Harland Simon UPS Ltd

Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

  • Upload
    ledung

  • View
    230

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Harland Simon UPS Ltd

Page 2: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Harland Simon offers a

comprehensive range of rugged

marine approved products that can

be certified by Lloyds, DNV, ABS

and others. These products are

designed and tested to meet the

harsh environment requirements

Page 3: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Job Title Job Number Type of Installation

MCI Electrotechnics - North Sea BO4390 Supply of 8kVA fully marinised and Lloyds Certified UPS for offshore rigs

Hamworthy Combustion Systems BO4974 Design and supply IP54 AC UPS using Vantage NiCad batteries

Electrical Power Engineering BO5409 Supply of 4kVA redundant UPS system

James Fisher - Japan BO5357 Design and supply of 8kVA fully marinised UPS to include and install 24VDC power supply

ABMAS - North Sea BO4969 Supply of 10kVA fully marinised and Lloyds certified UPS systems

Peto - deBeers BO4920/BO5004 Supply of various marine and Lloyds certified UPS systems

Consafe - Karachaganak BO2686 Supply of 2 x redundant 40kVA AC UPS & 110VDC 10A DC Charger housed in an explosive proof enclosure

British Gas - Trinidad BO4411 3 x 15kVA parallel AC UPS complete with 20 year life batteries, transformers and switchgear

Silvertech - Russia BO5158 Custom built AC and DC UPS with a backup time of 24 hours, housed in an IP54 enclosure

Monitor Oil - North Sea BO5110 Custom built AC and DC UPS complete in a 19" rackmount enclosure

Silvertech - Russia BO5111/BO5294 Supply 2 x 8kVA/80 minute 9155M UPS

Silvertech - Dubai BO6262 Supply 3 x 9155 UPS's plus 8 hour batteries - USA version for Libya

ABMAS - North Sea BO6288 Supply 2 x 8kVA 9155M UPS's

James Fisher BO6365 Supply 15kVA 9155M UPS

ICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack

Page 4: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

4

1.

Selection Consideration

for Marine UPS

Section 1.1 of 18

Page 5: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Vessels and rigs have IT-mains

• Physical environment

Vibration

Temperature range

Water

Salt

Little space for installation

• Special regulation requirements

• Classification Societies

• Requirements and wishes of the ship owner, shipyard, etc...

• After sales when the installation site is a moving one

• Competitors

Section 1.2 of 18

Page 6: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• IMO SOLAS + IEC 60092 + Other IEC + Electric code of the flag country + Class flavour

Lloyd’s Register of Shipping Det Norske Veritas (DNV) American Bureau of Shipping ABS Germanischer Lloyd Bureau Veritas

• Interested in UPS if: Critical load: emergency lighting, navigation lighting, alarm monitoring, navigation equipment, radio comm, rudder control

Section 1.3 of 18

Page 7: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Electrical safety

• Insulation, grounding, selectivity, flame retardant materials

Environmental

• Temperature, moisture, salt, vibrations, shock, tilt, roll, pitch

Generation of explosive/inflammable gas

• Mainly battery in our case

Functional

• Electrical performance, back-up time

Section 1.4 of 18

Page 8: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• double-conversion topology

• with static bypass switch

• built to safety and EMC standards

• microprocessor controlled

• robust design for marine use

• power range from 1 to hundreds of kVA’s

• built to the highest requirements of performance, VFI-SS-111 class UPS

(IEC 62040-3 class)

Section 1.5 of 18

Page 9: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Matching outlook

• Various dimensions

• Battery options

• Other optional devices

Section 1.6 of 18

Page 10: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 1.7 of 18

Page 11: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Lloyd’s Register of Shipping

• Det Norske Veritas (DNV)

• Germanisher Lloyd

• Bureau Veritas

• RINA

• American Bureau of Shipping ABS

• Korean standard

• China Classification Society

Section 1.8 of 18

Page 12: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Vessels and rigs have IT-mains

• Often used voltages

208 3-phase

220

230

380

400

440

690

• 50 hz and 60 hz

Section 1.9 of 18

Page 13: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 1.1 0 of 18

Page 14: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 1.11 of 18

Page 15: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

High quality UPS and other components.

