DRAWING TITLE
DRAWING
NUMBER
H000
DRAWING SCHEDULE
DA
TE
IS
SU
E
HVAC COVER SHEET
MEDIUM PRESSURE STEAM SUPPLY
MEDIUM PRESSURE STEAM RETURN
TRANSFER FAN
WATER SOURCE HEAT PUMP
VARIABLE FREQUENCY DRIVE
TOTAL STATIC PRESSURE
WALL SUPPLY GRILLE
WALL SUPPLY REGISTER
WALL RETURN GRILLE
VARIABLE AIR VOLUME
WALL EXHAUST GRILLE
WALL EXHAUST REGISTER
WALL RETURN REGISTER
WET BULB
VOLUME DAMPER
TOP OF DUCT
TRANSITION
UNIT HEATER
UNLESS NOTED OTHERWISE
VERIFY IN FIELD
TOTAL DEVELOPED HEAD(DYNAMIC)
TESTING, ADJUSTING & BALANCING
TRANSFER AIR GRILLE
WATER PRESSURE DROP
NOT TO SCALE
REFRIGERANT GAS RETURN LINE
PUMPED CONDENSATE DRAIN PIPING
REVOLUTIONS PER MINUTE
EXISTING TO BE RELOCATED
EXISTING TO BE REMOVED
PRE-ENGINEERED METAL BUILDING
PLUMBING CONTRACTOR
POUNDS PER SQUARE INCH
PRESSURE REDUCING VALVE
OUTSIDE AIR INTAKE
OPPOSED BLADE DAMPER
PACKAGED TERMINAL AIR CONDITIONER
RETURN AIR
SQUARE FEET
SANITARY/SLOPE
RELATIVE HUMIDITY
ROOF TOP UNIT
SUPPLY AIR
SPLITTER DAMPER
OUTSIDE AIR
NOT IN CONTRACT
NOT APPLICABLE
MAKE-UP AIR
NORMALLY OPEN
NORMALLY CLOSED
HIGH PRESSURE STEAM SUPPLY
HIGH PRESSURE STEAM RETURN
LINEAR DIFFUSER
HEAT EXCHANGER
1000 BTUH
LINEAR RETURN GRILLE
LINEAR SUPPLY REGISTER
MOTORIZED DAMPER
LINEAR BAR GRILLE
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
LEAVING AIR TEMPERATURE
LEAVING WATER TEMPERATURE
MINIMUM FUSE AMPACITY
MECHANICAL CONTRACTOR
MAXIMUM OVER-CURRENT PROTECTION SIZE
REFRIGERANT LIQUID LINE/LOUVER
LOW PRESSURE STEAM RETURN
LOW PRESSURE STEAM SUPPLY
VAV
FUEL OIL SUPPLYFOS
HEAT PUMP/HORSE POWER
FIN-TUBE CONVECTOR
FLOOR RETURN GRILLE
FLOOR SUPPLY GRILLE
GRAVITY CONDENSATE
FLOOR RETURN REGISTER
FIRE PROTECTION CONTRACTOR
FLOOR SUPPLY REGISTER
HP
FTC
FRR
FRG
FPM
FPC
FSG
FT
GC
FSR
G
FEET PER MINUTE
FOOT/FEET
GAS
VD
WSHP
WER
WSR
WSG
WRR
WRG
VIF
WEG
WB
WPD
VFD
BRITISH THERMAL UNIT
AIR PRESSURE DROP
CUBIC FEET PER HOUR
AIR HANDLING UNIT
BOTTOM OF DUCT
AUTOMATIC AIR VENT
CABINET UNIT HEATER
CONDENSING UNIT
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CEILING RETURN REGISTER
CEILING RETURN GRILLE
CUBIC FEET PER MINUTE
CEILING EXHAUST REGISTER
CEILING EXHAUST GRILLE
ABOVE FINISHED FLOOR
COMPRESSED AIR PIPING
AUTOMATIC TEMPERATURE CONTROLS
CONSTRUCTION MANAGER
DOMESTIC COLD WATER
DRY BULB
A-WEIGHTED DECIBEL
DIRECT EXPANSION
EXISTING TO REMAIN
ELECTRIC BASEBOARD CONVECTOR
ELECTRIC DUCT HEATER
DIRECT DIGITAL CONTROLS
CHILLED WATER RETURN
CHILLED WATER SUPPLY
DUAL TEMPERATURE WATER SUPPLY
DUAL TEMPERATURE WATER RETURN
CONDENSATE DRAIN PIPING
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
EXTERNAL STATIC PRESSURE
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ENTERING WATER TEMPERATURE
FREE AREA/FRESH AIR
FLEXIBLE CONNECTION/FAN COIL
FURNACE/FAHRENHEIT
CONSTANT VOLUME
ET
BTU
BTUH
AS
APD
BOP
CFH
AC
AHU
AFF
AAV
CD
CER
CEG
BOD
ATC
AP
CH
CM
CO
CRG
CONT
CT
CU
CRR
CUH
CWS
CWR
CFM
DCW
DB
DBA
CHWR
CHWS
DN
DX
DDC
DIA
DTS
DTR
EA
EC
EDH
EBBC
EAT
EF
EX
ESP
EWC
EWH
EWT
(E)
FC
FA
FAI
FD
FOR
FLEX
CV
D
E
F
A
B
EXPANSION TANK
DOWN
DIAMETER
EACH
EXISTING
EXHAUST AIR
EXHAUST FAN
FIRE DAMPER
FRESH AIR INLET
FLEXIBLE
FUEL OIL RETURN
BTU PER HOUR
AIR SEPARATOR
BOTTOM OF PIPE
BOILER
CEILING DIFFUSER
ACCESS PANEL
AIR COMPRESSOR
CHILLER
CONTINUED
COOLING TOWER
CLEAN OUT
ABBREVIATIONS
NTS
TF
TYP
U.N.O.
