Hawaiian Electric Advanced Inverter Test Plan – Result Summary

Anderson Hoke, Ph.D., P.E. Austin Nelson, Kumaraguru Prabakar, and Adarsh Nagarajan

Hawaiian Electric Companies Technical Conference Honolulu, Hawaii October 14, 2016 NREL/PR-5D00-67267

Page 2: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

2

1. HECO-SolarCity-NREL collaboration (2014-2016, complete) • Transient and temporary overvoltage evaluation • Anti-islanding with advanced inverters in multi-inverter, multi-point islands • Impacts of coordinated volt-var control on power quality and conservation voltage reduction

2. HECO advanced inverter test plan (2016 – Focus of this presentation) • Baseline testing • Circuit-level PHIL testing

3. DOE GMLC – Hawaii regional partnership, DOE funded (2016-2017 – Next presentation) • Focus is on fast grid frequency support from DERs (including, but not limited to, frequency-

Watt function) • Modeling, simulation, and controls development • Hardware testing • Field deployment

4. Simulation of inverter-based voltage regulation (2016-2017 – Started September 2016) • Simulate 3 HECO circuits with volt-var, volt-watt, fixed PF (and combinations), plus legacy

inverters • Variables: PV penetration, portion of legacy inverters, PV system DC:AC ratio • Quantify effects on annual feeder voltage profiles and on PV kWh production loss • Extension of advanced inverter test plan

Note: Other work not covered here: PSIP support, work prior to 2015, etc

Context – Recent and ongoing NREL-HECO work

Page 3: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

3

• NREL: Andy Hoke, Austin Nelson, Kumar Prabakar, Adarsh Nagarajan, Shaili Nepal, Rasel Mahmud – NREL

• Hawaiian Electric Companies: Earle Ifuku, Marc Asano, Reid Ueda, Jon Shindo, Kandice Kubojiri, Riley Ceria, Justin Goza

• Inverter manufacturer participants: o Apparent o Enphase Energy o SMA o SolarEdge

• Smart Inverter Technical Working Group

Advanced Inverter Test Plan Team

Page 4: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

4

1. Define test details (test scenarios) – Complete 2. Baseline testing – Complete

• Evaluate each inverter’s ability to perform selected advanced functions • Results used to develop simple model of each inverter • Based on draft UL 1741 SA (but will not qualify for or impact UL certification) • Volt-Watt, FPF, VRT, FRT, ramp rate, soft start • Volt-var added later. (Baseline testing only – no PHIL testing)

3. PHIL testing – Complete • Use PHIL to test inverters as if connected to high penetration HECO circuits • One/two inverters in hardware, many more simulated in real time • Compare tests with/without various advanced functions active • Vary advanced function control parameters

4. Result dissemination to stakeholders (ongoing, including today) 5. Final Report to PUC – December 15 6. Follow-up project – Recently started

• NREL-HECO CRADA: Voltage Regulation Operational Strategies (VROS) • Long-term simulation of various PV voltage regulation functions on HECO

feeders

Statement of Work Fo

cus o

f pre

sent

atio

n

Page 5: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

5

Baseline testing: Volt-Watt

• Based on draft UL 1741 SA volt-watt test • Three volt-watt curves tested

• Snapshot mode (“0”) and Pmax mode (“1”) on 2/4 inverters • Varying time responses • Varying levels of available PV power (irradiance) • 33 test series, 495 total points tested • All inverters capable; responses as expected

0.950, 1.000 1.060, 1.000

1.075, 0.625

1.100, 0.000

1.05, 1

1.06, 0

1.10, 0.50

1.14, 0.000.00

0.20

0.40

0.60

0.80

1.00

1.20

0.90 0.95 1.00 1.05 1.10 1.15 1.20

Max

Wat

t Rat

ed, p

er u

nit

or

Max

Wat

t Ava

ilabl

e, p

er u

nit

Voltage, per unit

Proposed Volt-Watt Function

Function 1 Function 3 Function 4 (~AI TWG)

“Mild” curve (Based on MAITAI input)

“Moderate” curve (HECO 1st )

