    Spreadsheet Problem Solving for ChE Faculty

    Heat Loss from a Pipe

    Basic Data Heat Transfer Calculations

    Nominal Pipe Size 2 inches Surface Temperature Estimate

    Pipe Outside Diameter 2.38 inches 125.0 degFDo 0.0605 m TsEst 51.7 degC

    Fluid Temperature 300 degF Surface Heat Transfer CoefficientTf 148.9 degC DeltaT 30.6 degC

    hs 12.1 W/(m 2*degC) Ambient Temperature 70 degF 2.12 BTU/(hr*ft 2*degF)

    Ta 21.1 degC Heat Lossq 99.4 W/m

    Insulation Thickness 0.5 inches 31.5 BTU/(hr*ft)0.0127 m

    Outside Diameter 3.38 inches Surface Temperature CheckDs 0.0859 m Ts 51.7 degC

    125.0 degFInsulation Thermal Conductivity

    0.033 BTU/(hr*ft*degF)k 0.0571 W/(m*degC)

    T F

    D i

    D o

    D s

    T a

    T s

    ( )( )

    f a

    s o

    s s

    T T q

    ln D D 12k h D

    p -

    =

    +

    ( ) s o s f

    ln D DT T q

    2 k p =-