GeneralSpecificationsGS 04L53B01-31EN
GX90UT PID Control ModuleGX10/GX20/GP10/GP20 Paperless RecorderData Acquisition System GMLoop Control Function, Program Control Function (/PG Option)
GS 04L53B01-31EN2017.06.26 2nd Edition (YK)
OverviewThe GX90UT is a PID control module that connects to the GX/GP, expandable I/O units, and GM main units and sub units.● TheGX90UTPIDControlModulecanperform
PIDcontrolonuptotwoloops.Itisequippedwithtwocontrolinputs,twocontroloutputs,eightdigitalinputs,andeightdigitaloutputs.Inadditiontosingleloopcontrol,cascadecontrolandloopcontrolwithPVswitchingarepossible.Forthecontroloutput,youcanselectcurrentoutputorvoltagepulseforeachloop.
● InstallingthePIDControlModuleintheGX/GP/GMenablesPIDcontrolofupto20loops/system(upto6loops/systemfortheGX10/GP10/GX20-1/GP20-1/GM10-1). In addition to control loop monitoring and thecontrolgroupscreenforconvenientoperation,adjustmentusingthetuningscreenisavailable.
● Addingthe/PGoptiontotheGX/GP/GMmainunitallows 99 patterns and 99 segments (1 pattern) ofprogrampatternstobestoredinthemainunit.Further,upto32timeeventsand32PVeventscanbesetforeachsegment.
● TheGX90UTcontroldatacanbeacquiredandrecordedintheGX/GP/GMmainunit.
PIDControlModuleSpecifications(Model: GX90UT)
UseControllingtemperature,flowrate,pressure,etc.
AnalogInput• Measurement types: DC voltage (DCV), standard
signal, type (TC), resistance temperature detector (RTD), DI (LEVEL, no-voltage contact), DC current (whenexternalshuntresistorisconnected)
•Numberofmeasurementpoints:2•Scanperiod:Sameasthecontrolperiod•Inputformat:Floatingunbalancedinput,isolation
betweenchannels• Measuring range/accuracy: Seethetablein“MeasuringRange/
Accuracy” (page 3).• Burnout detection: Upscale,downscale,andoffcan
bespecified(foreachchannel). Detectableinputs:Thermocouple,resistance
temperature detector, standard signal Detection condition: Thermocouple:Detectioncurrent:approx.100nA,
superposed electric current system RTD:Detectioncurrent:approx.100nA,superposed
electric current system
Standardsignal:Normal:withinmeasurementrange Disconnection:basedontheburnoutcriteria setting
Thecriteriaissetasapercentageofthespecifiedspanwidth. Lower limit: -20.0 to -5.0% Upper limit: 105 to 120%
•Externalinputresistance: DCvoltage,thermocouple:2kΩorless RTD: 10Ωorlessperline(thesameresistanceforall
threelines)•Inputbiascurrent: ±10nAorless(exceptwhen
burnoutdetectionisset)•Measurementcurrent(RTD):Approx.1mA,approx.
1.6 mA• Input resistance: 10MΩormoreforthermocouple/DCvoltage(1V
range or lower) About1MΩforDCvoltage(2Vrangeorhigher)/
standard signal•Allowablesignalsourceresistance 2kΩorlessforthermocouple/DCvoltage(1Vrange
or less)•Effectofsignalsourceresistance: ±10μV/1kΩorlessforthermocouple/DCvoltage(1
V range or less) ±0.15%/1kΩorlessforDCvoltage(2Vrangeorhigher)/standardsignal
•Effectofwiringresistance: Fluctuationper10Ωchangeperline(the
sameresistanceforallthreelines) RTD(100Ωtypeorhigher):±0.1°C/10Ω RTD(50Ωtypeorlower):±1°C/10Ω•Allowableinputvoltage: Thermocouple,DCvoltage(1Vrangeorlower),
RTD, DI(contact input): ±10 VDC DCvoltage(2Vrangeorhigher),DI(level):±60VDC• Normal-mode rejection ratio: 40 dB or more• Common mode rejection ratio: 120 dB or more
GX90UT
GS 04L53B01-31EN
2
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
• Normal mode voltage: Thermocouple,DCvoltage,DI(voltage):1.2timestherangeratingorless
Standard signal 0.4-2 V range: 2.4 V Standard signal 1-5 V range: 6 V RTD100Ωtypeorhigher:50mVpeak RTD50Ωtypeorlower:10mVpeak• Common mode voltage: 30 VACrms or ±60 VDC Maximumcommonmodenoisevoltage:250VACrms•Commonmodevoltagebetweenchannels: 30 VACrms or ±60 VDC Maximumcommonmodenoisevoltage:250VACrms•Referencejunctioncompensationaccuracy: Whenmeasuringtemperaturegreaterthan
orequalto0°C,usingapowersupplyfrequencynoisereductionfilter,andwhenthetemperatureoftheinputterminalisbalanced
Type K, E, J, T, N, XK GOST: ±0.5°C(23°C±2°C) ±0.7°C(0to50°C) ±1.0°C(-20to60°C)
Type R, S, W, L, U, WRe3-25, PLATINEL II, NiNiMo, W/WRe26, N (AWG14): ±1.0°C(23°C±2°C) ±1.4°C(0to50°C) ±2.0°C(-20to60°C)
Type KpvsAu7Fe: ±1.0K(23°C±2°C) ±1.4K(0to50°C) ±2.0K(-20to60°C)
TypeB,PR20-40:internalRJCfixedat0°C•Calibrationcorrectionfunction: Mode: Linearizerapproximation,linearizerbias
(numberofcorrectionpoints:12),correctionfactor
•First-orderlaginputfilter: on/offswitchable(foreachchannel)
Time constant: 1 to 120 s•Referencejunctioncompensation: internal/externalswitchable(foreach
channel)• Input calculation: off,linear scaling, square root
calculation(foreachchannel)*DCvoltage/standard signal
•Biasfunction: Biastoaddtoinputvaluescanbespecified(foreachchannel).
