DRAWING TITLE DRAWING NUMBER H000 DRAWING SCHEDULE DATE ISSUE HVAC COVER SHEET MEDIUM PRESSURE STEAM SUPPLY MEDIUM PRESSURE STEAM RETURN TRANSFER FAN WATER SOURCE HEAT PUMP VARIABLE FREQUENCY DRIVE TOTAL STATIC PRESSURE WALL SUPPLY GRILLE WALL SUPPLY REGISTER WALL RETURN GRILLE VARIABLE AIR VOLUME WALL EXHAUST GRILLE WALL EXHAUST REGISTER WALL RETURN REGISTER WET BULB VOLUME DAMPER TOP OF DUCT TRANSITION UNIT HEATER UNLESS NOTED OTHERWISE VERIFY IN FIELD TOTAL DEVELOPED HEAD(DYNAMIC) TESTING, ADJUSTING & BALANCING TRANSFER AIR GRILLE WATER PRESSURE DROP NOT TO SCALE REFRIGERANT GAS RETURN LINE PUMPED CONDENSATE DRAIN PIPING REVOLUTIONS PER MINUTE EXISTING TO BE RELOCATED EXISTING TO BE REMOVED PRE-ENGINEERED METAL BUILDING PLUMBING CONTRACTOR POUNDS PER SQUARE INCH PRESSURE REDUCING VALVE OUTSIDE AIR INTAKE OPPOSED BLADE DAMPER PACKAGED TERMINAL AIR CONDITIONER RETURN AIR SQUARE FEET SANITARY/SLOPE RELATIVE HUMIDITY ROOF TOP UNIT SUPPLY AIR SPLITTER DAMPER OUTSIDE AIR NOT IN CONTRACT NOT APPLICABLE MAKE-UP AIR NORMALLY OPEN NORMALLY CLOSED HIGH PRESSURE STEAM SUPPLY HIGH PRESSURE STEAM RETURN LINEAR DIFFUSER HEAT EXCHANGER 1000 BTUH LINEAR RETURN GRILLE LINEAR SUPPLY REGISTER MOTORIZED DAMPER LINEAR BAR GRILLE HEATING HOT WATER SUPPLY HEATING HOT WATER RETURN LEAVING AIR TEMPERATURE LEAVING WATER TEMPERATURE MINIMUM FUSE AMPACITY MECHANICAL CONTRACTOR MAXIMUM OVER-CURRENT PROTECTION SIZE REFRIGERANT LIQUID LINE/LOUVER LOW PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY VAV FUEL OIL SUPPLY FOS HEAT PUMP/HORSE POWER FIN-TUBE CONVECTOR FLOOR RETURN GRILLE FLOOR SUPPLY GRILLE GRAVITY CONDENSATE FLOOR RETURN REGISTER FIRE PROTECTION CONTRACTOR FLOOR SUPPLY REGISTER HP FTC FRR FRG FPM FPC FSG FT GC FSR G FEET PER MINUTE FOOT/FEET GAS VD WSHP WER WSR WSG WRR WRG VIF WEG WB WPD VFD BRITISH THERMAL UNIT AIR PRESSURE DROP CUBIC FEET PER HOUR AIR HANDLING UNIT BOTTOM OF DUCT AUTOMATIC AIR VENT CABINET UNIT HEATER CONDENSING UNIT CONDENSER WATER SUPPLY CONDENSER WATER RETURN CEILING RETURN REGISTER CEILING RETURN GRILLE CUBIC FEET PER MINUTE CEILING EXHAUST REGISTER CEILING EXHAUST GRILLE ABOVE FINISHED FLOOR COMPRESSED AIR PIPING AUTOMATIC TEMPERATURE CONTROLS CONSTRUCTION MANAGER DOMESTIC COLD WATER DRY BULB A-WEIGHTED DECIBEL DIRECT EXPANSION EXISTING TO REMAIN ELECTRIC BASEBOARD CONVECTOR ELECTRIC DUCT HEATER DIRECT DIGITAL CONTROLS CHILLED WATER RETURN CHILLED WATER SUPPLY DUAL TEMPERATURE WATER SUPPLY DUAL TEMPERATURE WATER RETURN CONDENSATE DRAIN PIPING ENTERING AIR TEMPERATURE ELECTRICAL CONTRACTOR EXTERNAL STATIC PRESSURE ELECTRIC WATER COOLER ELECTRIC WATER HEATER ENTERING WATER TEMPERATURE FREE AREA/FRESH AIR FLEXIBLE CONNECTION/FAN COIL FURNACE/FAHRENHEIT CONSTANT VOLUME ET BTU BTUH AS APD BOP CFH AC AHU AFF AAV CD CER CEG BOD ATC AP CH CM CO CRG CONT CT CU CRR CUH CWS CWR CFM DCW DB DBA CHWR CHWS DN DX DDC DIA DTS DTR EA EC EDH EBBC EAT EF EX ESP EWC EWH EWT (E) FC FA FAI FD FOR FLEX CV D E F A B EXPANSION TANK DOWN DIAMETER EACH EXISTING EXHAUST AIR EXHAUST FAN FIRE DAMPER FRESH AIR INLET FLEXIBLE FUEL OIL RETURN BTU PER HOUR AIR SEPARATOR BOTTOM OF PIPE BOILER CEILING DIFFUSER ACCESS PANEL AIR COMPRESSOR CHILLER CONTINUED COOLING TOWER CLEAN OUT ABBREVIATIONS NTS TF TYP U.N.O. UH TSP TOD TR TAB TDH TAG OA PTAC s=02' RA SF SA SD RPM RTU S (RL) RH R (R) PRV PD PSI OBD PEMB PC P OAI TYPICAL SLOPE PUMP MPS MPR NIC NC NO N/A MUA HPS HPR HWS HWR L LAT HX LD LPS LPR LRG LSR LWT LBG MC MBH MD MIN MCA MAX MOCP MINIMUM MAXIMUM HVAC WATER RISER LOCATION OUTSIDE AIR INTAKE GRILLE OR REGISTER UNDERCUT DOOR OR LOUVERED DOOR OUTSIDE AIR GRILLE OR REGISTER RETURN, EXHAUST, MAKEUP OR SUPPLY AIR 4-WAY DIFFUSER, RETURN, EXHAUST, MAKEUP OR PIPE DOWN PIPE DROP (RL) (E) H S (R) T FIRE DAMPER WITH ACCESS PANEL EXISTING TO BE REMOVED CONNECT NEW TO EXISTING EXISTING TO BE REMOVED EXISTING TO BE RELOCATED FIRE AND SMOKE DAMPER CUT AND CAP EXISTING TO REMAIN HUMIDISTAT THERMOSTAT SENSOR PIPE UP SMOKE DETECTOR DIAMETER EXISTING TO REMAIN NEW WORK THERMOMETER PRESSURE GAGE W/ BALL VALVE SHEET NUMBER REDUCED PRESSURE SYMBOLS TWO-WAY CONTROL VALVE BUTTERFLY VALVE GATE VALVE CHECK VALVE BALL-TYPE SHUTOFF VALVE CALIBRATED BALANCING VALVE DOUBLE CHECK VALVE THREE-WAY CONTROL VALVE STRAINER VERTICAL VALVE B CAP SECTION NUMBER SECTION MARKER VOLUME DAMPER EQUIPMENT NUMBER EQUIPMENT TYPE DESIGNATOR RISER NUMBER RISER TYPE FLEX DUCT S F S F X X X XX X X XX.X PRESSURE RELIEF VALVE ERW ENERGY RECOVERY WHEEL (N) NEW WORK MOTORIZED M DUCT MOUNTED SUPPLY GRILLE DSG AD DUCT ACCESS DOOR WIRE MESH SCREEN WMS SOUND TRAP/SILENCER ST UNION SIDEWALL GRILLE AIR VENT VD BACKFLOW PREVENTION 02/05/2021 HVAC LEGEND GENERAL REQUIREMENTS 1. EXAMINE JOB SITE AND VERIFY ALL SITE CONDITIONS PRIOR TO STARTING WORK. BRING ANY DISCREPANCY BETWEEN THE CONTRACT DOCUMENTS AND THE ACTUAL FIELD CONDITIONS TO THE ATTENTION OF THE ARCHITECT. 