UH
TSP
TOD
TR
TAB
TDH
TAG
OA
PTAC
s=02'
RA
SF
SA
SD
RPM
RTU
S
(RL)
RH
R
(R)
PRV
PD
PSI
OBD
PEMB
PC
P
OAI
TYPICAL
SLOPE
PUMP
MPS
MPR
NIC
NC
NO
N/A
MUA
HPS
HPR
HWS
HWR
L
LAT
HX
LD
LPS
LPR
LRG
LSR
LWT
LBG
MC
MBH
MD
MIN
MCA
MAX
MOCP
MINIMUM
MAXIMUM
HVAC WATER RISER LOCATION
OUTSIDE AIR INTAKE
GRILLE OR REGISTER
UNDERCUT DOOR OR LOUVERED DOOR
OUTSIDE AIR GRILLE OR REGISTER
RETURN, EXHAUST, MAKEUP OR
SUPPLY AIR 4-WAY DIFFUSER,
RETURN, EXHAUST, MAKEUP OR
PIPE DOWN
PIPE DROP
(RL)
(E)
H
S
(R)
T
FIRE DAMPER WITH ACCESS PANEL
EXISTING TO BE REMOVED
CONNECT NEW TO EXISTING
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
FIRE AND SMOKE DAMPER
CUT AND CAP
EXISTING TO REMAIN
HUMIDISTAT
THERMOSTAT
SENSOR
PIPE UP
SMOKE DETECTOR
DIAMETER
EXISTING TO REMAIN
NEW WORK
THERMOMETER
PRESSURE GAGE W/ BALL VALVE
SHEET NUMBER
REDUCED PRESSURE
SYMBOLS
TWO-WAY CONTROL VALVE
BUTTERFLY VALVE
GATE VALVE
CHECK VALVE
BALL-TYPE SHUTOFF VALVE
CALIBRATED BALANCING VALVE
DOUBLE CHECK VALVE
THREE-WAY CONTROL VALVE
STRAINER
VERTICAL VALVE
B
CAP
SECTION NUMBER
SECTION MARKER
VOLUME DAMPER
EQUIPMENT NUMBER
EQUIPMENT TYPE DESIGNATOR
RISER NUMBER
RISER TYPE
FLEX DUCT
S
F
S
F
X
X
X
XX
XX
XX.X
PRESSURE RELIEF VALVE
ERW ENERGY RECOVERY WHEEL
(N) NEW WORK
MOTORIZED
M
DUCT MOUNTED SUPPLY GRILLEDSG
AD DUCT ACCESS DOOR
WIRE MESH SCREENWMS
SOUND TRAP/SILENCERST
UNION
SIDEWALL GRILLE
AIR VENT
VD
BACKFLOW PREVENTION
02/05/2021
HVAC LEGEND
GENERAL REQUIREMENTS
1. EXAMINE JOB SITE AND VERIFY ALL SITE CONDITIONS PRIOR TO STARTING
WORK. BRING ANY DISCREPANCY BETWEEN THE CONTRACT DOCUMENTS AND
THE ACTUAL FIELD CONDITIONS TO THE ATTENTION OF THE ARCHITECT.
2. THE DRAWINGS ARE DIAGRAMMATIC. COORDINATE IN THE FIELD, WITH THE
ARCHITECT AND WITH ALL TRADES, THE EXACT LOCATION OF EQUIPMENT,
FIXTURES, VALVES, THERMOSTATS, ETC. AND ROUTING OF PIPING, DUCTWORK,
CONDUIT, ETC.
3. ARRANGE FOR PIPE SPACES, CHASES, SLOTS, AND OPENINGS IN BUILDING
STRUCTURE DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR
MECHANICAL INSTALLATIONS.
4. COORDINATE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET
SLEEVES IN POURED-IN-PLACE CONCRETE AND OTHER STRUCTURAL
COMPONENTS AS THEY ARE CONSTRUCTED.
5. PERFORM WORK IN ACCORDANCE WITH RULES, REGULATIONS, STANDARDS,
CODES, ORDINANCES, AND LAWS OF LOCAL, STATE, AND FEDERAL
GOVERNMENTS, AND OTHER AUTHORITIES HAVING JURISDICTION AND BE
RESPONSIBLE FOR COMPLIANCE THEREWITH.
6. GUARANTEE ALL SYSTEMS AND WORK FOR A PERIOD OF ONE (1) YEAR FROM
DATE OF FINAL ACCEPTANCE.
7. ALL MATERIALS SHALL BE NEW AND OF COMMERCIAL GRADE AND BEAR THE
UNDERWRITER'S LABEL WHERE APPLICABLE.
8. LOCATE ALL EXISTING UTILITIES AND MAKE SERVICEABLE CONNECTIONS TO
SAME.
9. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, THE MECHANICAL
CONTRACTOR SHALL CHECK AND VERIFY ALL MEASUREMENTS, INCLUDING
LINES, GRADES, PIPE AND DUCT ELEVATIONS AT THE BUILDING AND SHALL BE
RESPONSIBLE FOR THE CORRECTNESS OF SAME.
10. “PROVIDE” SHALL MEAN FURNISH AND INSTALL, MAKE ALL FINAL CONNECTIONS
AND LEAVE IN AN APPROVED OPERATING CONDITION.
11. “MECHANICAL WORK” OR “WORK” SHALL MEAN ALL LABOR, TRANSPORTATION,
MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, INSTALLATION,
SUPERVISION, SERVICES, AND ANY OTHER INCIDENTAL ITEMS OR SERVICES
NECESSARY FOR A COMPLETE AND OPERABLE INSTALLATION.
12. INTENT
a. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS THAT ALL WORK,
EQUIPMENT, APPURTENANCES, CONTROLS AND WIRING BE FURNISHED
AND INSTALLED TESTED, COMPLETED AND READY FOR OPERATION.
b. ANY INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE WORK
COMPLETE AND FUNCTIONAL IN ALL RESPECTS AND READY FOR
OPERATION, EVEN IF NOT EXPLICITLY SPECIFIED OR SHOWN, SHALL BE
PROVIDED WITHOUT ADDITIONAL EXPENSE. MINOR DETAILS NOT USUALLY
SHOWN OR SPECIFIED, BUT MANIFESTLY REQUIRED FOR THE PROPER
INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE
INCLUDED IN THE WORK, THE SAME AS IF SPECIFIED OR SHOWN ON THE
DRAWINGS.
c. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ASSURING THAT THE
PROPOSED SYSTEMS CAN BE INSTALLED AS REQUIRED FROM THE
DRAWINGS AND SPECIFICATIONS. IF ANY DEPARTURES FROM THE
DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY BY THE
CONTRACTOR, DETAILS OF SUCH DEPARTURES AND CLEAR JUSTIFICATION
SHALL BE SUBMITTED TO THE OWNER FOR APPROVAL. NO SUCH
DEPARTURES SHALL BE MADE WITHOUT THE PRIOR WRITTEN APPROVAL OF
THE OWNER.
17. DRAWINGS
a. DRAWINGS ARE DIAGRAMMATIC, SMALL SCALE AND INDICATE THE GENERAL
ARRANGEMENT OF SYSTEMS AND WORK INCLUDED AS IT IS NOT POSSIBLE
TO INDICATE ALL OFFSETS, BENDS, FITTINGS AND ACCESS PANELS
REQUIRED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL
SUCH APPURTENANCES AND DEVICES REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM WHETHER OR NOT THE APPURTENANCE OR DEVICE IS
SHOWN ON THE DRAWINGS. DRAWINGS ARE NOT TO BE SCALED.
W/ ACCESS PANEL
GALLONS PER MINUTEGPM
GD RATED GREASE DUCT
HVAC
COVER SHEET
KCB
LEG
KCB
H000
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
30%
C
Ds
HVAC GROUND FLOOR PLANH100
HVAC DETAILSH900
HVAC SCHEDULESH700
HVAC GROUND FLOOR PLANS - ENLARGEDH500
02/19/2021
80%
C
Ds
HVAC GROUND FLOOR PLANS - ALTERNATEH500A
10987654321
E E
B B
A
D D
C C
7.5 8.3
7.3 8.5
CO/NO2 1
1
R
1
H500
M
4" GAS [1745]
EF
3
EF
4
ENLARGED
GAS SERVICE. REFER
TO CIVIL DWGS FOR
CONTINUATION
REGULATOR
METER
EF
1
EF
2
T
HV-1
3
H500
MEZZANINE
2" GAS [360]
CO/NO2 1
2
CO/NO2 1
3
CO/NO2 1
5
CO/NO2 1
6
CO/NO2 1
7
CO/NO2 1
HV
1
50x26 RETURN AIR GRILLE,
FLUSH WITH EXTERIOR WALL
(RAPID BOTTOM RETURN)
3" GAS [1125]
VERTICAL, MOUNTED ON
CONCRETE PAD
47x25 SUPPLY AIR
(RAPID UP DISCHARGE)
RAPID 3-WAY
DISCHARGE HEAD
SA AND RA DUCTS CONNECTED TO HV
WITH EXTERIOR RATED FLEXIBLE DUCT
CONNECTORS. PROFLEX COMMERCIAL
STAINLESS STEEL (OR EQUIVALENT)
RH
1
CRV-B6
RH
1
CRV-B6
RH
2
CRV-B8
RH
1
CRV-B6
4" CAT 3 VENT
RH
2
CRV-B8
RH
1
CRV-B6
RH
1
CRV-B6
RH
1
CRV-B6
4" CAT 3 VENT
RH
3
TF-250
6" CAT 3 VENT
1-1/4" GAS [160]
P
2
P
1
BOTTOM OF RH AT 18'-0" (TYP)
MAINTAIN A MIN. 5'-0" CLEARANCE TO
COMBUSTIBLES
[60 MBH][60 MBH][80 MBH][60 MBH]
[80 MBH][60 MBH]
[60 MBH]
[1125]
1" GAS [60] 1-1/4" GAS [140] 1-1/4" GAS [200] 1-1/2" GAS [260]
4" GAS [1385]
1" GAS [60] 1-1/4" GAS [140] 1-1/4" GAS [200]
[60 MBH]
1-1/2" GAS [260]
1" GAS [100]
4" GAS [1905]
BOTTOM OF RH AT 18'-0" (TYP)
MAINTAIN A MIN. 5'-0" CLEARANCE TO
COMBUSTIBLES
BOTTOM OF RH AT 18'-0" (TYP)
MAINTAIN A MIN. 5'-0" CLEARANCE TO
COMBUSTIBLES
T RH-3
T RH
T RH
KEYED NEW WORK NOTES
ARMSTRONG MODEL AMC-1222 LOW VOLTAGE
COMBINATION CO & NO2 GAS DETECTOR.