GS 04L53B01-31EN
3
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
MeasuringRange/Accuracy1
Inputtype Range Measurementrange Measurementaccuracy(digitaldisplay) Digitaldisplayhighestreso-
lutionDC voltage 20 mV -20.000 to 20.000 mV ±(0.05%ofrdg+12μV) 1μV
60 mV -60.00 to 60.00 mV ±(0.05%ofrdg+0.02mV) 10μV200 mV -200.00 to 200.00 mV ±(0.05%ofrdg+0.03mV) 10μV1 V -1.0000 to 1.0000 V ±(0.05%ofrdg+0.2mV) 100μV2 V -2.0000 to 2.0000 V ±(0.05%ofrdg+1.2mV) 100μV6 V -6.000 to 6.000 V ±(0.05%ofrdg+2mV) 1 mV20 V -20.000 to 20.000 V ±(0.05%ofrdg+3mV) 1 mV50 V -50.00 to 50.00 V ±(0.05%ofrdg+0.02V) 10 mV
Standard signal 0.4-2V 0.3200 to 2.0800 V ±(0.05%ofrdg+1.2mV) 100μV1-5V 0.800 to 5.200 V ±(0.05%ofrdg+2mV) 1 mV
Thermocouple(does not include referencejunction compensation accuracy)
R2 0.0 to 1760.0°C ±(0.05%ofrdg+1.0°C)ExceptRandS;0.0to800.0°C:±1.4°CB;400.0to800.0°C:±3.0°CAccuracynotguaranteedfortemperatureslessthan400.0°C
0.1°CS2 0.0 to 1760.0°CB2 0.0 to 1820.0°C
K2 -270.0 to 1370.0°C ±(0.05%ofrdg+0.7°C)Except-200.0to0.0°C:±(0.2%ofrdg+0.7°C)Accuracynotguaranteedfortemperatureslessthan-200.0°C
0.1°C-200.0 to 500.0°C
E2 -270.0 to 800.0°C ±(0.05%ofrdg+0.5°C)Except-200.0to0.0°C:±(0.2%ofrdg++0.5°C)Accuracynotguaranteedfortemperatureslessthan-200.0°C
0.1°CJ2 -200.0 to 1100.0°C
T2 -270.0 to 400.0°C ±(0.05%ofrdg+0.5°C)Except-200.0to0.0°C:±(0.2%ofrdg++0.5°C)Accuracynotguaranteedfortemperatureslessthan-200.0°C
0.1°C
N2 -270.0 to 1300.0°C ±(0.05%ofrdg+0.7°C)Except-200.0to0.0°C:±(0.5%ofrdg+0.7°C)Accuracynotguaranteedfortemperatureslessthan-200.0°C
0.1°C
W3 0.0 to 2315.0°C ±(0.05%ofrdg+1.0°C)1000.0°Cormore:±0.15%ofrdg
0.1°C
L4 -200.0 to 900.0°C ±(0.05%ofrdg+0.5°C)Lessthan0.0°C:±(0.25%ofrdg+0.5°C)
0.1°C
U4 -200.0 to 400.0°C ±(0.05%ofrdg+0.5°C)Lessthan0.0°C:±(0.5%ofrdg+0.5°C)
0.1°C
Thermocouple(does not include referencejunction compensation accuracy)
WRe3-255 0.0 to 2320.0°C ±(0.05%ofrdg+2.0°C)2000.0°Cormore:±0.15%ofrdg
0.1°C
KpvsAu7Fe6 0.0 to 300.0 K ±(0.05%ofrdg+2.0K) 0.1 KPLATINEL II6 0.0 to 1395.0°C ±(0.05%ofrdg+1.0°C) 0.1°CPR20-407 0.0 to 1900.0°C ±(0.05%ofrdg+5.5°C)
Accuracynotguaranteedfortemperatureslessthan800.0°C0.1°C
NiNiMo6 0.0 to 1310.0°C ±(0.05%ofrdg+0.7°C) 0.1°CW/WRe268 0.0 to 2320.0°C ±(0.05%ofrdg+2.0°C)
Accuracynotguaranteedfortemperatureslessthan300.0°C0.1°C
N(AWG14)9 0.0 to 1300.0°C ±(0.05%ofrdg+0.7°C) 0.1°CXK GOST10 -200.0 to 600.0°C ±(0.05%ofrdg+0.5°C)
Lessthan0.0°C:±(0.2%ofrdg+0.5°C)0.1°C
RTD(measurement current 1 mA)
Pt10011 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt10011 -200.0 to 550.0°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu100at0°Cα=0.00425
-50.0 to 150.0°C ±(0.05%ofrdg+0.3°C) 0.1°C
Cu25at0°Cα=0.00425
-200.0 to 300.0°C ±(0.1%ofrdg+0.8°C) 0.1°C
Cu53at0°Cα=0.00426035
-50.0 to 150.0°C ±(0.05%ofrdg+0.6°C) 0.1°C
J263B17 0.0 to 300.0 K ±0.4 KLessthan40.0K:±0.8K
0.1 K
Pt2518 -200.0 to 550.0°C ±(0.1%ofrdg+0.8°C) 0.1°CNi100 (SAMA) -200.0 to 250.0°C ±(0.05%ofrdg+0.3°C) 0.1°CNi100 (DIN)12 -60.0 to 180.0°CNi12013 -70.0 to 200.0°CPt5014 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.05%ofrdg+1.0°C)Cu100 GOST15 -200.0 to 200.0°C ±(0.05%ofrdg+0.3°C) 0.1°CPt46 GOST16 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) 0.1°CPt100 GOST15 -200.0 to 600.0°C ±(0.05%ofrdg+0.3°C) 0.1°C
rdg: reading
GS 04L53B01-31EN
4
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
ContinuedInputtype Range Measurementrange Measurementaccuracy(digitaldisplay) Digitaldisplay
highestreso-lution
RTD(measurement current 1.6mA)
Cu10 GE -200.0 to 300.0°C ±(0.1%ofrdg+2.0°C)Guaranteed accuracy rangeCu10GE:-70.0to170.0°CCu10L&N:-75.0to150.0°CCu10WEED:-200.0to260.0°COtherthanabove:-200.0to300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10at20°Cα=0.00392
-200.0 to 300.0°C
Cu10at20°Cα=0.00393
-200.0 to 300.0°C
Cu10 GOST19 -200.0 to 200.0°C ±(0.1%ofrdg+2.0°C) 0.1°CCu50 GOST16 -200.0 to 200.0°C ±(0.05%ofrdg+0.6°C) 0.1°C
DI Level Thresholdlevel(Vth=2.4V)accuracy±0.1V -Contact20 100Ωorless:1(ON),10kΩormore:0(OFF) -
rdg: reading
1 Understandardoperatingconditions:23±2ºC,55±10%RH,supplyvoltage90–132,180–264VAC,supplyfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.
