500.00
Subtotal 13500.00Safety factor 5% 675.00
Room latent heat 14175.00
Fresh Air 3 1364.69 2.4 0.68 6681.51
Effective room latent heat 20856.51
Effective room total heat 130859.47
Outdoor Air Heat
Fresh Air Sen 1364.69 20 0.88 1.08 25939.99
Fresh air lat 1364.69 73 0.88 0.68 59613.94
RA gain
RA fan gain
Grand Total 216413.40
Tons TR 18.03
8/13/2019 Heat Load Calculation Ktm Mch
13/16
o be changed from .56 to.1.0 ad to be taken as per site conditions.
building.
d when the Roof is exposed.
ed up in case of Floor on top.
have floor below the Space to be airconditioend/\
only for large areas of Above 500 sq ft.
8/13/2019 Heat Load Calculation Ktm Mch
14/16
DB WB F RH% DP Grs./ lb Enthalpy
Btu/lb
Summer 95 80 52.5 188 44
Monsoon 85 80 80.65 212 44
Room 74 100 27.5
Diff 21 88 16.5
Item Area sqft Sun gain Factor Btu / hr
TD Summer Outdoor air details
Solar heat gain through glass Fresh air Fresh air
North 0 11 0.56 0.00 cfm change
East 0 11 0.56 0.00
South 119.4 13 0.56 869.23 909.792 3
West 0 164 0.56 0.00 ESHF ADP Deh. Rise Deh. Cfm
North East 0 11 0.56 0.00
North West 0 103 0.56 0.00 0.79 56 15.84 4086 1.Plain Gla
South East 0 11 0.56 0.00 2.Light & ESouth West 0 127 0.56 0.00 3.Roof faco
Solar heat gain through walls 4.Roof fact
North 0 19 0.44 0.00 Deh rise ( 1- BF)* ( RM DB - ADP) 5.Ceiling fa
East 0 23 0.44 0.00 Deh cfm ERSH / 1.08 * temp rise 6.Floor fac
South 442.2 21 0.44 4085.93 Supply cfm ERSH / 1.08 * DESIRED Td 7.The calic
West 0 17 0.44 0 Outlet Td ERSH / 1.08 * De hum CFM
North East 16 0.44 0.00
North West 11 0.44 0.00
South East 23 0.44 0.00
South West 19 0.36 0.00
Transmission gain through roof/ ceiling/partitions
Roof 0 0.48 0.00
Ceiling 1399.68 16 0.48 10749.54
Floor 1399.68 16 0.48 10749.54
Partition 0 16 0.40 0.00
All glass 0 21 1.10 0.00
Internal heat gain
People 50 280 14000.00
Equipment k 2.96 3410 1.00 10093.60
Latitude 8.29Height ft 13 Suntime 16 :00
HEAT LOAD ESTIMATE
Client Medical College City : KOTAYAM
Space used : DEPARTMENT OF ORTHODONTICS Date : 23/01/2010
Volume cuft 18195.84
Total Area in sqft 1399.68
Floor lvl SECOND
8/13/2019 Heat Load Calculation Ktm Mch
15/16
Lights watts 1200 3.41 1.25 5115.00
Subtotal 55662.84
Safety factor 5% 2783.14
Room sensible heat 58445.99
SA duct gain 2.5% 1461.15
SA fan gain 5% 2922.30
Fresh Air 3 909.79 2.4 1.08 7074.54
Reheat
Effective room sensible heat 69903.98
Latent heat
People 50 270 13500.00
Subtotal 13500.00
Safety factor 5% 675.00
Room latent heat 14175.00
Fresh Air 3 909.79 2.4 0.68 4454.34
Effective room latent heat 18629.34
Effective room total heat 88533.32
Outdoor Air Heat
Fresh Air Se 909.79 20 0.88 1.08 17293.33
Fresh air lat 909.79 73 0.88 0.68 39742.63
RA gain
RA fan gain
Grand Total 145569.27
Tons TR 12.13
8/13/2019 Heat Load Calculation Ktm Mch
16/16
s( cl E) has to be changed from .56 to.1.0
uipmnet load to be taken as per site conditions. r,as normal building.
or to be filled when the Roof is exposed.
cor to be filled up in case of Floor on top.
r when ,we have floor below the Space to be airconditioend/\
lation table only for large areas of Above 500 sq ft.