2. THE DRAWINGS ARE DIAGRAMMATIC. COORDINATE IN THE FIELD, WITH THE ARCHITECT AND WITH ALL TRADES, THE EXACT LOCATION OF EQUIPMENT, FIXTURES, VALVES, THERMOSTATS, ETC. AND ROUTING OF PIPING, DUCTWORK, CONDUIT, ETC. 3. ARRANGE FOR PIPE SPACES, CHASES, SLOTS, AND OPENINGS IN BUILDING STRUCTURE DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR MECHANICAL INSTALLATIONS. 4. COORDINATE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET SLEEVES IN POURED-IN-PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED. 5. PERFORM WORK IN ACCORDANCE WITH RULES, REGULATIONS, STANDARDS, CODES, ORDINANCES, AND LAWS OF LOCAL, STATE, AND FEDERAL GOVERNMENTS, AND OTHER AUTHORITIES HAVING JURISDICTION AND BE RESPONSIBLE FOR COMPLIANCE THEREWITH. 6. GUARANTEE ALL SYSTEMS AND WORK FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL ACCEPTANCE. 7. ALL MATERIALS SHALL BE NEW AND OF COMMERCIAL GRADE AND BEAR THE UNDERWRITER'S LABEL WHERE APPLICABLE. 8. LOCATE ALL EXISTING UTILITIES AND MAKE SERVICEABLE CONNECTIONS TO SAME. 9. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, THE MECHANICAL CONTRACTOR SHALL CHECK AND VERIFY ALL MEASUREMENTS, INCLUDING LINES, GRADES, PIPE AND DUCT ELEVATIONS AT THE BUILDING AND SHALL BE RESPONSIBLE FOR THE CORRECTNESS OF SAME. 10. “PROVIDE” SHALL MEAN FURNISH AND INSTALL, MAKE ALL FINAL CONNECTIONS AND LEAVE IN AN APPROVED OPERATING CONDITION. 11. “MECHANICAL WORK” OR “WORK” SHALL MEAN ALL LABOR, TRANSPORTATION, MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, INSTALLATION, SUPERVISION, SERVICES, AND ANY OTHER INCIDENTAL ITEMS OR SERVICES NECESSARY FOR A COMPLETE AND OPERABLE INSTALLATION. 12. INTENT a. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS THAT ALL WORK, EQUIPMENT, APPURTENANCES, CONTROLS AND WIRING BE FURNISHED AND INSTALLED TESTED, COMPLETED AND READY FOR OPERATION. b. ANY INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE WORK COMPLETE AND FUNCTIONAL IN ALL RESPECTS AND READY FOR OPERATION, EVEN IF NOT EXPLICITLY SPECIFIED OR SHOWN, SHALL BE PROVIDED WITHOUT ADDITIONAL EXPENSE. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY REQUIRED FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK, THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. c. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ASSURING THAT THE PROPOSED SYSTEMS CAN BE INSTALLED AS REQUIRED FROM THE DRAWINGS AND SPECIFICATIONS. IF ANY DEPARTURES FROM THE DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY BY THE CONTRACTOR, DETAILS OF SUCH DEPARTURES AND CLEAR JUSTIFICATION SHALL BE SUBMITTED TO THE OWNER FOR APPROVAL. NO SUCH DEPARTURES SHALL BE MADE WITHOUT THE PRIOR WRITTEN APPROVAL OF THE OWNER. 17. DRAWINGS a. DRAWINGS ARE DIAGRAMMATIC, SMALL SCALE AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED AS IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, BENDS, FITTINGS AND ACCESS PANELS REQUIRED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL SUCH APPURTENANCES AND DEVICES REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM WHETHER OR NOT THE APPURTENANCE OR DEVICE IS SHOWN ON THE DRAWINGS. DRAWINGS ARE NOT TO BE SCALED. W/ ACCESS PANEL GALLONS PER MINUTE GPM GD RATED GREASE DUCT HVAC COVER SHEET KCB LEG KCB H000 Drawing Number: Date: 02/19/2021 Drawing Title: Approved: Checked: Drawn: Drawing Set: Project Name: No. Date Revisions Scale: Job Number: 80% CDs Notes: 1002 West 9th Avenue, King of Prussia, PA 19406 610-989-3800 - www.cvmprofessional.com MECHANICAL ENGINEER CHESTNUT ENGINEERING 2 E Lancaster Ave, 2nd Flr., Ardmore, PA 19003 610-642-1750 CIVIL ENGINEER/SURVEYOR NORTH COUNTRY ENGINEERING, INC. 706 Chippewa Square, Suite 102 Marquette, MI 49855 906-226-7683 Seal: PROJECT MANAGER, LEAD DESIGNER, STRUCTURAL ENGINEER UPS MARQUETTE ARCHITECT TPD ARCHITECTS, LLC 109 Hewett Road Wyncote, PA 19095 215-887-2460 30% CDs HVAC GROUND FLOOR PLAN H100 HVAC DETAILS H900 HVAC SCHEDULES H700 HVAC GROUND FLOOR PLANS - ENLARGED H500 02/19/2021 80% CDs HVAC GROUND FLOOR PLANS - ALTERNATE H500A