2 R, S, B, K, E, J, T, N: IEC 60584-1, DIN EN 60584, JIS16023 W:W-5%Re/W-26%Re(HoskinsMfg.Co.)ASTME988-964 L: Fe-CuNi, DIN43710, U: Cu-CuNi, DIN437105 WRe3-25:W-3%Re/W-25%Re(HoskinsMfg.Co.)ASTME988-966 KpvsAu7Fe, PLATINEL II, NiNiMo: ASTM E17517 PR20-40:PtRH20%-PtRh40%(JohnsonMattheyPlc)ASTM
E17518 W/WRe26:W/W-26%Re(HoskinsMfg.Co.)ASTME17519 N(AWG14): NBS10 XK GOST: Type L (GOST R 8.525-2001)11 Pt100: JIS C 1604, IEC 60751, DIN EN 60751
JPt100: JIS C1604, JIS C160612 Ni100 (DIN): DIN 4376013 Ni120: McGRAW EDISON COMPANY14 Pt50: JIS C1604, JIS C160615 Cu100 GOST, Pt100 GOST: GOST 6651-200916 Cu50 GOST, Pt46 GOST: GOST 6651-9417 J263B:YOKOGAWAJ263*B18 Pt25:1/4theJPt100resistance19 Cu10GOST:1/10theCu100GOSTresistance20 Detectedcurrentvalue:approx.10μA
Measuringaccuracywhenscaling: Measuringaccuracywhenscaling(digits)=measuringaccuracy(digits)×scalingspan(digits)/measurementspan(digits)+2digits
*Fractionsroundedup
GS 04L53B01-31EN
5
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
ContinuedInputtype Range Measurementrange Measurementaccuracy(digitaldisplay) Digitaldisplay
highestreso-lution
RTD(measurement current 1.6mA)
Cu10 GE -200.0 to 300.0°C ±(0.1%ofrdg+2.0°C)Guaranteed accuracy rangeCu10GE:-70.0to170.0°CCu10L&N:-75.0to150.0°CCu10WEED:-200.0to260.0°COtherthanabove:-200.0to300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10at20°Cα=0.00392
-200.0 to 300.0°C
Cu10at20°Cα=0.00393
-200.0 to 300.0°C
Cu10 GOST19 -200.0 to 200.0°C ±(0.1%ofrdg+2.0°C) 0.1°CCu50 GOST16 -200.0 to 200.0°C ±(0.05%ofrdg+0.6°C) 0.1°C
DI Level Thresholdlevel(Vth=2.4V)accuracy±0.1V -Contact20 100Ωorless:1(ON),10kΩormore:0(OFF) -
rdg: reading
1 Understandardoperatingconditions:23±2ºC,55±10%RH,supplyvoltage90–132,180–264VAC,supplyfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.
2 R, S, B, K, E, J, T, N: IEC 60584-1, DIN EN 60584, JIS16023 W:W-5%Re/W-26%Re(HoskinsMfg.Co.)ASTME988-964 L: Fe-CuNi, DIN43710, U: Cu-CuNi, DIN437105 WRe3-25:W-3%Re/W-25%Re(HoskinsMfg.Co.)ASTME988-966 KpvsAu7Fe, PLATINEL II, NiNiMo: ASTM E17517 PR20-40:PtRH20%-PtRh40%(JohnsonMattheyPlc)ASTM
E17518 W/WRe26:W/W-26%Re(HoskinsMfg.Co.)ASTME17519 N(AWG14): NBS10 XK GOST: Type L (GOST R 8.525-2001)11 Pt100: JIS C 1604, IEC 60751, DIN EN 60751
JPt100: JIS C1604, JIS C160612 Ni100 (DIN): DIN 4376013 Ni120: McGRAW EDISON COMPANY14 Pt50: JIS C1604, JIS C160615 Cu100 GOST, Pt100 GOST: GOST 6651-200916 Cu50 GOST, Pt46 GOST: GOST 6651-9417 J263B:YOKOGAWAJ263*B18 Pt25:1/4theJPt100resistance19 Cu10GOST:1/10theCu100GOSTresistance20 Detectedcurrentvalue:approx.10μA
Measuringaccuracywhenscaling: Measuringaccuracywhenscaling(digits)=measuringaccuracy(digits)×scalingspan(digits)/measurementspan(digits)+2digits
*Fractionsroundedup
• Between input terminals and output terminals: 1000 V ACfor1minute
•Betweenanaloginputchannels:1000VACfor1minute
•Betweenanalogoutputchannels:20MΩormoreat500 V AC
• Between analog I/O terminals and digital I/O terminals:1000VACfor1minute
Insulationresistance• Between analog input terminals and internal circuit: 20MΩormoreat500VDC
• Between analog output terminals and internal circuit: 20MΩormoreat500VDC
• Between digital input terminals and internal circuit: 20 MΩormoreat500VDC
• Between digital output terminals and internal circuit: 20MΩormoreat500VDC
•Betweeninputterminalsandoutputterminals:20MΩor more at 500 V DC
•Betweenanaloginputchannels:20MΩormoreat500 V DC
•Betweenanalogoutputchannels:20MΩormoreat500 V DC
• Between analog I/O terminals and digital I/O terminals:20MΩormoreat500VDC
StandardsCompliance• CSA:
CAN/CSA-C22.2 No. 61010-1, installation category II,*1 pollution degree 2*2
CAN/CSA-C22.2 No. 61010-2-030CAN/CSA-IEC 61010-2-201*4
• UL:UL 61010-1, UL 61010-2-030 (CSA NRTL/C)UL 61010-2-201(CSA NRTL/C)*4
• CE/EMC directives:EN61326-1compliance,ClassATable2EN 61000-3-2 complianceEN 61000-3-3 complianceEN 55011 Class A Group 1
• CE/Low-voltage directives:EN 61010-1, EN 61010-2-030 complianceinstallationcategoryII,*1pollutiondegree2,*2measurement category II*3
EN 61010-2-201 compliance*4
• Australia, New Zealand EMC standard (RCM):EN55011 compliance, Class A Group 1
•KCmark:Electromagneticwaveinterferencepreventionstandard, electromagnetic wave protection standard compliance
*1 Installationcategory(overvoltagecategory)II:Describesanumberwhichdefinesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.“II”appliestoelectricalequipmentwhichissuppliedfromthefixedinstallationlikeadistributionboard.