“Aggressive” curve (HECO 2nd )

Moderate curve

Aggressive curve

Mild curve

Proprietary data and preliminary results Please do not distribute

Page 6: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

6

Volt-Watt example

Time (sec)

500 1000 1500 2000 2500 3000 3500 4000

RM

S V

olta

ge (V

)

120

125

130

Enphase S280 Test # 43: Time Const = 50 sec, Curve 1, Power = 100, Mode = 1

L1

L2

Time (sec)

500 1000 1500 2000 2500 3000 3500 4000

Pow

er (k

VA

)

0

2

4

6

P

Q

S

Inverter 2

Moderate curve

Proprietary data and preliminary results Please do not distribute

Page 7: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

7

Baseline testing: Simultaneous volt-var and volt-watt

Volt-var curves depend on inverter’s maximum VArs . This plot assumes Qmax = 0.5 pu.

Proprietary data and preliminary results Please do not distribute

Only 2 inverters capable; 2 curve combinations; 4 test series, 108 total test points Can be activated under Rule 14H by mutual agreement, per HECO

Page 8: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

8

Volt-var with volt-watt example

Voltage (% Nominal)

100 102 104 106 108 110 112

Rea

ctiv

e P

ower

(% N

amep

late

)

-30

-20

-10

0SolarEdge V-VAr with V-W Test Case 1

Measured

Expected

Voltage (% Nominal)

100 102 104 106 108 110 112

Rea

l Pow

er (%

Nam

epla

te)

0

50

100

150Measured

Expected

Inverter 4

Proprietary data and preliminary results Please do not distribute

Page 9: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

9

Baseline testing: Voltage and frequency ride-through

• Based on draft UL 1741 SA ride-through tests • Tested using Oahu country/profile (as in field) • VRT: 3 UVR levels, 2 OVR levels (per 14H)

o UVR2 tested at two adjustable time settings (per 14H) o 56 total tests

• FRT: 2 UFR levels, 2 OFR levels (per 14H) o UFR1 tested at two adjustable time settings (per 14H) o 56 total tests

• Each test repeated at 20% and 100% power levels • Legacy Enphase (i.e., M-Series) inverters also tested • All inverters capable of meeting Rule 14H, but slope of ride-through

test profile in draft test was too steep for one – product is being updated based on recently-published 1741 SA

Proprietary data and preliminary results Please do not distribute

Page 10: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

10

Frequency ride-through examples

OFR1: 57 < f < 56 Hz for 20 s

OFR1: 63 < f < 65 Hz for 20 s (high end of 14H range of adjustability)

Time (sec)

15 20 25 30 35Freq

uenc

y (H

z)

56

60

64

SolarEdge Test # 26:

Time (sec)

15 20 25 30 35

Pow

er (k

VA

)

-20

0

20

P

Q

S

Time (sec)

15 20 25 30 35Freq

uenc

y (H

z)

56586062

SolarEdge Test # 31:

Time (sec)

15 20 25 30 35

Pow

er (k

VA

)

-20

0

20

P

Q

S

Inverter 4 Inverter 4

Proprietary data and preliminary results. Please do not distribute

Page 11: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

11

Baseline testing summary

All inverters “passed” all tests, but some tests required interaction with manufacturer: • Some IMs had not seen draft UL 1741 SA in advance (or had seen

an old version), so some test details were a surprise, requiring slight test modifications

• Functions (or combinations of functions) not required in another grid code were not supported in all inverters: o Ramp-rate control o Simultaneous volt-watt and volt-var

• All IMs expected to be able to pass UL 1741 SA in next 12 months – timing and selection of functions is up to each manufacturer

• Configuring functions manually is time-consuming and error-prone. Engineering and firmware development of pre-configured function profiles (aka “country settings”) will be needed for commercial field deployment.