H000 - mqtbx.org

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: H000 - mqtbx.org

DRAWING TITLE

DRAWING

NUMBER

H000

DRAWING SCHEDULE

DA

TE

IS

SU

E

HVAC COVER SHEET

MEDIUM PRESSURE STEAM SUPPLY

MEDIUM PRESSURE STEAM RETURN

TRANSFER FAN

WATER SOURCE HEAT PUMP

VARIABLE FREQUENCY DRIVE

TOTAL STATIC PRESSURE

WALL SUPPLY GRILLE

WALL SUPPLY REGISTER

WALL RETURN GRILLE

VARIABLE AIR VOLUME

WALL EXHAUST GRILLE

WALL EXHAUST REGISTER

WALL RETURN REGISTER

WET BULB

VOLUME DAMPER

TOP OF DUCT

TRANSITION

UNIT HEATER

UNLESS NOTED OTHERWISE

VERIFY IN FIELD

TOTAL DEVELOPED HEAD(DYNAMIC)

TESTING, ADJUSTING & BALANCING

TRANSFER AIR GRILLE

WATER PRESSURE DROP

NOT TO SCALE

REFRIGERANT GAS RETURN LINE

PUMPED CONDENSATE DRAIN PIPING

REVOLUTIONS PER MINUTE

EXISTING TO BE RELOCATED

EXISTING TO BE REMOVED

PRE-ENGINEERED METAL BUILDING

PLUMBING CONTRACTOR

POUNDS PER SQUARE INCH

PRESSURE REDUCING VALVE

OUTSIDE AIR INTAKE

OPPOSED BLADE DAMPER

PACKAGED TERMINAL AIR CONDITIONER

RETURN AIR

SQUARE FEET

SANITARY/SLOPE

RELATIVE HUMIDITY

ROOF TOP UNIT

SUPPLY AIR

SPLITTER DAMPER

OUTSIDE AIR

NOT IN CONTRACT

NOT APPLICABLE

MAKE-UP AIR

NORMALLY OPEN

NORMALLY CLOSED

HIGH PRESSURE STEAM SUPPLY

HIGH PRESSURE STEAM RETURN

LINEAR DIFFUSER

HEAT EXCHANGER

1000 BTUH

LINEAR RETURN GRILLE

LINEAR SUPPLY REGISTER

MOTORIZED DAMPER

LINEAR BAR GRILLE

HEATING HOT WATER SUPPLY

HEATING HOT WATER RETURN

LEAVING AIR TEMPERATURE

LEAVING WATER TEMPERATURE

MINIMUM FUSE AMPACITY

MECHANICAL CONTRACTOR

MAXIMUM OVER-CURRENT PROTECTION SIZE

REFRIGERANT LIQUID LINE/LOUVER

LOW PRESSURE STEAM RETURN

LOW PRESSURE STEAM SUPPLY

VAV

FUEL OIL SUPPLYFOS

HEAT PUMP/HORSE POWER

FIN-TUBE CONVECTOR

FLOOR RETURN GRILLE

FLOOR SUPPLY GRILLE

GRAVITY CONDENSATE

FLOOR RETURN REGISTER

FIRE PROTECTION CONTRACTOR

FLOOR SUPPLY REGISTER

HP

FTC

FRR

FRG

FPM

FPC

FSG

FT

GC

FSR

G

FEET PER MINUTE

FOOT/FEET

GAS

VD

WSHP

WER

WSR

WSG

WRR

WRG

VIF

WEG

WB

WPD

VFD

BRITISH THERMAL UNIT

AIR PRESSURE DROP

CUBIC FEET PER HOUR

AIR HANDLING UNIT

BOTTOM OF DUCT

AUTOMATIC AIR VENT

CABINET UNIT HEATER

CONDENSING UNIT

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

CEILING RETURN REGISTER

CEILING RETURN GRILLE

CUBIC FEET PER MINUTE

CEILING EXHAUST REGISTER

CEILING EXHAUST GRILLE

ABOVE FINISHED FLOOR

COMPRESSED AIR PIPING

AUTOMATIC TEMPERATURE CONTROLS

CONSTRUCTION MANAGER

DOMESTIC COLD WATER

DRY BULB

A-WEIGHTED DECIBEL

DIRECT EXPANSION

EXISTING TO REMAIN

ELECTRIC BASEBOARD CONVECTOR

ELECTRIC DUCT HEATER

DIRECT DIGITAL CONTROLS

CHILLED WATER RETURN

CHILLED WATER SUPPLY

DUAL TEMPERATURE WATER SUPPLY

DUAL TEMPERATURE WATER RETURN

CONDENSATE DRAIN PIPING

ENTERING AIR TEMPERATURE

ELECTRICAL CONTRACTOR

EXTERNAL STATIC PRESSURE

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

ENTERING WATER TEMPERATURE

FREE AREA/FRESH AIR

FLEXIBLE CONNECTION/FAN COIL

FURNACE/FAHRENHEIT

CONSTANT VOLUME

ET

BTU

BTUH

AS

APD

BOP

CFH

AC

AHU

AFF

AAV

CD

CER

CEG

BOD

ATC

AP

CH

CM

CO

CRG

CONT

CT

CU

CRR

CUH

CWS

CWR

CFM

DCW

DB

DBA

CHWR

CHWS

DN

DX

DDC

DIA

DTS

DTR

EA

EC

EDH

EBBC

EAT

EF

EX

ESP

EWC

EWH

EWT

(E)

FC

FA

FAI

FD

FOR

FLEX

CV

D

E

F

A

B

EXPANSION TANK

DOWN

DIAMETER

EACH

EXISTING

EXHAUST AIR

EXHAUST FAN

FIRE DAMPER

FRESH AIR INLET

FLEXIBLE

FUEL OIL RETURN

BTU PER HOUR

AIR SEPARATOR

BOTTOM OF PIPE

BOILER

CEILING DIFFUSER

ACCESS PANEL

AIR COMPRESSOR

CHILLER

CONTINUED

COOLING TOWER

CLEAN OUT

ABBREVIATIONS

NTS

TF

TYP

U.N.O.

UH

TSP

TOD

TR

TAB

TDH

TAG

OA

PTAC

s=02'

RA

SF

SA

SD

RPM

RTU

S

(RL)

RH

R

(R)

PRV

PD

PSI

OBD

PEMB

PC

P

OAI

TYPICAL

SLOPE

PUMP

MPS

MPR

NIC

NC

NO

N/A

MUA

HPS

HPR

HWS

HWR

L

LAT

HX

LD

LPS

LPR

LRG

LSR

LWT

LBG

MC

MBH

MD

MIN

MCA

MAX

MOCP

MINIMUM

MAXIMUM

HVAC WATER RISER LOCATION

OUTSIDE AIR INTAKE

GRILLE OR REGISTER

UNDERCUT DOOR OR LOUVERED DOOR

OUTSIDE AIR GRILLE OR REGISTER

RETURN, EXHAUST, MAKEUP OR

SUPPLY AIR 4-WAY DIFFUSER,

RETURN, EXHAUST, MAKEUP OR

PIPE DOWN

PIPE DROP

(RL)

(E)

H

S

(R)

T

FIRE DAMPER WITH ACCESS PANEL

EXISTING TO BE REMOVED

CONNECT NEW TO EXISTING

EXISTING TO BE REMOVED

EXISTING TO BE RELOCATED

FIRE AND SMOKE DAMPER

CUT AND CAP

EXISTING TO REMAIN

HUMIDISTAT

THERMOSTAT

SENSOR

PIPE UP

SMOKE DETECTOR

DIAMETER

EXISTING TO REMAIN

NEW WORK

THERMOMETER

PRESSURE GAGE W/ BALL VALVE

SHEET NUMBER

REDUCED PRESSURE

SYMBOLS

TWO-WAY CONTROL VALVE

BUTTERFLY VALVE

GATE VALVE

CHECK VALVE

BALL-TYPE SHUTOFF VALVE

CALIBRATED BALANCING VALVE

DOUBLE CHECK VALVE

THREE-WAY CONTROL VALVE

STRAINER

VERTICAL VALVE

B

CAP

SECTION NUMBER

SECTION MARKER

VOLUME DAMPER

EQUIPMENT NUMBER

EQUIPMENT TYPE DESIGNATOR

RISER NUMBER

RISER TYPE

FLEX DUCT

S

F

S

F

X

X

X

XX

XX

XX.X

PRESSURE RELIEF VALVE

ERW ENERGY RECOVERY WHEEL

(N) NEW WORK

MOTORIZED

M

DUCT MOUNTED SUPPLY GRILLEDSG

AD DUCT ACCESS DOOR

WIRE MESH SCREENWMS

SOUND TRAP/SILENCERST

UNION

SIDEWALL GRILLE

AIR VENT

VD

BACKFLOW PREVENTION

02/05/2021

HVAC LEGEND

GENERAL REQUIREMENTS

1. EXAMINE JOB SITE AND VERIFY ALL SITE CONDITIONS PRIOR TO STARTING

WORK. BRING ANY DISCREPANCY BETWEEN THE CONTRACT DOCUMENTS AND

THE ACTUAL FIELD CONDITIONS TO THE ATTENTION OF THE ARCHITECT.

2. THE DRAWINGS ARE DIAGRAMMATIC. COORDINATE IN THE FIELD, WITH THE

ARCHITECT AND WITH ALL TRADES, THE EXACT LOCATION OF EQUIPMENT,

FIXTURES, VALVES, THERMOSTATS, ETC. AND ROUTING OF PIPING, DUCTWORK,

CONDUIT, ETC.

3. ARRANGE FOR PIPE SPACES, CHASES, SLOTS, AND OPENINGS IN BUILDING

STRUCTURE DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR

MECHANICAL INSTALLATIONS.

4. COORDINATE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET

SLEEVES IN POURED-IN-PLACE CONCRETE AND OTHER STRUCTURAL

COMPONENTS AS THEY ARE CONSTRUCTED.

5. PERFORM WORK IN ACCORDANCE WITH RULES, REGULATIONS, STANDARDS,

CODES, ORDINANCES, AND LAWS OF LOCAL, STATE, AND FEDERAL

GOVERNMENTS, AND OTHER AUTHORITIES HAVING JURISDICTION AND BE

RESPONSIBLE FOR COMPLIANCE THEREWITH.