*2 Pollutiondegree2:Describesthedegreetowhichasolid,liquid,orgaswhichdeterioratesdielectricstrengthorsurfaceresistivityisadhering.“2”appliestonormalindooratmosphere.Normally,onlynon-conductive pollution occurs.
*3 MeasurementcategoryII(CATII):Availableinthetesting and measuring circuits directly connected toausagelocation(receptacleorthelike)ofalow-voltagemainpowersupplyfacility.Appliances,portableequipment,etc.
Analogoutput•Numberofoutputs:2• Output types: Current, voltage pulse, or DC loop
power supply (15 VDC)Current output: Output signal: 4 to 20 mA or 0 to 20 mA
(reverseoutputpossible) Loadresistance:600Ωorless Output: ±0.1%ofF.S.Except±5%ofF.S.
(F.S.:20mA)for1mAorless Temperatureeffect:±200ppm/°C Humidityeffect:±0.05%ofF.S.@40°C,93%RH Long-termdrift:±0.05%ofF.S.Voltage pulse output: ON voltage: 12 VDC or more (load resistance of600Ωormore) OFF voltage: 0.1 VDC or less Cycle time: 0.5 to 1000.0 s Time resolution: 10msor0.1%ofoutput
value,whicheverislargerDC loop power supply: Supply voltage: 13.0 to 18.3 V Maximumsupplycurrent: about22mA(withshort-circuit
current limiting circuit)• Output calculation: split computation
DigitalInput/OutputDigitalInput•Numberofinputs:8•Statusdetectionminimumholdtime:controlperiod+
50 ms• Input type: no-voltage contact or open collector•Isolationtype:photocouplerisolation• Contact rating: 12 VDC or more, 20 mA or more
UsingacontactwithaminimumONcurrentof1mAorless
•Inputresistance:about2.4kΩ•Allowableinputvoltage:10V• Input detection:
For open collector contact input ON voltage: 0.5 VDC or less Leakagecurrentwhenturnedoff:0.5
mA or less For no-voltage contact input Contactresistancewhenturnedon:
200Ωorless Contactresistancewhenturnedoff:50kΩormore
•Numberofcommons:1•Application:SPswitching,operationmodeswitching,
event inputDigitalOutput•Numberofoutputs:8• Output time resolution: 100 ms min.•Outputtype:opencollector(sinktype)•Isolationtype:photocouplerisolation•Outputcontactcapacity:24VDCmax.,50mA• Application: alarm output, FAIL output, etc.
Withstandvoltage• Between analog input terminals and internal circuit: 1500VACfor1minute
• Between analog output terminals and internal circuit: 1500VACfor1minute
• Between digital input terminals and internal circuit: 1500VACfor1minute
• Between digital output terminals and internal circuit: 1500VACfor1minute
GS 04L53B01-31EN
6
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
*4 Thisproductisdesignedasopenequipmentundertherelevantstandard,installitasfollows:• TheGX10/GX20isdesignedtobeinstalledinan
instrumentationpanel.Installitinalocationwherepeoplecannottouchtheterminalscarelessly.
• TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceotherthanthefront-panelcontrolareawithaninstrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelesslyorinapanel.
• InstalltheGX60/GMunitinapanelwithadoor.• Theinstrumentationpanelorpanelusedfor
supportmustcomplywithCSA/UL/EN61010-2-201ormustbeatleastIP1X(degreesofprotection) and at least IK09.
• Tocomplywiththerelevantstandard,makesurethatthestylenumbersoftheGX/GPmainunit,GM90PS power supply module, and GX60 I/O baseunitareatleast2.
• WEEE Directive Compliant
Construction• Front panel (terminal) area: Dust-proofanddrip-proof,
IEC529-IP20•Material:Polycarbonate• Color: Frontpanel:Lightcharcoalgray(Munsell10B3.6/0.3
equivalent) Case:Smokegray(Munsell4.1PB6.0/4.5equivalent)• Externaldimensions:45.2(W)x111(H)x133.1(D)mm (D:depthincludingtheterminalcover)• Terminal type: M3 screw terminal•Weight:Approx.0.3kg
PowersupplySuppliedfromGX/GP,GX60,GM90PS• Power consumption: 2.8 W or less
Isolation
Functional isolation
Analog input CH1Analog input CH2Analog output CH1Analog output CH2Digital input CH1 to 8Digital output CH1 to 8
Internal circuit
Terminalarrangement:M3screwterminal
No. Symbol No. Symbol No. Symbol301 DI3 201 DI2 101 DI1302 DI6 202 DI5 102 DI4303 DI-COM 203 DI8 103 DI7304 DO3 204 DO2 104 DO1305 DO6 205 DO5 105 DO4306 DO-COM 206 DO8 106 DO7307 AI1( /A) 207 AI1(-/b) 107 AI1(+/B)308 AI2( /A) 208 AI2(-/b) 108 AI2(+/B)309 N.C. 209 AO1(-) 109 AO1(+)310 N.C. 210 AO2(-) 110 AO2(+)
A/DCalibrationValueYoucansavetwotypesofADcalibrationvalues:factorydefaultvaluesanduser-definedvalues.Ifthereisaproblemwithuser-definevalues,theycanberesettofactorydefaultcalibrationvalues.
ExternalDimensions
107.
126
92 100
38
1.9
43.8
45.2
Unit: mm
NormalOperatingConditions•Ambienttemperature:–20to50°C However,useitwithintheambienttemperaturerangedefinedfortheGX/GP/GMmainunit.
Forthenormaloperatingconditionsofthismodule,seethespecificationsoftheinstrument(GX/GP,expandableI/O,GM)thatthismoduleisinstalledin.GXspecifications:GS04L51B01-01ENGPspecifications:GS04L52B01-01ENExpandableI/Ospecifications:GS04L53B00-01ENGMspecifications:GS04L55B01-01EN
TransportandStorageConditions•Ambienttemperature:-25to70°C•Ambienthumidity:5to95%RH(nocondensation)•Vibration:10to60Hz,4.9m/s2 or less•Shock:392m/s2maximum(inpackagedcondition)
EffectsofOperatingConditions• Effectsofambienttemperature: Fluctuationper10°Cchange ±(0.05%ofrdg+0.05%ofrange)orless
However,forKpvsAu7Fe,PR20-40:±(0.05%ofrdg+0.1%ofrange)orless
Cu10Ωorless:±(0.2%ofrange+0.1°C)orless•Effectsofpowerfluctuation: Meetstheaccuracyspecificationsintheratedpower
supply range•Effectsofmagneticfield: FluctuationinresponsetoamagneticfieldofAC(50/60Hz)400A/mis±(0.1%ofrdg+0.1%ofrange)or less.