Proprietary data and preliminary results Please do not distribute

Page 12: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

12

Recommendations from baseline testing

• Some areas of Rule 14H would benefit from clarification. Work is underway between Hawaiian Electric and NREL to address gaps: o Volt-var requirements need to be defined in detail

– Pay attention to var capability (rectangular vs triangular; vars at max P) o Volt-watt requirements need to be defined in detail o Clarify how response times are defined o Where possible, align with Rule 21 and/or IEEE P1547 (draft, near-final)

– Some variation in settings from other codes should be okay o If simultaneous operation of various voltage regulation functions is

required, that should be specified. • Where function details not yet specified, unclear if manufacturers

will make Hawaii-specific functions available in 12 months o Recommend continued discussions with stakeholders on the near-term,

high-priority voltage regulation functions

Proprietary data and preliminary results Please do not distribute

Page 13: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

Circuit-level Power Hardware-in-the-Loop Testing

Page 14: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

14

PHIL test introduction

• Goal: Test inverters as if connected to real HECO circuits • Method: Run real-time dynamic simulation of HECO circuit in parallel

with, and interacting dynamically with, hardware inverter test. (Power hardware-in-the-loop, PHIL)

• To capture fast dynamics, real-time feeder simulation solves circuit over 4000 times per second.

• Feeder model detail must be reduced to allow fast computation. • Feeder reduction overview:

1. Convert from Synergi to OpenDSS and validate 2. Select nodes to retain 3. Reduce feeder (process depicted on next slide) 4. Validate voltages by simulating at multiple load levels (100%, 75%, 50%) 5. Translate reduced model from OpenDSS (quasistatic) to

SimPowerSystems (electromagnetic transient) and re-validate 6. Add aggregated PV models 7. Add selected distribution secondary circuit(s)

Proprietary data and preliminary results

Please do not distribute

Page 15: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

15

Feeder reduction process

Reduction Validation

Proprietary data and preliminary results. Please do not distribute

Page 16: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

16

PHIL test summary

• Two circuits (K3L and M34) adapted from full HECO Synergi models: o Synergi → OpenDSS → reduced OpenDSS → SimPowerSystems o 8 primary nodes retained, voltages validated o 4 aggregated inverter types at each node → 32 modeled inverters:

o Inverter capacities based on detailed data on existing PV systems and projections of future inverters provided by HECO

o Capacity and settings of each type of inverter at each node vary between tests

• Both circuits contain a detailed single-phase secondary model in one location, provided by HECO. Single-phase hardware inverters are connected here. Three-phase hardware inverter (#4) connected to a simple fabricated secondary far from the feeder head.

• Secondary impedances not modeled elsewhere.

Legacy Enphase Advanced function capable Enphase

Legacy non-Enphase Advanced function capable non-Enphase

Proprietary data and preliminary results Please do not distribute

Page 17: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

17

Reduced-order distribution feeder model (one of two)

Proprietary data and preliminary results. Please do not distribute.

Feeder head

Reduced-order feeder

primary

Selected secondary

circuit (detailed model)

Hardware inverter PCC

Primary nodes with: • Aggregated load • Four aggregated PV

inverter models

Simulated PV inverter

Secondary nodes (e.g. houses)

Proprietary data and preliminary results

Please do not distribute

MV:LV transformer

Page 18: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

18

Real-time model for PHIL

• Real-time HECO feeder model contains two PCCs for hardware inverters

• Hardware inverters are connected to AC supply driven by simulated PCC voltage

• Many more inverters simulated with various controls in distribution feeder model

Real-time simulation (OPAL-RT)

Oahu frequencydynamic model

Controllable voltage source

HECO feeder model

Trip signal and event

parameters

f

Console subsystemSlave subsystem:Bulk power system

Master subsystem:Distribution system

Data and control signals

va, vb, vc

Slave subsystem: Inverter controls & data processing

Simulated inverter controls

iinv1,iinv2, …, iinv32

vinv1, vinv2, …,

vinv32

Data and control signals

vpcc1 iac1

Physical hardware

Inverter hardware

AC power amplifier

Inverter hardware

AC power amplifier

iac2

vpcc2

PV / DC supply

PV / DC supply

Proprietary data and preliminary results Please do not distribute

Page 19: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

19

PHIL test scenario overview

• Each PHIL test focuses on a single event lasting few minutes in time • Summary of test scenario matrix developed by NREL and HECO,

vetted by SITWG: o 180 volt-watt tests (details on next slide) o 24 VRT tests:

– Distant event (simulated) reduces voltage at inverter terminals, then recovers within required ride-through time. Voltage event designed to cover multiple VRT levels

o 24 FRT tests: – Bulk system conditions cause temporary frequency event. Frequency

recovers within required ride-through time. Event designed to cover multiple FRT levels

o 18 ramp-rate tests: – PV output low due to low irradiance. Irradiance rises (200 W/m2 → 1000

W/m2) o 18 soft-start tests:

– Inverter comes online following voltage event and ramps to full power

Proprietary data and preliminary results Please do not distribute

Page 20: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

20

Volt-watt PHIL test scenarios

• General scenario: POI voltage near top of ANSI Range A (1.05 pu). PV output low due to low irradiance. Irradiance rises (e.g. 200 W/m2 → 1000 W/m2 in 40 seconds). o Record voltages and powers at inverter POI and other key locations on circuit. o Load set low (MDL), feeder head voltage set high, and legacy PV added to

secondary to produce interesting test cases • Volt-watt test variables

o 3 volt-watt curves, plus baseline with volt-watt off o 2 volt-watt styles: snapshot, Pmax o 3 fixed PF settings (0.98, 0.95, 0.90), plus baseline with unity PF o 2 retrofit proportions for legacy inverters: (25%, 50%), plus baseline with

no retrofit o Present and future (2021) PV penetration cases

– All “future” inverters assumed to be capable of V-W and non-unity PF • Inverter 1 and Inverter 4 tested independently • Inverters 2 and 3 tested simultaneously (neighboring locations on same

secondary) • Different subset of variable combinations tested for each inverter to

maximize the number of variables covered within time available

Proprietary data and preliminary results Please do not distribute

Page 21: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

21

Simulated inverters – volt-watt test scenarios

Total PV inverter ratings • M34 circuit:

• K3L circuit:

Proprietary data and preliminary results Please do not distribute

Year Portion of PV

inverters retrofitted Legacy PV

(MW) Advanced PV

(MW) Total PV

(MW)

2016

None 3.9 0 3.9

25% 2.9 1.0 3.9

50% 1.9 1.9 3.9

2019

None 3.9 11.2 15.1

25% 2.9 12.1 15.1

50% 1.9 13.1 15.1

Year Portion of PV

inverters retrofitted Legacy PV

(MW) Advanced PV

(MW) Total PV

(MW)

2016

None 3.0 0 3.0

25% 2.3 0.8 3.0

50% 1.5 1.5 3.0

2019

None 3.0 1.8 4.8

25% 2.3 2.5 4.8

50% 1.5 3.3 4.8

Page 22: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

22

Volt-watt PHIL test example

Inverter 1, volt-watt disabled, unity PF, year 2021, no retrofit

Proprietary data and preliminary results. Please do not distribute

0 20 40 60 80 100 120 140 160 180 200

P (W

)

10 6

0

0.5

1

1.5

2Inverter 1, K3L, V-W Curve 0, Power Factor = 1, Mode = Snapshot

0

1

2

3

4

5

6

7

Inv1

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.1

Time (sec)

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.11

3

5

7

9

11

13

Inv1

Secondary

Primary

300x Power for Hardware Inverters

1.082 pu

1.03 pu

1.034 pu

Dashed lines show total power at each node from all four

types of modeled inverters

Page 23: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

23

0 20 40 60 80 100 120 140 160 180 200

P (W

)

10 6

0

1

2Inverter 1, K3L, V-W Curve 1, Power Factor = 0.95, Mode = Snapshot

0 20 40 60 80 100 120 140 160 180 200

Q (V

AR

)

10 5

-4

-2

0

0

1

2

3

4

5

6

7

Inv1

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.1

Time (sec)

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.1

1

3

5

7

9

11

13

Inv1

Secondary

Primary

300x Power for Hardware Inverters

300x Power for Hardware Inverters

Volt-watt PHIL test example

• Inverter 1, moderate volt-watt, 0.95 PF, year 2021, no retrofit

Proprietary data and preliminary results. Please do not distribute

1.069 pu

0.43 pu

0.15 pu

1.034 pu

Page 24: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

24

Summary of Inverter 1 volt-watt tests, K3L circuit

Proprietary data and preliminary results. Please do not distribute

V-W Curve

0 1 2

Vol

tage

(p.u

.)