NORMALLY OPEN MOTORIZED DAMPER WITH 24V
ACTUATOR (GREENHECK MODEL VCDR-53 OR
EQUIVALENT)
OVERHEAD LUBE REEL SYSTEM 15' MIN. CLEAR HEIGHT
A.F.F.
SYSTEM CONSISTS OF:
(2) 3/8" COMPRESSED AIR LINE REEL
(1) GREASE REEL
(1) FRESH OIL REEL
INSULATED REFRIGERANT LINESET, SIZED PER 1/H700
FIELD CONSTRUCTED RETURN AIR PLENUM WITH SIDE
AND BOTTOM PULL FILTER RACK. SIZE OF PLENUM TO
MATCH INLET DIMENSION OF VRF TERMINAL UNIT.
24 VOLT HIGH LIMIT TEMPERATURE SWITCH. SWITCH
CLOSES MOTORIZED DAMPER WHEN SUPPLY AIR
TEMPERATURE IS GREATER THAN 72° F.
LINESETS TO BE CONNECTED TO CONDENSING UNIT WITH
A FLEXIBLE CONNECTOR. RECTORSEAL NOKINK (OR
EQUIVALENT).
1
GENERAL NOTES
1. ALL AIR DEVICES SHALL BE BALANCED TO THE CFM VALUE
(SHOWN AS [XXX]) ON THE FLOOR PLANS. SUBMIT
BALANCING REPORT TO ARCHITECT/ENGINEER.
BALANCING WORK SHALL CONFORM TO REQUIREMENTS
OF AABC OR NEBB.
2. ALL NEW EQUIPMENT, PIPING, AND DUCTWORK SHALL BE
INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE
FOR MAXIMUM CEILING HEIGHTS.
3. COORDINATE DIFFUSER AND GRILLES LOCATION WITH
ALL OTHER CEILING COMPONENTS.
4. PROVIDE ALL VOLUME DAMPERS REQUIRED TO BALANCE
THE SYSTEMS. INSTALL VOLUME DAMPERS AT ALL
BRANCH TAKE OFFS FROM TRUNK DUCTS.
5. COMBO CO/NO2 SENSORS SHALL BE MOUNTED 5'-0" A.F.F
6. REFER TO SPECIFICATION SECTION 237338 FOR
CONTROLS AND SEQUENCE OF OPERATIONS FOR
HEATING AND VENTILATION SYSTEM.
7. ALL DUCTWORK SHALL BE INSULATED WITH A MINIMUM
R-8 INSULATION TO MEET ENERGY CODE.
8. MAINTAIN WAREHOUSE AREA AT 45°F.
9. MAINTAIN AUTOSHOP AT 55°F.
2
3
4
5
6
7
HVAC
GROUND
FLOOR PLAN
KCB
LEG
KCB
H100
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
H100
1
SCALE: 1/8" = 1' - 0"
HVAC GROUND FLOOR PLAN
KEYED NEW WORK NOTES
ARMSTRONG MODEL AMC-1222 LOW VOLTAGE
COMBINATION CO & NO2 GAS DETECTOR.
NORMALLY OPEN MOTORIZED DAMPER WITH 24V
ACTUATOR (GREENHECK MODEL VCDR-53 OR
EQUIVALENT)
OVERHEAD LUBE REEL SYSTEM 15' MIN. CLEAR HEIGHT
A.F.F.
SYSTEM CONSISTS OF:
(2) 3/8" COMPRESSED AIR LINE REEL
(1) GREASE REEL
(1) FRESH OIL REEL
INSULATED REFRIGERANT LINESET, SIZED PER 1/H700
FIELD CONSTRUCTED RETURN AIR PLENUM WITH SIDE
AND BOTTOM PULL FILTER RACK. SIZE OF PLENUM TO
MATCH INLET DIMENSION OF VRF TERMINAL UNIT.
24 VOLT HIGH LIMIT TEMPERATURE SWITCH. SWITCH
CLOSES MOTORIZED DAMPER WHEN SUPPLY AIR
TEMPERATURE IS GREATER THAN 72° F.
LINESETS TO BE CONNECTED TO CONDENSING UNIT WITH
A FLEXIBLE CONNECTOR. RECTORSEAL NOKINK (OR
EQUIVALENT).