6. GUARANTEE ALL SYSTEMS AND WORK FOR A PERIOD OF ONE (1) YEAR FROM

DATE OF FINAL ACCEPTANCE.

7. ALL MATERIALS SHALL BE NEW AND OF COMMERCIAL GRADE AND BEAR THE

UNDERWRITER'S LABEL WHERE APPLICABLE.

8. LOCATE ALL EXISTING UTILITIES AND MAKE SERVICEABLE CONNECTIONS TO

SAME.

9. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, THE MECHANICAL

CONTRACTOR SHALL CHECK AND VERIFY ALL MEASUREMENTS, INCLUDING

LINES, GRADES, PIPE AND DUCT ELEVATIONS AT THE BUILDING AND SHALL BE

RESPONSIBLE FOR THE CORRECTNESS OF SAME.

10. “PROVIDE” SHALL MEAN FURNISH AND INSTALL, MAKE ALL FINAL CONNECTIONS

AND LEAVE IN AN APPROVED OPERATING CONDITION.

11. “MECHANICAL WORK” OR “WORK” SHALL MEAN ALL LABOR, TRANSPORTATION,

MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, INSTALLATION,

SUPERVISION, SERVICES, AND ANY OTHER INCIDENTAL ITEMS OR SERVICES

NECESSARY FOR A COMPLETE AND OPERABLE INSTALLATION.

12. INTENT

a. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS THAT ALL WORK,

EQUIPMENT, APPURTENANCES, CONTROLS AND WIRING BE FURNISHED

AND INSTALLED TESTED, COMPLETED AND READY FOR OPERATION.

b. ANY INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE WORK

COMPLETE AND FUNCTIONAL IN ALL RESPECTS AND READY FOR

OPERATION, EVEN IF NOT EXPLICITLY SPECIFIED OR SHOWN, SHALL BE

PROVIDED WITHOUT ADDITIONAL EXPENSE. MINOR DETAILS NOT USUALLY

SHOWN OR SPECIFIED, BUT MANIFESTLY REQUIRED FOR THE PROPER

INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE

INCLUDED IN THE WORK, THE SAME AS IF SPECIFIED OR SHOWN ON THE

DRAWINGS.

c. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ASSURING THAT THE

PROPOSED SYSTEMS CAN BE INSTALLED AS REQUIRED FROM THE

DRAWINGS AND SPECIFICATIONS. IF ANY DEPARTURES FROM THE

DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY BY THE

CONTRACTOR, DETAILS OF SUCH DEPARTURES AND CLEAR JUSTIFICATION

SHALL BE SUBMITTED TO THE OWNER FOR APPROVAL. NO SUCH

DEPARTURES SHALL BE MADE WITHOUT THE PRIOR WRITTEN APPROVAL OF

THE OWNER.

17. DRAWINGS

a. DRAWINGS ARE DIAGRAMMATIC, SMALL SCALE AND INDICATE THE GENERAL

ARRANGEMENT OF SYSTEMS AND WORK INCLUDED AS IT IS NOT POSSIBLE

TO INDICATE ALL OFFSETS, BENDS, FITTINGS AND ACCESS PANELS

REQUIRED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL

SUCH APPURTENANCES AND DEVICES REQUIRED FOR A COMPLETE AND

FUNCTIONAL SYSTEM WHETHER OR NOT THE APPURTENANCE OR DEVICE IS

SHOWN ON THE DRAWINGS. DRAWINGS ARE NOT TO BE SCALED.

W/ ACCESS PANEL

GALLONS PER MINUTEGPM

GD RATED GREASE DUCT

HVAC

COVER SHEET

KCB

LEG

KCB

H000

Drawing Number:

Date: 02/19/2021

Drawing Title:

Approved:

Checked:

Drawn:

Drawing Set:

Project Name:

No. Date Revisions

Scale:

Job Number:

80% CDs

Notes:

1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com

MECHANICAL ENGINEER

CHESTNUT ENGINEERING

2 E Lancaster Ave, 2nd Flr.,

Ardmore, PA 19003

610-642-1750

CIVIL ENGINEER/SURVEYOR

NORTH COUNTRY ENGINEERING, INC.

706 Chippewa Square, Suite 102

Marquette, MI 49855

906-226-7683

Seal:

PROJECT MANAGER, LEAD DESIGNER,

STRUCTURAL ENGINEER

UPS MARQUETTE

ARCHITECT

TPD ARCHITECTS, LLC

109 Hewett Road

Wyncote, PA 19095

215-887-2460

30%

C

Ds

HVAC GROUND FLOOR PLANH100

HVAC DETAILSH900

HVAC SCHEDULESH700

HVAC GROUND FLOOR PLANS - ENLARGEDH500

02/19/2021

80%

C

Ds

HVAC GROUND FLOOR PLANS - ALTERNATEH500A

AutoCAD SHX Text
EQUIPMENT TAG
Page 2: H000 - mqtbx.org

10987654321

E E

B B

A

D D

C C

7.5 8.3

7.3 8.5

CO/NO2 1

1

R

1

H500

M

4" GAS [1745]

EF

3

EF

4

ENLARGED

GAS SERVICE. REFER

TO CIVIL DWGS FOR

CONTINUATION

REGULATOR

METER

EF

1

EF

2

T

HV-1

3

H500

MEZZANINE

2" GAS [360]

CO/NO2 1

2

CO/NO2 1

3

CO/NO2 1

5

CO/NO2 1

6

CO/NO2 1

7

CO/NO2 1

HV

1

50x26 RETURN AIR GRILLE,

FLUSH WITH EXTERIOR WALL

(RAPID BOTTOM RETURN)

3" GAS [1125]

VERTICAL, MOUNTED ON

CONCRETE PAD

47x25 SUPPLY AIR

(RAPID UP DISCHARGE)

RAPID 3-WAY

DISCHARGE HEAD

SA AND RA DUCTS CONNECTED TO HV

WITH EXTERIOR RATED FLEXIBLE DUCT

CONNECTORS. PROFLEX COMMERCIAL

STAINLESS STEEL (OR EQUIVALENT)

RH

1

CRV-B6

RH

1

CRV-B6

RH

2

CRV-B8

RH

1

CRV-B6

4" CAT 3 VENT

RH

2

CRV-B8

RH

1

CRV-B6

RH

1

CRV-B6

RH

1

CRV-B6

4" CAT 3 VENT

RH

3

TF-250

6" CAT 3 VENT

1-1/4" GAS [160]

P

2

P

1

BOTTOM OF RH AT 18'-0" (TYP)

MAINTAIN A MIN. 5'-0" CLEARANCE TO

COMBUSTIBLES

[60 MBH][60 MBH][80 MBH][60 MBH]

[80 MBH][60 MBH]

[60 MBH]

[1125]

1" GAS [60] 1-1/4" GAS [140] 1-1/4" GAS [200] 1-1/2" GAS [260]

4" GAS [1385]

1" GAS [60] 1-1/4" GAS [140] 1-1/4" GAS [200]

[60 MBH]

1-1/2" GAS [260]

1" GAS [100]

4" GAS [1905]

BOTTOM OF RH AT 18'-0" (TYP)

MAINTAIN A MIN. 5'-0" CLEARANCE TO

COMBUSTIBLES

BOTTOM OF RH AT 18'-0" (TYP)

MAINTAIN A MIN. 5'-0" CLEARANCE TO

COMBUSTIBLES

T RH-3

T RH

T RH

KEYED NEW WORK NOTES

ARMSTRONG MODEL AMC-1222 LOW VOLTAGE

COMBINATION CO & NO2 GAS DETECTOR.

NORMALLY OPEN MOTORIZED DAMPER WITH 24V

ACTUATOR (GREENHECK MODEL VCDR-53 OR

EQUIVALENT)

OVERHEAD LUBE REEL SYSTEM 15' MIN. CLEAR HEIGHT

A.F.F.