GS 04L53B01-31EN
7
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
BlockDiagram
SP limit
(Thermocouple)
GX90UT module
Single Loop Control Block Diagram
(DC voltage/standard signal)
(Thermocouple/RTD)
(AI1 used)
(LOCAL)
(Not OUT)
(OUT1 selected)
(REMOTE/PROG/RESET)
(REMOTE) (PROG/RESET)
PV input
Setup item
Module terminal
PID channel
Legend
(Recorder option /PG is required.)
Control output
AO2: PV/SP/OUT/EXPV can be output as analog signals through configuration.
DO1 to DO8: Alarm output and status output are possible through configuration.
GX/GP screenGX/GP Web app
GM Web app
Select with SP group number
During program operation, the SP rate-of-change limiter does not work.
(EXPV1 used)
RJC
ScalingSquare root extraction
Input typeMeasuring range/unitBurnout detection
Input linearizerBiasFilter
Overrange detection
Control PV range/unit
Control overrange detection
Output limiter 1
Control alarm function
AI1
AO2
PV1
OUT1
SP1
EXPV1 selection
Output format setting
Sensor burnout 1
MAN
STOP
Normal
AUTO
RUN
Input error preset output 1
Manual output 1Output limiter 1
Preset output 1
PID1 computation
Retransmission output
Program operation
Ratio biasFilter
SP rate-of-change limiter
Split computation
AO1
AI1 AI2
DO1 to DO8
DI1 to DI8
AO1
DI1 to DI8: Event input is possible through configuration.
DI1 DI8to
DO1 DO8toDO1 DO8to
SP limitRSP1 selection
During program operation, RSP1 is set to the SP of program operation.
Loop 2
(same operation as PID of loop 1)
Scaling
GS 04L53B01-31EN
8
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
SP limit
(Thermocouple)
GX90UT module
Cascade Control Block Diagram
(DC voltage/standard signal)
(Thermocouple/RTD)
(AI1 used)
(LOCAL)
Sensor burnout 1
AUTO/MAN
STOP
Normal
CASCADE
RUN
(CASCADE) (AUTO/MAN)
(Not OUT)(OUT2 selected)
(REM/PROG/RESET)
Primary PV input
Setup item
Module terminal
PID channel
Legend
Secondary PV input
(Recorder option /PG is required.)
Control output
GX/GP screenGX/GP Web app
GM Web app
Select with SP group number
Select with SP group numberDuring program operation, the SP rate-of-change limiter does not work.
(EXPV1 used)
RJC
ScalingSquare root extraction
Input typeMeasuring range/unit
Burnout detection
Input linearizerBiasFilter
Overrange detection
Control PV range/unit
Control overrange detection
Input error preset output 1
Output limiter 1
SP2
Control alarm function
Control alarm function
AI1
(TC)(DC voltage/standard signal)
(Thermocouple/RTD)
AO2AO1
RJC
ScalingSquare root extraction
Input typeMeasuring range/unit
Burnout detection
Input linearizerBiasFilter
Overrange detection AI2
PV1
OUT1
SP1
EXPV1 selection
SP limit
Output format setting
(AI2 used) (EXPV2 used)
EXPV2 selection
Preset output 1
Sensor burnout 2
MAN
STOP
Normal
CASCADE/AUTO
RUN
Input error preset output 2
Manual output 2Output limiter 2
Preset output 2
PID1computation
Control PV range/unit
Control overrange detection PV2
OUT2
SP2 PID2computation
Program operation
SP rate-of-change limiter
Split computation
AO2
(Not OUT)
Output format setting
Retransmission output
Split computation
AO1
AI1 AI2
DO1 to DO8
DI1 to DI8
Output limiter 2
SP limit 1
AO1: PV/SP/OUT/EXPV can be output as analog signals through configuration.DO1 to DO8: Alarm output and status output are possible through configuration.
DI1 to DI8: Event input is possible through configuration.
SP limitRSP1 selection
Ratio biasFilter
(REM) (PROG/RESET)
During program operation, RSP1 is set to the SP of program operation.
DI1 DI8to
DO1 DO8toDO1 DO8to
Retransmission output
Scaling
Scaling
GS 04L53B01-31EN
9
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
SP limit
(Thermocouple)
GX90UT module
Loop Control with PV Switching Block Diagram
(DC voltage/standard signal)
(Thermocouple/RTD)
(AI1 used)
(LOCAL)
(Not OUT)(OUT1 selected)
(REMOTE/PROG/RESET)
PV input 1 PV input 2
Setup item
Module terminal
PID channel
Legend
(Recorder option /PG is required.)
Control output
GX/GP screenGX/GP Web app
GM Web app
Select with SP group number
During program operation, the SP rate-of-change limiter does not work.
(EXPV1 used)
RJC
ScalingSquare root extraction
Input typeMeasuring range/unit
Burnout detection
Input linearizerBiasFilter
Overrange detection
Control PV range/unit
Control overrange detection
Output limiter 1
Control alarm function
AI1
AO2
PV1
OUT1
SP1
EXPV1 selection
Output format setting
(Thermocouple)
(DC voltage/standard signal)
(Thermocouple/RTD)
(AI2 used) (EXPV2 used)
RJC
ScalingSquare root extraction
Input typeMeasuring range/unit
Burnout detection
Input linearizerBiasFilter
Overrange detection AI2
EXPV2 selection
Sensor burnout 1
MAN
STOP
Normal
AUTO
RUN
Input error preset output 1
Manual output 1Output limiter 1
Preset output 1
PID1 computation
PV switching
Program operation
SP rate-of-change limiter
Split computation
AO1
(Not OUT)
Output format setting
Retransmission output
Split computation
AO2
AI1 AI2
DO1 to DO8
DI1 to DI8
AO1
AO2: PV/SP/OUT/EXPV can be output as analog signals through configuration.