1
2
3
4
5
6
7
CU
2-1
CU
1
CEG-1
[-225]
EF
5
L
1
PROVIDE MANUFACTURERS 24" STAND
(MITSUBISHI MODEL SS100 OR EQUIVALENT)
ON TOP OF CONCRETE PAD
109
MEN'S ROOM
108
WOMEN'S
ROOM
111
REST ROOM
ENTRANCE
107
CONF./TRAINING
ROOM
106
CENTER
MANAGER'S
OFFICE
105
SUPERVISOR'S
OFFICE
103
OMS
110
CORRIDOR
102
CUSTOMER
COUNTER
104
LOCAL SORT
PRELOAD
OFFICE
CEG-1
[-225]
12
Ø E
A
10
Ø E
A
VD
10Ø EA
CD-1
[300]
CD-1
[300]
CD-1
[150]
CD-1
[200]
CD-1
[155]
CD-1
[155]
CD-1
[220]
CD-1
[200]
CD-1
[100]
CD-1
[100]
CD-1
[75]
CD-1
[75]
CRG-1
CRG-1
CRG-1
CRG-1
CRG-1
CRG-1
CRG-1
PAC
1
AC-1 GRAVITY
CONDENSATE TO SPILL
TO FLOOR DRAIN
18" WINDOW VENT PANEL
INSTALLED IN DIAD
ENCLOSURE SIDEWALL
FLEXIBLE HOSE
T
SITS ON FLOOR
DIAD ENCLOSURE
TU
1-2
[600]
TU
1-1
[880]
TU
1-3
[880]
14x12 SA
T
5
M
14
x1
2 S
A
VD
VD
8x12 SA
VD
VD
T
5
T
10x12 SA
VD VD
5
VD
VD
VD
8x12 SA
VDVD
8x8 SA
VD
[50]
5Ø OA
[65]
[55]
5Ø
O
A
4
8Ø SA UP
VD
T
8Ø
S
A
6
2
12Ø EA
1-1/4" GC
1-1/4" GC DRAIN TO GRADE.
TERMINATE WITH J.R. SMITH 1770 (OR
EQUIVALENT) DOWNSPOUT NOZZLE
1-1/4" GC
1-1/4" GC
1-1/4" GC
1-1/4"
GC UP
6Ø SA UP
6Ø
S
A
VD
4
WALL
MOUNTED
8.5
A
B
C
CU
2-2
INSULATED
REFRIGERANT LINESET
SIZED PER 1/H700
WALL
MOUNTED
4Ø OA UP
L
2
8Ø
O
A
VD
VD
5Ø
O
A
VD
7
7
7
1098
B
A
8.5
B.8
8.1
202
TSG STORAGE
ROOM
200
MECHANICAL
AREA
201
SERVER
ROOM
T
TU
2-1
2
H900
WSR-1
[220]
1-1/4" GC
1-1/4" GC DN TO
1ST FLOOR
[15]
OUTLINE OF SERVER RACKS. DO
NOT INSTALL EQUIPMENT OR
PIPING ABOVE RACKS
INSULATED
REFRIGERANT LINESET
DN. SIZED PER 1/H700
6Ø SA DN
8Ø
S
A
8Ø SA DN
CD-1
[100]
6Ø SA
TU
2-2
1-1/4" GC
T
INSULATED
REFRIGERANT LINESET
DN. SIZED PER 1/H700
[15]
4Ø
O
A
4Ø
O
A4
Ø O
A
4Ø OA DN
HVAC
GROUND
FLOOR PLANS -
ENLARGED -
ALTERNATE
KCB
LEG
KCB
H500A
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
H500A
1
SCALE: 1/4" = 1' - 0"
HVAC GROUND FLOOR PLAN - ENLARGED PLAN - ALTERNATE
H500A
2
SCALE: 1/4" = 1' - 0"
HVAC MEZZANINE - ENLARGED PLAN - ALTERNATE
H500A
3
SCALE: NONE
VRF SCHEMATIC
J1
P1
PEFY-
P24NMAU-E3
001
Gp6
J2
P2
16-2 AWG(S)
PEFY-
P18NMAU-E3
002
Gp8
PEFY-
P24NMAU-E3
003
Gp7
P3 P2P2
DIP SWITCH 6 - 2 ON, SW4 Function 968 ON for High Heating performance mode
[CU-1]
PUHY-
HP96YNU-A
051
TB7
Office
TU 1-1 TU 1-2 TU 1-3
E
PUZ-
A24NHA7 [CU 2-1]
N/A
TB5
TB4
PLA-
A24EA7
N/A
Gp5
P2
Server Room 1
TU 2-1
E
PUZ-
A24NHA7 [CU 2-2]
N/A
TB5
TB4
PLA-
A24EA7
N/A
Gp9
P2
Server Room 2
TU 2-2
AE-200A
PIPING AND CONTROLS
SYMBOL BRANCH PIPE MODEL NAME
J1 CMY-Y102LS-G2
J2 CMY-Y102SS-G2
SYMBOL LIQUID PIPE/GAS PIPE SIZE
P1 3/8 / 7/8
P2 3/8 / 5/8
P3 1/4 / 1/2
SYMBOL MODEL NUMBER
CR PAC-YT53CRAU-J
1. PROVIDE LOW AMBIENT KIT,M SNOW HOOD, AND FRONT, SIDE, AND REAR WIND BAFFLES FOR ALL CUs
NOTES:
KEYED NEW WORK NOTES
ARMSTRONG MODEL AMC-1222 LOW VOLTAGE
COMBINATION CO & NO2 GAS DETECTOR.
NORMALLY OPEN MOTORIZED DAMPER WITH 24V
ACTUATOR (GREENHECK MODEL VCDR-53 OR
EQUIVALENT)
OVERHEAD LUBE REEL SYSTEM 15' MIN. CLEAR HEIGHT
A.F.F.