Correct configuration and installation.

Sufficient preventative maintenance.

Reliable operation

Lower lifetime cost of ownership

Section 1.12 of 18

Page 16: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Special ships with special equipment

Section 1.13 of 18

Page 17: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Emergency lighting

• Navigation equipment

• Radio etc. telecom, Satcom

• Computer systems and networks

• Emergency PA

• Waterproof doors

Section 1.14 of 18

Page 18: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Azipod propulsion control• Dynamic Positioning Systems• Automation• Power distribution and filtering

Section 1.15 of 18

Page 19: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Critical marine applications: Emergency lighting Integrated bridge (navigation,

communications etc.) Ship automation Cargo automation

Section 1.16 of 18

Page 20: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Critical marine applications: Emergency lighting Navigation & Satcom, radiocom Integrated bridge Automation Propulsion control Emergency public announcement Security camera system Fog horn, alarm bells, etc.

• Cruising applications Computers & data systems Internal cable TV & phone Casino, theatre, audio-visual equipment Hotel, restaurants, shops, EPoS

Section 1.17 of 18

Page 21: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Internal cable TV, phone & loud speaker systems

• Security camera system

• Hotel, restaurants, shops, EPOS

• Casino

Section 1.18 of 18

Page 22: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

4

2.

Eaton Engineered Marine

UPS Solutions

Section 2.1 of 17

Page 23: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

For AC Marine UPS applications Harland Simon are engineering partners for Eaton Powerware Marine and Eaton Pulsar Marine UPS

• 9130 Marine UPS

• 9155 1ph:1ph/3ph:1ph Marine UPS

• Evolution Marine UPS

• EX Marine UPS

• EX RT Marine UPS vibration spec.

• 9355 3ph:3ph Marine UPS

• 9390 Marine UPS

• 9395 Marine UPS

Section 2.2 of 17

Page 24: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

A standard base technology

+ modifications

+ additional components

+ Classification Society Certification

= Marine UPS

Benefits of the modified standard:

Same core components as in normal production

=> proven technology due to large installed base

=> cost wise benefit from the factory volume

Project specific design minimized, R&D not needed

=> shorter project run time, less costs

Field services around the world can use the standard spares, documentation, training and tools

Section 2.3 of 17

Page 25: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

• Voltage conversion

• Galvanic isolation

• Earth leakage monitoring

• Frequency conversion

• Backup time, battery types

• Load distribution gear

• Protection class (IP class)

• Anti-vibration mounts

• Classification societies requirements

Section 2.4 of 17

Page 26: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 2.5 of 17

Page 27: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Standard UPS Marine UPS

Section 2.6 of 17

Page 28: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

MARINISING

ENVIRONMENT

ON BOARD

SHIP OWNER

SHIPYARD etc.

REGULATIONS

SAFETY, CLASS

AFTER SALES

SERVICEPROFITABILITY COMPETITOR

Section 2.7 of 17

Page 29: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 2.8 of 17

Page 30: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Tower

1kVA, 2kVA or 3KVA

Marine approved by DNV

Matching battery packs

Hot swappable batteries

Marine filter for comms.

bridge applications

AVM installation kit

Section 2.9 of 17

Page 31: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Rack or tower

1150VA

Marine approved by DNV

Matching battery packs

Hot swappable batteries

Marine filter for comms.

bridge applications

Section 2.10 of 17

Page 32: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Rack or tower

1.5kVA, 2.2kVA, 3kVA

Marine approved by DNV

Matching battery packs

Hot swappable batteries

Marine filter for comms.