1.06

1.065

1.07

1.075

1.08

1.085Final PCC Voltages, Inverter 1, V-W Tests, K3L

PF = 1.00, Mode = Snapshot

PF = 0.98, Mode = Snapshot

PF = 0.95, Mode = Snapshot

PF = 0.90, Mode = Snapshot

PF = 1.00, Mode = Pmax

PF = 0.98, Mode = Pmax

PF = 0.95, Mode = Pmax

PF = 0.90, Mode = Pmax

Curve 0 = OFF

Curve 1 = MODERATE

Curve 2 = AGGRESSIVE

All Inverter 1 tests: • Year 2021 • No retrofitting

(but all post-2015 PV assumed capable of V-W and Fixed PF)

Page 25: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

25

Summary of Inverter 1 volt-watt tests, K3L circuit

Proprietary data and preliminary results. Please do not distribute

V-W Curve

0 1 2

Vol

tage

(p.u

.)

1.06

1.065

1.07

1.075

1.08

1.085Final PCC Voltages, Inverter 1, V-W Tests, K3L

Curve 0 = OFF

Curve 1 = MODERATE

Curve 2 = AGGRESSIVE

V-W Curve

0 1 2

Pow

er (p

.u.)

0

0.2

0.4

0.6

0.8

1

1.2Final Output Power, Inverter 1 V-W Tests, K3L

PF = 1.00, Mode = Snapshot

PF = 0.98, Mode = Snapshot

PF = 0.95, Mode = Snapshot

PF = 0.90, Mode = Snapshot

PF = 1.00, Mode = Pmax

PF = 0.98, Mode = Pmax

PF = 0.95, Mode = Pmax

PF = 0.90, Mode = Pmax

V-W Curve

0 1 2

Vol

tage

Cha

nge

(p.u

.)

0.028

0.03

0.032

0.034

0.036

0.038

0.04

0.042

0.044

0.046

0.048Voltage Change, Inverter 1 V-W Tests, K3L

• In this case, both V-W and FPF have significant impacts on voltage

Same plot as previous slide:

PCC voltage change from beginning of test till end:

Effect on hardware PV power output:

Page 26: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

26

Summary of Inverter 1 volt-watt tests, M34 circuit

Proprietary data and preliminary results. Please do not distribute

V-W Curve

0 1 2

Pow

er (p

.u.)

0

0.2

0.4

0.6

0.8

1

1.2Final Output Power, Inverter 1 V-W Tests, M34

PF = 1.00, Mode = Snapshot

PF = 0.98, Mode = Snapshot

PF = 0.95, Mode = Snapshot

PF = 0.90, Mode = Snapshot

PF = 1.00, Mode = Pmax

PF = 0.98, Mode = Pmax

PF = 0.95, Mode = Pmax

PF = 0.90, Mode = Pmax

V-W Curve

0 1 2

Vol

tage

Cha

nge

(p.u

.)

-0.02

-0.01

0

0.01

0.02

0.03

0.04

0.05Voltage Change, Inverter 1 V-W Tests, M34

V-W Curve

0 1 2

Vol

tage

(p.u

.)