SYSTEM CONSISTS OF:
(2) 3/8" COMPRESSED AIR LINE REEL
(1) GREASE REEL
(1) FRESH OIL REEL
INSULATED REFRIGERANT LINESET, SIZED PER 1/H700
FIELD CONSTRUCTED RETURN AIR PLENUM WITH SIDE
AND BOTTOM PULL FILTER RACK. SIZE OF PLENUM TO
MATCH INLET DIMENSION OF VRF TERMINAL UNIT.
24 VOLT HIGH LIMIT TEMPERATURE SWITCH. SWITCH
CLOSES MOTORIZED DAMPER WHEN SUPPLY AIR
TEMPERATURE IS GREATER THAN 72° F.
LINESETS TO BE CONNECTED TO CONDENSING UNIT WITH
A FLEXIBLE CONNECTOR. RECTORSEAL NOKINK (OR
EQUIVALENT).
1
GENERAL NOTES
1. ALL AIR DEVICES SHALL BE BALANCED TO THE CFM VALUE
(SHOWN AS [XXX]) ON THE FLOOR PLANS. SUBMIT
BALANCING REPORT TO ARCHITECT/ENGINEER.
BALANCING WORK SHALL CONFORM TO REQUIREMENTS
OF AABC OR NEBB.
2. ALL NEW EQUIPMENT, PIPING, AND DUCTWORK SHALL BE
INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE
FOR MAXIMUM CEILING HEIGHTS.
3. COORDINATE DIFFUSER AND GRILLES LOCATION WITH
ALL OTHER CEILING COMPONENTS.
4. PROVIDE ALL VOLUME DAMPERS REQUIRED TO BALANCE
THE SYSTEMS. INSTALL VOLUME DAMPERS AT ALL
BRANCH TAKE OFFS FROM TRUNK DUCTS.
5. COMBO CO/NO2 SENSORS SHALL BE MOUNTED 5'-0" A.F.F
6. REFER TO SPECIFICATION SECTION 237338 FOR
CONTROLS AND SEQUENCE OF OPERATIONS FOR
HEATING AND VENTILATION SYSTEM.
7. ALL DUCTWORK SHALL BE INSULATED WITH A MINIMUM
R-8 INSULATION TO MEET ENERGY CODE.
8. MAINTAIN WAREHOUSE AREA AT 45°F.
9. MAINTAIN AUTOSHOP AT 55°F.
2
3
4
5
6
7
AC
1
3
1/2" FO
1/2" CG
PIPE LABELING LEGEND
CA = COMPRESSED AIR
FO = FRESH OIL
CG = CHASSIS GREASE
3/4" CA
3/4" CA DROP WITH
QUICK CONNECT FITTING
WASTE
OIL SINK
1/2"
CA
WASTE OIL
TANK
1/2" CA BALL VALVE,
MOUNTED 36" A.F.F.
1" PUMPED
WASTE OIL
1" CA
7.3 8.5
A
B
C
101
AUTO SHOP
100
WAREHOUSE
RAPID ENGINEERING INFINITY PRO
SERIES CONTROL (DDC) AND
EQUIPMENT TOUCH REMOTE PANEL.
ARMSTRONG MODEL AMC-1DBx DIGITAL,
ADDRESSABLE CO/NO2 DETECTION
SYSTEM CONTROL PANEL.
1" GAS [100]
RH
5
[60]
T
ALEMITE 7788-B5
GREASE PUMP
CHASSIS GREASE
BARREL
FRESH OIL TANK
1/2" FO
ALEMITE 7783-C4
FRESH OIL PUMP
3/4" CA
1/2"
CA
1/2" CA TO WASTE OIL SINK
PNEUMATIC PUMP. PROVIDE
PRESSURE REGULATOR AND
GAUGE. ADJUST TO 5 GPM
AD
1
CU
2-1
CEG-1
[-225]
EF
5
L
1
109
MEN'S ROOM
108
WOMEN'S
ROOM
111
REST ROOM
ENTRANCE
107
CONF./TRAINING
ROOM
106
CENTER
MANAGER'S
OFFICE
105
SUPERVISOR'S
OFFICE
103
OMS
110
CORRIDOR
102
CUSTOMER
COUNTER
104
LOCAL SORT
PRELOAD
OFFICE
100
WAREHOUSE
CEG-1
[-225]
12Ø
E
A
10Ø
E
A
VD
10Ø EA
CD-1
[300]
CD-1
[300]
CD-1
[150]
CD-1
[200]
CD-1
[155]
CD-1
[155]
CD-1
[220]
CD-1
[200]
CD-1
[100]
CD-1
[100]
CD-1
[75]
CRG-1
CRG-1
CRG-1
CRG-1
CRG-1
CRG-1
PAC
1
AC-1 GRAVITY
CONDENSATE TO SPILL
TO FLOOR DRAIN
18" WINDOW VENT PANEL
INSTALLED IN DIAD
ENCLOSURE SIDEWALL
FLEXIBLE HOSE
T
SITS ON FLOOR
DIAD ENCLOSURE
T
T
10
x1
2 S
A
VD
8x12 S
A
VD
VD
8x8 SA
VD
12Ø EA
1-1/4" GC DRAIN TO GRADE.