bridge applications

Section 2.11 of 17

Page 33: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

7/11kVA single phase input / single

phase output

5/7/11kVA three phase input / single

phase output

Rugged steel case

Meets marine vibration standards

Matching battery packs

Marine filter for comms. bridge

applications

Section 2.12 of 17

Page 34: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

UPS Marine, also applicable: Offshore, Oil & Gas

9155 / 9355 / 9390 entire range: 8 -160kVA

Hot sync technology for paralleling 1 or more UPS

Advanced Battery Management (ABM)

For ungrounded networks (IT- mains)

Voltage adaption by transformers

Hardened design for vibration and shocks

Mechanical shock absorbers

Higher IP class

Harsh environment applications

Classification society certificates

Section 2.13 of 17

Page 35: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

9155 3 in/1 out 8 – 10kVA

9155 3 in/1 out 8 – 15kVA

9355 3 in/3 out 8 – 15kVA

UPS module

Transformer and MBS module

Battery modules as needed

Section 2.14 of 17

Page 36: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

3 in/3 out 20, 30 and 40kVA

20 and 30kVA: Space for built in

input and output transformer

40kVA: Space for one internal

transformer

External battery cabinets

IP22 Protection Class

Rugged design –

shock/vibration absorbers

Section 2.15 of 17

Page 37: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

40 - 160kVA

External transformers

IP22 Protection Class

Easy to install - can be welded or

bolted to deck/bulkhead

Mechanical shock/vibration

absorbers

Section 2.16 of 17

Page 38: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

225 - 1100kVA

External transformers

IP22 Protection Class

Easy to install - can be welded or

bolted to deck/bulkhead

Mechanical shock/vibration

absorbers

Section 2.17 of 17

Page 39: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

4

3.

Harland Custom Marine

AC UPS Solutions

Section 3.1 of 18

Page 40: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Harland Simon have full engineering & technical expertise to design, manufacture and project manage

complete turnkey AC or DC systems.

Capabilities include but are not limited too:

• Bespoke enclosures - marine spec. finish

• Custom colour finish

• Environmental protection – IP22, IP43, IP44, IP54, etc.

• Rolled steel plinths that can be welded or bolted down

• Input, output, bypass transformers all to marine specifications

• Connectors as required

• Electrical protection & distribution

• Changeover panels for dual supply systems

• Thermal control, heater mats, fans, etc.

• Labelling, earthing

• Earth leakage detection devices

• User display and control

• EMC filters

Section 3.2 of 18

Page 41: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.3 of 18

Page 42: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.4 of 18

Page 43: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: L3

Application: Ship Dynamic Positioning

Rugged 2mm thick welded steel enclosure

To IP23 with AVM and fixing bracket

3kVA AC UPS

30 Minute battery

12 way DP distribution

Input isolation transformer

Earth Fault monitoring

24VDC remote ESD

Dual input C/O contactors

Section 3.5 of 18

Page 44: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: L3

Application: Ship Dynamic Positioning

Rugged 2mm thick welded steel enclosure

To IP23 with AVM and fixing bracket

7kVA AC UPS

30 Minute battery

12 way DP distribution

Input isolation transformer

Earth Fault monitoring

24VDC remote ESD

Dual input C/O contactors

Section 3.6 of 18

Page 45: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: ICS

Application: Proman - Oman

Customer: ICS

Application: Proman - Oman

Rittal TS enclosure

24 hour autonomy DC UPS

4 Hour autonomy AC UPS

Dual AC Input

Long life batteries

IP54 protection

Section 3.7 of 18

Page 46: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: Yokogawa

Application: Sabic - Saudi

Rittal TS enclosure

5 x 3kVA 110VAC UPS

5 x 30 minute NiCd

Dual AC Input

20 year life batteries

IP54 protection

Section 3.8 of 18

Page 47: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: Rolls Royce

Application: QE Class Aircraft Carrier

Rugged enclosure

IP54 and AVM

8-15kVA UPS power module

Input transformer

30 minute VRLA battery

Removable UPS module

Section 3.9 of 18

Page 48: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: Lindsey Oil Refinery

Application: Lincolnshire

An IP54 AC UPS system incorporating Comet

EX RT 7kVA marine vibration approved UPS

to provide 30 minutes autonomy for a 5kVA

load.