1

1.01

1.02

1.03

1.04

1.05

1.06

1.07

1.08Final PCC Voltages, Inverter 1, V-W Tests, M34

Curve 0 = OFF

Curve 1 = MODERATE

Curve 2 = AGGRESSIVE

• In this case, Fixed PF impacts voltage strongly; V-W has comparatively little impact • Reason: much more future PV on this circuit (11 MW on M34 vs 1.8 MW on K3L)

Final hardware inverter PCC voltage:

PCC voltage change from beginning of test till end:

Effect on hardware PV power output:

Page 27: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

27

Volt-watt test example, Inverter 2&3, M34 circuit

Proprietary data and preliminary results. Please do not distribute

Year 2016, no retrofit, no V-W, unity PF, (baseline test)

0 20 40 60 80 100 120 140 160 180 200

P (W

)

10 6

0

5

10Inverters 2 and 3, M34, V-W Curve 0, Power Factor = 1, PV Scenario = 1

0

1

2

3

4

5

6

7

Inv2

Inv3

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.1

Time (sec)

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.10

1

2

3

4

5

Inv2

Inv3

Secondary

Primary

1000x Power for Hardware

Inverters

1.070 pu

1.00 pu

1.043 pu

Page 28: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

28

Volt-watt test example, Inverter 2&3, M34 circuit

Proprietary data and preliminary results. Please do not distribute

Year 2019, no retrofit, moderate V-W (Pmax mode), 0.95 PF

0 20 40 60 80 100 120 140 160 180 200

P (W

)

10 6

0

5

10Inverters 2 and 3, M34, V-W Curve 1, Power Factor = 0.95, PV Scenario = 4

0 20 40 60 80 100 120 140 160 180 200

Q (V

AR

)

10 6

-2

-1

0

1

0

1

2

3

4

5

6

7

Inv2

Inv3

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.1

Time (sec)

0 20 40 60 80 100 120 140 160 180 200

Vrm

s (p

u)

1

1.05

1.1

0

1

2

3

4

5

Inv2

Inv3

Secondary

Primary

1000x Power for Hardware

Inverters

1000x Power for Hardware Inverters

1.030 pu

0.95 pu

0.30 pu

1.037 pu

Page 29: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

29

PV Ratings

1 2 3 4 5 6

Vol

tage

(p.u

.)

0.99

1

1.01

1.02

1.03

1.04

1.05

1.06

1.07

1.08

1.09Final PCC Voltages, Inverter 3 V-W Tests, M34

PF = 1.00, Curve = OFF

PF = 0.95, Curve = OFF

PF = 0.90, Curve = OFF

PF = 1.00, Curve = MODERATE

PF = 0.95, Curve = MODERATE

PF = 0.90, Curve = MODERATE

PF = 1.00, Curve = MILD

PF = 0.95, Curve = MILD

PF = 0.90, Curve = MILD

Ratings 1 = 2016, NO RETROFIT

Ratings 2 = 2016, 25% RETROFIT

Ratings 3 = 2016, 50% RETROFIT

Ratings 4 = 2021, NO RETROFIT

Ratings 5 = 2021, 25% RETROFIT

Ratings 6 = 2021, 50% RETROFIT

Summary of Inverter 2&3 volt-watt tests, M34 circuit

Proprietary data and preliminary results. Please do not distribute

Fixed PF has the dominant impact for this circuit.

2016 2019

Page 30: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

30

Summary of Inverter 2&3 volt-watt tests, K3L circuit Proprietary data and preliminary results.

Please do not distribute

For K3L, both V-W and fixed PF have significant impact, but…

2016 2019 PV Ratings

1 2 3 4 5 6

Vol

tage

(p.u

.)

1.065

1.07

1.075

1.08

1.085

1.09Final PCC Voltages, Inverter 3 V-W Tests, K3L

PF = 1.00, Curve = OFF

PF = 0.95, Curve = OFF

PF = 0.90, Curve = OFF

PF = 1.00, Curve = MODERATE

PF = 0.95, Curve = MODERATE

PF = 0.90, Curve = MODERATE

PF = 1.00, Curve = MILD

PF = 0.95, Curve = MILD

PF = 0.90, Curve = MILD

Ratings 1 = 2016, NO RETROFIT

Ratings 2 = 2016, 25% RETROFIT

Ratings 3 = 2016, 50% RETROFIT

Ratings 4 = 2021, NO RETROFIT

Ratings 5 = 2021, 25% RETROFIT

Ratings 6 = 2021, 50% RETROFIT

Page 31: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

31

Summary of Inverter 2&3 volt-watt tests, K3L circuit – Voltage change

Proprietary data and preliminary results. Please do not distribute Fixed PF has dominant impact on voltage change.