SYSTEM CONSISTS OF:

(2) 3/8" COMPRESSED AIR LINE REEL

(1) GREASE REEL

(1) FRESH OIL REEL

INSULATED REFRIGERANT LINESET, SIZED PER 1/H700

FIELD CONSTRUCTED RETURN AIR PLENUM WITH SIDE

AND BOTTOM PULL FILTER RACK. SIZE OF PLENUM TO

MATCH INLET DIMENSION OF VRF TERMINAL UNIT.

24 VOLT HIGH LIMIT TEMPERATURE SWITCH. SWITCH

CLOSES MOTORIZED DAMPER WHEN SUPPLY AIR

TEMPERATURE IS GREATER THAN 72° F.

LINESETS TO BE CONNECTED TO CONDENSING UNIT WITH

A FLEXIBLE CONNECTOR. RECTORSEAL NOKINK (OR

EQUIVALENT).

1

GENERAL NOTES

1. ALL AIR DEVICES SHALL BE BALANCED TO THE CFM VALUE

(SHOWN AS [XXX]) ON THE FLOOR PLANS. SUBMIT

BALANCING REPORT TO ARCHITECT/ENGINEER.

BALANCING WORK SHALL CONFORM TO REQUIREMENTS

OF AABC OR NEBB.

2. ALL NEW EQUIPMENT, PIPING, AND DUCTWORK SHALL BE

INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE

FOR MAXIMUM CEILING HEIGHTS.

3. COORDINATE DIFFUSER AND GRILLES LOCATION WITH

ALL OTHER CEILING COMPONENTS.

4. PROVIDE ALL VOLUME DAMPERS REQUIRED TO BALANCE

THE SYSTEMS. INSTALL VOLUME DAMPERS AT ALL

BRANCH TAKE OFFS FROM TRUNK DUCTS.

5. COMBO CO/NO2 SENSORS SHALL BE MOUNTED 5'-0" A.F.F

6. REFER TO SPECIFICATION SECTION 237338 FOR

CONTROLS AND SEQUENCE OF OPERATIONS FOR

HEATING AND VENTILATION SYSTEM.

7. ALL DUCTWORK SHALL BE INSULATED WITH A MINIMUM

R-8 INSULATION TO MEET ENERGY CODE.

8. MAINTAIN WAREHOUSE AREA AT 45°F.

9. MAINTAIN AUTOSHOP AT 55°F.

2

3

4

5

6

7

HVAC

GROUND

FLOOR PLAN

KCB

LEG

KCB

H100

Drawing Number:

Date: 02/19/2021

Drawing Title:

Approved:

Checked:

Drawn:

Drawing Set:

Project Name:

No. Date Revisions

Scale:

Job Number:

80% CDs

Notes:

1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com

MECHANICAL ENGINEER

CHESTNUT ENGINEERING

2 E Lancaster Ave, 2nd Flr.,

Ardmore, PA 19003

610-642-1750

CIVIL ENGINEER/SURVEYOR

NORTH COUNTRY ENGINEERING, INC.

706 Chippewa Square, Suite 102

Marquette, MI 49855

906-226-7683

Seal:

PROJECT MANAGER, LEAD DESIGNER,

STRUCTURAL ENGINEER

UPS MARQUETTE

ARCHITECT

TPD ARCHITECTS, LLC

109 Hewett Road

Wyncote, PA 19095

215-887-2460

H100

1

SCALE: 1/8" = 1' - 0"

HVAC GROUND FLOOR PLAN

Page 3: H000 - mqtbx.org

KEYED NEW WORK NOTES

ARMSTRONG MODEL AMC-1222 LOW VOLTAGE

COMBINATION CO & NO2 GAS DETECTOR.

NORMALLY OPEN MOTORIZED DAMPER WITH 24V

ACTUATOR (GREENHECK MODEL VCDR-53 OR

EQUIVALENT)

OVERHEAD LUBE REEL SYSTEM 15' MIN. CLEAR HEIGHT

A.F.F.

SYSTEM CONSISTS OF:

(2) 3/8" COMPRESSED AIR LINE REEL

(1) GREASE REEL

(1) FRESH OIL REEL

INSULATED REFRIGERANT LINESET, SIZED PER 1/H700

FIELD CONSTRUCTED RETURN AIR PLENUM WITH SIDE

AND BOTTOM PULL FILTER RACK. SIZE OF PLENUM TO

MATCH INLET DIMENSION OF VRF TERMINAL UNIT.

24 VOLT HIGH LIMIT TEMPERATURE SWITCH. SWITCH

CLOSES MOTORIZED DAMPER WHEN SUPPLY AIR

TEMPERATURE IS GREATER THAN 72° F.

LINESETS TO BE CONNECTED TO CONDENSING UNIT WITH

A FLEXIBLE CONNECTOR. RECTORSEAL NOKINK (OR

EQUIVALENT).

1

2

3

4

5

6

7

CU

2-1

CU

1

CEG-1

[-225]

EF

5

L

1

PROVIDE MANUFACTURERS 24" STAND

(MITSUBISHI MODEL SS100 OR EQUIVALENT)

ON TOP OF CONCRETE PAD

109

MEN'S ROOM

108

WOMEN'S

ROOM

111

REST ROOM

ENTRANCE

107

CONF./TRAINING

ROOM

106

CENTER

MANAGER'S

OFFICE

105

SUPERVISOR'S

OFFICE

103

OMS

110

CORRIDOR

102

CUSTOMER

COUNTER

104

LOCAL SORT

PRELOAD

OFFICE

CEG-1

[-225]

12

Ø E

A

10

Ø E

A

VD

10Ø EA

CD-1

[300]

CD-1

[300]

CD-1

[150]

CD-1

[200]

CD-1

[155]

CD-1

[155]

CD-1

[220]

CD-1

[200]

CD-1

[100]

CD-1

[100]

CD-1

[75]

CD-1

[75]

CRG-1

CRG-1

CRG-1

CRG-1

CRG-1

CRG-1

CRG-1

PAC

1

AC-1 GRAVITY

CONDENSATE TO SPILL

TO FLOOR DRAIN

18" WINDOW VENT PANEL

INSTALLED IN DIAD

ENCLOSURE SIDEWALL

FLEXIBLE HOSE

T

SITS ON FLOOR

DIAD ENCLOSURE

TU

1-2

[600]

TU

1-1

[880]

TU

1-3

[880]

14x12 SA

T

5

M

14

x1

2 S

A

VD

VD

8x12 SA

VD

VD

T

5

T

10x12 SA

VD VD

5

VD

VD

VD

8x12 SA

VDVD

8x8 SA

VD

[50]

5Ø OA

[65]

[55]

O

A

4

8Ø SA UP

VD

T

S

A

6

2

12Ø EA

1-1/4" GC

1-1/4" GC DRAIN TO GRADE.

TERMINATE WITH J.R. SMITH 1770 (OR

EQUIVALENT) DOWNSPOUT NOZZLE

1-1/4" GC

1-1/4" GC

1-1/4" GC

1-1/4"

GC UP

6Ø SA UP

S

A

VD

4

WALL

MOUNTED

8.5

A

B

C

CU

2-2

INSULATED

REFRIGERANT LINESET

SIZED PER 1/H700

WALL

MOUNTED

4Ø OA UP

L

2

O

A

VD

VD

O

A

VD

7

7

7

1098

B

A

8.5

B.8

8.1

202

TSG STORAGE

ROOM

200

MECHANICAL

AREA

201

SERVER

ROOM

T

TU

2-1

2

H900

WSR-1

[220]

1-1/4" GC

1-1/4" GC DN TO

1ST FLOOR

[15]

OUTLINE OF SERVER RACKS. DO

NOT INSTALL EQUIPMENT OR

PIPING ABOVE RACKS

INSULATED

REFRIGERANT LINESET

DN. SIZED PER 1/H700

6Ø SA DN

S

A

8Ø SA DN

CD-1

[100]

6Ø SA

TU

2-2

1-1/4" GC

T

INSULATED

REFRIGERANT LINESET

DN. SIZED PER 1/H700

[15]

O

A

O

A4

Ø O

A

4Ø OA DN

HVAC

GROUND

FLOOR PLANS -

ENLARGED -

ALTERNATE

KCB

LEG

KCB

H500A

Drawing Number:

Date: 02/19/2021

Drawing Title:

Approved:

Checked:

Drawn:

Drawing Set:

Project Name:

No. Date Revisions

Scale:

Job Number:

80% CDs

Notes:

1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com

MECHANICAL ENGINEER

CHESTNUT ENGINEERING

2 E Lancaster Ave, 2nd Flr.,

Ardmore, PA 19003

610-642-1750

CIVIL ENGINEER/SURVEYOR

NORTH COUNTRY ENGINEERING, INC.