DO1 to DO8: Alarm output and status output are possible through configuration.
DI1 to DI8: Event input is possible through configuration.
SP limitRSP1 selection
Ratio biasFilter
(REMOTE)(PROG/RESET)
During program operation, RSP1 is set to the SP of program operation.
DI1 DI8to
DO1 DO8toDO1 DO8to
Retransmission output
Scaling
Scaling
GS 04L53B01-31EN
10
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
Loop Control Function (Function of theGX/GP/GMMainUnit)
ThisfunctioncanbeusedwhenaPIDControlModuleisinstalledinGX/GPmainunit,expandableI/O,GMmainunit,orsubunit.
Control ScreenDisplayupdateinterval(GX/GP):500ms(fixed)OntheGM,aWebapplicationisusedtoperformoperationssimilartothoseperformedontheGX/GPmain unit’s screen.
Control Group ScreenMultipleloopscanbeshownasagroup(controlgroup)on a single screen.Controllerstyle:AscreenthatemphasizesPVvalues
as on a digital indicating controllerDisplay items: Tag No., tag string, operation mode,
operating status, control alarm status, PV value, PV unit string, deviation status, SP value, OUT value, OUT unit string, error display
Faceplatestyle:Ascreenthatshowscontrolvaluesgraphically.
Displayitems:SameitemsshownonthecontrollerstyledisplayaswellasPVscalehighandlowlimits,bargraphofPVvalue,PValarmhighandlowlimitmarks,bargraphofOUTvalue,SPpointer
Faceplate Controller
Control Group Screen
NumberofControlGroupsandNumberofLoopsThatCanBeRegistered
Model NumberofGroups(max.)
NumberofLoops(max.)/ Group
GX10/GP10 5 6GX20-1/GP20-1 (standard type) 5 8GM10-1 (standard type) 5 8GX20-2/GP20-2 (large memory type)
10 8
GM10-2 (large memory type) 10 8
Controllerstyledisplayexample
Faceplatestyledisplayexample
Control Overview ScreenThecontroloverviewscreenshowsonasinglescreenthealarmstatusofallloops.Whenanalarmoccurs,thebackgroundcolorturnsredandthetextcolorwhite.
GS 04L53B01-31EN
11
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
TuningScreenThetuningscreencanbeusedtosetoradjustPIDconstantsandthelikewhileviewingprocessdataduring operation.
ControlSummaryScreenThecontrolsummaryscreenshowsahistoryofcontroloperations (run/stop, auto/manual, etc.). You can select ahistoricalentryandjumptothehistoricaltrendofthatsection.• Displayed contents: name, status, time•Maximumnumberofsummaries:1000(ifthemaximumnumberisexceeded,theoldesteventisdeleted)
ControlAlarmSummaryScreenThecontrolalarmsummaryscreenshowsahistoryofcontrolalarms.Youcanselectahistoricalentryandjumptothehistoricaltrendofthatsection.• Displayed contents: loop, level, type, time•Maximumnumberofsummaries:500(ifthemaximumnumberisexceeded,theoldesteventisdeleted)
MultiPanelScreenYou can assign a control group screen, control overview screen, control alarm summary screen, and control summaryscreentothemultipanelscreen.
Thecontrolgroupscreenandcontroloverviewscreenmaynotbedisplayeddependingonthesizeofthemultipanelareathattheyareassignedto.
FavoriteandStandardScreensControlscreenscanberegisteredtofavoriteandstandard screens.
BackgroundColorThebackgroundcolorofcontrolscreenscanbesettowhiteorblack.(Controllerstyledisplayexample)
GS 04L53B01-31EN
12
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
LoopNumber:
Loop Number; loop 1: 1loop 2: 2
L x x x
Unit number: GX/GP recorder/GM main unit: 0GX60 expandable I/O unit/GM sub unit: 1 to 6
Slot number: GX10/GP10: 0 to 2GX20/GP20 main unit: 0 to 9GM main unit: 0 to 4GX60 expandable I/O unit/GM sub unit: 0 to 5
Tag:Tagstringsandtagnumberscanbeassignedtoloopnumbers.•Tagstring:upto32characters Displayablecharacters:English,Japanese,andChinesecharacters
•TagNo.:upto16characters Displayablecharacters:AlphanumericandsymbolsPIDChannel:PIDchannelsareusedtodisplaycontroldataandI/OdataofPIDcontrolmodulesontrendordigitaldisplaysandsavethedataasrecordeddata.•PIDchannel:
analog input (AI1/AI2), digital input (DI1 to DI8), analog output (AO1/AO2), digital output (DO1 to DO8), control data (PV1/PV2, SP1/SP2, OUT1/OUT2)
•PIDchannelrecordinginterval: dependsontherecorder’s recording interval
PIDChannelDisplaySettings:tag,color,zone,scale,bargraph
Control data; PV1: 01, SP1: 02, OUT1: 03PV2: 04, SP2: 05, OUT2:06
I/O data; AIN1: 07, AIN2: 08, AO1: 09, AO2: 10DI1 to DI8: 11 to 18DO1 to DO8: 19 to 26
x x x x
Unit number: GX/GP recorder/GM main unit: 0GX60 expandable I/O unit/GM sub unit: 1 to 6
Slot number: GX10/GP10: 0 to 2GX20/GP20/GM main unit: 0 to 9GX60 expandable I/O unit/GM sub unit: 0 to 5
NumberofPIDChannels:ThenumberofchannelsoftheGX90UTmoduleis26(fixed).WhenchoosingthetypeofGX/GP/GMmainunit(Standard / Large memory), please calculate it as 26 channelsperoneunit.
ControlFunctionsControl ModeSelectfromsingleloopcontrol,* cascade control, and loopcontrolwithPVswitching
* Twosingleloopscanrunonasingleunit.(Dual-loopcontrolispossible.)