2016 2019 PV Ratings

1 2 3 4 5 6

Vol

tage

Cha

nge

(p.u

.)

-0.04

-0.03

-0.02

-0.01

0

0.01

0.02

0.03

0.04

0.05Voltage Change, Inverter 3 V-W Tests, K3L

PF = 1.00, Curve = OFF

PF = 0.95, Curve = OFF

PF = 0.90, Curve = OFF

PF = 1.00, Curve = MODERATE

PF = 0.95, Curve = MODERATE

PF = 0.90, Curve = MODERATE

PF = 1.00, Curve = MILD

PF = 0.95, Curve = MILD

PF = 0.90, Curve = MILD

Ratings 1 = 2016, NO RETROFIT

Ratings 2 = 2016, 25% RETROFIT

Ratings 3 = 2016, 50% RETROFIT

Ratings 4 = 2021, NO RETROFIT

Ratings 5 = 2021, 25% RETROFIT

Ratings 6 = 2021, 50% RETROFIT

Voltage change from beginning till end of test:

Page 32: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

32

Voltage ride-through PHIL test example (Inverter 1)

0 5 10 15 20 25 30 35 40 45 50

Pow

er (W

)

10 6

0

2

4Mikilua LVRT Test with 14H Settings

Inv0 Inv1 Inv2 Inv3 Inv4 Inv5 Inv6 Inv7 Inv Meas (1000x)

Time (sec)

0 5 10 15 20 25 30 35 40 45 50

Vol

tage

(pu)

0.6

0.8

1

1.2Primary Voltages

Inv0 Inv1 Inv2 Inv3 Inv4 Inv5 Inv6 Inv7 Inv Meas

• Event tests all LVRT levels • Hardware inverter stays online. Modeled legacy inverters trip

Proprietary data and preliminary results Please do not distribute

Page 33: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

33

Voltage ride-through disabled

0 5 10 15 20 25 30 35 40 45 50

Pow

er (W

)

10 6

0

2

4Mikilua LVRT Test with 1547 Settings

Inv0 Inv1 Inv2 Inv3 Inv4 Inv5 Inv6 Inv7 Inv Meas (1000x)

Time (sec)

0 5 10 15 20 25 30 35 40 45 50

Vol

tage

(pu)

0.6

0.8

1

1.2Primary Voltages

Inv0 Inv1 Inv2 Inv3 Inv4 Inv5 Inv6 Inv7 Inv Meas

• Same event • All inverters trip

Proprietary data and preliminary results Please do not distribute

Page 34: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

34

Conclusions: Volt-watt and fixed PF

Proprietary data and preliminary results Please do not distribute

• All inverters were capable of simultaneous V-W and fixed PF • PHIL tests showed V-W has significant impact on voltage in some

cases, but fixed PF tended to have a larger impact. o However, non-unity PF may increase system losses, and requires vars

to be sourced by utility (even if voltages are not high). • A moderate V-W curve had substantial impact on voltage, especially

when combined with 0.95 PF. • The impact of both V-W and fixed PF is highly dependent on the

proportion of total inverters participating. • High feeder head voltages were typically needed to produce high

secondary voltages. => Adjusting LTC controls may help The fine print: • Volt-watt tests were intentionally designed to create high voltages.

Actual feeder voltages will vary. • These tests focused on one specific secondary per feeder. Results

at other locations will vary. (See VROS CRADA)

Page 35: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

35

Next steps

Proprietary data and preliminary results Please do not distribute

• Advanced inverter test plan: o NREL deliver final report to HECO o HECO deliver to PUC by Dec 15

• Voltage regulation operational strategies (VROS) study o Design simulation scenarios and collect data o Conduct simulations to select combinations of volt-watt, volt-

var, and fixed PF o Quantify impacts of selected combinations on annual PV kWh

production and feeder voltage profiles o Complete in Spring 2017

• DOE GMLC work o Simulation and testing of frequency-watt (both presently

available function and possible future advancements) o Complete in Fall 2017

Page 36: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

Thank you!