706 Chippewa Square, Suite 102

Marquette, MI 49855

906-226-7683

Seal:

PROJECT MANAGER, LEAD DESIGNER,

STRUCTURAL ENGINEER

UPS MARQUETTE

ARCHITECT

TPD ARCHITECTS, LLC

109 Hewett Road

Wyncote, PA 19095

215-887-2460

H500A

1

SCALE: 1/4" = 1' - 0"

HVAC GROUND FLOOR PLAN - ENLARGED PLAN - ALTERNATE

H500A

2

SCALE: 1/4" = 1' - 0"

HVAC MEZZANINE - ENLARGED PLAN - ALTERNATE

H500A

3

SCALE: NONE

VRF SCHEMATIC

J1

P1

PEFY-

P24NMAU-E3

001

Gp6

J2

P2

16-2 AWG(S)

PEFY-

P18NMAU-E3

002

Gp8

PEFY-

P24NMAU-E3

003

Gp7

P3 P2P2

DIP SWITCH 6 - 2 ON, SW4 Function 968 ON for High Heating performance mode

[CU-1]

PUHY-

HP96YNU-A

051

TB7

Office

TU 1-1 TU 1-2 TU 1-3

E

PUZ-

A24NHA7 [CU 2-1]

N/A

TB5

TB4

PLA-

A24EA7

N/A

Gp5

P2

Server Room 1

TU 2-1

E

PUZ-

A24NHA7 [CU 2-2]

N/A

TB5

TB4

PLA-

A24EA7

N/A

Gp9

P2

Server Room 2

TU 2-2

AE-200A

PIPING AND CONTROLS

SYMBOL BRANCH PIPE MODEL NAME

J1 CMY-Y102LS-G2

J2 CMY-Y102SS-G2

SYMBOL LIQUID PIPE/GAS PIPE SIZE

P1 3/8 / 7/8

P2 3/8 / 5/8

P3 1/4 / 1/2

SYMBOL MODEL NUMBER

CR PAC-YT53CRAU-J

1. PROVIDE LOW AMBIENT KIT,M SNOW HOOD, AND FRONT, SIDE, AND REAR WIND BAFFLES FOR ALL CUs

NOTES:

AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
5
AutoCAD SHX Text
B
AutoCAD SHX Text
T
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
5
AutoCAD SHX Text
B
AutoCAD SHX Text
T
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
B
AutoCAD SHX Text
T
AutoCAD SHX Text
3
AutoCAD SHX Text
L1L2L3
AutoCAD SHX Text
)
AutoCAD SHX Text
S
AutoCAD SHX Text
(
AutoCAD SHX Text
G
AutoCAD SHX Text
460V/60Hz
AutoCAD SHX Text
3~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
AutoCAD SHX Text
208-230V/60Hz
AutoCAD SHX Text
1~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
G
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
AutoCAD SHX Text
208-230V/60Hz
AutoCAD SHX Text
1~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
G
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
AutoCAD SHX Text
LAN
AutoCAD SHX Text
TB3
AutoCAD SHX Text
TB1
AutoCAD SHX Text
M-Net
AutoCAD SHX Text
100~240V
AutoCAD SHX Text
1
AutoCAD SHX Text
F
AutoCAD SHX Text
16-2 AWG(S)
AutoCAD SHX Text
REF. PIPE
AutoCAD SHX Text
DISPLAY
AutoCAD SHX Text
DIAGRAM SYMBOL LEGEND
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CONTROL WIRE
AutoCAD SHX Text
POWER WIRE
Page 4: H000 - mqtbx.org

KEYED NEW WORK NOTES

ARMSTRONG MODEL AMC-1222 LOW VOLTAGE

COMBINATION CO & NO2 GAS DETECTOR.

NORMALLY OPEN MOTORIZED DAMPER WITH 24V

ACTUATOR (GREENHECK MODEL VCDR-53 OR

EQUIVALENT)

OVERHEAD LUBE REEL SYSTEM 15' MIN. CLEAR HEIGHT

A.F.F.

SYSTEM CONSISTS OF:

(2) 3/8" COMPRESSED AIR LINE REEL

(1) GREASE REEL

(1) FRESH OIL REEL

INSULATED REFRIGERANT LINESET, SIZED PER 1/H700

FIELD CONSTRUCTED RETURN AIR PLENUM WITH SIDE

AND BOTTOM PULL FILTER RACK. SIZE OF PLENUM TO

MATCH INLET DIMENSION OF VRF TERMINAL UNIT.

24 VOLT HIGH LIMIT TEMPERATURE SWITCH. SWITCH

CLOSES MOTORIZED DAMPER WHEN SUPPLY AIR

TEMPERATURE IS GREATER THAN 72° F.

LINESETS TO BE CONNECTED TO CONDENSING UNIT WITH

A FLEXIBLE CONNECTOR. RECTORSEAL NOKINK (OR

EQUIVALENT).

1

GENERAL NOTES

1. ALL AIR DEVICES SHALL BE BALANCED TO THE CFM VALUE

(SHOWN AS [XXX]) ON THE FLOOR PLANS. SUBMIT

BALANCING REPORT TO ARCHITECT/ENGINEER.

BALANCING WORK SHALL CONFORM TO REQUIREMENTS

OF AABC OR NEBB.

2. ALL NEW EQUIPMENT, PIPING, AND DUCTWORK SHALL BE

INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE

FOR MAXIMUM CEILING HEIGHTS.

3. COORDINATE DIFFUSER AND GRILLES LOCATION WITH

ALL OTHER CEILING COMPONENTS.

4. PROVIDE ALL VOLUME DAMPERS REQUIRED TO BALANCE

THE SYSTEMS. INSTALL VOLUME DAMPERS AT ALL

BRANCH TAKE OFFS FROM TRUNK DUCTS.

5. COMBO CO/NO2 SENSORS SHALL BE MOUNTED 5'-0" A.F.F

6. REFER TO SPECIFICATION SECTION 237338 FOR

CONTROLS AND SEQUENCE OF OPERATIONS FOR

HEATING AND VENTILATION SYSTEM.

7. ALL DUCTWORK SHALL BE INSULATED WITH A MINIMUM

R-8 INSULATION TO MEET ENERGY CODE.

8. MAINTAIN WAREHOUSE AREA AT 45°F.

9. MAINTAIN AUTOSHOP AT 55°F.

2

3

4

5

6

7

AC

1

3

1/2" FO

1/2" CG

PIPE LABELING LEGEND

CA = COMPRESSED AIR

FO = FRESH OIL

CG = CHASSIS GREASE

3/4" CA

3/4" CA DROP WITH

QUICK CONNECT FITTING

WASTE

OIL SINK

1/2"

CA

WASTE OIL

TANK

1/2" CA BALL VALVE,

MOUNTED 36" A.F.F.

1" PUMPED

WASTE OIL

1" CA

7.3 8.5

A

B

C

101

AUTO SHOP

100

WAREHOUSE

RAPID ENGINEERING INFINITY PRO

SERIES CONTROL (DDC) AND

EQUIPMENT TOUCH REMOTE PANEL.