TERMINATE WITH J.R. SMITH 1770 (OR
EQUIVALENT) DOWNSPOUT NOZZLE
1-1/4"
GC UP
WALL
MOUNTED
CU
2-2
INSULATED
REFRIGERANT LINESET
.SIZED PER 1/H700
WALL
MOUNTED
10x12 SA UP
VD
10x12 RA UP
AHU 1-1
CU
1-1
CU
1-2
20x12
SA UP
20x12 S
A
VD
18x12 S
A
VD
CD-1
[75]
VD
VD
14x12 SA
VD
AHU 1-2
VD
8x12 S
A
VD
VD
1-1/4"
GC UP
1-1/4"
GC UP
20x12
RA UP
CRVSF-6
RH
4
[40]
CRVSF-4
BOTTOM OF RH AT 22'-0" MIN.
MAINTAIN A MIN. 5'-0" CLEARANCE TO
COMBUSTIBLES
(TYP AUTO SHOP)
F
24X24 MAKE-UP AIR TRANSFER
OPENING WITH FIRE DAMPER.
INSTALLED APPROX. 24" BELOW
UNDERSIDE OF STRUCTURE
4Ø CAT 3 VENT
P
3
1/2"
CA
1" GAS [60]
RH-4, RH-5
WMS
PUMP HOUSE
UH
1
T
1098
B
A
8.5
B.8
8.1
M
T
6
2
L
2
8Ø
O
A
202
TSG STORAGE
ROOM
200
MECHANICAL
AREA
201
SERVER
ROOM
T
TU
2-1
2
H900
WSR-1
[220]
1-1/4" GC
1-1/4"
GC DN
[15]
OUTLINE OF SERVER RACKS. DO
NOT INSTALL EQUIPMENT OR
PIPING ABOVE RACKS
INSULATED
REFRIGERANT LINESET
DN. SIZED PER 1/H700
8Ø SA
CD-1
[100]
6Ø SA
TU
2-2
1-1/4" GC
T
INSULATED
REFRIGERANT LINESET
DN. SIZED PER 1/H700
[15]
4Ø
O
A
4Ø
O
A
AHU
1-1
AHU
1-2
10x12
SA DN
1.5 TON
[600]
10x12
RA DN
[50]
VD
5Ø
O
A
4 TON
[1600]
10
Ø S
A
4Ø OA
20x12
SA DN
VD
10x12 SA
20x12
RA DN
[120]
VD
AHU FLUE (TYP)
1-1/4" GAS [160]
1-1/4"
GC DN
1-1/4"
GC DN
[40]
[120]
HVAC
GROUND
FLOOR PLANS -
ENLARGED
KCB
LEG
KCB
H500
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
H500
2
SCALE: 1/4" = 1' - 0"
HVAC PUMP HOUSE PLAN
H500
1
SCALE: 1/4" = 1' - 0"
HVAC GROUND FLOOR PLAN - ENLARGED PLAN
H500
3
SCALE: 1/4" = 1' - 0"
HVAC MEZZANINE - ENLARGED PLAN
ROOF
GRADE
GAS SERVICE.
REFER TO CIVIL
DWGS FOR
CONTINUATION
A
RM
A B
CALCULATION PERFORMED BASED ON
LONGEST LENGTH METHOD.
INLET PRESSURE: LESS THAN 2 PSI
PRESSURE DROP: 0.5 IN W.C.
SPECIFIC GRAVITY: 0.60
PIPE MATERIAL: METALLIC
TABLE 402.4(2) OF THE IFGC
TO = 300 EQUIVALENT FEET
7"-14" W.C.
MEZZ
AHU
1
[40]
AHU
2
[120]
1-1/4" G [160] 4" G [1905]
4" G [1745]
2" G [360]
RH
4
[40]
RH
5
[60]
1" G [100]1-1/2" G [260]
RH
1
[60]
RH
1
[60]
RH
2
[80]
RH
1
[60]
1-1/4" G
[200]
1-1/4" G
[140]
1" G [60]
3" G [1385]
HV
1
[1125]
3" G [1125]
1-1/2" G
[260]
RH
1
[60]
RH
1
[60]
RH
2
[80]
RH
1
[60]
1-1/4" G
[200]
1-1/4" G
[140]
1" G [60]
HVAC
SCHEDULES
KCB
LEG
KCB
H700
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
H700
1
SCALE: NONE
VRF SCHEMATIC
ARMSTRONG AMC-1DBX,
DIGITAL, ADDRESSABLE
CONTROL MONITOR
120 V (BY EC)
EF
1
EF
2
EF
3
EF
4
MOTOR STARTER
BY EC (TYP ALL EFs)
LINE VOLTAGE BY EC
(TYP)
LOW VOLTAGE
CONTROL
WIRING BY MC
(TYP ALL EFs)
RELAY (TYP)
1
CO/NO2
2
CO/NO2
3
CO/NO2
4
CO/NO2
5
CO/NO2
6
CO/NO2
LOW VOLTAGE POWER AND
CONTROL WIRING BY MC
(TYP ALL CO SENSORS)
A DETECTION OF CO LEVEL OF 25 PPM (ADJ) OR A
DETECTION OF NO2 LEVEL OF 2 PPM (ADJ) SHALL
ACTIVATE THE SPECIFIC EXHAUST FAN PER THE
MATRIX. REFER TO SPECIFICATION SECTION
237338 FOR THE LEVEL OF CARBON MONOXIDE
CONCENTRATION, THE SEQUENCE OF OPERATION,
AND FURTHER DETAILS ON THE SYSTEM.