Questions welcome

Page 37: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

Extra Slides

Page 38: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

38

Baseline testing: Volt-var

• Based on UL 1741 SA volt-var test • Three curves tested, plus inductive and capacitive offsets:

• \

• Tested at various power levels • Varying time responses tested • 29 test series, 950 total points tested

Volt-var curves depend on inverter’s maximum VArs . This plot assumes Qmax = 0.5 pu.

Proprietary data and preliminary results Please do not distribute

Page 39: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

39

Volt-var example

Time (sec)

0 50 100 150 200

RM

S V

olta

ge (V

)

200

250

300SMA Test # 74:

Time (sec)

0 50 100 150 200

Pow

er (k

VA

)

-5

0

5

10P

Q

S

Voltage (% Nominal)

90 95 100 105Rea

ctiv

e P

ower

(% B

asel

ine)

-20

0

20

SMA V-VAr Test Case 1

Measured

Expected

• Moderate curve • 1-second response time • Full power

Inverter 3

Inverter 3

Proprietary data and preliminary results Please do not distribute

Page 40: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

40

Voltage ride-through examples

UVR1: 70% < V < 88% for 20 s

Time (sec)

17.5 18 18.5 19RM

S V

olta

ge (V

)

120

140

Enphase S280 Test # 53:

L1

L2

Time (sec)

17.5 18 18.5 19

Pow

er (k

VA

)

-5

0

5

P

Q

S

OVR1: 110% < V < 120% for 1 s

Time (sec)

10 15 20 25 30RM

S V

olta

ge (V

)

80

100

120

Enphase S280 Test # 11:

L1

L2

Time (sec)

10 15 20 25 30

Pow

er (k

VA

)

-5

0

5

P

Q

S

Inverter 2 Inverter 2

Proprietary data and preliminary results Please do not distribute

Page 41: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

41

Baseline testing: Soft-start and ramp rate control

• Based on UL 1741 SA tests • Soft-start tested at three rates:

o Fastest available o 0.33% per second o Slower ramp rate (typically slowest available)

• Ramp rate control (normal operation) tested at three rates: o Fastest available o 0.33% per second o Slower ramp rate (typically slowest available)

• Legacy Enphase inverters also tested (default values only) • Ramp rate control was a new function for some inverters

Proprietary data and preliminary results Please do not distribute

Page 42: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

42

Soft-start example

Soft-start ramp-rate: 0.33% per second:

Time (sec)

350 400 450 500 550 600 650RM

S V

olta

ge (V

)

276

277

278SolarEdge Test # 4:

L1

L2

L3

All

Time (sec)

350 400 450 500 550 600 650Rea

l Pow

er (k

W)

0

10

20

Inverter 4

Proprietary data and preliminary results Please do not distribute

Page 43: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

43

Baseline testing: Fixed power factor

• Based on UL 1741 SA tests • Not in original test plan – added to allow for PHIL testing of

volt-watt with fixed PF. • Tested 0.9 and 0.95 PF • 0.95 PF tested using Oahu profile • Tested at 100%, 60% and 20% power • Power factor accuracy typically only guaranteed down to 20%

of rated real power. Tested at 10% power as well to characterize behavior. o Commanded power factors still maintained at 10% power, but

accuracy slightly reduced (e.g. 0.94 instead of 0.95)

Proprietary data and preliminary results Please do not distribute

Page 44: Hawaiian Electric Advanced Inverter Test Plan – Result Summary · • Two circuits (K3L and M34) adapted from full HECO Synergi models: o. Synergi → OpenDSS → reduced OpenDSS

44

Fixed power factor example

Time (sec)

50 100 150 200

Pow

er (p

u)

-1

0

1

2SMA Power Factor Test # 72:

Apparent PowerReal Power

Reactive Power

Time (sec)

50 100 150 200

Pow

er F

acto

r

0.9

0.95

1

Inverter 3

Proprietary data and preliminary results Please do not distribute