ARMSTRONG MODEL AMC-1DBx DIGITAL,

ADDRESSABLE CO/NO2 DETECTION

SYSTEM CONTROL PANEL.

1" GAS [100]

RH

5

[60]

T

ALEMITE 7788-B5

GREASE PUMP

CHASSIS GREASE

BARREL

FRESH OIL TANK

1/2" FO

ALEMITE 7783-C4

FRESH OIL PUMP

3/4" CA

1/2"

CA

1/2" CA TO WASTE OIL SINK

PNEUMATIC PUMP. PROVIDE

PRESSURE REGULATOR AND

GAUGE. ADJUST TO 5 GPM

AD

1

CU

2-1

CEG-1

[-225]

EF

5

L

1

109

MEN'S ROOM

108

WOMEN'S

ROOM

111

REST ROOM

ENTRANCE

107

CONF./TRAINING

ROOM

106

CENTER

MANAGER'S

OFFICE

105

SUPERVISOR'S

OFFICE

103

OMS

110

CORRIDOR

102

CUSTOMER

COUNTER

104

LOCAL SORT

PRELOAD

OFFICE

100

WAREHOUSE

CEG-1

[-225]

12Ø

E

A

10Ø

E

A

VD

10Ø EA

CD-1

[300]

CD-1

[300]

CD-1

[150]

CD-1

[200]

CD-1

[155]

CD-1

[155]

CD-1

[220]

CD-1

[200]

CD-1

[100]

CD-1

[100]

CD-1

[75]

CRG-1

CRG-1

CRG-1

CRG-1

CRG-1

CRG-1

PAC

1

AC-1 GRAVITY

CONDENSATE TO SPILL

TO FLOOR DRAIN

18" WINDOW VENT PANEL

INSTALLED IN DIAD

ENCLOSURE SIDEWALL

FLEXIBLE HOSE

T

SITS ON FLOOR

DIAD ENCLOSURE

T

T

10

x1

2 S

A

VD

8x12 S

A

VD

VD

8x8 SA

VD

12Ø EA

1-1/4" GC DRAIN TO GRADE.

TERMINATE WITH J.R. SMITH 1770 (OR

EQUIVALENT) DOWNSPOUT NOZZLE

1-1/4"

GC UP

WALL

MOUNTED

CU

2-2

INSULATED

REFRIGERANT LINESET

.SIZED PER 1/H700

WALL

MOUNTED

10x12 SA UP

VD

10x12 RA UP

AHU 1-1

CU

1-1

CU

1-2

20x12

SA UP

20x12 S

A

VD

18x12 S

A

VD

CD-1

[75]

VD

VD

14x12 SA

VD

AHU 1-2

VD

8x12 S

A

VD

VD

1-1/4"

GC UP

1-1/4"

GC UP

20x12

RA UP

CRVSF-6

RH

4

[40]

CRVSF-4

BOTTOM OF RH AT 22'-0" MIN.

MAINTAIN A MIN. 5'-0" CLEARANCE TO

COMBUSTIBLES

(TYP AUTO SHOP)

F

24X24 MAKE-UP AIR TRANSFER

OPENING WITH FIRE DAMPER.

INSTALLED APPROX. 24" BELOW

UNDERSIDE OF STRUCTURE

4Ø CAT 3 VENT

P

3

1/2"

CA

1" GAS [60]

RH-4, RH-5

WMS

PUMP HOUSE

UH

1

T

1098

B

A

8.5

B.8

8.1

M

T

6

2

L

2

O

A

202

TSG STORAGE

ROOM

200

MECHANICAL

AREA

201

SERVER

ROOM

T

TU

2-1

2

H900

WSR-1

[220]

1-1/4" GC

1-1/4"

GC DN

[15]

OUTLINE OF SERVER RACKS. DO

NOT INSTALL EQUIPMENT OR

PIPING ABOVE RACKS

INSULATED

REFRIGERANT LINESET

DN. SIZED PER 1/H700

8Ø SA

CD-1

[100]

6Ø SA

TU

2-2

1-1/4" GC

T

INSULATED

REFRIGERANT LINESET

DN. SIZED PER 1/H700

[15]

O

A

O

A

AHU

1-1

AHU

1-2

10x12

SA DN

1.5 TON

[600]

10x12

RA DN

[50]

VD

O

A

4 TON

[1600]

10

Ø S

A

4Ø OA

20x12

SA DN

VD

10x12 SA

20x12

RA DN

[120]

VD

AHU FLUE (TYP)

1-1/4" GAS [160]

1-1/4"

GC DN

1-1/4"

GC DN

[40]

[120]

HVAC

GROUND

FLOOR PLANS -

ENLARGED

KCB

LEG

KCB

H500

Drawing Number:

Date: 02/19/2021

Drawing Title:

Approved:

Checked:

Drawn:

Drawing Set:

Project Name:

No. Date Revisions

Scale:

Job Number:

80% CDs

Notes:

1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com

MECHANICAL ENGINEER

CHESTNUT ENGINEERING

2 E Lancaster Ave, 2nd Flr.,

Ardmore, PA 19003

610-642-1750

CIVIL ENGINEER/SURVEYOR

NORTH COUNTRY ENGINEERING, INC.

706 Chippewa Square, Suite 102

Marquette, MI 49855

906-226-7683

Seal:

PROJECT MANAGER, LEAD DESIGNER,

STRUCTURAL ENGINEER

UPS MARQUETTE

ARCHITECT

TPD ARCHITECTS, LLC

109 Hewett Road

Wyncote, PA 19095

215-887-2460

H500

2

SCALE: 1/4" = 1' - 0"

HVAC PUMP HOUSE PLAN

H500

1

SCALE: 1/4" = 1' - 0"

HVAC GROUND FLOOR PLAN - ENLARGED PLAN

H500

3

SCALE: 1/4" = 1' - 0"

HVAC MEZZANINE - ENLARGED PLAN

Page 5: H000 - mqtbx.org

ROOF

GRADE

GAS SERVICE.

REFER TO CIVIL

DWGS FOR

CONTINUATION

A

RM

A B

CALCULATION PERFORMED BASED ON

LONGEST LENGTH METHOD.

INLET PRESSURE: LESS THAN 2 PSI

PRESSURE DROP: 0.5 IN W.C.

SPECIFIC GRAVITY: 0.60

PIPE MATERIAL: METALLIC

TABLE 402.4(2) OF THE IFGC

TO = 300 EQUIVALENT FEET

7"-14" W.C.

MEZZ

AHU

1

[40]

AHU

2

[120]

1-1/4" G [160] 4" G [1905]

4" G [1745]

2" G [360]

RH

4

[40]

RH

5

[60]

1" G [100]1-1/2" G [260]

RH

1

[60]

RH

1

[60]

RH

2

[80]

RH

1

[60]

1-1/4" G

[200]

1-1/4" G

[140]

1" G [60]

3" G [1385]

HV

1

[1125]

3" G [1125]

1-1/2" G

[260]

RH

1

[60]

RH

1

[60]

RH

2

[80]

RH

1

[60]

1-1/4" G

[200]

1-1/4" G

[140]

1" G [60]

HVAC

SCHEDULES

KCB

LEG

KCB

H700

Drawing Number:

Date: 02/19/2021

Drawing Title:

Approved:

Checked:

Drawn:

Drawing Set:

Project Name:

No. Date Revisions

Scale:

Job Number:

80% CDs

Notes:

1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com

MECHANICAL ENGINEER

CHESTNUT ENGINEERING

2 E Lancaster Ave, 2nd Flr.,

Ardmore, PA 19003

610-642-1750

CIVIL ENGINEER/SURVEYOR

NORTH COUNTRY ENGINEERING, INC.