The Rugged enclosure included

• split doors with glazed panel

• Output Isolation transformer

• Front mounted filters

• Rear mounted cooling fans

• Maintenance Bypass Switch

• AC and DC Distribution

• Various alarms

Section 3.10 of 18

Page 49: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

IP54 Wall Mount Marine UPS Systems

Incorporating 1 to 3kVA VA UPS typically

Autonomy 15/30 up to 3 hours

Manufacturers battery pack or loose batteries +

Charger option

Separate enclosure for batteries if required

Painted steel or stainless steel finish

Built-in input, output and bypass MCBs

LED Alarm Indication on front door

Alarms, mains fail, low battery, bypass, fault, fan fail

Built in maintenance bypass option

UPS install kit and AVM

Section 3.11 of 18

Page 50: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.12 of 18

Page 51: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.13 of 18

Page 52: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.14 of 18

Page 53: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.15 of 18

Page 54: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.16 of 18

Page 55: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.17 of 18

Page 56: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 3.18 of 18

Page 57: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

4

4.

Harland Custom Marine

DC UPS Solutions

Section 4.1 of 9

Page 58: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

The DCC is a range of automatically controlled

chargers for high reliability in critical

applications

Robust sheet steel enclosure, floor

standing

1 or 3 phase 50/60Hz Input

Output any voltage to 250VDC

Standing Loads up to 500A

Lead-Acid or Ni-Cad battery

Meters, alarms & indications

Section 4.2 of 9

Page 59: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: ICS

Application: Proman - Oman

Customer: ICS

Application: Proman - Oman

Rittal TS enclosure

24 hour autonomy DC UPS

4 Hour autonomy AC UPS

Dual AC Input

Long life batteries

IP54 protection

Section 4.3 of 9

Page 60: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: Monitor Oil

Application: Lyell Buoy

19” rack mount DC UPS System c/w

Dual redundant 250A chargers

24V-12V DC-DC converter for navigation

controls

1500VA inverter

Distribution module

Output isolators

Timed load shedding

20 year life batteries supplied on racks

Space in enclosure for customers own

equipment

Section 4.4 of 9

Page 61: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: Brisco Engineering

19” rack mount system incorporating

Dual redundant 24DC/250A AEG switch mode

Power supply

Side mounted heat exchange unit

Input and output circuit breakers

Section 4.5 of 9

Page 62: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 4.6 of 9

Page 63: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: JP Power

Application: Shipboard DC UPS

Rugged 2mm thick welded steel enclosure to

IP31

Dual redundant DC UPS system incorporating

dual input supplies

Dual redundant 24DC 40A switch mode

PSU/charger modules

PSU’s are rackmount and can be isolated and

removed without powering down the 24DC

load.

Bottom of enclosure houses 2 x 12VDC 100Ah

batteries

Section 4.7 of 9

Page 64: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Section 4.8 of 9

Page 65: Harland Simon UPS · PDF fileICS TRIPLEX Silvertech BO6395 9130/3kVA UPS & battery pack. 4 1. Selection Consideration ... 24V-12V DC-DC converter for ... Dual redundant 24DC/250A AEG

Customer: PDS – Teledyne TSS

Application: Shipboard

DC UPS system for backing up onboard

navigation, gyrocompasses and steering

control systems

System incorporates 2 x 7.5A parallel charger

modules giving total 15A capacity

This system was built into a stainless steel

enclosure, painted with Munsell 7.5BG7/2

finish

Low voltage battery disconnect to prevent

damage to the batteries by deep discharge

Section 4.9 of 9