NumberofControlLoops2loops/module(singleloopcontrol×2,cascadecontrol)1loop/module(loopcontrolwithPVswitching) GX/GP/GMsystem(standardtype):6loopsmax. GX/GP/GMsystem(largememorytype):20loopsmax.ControlPeriod(InputSamplingPeriod)100msor200ms(systemglobalsetting)
ControlComputationFunction•Controltype:PIDcontrol,on/offcontrol• Target setpoint (SP): up to 8 per loop• PID parameter: 8 groups/loop• PID parameter group selection:Usingtargetsetpointnumbers(SPNO)(PIDnumberscanbeassignedasyoulike)orsegmentPIDs(duringprogram control)UsingPVinputzones(zonePIDs)*Usingtargetsetpointzones(zonePIDs)*Usingfinaltargetsetpointzones(zonePIDs)*Externally(usingthecontactinput)* Ifthedeviationexceedsthereferencedeviation
setpointduringconstantpresetcontrol,thePIDconstantswitchesautomaticallytothepresetPIDparameter group.
•ZonePIDswitches:7max.•PIDdefaultsettingfunction:ThecontrolledtargetcanbesettoaPIDconstantsuitableforthetemperatureorthatsuitableforthepressureorflowrate.
• PID control mode: fixed-pointcontrolmodeorconstantpresetcontrol•SPlimiterfunction:Ahighlimitorlowlimitcanbeset.•SPrampratesettingfunction:Arisingramprateorfallingrampratecanbeset.
•Trackingfunction:SPtracking,PVtracking
•Auto-tuningfunction•“Super”function(overshoot-suppressingfunction)• Anti-reset windup (over-integration prevention function)
•Presetfunction(whenoperationisstopped)•InputerrorpresetfunctionOperationModeSwitching Remote/local (R/L), auto/manual (A/M), run/stop
(R/S), cascade/auto/manual (CAS/AUTO/MAN), auto tuning (AT) run/stop
GS 04L53B01-31EN
13
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
ControlParameterSettingRange•Proportionalband(P):0.0to999.9%• Integral time (I): 0 to 6,000 s• Derivative time (D): 0 to 6,000 s•ON/OFFcontrolhysteresis:0.0to100.0%ofmeasuringrange(highandlowcanbesetseparately)
• Preset output value: -5.0 to 105.0%• Output limiter setting range: -5.0 to 105.0% (limiterlowlimit<limiterhighlimit)•Normal/reverseoperationswitching:normalor
reverse•Tightshutfunction:Whenmanualcontroliscarriedoutwith4to20mAoutput,controloutputcanbereducedtoabout0mA.
•Rate-of-changelimiterofoutput:Offor0.1to100.0%/s
ExternalPV(EXPV)ExternalPVcanbeturnedonandoff. AnI/O,math,orcommunicationchannelcanbeassigned to PV.EXPVsendperiod:100msto500ms(dependsonthesystemconfiguration.)
RemoteSP(RSP)RemoteSPcanbeturnedonandoff. AnI/O,math,orcommunicationchannelortheanaloginputofaPIDcontrolmodulecanbeassignedtoSP.AfilterandratiobiascanbesetontheremoteSP.Remote SP send period: 100ms to 500ms (depends onthesystemconfiguration.)
RetransmissionOutput(AnalogRetransmission)FunctionOutputfunction:currentoutput(reverseoutputpossible)PV,SP,orOUTcanberetransmittedfromanalogoutput.
MathFunctionCP computation (zirconia O2 sensor electromotive force,CO2partialpressure),specialCLOG.AVEcomputation,magicnumber* Themathfunctionisarecorderoption(/MT).For
details,seethegeneralspecificationsoftheGX/GP/GM recorder.
AlarmFunction• Control alarm typesPVhighlimit,PVlowlimit,SPhighlimit,SPlowlimit,deviationhighlimit,deviationlowlimit,deviationhighandlowlimits,deviationwithinhighandlowlimits,controloutputhighlimit,controloutputlowlimit,PVrate-of-change
• Alarm actionStandbyaction,relayaction(hold/nonhold,resetonACK,normalactiononACK),hysteresis,ON-delaytimer,Off-delaytimer
•Numberofalarmsetpoints:4perloop•StandbyactionTurnsoffalarmsfromthestartofcontrol(power-on)untilastableconditionisreached.
•Hysteresis:Hysteresiscanbesetforeachalarmsetting.
•Display:statusdisplayinthedigitaldisplayareawhenan alarm occurs. Common alarm display can beswitchedbetweenholdandnonhold.
OtherFunctions• Recorder operation Operation Operation security settingsControl Event ActionControlactionorstatusoutputcanbeperformedusingDI,DO,andinternalswitch.• Action
All loop control operation startAll loop control operation stopControloperationstart/stop(specifiedloop)Auto/manualswitch(specifiedloop)Remote/localswitch(specifiedloop)Autoswitch(specifiedloop)Manualswitch(specifiedloop)Cascadeswitch(specifiedloop)Remoteswitch(specifiedloop)Localswitch(specifiedloop)Hold operationAdvance operationProgram operation startProgram operation stopProgramoperationmodechangeHoldoperation(specifiedloop,specifiedprogrampattern)Advanceoperation(specifiedloop,specifiedprogrampattern)Programoperationstart(specifiedloop,specifiedprogrampattern)Programoperationstop(specifiedloop,specifiedprogrampattern)Patternnumberswitch(BIN,BCD)
• Status output•Notificationduringcontroloperation•Segmentnumber(BIN,BCD)•Patternnumber(BIN,BCD)• PROG/RESET monitoring• Wait end signal (1s, 3s, 5s)• Pattern end signal (1s, 3s, 5s)• PV event status• Time event status•Waitflag•Hold-onflag
GS 04L53B01-31EN
14
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
ProgramControlFunction(/PGGX/GP/GMrecorderoption)
Withtheprogramcontrolfunction,aPIDcontrolmoduleinstalledintheGX/GPmainunit,expandableI/O,GMmainunitorsubunitcancontrolasystemaccordingtotimevaryingsetpointssentfromtheGX/GP/GMmainunit.
99 program pattern sets
Program pattern set 1
(Recorder option /PG is required.)
GX/GP screenGX/GP Web app
GM Web app
Program patterns are executed by operating the GX/GP or GM recorder or Web app.
Program pattern set 2
Program pattern set 99
. . . .