706 Chippewa Square, Suite 102

Marquette, MI 49855

906-226-7683

Seal:

PROJECT MANAGER, LEAD DESIGNER,

STRUCTURAL ENGINEER

UPS MARQUETTE

ARCHITECT

TPD ARCHITECTS, LLC

109 Hewett Road

Wyncote, PA 19095

215-887-2460

H700

1

SCALE: NONE

VRF SCHEMATIC

ARMSTRONG AMC-1DBX,

DIGITAL, ADDRESSABLE

CONTROL MONITOR

120 V (BY EC)

EF

1

EF

2

EF

3

EF

4

MOTOR STARTER

BY EC (TYP ALL EFs)

LINE VOLTAGE BY EC

(TYP)

LOW VOLTAGE

CONTROL

WIRING BY MC

(TYP ALL EFs)

RELAY (TYP)

1

CO/NO2

2

CO/NO2

3

CO/NO2

4

CO/NO2

5

CO/NO2

6

CO/NO2

LOW VOLTAGE POWER AND

CONTROL WIRING BY MC

(TYP ALL CO SENSORS)

A DETECTION OF CO LEVEL OF 25 PPM (ADJ) OR A

DETECTION OF NO2 LEVEL OF 2 PPM (ADJ) SHALL

ACTIVATE THE SPECIFIC EXHAUST FAN PER THE

MATRIX. REFER TO SPECIFICATION SECTION

237338 FOR THE LEVEL OF CARBON MONOXIDE

CONCENTRATION, THE SEQUENCE OF OPERATION,

AND FURTHER DETAILS ON THE SYSTEM.

H700

2

SCALE: NONE

CO/NO2 SENSOR / EF SCHEMATIC

RRRR

H700

3

SCALE: NONE

GAS RISER DIAGRAM

7

CO/NO2

NOTES: 1. PROVIDE LOW AMBIENT KIT,M SNOW HOOD, AND FRONT, SIDE, AND REAR WIND BAFFLES FOR ALL CUs

[CU-1]

E

PUZ-

A24NHA7 [CU 2-1]

N/A

TB5

TB4

PLA-

A24EA7

N/A

Gp5

P2

Server Room 1

TU 2-1

E

PUZ-

A24NHA7 [CU 2-2]

N/A

TB5

TB4

PLA-

A24EA7

N/A

Gp9

P2

Server Room 2

TU 2-2

AutoCAD SHX Text
208-230V/60Hz
AutoCAD SHX Text
1~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
G
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
AutoCAD SHX Text
208-230V/60Hz
AutoCAD SHX Text
1~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
G
AutoCAD SHX Text
CR
AutoCAD SHX Text
22~16-2 AWG
Page 6: H000 - mqtbx.org

END VIEW DIMENSIONS ARE FOR HOUSING NOT FAN PANEL

MOTOR IS ACCESSIBLE FROM INTERIOR OF BUILDING

THIS IS AN EXHAUST FAN DUE TO MOTOR ORIENTATION

WALL OPENING 33.25 SQ.

ELEVATION VIEWSIDE VIEW

WALL HOUSING

DAMPER WEATHER HOOD

No UL Listing

Airflow Direction: Exhaust

Damper Mounted, WD-320-PB-26X26, Gravity Operated, Not Coated

Short Wall Hsg, Flush Exterior, w/ OSHA Grd.

Motor Access: From Int. of Bldg.

Weatherhood, Galvanized 45 deg. with Bird Screen

MODEL

OPERATING

POWER (HP)

V/C/P ENCLOSURE

VOLUME

(CFM)

FAN

RPM

MOTOR

RPM

WINDINGS

MOTOR INFORMATION

SIZE (HP)

WEIGHT

(LB.)

MARK

TOTAL EXTERNAL SP

(IN WG)

MARK INFORMATION FAN INFORMATION

GREENHECK AER-E24C-320-VG 0.41 277/60/1 OP3,125 1,208

1300 1

0.75

234

EF-1 through EF-4

0.3

EF-1 through EF-4 : SELECTED OPTIONS AND ACCESSORIES

26

26

3.5

1.5

2.75

32.25

37

32.25

3

29.125

26.875

30.375

DRAWING VIEWED FROM INTERIOR

EXHAUST AIRFLOW

DAMPER

GUARD

WALL HOUSING

INTERIOR EXTERIOR

WEATHERHOOD

32.25

32.25

38.25

38.25

5.00

37.00

30.38

26.88

HVAC

DETAILS

KCB

LEG

KCB

H900

Drawing Number:

Date: 02/19/2021

Drawing Title:

Approved:

Checked:

Drawn:

Drawing Set:

Project Name:

No. Date Revisions

Scale:

Job Number:

80% CDs

Notes:

1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com

MECHANICAL ENGINEER

CHESTNUT ENGINEERING

2 E Lancaster Ave, 2nd Flr.,

Ardmore, PA 19003

610-642-1750

CIVIL ENGINEER/SURVEYOR

NORTH COUNTRY ENGINEERING, INC.

706 Chippewa Square, Suite 102

Marquette, MI 49855

906-226-7683

Seal:

PROJECT MANAGER, LEAD DESIGNER,

STRUCTURAL ENGINEER

UPS MARQUETTE

ARCHITECT

TPD ARCHITECTS, LLC

109 Hewett Road

Wyncote, PA 19095

215-887-2460

H900

2

SCALE: NONE

CASSETTE TERMINAL UNIT DETAIL

RS

RL

TRAP

INSULATE

CONDENSATE

PIPING

CEILING CASSETTE UNIT

CONDENSATE PIPING

DISCHARGE AS INDICATED

ON FLOOR PLAN

CLEANOUT TEE

CHECK VALVE

SHUTOFF VALVE (TYP)

REFRIGERANT SUCTION/LIQUID

LINE SET TO CONDENSING UNIT OF

ROOF

THREADED ROD (TYP OF 4)

STRUCTURE

H900

4

SCALE: NONE

EF-1 THROUGH EF-4 SCHEDULE AND DETAIL

7-1/2 HP

2 STAGE

120 GAL.

ZEKS MODEL 50 NLA

REFRIGERATED AIR

DRYER. 115V-1Ø-60HZ

5.8 FLA.

SLOPE MAIN IN DIRECTION

OF FLOW TO MAIN DRIP

(SIMILAR TO AIR DROP)

1/8" DRAIN LINE TO

FLOOR DRAIN

AIR SUPPLY TO SYSTEM

PRESSURE

REDUCING VALVE

FLEX CONNECTOR

GATE VALVE (TYP.)

UNION (TYP.)

DRAIN VALVE

TO FUNNEL ABOVE

FLOOR DRAIN

COMPRESSOR

MOTOR

PRESSURE GAUGE

SAFETY RELIEF

VALVE SET AT 150

P.S.I.G.

RECEIVER

VIBRATION

ISOLATION PAD

H900

7

SCALE: NONE

COMPRESSED AIR SYSTEM PIPING SCHEMATIC

H900

1

SCALE: NONE

HV GAS MANIFOLD DETAIL

PILOT

REGULATOR

PILOT VALVE SOLENOID

(NORMALLY CLOSED)

BURNER

INTEGRAL VENT LIMITER

VENT LIMITER

VENT LIMITER

LEG TRAP

FURNISHED BY AHU

MANUFACTURER

LOCKABLE MANUAL

SHUT-OFF VALVE

PRIMARY SAFETY

SHUT OFF VALVE AND

ACTUATOR

BLOCK VALVE

AND ACTUATOR

VENT LIMITERMODULATOR VALVE/ GAS

PRESSURE REGULATOR

MODULATOR VALVE/ GAS

PRESSURE REGULATOR

H900

3

SCALE: NONE

RADIANT HEATER VENT DETAIL

VENT CAP

6"

4Ø VENT PIPE

EXTERIOR WALL

RADIANT HEATER

BURNER

PROVIDE INSULATED WALL THIMBLE

H900

5

SCALE: NONE

GAS CONNECTION DETAIL

COMBINATION REGULATOR

& GAS VALVE

PLUG LUBRICATED

GAS COCKGAS FIRED UNIT

UNION

R

DRIP LEG

W/ CAP

GAS MAIN