H700
2
SCALE: NONE
CO/NO2 SENSOR / EF SCHEMATIC
RRRR
H700
3
SCALE: NONE
GAS RISER DIAGRAM
7
CO/NO2
NOTES: 1. PROVIDE LOW AMBIENT KIT,M SNOW HOOD, AND FRONT, SIDE, AND REAR WIND BAFFLES FOR ALL CUs
[CU-1]
E
PUZ-
A24NHA7 [CU 2-1]
N/A
TB5
TB4
PLA-
A24EA7
N/A
Gp5
P2
Server Room 1
TU 2-1
E
PUZ-
A24NHA7 [CU 2-2]
N/A
TB5
TB4
PLA-
A24EA7
N/A
Gp9
P2
Server Room 2
TU 2-2
END VIEW DIMENSIONS ARE FOR HOUSING NOT FAN PANEL
MOTOR IS ACCESSIBLE FROM INTERIOR OF BUILDING
THIS IS AN EXHAUST FAN DUE TO MOTOR ORIENTATION
WALL OPENING 33.25 SQ.
ELEVATION VIEWSIDE VIEW
WALL HOUSING
DAMPER WEATHER HOOD
No UL Listing
Airflow Direction: Exhaust
Damper Mounted, WD-320-PB-26X26, Gravity Operated, Not Coated
Short Wall Hsg, Flush Exterior, w/ OSHA Grd.
Motor Access: From Int. of Bldg.
Weatherhood, Galvanized 45 deg. with Bird Screen
MODEL
OPERATING
POWER (HP)
V/C/P ENCLOSURE
VOLUME
(CFM)
FAN
RPM
MOTOR
RPM
WINDINGS
MOTOR INFORMATION
SIZE (HP)
WEIGHT
(LB.)
MARK
TOTAL EXTERNAL SP
(IN WG)
MARK INFORMATION FAN INFORMATION
GREENHECK AER-E24C-320-VG 0.41 277/60/1 OP3,125 1,208
1300 1
0.75
234
EF-1 through EF-4
0.3
EF-1 through EF-4 : SELECTED OPTIONS AND ACCESSORIES
26
26
3.5
1.5
2.75
32.25
37
32.25
3
29.125
26.875
30.375
DRAWING VIEWED FROM INTERIOR
EXHAUST AIRFLOW
DAMPER
GUARD
WALL HOUSING
INTERIOR EXTERIOR
WEATHERHOOD
32.25
32.25
38.25
38.25
5.00
37.00
30.38
26.88
HVAC
DETAILS
KCB
LEG
KCB
H900
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
H900
2
SCALE: NONE
CASSETTE TERMINAL UNIT DETAIL
RS
RL
TRAP
INSULATE
CONDENSATE
PIPING
CEILING CASSETTE UNIT
CONDENSATE PIPING
DISCHARGE AS INDICATED
ON FLOOR PLAN
CLEANOUT TEE
CHECK VALVE
SHUTOFF VALVE (TYP)
REFRIGERANT SUCTION/LIQUID
LINE SET TO CONDENSING UNIT OF
ROOF
THREADED ROD (TYP OF 4)
STRUCTURE
H900
4
SCALE: NONE
EF-1 THROUGH EF-4 SCHEDULE AND DETAIL
7-1/2 HP
2 STAGE
120 GAL.
ZEKS MODEL 50 NLA
REFRIGERATED AIR
DRYER. 115V-1Ø-60HZ
5.8 FLA.
SLOPE MAIN IN DIRECTION
OF FLOW TO MAIN DRIP
(SIMILAR TO AIR DROP)
1/8" DRAIN LINE TO
FLOOR DRAIN
AIR SUPPLY TO SYSTEM
PRESSURE
REDUCING VALVE
FLEX CONNECTOR
GATE VALVE (TYP.)
UNION (TYP.)
DRAIN VALVE
TO FUNNEL ABOVE
FLOOR DRAIN
COMPRESSOR
MOTOR
PRESSURE GAUGE
SAFETY RELIEF
VALVE SET AT 150
P.S.I.G.
RECEIVER
VIBRATION
ISOLATION PAD
H900
7
SCALE: NONE
COMPRESSED AIR SYSTEM PIPING SCHEMATIC
H900
1
SCALE: NONE
HV GAS MANIFOLD DETAIL
PILOT
REGULATOR
PILOT VALVE SOLENOID
(NORMALLY CLOSED)
BURNER
INTEGRAL VENT LIMITER
VENT LIMITER
VENT LIMITER
LEG TRAP
FURNISHED BY AHU
MANUFACTURER
LOCKABLE MANUAL
SHUT-OFF VALVE
PRIMARY SAFETY
SHUT OFF VALVE AND
ACTUATOR
BLOCK VALVE
AND ACTUATOR
VENT LIMITERMODULATOR VALVE/ GAS
PRESSURE REGULATOR
MODULATOR VALVE/ GAS
PRESSURE REGULATOR
H900
3
SCALE: NONE
RADIANT HEATER VENT DETAIL
VENT CAP
6"
4Ø VENT PIPE
EXTERIOR WALL
RADIANT HEATER
BURNER
PROVIDE INSULATED WALL THIMBLE
H900
5
SCALE: NONE
GAS CONNECTION DETAIL
COMBINATION REGULATOR
& GAS VALVE
PLUG LUBRICATED
GAS COCKGAS FIRED UNIT
UNION
R
DRIP LEG
W/ CAP
GAS MAIN