•Numberofprogrampatternsets:99•Programpatternname:upto20characters•Numberofsegments:99segments/pattern•Numberofsimultaneousexecution:1patternonly• SP update period: 100to500ms(dependsonthe
systemconfiguration)• PV events:
PValarms,deviationalarms,andthelikeinprogram patterns
Maximumnumberofevents:32persegmentType: PVhighlimit,PVlowlimit,SPhighlimit,SP
lowlimit,deviationhighlimit,deviationlowlimit,deviationhighandlowlimits,deviationwithinhighandlowlimits,controloutputhighlimit,control output low limit
• Time event: Statusoutputispossibleaccordingtothe
progressofprogrampatterns.Maximumnumberofevents:32persegmentTime setting: 0 to (segment time - 1 s)
•Operationmodeswitching: Programrun/reset,hold/releasehold,advance
execute,localoperation•Numberofpatternrepetitions:
999max.orinfinite• Segment time:
0hours0minutes1secondto99hours59minutes 59 seconds
• Program pattern start/stop: Programpatternstart,stop,hold,and
advancecanbecontrolledfromdigitalinput,communication, or recorder’s screen.
• Program pattern selection: canbecontrolledfromdigitalinput,
communication, or recorder’s screen.•Advancefunction: forciblymovestothenextsegment•Waitfunction:
Wait time: off,0hours0minutes1secondto99hours59
minutes 59 secondsWait zone: 0.0to10.0%ofPVrangespan
•Holdfunction:available•PIDparameterswitching: SegmentPIDswitching: PIDparameternumbercanbeswitchedfor
eachsegment.ZonePIDswitching: PIDparameterscanbeswitchedusingPV
valuesandthelike.•Statusoutputthroughdigitaloutput(controlevent
action) Statusmonitoringispossibleusingdigitaloutput.
Program patternnumbermonitoring,programend(patternend)notification,segmentnumbermonitoring,operationmode monitoring (PROG/REST), wait end notification,PV/timeeventnotification,waitingnotification,holdingnotification,localoperation
ProgramSelectionScreenTheprogramselectionscreenisforselectingtheprogram pattern to start operations and viewing pattern settings.
GS 04L53B01-31EN
15
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
• Program screen display: Program operation status display screen:
displaystheprogramoperatingstatusandthecurrent PV simultaneously (GX/GP only)
Numberofdisplayloops:20max. Numberofscreens:1 Display update interval: Digitaldisplayarea:500msfixed
Trenddisplayarea:accordingtothetrend interval
Programeventdisplay:possibleProgramOperationScreenTheprogramoperationscreenisfordisplayingtheprogrampatternthatiscurrentlyrunning.
•Otherrecorderoperations: Saveeachprogrampatterntofile Load program patterns Delete program patterns
ControlDataAcquisition/RecordingFunction(GX/GP/GMrecorderfunction)
• Acquires/records control data (PV, SP, OUT, etc.) Acquisition/recordingispossiblebyinstallingaPIDControlModuleandreconfiguringthesystem.
PIDchanneldatacanbeusedasanI/Ochanneltobesavedindatafilesorusedincomputationandreports.
•Controloperationsummary(numberofsavedfiles:upto3000datavalues,numberofdisplaydatavalues:up 1000 data values)
•Controlalarmsummary(numberofsavedfiles:upto1000,numberofdisplaydataentries:up500)
InstallationConditionsSystematicPIDControlModuleLimitations
GX/GP/GMsystem(Standardtype)
Max.3devices
GX/GP/GMsystem(Largememorytype)
Max.10devices
However,ifthesystemincludesPIDcontrolmodules (GX90UT), digital output modules (GX90YD), and digital input/output modules (GX90WD),themaximumtotalnumberofthesemodules is 10.
Iftherecorder’smeasurementoperationmodeishighspeed or dual interval, PID control modules will not work.(Fordetails,seethegeneralspecificationsoftheGX/GP/GMrecorder.)
Input/OutputModuleLimitationsonRecordersandUnitsWhenUsingthePIDControlModule
GX10/GP10recorder(Standardtype)
Max.3devices*Note:
GX20/GP20recorder(Standardtype)
Max.8devices*
GX20/GP20recorder(Largememorytype)
Max.8devices*
GMsingleunitconfiguration,main(standardtype)
Max.5devices*
GMsingleunitconfiguration,main(largememorytype)
Max.5devices*
GMmultiunitconfiguration,main(standardtype)
Max.5devices*
GMmultiunitconfiguration,main(largememorytype)
Max.5devices*
GX60expandableI/O Installablewithinthesystem limitations
GMmultiunitconfiguration,subunit
Installablewithinthesystem limitations
* Thisisthenumberofdevicesincludingtheexpansionmodules(GX90EX)installedintheGX/GP/GMrecorderwhenanexpandableI/Ounit(GX60)orGMsubunitisused.
Note:Themaximumnumberis2whentheGP10supply voltage is 12 VDC.
GS 04L53B01-31EN
16
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
ModelandSuffixCodesModelandSuffixCodes(GX90UT)
Model Suffixcode DescriptionGX90UT PID Control ModuleNumberofloops
-02 2 loops
Function -11 DI 8 points, DO 8 points- N Always NTerminal type -3 Screw terminal (M3)Region N General
OptionalAccessories(Soldseparately)
Name TypeShuntresisterforcurrentinput(forM3screwterminal)(250Ω±0.1%)
415940
Shuntresisterforcurrentinput(forM3screwterminal)(100Ω±0.1%)
415941
Shuntresisterforcurrentinput(forM3screwterminal)(10Ω±0.1%)
415942
CalibrationCertificate(Soldseparately)WhenyouorderPIDcontrolmodules,eachmodulegetsitsowncalibrationcertificate.
TestCertificate(QIC,soldseparately)WhenyouorderPIDcontrolmodules,eachmodulegets its own QIC.
User’sManualYoucandownloadtheproductuser’smanualsfromthefollowingURL.YouwillneedAdobeReader7orlater(latestversionrecommended)byAdobeSystems.
URL:www.smartdacplus.com/manual/ja/
TrademarksTheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.SMARTDAC+andSMARTDACPLUSaretrademarksofYokogawaElectricCorporation.Microsoft,MS,andWindowsaretrademarksorregisteredtrademarksofMicrosoftCorporationintheUnitedStatesandothercountries.PentiumisaregisteredtrademarkofIntelCorporation.ModbusisaregisteredtrademarkofAEGSchneider.Othercompanynamesandproductnamesappearinginthisdocumentareregisteredtrademarksortrademarksoftheirrespectiveholders.Thecompanyandproductnamesusedinthismanualarenotaccompaniedbytheregisteredtrademarkortrademarksymbols(®and™).