Guide for the Application of Alternating
Current High-voltage (Rated above 72.5
kV) Short-circuit-current-restricting
Circuit BreakersElectric Power Research Institute of
Zhejiang Electric Power Co., Ltd.
Recommended PES TC: 15. Switchgear
17 June 2021
Background
Requirement Analysis
Existing Standard Investigation
Scope
Working Group
Framework
AGENDA
Background
Problems
power grid
development
large-scale
interconnection
increasing short-
circuit current
exceeding
breaking capacity
of circuit breakers
The conventional circuit breakers will not be able to break the fault
current, which seriously threatens the safe and stable operation of the
power system.
Background
Technical Solutions
A kind of special circuit breaker thatcan open rapidly to disconnect thepower grids after a power systemfailure occurs and before conventionalcircuit breakers intervene.
▸Much faster breaking speed
▸Reduce short-circuit current by more than 40%
▸Return normal system topology after the failure is removed
▸negligible impact on normal operations
AC High-voltage Short-
circuit-current-restricting
Circuit Breakers
Requirement Analysis
Technical requirement
Technical schemes for solving the problem of excessive short-circuit current
Line outage
Busbar
separated
operation
Current-
limiting reactor
Short-circuit-
current-
restricting
circuit breaker
Change the power system topology,
reduce its transmission capacity and
decrease its power supply reliability
Increase
system loss
Technically
preferable
Requirement Analysis Market requirement▸Increasing electricity consumption
causes a growing problem of
excessive short-circuit current . An
effective solution is urgently needed
by the market.
Short -c i rcui t
grounding test
verification on
the 2 2 0 k V
short-circuit -
c u r r e n t -
r e s t r i c t i n g
circuit breaker
in Zhej iang ,
China
▸Technologies of AC high-voltage
short-circuit-current-restricting
circuit breakers have become
mature and been applied in some
engineering projects.
Electricity consumption of China
Great application prospects and market demand can be anticipated.
Requirement Analysis
Standardization
▸Power grid enterprises, equipment manufacturers, equipment operation andmaintenance companies, technology R&D institutes who are interested inshort-circuit-current-restricting equipment and technology will benefit fromthis guide.
▸Structural design, technical parameters, test requirements, selectionguidelines of AC high-voltage short-circuit-current-restricting circuitbreakers will be standardized.
▸Conflicting product requirements, poor interchangeability, and unclearapplication methods in the promotion process will be avoided.
Existing Standard Investigation
Title Scope Explain
IEEE C37.04-2018 - IEEE
Standard for Ratings and
Requirements for AC High-Voltage
Circuit Breakers with Rated
Maximum Voltage Above 1000 V
Applies to ac high-voltage circuit
breakers with rated nominal voltage
above 1000 V, including rating structure,
preferred ratings, construction and
functional component requirements.
Does not cover AC
high-voltage short-
circuit-current-
restricting circuit
breakers.
IEEE C37.09-2018 IEEE Standard
Test Procedures for AC High-
Voltage Circuit Breakers with
Rated Maximum Voltage Above
1000 V
Applies to conventional AC high-voltage
circuit breakers with rated maximum
voltage above 1000 V. Defines various
tests that are made on ac high-voltage
circuit breakers.
Special tests for AC
high-voltage short-
circuit-current-
restricting circuit
breakers are not
included.
IEEE C37.012-2014 - IEEE Guide
for the Application of Capacitance
Current Switching for AC High-
Voltage Circuit Breakers Above
1000 V
For a special-purpose circuit breaker.
Addresses the general theory of
capacitance current switching; and the
notions of restrike, re-ignition, non-
sustained disruptive discharge.
Does not cover AC
high-voltage short-
circuit-current-
restricting circuit
breakers
IEEE Standards
Existing Standard Investigation IEC Standards
Title Scope Explain
IEC 62271-1-2017 High-voltage
switchgear and controlgear -
Part 1: Common specifications
for alternating current
switchgear and controlgear
General guideline of the IEC 62271 series
standards. Applies to AC switchgear and
controlgear designed for indoor and/or
outdoor installation and for operation at
service frequencies up to and including 60
Hz and having rated voltages above 1 000 V.
Does not involve
AC high-voltage
short-circuit-
current-restricting
circuit breakers.
IEC 62271-100 High-voltage
switchgear and controlgear -
Part 100: Alternating current
circuit-breakers
A part of IEC 62271 series. Applicable to
AC circuit-breakers designed for indoor or
outdoor installation and for operation at
frequencies of 50 Hz and 60 Hz on systems
having voltages above 1 000 V.
Does not involve
AC high-voltage
short-circuit-
current-restricting
circuit breakers.
IEEE/IEC 62271-37-013-2015
IEEE/IEC International
Standard for High-voltage
switchgear and controlgear --
Part 37-013: Alternating-current
generator circuit-breakers
For a special-purpose circuit breaker.
Specifies the technical requirements for high
voltage AC circuit breakers used in
generator terminals.
Does not involve
AC high-voltage
short-circuit-
current-restricting
circuit breakers.
Scope
Working Group
• This standard specifies the conditions of use, rated values, design and
structure, type tests, factory tests, selection guidelines, installation and
operation rules for AC high-voltage short-circuit-current-restricting
circuit breakers.
• This standard is applicable to the AC high-voltage short-circuit-current-
restricting circuit breakers which are designed for indoor or outdoor use
in AC power systems with voltage level above 72.5 kV.
1. State Grid Zhejiang Electric Power Co., Ltd. Research Institute
2. China Electric Power Research Institute
3. Pinggao Group Co., Ltd.
4. China XD Group Co., Ltd.
5. Shenyang University of Technology
6. Shanghai JiaoTong University
7. Zhejiang Energy Research Institute Co. Ltd.
... More companies will be invited to participate in the working group.
Framework
Guide for the Application of AC High-voltage (Rated above 72.5 kV)
Short-circuit-current-restricting Circuit Breakers
Conditions of use
Rated values
Design and structure
Type tests
Factory tests
Selection guidelines
Installation and operation rules
Tests